45 Series F Frame Service Manual (11005158 Rev AB Sept 2007)
-
Upload
sasko-dimitrov -
Category
Documents
-
view
220 -
download
0
Transcript of 45 Series F Frame Service Manual (11005158 Rev AB Sept 2007)
-
7/27/2019 45 Series F Frame Service Manual (11005158 Rev AB Sept 2007)
1/28
Series 45 Frame F
Open Circuit AxialPiston Pumps
Service Manual
-
7/27/2019 45 Series F Frame Service Manual (11005158 Rev AB Sept 2007)
2/28
11005158 Rev. AB September 2007
Series 45 Frame F Open Circuit Axial Piston Pumps
Service Manual
Revisions
2007 Sauer-Danoss. All rights reserved.
Sauer-Danoss accepts no responsibility or possible errors in catalogs, brochures and other printed material.
Sauer-Danoss reserves the right to alter its products without prior notice. This also applies to products
already ordered provided that such alterations arent in conict with agreed specifcations. All trademarks in
this material are properties o their respective owners. Sauer-Danoss and the Sauer-Danoss logotype are
trademarks o the Sauer-Danoss Group.
Front cover illustrations: F101 503, P105265E
Table o Revisions
D P Chd R.
September 2007 28 revision to change per turn or displacement limiter AB
November 2006 - First edition AA
HistoRy o Revisions
-
7/27/2019 45 Series F Frame Service Manual (11005158 Rev AB Sept 2007)
3/28
11005158 Rev. AB September 2007
Series 45 Frame F Open Circuit Axial Piston Pumps
Service Manual
intRoDuCtion
teCHniCal
sPeCiiCations
eatuRes
PRessuRe
measuRement
initial staRt-uP
PRoCeDuRes
luiD anD ilteR
maintenanCe
Overview ...........................................................................................................................................................5
Saety precautions .........................................................................................................................................5
Unintended machine movement .......................................................................................................5Flammable cleaning solvents ...............................................................................................................5
Fluid under pressure ................................................................................................................................5
Personal saety ...........................................................................................................................................5
Symbols used in Sauer-Danoss literature.............................................................................................6
General description ....................................................................................................................................... 7
System circuit ...................................................................................................................................................8
General specifcations ..................................................................................................................................9
Type o mounting ..................................................................................................................................... 9
Auxiliary mounting pad options ......................................................................................................... 9
Control options ..........................................................................................................................................9Port options ................................................................................................................................................9
Direction o rotation ................................................................................................................................9
Installation position .................................................................................................................................9
Technical specifcations ..........................................................................................................................9
Hydraulic parameters..................................................................................................................................10
Inlet pressure ............................................................................................................................................10
Pressure compensator valve setting ................................................................................................10
Case pressure ...........................................................................................................................................10
Hydraulic uid .........................................................................................................................................10
Temperature range.................................................................................................................................11
Fluid viscosity ...........................................................................................................................................11
Filtration ....................................................................................................................................................11
Displacement limiter ...................................................................................................................................12
Auxiliary mounting pads ...........................................................................................................................12
Input shats .....................................................................................................................................................12
Control options .............................................................................................................................................13
Operation ...................................................................................................................................................13
Control options .............................................................................................................................................14
Required tools ...............................................................................................................................................15
Port locations and gauge installation ...................................................................................................15
General .............................................................................................................................................................16
Start-up procedure ......................................................................................................................................16
Recommendations.......................................................................................................................................17
-
7/27/2019 45 Series F Frame Service Manual (11005158 Rev AB Sept 2007)
4/28
11005158 Rev. AB September 2007
Series 45 Frame F Open Circuit Axial Piston Pumps
Service Manual
tRoublesHooting
aDjustments
minoR RePaiR
Excessive noise and / or vibration ..........................................................................................................18
Actuator response is sluggish ..................................................................................................................18
System operating hot .................................................................................................................................19Low pump output ow ..............................................................................................................................19
Pressure or ow instability ........................................................................................................................19
System pressure not reaching PC setting ............................................................................................20
High inlet vacuum ........................................................................................................................................20
PC control ........................................................................................................................................................21
LS control ........................................................................................................................................................22
Shat seal replacement ...............................................................................................................................23
Removal ......................................................................................................................................................23Installation .................................................................................................................................................23
Auxiliary pads ................................................................................................................................................24
Removal ......................................................................................................................................................24
Installation .................................................................................................................................................24
Control..............................................................................................................................................................25
Disassembly ..............................................................................................................................................25
Inspection ..................................................................................................................................................25
Reassembly ...............................................................................................................................................26
Plug and ftting sizes and torques ..........................................................................................................27
-
7/27/2019 45 Series F Frame Service Manual (11005158 Rev AB Sept 2007)
5/28
511005158 Rev. AB September 2007
Series 45 Frame F Open Circuit Axial Piston Pumps
Service Manual
Introduction
This manual includes inormation or the installation, maintenance, and minor repair o
the Series 45 Frame F open circuit axial piston pumps. The manual includes a description
o the units and their individual components, troubleshooting inormation, and minorrepair procedures. Perorming installation, maintenance, and minor repair o Series 45
Frame F axial piston pumps according to the procedures in this manual will not aect
your warranty.
Perorming minor repairs requires the unit to be removed rom the vehicle/machine.
Thoroughly clean the unit beore beginning maintenance, or repair activities. Since dirt
and contamination are the greatest enemies o any type o hydraulic equipment, ollow
cleanliness requirements strictly. This is especially important when changing the system
flter and when removing hoses or plumbing.
A worldwide Global Service Partner Network is available or major repairs. Major repairs
require the removal o the units endcap, which voids the warranty unless done by aGlobal Service Partner. Sauer-Danoss Global Service Partners are trained by the actory
and certifed on a regular basis. You can locate your nearest Global Service Partner using
the distributor locator at www.sauer-danoss.com
Always consider saety precautions beore beginning a service procedure. Protect
yoursel and others rom injury. Take these general precautions whenever servicing a
hydraulic system.
udd ch
WarningUnintended movement o the machine or mechanism may cause injury to the technician
or bystanders. To protect against unintended movement, secure the machine or
disable / disconnect the mechanism while servicing.
c
WarningSome cleaning solvents are ammable. To avoid possible fre, do not use cleaning
solvents in an area where a source o ignition may be present.
d dr prr
WarningEscaping hydraulic uid under pressure can have sufcient orce to penetrate your skin
causing serious injury and/or inection. This uid may also be hot enough to cause burns.
