3M Cold Shrink QS4 Integrated Splice Kit QS4-15JCN-4/0-500 for Jacketed Concentric Neutral (JCN) and Flat Strap Neutral Cable Instructions IEEE Std. 404 15 kV Class 150 kV BIL CAUTION Working around energized systems may cause serious injury or death. Installation should be performed by personnel familiar with good safety practice in handling electrical equipment. De-energize and ground all electrical systems before installing product. Kit Selection Table Kit Number Cable Insulation O.D. Range Conductor Size Range QS4-15JCN-4/0-500 0.84"–1.38" (21,3–35,1 mm) 4/0 AWG–500 kcmil* (95-240 mm 2 ) *Splices (including size transitions) can be made to smaller or larger conductors (but larger conductors may require special neutral handling), provided both cables are within the Insulation O.D. Range and the connector meets the dimensional requirements shown below. Connector Dimensional Requirements Minimum Inches (mm) Maximum Inches (mm) Outside Diameter 0.69" (17,5 mm) 1.49" (38 mm) Length Aluminum (Al/Cu) Compression 5.00" (127 mm) Length Copper Compression and 3M Shearbolt Connector QCI 4/0-600 5.75" (146 mm) January 2013 78-8141-5583-0-A 3

Transcript of 3M Cold Shrink QS4 Integrated Splice Kit QS4-15JCN-4/0-500...3M Cold Shrink QS4 Integrated Splice...

Page 1: 3M Cold Shrink QS4 Integrated Splice Kit QS4-15JCN-4/0-500...3M Cold Shrink QS4 Integrated Splice Body QS4-15JCN-4/0-500 (1 ea.) b. Constant Force Springs (4 ea.) c. 3M Red Compound

3M™ Cold Shrink QS4 Integrated Splice Kit QS4-15JCN-4/0-500for Jacketed Concentric Neutral (JCN) and Flat Strap Neutral Cable

InstructionsIEEE Std. 40415 kV Class150 kV BIL

� CAUTION Working around energized systems may cause serious injury or death. Installation should

be performed by personnel familiar with good safety practice in handling electrical equipment. De-energize and ground all electrical systems before installing product.

Kit Selection TableKit Number Cable Insulation O.D. Range Conductor Size Range

QS4-15JCN-4/0-500 0.84"–1.38"(21,3–35,1 mm)

4/0 AWG–500 kcmil*(95-240 mm2)

* Splices (including size transitions) can be made to smaller or larger conductors (but larger conductors may require special neutral handling), provided both cables are within the Insulation O.D. Range and the connector meets the dimensional requirements shown below.

Connector Dimensional RequirementsMinimum Inches (mm) Maximum Inches (mm)

Outside Diameter 0.69" (17,5 mm) 1.49" (38 mm)

LengthAluminum (Al/Cu) Compression — 5.00" (127 mm)

LengthCopper Compression and 3M™ Shearbolt Connector QCI 4/0-600 — 5.75" (146 mm)

January 201378-8141-5583-0-A 3

Page 2: 3M Cold Shrink QS4 Integrated Splice Kit QS4-15JCN-4/0-500...3M Cold Shrink QS4 Integrated Splice Body QS4-15JCN-4/0-500 (1 ea.) b. Constant Force Springs (4 ea.) c. 3M Red Compound

2 78-8141-5583-0-A

1.0 Kit Contentsa. 3M™ Cold Shrink QS4 Integrated Splice Body QS4-15JCN-4/0-500 (1 ea.)

b. Constant Force Springs (4 ea.)

c. 3M™ Red Compound Tubes P55/R (non-silicone grease) (2 ea.)

d. Scotch® Rubber Mastic Tape 2228 Rolls, 2" x 36" (2 ea.)

e. Scotch® Mastic Strips 2230, 6" length (9 ea.)

f. Cold Shrink Adapter Tube (1 ea.*)

g. 3M™ Cable Cleaning Pads CC-3 (1 ea.)

h. Cut-back Template (1 ea.)

i. Instruction Booklet (1 ea.)

*Cold shrink adapter tube may not be included in all kits.

Note: Do not use knives to open plastic bags.

