47742961 Electrical Details

download 47742961 Electrical Details

of 8

Transcript of 47742961 Electrical Details

  • 7/30/2019 47742961 Electrical Details

    1/8

    Size in

    s mm

    Single

    Phase

    Three

    Phase

    Size in

    s mm

    Single

    Phase

    Three

    Phase1.5 20 18

    2.5 29 24 2.5 21 19

    4 37 31 4 27 25

    6 48 41 6 35 32

    10 66 56 10 48 43

    16 86 73 16 65 58

    25 115 97 25 84 74

    35 142 119 35 105 90

    50 168 147 50 125 115

    70 209 180 70 150 135

    90 257 219 95 185 165

    120 295 257 120 210 190

    150 337 295 150 240 215

    185 390 333 185 280 250

    240 461 399 240 325 295

    300 523 451 300 380 340

    400 589 523 400 460 415

    CURRENT CARRYING

    CAPACITY FOR COPPER

    CABLES

    CURRENT CARRYING

    CAPACITY FOR ALUMINUM

    CABLES

  • 7/30/2019 47742961 Electrical Details

    2/8

    12x2 23.5 0.209 12x2 110 20015x2 29.5 0.262 15x2 140 200

    15x3 44.5 0.396 15x3 170 300

    20x2 39.5 0.351 20x2 185 315

    20x3 59.5 0.529 20x3 220 380

    20x5 99.1 0.882 20x5 295 500

    25x3 74.5 0.663 25x3 270 460

    25x5 124 1.11 25x5 350 600

    30x3 89.5 0.796 30x3 315 540

    30x5 149 1.33 30x5 400 700

    40x3 119 1.06 40x3 420 710

    40x5 199 1.77 40x5 520 900

    40x10 399 3.55 40x10 700 1350

    50x5 249 2.22 50x5 630 1100

    50x10 499 4.44 50x10 920 1600

    60x5 299 2.66 60x5 760 1250

    60x10 599 5.33 60x10 1060 1900

    80x5 399 3.55 80x5 970 1700

    80x10 799 7.11 80x10 1380 2300

    100x5 499 4.44 100x5 1200 2050

    100x10 999 8.89 100x10 1700 2800

    120x10 1200 10.7 120x10 2000 3100

    160x10 1600 14.2 160x10 2500 3900

    220x10 2000 17.8 220x10 3000 4750

    12x2 23.5 0.0633 12x2 80 140

    15x2 29.5 0.0795 15x2 95 170

    15x3 44.5 0.12 15x3 115 210

    20x2 39.5 0.107 20x2 120 220

    20x3 59.5 0.161 20x3 145 270

    20x5 99.1 0.268 20x5 195 350

    25x3 74.5 0.201 25x3 180 330

    25x5 124 0.335 25x5 230 430

    30x3 89.5 0.242 30x3 205 385

    30x5 149 0.403 30x5 270 500

    40x3 119 0.323 40x3 280 500

    40x5 199 0.588 40x5 350 650

    40x10 399 1.08 40x10 515 975

    50x5 249 0.673 50x5 425 780

    50x10 499 1.35 50x10 625 1150

    60x5 299 0.808 60x5 500 900

    60x10 599 1.62 60x10 730 1330

    80x5 399 1.08 80x5 680 1170

    80x10 799 2.16 80x10 940 1700

    100x5 499 1.35 100x5 820 440

    100x10 999 2.7 100x10 1150 2050

    100x15 1500 4.04 100x15 1450 2500

    120x10 1200 3.24 120x10 1350 2400

    120x15 1800 4.86 120x15 1650 2900

    160x10 1600 4.32 160x10 1750 3000

    160x15 2400 6.47 160x15 2100 3600

    200x10 2000 5.4 200x10 2150 3650