Use caution when dealing with hydraulic uid under pressure. Relieve pressure in thesystem beore removing hoses, fttings, gauges, or components. Never use your hand
or any other body part to check or leaks in a pressurized line. Seek medical attention
immediately i you are cut by hydraulic uid.
Pr
WarningProtect yoursel rom injury. Use proper saety equipment, including saety glasses, at all
times.
oveRview
saety PReCautions
-
7/27/2019 45 Series F Frame Service Manual (11005158 Rev AB Sept 2007)
6/28
11005158 Rev. AB September 2007
Series 45 Frame F Open Circuit Axial Piston Pumps
Service Manual
Introduction
symbols useD in
saueR-Danoss
liteRatuRe
These symbols are in the illustrations and text o this manual. They communicate helpul
inormation at the point where it is most useul to the reader.
In most instances, the appearance o the symbol itsel denotes its meaning. The legend
below defnes the symbol and explains its purpose.
WARNING may result in injury
CAUTION may result in damage toproduct or property
Reusable part
Non-reusable part, use a new part
Non-removable item
Option either part may exist
Superseded parts are notinterchangeable
Measurement required
Flatness specifcation
Parallelism specifcation
External hex head
Internal hex head
Torx head
O-ring boss port
Tip, helpul suggestion
Lubricate with hydraulic uid
Apply grease / petroleum jelly
Apply locking compound
Inspect or wear or damage
Clean area or part
Be careul not to scratch or damage
Note correct orientation
Mark orientation or reinstallation
Torque specifcation
Press in press ft
Pull out with tool press ft
Cover splines with installationsleeve
Pressure measurement / gaugelocation or specifcation
waRRanty Perorming installation, maintenance, and minor repairs according to the procedures in
this manual will not aect your warranty. Major repairs requiring the removal o a units
endcap voids the warranty unless done by a Sauer-Danoss Global Service Partner.
-
7/27/2019 45 Series F Frame Service Manual (11005158 Rev AB Sept 2007)
7/28
11005158 Rev. AB September 2007
Series 45 Frame F Open Circuit Axial Piston Pumps
Service Manual
Introduction
Sauer-Danoss Series 45 Frame F open circuit piston pumps convert input torque into
hydraulic power. The input shat transmits rotational orce rom the prime mover to
the cylinder block. Tapered roller bearings support the shat at the ront and rear o thepump. The cylinder block connects to the input shat through splines on the shat. A
lip-seal at the ront end o the pump prevents leakage where the shat exits the pump
housing. The spinning cylinder block contains nine reciprocating pistons. Each piston
has a brass slipper connected at one end by a ball joint. The slippers are held to the
swashplate by the spring retainer and block spring. The block spring also holds the
cylinder block to the valve plate. The reciprocating movement o the pistons occurs
as the slippers slide against the inclined swashplate during rotation. The valve plate
connects one hal o the cylinder block to pump inlet and the other hal to pump outlet.
As each piston cycles in and out o its bore, uid is drawn rom the inlet and displaced to
the outlet thereby imparting power into the system circuit. A small amount o uid leaks
rom the cylinder block / valve plate and slipper / swashplate interaces or lubrication
and cooling. Case drain ports return this uid to the reservoir.
The angle o the swashplate controls the volume o uid displaced into the system
circuit. The bias piston orces the swashplate into an inclined position (into stroke). The
servo piston opposes the action o the bias piston and spring, orcing the swashplate out
o stroke when hydraulic pressure in the control circuit rises above the spring orce.
The pump control, by varying the pressure at the servo piston, controls the displacement
o uid in the system circuit. Controls designed or Pressure Compensation (PC) or
load sensing (LS) are available. For a detailed description o control operation, reer to
Control op tions, operation, page 13.
geneRal DesCRiPtion
Pump and control sectional view
Slipper
LS adjustment
PC adjustment
LS spool
PC spool
LS control(attached to endcap)
Servo piston
Swashplate
Taperedrollerbearing
Shaft seal
Tapered rollerbearing
Input shaft
Cylinderblock
Valveplate
Cylinderblockspring
Piston
Slipper retainer
Bias spring
P104 341EBias piston
-
7/27/2019 45 Series F Frame Service Manual (11005158 Rev AB Sept 2007)
8/28
8 11005158 Rev. AB September 2007
Series 45 Frame F Open Circuit Axial Piston Pumps
Service Manual
Introduction
1 Full available ow is a unction o pump displacement, operating speed, and efciency. Reer to Series 45 Frame
F Axial Piston Open Circuit Pumps Technical Inormation,50l098or details.
system CiRCuit
Pictorial circuit diagram
System pressure
Servo pressure
Actuator pressure
Load sense pressure
Actuator return
Suction / case drain /system return
Series 45 F Frameopen circuit axialpiston pump withload sensing control PVG 32
multi-sectionloadsensingcontrol
valve
P106 212E
Reservoir Filter
Heat exchanger
Double-acting cylinder
Bi-directionalgear motor
The pump receives uid directly rom the reservoir through the inlet line. A screen in the
inlet line protects the pump rom large contaminants. The pump outlet eeds a PVG-32
multi-section, load sensing, directional control valve. The PVG valve directs pump ow tothe cylinder and gear motor. A heat exchanger cools the uid returning rom the valve. A
flter cleans the uid beore it returns to the reservoir.
Flow in the circuit determines the speed o the actuators. The position o the PVG valve
determines the ow demand. A hydraulic pressure signal (LS signal) communicates
demand to the pump control. The pump control monitors the pressure dierential
between pump outlet and the LS signal, and regulates servo pressure to control the
swashplate angle. Swashplate angle determines pump ow.
Actuator load determines system pressure. The pump control monitors system pressure
and will decrease the swashplate angle to reduce ow i system pressure reaches the
PC setting. A system relie valve in the PVG valve acts as a back-up to control systempressure.
-
7/27/2019 45 Series F Frame Service Manual (11005158 Rev AB Sept 2007)
9/28
911005158 Rev. AB September 2007
Series 45 Frame F Open Circuit Axial Piston Pumps
Service Manual
Technical specifcations
tp
SAE-C mounting ange.
ar pd p
SAE-A, SAE-B, SAE-B-B, SAE-C, SAE C-C
Cr p
PC: Pressure Compensator
LS: Load Sensing (with PC)
Pr p
Inlet and system ports: SAE anged ports, code 61 Inlet Code 62 outlet.
Axial (end) ports or radial (side) ports.
All other ports: SAE straight thread O-ring boss.