Note: Connector not shown, but if included, it is indicated on the packaging label.

Page 3: 3M Cold Shrink QS4 Integrated Splice Kit QS4-15JCN-4/0-500...3M Cold Shrink QS4 Integrated Splice Body QS4-15JCN-4/0-500 (1 ea.) b. Constant Force Springs (4 ea.) c. 3M Red Compound

78-8141-5583-0-A 3

2.0 Prepare Cables2.1 Check to be sure the cable fits within the kit ranges as shown on the cover page.

2.2 Prepare cables according to standard procedures. Refer to template provided or illustration below for proper dimensions (Figure 1).

11 3/4"(298 mm)

Cable Jacket Neutral Wires InsulationSemi-con

4"(102 mm)

7 1/4"(184 mm)

Figure 1

2.3 Clean or cover cable jacket 30" (760 mm) from jacket edge on side where splice body will be parked.

2.4 Select a Scotch® Mastic Strip 2230 from the kit and remove white release liners. Using light tension, apply a single wrap of mastic at the edge of the cable jacket and partially over the neutral wires. (Figure 2).

Cable Jacket

Neutral Wires

Scotch® Mastic Strip 2230

Semi-con

Figure 2

Page 4: 3M Cold Shrink QS4 Integrated Splice Kit QS4-15JCN-4/0-500...3M Cold Shrink QS4 Integrated Splice Body QS4-15JCN-4/0-500 (1 ea.) b. Constant Force Springs (4 ea.) c. 3M Red Compound

4 78-8141-5583-0-A

2.5 Carefully bend the cut neutral wires up and away from the cable semi-con. Fold neutral wires over cable jacket, taking care to keep wire profile low by following the concentric turn in the cable. Secure the ends of the neutral wires with one wrap of vinyl tape. Fold one Scotch® Mastic Strip 2230 in half lengthwise and apply one wrap only at cable jacket edge under the neutral wires (Figure 3). Knead mastic around neutral wires.

InsulationSemi-Con

Neutral Wires

Scotch® Mastic Strip 2230

Scotch® Mastic Strip 2230

Fold mastic strip in half lengthwise

Bend neutral wiresover cable jacket

Figure 3

2.6 Apply an additional single wrap of Scotch® Mastic Strip 2230 at the edge of the cable jacket and partially over the neutral wires. Overwrap mastic with vinyl tape, taking care not to extend tape along neutral wires (Figure 4).

Scotch® Mastic Strips 2230Overwrap with vinyl tapeCable Jacket

1 Wrap of Vinyl Tape

Figure 4

Page 5: 3M Cold Shrink QS4 Integrated Splice Kit QS4-15JCN-4/0-500...3M Cold Shrink QS4 Integrated Splice Body QS4-15JCN-4/0-500 (1 ea.) b. Constant Force Springs (4 ea.) c. 3M Red Compound

78-8141-5583-0-A 5

2.7 Slide integrated splice body onto clean cable jacket, loose core end first (Figure 5).

Loose core end

Integrated splice body Cleaned cable jacket

Figure 5

3.0 Install ConnectorNote: If using a crimp-type connector, go to step (3.3).

3.1 If using a 3M™ Shearbolt Connector QCI 4/0-600, refer to the instructions included with the connector for insulation cut-back dimension. Insulation removal length shall not exceed 3" (76 mm) from conductor end (Figure 6).

Refer to connector instructions for dimensions

Figure 6

3.2 Install 3M Shearbolt Connector QCI 4/0-600 according to the instructions included with the connector (Figure 7).

Connector

Shearbolt

Figure 7

Go to section 4.0 “Install Splice.”

Page 6: 3M Cold Shrink QS4 Integrated Splice Kit QS4-15JCN-4/0-500...3M Cold Shrink QS4 Integrated Splice Body QS4-15JCN-4/0-500 (1 ea.) b. Constant Force Springs (4 ea.) c. 3M Red Compound

6 78-8141-5583-0-A

3.3 If using a crimp type connector, remove cable insulation for 1/2 connector length plus an allowance* for increases in connector length due to crimping. Insulation removal length shall not exceed 2 7/8" (73 mm) from conductor end. Do not install connector now (Figure 8).