    200x15 3000 8.09 200x15 2550 4200

    Thicknes

    s in mmKg./sq.M

    5 39.2

    10 3.15 24.7 10 7 55

    12 2.5 19.61 12 10 78.5

    14 2 15.69 14 12 94.2

    16 1.66 12.55 16 14 109.9

    18 1.25 9.8 18 16 125.6

    20 1 7.84 20 18 141.3

    22 0.8 6.27 22 20 157

    24 0.63 4.94 24 22 172.7

    26 0.5 3.91 26 25 196.2

    width in

    mm.3 5 6 8 10

    12 0.28 0.5 0.6 0.8 0.9

    25 0.6 1 1.2 1.6 2

    32 0.8 1.3 1.5 2 2.5

    40 0.9 1.6 1.9 2.5 3.1

    50 1.2 2 2.4 3.1 3.9

    Beam

    150x80 14.9

    175x90 19.3

    200x100 25.4

    Wt.in

    K ./Mtr

    ISMC 75 75x40x4.4 6.8

    ISMC 100100x50x4.

    79.2

    ISMC 125 125x65x5

    ISMC 150 12.7

    150x75x5.

    416.5

    Size in

    mm

    Cross

    Sectional

    Area in

    MM2

    Weight

    (Approx)

    kg / Metre

    Weight of Steel Sheets Weight of Steel Plates

    SWGThicknes

    s in mmKg./sq.M SWG

    Copper Bus Bars : Current

    Carrying Capacity

    Size in

    mm1 Bus 2 Bus

    Copper Bus Bars :

    Constructional Details

    Aluminum Bus Bars :

    Constructional Details

    Aluminium, Bus Bars : Current

    Carrying Capacity

    2 BusSize in

    mm

    Cross

    Sectional

    Area in

    MM2

    Weight

    (Approx)

    kg / Metre

    6).Equal Angle

    5).Channels

    Size in

    mm1 Bus

    Wt.in Kg.

    /

    Size in

    mm

    M.S.Flat weight in kg./M.

    Thickness in mm

  • 7/30/2019 47742961 Electrical Details

    3/8

    (in

    mmxmm

    xmm

    (in

    mmxmm

    xmm25x25x3 -1.1 50x50x3 -2.3

    25x25x4 -1.4 50x50x4 -3

    25x25x5 -1.8 50x50x5 -3.8

    40x40x3 -1.8 50x50x6 -4.5

    40x40x4 -2.4 75x75x5 -5.7

    40x40x5 -3 75x75x6 -6.840x40x6 -3.5 75x75x8 -8.9

    J for

    joule

    KWH for

    kilowatt

    hour

    KFM

    kilogram

    force

    metre

    KEAL

    kilocalori

    e

    HPH

    horsepo

    wer hour

    FT (foot

    pound

    force)

    BTU(briti

    sh

    thermal

    unit

    J 10.2778x10

    6 0.1011970.23885x1

    04

    0.37767x1

    06 0.73756

    0.94782x1

    04

    kWh 36x106 1

    0.3671x106 859.85 1.3596

    2.6552x106

    3.4142x104

    kfm 1 2.7241x106 1 2.3423x106 3.7037x106 7.233 9.2949x104

    keal 9.8066 1.163x106 426.94 1

    1.5312x103

    3.0880x104 3.9683

    hph4.1868x10

    3 0.7355 0.27x106 632.42 1

    1.9529x106

    2.5096x103

    f t-ibf 1.35580.37662x1

    06 0.13826

    0.32383x1

    03

    0.51206x1

    06 1

    1.2851x104

    Btu 1.055x103

    0.29307x1

    06 107.59 0.252

    0.39847x1

    03 778.17 1

    WNewton

    kgfm/skeal/s keal/h

    hp.metric

    horsepo

    wer

    hp.

