PROPOSED MINI-SPLIT OUTDOOR UNIT
EXISTING SUPPLY DIFFUSER
MECHANICAL LEGEND
T
INDOOR UNIT REMOTE THERMOSTAT
MOUNTED @48" A.F.F.
EXISTING RETURN GRILLE
OU-1
IU-1 PROPOSED MINI-SPLIT INDOOR UNIT
UNIT
NO.
OU-1
MINI SPLIT SYSTEM AIR CONDITIONER SCHEDULE
MANUF.
NO.
CLM1972*
OUTDOOR BTU'S
19,000
VOLTAGE
230
HxWxD DIMENSIONS
29-1/8" x 35-1/2" x 12-5/8"
CONNECTION
LIQUID
(3) 1/4"
CONNECTION
SUCTION
(3) 3/8" (1) 1/2"
UNIT
NO.
IU-1
MINI SPLIT SYSTEM AIR CONDITIONER SCHEDULE
MANUF.
NO.
KMS1272
INDOOR BTU'S
12,000
VOLTAGE
230
HxWxD DIMENSIONS
11-1/4" x 32-1/2" x 7-1/2"
CONNECTION
LIQUID
1/4"
CONNECTION
SUCTION
3/8"
IU-2 KMS07727,000
230 11-1/4" x 32-1/2" x 7-1/2" 1/4" 3/8"
OUTDOOR UNIT
INDOOR UNIT
* INDICATES LOW AMBIENT OPERATION OUTDOOR UNIT
-SANYO SPLIT SYSTEM FLEXI-MULTI AIR CONDITIONERS 16 S.E.E.R.
TRAINING
CENTER
RESOURCE
OPERATIONS
DIRECTOR
FILES
DISPATCH
SUPERVISOR
DISPATCH
ROADS
SUPERVISOR
ROADS
SUPERVISOR
ROADS
SUPERVISOR
TICKETS
E F
OU-1
8" MIN.
IU
-1
IU
-2
INDOOR
UNIT-BOTTOM
MOUNTED AT
9'-0" A.F.F.
1'-4" x 6" x 6" SOLID CONCRETE
BLOCK-ANCHOR LEGS OF UNIT TO
CONCRETE BLOCK AND ANCHOR
CONCRETE BLOCK TO GROUND
NOTE: INDOOR UNIT (IU) TO BE
MOUNTED SO UNIT AIR FLOW
IS NOT OBSTRUCTED BY
EXISTING CORNER MOUNTED
42" LCD MONITORS
ELECTRICAL AND
REFRIGERANT LINE
SETS-MAXIMUM RUN 82'
EXISTING
PLENUM
RETURN TO
REMAIN
EXISTING
135 CFM
SUPPLY
DIFFUSER TO
REMAIN
EXISTING 75 CFM SUPPLY
DIFFUSER TO REMAIN
CONDENSATE DRAIN LINE FROM IU
EVAPORATOR COILS TO SPLASH BLOCK
14(RJ)
OU-1 ELECTRIC
DISCONNECT SWITCH
POWER SOURCE
60 HZ
SINGLE PHASE
230/208 VAC
AWG #12-MAX 85FT
CIRCUIT CAPACITY 20A
NEW CONCRETE
SPLASH BLOCK
8" MIN.
OUTSIDE UNIT (OU) INSTALLED PER
MANUFACTURERS SPECIFICATIONS
T T
EXISTING
POWER
PANEL
(RJ)
INSTALLATION OF ALL EQUIPMENT AND THEIR ACCESSORIES SHALL BE PER MANUFACTURER'S
9.
21.
19.
18.
20.
PUBLISHED RECOMMENDATIONS.
13.
17.
14.
16.
15.
12.
11.
10.
8.
7.
5.
6.
4.
MECHANICAL NOTES
3.
1.
2.
ALL SPECIFICATIONS AND DRAWINGS (ie - ARCHITECTURAL, STRUCTURAL, MECHANICAL, PLUMBING,
ELECTRICAL AND FIRE PROTECTION) ARE COMPLIMENTARY AND MUST BE USED IN COMBINATION
TO OBTAIN COMPLETE CONSTRUCTION INFORMATION.
ANY CONFLICTS WITHIN THE SPECIFICATIONS OR BETWEEN THE SPECIFICATIONS AND DRAWINGS
SHALL BE BROUGHT TO THE ARCHITECT'S ATTENTION. THE CONTRACTOR SHALL NOT PROCEED WITH
ANY WORK UNTIL ALL CONFLICTS ARE RESOLVED AND THE CLARIFYING INFORMATION IS ISSUED TO
THE CONTRACTOR BY THE ARCHITECT.
