3M™ Novec 1230™ Model NFG & NFD Fire Suppression Systems Installation Instructions Owner’s Manual This manual is an integral part of the system approval and the suppression system must be installed and maintained in accordance with all listed requirements. FM approved (3045669) Read and comply with these instructions, warnings and limitations before installing. Suitable for use on: NFG 25-200 Models: 20°F (-7°C) to 130°F (54°C) NFD 225-825Models: 20°F (-7°C) to 130°F (54°C) NFD 850-1800 Models: 32°F (0°C) to 130°F (54°C) Always maintain this owner’s manual nearby for operator reference. Owner’s Manual PN: 123-456, Revision B Printed in the USA

Transcript of 3M™ Novec 1230™ Model NFG & NFD Fire Suppression Systems Installation Instructions ... · 2016....

  • 3M™Novec1230™

    ModelNFG&NFDFireSuppressionSystems

    InstallationInstructionsOwner’sManual

    Thismanualisanintegralpartofthesystemapprovalandthesuppressionsystemmustbeinstalledandmaintainedinaccordancewithalllistedrequirements.

    FMapproved(3045669)

    Readandcomplywiththeseinstructions,warningsandlimitationsbeforeinstalling.

    Suitableforuseon: NFG25-200Models: 20°F(-7°C)to130°F(54°C)NFD225-825Models: 20°F(-7°C)to130°F(54°C)NFD850-1800Models: 32°F(0°C)to130°F(54°C)

    Alwaysmaintainthisowner’smanualnearbyforoperatorreference.

    Owner’sManualPN:123-456,RevisionBPrintedintheUSA

  • PN:123-456,RevisionBPage2of28

    WARNINGCONCENTRATEDAGENTANDBY-PRODUCTOFAPPLICATIONTOFIREARETOXIC.AVOIDBREATHINGOFFUMESORPROLONGEDEXPOSURE.ACCIDENTALDISCHARGEDURINGHANDLINGORINSTALLATIONMAYCAUSESERIOUSINJURY.BEFOREATTEMPTINGTOINSTALLTHISDEVICE,READANDCOMPLYWITHINSTRUCTIONS,WARNINGS,ANDLIMITATIONSCONTAINEDINTHISMANUAL.DONOTLIFT,CARRYORHANDLEBYSENSORVALVE/DETECTOR.THESENSOR/VALVEDETECTORISVISUALLYDESCRIBEDINFIGURE8OFTHISMANUAL.DONOTDROP.KEEPAWAYFROMHEAT.KEEPAWAYFROMCHILDREN.AMATERIALSAFETYDATASHEET(MSDS)ISINCLUDEDINTHISMANUAL.

    WARNING

    PRIORTOPERFORMINGMAINTENANCEWITHINTHEPROTECTEDROOM,ALWAYSINSTALLTHESAFETYPININTOTHESUPPRESSIONSYSTEMTRIGGERASSEMBLYTOAVOIDACCIDENTALDISCHARGE.UPONCOMPLETIONOFMAINTENANCE,REMOVETHESAFETYPINFROMTRIGGERASSEMBLY,ANDSTORETHESAFETYPININTHEHOLEOFTHERELEASEBRACKETBEHINDTHEACTUATORLEVERASABACK-STOPINFARTHESTHOLEFROMCABLE/HOOKASSEMBLY.

    InstallationManualscurrentlyavailableinEnglish,German,Italian,andSpanish.Otherlanguagesavailablefromyourlocaldistributor.InstallationHandbüchermomentanverfügbaraufEnglisch,Deutsch,Italiener,undSpanisch.AndereSprachen,dieverfügbarsindvonIhremörtlichenVerteiler.

    Manualesdelainstalaciónactualmentedisponibleeninglés,alemán,italiano,yespañol.Otrosidiomasdisponiblesdesudistribuidorlocal.Manualidiinstallazioneattualmentedisponibileininglese,tedesco,italianoespagnolo.Lealtrelinguedisponibilidalsuodistributorelocale

  • PN:123-456,RevisionBPage3of28

    Index

    Section Page(s)Warnings InsideCoverApplication/Limitations 4SystemOperations 5SupervisoryPressureSwitch 5SystemStatusIndicatorLightOperation 6PressureReliefAssembly(BurstDisk) 6Interactionw/EnginesandHVACVentilation 6Installation 7-15CylinderandMountingBracket 7–9CableAssembly 9-14SystemStatusIndicatorLight 15SystemMaintenance/Inspection 16-18Cylinders 16-17AgentWeight 17PressureGauge 18IndicatorLight 18GlassBulb(TemperatureSensor/Detector) 18CableInspection 19AdditionalServicing 19SpecificationTables 19-21“NFG”AutomaticandManual/Automatic 19“NFD”AutomaticandManual/Automatic 20-21Warranty 22MSDS–Novec1230 23-27ContactInformation 28

  • PN:123-456,RevisionBPage4of28

    Application

    Novec1230TM(1,1,1,2,2,4,5,5,5-NONAFLUORO-4-(Trifluoromethyl)-3-Pentanone),theextinguishingagentusedinallFire-Hawk“NFG”and“NFD”seriesfiresuppressionsystems,isasuitableEPAacceptedalternatereplacementforHalon.Novecisanelectricallynonconductiveandresiduefreeextinguishingagentthatrequiresnocleanup.Novec1230TMisalsoreferredtoasFK-5-1-2(dodecaflouro-2-methylpentan-3-one),afluoroketone.

    Thesefeaturesandtheversatilityofdesignmakethe“NFG”and“NFD”seriesfiresuppressionsystemmodelsidealforabroadrangeofapplications.Theseapplicationswouldincludecommercialandindustrialusewhereelectricalorflammableliquidsarethelikelysourceoffire.Fire-Hawk“NFG”and“NFD”serieshavepassedarigidtestingprogramandcarryFactoryMutual(FMGlobal)approvalsforfiresuppressionapplicationsinmanyapplicationssuchasunoccupiedengineandgeneratorrooms,electricalandcomputerrooms,paintandflammablestoragelockers.

    Limitations

    Fire-Hawk“NFG”and“NFD”modelseriesNovecautomaticfiresuppressionsystemsaredesignedandtestedtoextinguishClassB(flammableliquid)firesinenclosedroomsonly.

    Theprotectedspace(room)limitationsare:MinimumHeight:2Feet(.6m)MaximumHeight:14FT(4.3m)MaximumWidth:32FT(9.75m)

    Anyopenings(doorsorpanels)willallowdischargingagenttoescapeandwillseriouslyaffecttheabilityofagenttoextinguishthefire.

    Fire-Hawk“NFG”and“NFD”suppressionsystemsaredesignedtoinduceaminimumatmosphericconcentrationof5.85percentwithintheprotectedroom.Thisisequivalenttoa30%safetyfactorona4.5%MinimumExtinguishingConcentration(MEC).Inadditiontogasolineanddieselfuel,otherflammableliquidswithMECvaluesequaltoorbelow4.5%forNovec1230TMmaybeprotectedbyFire-Hawk“NFG”and“NFD”systems.

    Thespecificationtablesinthismanuallisttheminimumandmaximumapprovedroomvolume(size)allowableforeachmodel(perNFPA2001,UL2166,FM5600*).Volumecanbedeterminedbymultiplyingtheroom’slengthxwidthxheightwhichequalsthevolumeincubicfeetormeters(LxWxH=V).*NFPA2001:StandardonCleanAgentFireExtinguishingSystems;UL2166:HalocarbonCleanAgentExtinguishingSystemUnits;FM5600:ApprovalStandardforCleanAgentExtinguishingSystemsModelsdescribedinthismanualarestockavailablein25CubicFeet(0.7Cubicmeters)intervals.Systemsareavailablein1CubicFeet(0.03Cubicmeters)intervalsifdesired.Exactcalculationsand/ormeasurementsoftheprotectedspaceshouldbeaccomplishediforderingthesemodels.TheSpecificationTableshowstheareaofprotectionrangeavailablefororderingwithineachbasicmodel.Forsimplicity,throughoutthismanual,onlythestocksizeswillbenoted.

    NFGandNFDsystemsaredesignedforonlyonecylinder(singlenozzle)toprotecttheentirespace.Usingtwocylinderstoachievecombinedcoverageisnotacceptable.

    CAUTION:NEVERINSTALLAUNITWITHAVOLUMERATINGLESSTHENTHEGROSSVOLUMEOFTHEROOMTOBEPROTECTED.DONOTDEDUCTFORENGINES,GENERATORS,REMOVABLETANKSOROTHEREQUIPMENT.

  • PN:123-456,RevisionBPage5of28

    Fire-HawkoffersallmodelscomplianttoapplicableEuropeanDirectives.Systemswillbeshippedasrequested.ForordersrequestedcomplianttoCEdirectives,aDeclarationofConformance(DOC)shallbeincluded.

    SystemOperations

    Fire-HawkunitsdescribedinthismanualareautomaticallyactuatedbyatemperaturesensitiveULlistedglassbulbtestedinaccordancewithUL199.Thesebulbsaremanufacturedandtestedtobeactivatedataminimumtemperatureofapproximately175°F(79°C)whenimmersedinaliquidbathorapproximately220°F(104°C)whentestedusinganairbath.Theactualactivationtemperatureofthebulbinafirescenarioisinfluencedbynumerousfactorsincludingairvelocity,rateoftemperaturerise,airflow,location,etc.Thedischargetemperatureranges(approximate)areshowninthespecificationtable,pages20–21,andonthelabelattachedtoeachunit.ThesesystemshavebeentestedtoUnitedStatesCoastGuard(USCG),UL2166andFM5600requirementsforAutomaticExtinguisherUnitAutomaticOperationFireTests.*UL199:StandardforSafetyofAutomaticSprinklersforFireProtectionService.DischargeTemperatureRanges(approximate):NFG25–75:200 - 250°F(93-121 °C)NFG100–200:175-225°F(79–107°C)NFD225–1800:175-225°F(79-107°C)

    CAUTION:INCASEOFSUPPRESSIONSYSTEMDISCHARGE,DONOTRUSHTOOPENTHEPROTECTEDROOM.THEPROTECTEDSPACEMUSTBEKEPTCLOSEDFORATLEAST15MINUTESTOALLOWTHEFIRETOBEEXTINGUISHEDANDSURFACESCOOLEDSUFFICIENTLYTOPREVENTREFLASH.STOPBLOWERSANDSECUREHATCHES.HAVEAPORTABLEEXTINGUISHERAVAILABLEANDUSECAREWHENOPENINGTHEROOM.