Drc r
Clockwise or counterclockwise.
i p
Installation position is discretionary. To satisy inlet pressure conditions, we recommend
you locate the pump below the lowest level o hydraulic uid in the reservoir. The
housing must always be flled with hydraulic uid.
tchc pcc
geneRal
sPeCiiCations
Features and options md
r u b 90C
Maximum displacement cm [in] 74 [4.52] 90 [5.49]
Flow at rated speed (theoretical) l/min
[US gal/min]
177.6
[46.9]
198
[52.3]
Input torque at maximum displacement
(theoretical)
Nm/bar
[lbin/1000 psi]
1.178
[719]
1.432
[874]
Mass moment o inertia o internal
rotating components
kgm
[slugt]
0.00630
[0.00465]
0.00650
[0.00480]
Weight Axial ports kg [lb] 29 [63]
Radial ports 31.8 [70.1]
Rotation Clockwise, Counterclockwise
Mounting SAE B 2 blot, SAE-C 4 bolt
Auxiliary mounting SAE-A, SAE-B, SAE-BB, SAE-CSystem ports (type) 4-bolt split ange
System ports (location) Axial, Radial
Control types PC, Remote PC, LS, Electric
Shats Splined 14 tooth, 17 tooth
Straight 31.75 mm [1.25 in]
Displacement limiters Optional, adjustable
-
7/27/2019 45 Series F Frame Service Manual (11005158 Rev AB Sept 2007)
10/28
10 11005158 Rev. AB September 2007
geneRal
sPeCiiCations
(cd)
Series 45 Frame F Open Circuit Axial Piston Pumps
Service Manual
Technical specifcations
i prr
Minimum pressure, continuous = 0.8 bar absolute [6.7 inch Hg vacuum]
(at reduced maximum pump speed)
Minimum pressure, cold start = 0.5 bar absolute [15.1 inch Hg vacuum]
Prr cpr
HyDRauliC
PaRameteRs
C prr
Maximum continuous: 0.5 bar [7 psi] above inlet
Intermittent: 2 bar [29 psi] cold start
Hdrc fdReer to Sauer-Danoss publication: Fluids and Filtration50l0. For inormation on
biodegradable uids reer to Biodegradable Hydraulic Fluids,50l05. See Fluid and
lter maintenance, page 17 or recommended uid and flter change intervals.
Ratings md
R u gb g90C
Input speed1 minimum min-1 (rpm) 500 500
continuous 2400 2200
maximum 2800 2600
Working pressure continuous bar [psi] 310 [4495] 260 [3770]
maximum 400 [5800] 350 [5075]
External shat
loads
External moment (Me) Nm [lbin] 300 [2655]
Thrust in (Tin), out (Tout) N [lb ] 2900 [650]
Bearing lie at 140 bar [2030 psi] B10 hours 31 300 17 400
at 210 bar [3045 psi] 1110 5700
at 260 bar [3770 psi] 4810 2490
at 310 bar [4495 psi] 3080 1636
Mounting ange
load moments
Vibratory (continuous) Nm [lbin] 3730 [33 000]
Shock (maximum) 13 220 [117 000]
1. Input speeds are valid at 1 bar absolute [0 in Hg vac] inlet pressure. See Inlet pressure vs. speedcharts.
PC control setting range
md r p
b 100310 14504495
90C 100260 14503770
-
7/27/2019 45 Series F Frame Service Manual (11005158 Rev AB Sept 2007)
11/28
1111005158 Rev. AB September 2007
HyDRauliC
PaRameteRs
(cd)
Series 45 Frame F Open Circuit Axial Piston Pumps
Service Manual
Technical specifcations
1 Hydraulic uid viscosity must be maintained within the prescribed limits.2 As measured at the hottest point in the system, e.g. drain line.
r
Required cleanliness level: ISO 4406 Class 18/13 or better. Reer to Sauer-Danoss
publications Fluids and Filtration50l0 and Design Guidelines or Selecting and
Maintaining the Required Hydraulic Fluid Cleanliness50l05. See Fluid and lter
maintenance, page 17 or recommended uid and flter change intervals.
tprr r
d c
Fluid viscosity limits
Cd / (cs) sus
min.continuous 9 58
intermittent 6.4 47
max.
continuous 110 500
intermittent(cold start)
1000 4700
Temperature limitsm
(r, cd r)- 40 C [- 40 F]
C 82 C [180 F]
m 104 C [220 F]
-
7/27/2019 45 Series F Frame Service Manual (11005158 Rev AB Sept 2007)
12/28
1 11005158 Rev. AB September 2007
Series 45 Frame F Open Circuit Axial Piston Pumps
Service Manual
Features
DisPlaCement limiteR
auxiliaRy mounting
PaDs
inPut sHats Series 45 F Frame pumps are available with a variety o splined and straight keyed
shats. For inormation on shats reer to Series 45 F Frame Axial Piston Open Circuit Pumps
Technical Inormation50l098.
Frame F Series 45 pumps are available
with an optional adjustable maximum
displacement limiter. The adjustablestop limits the pumps maximum
displacement. The displacement change
per turn is 6.8 cm/turn [0.47 in/turn] or
the F90C and 6.0 cm/turn [6.1 in/turn]
or the F74B
Displacement limiter
P104 345
Auxiliary mounting pads are available or
all radial ported Series 45 pumps. These
pads are typically used or mountingauxiliary hydraulic pumps.
Since the auxiliary pad operates under
case pressure, you must use an O-ring to
seal the auxiliary pump mounting ange
to the pad. Oil rom the main pump case
lubricates the drive coupling. For details
reer to Series 45 F Frame Axial Piston
Open Circuit Pumps Technical Inormation
50l098.
Auxiliary pad options
P106 262E
-
7/27/2019 45 Series F Frame Service Manual (11005158 Rev AB Sept 2007)
13/28
111005158 Rev. AB September 2007
Series 45 Frame F Open Circuit Axial Piston Pumps
Service Manual
Features
The Series 45 Frame F pumps have two control options, a load sensing (LS) control with
Pressure Compensator (PC) or a PC only control.
b pr d r p hp
p
Cross-section pumpopr
General
The bias piston and spring (1&2) acts at
all times to push the swashplate (4) to
maximum angle causing the pump to
stroke. The servo piston (3) acts against
the bias piston and spring to reduce the
swashplate angle causing the pump to
destroke. Swashplate angle determines
pump outlet ow. The pump control,
depending on conditions in the system
circuit, sets swashplate angle by meteringsystem pressure to the servo piston.
