Christoph ReinhartL11 Occupant Behavior + Electric Lighting
4.401/4.464 Environmental Technologies in Buildings
Massachusetts Institute of TechnologyDepartment of ArchitectureBuilding Technology Program
Party Mode in the BT Lab
1
![Page 2: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/2.jpg)
Assignment 3 – Thermal Comfort
You were comfortable and the standard…
Predicted Mean Vote
Adaptive Comfort
Agreed √
Disagreed ×
Agreed √
Disagreed ×
74% 88%
26% 12%
Photo courtesy of Rick on Flickr. License: CC BY-NC-SA.
2
![Page 3: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/3.jpg)
Assignment 3 – Thermal Comfort You were uncomfortable and the standard…
Predicted Mean Vote
Adaptive Comfort
Agreed √
Disagreed ×
Agreed √
Disagreed ×
76% 24%
24% 76%
Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors such as noise, poor daylight, and low indoor air quality could influence perception of
thermal comfort. Thermal history: The climate of the previous city you lived in may set your thermal expectations.
Photo courtesy of Steven Leckart on Flickr. License: CC BY-NC.
3
![Page 4: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/4.jpg)
Lighting Module Light and Human Vision Daylighting Design Principles Daylight Simulations & Metrics Visual Comfort Electric Lighting
√√√√√
4
![Page 5: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/5.jpg)
Occupant Behavior
5
![Page 6: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/6.jpg)
Framework for High-Performance Buildings
Visual Comfort
Daylight Availability
Energy
Occupant BehaviorControls
6
![Page 7: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/7.jpg)
Occupant Behavior
Occupant use of lighting and shading controls matters. Priority one: switch lights off when nobody is present.
7
![Page 8: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/8.jpg)
Earth at Night
Photo courtesy of NASA. This image is in the public domain.
Nearly all the light that you see here does not serve any purpose.8
![Page 9: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/9.jpg)
Blind & Lighting Use in NYC Classrooms
Image removed due to copyright restrictions.
183 teacher surveys, 9 participating schools9
![Page 10: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/10.jpg)
Blind & Lighting Use in NYC Classrooms
183 teacher surveys, 9 participating schools
Image removed due to copyright restrictions.
10
![Page 11: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/11.jpg)
Monitoring User Behavior
Paper: Reinhart C F, Voss K, “Monitoring manual control of electric lighting and blinds.” Lighting Research & Technology 35:3, pp. 243-260,2003.
11
![Page 12: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/12.jpg)
HOBO data logger
IlluminanceTemperature
occupancy
Monitoring Setup in the Offices
12
![Page 13: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/13.jpg)
receiver2414.5 MHz
data acquisitionEIB systemBlind setting
video surveillance camera
Monitoring Blind Usage
13
![Page 14: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/14.jpg)
Switch-on Probability
Electric lighting tends to get switched on when occupants arrive.14
![Page 15: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/15.jpg)
People are Consistent but Different
Two main behavior types, active and passive.15
![Page 16: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/16.jpg)
Switch-On Probability
Surprising consistency at the building level.16
![Page 17: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/17.jpg)
Behavioral patterns can change in the presence of automated controls
Switch-Off Probability
17
![Page 18: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/18.jpg)
Intermediate Switch-On Probability
18
![Page 19: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/19.jpg)
annual occupancyprofiles
annual illuminanceprofiles
Lightswitch 2002
Lightswitch Algorithm(stochastic)
el. lighting/blinds profile
Model Overview
Paper: Reinhart C F, "Lightswitch 2002: A model for manual control of electric lighting and blinds," Solar Energy 77:1, pp. 15-28, 200419
![Page 20: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/20.jpg)
Lightswitch - Manual Lighting Control
20
![Page 21: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/21.jpg)
Manual Blind Control
Occupants tend to avoid direct sunlight stripes like this near the work place.
Photo courtesy of Mathias Wambsganss. Used with permission.
21
![Page 22: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/22.jpg)
Manual Blind Control
Blinds get lowered to avoid direct sunlight falling on the work plane.22
![Page 23: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/23.jpg)
Lightswitch - Manual Blind Control
23
![Page 24: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/24.jpg)
Lightswitch - Manual Blind Control
Define work plane sensors that define where the occupants are usually located.Associate sensors with shading groups. A shading group consists of a (set of) blinds that are opened and loweredat the same time.Check when direct sunlight (>50 Wm-2) is incident on a work plan sensor.Close shading device if yes until occupant is away for more than an hour.