    Avoidbreathingfirerelatedfumesorvapor.

    Note:Itisimportanttoretainthedesignedvaporconcentrationwithintheroomtoinsurecompletefireoutage.Upondischarge,engines,generators,equipmentandallpoweredventilation(HVAC)mustbeshutdown.

    SupervisoryPressureSwitch

    Fire-Hawk“NFG”and“NFD”seriessuppressionsystemsareequippedwithafactoryinstalledpressureswitchwhichisintendedforcylinderpressuremonitoringandsupervisionandmayalsobeusedtocontrolotherelectricalfunctions(engineshutdown,airexchangeequipmentetc.).Whenusingthepressureswitchasanelectricaldisconnectforanyequipmentshutdownfunction,ameansofoverriding(bypassing,shunting)thepressureswitchmustbeprovidedinordertoreturntheaffectedequipmenttoanoperationalmodeaftersuppressionsystemdischargehasoccurred.Thepressureswitchisasinglepolesinglethrow(SPST)typethatisnormallyclosed(NC)withthesysteminthechargedcondition.Dischargeorlossofsystempressurewillreleasethecontactstoanopenstatetherebycuttingoffanyelectricalcurrentflow.Neverusepressureswitchforelectricalloadsoverratedcapacity.

    SwitchSpecifications 4.0AMPSat12VDC, 2.0AMPSat28VDCForapplicationsrequiringlargerloadcapacities,contactthefactory.

  • PN:123-456,RevisionBPage6of28

    SystemStatusIndicatorLightOperation

    AllFire-Hawkpre-engineeredfiresuppressionsystemsarepackagedwithanindicatorlightandfaceplate.Systemapprovalrequiresthattheindicatorlight(unlessreplacedbyanotherFire-Hawkdevice:i.e.:displaypanel)mustbeinstalledforsystemsupervisionandoperatorawareness.Whenproperlyinstalled,activationofelectricalpowertothesystemwillilluminatethelightindicatingnormalchargecondition.Systemdischargeorlossofpressurewillimmediatelyturnofftheindicatorlight.Intheeventthattheindicatorlightisnotlitwhenpowerisapplied,checkforthefollowingconditions:

    1. Checkpressureindicatorgaugeforproperrange.2. Checkfuseandindicatorlightandreplaceifdefective(lampreplacementsavailablefrom

    factory).3. Checkforlooseelectricalconnections.4. RemoveandweighsystemcylinderasdescribedinSystemMaintenanceSectionofthe

    manual.

    PressureReliefAssembly(BurstDisk)

    Allmodelsareprotectedfromoverpressureofsystem.NFGModels25–200andNFD225–825areprotectedbythedesignoftheglassbulbtemperature/pressurerelationship.Fire-HawkmaintainsaDepartmentofTransportation(DOT)SpecialPermit,DOT-SP-11598forthesemodels.

    NFDModels850–1800haveadefinitepurposePressureReliefDevice(designedandmanufacturedperCGAS.1-1)installedonthemanifold.Donotremoveorperformanymaintenanceonthisdevice.Removingorlooseningthisdevicewillcausethecontentsunderpressuretoescape.

    InteractionwithEngines,GeneratorsandPoweredVentilation(HVAC)

    Fire-Hawkoffersoptionalcircuitinterruptsystemswhichwillautomaticallyshutdownrelayswhichmaybeusedtocontroldevicessuchasengines,generatorsandpoweredventilation(HVAC)upondischargeofthefiresuppressionsystem.Theyareavailablewith4,6or8controlcircuitsandoperatebetween9–32voltsDC.Shutdownmaybeaccomplishedbyinterruptionoftheelectricalcircuitpoweringthedevice.Relaycontactsareprovidedinnormallyopen(NO)andnormallyclosed(NC)states.Itistheresponsibilityofthesystemdesigner/installertocomplywiththefollowinginstructionsonDieselandGasolineEngines/Generatorsthattakeinairfromtheroom.

    DieselEnginesorGenerators,PoweredVentilation(HVAC)

    Thesystemshallbedesignedandinstalledsothattheengine(s),generator(s),andventilationlocatedintheprotectedspaceshutdownautomaticallyandafterdischargetheminimumrequireddesignconcentration(5.85percentNovec1230)mustremain.

    GasolineEnginesorGeneratorsItisoptionaltoautomaticallyshutdowngasolineenginesandgenerators,butitishighlyrecommended.Inthecaseofengineroomfire,youmuststillmanuallyshutdownengine(s)orgenerator(s)beforeamanualdischarge,orimmediatelyafterautomaticdischargeofthefiresuppressionsystem.

    ManualDischargeCapability

    Modelswithmanualcableconnectionsaredesignatedas“M”followingthesystemsize.“M”designatesmanual/automatic.“A”alonedesignatesautomaticonly.

  • PN:123-456,RevisionBPage7of28

    InstallationReadentireinstructionmanualandcylindernameplatepriortoinstallation.Theseinstallationinstructionsareintendedtocovermostnormalinstallations.Additionaltechnicalorapplicationinformationcanbeobtainedbycontacting:

    Fire-Hawk–USAADivisionofGlobalTecSolutionsLLC

    Baltimore,MarylandTel:(410)202-2347

    Website:www.fire-hawksafety.comOnlyonesystem(cylinder)maybeusedtoprotectaroom.Ifmorethanonesuppressionsystemisusedtoachievetherequiredamountofagentconcentration,thereisnoguaranteethatseveralsuppressionsystemswillactuatesimultaneouslyaseachsuppressionsystemoperatesindependently.Severalsuppressionsystemsmaybeusedonlyifeachindependentsuppressionsystemiscapableofprotectingtheentirevolumeoftheroom.

    CAUTION:1. DONOTINSTALLINANAREADESIGNATEDFOROCCUPANCY.2. ACCIDENTALDISCHARGEMAYCAUSESERIOUSINJURY.3. HANDLETHECYLINDERWITHEXTREMECARE.4. WEAREYEPROTECTION.5. DONOTLIFTORCARRYCYLINDERBYTHEMANIFOLDORACTUATOR

    COMPONENTS.6. DONOTATTEMPTTOLOOSENORREMOVEANYSUPPRESSIONSYSTEM

    COMPONENTS.I.CylinderInstallation:Step1Carefullyremovecylinderfromcartonandvisuallycheckfordamageinshipment.Step2Toensurethatthecylinderisoperational,boththeweightandpressureindicatormust

    conformwiththecylinderspecificationasshownonthenameplate.Weighcylinder(lessbracket)onanaccuratecalibratedscalebeforeinstalling.Recorddateandweightontagprovidedforthispurpose.

    Step3Do’sandDon’ts

    DoplaceUnit: Don’tplaceunit:a. Ashighaspossible,nomorethan3feet

    belowtheceiling,onroomwalljoistorstudformounting.

    b. Withdetectorheadneartheareainwhichafireismostlikelytooccur.Thiswouldbeonthefuellinesideoftheengine,nearacarburetor,orfuelpump.

    c. Atthecenterlineoftheroomwall.d. Verticalorhorizontalasdescribedper

    model.e. Betweenthelikelyignitionsourceswhen

    twoormoresourcesaretobeprotected.f. Avoidimmediateobstructionstothe

    dischargeorifices.

    a. Nearafreshairorventilationductsupplyopening.

    b. Nearaccessdoor.c. Toundersideorinsideofaccessdooror

    panel.d. Extremelyclosetoahighheatgenerating

    deviceorexhaustsystem.e. Whereanaccumulationofstandingwater

    couldblocksensororcausecorrosion.f. Onundersideofcoverorroomhatchthat

    couldbethrownclearduetopossibleexplosion.

    g. Onaceiling.h. Tooclosetoaroomcornerorlarge

    obstruction.

  • PN:123-456,RevisionBPage8of28

    Step4Loosenmountingbracketcylinderholdingstraps(Figure1)andremovecylinderfromracket.

    Althoughthesensorvalve/detectorisprotected,careshouldbeexercisedtoavoidstrikingthesensorvalve/detector.

    Figure1

    WallMountingModelsNFG25-200andNFD225–NFD825maybeinstalledVerticalorhorizontalwiththefollowingangular/off-setlimitations.Verticalinstallationisrecommendedforoptimumperformance.Off-setisdefinedasthedistancebelowlevellinefromendofthebracket.Thedischargeorificespraypatternmustbeorientedawayfromthewallandtowardstheroom.SeeFigure2.

    ModelsNFG25-100• Verticalinstallation.• Horizontalwithaminimum8degreeangleor1”(25.4mm)offsetbelowlevel.

    ModelsNFG101-200• Verticalinstallation.• Horizontalwithaminimum5degreeangleor1/2”(12.7mm)offsetbelowlevel.Figure2

    MODELSNFD225THRU825• Verticalinstallation.• Horizontalwithaminimum2.5degreeangleor1/2”(12.7mm)offsetbelowlevel.

    MODELSNFD850–1800• VerticalInstallationOnly

  • PN:123-456,RevisionBPage9of28

    WARNING:WHENINSTALLINGCYLINDERINHORIZONTALPOSITION,THEACTUATOR(TOPOFCYLINDER)MUSTNEVERBELOWERTHANTHEBOTTOMOFTHECYLINDERORPROPERDISCHARGEOFAGENTWILLNOTOCCUR(SEEFIGURE2ABOVE).Step5Locatebracketindesiredposition(Vertical-sensorValve/DetectorHeadUp,orHorizontal,

    Figure2).Ensurewall,joistormountingsurfaceissolidenoughtoholdtheweightoftheunit.Fastenersarenotincluded.Usemediumstrength(Grade5,PropertyClass8.8)orbettergradematerial.Useminimum5/16”(M8)diameter[recommend3/8”(M10)diameter]fastenersforallbut130-249bracketassemblies.130-249minimumhardwaresizeis¼”(M6)diameter.Allmountingholesmustbeutilized.Seetablebelowforqtyandholesizeinrespectivebracket.Usingthebracketasatemplate,markanddrillholesinwallandinstallbracketensuringthatallfastenersarethoroughlytight.

