480V Switchgear & MCC deficiencies found during inspections
• Loose PT connections• Loose CT connection• Dirty • Panels and covers not affixed properly (bolts without nuts held in with tape• Ground ball covers missing• Stainless wire for tag securement and other foreign material left in sections (hard hats, gloves tools, metal bars, etc.)• Deformed/damaged structure • Modified structure• Missing components• Non Manufacturer hard ware• Damaged cables• Damaged breaker and breaker cubicle components• Conduit entry into arc flash doors• Wiring ferruls too small for the wire and strands that did not fit were “trimmed” off.• Bus boots and covers not secured or covering bus bolts or splices• Equipment numbers missing or on wrong devices• Ferrous Gland Plate on MCC incoming sections.• Incorrect cables on all Battery systems, flexible cable is required by spec• LCS tags need to follow specific EMETL methods and include equipment tag number (not LCS P&ID number), Description,
and Source (MCC and cubicle), if more than one substation in facility then building number shall be included as well. S7C-0702-06, 07, &08
• SEOLDs not created• MCC cubicles not identified with cubicle numbers. • Missing communication cable between SEL relays on MTM
![Page 2: 480V Switchgear & MCC deficiencies found during inspections](https://reader033.fdocuments.in/reader033/viewer/2022051710/58ec81721a28abd1188b4717/html5/thumbnails/2.jpg)
Loose 480V SWR PT Connections
![Page 3: 480V Switchgear & MCC deficiencies found during inspections](https://reader033.fdocuments.in/reader033/viewer/2022051710/58ec81721a28abd1188b4717/html5/thumbnails/3.jpg)
Loose 480V SWR PT & CT Connections
![Page 4: 480V Switchgear & MCC deficiencies found during inspections](https://reader033.fdocuments.in/reader033/viewer/2022051710/58ec81721a28abd1188b4717/html5/thumbnails/4.jpg)
Bolts without nuts on panels & covers
![Page 5: 480V Switchgear & MCC deficiencies found during inspections](https://reader033.fdocuments.in/reader033/viewer/2022051710/58ec81721a28abd1188b4717/html5/thumbnails/5.jpg)
Before cleaning
![Page 6: 480V Switchgear & MCC deficiencies found during inspections](https://reader033.fdocuments.in/reader033/viewer/2022051710/58ec81721a28abd1188b4717/html5/thumbnails/6.jpg)
Cleanliness/PT/CT connections & Ground ball covers
![Page 7: 480V Switchgear & MCC deficiencies found during inspections](https://reader033.fdocuments.in/reader033/viewer/2022051710/58ec81721a28abd1188b4717/html5/thumbnails/7.jpg)
Deformed/damaged structural members
![Page 8: 480V Switchgear & MCC deficiencies found during inspections](https://reader033.fdocuments.in/reader033/viewer/2022051710/58ec81721a28abd1188b4717/html5/thumbnails/8.jpg)
Structural Modifications (this bracket was moved form its original position)
![Page 9: 480V Switchgear & MCC deficiencies found during inspections](https://reader033.fdocuments.in/reader033/viewer/2022051710/58ec81721a28abd1188b4717/html5/thumbnails/9.jpg)
Missing Components (a barrier between sections is missing in this photo)
![Page 10: 480V Switchgear & MCC deficiencies found during inspections](https://reader033.fdocuments.in/reader033/viewer/2022051710/58ec81721a28abd1188b4717/html5/thumbnails/10.jpg)
Non manufacturer hardware
![Page 11: 480V Switchgear & MCC deficiencies found during inspections](https://reader033.fdocuments.in/reader033/viewer/2022051710/58ec81721a28abd1188b4717/html5/thumbnails/11.jpg)
Inspect power cables for damage and tightness
![Page 12: 480V Switchgear & MCC deficiencies found during inspections](https://reader033.fdocuments.in/reader033/viewer/2022051710/58ec81721a28abd1188b4717/html5/thumbnails/12.jpg)
Damaged hardware in breaker cubicles (this shutter mechanism is bent in a “U”
![Page 13: 480V Switchgear & MCC deficiencies found during inspections](https://reader033.fdocuments.in/reader033/viewer/2022051710/58ec81721a28abd1188b4717/html5/thumbnails/13.jpg)
Damage to Structure
![Page 14: 480V Switchgear & MCC deficiencies found during inspections](https://reader033.fdocuments.in/reader033/viewer/2022051710/58ec81721a28abd1188b4717/html5/thumbnails/14.jpg)
Conduit in arc flash blast openings
![Page 15: 480V Switchgear & MCC deficiencies found during inspections](https://reader033.fdocuments.in/reader033/viewer/2022051710/58ec81721a28abd1188b4717/html5/thumbnails/15.jpg)
Conduit hole repair
![Page 16: 480V Switchgear & MCC deficiencies found during inspections](https://reader033.fdocuments.in/reader033/viewer/2022051710/58ec81721a28abd1188b4717/html5/thumbnails/16.jpg)
Lug feral to small for wire (you can see where wire strands were given a “haircut”
![Page 17: 480V Switchgear & MCC deficiencies found during inspections](https://reader033.fdocuments.in/reader033/viewer/2022051710/58ec81721a28abd1188b4717/html5/thumbnails/17.jpg)
Foreign objects found in gear (here is wire that held on information tags left on a ground ball that will be energized). Hard hats, gloves, metal rods, info
tags, tools etc. were found in the gear during our inspections.
![Page 18: 480V Switchgear & MCC deficiencies found during inspections](https://reader033.fdocuments.in/reader033/viewer/2022051710/58ec81721a28abd1188b4717/html5/thumbnails/18.jpg)
Info tag left in gear
![Page 19: 480V Switchgear & MCC deficiencies found during inspections](https://reader033.fdocuments.in/reader033/viewer/2022051710/58ec81721a28abd1188b4717/html5/thumbnails/19.jpg)
Another example of CT layout also be sure that the bus boots & covers are all in place and secured.
![Page 20: 480V Switchgear & MCC deficiencies found during inspections](https://reader033.fdocuments.in/reader033/viewer/2022051710/58ec81721a28abd1188b4717/html5/thumbnails/20.jpg)
Equipment tagging – not there or wrong (below the Bus PTs are labeled Line PT and the Line PT is labeled Bus PT)
![Page 21: 480V Switchgear & MCC deficiencies found during inspections](https://reader033.fdocuments.in/reader033/viewer/2022051710/58ec81721a28abd1188b4717/html5/thumbnails/21.jpg)
Gland plates made from ferrous material
![Page 22: 480V Switchgear & MCC deficiencies found during inspections](https://reader033.fdocuments.in/reader033/viewer/2022051710/58ec81721a28abd1188b4717/html5/thumbnails/22.jpg)
Incorrect battery cable, flexible cable required to eliminate stress on connections