24
![Page 25: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/25.jpg)
Dashboard Reference Office
25
![Page 26: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/26.jpg)
Electric Lighting Design
26
![Page 27: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/27.jpg)
Energy Use in Commercial Buildings
In 2014 11% of total U.S. electricity consumption was used for lighting by the residential and commercial sectors. In residential buildings lighting contributed to 14% of total electricity consumption. In the commercial sector (commercial and institutional buildings, public street and highway lighting) the portion was 19%
27
![Page 28: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/28.jpg)
Lighting Design and LEED
• ASHRAE 90.1: The art of lighting is reduced to lighting powerdensities (LPD) and power adjustment factors.
• Very simplistic. What actually matters isActivation Time x LPD
ASHARE/IESNA Standard 90.1
occupancy sensor
28
![Page 29: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/29.jpg)
Light Sources & Fixtures
29
![Page 30: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/30.jpg)
Light Direction
Light travels in a straight line…radiates out from the source
Image by MIT OpenCourseWare.
30
![Page 31: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/31.jpg)
Light Direction of Clear Lamps
Light travels in a straight line…radiates out from the source…. add a clear enclosure or envelope around the source, the light will still travel in a straight line.
31 Image by MIT OpenCourseWare.
![Page 32: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/32.jpg)
Light Direction of Frosted Lamps
Light travels in a straight line…radiates out from the source
…. add a coated or frosted enclosure or envelope around the source, the direction of light will bend and radiate from the surface of the enclosure
32 Image by MIT OpenCourseWare.
![Page 33: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/33.jpg)
Reflector Contours
CircularSpecular
Rays diverge through light source
Reflector
33 Image by MIT OpenCourseWare.
![Page 34: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/34.jpg)
Reflector Contours
Parabolic
Specular
Rays parallel
Parabola
Reflector
Slide courtesy of Conor Sampson.Image by MIT OpenCourseWare.34
![Page 35: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/35.jpg)
Reflector Contours
EllipsoidalSpecularRays converge
2 foci
Reflector
Slide courtesy of Conor Sampson.Image by MIT OpenCourseWare.35
![Page 36: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/36.jpg)
Lamps for General Use
36
![Page 37: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/37.jpg)
The higher the color temperature (CCT), the “cooler”
the color of the lamp is in appearance.
The lower the color temperature (CCT) the “warmer”
the color the lamp is in appearance.
This color temperature is measured in Kelvin.
Lamp Criteria: Color Temperature
37
![Page 38: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/38.jpg)
Kelvin Range 3000K 3500K 4100K 5000K
Associated Effects and Moods
Friendly Intimate Personal Exclusive
Friendly Inviting Non-threatening
Neat Clean
Efficient
Bright Alert Exacting
coloration
Appropriate Applications
Restaurants Hotels Lobbies Boutiques
Libraries Office areas Retail stores
Public reception areas Showrooms
Bookstores Office areas
Office areas Conference rooms Classrooms Mass merchandisers
Hospitals
Galleries Museums Jewelry stores
Medical examination areas Printing
companies
COLOR
TEMPERATURE WARM NEUTRAL COOL DAYLIGHT
Correlated Color Temperature
North sky light >10,000 K
Image by MIT OpenCourseWare.
38
![Page 39: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/39.jpg)
Standard Incandescent Lamps
Varied wattages, sizes, shapes, and bases Finishes: clear, inside frosted, coated Economical Short lamp life Warm light Can be dimmed
39
![Page 40: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/40.jpg)
Halogen Lamps (also Incandescent)
Varied wattages, sizes, shapes, and bases Finishes: clear, inside frosted, coated Small sources – Ideal for controlled optics Often low voltage and require transformers White light Can be dimmed
40
![Page 41: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/41.jpg)
Fluorescent Lamp Design
Rapid start and starter switch fluorescent bulbs have two pins that slide against two contact points in an electrical circuit.
Image by MIT OpenCourseWare.
41
![Page 42: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/42.jpg)
Ballasts perform three main functions: They start the lamp. They take the line voltage (120/240/277/480) and step it up or down as required by the
lamp. They make sure that the lamp operates in stable mode by regulating the current.
Ballasts can be electromagnetic (heavy coils) or electronic (lightweight and high frequency).
The Uniqueness Rule Ballasts are made specifically for the lamp they are designed to operate. You cannot simply replace a lamp
with a different type without changing the ballast. Since it regulates the voltage it is designed for a specificlamp type and wattage.