    Step6Carefullyattachcylindertobracket.Sensorvalve/detectorheadshouldpointtowards

    centeroftheroom.Nameplateandgaugeshouldbevisible.Tightenbracketstrapssothatthecylinderbodyisfirmlyandsecurelyheldinplacebyitsbracket(wormdriveclampsmustbetorquedto75-85in-lbs.,(6-7ft.-lbs.).Ensure180°dischargeorificesdonotfacethewall.

    Dependingonthemodel,thebracketstrapwillbedifferent:

    Types Screwdrivecoil,Phillips/hexdrive.----------NFG25–200andNFD201-825

    Twopiecebracket/saddleassembly.---------NFDmodels825-1800.

    BracketsModel Assembly MountingHoles

    (QtyxDia)NFD225-300 130-251 4x.39”

    (9.9mm)

    NFD325-400 130-252NFD425-525 130-253NFD550-675 130-254NFD700-825 130-777NFD850-1800 130-009 13x7/16”

    (10.7mm)

    II.CableAssemblyInstallation

    CAUTION:TOAVOIDKINKINGOFCABLE,DONOTPUSHCABLETORETRACTTHECORE.

    ModelSMAC-#XX(PN:136-#XX)isrequired.

    CAUTION:TOPREVENTACCIDENTALDISCHARGEDURINGCABLEINSTALLATION,VERIFYTHATTHEMANUALDISCHARGELEVERSAFETYPINISPROPERLYINSTALLED(SEEFIGURE6A–PAGE14).

    Step1Selecttheproperlocationforremotepullstation.

    a. Manualdischargereleasepullstationsshouldneverbeinstalledintheprotectedroom.b. Locatedischargepullhandleatthecontrolstationwithfullviewandeasyaccessbythe

    operator.

    BracketsModel Assembly Mounting

    Holes(QtyxDia

    NFG25 130-249 2x.29”(7.2mm)

    NFG50-75 130-775 4x.39”(9.9mm)NFG100 130-805

    NFG125-200 130-250

  • PN:123-456,RevisionBPage10of28

    c. Theareaselectedmustbestructurallysecureandprovideatleasttwelve(12)inches(305mm)ofclearanceattherearofthepaneltofacilitatecablehardware.

    Step2Installingcablealongroutingbetweencableends-a. Donotinstallcableinareawherethepossibilityofphysicalabuseislikely.Wherepractical,

    followthesamecablepathasinstalledbyoriginalinstaller(ifareplacementcable).b. Routethecabletoallowittolieinitsmostnaturalstate.Thecumulativebendinthecablerun

    mustneverexceed720degrees.Thisisequivalenttoeight(8)right(90°)angles.Useextremecarewhenbendingcabletoavoidkinking.Neverformabendwitharadiusoflessthanfive(5)inches(127mm).SelectionofthecorrectsizeFire-Hawkcablelengthwillreduceexcesscablecoil.

    c. Positionthecableinitsrouting,butdonotsecureatthistime.Steps3Athru3Fmustbecompletedpriortosecuringcableinitsfinallocation.• Donotconnectcabletothecylinderatthistime

    Step3Mountingcablefaceplateandrelease(T)handle.

    Confirmfaceplatesuppliedwithcableand/orcylinderassembly.Thefaceplateheadingshouldbe“MANUAL/AUTOMATIC”(Figure3).

    Manual/Automaticsystemsusefaceplate123-458

    Figure3

    a. Usingthemanualdischargefaceplate(Figure3,Figure4)asatemplate,markanddrilla13/32inch(10.4mm)hole.

    b. Removetheprotectivebackingfromthefaceplate.Whilealigningtheholes,placeevenpressureuponthefaceplate.Toinsureagoodbond,thetemperatureshouldbeinexcessof50°F(10°C).

    c. FollowingthediagraminFigure4,installthejamnutandlockwasheronthecableend–outer.Screwthejamnuttotheendofthethreads.Insertthecableendthroughthepanelandfaceplatehole.Pullthecableend–inner(threadedshaft)outtoitsfullesttravel.Installferrulebyscrewingontothecableend–outeruntilitbottomsout.Usepliersonthebackside–holdingthecableend–outerwhileturningtheferrule.Useplierswithrubbertipsorothernon-scratchinggrip.Donotovertighten.

    d. Withcableend–inner(threadedshaft)outtoitsfullesttravel,placerubberO-ringoverthreadsonshaft.Holdthecableend-innerfromrotatingusingthesafetypinincrosshole(seeFigure4–Page11)orbyusingneedlenosepliers.InstalltheT-Handleonthecableend–inner,screwingitonuntilitbottomsout.Donotovertighten.

    e. Pullonthecylinder(S-hook)endofthecabletoretractthehandleintotheferrule.ItmaybenecessarytoslightlypushontheT-handletoseattheO-ring.AlignthecrossholesintheT-

    PULL HANDLE REMOVE PIN FOR MANUAL OPERATION

    ELECTRICAL SYSTEMS FORCED VENTILATION UPON SYSTEM DISCHARGE, SHUT DOWN

    MANUAL AUTOMATIC FIRE SUPPRESSION SYSTEM

    WWW.FIRE-HAWKSAFETY.COM

    ENGINE

    TM

  • PN:123-456,RevisionBPage11of28

    Handleandferruleandinsertthesafetypinthroughbothitemssothattheendofthesafetypinshowsoutthefarside.LeavethesafetypininsertedthroughtheT-handle/Ferrule,butdonotinstalltheredsafetytieatthistime.

    f. TurntheT-handle/FerrulesothatthewordFIREisverticalororientedasneeded.g. Thisactionwillresultintheentirecablerotatingalongitslength.Ensurethatthecableis

    allowedtorotateandremaininanaturalstate.h. Tightenthejamnutbehindtheinstrumentpaneltolockinthepositionandorientationofthe

    T-handle/Ferrule.Step4Securingcableinplacea. Securethecablealongitslength.

    i. Nyloncabletiesshouldbeusedforcablesecuring.Fastenandsupportthecableonstraightrunsonly.Donotsecureatlocationswherecablebends.

    ii. Atthecylinder/actuatorS-Hookend:a. Thecableshouldhaveaminimumstraightlengthof6inches(15cm)beforemakingany

    bends.Thecableshouldbesecuredonastraightrunbeforemakingabend.b. Thecableshouldbesecuredwithin6inchesto18inches(15cm–46cm)ofthecylinder.

    Someflexibilitywillbeneededtomovethecableforservicingthecylinder.CAUTION:FAILURETOFOLLOWTHESEINSTRUCTIONSMAYPLACEUNDUEPRESSUREONTHEHAIRPINCOTTERPIN,CAUSINGITTOMALFUNCTION

    iii. Donotinstallcableswithotherwiring.Donotusetiewirearoundthecables.

    b. Temporarilyremovesafetypinandtestcableoperation.Neverpushcable.Pullfromcylinder(Shook)end,then,pullThandleandrepeat.Cablemustmovefreelywithoutfrictionorbinding.Reinstallsafetypinandconfirmthatreleasehandleisnowlockedinplace.

    Figure4

    CAUTION:ACCIDENTALDISCHARGEDURINGHANDLINGORINSTALLATIONMAYCAUSESERIOUSINJURY.DONOTREMOVEFACTORYINSTALLEDSAFETY(PULL)PINFROMCYLINDERSENSORVALVE/DETECTORUNTILINSTALLATIONISCOMPLETEDANDCHECKED.

    CrossHole

    InstrumentPanel

    CableEndOuter

    FacePlate

    Nut

    Washer

    SafetyPin

    Ferrule

    O-ring

    T-Handle

    CableEndInner

  • PN:123-456,RevisionBPage12of28

    Step5InstallationVerificationandTestRequirement.Specification/Regulation• NFPA12A-Operatingdevices.Para.1-8.3.7maximumof40lbs.offorcerequiredatThandle

    (pullstation)toactivatesystemdischarge.• Fire-Hawk-minimumof10lbs.offorcerequiredattheShook(extinguisher)toactivate

    systemdischarge.TestProcedure

    CAUTION:DONOTPUSH(FIRE)T-Handlewhileinstallingcableassemblytoavoidkinkingthecablecore.PullS-HookatoppositeendtoretracttheT-Handle.

    Aftertheinitialroutingofcableassemblyiscompleted:a. Attachascale(PN:128-212CableTestFixture)totheS-hook(cylinderend)inplaceofthe

    cylinderReleaseassembly.b. Attachascale(PN:128-092DigitalScale)totheT-handle(pullstation)endofthecable

    assembly.Ahandlehook,PN:128-115isavailabletofacilitateattachingthescale.(ScalesavailablefromFire-Hawkorothersmaybeused)

    c. PullontheT-handlescale,monitoringthedisplayedforce,until10lbs(4.5Kg)isshownontheS-hook(cylinderend)scale.

    d. EnsurethattherequiredforceattheT-handle(pullstation)doesnotexceed40Ibs.(18.2Kg)toachieve10lbs.(4.5Kg).i. Iflessthan40lbs.(atthepullstation)offorceachievesthe10lbs.(atcylinder),complete

    thecableassemblyinstallationperStep6.ii. Ifgreaterthan40Ibs.offorcewasexertedtoachieved10lbs.,thecableroutingshouldbe

    inspectedandlikelychanged.Repeatinspection.e. Removebothscales.PullontheS-Hookatthecylindertoretractthecable.f. Reinstallsafetypinandconfirmthatreleasehandleisnowlockedinplace.g. Attachthetamperresistantroundplastictietothesafetypinbypassingtiethroughthesafety

    pinringandaroundthecableassembly.Inserttheendofthetieintocableendandpullupsnug.Thetieprovidesameansofdeterringaccidentaldischargeanddeterminingifmanualactuationhasoccurred.