PC control
The PC control design maintains a
constant pressure in the hydraulic circuit
as ow varies. The PC control modulates
pump ow accordingly to maintain
system pressure at the PC setting as
the PC adjusting plug (4) and spring (5)
defne.
When system pressure, acting on the
non-spring end o the PC spool (6),
overcomes the orce o the PC spring (5),
the spool shits porting system pressure to the servo piston and the swashplate angle
decreases. When system pressure drops below the PC setting, the PC spring shits the
spool in the opposite direction connecting the servo piston to pump case and the
swashplate angle increases. The swashplate is maintained at whatever angle is required
to keep system pressure at the PC setting.
ContRol oPtions
PC spool shifts to port system pressure to
servo piston
Cross-section PC control
P104 049
4
56
P106 261E1
234
-
7/27/2019 45 Series F Frame Service Manual (11005158 Rev AB Sept 2007)
14/28
1 11005158 Rev. AB September 2007
Series 45 Frame F Open Circuit Axial Piston Pumps
Service Manual
Features
ContRol oPtions
(cd)
LS control
The LS control design matches pump
ow with system demand. The LS controlsenses the ow demand o the system
as a pressure drop across the external
Control valve (ECV). As the ECV opens
and closes, the pressure delta across
the valve changes. When opening, the
delta decreases. When closing, the delta
increases. The LS control then increases
or decreases pump ow to the system
until the pressure delta becomes equal
to the LS setting as defned by the LS
adjusting plug (7) and spring (8).
Load
pressure
Load sensepressure
Systempressure
Tank
Return
pressure
P101 665E
Typical load-sensing control valve
Prr drp cr r cr
d dd
The LS control consists o two spool
valves that connect the servo pistoneither to pump case or system pressure.
The PC spool (6) controls the pressure-
compensating unction o the control
as previously described. The LS spool (9)
controls the load-sensing unction. The
PC spool has priority over the LS spool.
Through internal porting, system pressure
(upstream o ECV) is applied to the non-
spring end o the LS spool, and through
hydraulic line connected at port X, LS
pressure (downstream o ECV) is applied
to the spring end. This arrangement allows the LS spool to act on the delta between system
pressure and LS pressure. The LS spring sets the threshold o operation (LS setting).
Because the swashplate is biased to maximum angle, the pump attempts to deliver
ull ow to the hydraulic system. When the ow being delivered exceeds demand, the
pressure delta across the ECV is great enough to overcome spring orce and shit the
LS spool porting system pressure to the servo piston. The pump de-strokes reducing
ow until the delta across the ECV becomes equal to the LS setting. When ow being
delivered is less than demand, the delta across the ECV drops below the LS setting and
the LS spring shits the spool connecting the servo piston to pump case. The pump
strokes increasing ow until the delta across the ECV becomes equal to the LS setting.
When the external control valve is placed in neutral, it connects the LS signal line todrain. With no LS pressure acting on the non-spring end o the LS spool, the pump
adjusts stroke to whatever position necessary to maintain system pressure at the LS
setting. The pump is now in standby mode.
Because o the series arrangement o the LS and PC spools, the PC spool will override
the LS spool. I at any time system pressure reaches the PC setting, the PC spool will shit
blocking the passage that connects the LS spool with the servo piston, thus porting
system pressure to the servo piston causing the pump to destroke.
ls p h pr prr r
p
Cross-section LS control
Spool
Spring
guide
Spring
7LS adjustingplug
LS spring
PC adjusting
plugPlug
Plug
Spool Spring
guide
Spring
(PC heavy)
P104 051
6
89
-
7/27/2019 45 Series F Frame Service Manual (11005158 Rev AB Sept 2007)
15/28
1511005158 Rev. AB September 2007
Series 45 Frame F Open Circuit Axial Piston Pumps
Service Manual
Pressure measurement
The service procedures described in this manual can be perormed using common
mechanics hand tools. Special tools, i required are shown. Calibrate pressure gauges
requently to ensure accuracy. Use snubbers to protect gauges.
The illustration below shows gauge port locations. Recommended pressure gauges and
fttings are in the table.
Gauge port locations
P106 263E
LegendB = Main pressure lineS = Suction lineL1, L2 = Case drain linesX = Load sensing pressure portM2 = Gauge port for port BM4 = Gauge port servo pressure
X
M2
L1
L2
SB
M4
RequiReD tools
PoRt loCations anD
gauge installation
Gauge and port inormation
Pr Prp R
M2 System pressure 0-300 bar [0-5000 psi] 9/16 - 18 O-ring ftting
M4 Servo pressure 0-300 bar [0-5000 psi] 9/16 - 18 O-ring ftting
L1, L2 Case pressure 0-10 bar [0-100 psi] 7/8 - 14 O-ring ftting
X1 LS signal 0-300 bar [0-5000 psi]7/16 - 20 O-ring ftting
(tee into LS signal line)
-
7/27/2019 45 Series F Frame Service Manual (11005158 Rev AB Sept 2007)
16/28
1 11005158 Rev. AB September 2007
Series 45 Frame F Open Circuit Axial Piston Pumps
Service Manual
Initial start-up procedures
CautionIncorrect shat alignment
may result in damage
to drive shat, bearings,
or seal which can cause
external oil leakage.
geneRal
staRt-uP PRoCeDuRe 1. Connect the pump to the prime mover. Ensure that pump shat is properly aligned
with the shat o the prime mover. 2. Fill the main pump housing with clean fltered hydraulic uid. Pour fltered oil
directly into the upper most case drain port.
3. To ensure the pump stays flled with oil, install the case drain line in the upper most
case drain port.
4. Fill the inlet line leading rom the pump to the reservoir. Check the inlet line or
properly tightened fttings. Be certain it is ree o restrictions and air leaks.
5. Fill the reservoir with recommended hydraulic uid. Always flter uid through a 10
micron flter pouring into the reservoir. Never reuse hydraulic uid.
6. Install a gauge at port or M2 to monitor system pressure during start up.
Follow recommendations in the vehicle / machine operators manual or prime mover
start up procedures.
7. While watching the pressure gauge installed at M2, jog the prime mover or run at
the lowest possible speed until system pressure builds to normal levels (minimum
11 bar [160 psi]). Once system pressure is established, increase to ull operating
speed. I system pressure is not maintained, shut down the prime mover, determine
cause, and take corrective action. Reer to Troubleshooting, page 18.
8. Operate the hydraulic system or at least fteen minutes under light load conditions.
9. Check and adjust control settings as necessary ater installation. Reer to
Adjustments, page 21.