    horsepo

    wer

    ft x lbf/s Btu/h

    W 1 1.101970.23885x1

    03 0.85985

    1.3596x103

    1.3410x103 0.73756 3.4121

    kgfm/s 9.8066 1 2.34x104 8.4322

    13.333x103

    13.151x103 7.233 33.462

    keal/s4.1868 x

    104 426.94 1 3.6x104 5.6925 5.6146

    3.0880x104

    14.286x103

    keal/h 1.163 0.118590.27778x1

    04 1

    1.5812x104

    1.5596x103 0.85779 3.9683

    hp,metric 735.5 75 0.17567 632.42 1 0.98632 542.482.5096x10

    4

    hp, 745.7 76.04 0.17811 644.19 1.0139 1 5502.5444x10

    4

    f t x lbf/s 13558 0.13826

    0.32383x1

    04 1.1658

    1.8434x10

    4

    1.8182x10

    4 1 4.6262

    Btu h 0.2930729.885x10

    4

    69.999x106 0.2522

    0.39847x1

    04

    0.39302x1

    03 0.21616 1

    POWER

    QUANTITIES AND UNITS CONVERSION TABLES

    ENERGY

  • 7/30/2019 47742961 Electrical Details

    4/8

    1).Sheets

    SWG Thickness in mm K ./s .M

    10 3.15 24.7

    12 2.5 19.61

    14 2 15.69

    16 1.66 12.55

    18 1.25 9.820 1 7.84

    22 0.8 6.27

    24 0.63 4.94

    26 0.5 3.91

    2).Plates

    Thickness in mm Kg./sq.M

    5 39.2

    7 55

    10 78.5

    12 94.2

    14 109.9

    16 125.6

    18 141.3

    20 157

    22 172.7

    25 196.2

    3)M.S.Flat weight in kg./M.

    width in mm. Thickness in mm

    3 5 6 8 10

    12 0.28 0.5 0.6 0.8 0.9

    25 0.6 1 1.2 1.6 2

    32 0.8 1.3 1.5 2 2.5

    40 0.9 1.6 1.9 2.5 3.1

    50 1.2 2 2.4 3.1 3.9

    4).Beam

    150x80 14.9175x90 19.3

    200x100 25.4

    5).Channels

    Wt.in Kg./Mtr

    ISMC 75 75x40x4.4 6.8

    ISMC 100 100x50x4.7 9.2

    ISMC 125 125x65x5

    ISMC 150 12.7

    150x75x5.4 16.5

    (in mmxmmxmm) (in mmxmmxmm)

    25x25x3 -1.1 50x50x3 -2.325x25x4 -1.4 50x50x4 -3

    25x25x5 -1.8 50x50x5 -3.8

    40x40x3 -1.8 50x50x6 -4.5

    40x40x4 -2.4 75x75x5 -5.7

    40x40x5 -3 75x75x6 -6.8

    40x40x6 -3.5 75x75x8 -8.9

    J for oule

    KWH for kilowatt

    hour

    KFM kilogram force

    metre KEAL kilocalorie

    HPH

    horsepower

    hour

    FT (foot

    pound

    force

    BTU(british

    thermal

    unitJ 1 0.2778x10

    60.101197 0.23885x10

    40.37767x10

    60.73756 0.94782x10

    4

    kWh 36x106

    1 0.3671x106

    859.85 1.3596 2.6552x106

    3.4142x104

    kfm 1 2.7241x106

    1 2.3423x106

    3.7037x106

    7.233 9.2949x104

    keal 9.8066 1.163x106

    426.94 1 1.5312x103

    3.0880x104

    3.9683

    hph 4.1868x103

    0.7355 0.27x106

    632.42 1 1.9529x106

    2.5096x103

    ft-ibf 1.3558 0.37662x106

    0.13826 0.32383x103

    0.51206x106

    1 1.2851x104

    Btu 1.055x103

    0.29307x106

    107.59 0.252 0.39847x103

    778.17 1

    W Newton kgfm/s keal/s keal/h

    hp.metric

    horsepower

    hp.

    horsepower ft x lbf/s Btu/h

    W 1 1.10197 0.23885x10

    3

    0.85985 1.3596x10

    3

    1.3410x10

    3

    0.73756 3.4121kgfm/s 9.8066 1 2.34x10

    48.4322 13.333x10

    313.151x10

    37.233 33.462

    keal/s 4.1868 x 104

    426.94 1 3.6x104 5.6925 5.6146 3.0880x104

    14.286x103

    keal/h 1.163 0.11859 0.27778x104

    1 1.5812x104

    1.5596x103

    0.85779 3.9683

    hp,metric 735.5 75 0.17567 632.42 1 0.98632 542.48 2.5096x104

    hp, 745.7 76.04 0.17811 644.19 1.0139 1 550 2.5444x104

    ft x lbf/s 13558 0.13826 0.32383x104

    1.1658 1.8434x104

    1.8182x104

    1 4.6262

    Btu h 0.29307 29.885x10 69.999x10 0.2522 0.39847x10 0.39302x10 0.21616 1

    QUANTITIES AND UNITS CONVERSION TABLES

    ENERGY

    6).Equal Angle (Wt.in Kg./ Mtr.)