*Note: This assumes that the installer has determined the increased length of an aluminum connector crimped with a specific tool and die.

Aluminum (Al/Cu) Crimp Connector Growth ChartConductor Size Typical growth allowance (per end)

4/0 AWG-500 kcmil 1/4" (6 mm)

Note: 1) Copper connectors do not require a length change allowance. 2) Maximum aluminum connector crimped length allowed is 5.75" (146 mm).

One-half connector length+ growth allowance*

Figure 8

3.4 For 4/0 AWG through 350 kcmil copper connectors, or connectors with an O.D. between 0.69-0.84" (17,5-21,3 mm): Park cold shrink adapter tube on cable insulation (Figure 9).

Cold shrink adapter tube

Figure 9

Page 7: 3M Cold Shrink QS4 Integrated Splice Kit QS4-15JCN-4/0-500...3M Cold Shrink QS4 Integrated Splice Body QS4-15JCN-4/0-500 (1 ea.) b. Constant Force Springs (4 ea.) c. 3M Red Compound

78-8141-5583-0-A 7

3.5 Install connector. See table (on cover) for proper connector dimensions. (For standard 3M™ Connectors, refer to table at the end of this instruction for crimping information). Remove any excess oxidation inhibitor from connector ends if aluminum connector is used (Figure 10).

Connector

Figure 10

4.0 Install Splice4.1 Apply a tape marker to semi-con insulation shield on cable which does not contain splice. Measure 9"

(229 mm) from center of connector (Figure 11).

Tape Marker

Semi-con

9"(229 mm)

Figure 11

4.2 If using cold shrink adapter tube: Position adapter tube over the connector. Shrink adapter near center of connector by pulling and unwinding the loose core end in a counter-clockwise direction (Figure 12).

Cold shrink adapter tube

Figure 12

Page 8: 3M Cold Shrink QS4 Integrated Splice Kit QS4-15JCN-4/0-500...3M Cold Shrink QS4 Integrated Splice Body QS4-15JCN-4/0-500 (1 ea.) b. Constant Force Springs (4 ea.) c. 3M Red Compound

8 78-8141-5583-0-A

4.3 Clean cables using standard practice:

a. Do not allow solvent or abrasive to contact the cable semi-conductive insulation shield.

b. Do not reduce cable insulation diameter below 0.84" (21,3 mm) specified for the splice.

c. The insulation surface must be round, smooth and free of cuts/voids. Sanding may be necessary, finish sanding should be done with a 120 grit or higher electrical grade abrasive.

d. Make certain that the cable insulation is smooth, clean and dry before continuing.

4.4 Apply 3M™ Red Compound P55/R on cable insulations, making certain to fill in edge of cable semi-con. Do not use silicone grease (Figure 13).

Apply RedCompound

Apply RedCompound

Fill semi-con stepFill semi-con step

Figure 13

Note: This core installs differently than other cold shrink products.4.5 Position the splice body over connector area, aligning end of the splice body (not the core) at the center

of the tape marker. Slowly start to remove the splice core by pulling and unwinding the loose core end counterclockwise, allowing only ¼" (6 mm) of the splice to shrink onto the tape marker. Carefully slide the splice body off the tape marker by pulling and twisting until the entire tape marker is exposed. Continue removing the core to complete the splice body installation (Figure 14).

Note: The splice body ends must overlap onto the semi-con of each cable by at least 1/2" (13 mm).

Note: Do not push the splice body toward the tape marker as this may cause the end to roll under. If the end does roll under, DO NOT use sharp-edged tools to pull it out as this could cut and damage the splice.

Unwind Counter-clockwise

Align splice body with tape marker

Figure 14

Page 9: 3M Cold Shrink QS4 Integrated Splice Kit QS4-15JCN-4/0-500...3M Cold Shrink QS4 Integrated Splice Body QS4-15JCN-4/0-500 (1 ea.) b. Constant Force Springs (4 ea.) c. 3M Red Compound

78-8141-5583-0-A 9

5.0 Connect Shielding5.1 Remove the vinyl tape holding the shield sleeve on the rejacketing tube, and spread the shield sleeve out toward

the cable jacket.