ALL CUTTING, DRILLING AND PATCHING OF WALLS, FLOORS OR STRUCTURAL MEMBERS FOR THE
INSTALLATION OF THE MECHANICAL AND/OR PLUMBING SYSTEMS SHALL BE PROVIDED BY THE
MECHANICAL OR PLUMBING CONTRACTORS. STRUCTURAL COMPONENTS SHALL NOT BE CUT,
DRILLED OR MODIFIED IN ANY WAY WITHOUT THE STRUCTURAL ENGINEER'S REVIEW AND PRIOR
WRITTEN APPROVAL.
ALL PIPING SHALL BE INSTALLED ABOVE CEILING OR IN CONCEALED SPACE UNLESS NOTED OR
INDICATED OTHERWISE. COORDINATE WITH THE ARCHITECTURAL DRAWINGS/REQUIREMENTS.
THESE DRAWINGS ARE SCHEMATIC AND ARE INTENDED TO CONVEY A FUNCTIONAL HVAC SYSTEM
AND TO DEPICT THE GENERAL LOCATION OF THE HVAC SYSTEM COMPONENTS.
CONTRACTOR SHALL EXAMINE THE CONTRACT DOCUMENTS AND FAMILIARIZE HIMSELF WITH ALL THE
REQUIREMENTS OF THE PROJECT AND SHALL NOTIFY THE ARCHITECT OF ANY OBSERVED FAULTS
AND/OR AMBIGUITY IN THE CONTRACT DOCUMENTS SO THAT THE MATTER MAY BE RESOLVED PRIOR
TO SUBMISSION OF BIDS.
BY SUBMISSION OF BID THE CONTRACTOR SHALL ACKNOWLEDGE ACCEPTANCE OF THE CONTRACT
DOCUMENTS AS AN ADEQUATE DEFINITION OF THE SCOPE OF THE WORK, AND EXTRA COST CLAIMS
BASED ON INADEQUACY OF DOCUMENTS SHALL NOT BE CONSIDERED.
THE CONTRACTOR SHALL COORDINATE THE INSTALLATION OF HVAC AND PLUMBING WORK WITH THE
WORK OF OTHER TRADES. MINOR DEVIATIONS FROM PLANS MAY BE MADE TO AVOID MINOR
CONFLICTS. WHEN MAJOR CONFLICTS ARE APPARENT, THE PROJECT MANAGER SHALL BE ADVISED
IMMEDIATELY AND AFFECTED WORK SHALL NOT PROCEED UNTIL THE CONFLICT HAS BEEN RESOLVED.
THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND LOCATIONS PRIOR TO PURCHASING AND
FABRICATION OF EQUIPMENT (ie - DUCTWORK, DIFFUSERS, ETC.)
CONTRACTOR SHALL VERIFY ALL VOLTAGE AND POWER REQUIREMENTS FOR ALL EQUIPMENT AND
COORDINATE WITH THE CONTRACT DRAWINGS PRIOR TO ISSUANCE OF SHOP DRAWINGS AND
PURCHASE OF EQUIPMENT.
ALL SYSTEMS SHALL BE CLEAN OF FOREIGN MATERIAL AND ROUGH SPOTS PRIOR TO BEING PLACED
IN SERVICE AND BEFORE OPERATIONAL TESTS ARE PERFORMED.
INSTALL U.L. APPROVED FIRE DAMPERS WHERE NECESSARY AS PER NFPA LOCAL CODES AND THE
MANUFACTURER'S RECOMMENDATIONS. PROVIDE ACCESS PANELS/DOORS TO FIRE DAMPERS AS
REQUIRED.
PROVIDE AIR TURNING DEVICES IN DUCTWORK AT ANY CHANGES IN DIRECTION.
ALL FLOOR MOUNTED EQUIPMENT SHALL BE INSTALLED ON VIBRATION ISOLATORS
IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO INSTALL THE HEATING, VENTILATION
AND AIR-CONDITIONING SYSTEM SO AS TO ENSURE QUIET OPERATION. NO VIBRATION OR SOUND
SHALL BE TRANSMITTED TO THE BUILDING OR STRUCTURE.
PROVIDE ACCESS DOORS AND/OR PANELS NECESSARY TO SERVICE ALL EQUIPMENT AND
ACCESSORIES THAT REQUIRE SERVICE AND/OR MAINTENANCE AND ARE LOCATED ABOVE
INACCESSIBLE CEILING OR WALLS. ACCESS DOOR SIZES SHALL PERMIT FULL ACCESSIBILITY TO
EQUIPMENT AND/OR ACCESSORIES, BUT NOT LESS THAN 18" x 18". ACCESS DOORS SHALL MATCH
THE WALL OR CEILING RATING AT THE LOCATION WHERE THEY ARE PLACED.