    POWER

    STEEL DATA FOR SHEETS,PLATES AND SECTIONS

    Wt.in Kg. /

    MtrWeight / Mtr.Size in mm

  • 7/30/2019 47742961 Electrical Details

    5/8

    Current Carryingcapacity

    VoltDrop/Amp./Metre(m

    V)

    Current Carrying

    Capacity(A)

    VoltDrop/Amp./Metre(m

    V)

    1.5 20 29 18 25

    2.5 29 18 24 16

    4 37 12 31 9.5

    6 48 7.4 41 6.3

    10 66 4.3 56 3.8

    16 86 2.7 73 2.3

    25 115 1.8 97 1.6

    35 142 1.3 119 1.1

    50 168 0.92 147 0.81

    70 209 0.65 180 0.57

    90 257 0.48 219 0.42

    120 295 0.4 257 0.34

    150 337 0.32 295 0.29

    185 390 0.29 333 0.24240 461 0.25 399 0.18

    300 523 0.23 451 0.18

    400 589 0.22 523 0.17

    2.5 21 29 19 25.1

    4 27 18.2 25 15.8

    6 35 12.1 32 10.5

    10 48 7.3 43 6.3

    16 65 4.5 58 3.9

    25 84 2.9 74 2.5

    35 105 2.1 90 1.8

    50 125 1.6 115 1.3

    70 150 1.1 135 0.93

    95 185 0.79 165 0.68

    120 210 0.65 190 0.54

    150 240 0.53 215 0.45

    185 280 0.45 250 0.37

    240 325 0.36 295 0.3

    300 380 0.31 340 0.25

    400 460 0.26 415 0.225

    worked

    out

    examples:

    Calculation of voltage frop in 25 Amps 240 volts single phase feeder having 150 mrs

    length.Size cable is 35sq mm AYFY

    Voltage drop / Amp / metre for

    35sq mm AYFY cable = 2.1mV

    Voltage drop in 150mr length

    with current 25 Amps = 2.1x25x150 =7.88V

    1000

    % Viltage drop = 7.88x100 =3.28%

    240

    Take next higher size cable,50sq.mm

    Voltage drop in 150 m length = 1.6x25x150 =6volts

    1000

    % Voltage drop

    So 50sq mm cable is to be selected = 6x100 =2.5%

    240

    VOLTAGE DROP IN INSULATED ALUMINIUM CABLESConductor

    Cross-

    Sectional

    Area

    Installation method (Clipped direct)

    One Twin Single phase Three Core Three Phase

    VOLTAGE DROP IN INSULATED COPPER CABLES

    Conductor

    Cross-

    Sectional

    Area

    (mm2

    )

    Installation method (Clipped direct)