10. Shut down the prime mover and remove the pressure gauge. Replace plug at port M2.
11. Check the uid level in the reservoir; add clean fltered uid i necessary.
The pump is now ready or operation.
Follow this procedure when starting-up a new Series 45 installation or when restarting
an installation in which the pump has been removed.
WarningUnintended movement o the machine or mechanism may cause injury to the technician
or bystanders. To protect against unintended movement, secure the machine or disable/
disconnect the mechanism while servicing.
Prior to installing the pump, inspect or damage incurred during shipping. Make certain
all system components (reservoir, hoses, valves, fttings, heat exchanger, etc.) are clean
prior to flling with uid.
-
7/27/2019 45 Series F Frame Service Manual (11005158 Rev AB Sept 2007)
17/28
111005158 Rev. AB September 2007
Series 45 Frame F Open Circuit Axial Piston Pumps
Service Manual
Fluid and flter maintenance
To ensure optimum lie o Series 45 products, perorm regular maintenance o the uid
and flter. Contaminated uid is the main cause o unit ailure. Take care to maintain uid
cleanliness when servicing.
Check the reservoir daily or proper uid level, the presence o water, and rancid uid
odor. Water in the uid may be noted by a cloudy or milky appearance or ree water
in the bottom o the reservoir. Rancid odor indicates the uid has been exposed to
excessive heat. Change the uid immediately i these conditions occur. Correct the
problem immediately.
ReCommenDations
Change the uid and flter per the
vehicle / machine manuacturers
recommendations or at these intervals:
Change the uid more requently i itbecomes contaminated with oreign
Fluid and lter change interval
Rrr p m ch r
Sealed 2000 hours
Breather 500 hours
matter (dirt, water, grease, etc.) or i the uid is subjected to temperature levels greater
than the recommended maximum.
Dispose o used hydraulic uid properly. Never reuse hydraulic uid.
Change flters whenever the uid is changed or when the flter indicator shows that it is
necessary to change the flter. Replace all uid lost during flter change.
-
7/27/2019 45 Series F Frame Service Manual (11005158 Rev AB Sept 2007)
18/28
18 11005158 Rev. AB September 2007
Series 45 Frame F Open Circuit Axial Piston Pumps
Service Manual
Troubleshooting
exCessive noise anD /
oR vibRation
aCtuatoR ResPonse is
sluggisH
i Dcrp ac
Check uid level in reservoir.Insufcient hydraulic uid causes
cavitation.Fill the reservoir to proper level.
Check or air in system.Air in system causes noisy, erratic
control.
Purge air and tighten fttings.
Check inlet or leaks.
Check pump inlet pressure /
vacuum.
Improper inlet conditions cause
erratic behavior and low output
ow.
Correct pump inlet pressure /
vacuum conditions. Reer to
Hydraulic parameters, page 10.
Inspect shat couplings.
A loose or incorrect shat coupling
causes excessive noise and / or
vibration.
Repair or replace coupling and
ensure that correct coupling is
used.
Check shat alignment.Misaligned shats create excessive
noise and / or vibration.Correct shat misalignment.
Hydraulic uid viscosity above
acceptable limits.
Hydraulic uid viscosity above
acceptable limits or low uid
temperature will not allow the
pump to fll or control to operate
properly.
Allow system to warm up beore
operating, or use uid with the
appropriate viscosity grade or
expected operating temperatures.
See Hydraulic Fluids, Series 45
F Frame Technical Inormation
Manual,50l098.
i Dcrp ac
Check external system relie valve
setting.
Low external relie valve setting
slows down system.
Adjust external relie valve
setting ollowing manuacturers
recommendations. External relie
setting must be above PC setting
to operate properly.
Check PC and LS control setting.
Low PC setting prevents the pump
rom achieving ull stroke. Low LS
setting limits output ow.
Adjust PC and LS setting. Reer to
Adjustments, pages 21 and 22.
Check LS control signal pressures.Incorrect LS signal will not allow
pump to operate correctly.
Inspect system to ensure that
proper LS signal transmit to pump.
Internal system leaks.Worn internal parts dont allow the
pump to operate properly.
Reer to Sauer-Danoss Global
Service Partner or required repair.
Hydraulic uid viscosity above
acceptable limits.
Hydraulic uid viscosity above
acceptable limits or low uid
temperature will not allow the
pump to fll or control to operateproperly.
Allow system to warm up beore
operation or sue uid with the
appropriate viscosity grade or
expected operating temperatures.
See Hydraulic Fluids, Series 45F Frame Technical Inormation
Manual,50l098.
Check external system valves.Malunctioning valves may not
allow system to respond properly.
Repair or replace system valving as
required.
Check pump case pressure.High case pressure causes the
system to be sluggish.Correct case drain line restrictions.
Check pump inlet pressure /
vacuum.
High inlet vacuum causes low
output ow.Correct inlet pressure conditions.
-
7/27/2019 45 Series F Frame Service Manual (11005158 Rev AB Sept 2007)
19/28
1911005158 Rev. AB September 2007
Series 45 Frame F Open Circuit Axial Piston Pumps
Service Manual
Troubleshooting
system oPeRating Hot
low PumP outPut
low
PRessuRe oR low
instability
i Dcrp ac
Check uid level in reservoir.
Insufcient volume o hydraulic
uid will not meet cooling
demands o system.
Fill reservoir to proper level. Veriy
proper size o reservoir.
Inspect heat exchanger. Check air
ow and input air temperature or
the heat exchanger.
Insufcient air ow, high input air
temperature, or undersized heat
exchangers will not meet cooling
demands o the system.
Clean, repair, or replace heat
exchanger as required. Veriy
proper size o heat exchanger.
Check external system relie valve
setting.
Fluid passing through relie valve
adds heat to system.
Adjust external system relie valve
setting ollowing manuacturers
recommendations. External relie
valve setting must be above PC
setting or proper operation.
Check pump inlet pressure /
vacuum.
High inlet vacuum adds heat to
system.
Correct inlet pressure / vacuum
conditions.
i Dcrp ac
Check uid level in reservoir.
Insufcient hydraulic uid will limit
output ow and cause internal
damage to pump.
Fill the reservoir to proper level.
Hydraulic uid viscosity above
acceptable limits.
Fluid viscosity above acceptable
limits or low uid temperature
will not allow the pump to fll or
control to operate properly.
Allow system to warm up beore
operating, or use uid with the
appropriate viscosity grade or
expected operating temperatures.
