ME 425
Fans
Keith Elder, P.E.
![Page 2: 425-7-Fans 2006](https://reader031.fdocuments.in/reader031/viewer/2022030312/577ccd071a28ab9e788b4f0a/html5/thumbnails/2.jpg)
Fan Types
Fans are classified by the direction of air flow relative to the impeller
Axial FansAir flow is perpendicular to blade rotation
Centrifugal FansAir flow is in the same direction as impeller rotation
![Page 3: 425-7-Fans 2006](https://reader031.fdocuments.in/reader031/viewer/2022030312/577ccd071a28ab9e788b4f0a/html5/thumbnails/3.jpg)
Axial FansPropeller
Designed to move air from one enclosed space to another in a wide range of volumes at low pressures.
Tube-axialAn axial flow wheel in a cylinder which moves a wide range of air at medium pressures.
Vane-axialVane-axial fans have a set of air guide vanes mounted in the cylinder before or behind an airfoil-type wheel. They move air over a wide range of volumes and pressures.
![Page 4: 425-7-Fans 2006](https://reader031.fdocuments.in/reader031/viewer/2022030312/577ccd071a28ab9e788b4f0a/html5/thumbnails/4.jpg)
Axial Fan Characteristics
![Page 5: 425-7-Fans 2006](https://reader031.fdocuments.in/reader031/viewer/2022030312/577ccd071a28ab9e788b4f0a/html5/thumbnails/5.jpg)
Centrifugal FansDesigned to move air over a wide volume range. Static pressures can go up to 25 inches. Centrifugal fan wheels come in the following types:
AirfoilBackward InclinedRadialForward Curved
![Page 6: 425-7-Fans 2006](https://reader031.fdocuments.in/reader031/viewer/2022030312/577ccd071a28ab9e788b4f0a/html5/thumbnails/6.jpg)
Centrifugal Fan Characteristics
![Page 7: 425-7-Fans 2006](https://reader031.fdocuments.in/reader031/viewer/2022030312/577ccd071a28ab9e788b4f0a/html5/thumbnails/7.jpg)
Fan Horsepower
fan6359 ηxCFMxTPBHP =
6359CFMxTPAHP =
Where:ηfan= Fan EfficiencyAHP = Air HorsepowerBHP = Brake HorsepowerTP = Total Pressure, inches H2O
![Page 8: 425-7-Fans 2006](https://reader031.fdocuments.in/reader031/viewer/2022030312/577ccd071a28ab9e788b4f0a/html5/thumbnails/8.jpg)
Fan Laws
Fan Performance at different speeds from the manufacturer’s fan curve can be predicted using the fan laws.
C F MC F M
R P MR P M
e s s u r ee s s u r e
R P MR P M
B H PB H P
R P MR P M
2
1
2
1
2
1
2
1
2
2
1
2
1
3
=
=
=
P rP r
![Page 9: 425-7-Fans 2006](https://reader031.fdocuments.in/reader031/viewer/2022030312/577ccd071a28ab9e788b4f0a/html5/thumbnails/9.jpg)
Fan Law Problem
A fan has the following characteristics:5000 CFM1.25 inches static pressure782 RPM1.98 BHP
What RPM is necessary to increase the flow to 6,000 CFM?
What BHP is required?
![Page 10: 425-7-Fans 2006](https://reader031.fdocuments.in/reader031/viewer/2022030312/577ccd071a28ab9e788b4f0a/html5/thumbnails/10.jpg)
System Curve
Pressure(in. w.c.)
CFM
![Page 11: 425-7-Fans 2006](https://reader031.fdocuments.in/reader031/viewer/2022030312/577ccd071a28ab9e788b4f0a/html5/thumbnails/11.jpg)
Fan Curve
Pressure(in. w.c.)
CFM
![Page 12: 425-7-Fans 2006](https://reader031.fdocuments.in/reader031/viewer/2022030312/577ccd071a28ab9e788b4f0a/html5/thumbnails/12.jpg)
System Operating Point
Pressure(in. w.c.)
CFM
![Page 13: 425-7-Fans 2006](https://reader031.fdocuments.in/reader031/viewer/2022030312/577ccd071a28ab9e788b4f0a/html5/thumbnails/13.jpg)
Catalog Fan Curve
![Page 14: 425-7-Fans 2006](https://reader031.fdocuments.in/reader031/viewer/2022030312/577ccd071a28ab9e788b4f0a/html5/thumbnails/14.jpg)
Method of Obtaining Fan Curves
![Page 15: 425-7-Fans 2006](https://reader031.fdocuments.in/reader031/viewer/2022030312/577ccd071a28ab9e788b4f0a/html5/thumbnails/15.jpg)
System EffectFan data is based upon discharge conditions at the time of testing, including certain minimum. For low velocity systems, the effective duct length is 2 - 1/2 equivalent duct diameters
![Page 16: 425-7-Fans 2006](https://reader031.fdocuments.in/reader031/viewer/2022030312/577ccd071a28ab9e788b4f0a/html5/thumbnails/16.jpg)
System Effect
![Page 17: 425-7-Fans 2006](https://reader031.fdocuments.in/reader031/viewer/2022030312/577ccd071a28ab9e788b4f0a/html5/thumbnails/17.jpg)
System Surge
Occurs when system resistance and fan performance curves do not intersect at a distinct point but rather over a range of volumes and pressures. - Trane
![Page 18: 425-7-Fans 2006](https://reader031.fdocuments.in/reader031/viewer/2022030312/577ccd071a28ab9e788b4f0a/html5/thumbnails/18.jpg)
Fan Surge
Occurs near “block-tight” conditions when blade rotation is insufficient to overcome pressure difference between wheel center & discharge.
![Page 19: 425-7-Fans 2006](https://reader031.fdocuments.in/reader031/viewer/2022030312/577ccd071a28ab9e788b4f0a/html5/thumbnails/19.jpg)
Variable Flow Control Devices
Bypass circuitsDischarge DamperVariable inlet vanesVari-ConeEcono-ConeVariable Frequency Drive
![Page 20: 425-7-Fans 2006](https://reader031.fdocuments.in/reader031/viewer/2022030312/577ccd071a28ab9e788b4f0a/html5/thumbnails/20.jpg)
Inlet/Discharge Control Schemes
![Page 21: 425-7-Fans 2006](https://reader031.fdocuments.in/reader031/viewer/2022030312/577ccd071a28ab9e788b4f0a/html5/thumbnails/21.jpg)
VAV Control Performance
![Page 22: 425-7-Fans 2006](https://reader031.fdocuments.in/reader031/viewer/2022030312/577ccd071a28ab9e788b4f0a/html5/thumbnails/22.jpg)
Variable Flow Device Performance
100
80
60
40
20
00 20 40 60 80 100
Variable Frequency Motor Control
Variable Speed Drive (Mechanical)
Inlet Vane Control
Discharge Damper
Bypass Circuit
%BHP
% CFM
![Page 23: 425-7-Fans 2006](https://reader031.fdocuments.in/reader031/viewer/2022030312/577ccd071a28ab9e788b4f0a/html5/thumbnails/23.jpg)
Discharge System Effect