    Three Core Three PhaseOne Twin Single phase

  • 7/30/2019 47742961 Electrical Details

    6/8

    1 2 3 4 1 2 3 4

    I II III II 50 II I II III IIII

    12x2 23.5 0.209 110 200 _ _ 115 205 _ _ 15x2 29.5 0.262 140 200 _ _ 145 245 _ _

    15x3 44.5 0.396 170 300 _ _ 175 305 _ _

    20x2 39.5 0.351 185 315 _ _ 190 325 _ _

    20x3 59.5 0.529 220 380 _ _ 225 390 _ _

    20x5 99.1 0.882 295 500 _ _ 300 510 _ _

    25x3 74.5 0.663 270 460 _ _ 275 470 _ _

    25x5 124 1.11 350 600 _ _ 355 610 _ _

    30x3 89.5 0.796 315 540 _ _ 320 560 _ _

    30x5 149 1.33 400 700 _ _ 410 720 _ _

    40x3 119 1.06 420 710 _ _ 430 740 _ _

    40x5 199 1.77 520 900 _ _ 530 930 _ _

    40x10 399 3.55 700 1350 1850 2500 770 1400 2000 _

    50x5 249 2.22 630 1100 1650 2100 850 1150 1750 _

    50x10 499 4.44 920 1600 2250 3000 960 1700 2500 _

    60x5 299 2.66 760 1250 1760 2400 780 1300 1900 2500

    60x10 599 5.33 1060 1900 2600 3500 1100 2000 2800 3800

    80x5 399 3.55 970 1700 2300 3000 1000 1800 2500 3200

    80x10 799 7.11 1380 2300 3100 4200 1400 2600 3700 4800

    100x5 499 4.44 1200 2050 2850 3500 1250 2250 3150 4050

    100x10 999 8.89 1700 2800 3650 5000 1800 3200 4500 5800

    120x10 1200 10.7 2000 3100 4100 5700 2100 3700 5200 6700

    160x10 1600 14.2 2500 3900 5300 7300 2800 4800 6900 9000

    220x10 2000 17.8 3000 4750 6350 8800 3400 6000 8500 10000

    1 2 3 4 1 2 3 4

    I II III II 50 II I II III IIII

    12x2 23.5 0.0633 80 140 _ _ 80 145 _ _

    15x2 29.5 0.0795 95 170 _ _ 95 175 _ _

    15x3 44.5 0.12 115 210 _ _ 115 220 _ _

    20x2 39.5 0.107 120 220 _ _ 125 225 _ _

    20x3 59.5 0.161 145 270 _ _ 150 280 _ _

    20x5 99.1 0.268 195 350 _ _ 200 370 _ _

    25x3 74.5 0.201 180 330 _ _ 185 340 _ _

    25x5 124 0.335 230 430 _ _ 235 440 _ _

    30x3 89.5 0.242 205 385 _ _ 220 400 _ _

    30x5 149 0.403 270 500 _ _ 275 520 _ _

    40x3 119 0.323 280 500 _ _ 285 525 _ _

    40x5 199 0.588 350 650 _ _ 360 660 _ _

    40x10 399 1.08 515 975 1350 1800 540 1000 1420 _

    50x5 249 0.673 425 780 1120 1500 445 815 1220 _

    50x10 499 1.35 625 1150 1600 2160 655 1220 1730 _

    60x5 299 0.808 500 900 1300 1730 530 960 1420 1850

    60x10 599 1.62 730 1330 1900 2500 770 1430 2030 2600

    80x5 399 1.08 680 1170 1650 2230 700 1260 1850 2400

    80x10 799 2.16 940 1700 2360 3150 985 1840 2640 3400

    100x5 499 1.35 820 440 2000 2600 855 1550 2220 2900

    100x10 999 2.7 1150 2050 2800 3700 1200 2240 3200 4200

    100x15 1500 4.04 1450 2500 3350 4400 1500 2750 4000 5200

    120x10 1200 3.24 1350 2400 3250 4300 1420 2700 3900 5100

    120x15 1800 4.86 1650 2900 3900 5000 1750 3250 4800 6300

    160x10 1600 4.32 1750 3000 4150 5300 1850 3450 5000 6500160x15 2400 6.47 2100 3600 4850 6250 2300 4300 6200 8100