See Hydraulic fuids, Series 45
F Frame Technical Inormation
Manual,50l098.
Check external system relie valve
setting.
Eternal relie valve set below PC
setting causes low output ow.
Adjust external relie valve
ollowing manuacturers
recommendation. External relie
valve setting must be above PC
setting to operate properly.
Check PC and LS control setting.Low PC setting prevents the pump
rom achieving ull stroke.
Adjust PC and LS setting. Reer to
Adjustment, page 21.
Check pump inlet pressure /
vacuum.
High inlet vacuum causes low
output ow.Correct inlet pressure conditions.
Check input speed. Low input speeds decrease ow. Adjust input speed.
Check pump rotation.Incorrect rotational confguration
causes low ow.
Use pump with appropriate
rotational confguration.
i Dcrp ac
Check or air in system.Air in system causes erratic
operation.
Activate PC allowing system
to bleed air. Check inlet line or
leaks and eliminate source o air
ingression.
Check control spools.Sticking control spools cause
erratic operation.
Inspect spools or ree movement
in bore. Clean or replace.
-
7/27/2019 45 Series F Frame Service Manual (11005158 Rev AB Sept 2007)
20/28
0 11005158 Rev. AB September 2007
PRessuRe oR low
instability
(cd)
Series 45 Frame F Open Circuit Axial Piston Pumps
Service Manual
Troubleshooting
system PRessuRe not
ReaCHing PC setting
HigH inlet vaCuum
CautionHigh inlet vacuum causes
cavitation which candamage internal pump
components.
i Dcrp ac
Check LS setting.Low LS setting may cause
instability.
Adjust LS setting to proper level.
SeeAdjustments, page 21.
Check LS signal line.Blocked LS signal line intereres
with proper LS operation.Remove blockage.
Check external relie valve and PC
setting.
Insufcient pressure dierential
between PC setting and external
relie valve.
Adjust external relie valve or PC
control settings to appropriate
level. Relie valve setting must
be above PC setting to operate
properly.
Check external relie valve.
Chattering external relie valve
may cause unstable eedback to
pump control.
Adjust or replace relie valve.
i Dcrp ac
Check PC control setting.System pressure will not rise above
PC setting.
Adjust PC to appropriate setting.
Reer toAdjustments, page 21.
Check external relie valve.
External relie valve setting below
PC setting prevents pressure
compensation.
Adjust external relie valve
according to manuacturers
recommendations. External relie
valve must be set above PC setting
to operate properly.
Inspect PC control spring.Broken, damaged, or missing
spring will cause erratic operation.Replace the spring as required.
Inspect PC spool or wear.Wear o PC spool causes internal
leakage in the control.Replace the spool as required.
Inspect PC spool or proper
orientation.
Improper orientation results in
poor operation.Correct orientation o spool.
Check PC control or
contamination.
Contamination may interere with
movement o the PC spool.
Clean PC control components, take
appropriate action to eliminate
contamination.
i Dcrp ac
Check uid temperature.
Low temperature increases
viscosity. High uid viscosity
causes high inlet vacuum.
Allow system to warm up beore
operating.
Inspect inlet screen. Blocked or restricted inlet screencauses high inlet vacuum.
Clean screen / remove blockage.
Check inlet piping.Too many fttings, bends, or long
piping causes high inlet vacuum.
Eliminate fttings to make path
more direct.
Hydraulic uid viscosity above
acceptable limits.
High uid viscosity causes high
inlet vacuum.
Select uid with appropriate
viscosity or expected operating
temperature. See Hydraulic
fuids, Series 45 F Frame Technical
Inormation Manual, 50l098.
-
7/27/2019 45 Series F Frame Service Manual (11005158 Rev AB Sept 2007)
21/28
111005158 Rev. AB September 2007
Series 45 Frame F Open Circuit Axial Piston Pumps
Service Manual
Adjustments
PC ContRol PC setting is indicated in the pump model code. Reer to the Series 45 Frame F Open
Circuit Axial Piston Pumps Technical Inormation Manual,50l098, or more inormation.
Beore perorming adjustments, read page 15, Pressure measurement.WarningEscaping hydraulic uid
under pressure can
have sufcient orce
to penetrate your skin
causing serious injury
and/or inection. Relieve
pressure in the system
beore removing hoses,
fttings, gauges, or
components.
Unintended movement o
the machine or mechanism
may cause injury to the
technician or bystanders.
To protect against
unintended movement,
secure the machine or
disable / disconnect
the mechanism while
servicing.
1. Install a pressure gauge in port M2
to measure system pressure. Install a
pressure gauge in case drain port L1
or L2 to measure case pressure.C
2. Start the prime mover and allow
uid to reach normal operating
temperature. Operate a hydraulic
unction to its ull extension, loadingthe pump to maximum pressure and
zero ow.
3. Loosen the PC set screw and turn the
PC adjusting plug until the gauge
at port M2 indicates the desired
setting. Clockwise rotation increases
pressure, counterclockwise rotation
decreases; approximate gain 42 bar
[610 psi] per turn.
I the pressure does not increase, an
external system relie valve may require
adjustment. External system relie valve
must be set above the PC setting or
proper operation.
4. While holding the position o the
PC adjusting plug, torque the PC set
screw to 9 Nm [7 lbt].
1 PC setting is reerenced to case pressure. Subtract case pressure rom system pressure to compute the actual
setting.
PC control adjustment
Gauge port M2
0 - 300 bar [0 - 4351 psi]
3/16 in
7/16-20
50 Nm
[37 lbfft]
Case drain port L1
0 - 10 bar [0 - 145 psi]
3/8 in
7/8-14
90 Nm
[67 lbfft]LS set screw
4 mm9 Nm
[7 lbfft]
P106 264E
X Port
0-300 bar
[0-5000 psi]
3/16 in
7/16-20
20 Nm
[51 lbfft]
CautionContamination can
damage internal
components and void the
manuacturers warranty.
Take precautions to ensure
system cleanliness when
removing and reinstalling
system lines.
5. Stop the prime mover, remove the pressure gauges, and return the system to its
normal operating confguration.
-
7/27/2019 45 Series F Frame Service Manual (11005158 Rev AB Sept 2007)
22/28
11005158 Rev. AB September 2007
Series 45 Frame F Open Circuit Axial Piston Pumps
Service Manual
Adjustments
ls ContRol
1. Install a pressure gauge in port M2
to measure system pressure. Install
a pressure gauge in drain port L1 or
L2 to measure case pressure. Tee-in
a gauge to the LS / remote PC signal
line (port X).C
2. Start the prime mover and allow uid
to reach normal operating temperature.