Ballasts
42
![Page 43: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/43.jpg)
Fluorescent Lamps
Varied wattages, sizes, shapes, and bases Finishes: Coated only – coating determines color Operates with specific ballast Long life Cool burning Dimming: Yes, with dimming ballast and specific dimmers
43
![Page 44: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/44.jpg)
Spectral Intensity of Various Light Sources
44
![Page 45: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/45.jpg)
How LEDs Work
Slide courtesy of Conor Sampson.45
![Page 46: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/46.jpg)
LED Replacements for Incandescents
6W LED (~40W incandescent)$10 per bulbLifetime: 25,000 hours
46
![Page 47: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/47.jpg)
Electric Lighting Design
47
![Page 48: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/48.jpg)
Lighting Design Step 1
48
![Page 49: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/49.jpg)
Lighting Design Step 2
49
![Page 50: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/50.jpg)
Lighting Design Step 3
50
![Page 51: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/51.jpg)
Related Tutorial
• DIVA RH 05: Electric Lighting
51
![Page 52: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/52.jpg)
Lighting Controls
52
![Page 53: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/53.jpg)
Framework for High-Performance Buildings
Visual Comfort
Daylight Availability
Energy
Occupant BehaviorControls
53
![Page 54: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/54.jpg)
Electric Lighting Energy Use = LPD x Time Activated
54
![Page 55: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/55.jpg)
Manual, automated, and automated with manual override
Bi-level switching
Manual dimming
Photocell–controlled on/off
Photocell–controlled dimming
Occupancy sensors
Overview of Traditional Lighting Controls
55
![Page 56: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/56.jpg)
To tailor lighting conditions to occupant’s changing need.
To raise occupant satisfaction.
To save energy.
Why Lighting Controls?
56
![Page 57: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/57.jpg)
Ceiling mounted (classrooms, open offices)Wall mounted (small spaces, single offices)
Detecting Occupancy
57
![Page 58: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/58.jpg)
Photocell Controlled Dimming
fewer sensors less dependent on interior changes works well for top lighting or in the absence of
a shading device good solution for shared spaces (atria, retail,
open plan)
more sensors but more individualized considers blind setting suitable for private offices requires careful commissioning
58
![Page 59: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/59.jpg)
New York Times Headquarters
Architects: Renzo Piano, Fox & FowleResearch Project: Lawrence Berkeley National Laboratory
Photo courtesy of Eleanor Lee. Used with permission.
At the time (2001), the largest installation of automated lighting and dimming controls in North America. The size of theproject halved the price for electronic dimming ballasts.59
![Page 60: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/60.jpg)
Electric LightingReference Office
60
![Page 61: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/61.jpg)
Modern Smartphone-Based Lighting
A room like this has millions of different lighting settings.61
![Page 62: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/62.jpg)
Modern Smartphone-Based Lighting
We are typically reducing the number of settings to a handful.62
![Page 63: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/63.jpg)
Lighting Study
Evaluate occupant preference for different scenes on 13 dimensions.
Home screen One time survey
Is the current scene suitable for: sketching on paper informal presentation with slides coffee break brainstorming in a group programming/CAD or video editing on a computer formal presentation with slides creative task using a computer reading a magazine hand-craft informal phone conversation formal phone conversation study/memorization casual conversation with a friend (routine) email on computer
63
![Page 64: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/64.jpg)
Lighting Study
Using principal component analysis we are mapping/grouping individual survey results on two axes.
N Zhao, CF Reinhart and JA Paradiso, 2018, "Image-based perceptual analysis of lit environments," Lighting Research & Technology, first published July 19, 2018, https://doi.org/10.1177/1477153518786768
64
![Page 65: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/65.jpg)
Results for Multiple Users
65
![Page 66: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/66.jpg)
Democratic Map
66
![Page 67: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/67.jpg)
Example
The lighting preference maps are offered as a complement to traditional scene selectors. If no user is present who has defined his or her preferences, use the democratic map.
67
![Page 68: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/68.jpg)
Example
The lighting preference maps are offered as a complement to traditional scene selectors. If no user is present who has defined his or her preferences, use the democratic map. If a single user is present with a preference, use his or her individualized preference.
68
![Page 69: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/69.jpg)
Example
The lighting preference maps are offered as a complement to traditional scene selectors. If no user is present who has defined his or her preferences, use the democratic map. If a single user is present with a preference, use his or her individualized preference. Otherwise we combine the map for everybody in the room.
69
![Page 70: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/70.jpg)
Take your map with you…
People can take their preference with them without sharing their data unless needed.
Photo courtesy of Christopher on Flickr. License: CC BY-NC.
70
![Page 71: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/71.jpg)
Questions?
www.daylight1-2-3.com
www.daysim.com
71
![Page 72: 4.401/4.464 Environmental Technologies in Buildings · Applicability of the adaptive comfort standard is not valid in indoor spaces with active cooling. Other environmental factors](https://reader035.fdocuments.in/reader035/viewer/2022062918/5eddee8bad6a402d66692b7d/html5/thumbnails/72.jpg)