    200x10 2000 5.4 2150 3650 4950 6400 2300 4300 6200 8100

    200x15 3000 8.09 2550 4200 5600 7300 2850 5250 7650 10100

    Copper Bus Bars : Constructional Details and Current Carrying Capacity at 350

    C AmbientTemp.and 300C Temp.Rise

    Size in mmCross Sectional Area

    in MM2

    Weight (Approx) kg

    / Metre

    Continuous Current Carrying Capacity in Amps

    A.C. No.of Buseness A.C.No.of Buses

    Copper Bus Bars : Constructional Details and Current Carrying Capacity at 350

    C AmbientTemp.and 300C Temp.Rise

    Size in mmCross Sectional Area

    in MM2

    Weight (Approx) kg

    / MetreA.C. No.of Buseness A.C.No.of Buses

    Continuous Current Carrying Capacity in Amps

  • 7/30/2019 47742961 Electrical Details

    7/8

    Rated

    Capacity

    No of

    Load

    Loss

    Impedence Rated HV Rated LVLowVoltage

    Conn.Bolts

    Weight

    kVA kW %Z kV kV al a b c d e f g h i k Strap kg25 0.2 4 11 0.433 810 720 940 500 920 880 230 375 350 150 M10 290

    50 0.3 4 11 0.433 810 720 940 500 970 930 230 375 350 150 M10 450

    63 0.3 4 11 0.433 810 720 1040 500 1070 900 210 379 190 190 M10 400

    100 0.38 4 11 0.433 900 840 1200 500 1180 1140 230 375 360 160 M10 600

    125 0.4 4 11 0.433 900 840 1300 500 1280 1240 230 375 350 150 M10 700

    160 0.6 4 11 0.433 900 840 1400 500 1380 1340 230 375 350 150 M16 820

    200 0.75 4 11 0.433 1215 1040 1300 700 1270 1100 230 405 350 150 40X8 1070

    250 0.85 4 11 0.433 1215 1040 1400 700 1370 1200 230 405 350 200 40X8 1250

    315 0.9 4 11 0.433 1215 1040 1510 700 1500 1450 230 405 350 200 40X8 1450

    400 0.93 5 11 0.433 1215 1040 1760 700 1750 1700 230 405 350 200 40X8 1750

    500 1.3 5 11 0.433 1400 1185 1400 820 1420 1340 380 445 350 200 60X8 1900

    630 1.45 5 11 0.433 450 1400 1185 1600 820 1620 1540 380 445 350 200 60X8 2250800 1.85 5 11 0.433 450 1620 1185 1710 820 1790 1650 390 455 350 250 100X8 2700

    1000 2.1 5 11 0.433 475 1620 1185 1800 820 1880 1740 390 455 350 250 100X8 3200

    1250 2.3 5 11 0.433 475 1620 1185 2210 820 2290 2150 390 455 350 350 100X8 3800

    1600 3.2 7 11 0.433 475 1920 1500 2370 1070 2470 2310 415 470 350 350 120X15 4800

    2000 3.6 8 11 0.433 475 2100 1500 2320 1070 2420 2260 420 480 350 350 120X15 5500

    2500 4.4 8 11 0.433 650 2300 1500 2470 1070 2610 2410 440 500 350 350 150X15 6500

    0.72

    1.1

    1.35

    1.7

    2

    2.2

    2.6

    2.8

    3.63.7

    5.7

    6

    8.8

    9.8

    11

    16.5

    2124.5

    Rated freequency : 50HzRated high voltages : 3300,6600,11000, and others upto 12000 volts : Standards taps 2 1/2%,+5%

    Rated low voltage : 110 /220 /380 / 400 / 415 / 525 / 600.

    Dimensions in (mm)

    TYPICAL DETAILS OF DRY TYPE TRANSFORMERS

  • 7/30/2019 47742961 Electrical Details

    8/8

    Recommended size of cables on secondary side of Transformers and for M.V. Alternators

    I Transformers Capacity in KVA PVC Aluminium cable size

    3 Phase at 433 volts (Armoured)

    100 One Run of 31/2 core 95sq.mm.

    150 One Run of 31/2 core 185sq.mm.

    160 One Run of 31/2 core 240sq.mm.

    200 One Run of 31/2 core 300sq.mm.

    250 One Run of 31/2 core 400sq.mm.(or)

    Two Run of 31/2 core 185sq.mm.

    315 Two Run of 31/2 core 240sq.mm.

    400 Three Run of 31/2 core 300sq.mm.

    500 Three Run of 31/2 core 400sq.mm.

    Four Run of 31/2 core 300sq.mm.