Slowly operate a hydraulic unctionthat will demand approximately hal
ow rom the pump, but keep system
pressure below the PC set point.
3. Loosen the LS set screw. While
watching the pressure gauges,
turn the LS adjusting plug until the
desired pressure dierential between
port M2 and port X is achieved.
Clockwise rotation increases
the setting, counterclockwise
rotation decreases it; approximate
gain = 17 bar [250 psi] per turn.
4. While holding the position o the
LS adjusting plug, torque the LS set
screw to 9 Nm [7 lbt].
5. Operate a hydraulic unction to its
ull extension loading the pump at
maximum pressure and zero ow.
6. Loosen the PC set screw and turn the
PC adjusting plug until the pressure
WarningEscaping hydraulic uid
under pressure can
have sufcient orce
to penetrate your skin
causing serious injury
and/or inection. Relieve
pressure in the system
beore removing hoses,
fttings, gauges, or
components.
Unintended movement o
the machine or mechanism
may cause injury to the
technician or bystanders.
To protect against
unintended movement,
secure the machine or
disable / disconnect
the mechanism while
servicing.
LS control adjustment
ad p, cr, d
c h
CautionContamination can
damage internal
components and void the
manuacturers warranty.
Take precautions to ensure
system cleanliness when
removing and reinstalling
system lines.
gauge at port M1 or M2 indicates the desired setting . Clockwise rotation increasespressure, counterclockwise rotation decreases it; approximate gain = 42 bar [610 psi]
per turn.
7. While holding the position o the PC adjusting plug, torque the PC set screw to
9 Nm [7 lbt].
8. Stop the prime mover, remove the pressure gauges, and return the system to its
normal operating confguration.
The LS setting is indicated in the pump model code. Reer to the Series 45 Frame F Open
Circuit Axial Piston Pumps Technical Inormation Manual,50l098, or more inormation.
Beore perorming adjustments, read page 15, Pressure measurement.
I the pressure does not
increase, an externalsystem relie valve may
require adjustment.
External system relie
valve must be set above
the PC setting or proper
operation.
1 The LS setting is a dierential pressure. Subtract pilot pressure at port X rom system pressure at port M2 to
compute the actual setting. PC setting is reerenced to case pressure. Subtract case pressure rom system pressure to compute the actual
setting.
Gauge port M2
0 - 300 bar [0 - 4351 psi]
3/16 in
7/16-20
50 Nm
[37 lbfft]
Case drain port L1
0 - 10 bar [0 - 145 psi]
3/8 in
7/8-14
90 Nm
[67 lbfft]LS set screw
4 mm9 Nm
[7 lbfft]
P106 264E
X Port
0-300 bar
[0-5000 psi]
3/16 in
7/16-20
20 Nm
[51 lbfft]
-
7/27/2019 45 Series F Frame Service Manual (11005158 Rev AB Sept 2007)
23/28
11005158 Rev. AB September 2007
Series 45 Frame F Open Circuit Axial Piston Pumps
Service Manual
Minor repair
sHat seal
RePlaCement
The Series 45 open circuit variable pumps use a lip-type shat seal. You can replace this
seal without major disassembly o the unit. Replacing the shat seal requires removing
the pump rom the machine.
CautionPremature bearing ailure
can result i the shat seal
contacts the shat bearing.
Press the seal into the
housing only ar enough
to clear the retaining ring
groove.
R
1. Using the appropriate snap-ring
pliers, remove the retaining ring
(K010) rom the housing.
2. Remove the shat seal (K020) rom
the bore in the pump housing and
discard. C
Puncture the ace o the seal with a
packing hook, or use a slide-hammertype puller to remove the seal.
i
3. Inspect the pump housing and new
seal or damage. Inspect the sealing
area on the shat or rust, wear, or
contamination. Polish the sealing
area on the shat i necessary.
4. Lubricate the lip o the new shat
seal with clean hydraulic uid.
Shat seal and retaining ring
Place a protective sleeve over the shat end to prevent damage to the seal during
installation.
5. Keeping the seal perpendicular to the shat, press the new seal into the housing just
ar enough to clear the retaining ring groove. Install seal with the cupped sidetoward the shat bearing. Do not damage the seal during installation.
6. Using the appropriate snap ring pliers, install the seal retaining ring.
7. Remove the installation sleeve.
K020
K010
E101 254
C CautionDont damage the pump
housing or shat.
-
7/27/2019 45 Series F Frame Service Manual (11005158 Rev AB Sept 2007)
24/28
11005158 Rev. AB September 2007
Series 45 Frame F Open Circuit Axial Piston Pumps
Service Manual
Minor repair
auxiliaRy PaDs You may install auxiliary mounting pads on pumps equipped with through-drive radial
ported end caps. Follow these steps to either remove, replace, or exchange auxiliary
mounting pads.
R
1. Remove the screws (J130), retaining the cover plate (J110) or auxiliary pump (not
shown). Remove the shipping cover or auxiliary pump and its seal (J120).
2. Remove the drive coupling (J140) i present.
3. Remove the 4 screws (J100) retaining the pad adapter (J080) to the endcap. Discard
the pad adapter O-ring (J090) i present.
i
4. Lubricate new O-ring (J090) with petroleum jelly. Install the pad adapter to theendcap.
5. Install the 4 screws (J100 ) and torque to 55 Nm [40 lbt].
6. Install the drive coupling (J140) i present.
7. Install shipping cover or auxiliary pump with seal (J120).
8. Install the screws (J130) and torque to 105 Nm [77 lbt].
CautionShipping cover is intended
only to retain coupling
during shipment and
storage. Do not operate
pump with coupling and
shipping cover installed. Auxiliary mounting pads
J095
J140
J080J120
J110
J080
J140
J095
J110
J120
P106 267E
J080
J100
J120
J110
J130
J140
J095
J130
J100
105 Nm
[77 lbfft]
55 Nm[40 lbfft]
105 Nm
[77 lbfft]
-
7/27/2019 45 Series F Frame Service Manual (11005158 Rev AB Sept 2007)
25/28
511005158 Rev. AB September 2007
Series 45 Frame F Open Circuit Axial Piston Pumps
Service Manual
Minor repair
ContRol Control assembly
ls cr h; pr C10 hrh C10 d
C11 hrh C118 r d PC cr
D
1. Remove the 4 screws (C300) holding
the control housing onto the endcap.
2. Remove the control and discard the
4 interace O-rings (C200).