    CAUTION:DONOTUSENYLONCABLETIESINPLACEOFTHETAMPERRESISTANTTIEFORSAFETYPIN.

    Note:Limitthequantity,andtightnessoftiedownstoavoidrestriction.Note:Amaximumof720°inturns,andnolessthanfive(5)inches(127mm)ofradiusperturnshouldbeutilized.Step6Connectingcableassemblytocylinder(Figure6).

    Note:ThecablemaybeinstalledfromeitherdirectionusingtheexistingBi-Directionalhardwareinstalledonthesystem.

  • PN:123-456,RevisionBPage13of28

    a. Confirmthatthecylinderismountedinitsbracket,thecablepullhandleendisinstalledand

    thecableiscorrectlyroutedtothecylinder.b. Insertthe“S”hook[Fig5-A]intotheactuatorleverfromthefrontside(overtopofthe2

    mountingscrewsintheReleaseBracket[Fig6-B].Afterthe“S”hookisconnectedtothelever,alignthegrooveinthecableend-outer[Fig5-B]withtheslotintheReleaseBracketassembly[Fig6-C].

    c. InserttheHairpinCotterPinprovidedwiththecableintothereleasebracket,overtopofthecableend[Fig6-D].• Theremaybeaslightbend(bump)inthecablebetweenwhereitisattachedtothe

    actuatorleverandwherethecableend-outerisclippedintotheReleaseBracket.Thisisnormal.

    • Thereshouldnotbetensioninthecablepullingonthelever.Tensiononthelevercancausethecylindertodischargewhenthesafetypinisremoved.

    d. WithStepcsuccessfullycomplete,usecaretoremovethefactoryinstalledsafetypinfromtheactuatorassembly[Fig6-E].

    e. StorethesafetypinintheholeoftheReleaseBracketbehindtheactuatorleverasaback-stopinfarthestholefromcable/hookassembly[Fig6-F].

    f. Ensurethesafetypiniscompletelyinstalledthroughthebracket.

    WARNING–DONOTINSTALLTHESAFETYPINBETWEENTHELEVERANDTHECABLE.THISWILLPREVENTTHECABLEFROMACTUATINGTHESYSTEM.

    g. Thefiresuppressionsystemextinguisherisnowfullyoperational.

    CAUTION–ALWAYSINSTALLSAFETYPININCYLINDERACTUATORLEVER[FIG6-A]WHENPERFORMINGSERVICEORMAINTENANCEONSYSTEM.BESURETOREMOVESAFETYPINFROMACTUATORLEVERUPONCOMPLETIONOFSERVICING.Figure5--SMACCableS-HookEnd

    CableEndOuter

    S-Hook

    B

    A

  • PN:123-456,RevisionBPage14of28

    BiDirectionalReleaseBracketCableConnection

    Figure6

    ReleaseBracket

    RemovePinfromCylinder

    HeadBi-Directional

    ReleaseBracket(MiddleHole) Fig6-F

    CylinderHead

    SafetyPinisLocatedinCenterPosition

    Fig6-A Fig6-B

    CarefullyInsert“S”HookintoReleaseArm

    Fig6-C Fig6-D

    LockCableinPlacewithHairpinCotterPin

    Fig6-E

    ReleaseArm

    LocatePinBehindReleaseArmasaBackstopinFarthestHolefromCable/HookAssembly

  • PN:123-456,RevisionBPage15of28

    III.SystemStatusIndicatorLightInstallationSelectalocationatthecontrolstationonorneartheconsolethatisinfullview.Thelocationselectedmusthaveaccessforelectricalwiring.Removetheadhesiveprotectivecoverfrombackofindicatorfaceplateandattach.Forproperadhesion,surfacemustbecleananddryandtemperaturemustbeabove50°F(10°C).Usethepreformedfaceplateholeasatemplateandcarefullydrilla5/16inch(8mm)hole.Insertindicatorlightwire(seeFigure7).

    CAUTION:PRIORTOWIRINGINDICATORLIGHT,TURNOFFELECTRICALPOWERBYSWITCHINGOFFCIRCUITBREAKER,REMOVINGFUSEORDISCONNECTINGPOSITIVEBATTERYTERMINAL.FAILURETODISCONNECTELECTRICALPOWERWHILEMAKINGELECTRICALCONNECTIONCANRESULTININJURYFROMFIREORELECTRICALBURNS.

    Thestandardindicatorlightisratedfor12VDC(contactfactoryforothervoltages).Supplies,whicharenotincludedwithyourFire-Hawksystemandshouldbeathandbeforetheindicatorlightinstallation,areasfollows:

    1. Five(5)amperein-linefuseandholder.2. Sufficientlengthofinsulatedminimum16AWGstrandedwire.3. Crimponwireconnectors.4. Crimppliers,handtools.

    Attachonewireleadfromthein-linefuse(C)totheignitionterminalonthepowerlead(A).Connectotherleadfromthein-linefusetotheindicatorlight(D).Connectremainingindicatorlead(E)tooneoftheFire-Hawkcylinderpressureswitchconnectorwires(F).Connecttheremainingcylinderpressureswitchlead(G)tocommonground,whichmaybethenegativebatterybussatthecontrolpanel(seeFigure7).

    CAUTION:ELECTRICALSYSTEMSVARYFROMONEINSTALLATIONTOANOTHERANDTHESEDIRECTIONSMAYNOTBEAPPLICABLEFORYOURINSTALLATION.SHOULDYOUHAVEANYDOUBTSOFSAFELYACCOMPLISHINGTHISINSTALLATION,CONTACTAQUALIFIEDELECTRICIANORFIRE-HAWKUSAAT(410)687-5500FORTECHNICALASSISTANCE.

    Figure7

    TM E

    IndicatorLight

    In-LineFuse

    NegativeBatteryGround

    G

    FC

    D

    B A

    Power+V

  • PN:123-456,RevisionBPage16of28

    SystemMaintenance/Inspection

    CylinderInspection/CylinderTesting

    Thefollowinginstructionsareaccordingtoapplicableregulatoryagencies.Theseregulationschangeperiodicallyandmaybedifferentfromrulesinplacewhenthissystemandmanualwereshipped.ConfirmrequirementswithFire-Hawk,localauthoritieshavingjurisdictionorapplicableagency.Allinspectionsmustbeperformedbyanauthorized/Qualifiedinspector(CurrentRINforDOT)andotherrequirementsperlocalauthoritiesasapplicable.

    NFPA2001–CleanAgentFireExtinguisherSystems:Allmodels,allcylinders:• Ifmorethan5yearshaselapsedsincethedateofthelasttestandinspection,thecylinder

    shallnotberechargedwithoutretesting.Thetestshallbepermittedtoconsistofacompletevisualinspectionasdescribedin49CFR(explainedbelowpercylindertype).

    • Cylinderscontinuouslyinservicewithoutdischargingshallbegivenacompleteexternalvisualinspectionevery5yearsormorefrequentlyifrequired.ThevisualinspectionshallbeinaccordancewithSection3ofCGAC-6,exceptthatcylindersneednotbeemptiedorstampedwhileunderpressure.

    49CFR–Transportation(DOT)–CylinderRequalification(Hydrostatictestingviaproofpressureandvolumetrictesting;visualinspectionmethods)

    ModelsNFG25–200builtwithDOT39NRC/TC-39Mcylinders.Thesearenon-refillableandarenon-reusable.Theydonotrequire/arenotallowedtobetestedforre-use.Thesystemsmayremaininserviceindefinitelyaslongasallotherserviceabilityrequirementsaremet.Systemswiththesecylinders,per49CFRrequirements,areclearlymarked,“Federallawforbidstransportationifre-filled–penaltyupto$500,000fineand5yearsimprisonment(49U.S.C.5124).

    ModelsNFD225–825builtwithDOT3AL/TC-3ALMcylindersandModelsNFD850–1800builtwithDOT4BW/TC4BWweldedsteelcylinders.Bothofthesecylindertypesarereusableandmustbeperiodicallytestedandre-qualified.TheperiodicinspectionintervalforbothDOT3ALandDOT4BWcylindersfilledasaFiresuppressionsystemwiththeagentassuppliedis12yearsfromthedatestampedonthecylinder.However,acylinderfilledbeforeitsre-qualificationdate(becomesdue),andremainsfilled,mayremaininservicewithouttestinguntilitisemptiedforanyreason(reference49CFR180.205(c).

    • CorrelationtoNFPA2001(5year)requirement.Inbothstandards,ifthecylinderisnotalreadyempty,itdoesnotneedtobeemptiedsolelyforinspectionpurposes.Ifthecylinderhasmorethan5yearsofservice,andhasbeenemptiedforwhateverreason,itneedstobeinspectedperNFPA2001guidelineslistedabove.

    • ForDOT4BW/TC4BWMweldedsteelcylindersonly,avisualinspectioninaccordancewithCGAC-6orC-6.3,asappropriate,maybeperformedinsteadoftheperiodichydrostatictests.Whenthistestmethodisapplied,thesubsequentinspectioncomesdueafter5years.o ApplicabletestsmethodsforDOT4BWcylindersarebyProofPressureTestwhichyieldsa

    subsequenttestrequirementafter7yearsandaVolumetricExpansiontestusingtheWaterJacketMethodwhichyieldsasubsequenttestrequirementafter12years.

    • ForDOT3AL/TC3ALMcylinders,visualinspectionsarenotauthorizedtoreplacehydrostatictesting.o TheonlytestmethodforDOT3ALcylindersistheVolumetricExpansiontestusingthe

    WaterJacketMethodwhichyieldsasubsequenttestrequirementafter12years.