    630 Four Run of 31/2 core 400sq.mm.750&above Bus Bar trunking

    II M.V.Alternators PVC Aluminium cable size

    KVA.3 phase (Armoured)

    110 One Run of 31/2 core 95sq.mm.

    160 One Run of 3/12 core 240sq.mm.

    200 One Run of 3/12 core 300sq.mm.

    250 One Run of 3/12 core 400sq.mm.

    Two Rins of 3/12 core 185sq.mm.

    310 Two Rins of 3/12 core 240sq.mm.

    550 Four Runs of 3/12 core 400sq.mm.

    860 Bus bar trunking.

    CAPCITORS IN kVAR FOR REQUIRED P.F.CORRECTIONInitial

    Power

    Initial

    Power

    factor 0.85 0.9 0.95 0.98 1 factor 0.85 0.9 0.95 0.98 1

    0.5 1.112 1.248 1.403 1.529 1.732 0.75 0.262 0.398 0.535 673 0.882

    0.51 1.066 1.202 1.357 0.483 1.686 0.76 0.235 0.371 0.526 0.652 0.855

    0.52 1.024 1.16 1.315 1.441 1.644 0.77 0.209 0.345 0.5 0.62 0.829

    0.53 1.98 1.116 1.271 1.397 1.6 0.78 0.183 0.319 0.473 0.594 0.833

    0.54 0.939 1.075 1.23 1.356 1.559 0.79 0.156 0.292 0.447 0.567 0.776

    0.55 0.899 1.035 1.19 1.316 1.519 0.8 0.13 0.266 0.421 0.541 0.75

    0.56 0.86 0.996 1.151 1.277 1.459 0.81 0.104 0.25 0.395 0.515 0.725

    0.57 0.822 0.958 1.113 1.239 1.442 0.82 0.078 0.214 0.369 0.489 0.6980.58 0.785 0.921 1.076 1.202 1.405 0.83 0.052 0.188 0.343 0.463 0.672

    0.59 0.748 0.884 1.039 1.165 1.368 0.84 0.026 0.162 0.317 0.437 0.645

    0.6 0.714 0.849 1.005 1.131 1.334 0.85 _ 0.136 0.291 0.417 0.62

    0.61 0.679 0.815 0.97 1.096 1.299 0.86 _ 0.109 0.264 0.39 0.593

    0.62 0.645 0.781 0.936 1.062 1.265 0.87 _ 0.083 0.238 0.364 0.567

    0.63 0.613 0.749 0.904 1.03 1.233 0.88 _ 0.054 0.209 0.335 0.538

    0.64 0.58 0.716 0.871 0.997 1.2 0.89 _ 0.028 0.183 0.309 0.512

    0.65 0.549 0.685 0.84 0.966 1.169 0.9 _ _ 0.155 0.251 0.484

    0.66 0.518 0.654 0.809 0.935 1.138 0.91 _ _ 0.124 0.25 0.453

    0.67 0.488 0.624 0.779 0.905 1.108 0.92 _ _ 0.097 0.233 0.426

    0.68 0.459 0.595 0.75 0.876 1.076 0.93 _ _ 0.066 0.192 0.395

    0.69 0.429 0.565 0.72 0.84 1.049 0.94 _ _ 0.034 0.16 0.363

    0.7 0.4 0.536 0.691 0.811 1.02 0.95 _ _ _ 0.126 0.239

    0.71 0.372 0.508 0.663 0.753 0.992 0.96 _ _ _ 0.089 0.292

    0.72 0.343 0.479 0.634 0.754 0.963 0.97 _ _ _ 0.047 0.25

    0.73 0.316 0.452 0.607 0.727 0.863 0.98 _ _ _ _ 0.203

    0.74 0.289 0.425 0.508 0.7 0.909 0.99 _ _ _ _ 0.143

    Example: To find the capacitor rating required to correct a load of at 0.97kW at 0.67 P.F.to 0.95 P.F.

    Required kVAR per KW (vide table above) =0.779

    Total Capacitor rating=0.779x97=75.65 or 76 kVAR.

    Correction to Correction to

    ANNEXURE R