3. Remove the PC set screw (C102),
PC adjusting plug (C138), O-ring
(C138A), springs (C134, C135), and
seat (C133). Discard the O-ring.
4. Remove the plug (C103), O-ring
(C103A), and PC spool (C132) rom
the control housing. Discard theO-ring. Note orientation o the spool
or reassembly.
For PC only controls, skip steps 5
through 7
5. Remove the plug (C105) and O-ring
(C105A), or the plug (C106) and
O-ring (C106A). Discard the O-ring
(C105A or C106A).
6. Remove the LS set screw (C102),
LS adjusting plug (C118), O-ring
(C118A), back-up rings (C118B),
springs (C114, C115), and seat (C113).
Discard the O-ring and backup rings.
7. Remove the plug (C104), O-ring
(C104A), and LS spool (C112) rom the control housing; discard the O-ring. Note
orientation o the spool or reassembly.
ipc
8. Inspect the adjusting plugs or wear at the tips and where they contact the seat;
replace as necessary.
9. Inspect the springs and spring guides or wear or damage; replace as necessary.
10. Careully inspect the spools. Ensure the sealing lands are ree o nicks and scratches.
Check the ends that contact the spring guides or wear. Replace spools as necessary.
11. Inspect the control housing or damage. Check the spool bores or excessive wear.
12. Clean all parts and lubricate spools, springs, guides, and new O-rings with clean
hydraulic uid.
12 Nm
[9 lbfft]
12 Nm
[9 lbfft]
12 Nm
[9 lbfft]
6 Nm
[5 lbfft]
12 Nm
[9 lbfft]
9 Nm
[7 lbfft]
-
7/27/2019 45 Series F Frame Service Manual (11005158 Rev AB Sept 2007)
26/28
11005158 Rev. AB September 2007
Series 45 Frame F Open Circuit Axial Piston Pumps
Service Manual
Minor repair
12 Nm
[9 lbfft]
12 Nm
[9 lbfft]
12 Nm
[9 lbfft]
6 Nm
[5 lbfft]
12 Nm
[9 lbfft]
9 Nm
[7 lbfft]
Control assembly
ls cr h; pr C10 hrh C10 d
C11 hrh C118 r d PC cr
R
13. Install the PC spool (C132), spherical
end frst, into the PC bore. Using anew O-ring (C103A), install the plug
(C103). Torque the plug (C103) to
12 Nm [9 lbt].
14. Place the two PC springs (C134,
C135) onto the spring guide (C133)
and install into the PC bore. Place
a new O-ring (C138A) onto the PC
adjusting screw and thread it into
the PC bore until ush, then make
another ull turn. Install and torque
the PC set screw (C102) to 9 Nm[7 lbt].
For PC only controls, skip steps 15
through 17.
15. Install the LS spool (C112), spherical
end frst, into the LS bore. Using a
new O-ring (C105A or C106A), install
the plug (C105 or C106). Torque
the plug (C105 or C106) to 12 Nm
[9 lbt].
16. Using a new O-ring (C104A), install
the plug (C104). Torque the plug to
12 Nm [9 lbt].
17. Place the two LS springs (C114, C115)
onto the spring guide (C113) and
install into the LS bore. Place a new
O-ring (C118A) and back-up rings
(C118B) onto the LS adjusting screw
and thread it into the LS bore until ush, then make another ull turn. Install and
torque the LS set screw (C102) to 9 Nm [7 lbt].
18. Using petroleum jelly to retain them, install 4 new interace O-rings (C200) in therecesses on the control housing.
19. Install the control assembly onto the endcap using the 4 screws (C300). Torque the
screws to 6 Nm [5 lbt]. Torque screws in a criss-cross pattern and re-torque the frst
screw to ensure proper torque retention.
20. Check and adjust the control setting. SeeAdjustments, page 21.
ContRol
(cd)
-
7/27/2019 45 Series F Frame Service Manual (11005158 Rev AB Sept 2007)
27/28
11005158 Rev. AB September 2007
Series 45 Frame F Open Circuit Axial Piston Pumps
Service Manual
Minor repair
Plug anD itting sizes
anD toRques
I any plugs or fttings are removed rom the unit during service, install and torque as
indicated here. This drawing is a composite. Individual pump confgurations may be
dierent. The illustration below shows the appropriate wrench size and torque or plugsthat may be installed in the pump:
120 Nm
[155 lbfft]
12 Nm
[9 lbfft]
Plug locations, sizes, and torques
-
7/27/2019 45 Series F Frame Service Manual (11005158 Rev AB Sept 2007)
28/28
ouR PRoDuCts
Hydrostatic transmissions
Hydraulic power steering
Electric power steering
Electrohydraulic power steering
Closed and open circuit axial pistonpumps and motors
Gear pumps and motors
Bent axis motors
Orbital motors
Transit mixer drives
Planetary compact gears
Proportional valves
Directional spool valves
Cartridge valves
Hydraulic integrated circuits
Hydrostatic transaxles
Integrated systems
Fan drive systems
Electrohydraulics
Microcontrollers and sotware
Electric motors and inverters
Joysticks and control handlesDisplays
Sensors
sr-D m Pr d Cr s
mrk ldr wrdd
Sauer-Danoss is a comprehensive supplier providing complete
systems to the global mobile market.
Sauer-Danoss serves markets such as agriculture, construction, road
building, material handling, municipal, orestry, tur care, and manyothers.
We oer our customers optimum solutions or their needs and
develop new products and systems in close cooperation and
partnership with them.
Sauer-Danoss specializes in integrating a ull range o system
components to provide vehicle designers with the most advanced
total system design.
Sauer-Danoss provides comprehensive worldwide service or its
products through an extensive network o Global Service Partners
strategically located in all parts o the world.
Local address:
Sauer-Danoss (US) Company
2800 East 13th Street
Ames, IA 50010, USA
Phone: +1 515 239-6000
Fax: +1 515 239-6618
Sauer-Danoss ApS
DK-6430 Nordborg, Denmark
Phone: +45 7488 4444
Fax: +45 7488 4400
Sauer-Danoss-Daikin LTD
Sannomiya Grand Bldg. 8F
2-2-21 Isogami-dori, Chuo-ku
Kobe, Hyogo 651-0086, Japan
Phone: +81 78 231 5001
Fax: +81 78 231 5004
Sauer-Danoss GmbH & Co. OHG
Postach 2460, D-24531 Neumnster
Krokamp 35, D-24539 Neumnster, Germany
Phone: +49 4321 871-0
Fax: +49 4321 871 122