ALL WORK ON THIS PROJECT SHALL BE INSTALLED IN ACCORDANCE WITH APPLICABLE CODES
AND REGULATIONS.
WHERE DUCTWORK CROSSES STRUCTURAL BEAMS AND JOISTS CONTRACTOR SHALL EXAMINE
THE STRUCTURAL DRAWINGS AND COORDINATE LOCATION OF DUCTWORK WITH LOCATION OF
DUCT OPENINGS IN BEAMS AND JOISTS.
ALL REFRIGERANT PIPING SHALL BE CONNECTED TO RESPECTIVE AHU AND CU. DIAMETER AND
LENGTH OF RUN SHALL NOT EXCEED PER MANUFACTURER'S SPECIFICATIONS.
22.
ALL MECHANICAL SYSTEMS TO BE INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS CHECKLIST
FOUND IN THE APPROVED U.S. DEPARTMENT OF ENERGY MECHANICAL COMPLIANCE CERTIFICATE
PROVIDE AND INSTALL A OVERFLOW PAN UNDER EVERY AIR HANDLER. INSTALL FLOAT SWITCH IN EACH
OVERFLOW PAN THAT WILL SHUT DOWN CONDENSING UNIT WHEN OVERFLOW PAN FILLS WITH WATER
NOTES
CIRCUITING
EXISTING PANEL RJ
CKT FOR
SETS NO SIZE C
CB
P A
LOAD
KVA
1 REC: CALL CTR
3
5
7
9
11
13
15
17
19
21
23
25
27
29
1 0.72
0.72
1 2/1 12/12 3/4" 0.72
CKT FOR NOTES
CIRCUITING
SETS NO SIZE C
CB
P A
LOAD
KVA
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
1
1
20
20
20
1 2/1 12/12 3/4"
1 2/1 12/12 3/4"
V: 120/208
PH: 3
W: 4
AIC: 10K
a
b
c
a
b
c
a
b
c
a
b
c
a
b
c
-
REC: CALL CTR
REC: CALL CTR
1 2/1 12/12 3/4" 0.721 20REC: CALL CTR
1 2/1 12/12 3/4" 0.721 20REC: CALL CTR
1 2/1 12/12 3/4" 0.541 20REC: CALL CTR
- - - - 0.001 -SPACE
- - - - 0.001 -SPACE
- - - - 0.001 -SPACE
- - - - 0.001 -SPACE
- - - - 0.001 -SPACE
- - - - 0.001 -SPACE
- - - - 0.001 -SPACE
- - - - 0.001 -SPACE
- - - - 0.001 -SPACE - - - - 0.001 -SPACE
- - - - 0.001 -SPACE
- - - - 0.001 -SPACE
- - - - 0.001 -SPACE
- - - - 0.001 -SPACE
- - - - 0.001 -SPACE
- - - - 0.001 -SPACE
- - - - 0.001 --
1 2/1 12/12 3/4" 1.841 20HVAC: DISPATCH
SPARE: - - - - 0.001 20
SPARE: - - - - 0.001 20
SPARE: - - - - 0.001 20
REC: DISPATCH 1 0.72201 2/1 12/12 3/4"
REC: DISPATCH 1 0.90201 2/1 12/12 3/4"
REC: DISPATCH 1 0.72201 2/1 12/12 3/4"
DW
G. F
ILE
:
DR
AW
N B
Y:
DE
SIG
N B
Y:
IO
TT
P
RO
J. N
O.:
DA
TE
:
SC
ALE
:
ST
AG
E:
(410
) 749
-722
9
FAX
(410
) 749
-000
1
RE
VIS
IO
NS
RE
MA
RK
SD
AT
E N
O.
RE
MA
RK
SD
AT
E N
O.
I C
ER
TIF
Y T
HA
T T
HE
SE
DO
CU
ME
NT
S W
ER
E P
RE
PA
RE
D O
R
AP
PR
OV
ED
B
Y M
E A
D
ULY
LIC
EN
SE
D A
RC
HIT
EC
T U
ND
ER
T
HE
LA
WS
O
F T
HE
S
TA
TE
O
F
MA
RY
LA
ND
KE
IT
H IO
TT
:LIC
EN
SE
N
O: 8057
EX
PIR
AT
IO
N D
AT
E: 3/25/2016
09-035
KI
CO
NS
TR
UC
TIO
N
MA
R. 21, 2014
1
SCALE: 1/4" = 1'-0"
PARTIAL FIRST FLOOR PLAN - AREA "B" - MTA DISPATCH OFFICE AND DISPATCH SUPERVISOR
30
0
M
AS
N
OT
ED
RE
N.T.S.
MANUFACTURER INSTALLATION DETAILS