  • PN:123-456,RevisionBPage17of28

    MODEL W.O.XXXXXX NFDXXXMMANUAL/AUTO DISCHARGETEMPERATURERANGE:175-225F(79-107C) CONTAINS:X.XXLBS(X.XKG)NOVEC1230 MAXIMUMVOLUMEPROTECTED XXXCU.FT.(X.XCU.METERS) GROSSWEIGHT XXLBS.XOZS.(XXKGS) REPLACEIMMEDIATELYIFGROSSWEIGHT DECREASESBYXOZS.ORMORE MANUFACTUREDATE:XX/XXXXREV:X

    MODEL W.O.XXXXXX NFGXXXAAUTOMATIC

    CONTAINS:X.XXLBS(X.XKG)NOVEC1230 MAXIMUMVOLUMEPROTECTED XXXCU.FT.(X.XCU.METERS) GROSSWEIGHT XXLBS.XOZS.(XXKGS) REPLACEIMMEDIATELYIFGROSSWEIGHT DECREASESBYXOZS.ORMORE MANUFACTUREDATE:XX/XXXXREV:X

    DISCHARGETEMPERATURERANGE:XXX-XXXF(XX-XXXC)

    ForsystemscomplianttoEuropeanDirectives,(EC),specificcylindersmaybeuseddifferentthanDOT/TCapprovedsystems.Internationalrequirementsneedtobefollowedaswellasotherrequirementsaccordingtothelocalauthoritieshavingjurisdiction(AHJ).

    ModelsNFG25-200withECapprovalaredesignatedas“CE”markedinaccordancewiththePressureEquipmentDirective(PED)97/23/EC.ThosecylindersarebuilttotechnicalspecificationseitherBSEN12205orISO11118.Thesesystemsarenotrefillable.Systemswiththesecylindersarenotserviceableandthereforehavenoperiodicinspectionrequirements.(ReferenceISO11118andPEDDirective97/23/EC).Modelswiththesecylinders,perEuropeanAgreementGoverningtheInternationalCarriageofDangerousGoodsbyRoad(ADR)requirements,areclearlymarked,“DONOTREFILL”.

    ModelsNFD225–1800withECapprovalaredesignatedas“CE”markedinaccordancewiththePressureEquipmentDirective(PED)97/23/EC.Thesesystemsarerefillable.

    - NFDmodels225-825haveseamlessaluminumcylindersbuilttotechnicalstandardseitherBSEN1975orISO7866.SystemswithπmarkedcylindersbuilttoISOstandard7866aretobemaintainedinaccordancewithISO10461,GasCylinders–SeamlessAluminum–AlloyGasCylinders–PeriodicInspectionandTesting.SystemswithπmarkedcylindersbuilttoBSEN1975aretobemaintainedinaccordancewithBSEN1802.

    - NFDmodels850to1800haveweldedsteelcylindersbuilttotechnicalstandardEN13322-1.ThesecylindersneedtobemaintainedinaccordancewithBSEN1803.

    Summarizingthesestandards,thereisnogeneralrequirementtoperiodicallyinspectacylinderifthecontentshavenotbeenused,evenifthetestintervalhaslapsed.Intheeventthatcontentshavedischarged,leakedorotherwisebeenexhausted,theinspectionintervalis10yearsfromthemanufacturedatestampedonthecylinder.TPEDDirective96/36/ECalsohasrequirementsforperiodicinspection.

    WARNING:DONOTATTEMPTTODISASSEMBLEANYPARTORCOMPONENTOFTHEEXTINGUISHER.THISUNITISPRESSURIZEDANDSERIOUSINJURYCOULDRESULT.CONTACTTHEFACTORYORANAUTHORIZEDDEALERFORSERVICEINFORMATION.

    AgentWeightInspection

    Weighcylindertoinsureampleextinguisheragent(every6months,minimum).Allfiresuppressionsystemscontainingliquefiedgasrequireperiodicweighingtoensureafullychargedunit.Pressuregaugesindicatetheabilitytodischargetheagentbutnotthequantityofextinguishingagent.Thecylinder(lessbracket)mustbeweighedonatleastasemi-annualbasisandbereplacedimmediatelyifgrossweighthasdecreasedbythequantitynotedonthespecificationlabel.AninspectionTagissuppliedoneverynewcylinderforrecordingthisinspection.Thespecificationlabel(exampleshownbelow)identifiestheModelType,WorkOrder#,DischargeTemperatureRange,AgentWeight,MaximumVolumeProtected,GrossWeight,andManufacturerDate.

  • PN:123-456,RevisionBPage18of28

    PressureGaugeInspection

    Frequentlycheckgaugeforproperpressure,(every6months,minimum).

    ReadingthePressureGauge(Inspection)Thegreensectionofthegaugeisdesignedtoshowproperfillingandpressurizationat70°F(21°C).Perapplicabledesignstandards,thisisdefinedas±10%ofnominalfillpressure.Fire-Hawksystemsareratedforoperatingtemperaturesfrom20°F(-7°C)or32°F(0°C)upto130°F(54°C).Note:Thisisstorageandambientoperatingtemperature.Afireconditionwouldobviouslyreachhighertemperatures,withthesystemactivatingat175°F(79°C)or200°F(93°C).

    Theredsectionofthegauge,aboveandbelowthegreensection,indicatetheacceptablepressurereadingsfortemperaturesbelowandabove70°F(21°C).Thetablelocatedontheincludedtagsshowthepressureofthesystematcorrespondingtemperatures.Toinspectaunitwhentheambienttemperatureisotherthan70°F(21°C),measuretheambienttemperatureandfindthecorrespondingnominalpressureinthetable.Readthetipoftheyellowpointeranddeterminewhattheinternalpressureisbycountingthedivisionlinesandaddingorsubtractingforeachlinesegmentfromtheblackcenterlinemarked,500psi(34.3bar).(Eachlinesegmentwithinthegreenpieisequalto10psi(0.68bar).Eachlinesegmentwithintheredsectionsisequalto20psi(1bar).• Comparetheactualreadingtothereferencetableonthecardattachedtothecylinder.The

    pressuresshouldbewithin±20psi(1bar)ofeachother(onesegment).• Note:thisallowancetakesintoaccountallowingforgaugemanufacturingtolerance,

    temperaturereadingaccuracyandtheabilitytopreciselyseethepointerlocation.• Iftheyellowpointerisineitherthewhitezoneonthegauge,totheleft“REPLACE”ortothe

    right“OVERCHARGE”,theunitislikelynotfunctionalandmayrequirereplacement.• Iftimeandserviceabilitypermits,asuspectunitmaybeverifiedbystabilizingthetemperature

    oftheunitat70°F(21°C)foraminimumof4hoursandreadingthepressuregaugeatthatpoint.

    IndicatorLightInspection

    Beforeoperating,visuallychecktoinsureindicatorlightoralternatedisplayisoperational,andcylinderpressureindicatorisinthenormalrange.

    GlassBulb(TemperatureSensor)Inspection

    Neverpaintorobstructthecylindermanifoldorsensorvalve/detector,asthiswilladverselyaffectitsoperatingcharacteristic.

    Checkforpresenceofglassbulb.Figure8showstwostates:Charged(Intact)andDischarged(Activated).

    Figure8

    Detectors

    DischargedCharged

  • PN:123-456,RevisionBPage19of28

    CableInspection

    Manualactivationcablesshouldbecheckedforproperoperationevery6monthswhilecylinderinspectionisbeingperformed.Cablerunsshouldbevisuallycheckedtoensurenodamagehasbeendonetothecable.(Noexcessivewearorpinchingexists).Takesafetypinoutof‘backstop’positioninthereleasebracketandplaceintocenterhole,securingreleasearm.Disengage‘S’-hookfromreleasearm,removepinfromfirereleasehandle,andtestcableforsmoothoperation.Re-assembleinreverseorder(seeFigure6,page14).

    AdditionalServicingFurtherservicingofFire-Hawkpre-engineeredsystemsisreservedtocompetentindividualswhohavecompletedtrainingbyFire-Hawkpersonnel.ServiceManual123-350isavailabletotheseindividuals.

    SpecificationTableFire-Hawk“NFG”SeriesAutomaticandManual/AutomaticFireSuppressionsystems

    C UF T C UM

    R ang e R ang e IN mm IN mm IN mmNFG25A NFG25M 17-25 0.48-0.7 0.9 0.4 1.3 0.6 2.9 74 5 127 12.7 323 4.4 112

    NFG50A NFG50M 26-50 0.7-1.4 1.4 0.6 2.7 1.2 3.5 89 5 127 18.8 478 4.9 124

    NFG75A NFG75M 51-75 1.4-2.1 2.7 1.2 4.0 1.8 3.5 89 5 127 18.8 478 4.9 124

    NFG100A NFG100M 76-100 2.1-2.8 4.0 1.8 5.4 2.4 4.3 108 5.2 132 19 483 5.2 132

    NFG125A NFG125M 101-125 2.8-3.5 5.4 2.4 6.7 3.0 5.3 133 5.7 145 20.6 523 6.4 163

    NFG150A NFG150M 126-150 3.5-4.2 6.7 3.1 8.1 3.7 5.3 133 5.7 145 20.6 523 6.4 163

    NFG175A NFG175M 151-175 4.2-5.0 8.1 3.7 9.4 4.3 5.3 133 5.7 145 20.6 523 6.4 163

    NFG200A NFG200M 176-200 5.0-5.7 9.4 4.3 10.7 4.9 5.3 133 5.7 145 20.6 523 6.4 163

    NFGModelA reaof

    Protection

    MaximumNovec1230

    A g entC ylinderD iameter

    InstallationD imens ionR equirements

    A uto LB S KG LB S KGManual/A uto

    mmW H D

    MinimumNovec1230

    A g ent

    IN

    OperatingTemperatureRange: 20°F(-7°C)to130°F(54°C).DischargeTemperatureRange: NFG25throughNFG75:200-250°F(93-121°C) NFG100throughNFG200:175-225°F(79-107°C)

    • AllNFGModelsapprovedforverticalorhorizontalmounting.• AllNFGModelsareavailablewithmultipleapprovedcylinders,DOT/TCandCE.• AllNFGModelsarenon-refillable(non-serviceable)• NFGandNFDsystemsaredesignedforonlyonecylinder(singlenozzle)toprotectthe

    entirespace.Usingtwocylinderstoachievecombinedcoverageisnotacceptable.

    Abbreviations:CUFT=CubicFeet KG=Kilograms IN=InchesCUM=CubicMeters LBS=Pounds MM=Millimeters

  • PN:123-456,RevisionBPage20of28

    SpecificationTableFire-Hawk“NFD”SeriesAutomaticandManual/AutomaticFireSuppressionsystems

    DOT3AL/TC3ALMorTPED/ADRCylinders

    C ubicF T R ang e

    C ubicM R ang e

    LB S KG LB S KG IN mm IN mm IN mm IN mm

    NFD225 A NFD225 M 201–225 5.7–6.4 10.8 4.9 12.1 5.5 6.9 175 8 203 20.1 511 8 203

    NFD250 A NFD250 M 226–250 6.4–7.1 12.1 5.5 13.4 6.1 6.9 175 8 203 20.1 511 8 203

    NFD275 A NFD275 M 251–275 7.1–7.8 13.4 6.1 14.8 6.7 6.9 175 8 203 20.1 511 8 203

    NFD300 A NFD300 M 276–300 7.8–8.5 14.8 6.7 16.1 7.3 6.9 175 8 203 20.1 511 8 203

    NFD325 A NFD325 M 301–325 8.5–9.2 16.1 7.3 17.5 7.9 6.9 175 8 203 24.7 627 8 203

    NFD350 A NFD350 M 326–350 9.2–9.9 17.5 7.9 18.8 8.5 6.9 175 8 203 24.7 627 8 203

    NFD375 A NFD375 M 351–375 9.9–10.6 18.8 8.5 20.1 9.1 6.9 175 8 203 24.7 627 8 203

    NFD400 A NFD400 M 376–400 10.6–11.3 20.2 9.1 21.5 9.7 6.9 175 8 203 24.7 627 8 203

    NFD425 A NFD425 M 401–425 11.4–12.0 21.5 9.7 22.8 10.4 6.9 175 8 203 28.7 729 8 203

    NFD450 A NFD450 M 426–450 12.1–12.7 22.8 10.4 24.2 11.0 6.9 175 8 203 28.7 729 8 203

    NFD475 A NFD475 M 451–475 12.8–13.4 24.2 11.0 25.5 11.6 6.9 175 8 203 28.7 729 8 203

    NFD500 A NFD500 M 476–500 13.5–14.2 25.5 11.6 26.9 12.2 6.9 175 8 203 28.7 729 8 203

    NFD525 A NFD525 M 501–525 14.2–14.9 26.9 12.2 28.2 12.8 6.9 175 8 203 28.7 729 8 203

    NFD550 A NFD550 M 526–550 14.9–15.6 28.2 12.8 29.5 13.4 8 203 9 229 29 737 9.4 239

    NFD575 A NFD575 M 551–575 15.6–16.3 29.6 13.4 30.9 14.0 8 203 9 229 29 737 9.4 239

    NFD600 A NFD600 M 576–600 16.3–17.0 30.9 14.0 32.2 14.6 8 203 9 229 29 737 9.4 239

    NFD625 A NFD625 M 601–625 17.0–17.7 32.2 14.6 33.6 15.2 8 203 9 229 29 737 9.4 239

    NFD650 A NFD650 M 626–650 17.7–18.4 33.6 15.2 34.9 15.8 8 203 9 229 29 737 9.4 239

    NFD675 A NFD675 M 651–675 18.4–19.1 34.9 15.8 36.3 16.4 8 203 9 229 29 737 9.4 239

    NFD700 A NFD700 M 676–700 19.1–19.8 36.3 16.4 37.6 17.1 8 203 9 229 33.8 859 9.4 239

    NFD725 A NFD725 M 701–725 19.8–20.5 37.6 17.1 38.9 17.7 8 203 9 229 33.8 859 9.4 239

    NFD750 A NFD750 M 726–750 20.6–21.2 38.9 17.7 40.3 18.3 8 203 9 229 33.8 859 9.4 239

    NFD775 A NFD775 M 751–775 21.3–21.9 40.3 18.3 41.6 18.9 8 203 9 229 33.8 859 9.4 239

    NFD800 A NFD800 M 776–800 22.0–22.6 41.6 18.9 43.0 19.5 8 203 9 229 33.8 859 9.4 239

    NFD825 A NFD825 M 801–825 22.7–23.4 43.0 19.5 44.3 20.1 8 203 9 229 33.8 859 9.4 239

    H D

    A uto Manual/A uto

    InstallationD imens ionR equirements

    Model A reaofProtection

    M inimumNovec1230

    A g ent

    MaximumNovec1230

    A g ent

    C ylinderD ia W

    (Continuedonnextpage)

    OperatingTemperatureRange: NFD225-825:20°F(-7°C)to130°F(54°C)NFD850-1800:32°F(0°C)to130°F(54°C)

    DischargeTemperatureRange: NFD225throughNFD1800:175-225°F(79-107°C)

    • ModelsNFD225throughNFD825approvedforverticalorhorizontalmounting.• ModelsNFD850throughNFD1800forverticalmountingonly.• AllNFDModelsarerefillable.• NFDModelsareonlyofferedineitherUSDOT/TCorEuropean,CE.(NotBoth)• NFGandNFDsystemsaredesignedforonlyonecylinder(singlenozzle)toprotectthe

    entirespace.Usingtwocylinderstoachievecombinedcoverageisnotacceptable.

    Abbreviations:CUFT=CubicFeet KG=Kilograms LBS=PoundsCUM=CubicMeters IN=Inches MM=Millimeters

  • PN:123-456,RevisionBPage21of28

    SpecificationTableFire-Hawk“NFD”SeriesManual/AutomaticFireSuppressionsystems

    DOT4BW/TC4BWMorTPED/ADRCylinders

    C ubic FTR ange

    C ubic MR ange

    L B S K G LB S K G IN MM IN MM IN MM IN MM

    NFD 850 M 826–850 23.4–24.1 44.3 20.1 45.7 20.7 10 254 16.5 419 30.7 780 11.4 290

    NFD 875 M 851–875 24.1–24.8 45.7 20.7 47.0 21.3 10 254 16.5 419 30.7 780 11.4 290

    NFD 900 M 876–900 24.8–25.5 47.0 21.3 48.3 21.9 10 254 16.5 419 30.7 780 11.4 290

    NFD 925 M 901–925 25.5–26.2 48.3 21.9 49.7 22.5 10 254 16.5 419 30.7 780 11.4 290

    NFD 950 M 926–950 26.2–26.9 49.7 22.5 51.0 23.1 10 254 16.5 419 30.7 780 11.4 290

    NFD 975 M 951–975 26.9–27.6 51.0 23.1 52.4 23.8 10 254 16.5 419 30.7 780 11.4 290

    NFD 1000 M 976–1000 27.6–28.3 52.4 23.8 53.7 24.4 10 254 16.5 419 30.7 780 11.4 290

    NFD 1025 M 1001–1025 28.3–29.0 53.7 24.4 55.0 25.0 10 254 16.5 419 30.7 780 11.4 290

    NFD 1050 M 1026–1050 29.1–29.7 55.1 25.0 56.4 25.6 10 254 16.5 419 30.7 780 11.4 290

    NFD 1075 M 1051–1075 29.8–30.4 56.4 25.6 57.7 26.2 10 254 16.5 419 30.7 780 11.4 290

    NFD 1100 M 1076–1100 30.5–31.1 57.7 26.2 59.1 26.8 10 254 16.5 419 30.7 780 11.4 290

    NFD 1125 M 1101- 1125 31.2–31.9 59.1 26.8 60.4 27.4 10 254 16.5 419 30.7 780 11.4 290

    NFD 1150 M 1126–1150 31.9–32.6 60.4 27.4 61.8 28.0 10 254 16.5 419 30.7 780 11.4 290

    NFD 1175 M 1151–1175 32.6–33.3 61.8 28.0 63.1 28.6 10 254 16.5 419 30.7 780 11.4 290

    NFD 1200 M 1176–1200 33.3–34.0 63.1 28.6 64.4 29.2 10 254 16.5 419 30.7 780 11.4 290

    NFD 1225 M 1201–1225 34.0–34.7 64.5 29.2 65.8 29.8 10 254 16.5 419 30.7 780 11.4 290

    NFD 1250 M 1226–1250 34.7–35.4 65.8 29.8 67.1 30.4 10 254 16.5 419 30.7 780 11.4 290

    NFD 1275 M 1251–1275 35.4–36.1 67.1 30.5 68.5 31.1 10 254 16.5 419 39.9 1013 11.4 290

    NFD 1300 M 1276–1300 36.1–36.8 68.5 31.1 69.8 31.7 10 254 16.5 419 39.9 1013 11.4 290

    NFD 1325 M 1301–1325 36.8–37.5 69.8 31.7 71.2 32.3 10 254 16.5 419 39.9 1013 11.4 290

    NFD 1350 M 1326–1350 37.5–38.2 71.2 32.3 72.5 32.9 10 254 16.5 419 39.9 1013 11.4 290

    NFD 1375 M 1351–1375 38.3–38.9 72.5 32.9 73.8 33.5 10 254 16.5 419 39.9 1013 11.4 290

    NFD 1400 M 1376–1400 39.0–39.6 73.9 33.5 75.2 34.1 10 254 16.5 419 39.9 1013 11.4 290

    NFD 1425 M 1401–1425 39.7–40.3 75.2 34.1 76.5 34.7 10 254 16.5 419 39.9 1013 11.4 290

    NFD 1450 M 1426–1450 40.4–41.1 76.5 34.7 77.9 35.3 10 254 16.5 419 39.9 1013 11.4 290

    NFD 1475 M 1451–1475 41.1–41.8 77.9 35.3 79.2 35.9 10 254 16.5 419 39.9 1013 11.4 290

    NFD 1500 M 1476–1500 42.0–42.5 79.2 35.9 80.6 36.5 10 254 16.5 419 39.9 1013 11.4 290

    NFD 1525 M 1501–1525 42.5–43.2 80.6 36.5 81.9 37.1 10 254 16.5 419 39.9 1013 11.4 290

    NFD 1550 M 1526–1550 43.2–43.9 81.9 37.2 83.2 37.8 10 254 16.5 419 39.9 1013 11.4 290

    NFD 1575 M 1551–1575 43.9–44.6 83.2 37.8 84.6 38.4 10 254 16.5 419 39.9 1013 11.4 290

    NFD 1600 M 1576–1600 44.6–45.3 84.6 38.4 85.9 39.0 10 254 16.5 419 39.9 1013 11.4 290

    NFD 1625 M 1601–1625 45.3–46.0 85.9 39.0 87.3 39.6 10 254 16.5 419 39.9 1013 11.4 290

    NFD 1650 M 1626–1650 46.0–46.7 87.3 39.6 88.6 40.2 10 254 16.5 419 39.9 1013 11.4 290

    NFD 1675 M 1651–1675 46.7–47.4 88.6 40.2 89.9 40.8 10 254 16.5 419 39.9 1013 11.4 290

    NFD 1700 M 1676–1700 47.5–48.1 90.0 40.8 91.3 41.4 10 254 16.5 419 39.9 1013 11.4 290

    NFD 1725 M 1701–1725 48.2–48.8 91.3 41.4 92.6 42.0 10 254 16.5 419 39.9 1013 11.4 290

    NFD 1750 M 1726–1750 48.9–49.6 92.6 42.0 94.0 42.6 10 254 16.5 419 39.9 1013 11.4 290

    NFD 1775 M 1751–1775 49.6–50.3 94.0 42.6 95.3 43.2 10 254 16.5 419 39.9 1013 11.4 290

    NFD 1800 M 1776–1800 50.3–51.0 95.3 43.2 96.7 43.8 10 254 16.5 419 39.9 1013 11.4 290

    D

    Manual/Auto

    Installat ionDimensionR equirements

    Model A reaof P rotec t ion

    MinimumNovec 1230Agent

    Max imumNovec 1230Agent

    C y linderDia W H

  • PN:123-456,RevisionBPage22of28

    Three(3)Year“NFG”and“NFD”SeriesLimitedWarrantyWewarranttotheoriginalretailpurchaser,theNFDandNFGsuppressionsystemsforaperiodofthree(3)yearsafterretailpurchaseagainstdefectivematerialandfaultyworkmanship.Anysystemfoundtobedefectiveduringthewarrantyperiodwillrepairedifpossible,orreplacedfreeofchargeifclassifiedasnon-refillable(accordingtotheproductlabel)upontheprepaidreturnofthedefectivesystemtoFire-Hawkfacilityorauthorizedserviceparty.Proofofpurchaserequired,otherwisedateofmanufactureroncylinderspecificationlabelwillapply.Thiswarrantygivesyouspecificlegalrightswhichmayvarybystateorcountry.Theforegoingwarrantyismadeinlieuofallotherwarrantieswithrespecttothesystemincludinganyimpliedwarrantyofmerchantabilityorfitnessforaparticularpurpose.Nopersonisauthorizedtogiveanyotherwarranty,orassumeforFire-Hawkanyotherliabilityinconnectionwiththesaleorinstallationofitsproducts.Replacementofthesystemwillbethesoleremedywithrespecttoanylossordamagetoproperty.Buyerisnotrelyingonseller’sjudgmentregardingbuyer’sparticularrequirementsandbuyerhashadanopportunitytoinspecttheproducttobuyer’ssatisfaction.

    Conditions

    AllFire-Hawkproductsareleaktestedaftermanufactureandshippedinperfectworkingorder.Damagenoteduponreceiptofshipmentshouldbeaddressedasashippingclaim,thefilingofwhichisthesoleresponsibilityoftheconsigneeforwhichthetotalcompensatoryawardwillbelimitedtothatappropriatedbythecarrier.Insuredfreightcostsaretheresponsibilityoftheconsignee.Missingcomponentpartsanddamagenoteduponinstallationaretypicallytheresultofmishandlingduringtheinstallationprocessandwillnotqualifyforwarrantycoverage.Incidentsofaccidentaldischargearenotindicativeofproductfailure–heedproductwarningstoavoidinjuryand/orassociatedcosts.Noreturnswillbeprocessedwithoutproperreturnauthorization.

    OutofWarrantyReplacements/Recharges

    Fire-Hawk“NFG”ModelSeriescylinderscomplywithUSDOTSpecification39andPED.Thesecylindersarenotrefillable.ThedischargedcylinderwillbereplacedwithacomparableFire-Hawkcylinderuponprepaidreturnofthedischargedsystemforone-halfofthecurrentsuggestedlistprice.Fire-Hawk“NFD”ModelSeriescylinderscomplywithDOT/TCorEuropeanSpecifications(TPED/ADR),asdetailedinthecylinderinspection/cylindertestingsection,whichallowdischargedcylinderstoberefilledandserviced.Thedischargedcylindermayberefilledupontheprepaidreturnofthedischargedsystem.Contactfactoryoranauthorizeddealerfordetails.Returnto: Fire-Hawk–USA ADivisionofGlobalTecSolutionsLLC

    Baltimore,Maryland Website:www.fire-hawksafety.com

  • PN:123-456,RevisionBPage23of28

    Novecfilled - Engineered,Pre-engineered,PortablesandRaceSystems MATERIALSAFETYDATASHEET

    FireSuppressionSystem

    MSDSNo.123-241Rev.-ReviewDate:05/10/10

    Section1–CompanyandChemicalIdentification

    Fire-Hawk EmergencyPhone:1-800-535-5053(InfoTrac) InternationalPhone:352-323-3500

    9331-APhiladelphiaRoad Phone:1-800-445-7680Baltimore,Maryland21237 IssueDate:August30,2009www.fire-hawksafety.com ProductName:FireExtinguisher/SystemProductName:3M(TM)Novec(TM)1230FireProtectionFluid[FK-5-1-12]

    Section2:Ingredients

    C.A.S. IngredientName OSHAPEL ACGIHTLV OSHA

    STEL%

    756-13-8 1,1,1,2,2,4,5,5,5-NONAFLUORO-4-(Trifluoromethyl)-3-Pentanone

    N/A N/A N/A >99

    7727-37-9

    Nitrogen,Compressed None SimpleAsphyxiant

    N/A 1

    ThereareNOsubstancespresentingahealthorenvironmentalhazardwithinthemeaningofDirective67/548/EEC,inconcentrationsequaltoorgreaterthanthoselaiddowninthetablesetoutinArticle3(3)ofDirective1999/45/EC,norwithlowerlimitsgiveninAnnexItoDirective67/548/EECorinAnnexesII,IIIorVtoDirective1999/45/EC.ThereareNOsubstancesforwhichthereareCommunityworkplaceexposurelimits,whicharenotalreadyincludedinabove.NOTE:Unlessacomponentpresentsaseverehazard,itdoesnotneedtobeconsideredintheMSDSiftheconcentrationislessthan1%.[AccordingtoDirective1999/45/EC.]

    Section3:HazardsIdentification

    3.1EmergencyOverviewOdor,Color,Grade:Clearcolorless,lowodorgas.3.2PotentialHealthEffects(AcuteExposure):EyeContactContactwiththeeyesduringproductuseisnotexpectedtoresultinsignificantirritation.SkinContact:Contactwiththeskinduringproductuseisnotexpectedtoresultinsignificantirritation.Inhalation:Prolongedorrepeatedexposure,aboverecommendedguidelines,maybeabsorbedfollowinginhalationandcausetargetorganeffects.Ingestion:Nohealtheffectsareexpected.ChronicExposure:FORHUMANS:EUClassification:ThisproductisnotclassifiedasdangerousaccordingtoDirective1999/45/EC.LimitValuesforExposure:1,1,1,2,2,4,5,5,5-Nonafluoro-4-(trifluoromethyl)-3-pentanone.TWALimit:150ppm.Limitsetby3MCompany.NeitherthispreparationnorthesubstancescontainedinithavebeenlistedascarcinogenicbyNationalToxicologyProgram,I.A.R.C.,orOSHA.ASPARTOFGOODINDUSTRIALANDPERSONALHYGIENEANDSAFETYPROCEDURE,avoidallunnecessaryexposuretothechemicalsubstanceandensurepromptremovalfromskin,eyes,andclothing.DONOTeat,drinkorsmokewhenusingthisproduct.

  • PN:123-456,RevisionBPage24of28

    Prolongedorrepeatedexposure,aboverecommendedguidelines,maycauselivereffects.Signs/symptomsmayincludelossofappetite,weightloss,fatigue,weakness,abdominaltendernessandjaundice.MEDICALCONDITIONSGENERALLYAGGRAVATEDBYEXPOSURE:Noneknown.FORENVIRONMENT:Noharmtotheenvironmentisexpectedfromanaccidentalreleaseofthispreparation.SeeSection12,ECOLOGICALINFORMATION.

    Section4:FirstAidMeasures

    4.1FirstAidProceduresThefollowingfirstaidrecommendationsarebasedonanassumptionthatappropriatepersonalandindustrialhygienepracticesarefollowed.EyeContact:Flusheyeswithlargeamountsofwater.Ifsigns/symptomspersist,getmedicalattention.SkinContact:Washaffectedareawithsoapandwater.Ifsigns/symptomsdevelop,getmedicalattention.Inhalation:Ifsigns/symptomsdevelop,removepersontofreshair.Ifsigns/symptomspersist,getmedicalattention.IfSwallowed:Donotinducevomiting.Givevictimtwoglassesofwater.Nevergiveanythingbymouthtoanunconsciousperson.Ifsigns/symptomsdevelop,getmedicalattention.

    Section5:FireFightingMeasures

    5.1FlammablePropertiesAutoignitiontemperature:NotApplicable. FlammableLimits-LEL[Details:Nonflammable].FlashPoint:NotApplicable FlammableLimits-UEL[Details:Nonflammable].5.2ExtinguishingMediaProductisafire-extinguishingagent.5.3PROTECTIONOFFIREFIGHTERSSpecialFireFightingProcedures:Wearfullprotectiveequipment(BunkerGear)andaself-containedbreathingapparatus(SCBA).UnusualFireandExplosionHazards:Notapplicable.Note:SeeSTABILITYANDREACTIVITY(SECTION10)forhazardouscombustionandthermaldecompositioninformation.

    Section6:AccidentalReleaseMeasures

    Forpersonalprotection:Preventskinandeyecontact,seeSection8EXPOSURECONTROLS/PERSONALPROTECTION.Cleanup:Ventilatetheareawithfreshair.Containspill.Forlargerspills,coverdrainsandbuilddikestoprevententryintosewersystemsorbodiesofwater.Workingfromaroundtheedgesofthespillinward,coverwithbentonite,vermiculite,orcommerciallyavailableinorganicabsorbentmaterial.Mixinsufficientabsorbentuntilitappearsdry.Collectasmuchofthespilledmaterialaspossible.Cleanupresidue.Placeinametalcontainerapprovedfortransportationbyappropriateauthorities.Sealthecontainer.Disposeofcollectedmaterialassoonaspossible.SeeSection13,DISPOSALCONSIDERATIONS.NOharmtotheenvironmentisexpectedfromanaccidentalreleaseofthispreparation.SeeSection12,ECOLOGICALINFORMATION.Intheeventofareleaseofthismaterial,theusershoulddetermineifthereleasequalifiesasreportableaccordingtolocal,state,andfederalregulations.

  • PN:123-456,RevisionBPage25of28

    Section7:HandlingandStorage

    7.1HandlingContentsunderpressure.Avoidbreathingofvapors,mistsorspray.Avoideyecontactwithvapors,mists,orspray.Handle,transportandstorecarefullyandsecurelytoavoidaccidentalknockingoverorotherseverephysicalimpacts.Donotexposetodirectheatsources.SeeincompatibilityinformationinSection10,STABILITYANDREACTIVITY.7.2StorageKeepcontainerinwell-ventilatedarea.Donotstoreintemperatureabove130ºF(54ºC).SeeincompatibilityinformationinSection10,STABILITYANDREACTIVITY.Thereisminimaldangertotheenvironmentfromastoragerelease.SeeSection12,ECOLOGICALINFORMATION.7.3.SpecificuseTheintendedorrecommendeduseofthispreparationisasaFIREEXTINGUISHINGAGENT/SYSTEM.

    Section8:ExposureControls/PersonalProtection

    8.1PersonalProtectiveEquipment(PPE)Properhandlingshouldnotincurexposuretoagent.Asaprecautionforaccidentaldischargeorleakage,thefollowingshouldbefollowed:8.1.1Eye/FaceProtectionAvoideyecontact.Thefollowingeyeprotection(s)arerecommended:IndirectVentedGoggles.8.1.2SkinProtectionAvoidprolongedorrepeatedskincontact.Selectanduseglovesand/orprotectiveclothingtopreventskincontactbasedontheresultsofanexposureassessment.Consultwithyourgloveand/orprotectiveclothingmanufacturerforselectionofappropriatecompatiblematerials.Glovesmadefromthefollowingmaterial(s)arerecommended:ButylRubber.8.1.3RespiratoryProtectionAvoidbreathingofvapors,mistsorspray.Undernormaluseconditions,airborneexposuresarenotexpectedtobesignificantenoughtorequirerespiratoryprotection.SelectoneofthefollowingNIOSHapprovedrespiratorsbasedonairborneconcentrationofcontaminantsandinaccordancewithOSHAregulations:Halffacepieceorfullfaceair-purifyingrespiratorwithorganicvaporcartridges.Consultthecurrent3MRespiratorySelectionGuideforadditionalinformationorcall1-800-243-4630for3Mtechnicalassistance.Ifthermaldecompositionoccurs,wearsuppliedairrespiratoryprotection.8.1.4PreventionofSwallowingDonoteat,drinkorsmokewhenusingthisproduct.Washexposedareasthoroughlywithsoapandwater.8.1.5HandprotectionButylRubberglovesarerecommended.Selectanduseglovesand/orprotectiveclothingtopreventskincontactbasedontheresultsofanexposureassessment.Consultwithyourgloveand/orprotectiveclothingmanufacturerforselectionofappropriatecompatiblematerials.8.2ExposureLimitValues1,1,1,2,2,4,5,5,5-Nonafluoro-4-(trifluoromethyl)-3-pentanoneTWALimit:150ppm.Limitsetby3MCompany.8.3Environmentalexposurecontrols Thereisminimaldangertotheenvironmentfromastoragerelease.SeeSection12,ECOLOGICALINFORMATION.

    Section9:PhysicalAndChemicalProperties

    SpecificPhysicalForm:Liquidandgasmixture SpecificGravity:1.6[RefStd:WATER=1]Odor,Color,Grade:Clearcolorless,lowodor. Meltingpoint-108ºCGeneralPhysicalForm:Liquidandgas SolubilityinWater:Nil

  • PN:123-456,RevisionBPage26of28

    Autoignitiontemperature:NotApplicable Evaporationrate:>1[RefStd:BUOAC=1]FlashPoint:NotApplicable VolatileOrganicCompounds:NoDataAvailableFlammableLimits-LEL[Details:Nonflammable] Percentvolatile:100%FlammableLimits-UEL[Details:Nonflammable] VOCLessH2O&ExemptSolvents:NoDataAvailableBoilingpoint:49ºC(120.6ºF) Viscosity:0.6centipoise[@25ºC]VaporDensity:11.6[RefStd:AIR=1] VaporPressure:244mmHg[@20ºC]pH:NotApplicable

    Section10:StabilityandReactivity

    Stability:Stableundernormalconditionsofhandlinganduse.MaterialsandConditionstoAvoid:Strongbases;Amines;Alcohols:Avoiddirectsunlightandultravioletlightforextendedperiods.Donotstoreabove130ºF (54ºC)takingintoaccounteffectsofsunlight.HazardousPolymerization:Hazardouspolymerizationwillnotoccur.HazardousDecompositionorBy-Products:Combustionordecompositionproductsincludecarbonmonoxide,carbondioxide,andhydrogenfluoride.

    Section11:ToxicologicalInformation

    Product:ToxicityData:InhalationLC50(rat)>10%v/v.NOAELforcardiacsensitization>10%v/v.

    Section12:EcologicalInformation

    12.1.Ecotoxicity:Notdetermined.12.2.Mobility:Productishighlyinsolubleinwaterandvolatile.12.3.Persistenceanddegradability:Photolytichalf-lifeis3to5days.Thepersistentphotolyticdegradationproductistrifluoroaceticacid.12.4.Bioaccumulativepotential:Notdetermined.12.5.Otheradverseeffects:Ozonedepletionpotential:None.Photochemicalozonecreationpotential:None.Globalwarmingpotential:1.

    Section13:DisposalConsiderations

    WasteDisposalMethod:Reclaimiffeasible.Forinformationonproductreturn,contactFire-Hawk.Incinerateinanindustrialorcommercialfacilityinthepresenceofacombustiblematerial.CombustionproductswillincludeHF.Facilitymustbecapableofhandlinghalogenatedmaterials.Asadisposalalternative,disposeofwasteproductinafacilitypermittedtoacceptchemicalwaste.EPAHazardousWasteNumber(RCRA):Notregulated.Sinceregulationsvary,consultapplicablelocalregulationsorauthoritiesbeforedisposal.

    Section14:TransportInformation

    HazardClassorDivision:2.2.Label:Nonflammablegas.ProperShippingName:CompressedGas,n.o.s,(nitrogenandfluorinatedketonemixture)IDNumber:UN1956PackingGroup:N/APackingInstructions:200Foradditionaltransportinformation,contactFire-Hawk.Noharmtotheenvironmentisexpectedfromthispreparation.SeeSection12,ECOLOGICALINFORMATION.

  • PN:123-456,RevisionBPage27of28

    Section15:RegulatoryInformation

    EUClassification:ThisproductisnotclassifiedasdangerousaccordingtoDirective1999/45/EC.ExposureLimitValues:1,1,1,2,2,4,5,5,5-Nonafluoro-4-(trifluoromethyl)-3-pentanone.TWALimit:150ppm.Limitsetby3MCompany.EINECSStatus:ThecomponentofthisproducthasbeennotifiedtoELINCS(EuropeanListofNotifiedorNewChemicalSubstances).Certainrestrictionsapply.Contactyourdistributorforadditionalinformation.EPATSCAStatus:AllcomponentsareincludedinTSCAinventoriesorareexemptfromlisting.CanadianDSL(DomesticSubstancesList):AllcomponentsareincludedintheDSLorareexemptfromlisting.TheproductalsocomplieswiththechemicalnotificationrequirementsforKorea(KECI),Australia(AICS),Japan(METI),andChina(CICS).Environmentalrestrictions:Noneareknown.RestrictionsonMarketingandUse:Noneareknown.Refertoanyothernationalmeasuresthatmayberelevant.

    Section16:OtherInformation

    Formatisfromdirective2001/58/EC.ThereisnodatainEINECShttp://exb.jrc.it/existing-chemicals/.Datausedtocompilethedatasheetisfrom3MMaterialSafetyDataSheet,Jan.21,2004andotherproductliterature.TheEUClassificationisinaccordancewithDirective1999/45/EC.(WHMIS)CANADIANWORKPLACEHAZARDOUSMATERIALIDENTIFICATIONSYSTEMRATINGS:Thisproductisrated:NotHazardous.(HMIS)HAZARDOUSMATERIALIDENTIFICATIONSYSTEMRATINGS:HEALTH:0 4.SevereHazard___1.SlightHazardFLAMMABILITY:0 3.SeriousHazard___0.MinimalHazardREACTIVITY:1 2.ModerateHazard___PROTECTION:SeeSection8.EXPOSURECONTROLS/PERSONALPROTECTION.

    Section17:DisclaimerofExpressedandImpliedWarranties

    Metalcraft/Fire-Hawk,Inc.hastakenreasonablecareinpreparingthisdocument,however,sincetheuseofthisinformationandtheconditionsofuseoftheproductarenotwithinthecontrolofMetalcraft/Fire-Hawk,Inc.,itistheuser’sobligationtodeterminetheconditionsofsafeuseofthisproduct.Theinformationinthisdocumentisofferedwithnowarrantiesorrepresentationsastoaccuracyorcompletenessanditistheresponsibilityofeachindividualtodeterminethesuitabilityoftheinformationfortheirparticularpurpose(s).

  • PN:123-456,RevisionBPage28of28