Note: The 3M™ Cold Shrink Integrated Splice Body includes a pre-installed ground braid for external grounding on either side of the splice body. If not using the ground braid, it may be tied into the ground system with the shield sleeve using constant force springs as shown below.

5.2 Hand-tighten the shield sleeve outward and secure it (along with the ground braid if not grounding externally) to the neutral wires on either side of the splice using two constant force springs on each end between the vinyl tape at the jacket edge and the vinyl tape as shown (Figure 15).

Note: If using a ground strap for external grounding, leave room for a third constant force spring over the shield sock at the jacket end. Refer to step (6.5).

5.3 If shield sleeve extends beyond neutral wires, it may be interwoven with the constant force springs. Trim excess ground braid if needed. Cinch (tighten) the spring after wrapping the final winding (Figure 15).

Ground Braid

Constant Force SpringsCable Jacket

Rejacketing Tube

Vinyl Tape

Figure 15

5.4 Wrap two half-lapped layers of vinyl tape over the constant force springs (Figure 16).

Vinyl Tape

Figure 16

Page 10: 3M Cold Shrink QS4 Integrated Splice Kit QS4-15JCN-4/0-500...3M Cold Shrink QS4 Integrated Splice Body QS4-15JCN-4/0-500 (1 ea.) b. Constant Force Springs (4 ea.) c. 3M Red Compound

10 78-8141-5583-0-A

6.0 External Grounding (Optional)Note: Use these instructions if circuit grounding is required at this location.

Note: If using a ground strap for external grounding, go to step (6.5).

6.1 If using a ground wire: Connect a ground wire to the pre-installed ground braid on the integrated splice using an appropriate connector. Keep connector profile as low as possible. For C-tap or H-tap connectors, position flat against the cable. Crimp connector following the connector manufacturer’s recommendations (Figure 17).

Ground Wire

Connector

Ground Braid

Figure 17

6.2 Cut one mastic sealing strip into two equal pieces. Place one piece on the cable jacket centered under the ground wire near the jacket end. Roll two mastic strips into small rolls. Place one roll on either side of the ground wire. (Figure 18).

Ground Wire

Ground Wire

Rolled Mastic

Half Mastic Strip

Cable Jacket

Rolled Mastic

Half Mastic Strip

Figure 18

Page 11: 3M Cold Shrink QS4 Integrated Splice Kit QS4-15JCN-4/0-500...3M Cold Shrink QS4 Integrated Splice Body QS4-15JCN-4/0-500 (1 ea.) b. Constant Force Springs (4 ea.) c. 3M Red Compound

78-8141-5583-0-A 11

6.3 Place the other half mastic strip over the previously applied mastic and ground wire. Press the mastic around the ground wire and to the cable jacket (Figure 19).

Second Half Mastic StripGround Wire

Figure 19

6.4 Wrap two half-lapped layers of vinyl tape over the ground connector (Figure 20).

Vinyl Tape

Ground Wire

Mastic Seal for Ground Wire

Figure 20

Go to section 7.0 “Install Jacket.”

6.5 If using a ground strap (ground strap and constant force spring not included): Wrap the ground strap around the shield sleeve with the tails toward the cable jacket (Figure 21).

Ground Strap

Shield Sleeve

Figure 21

Page 12: 3M Cold Shrink QS4 Integrated Splice Kit QS4-15JCN-4/0-500...3M Cold Shrink QS4 Integrated Splice Body QS4-15JCN-4/0-500 (1 ea.) b. Constant Force Springs (4 ea.) c. 3M Red Compound

12 78-8141-5583-0-A

6.6 Secure ground strap to the shield sleeve using a constant force spring (Figure 22) .

Constant Force Spring

Figure 22

6.7 Overwrap the spring with two layers of stretched vinyl tape (Figure 23).

Vinyl Tape

Figure 23

6.8 Place one mastic sealing strip on the cable jacket under the solder blocks of the ground strap (Figure 24).

Solder Block

Mastic Strip

Figure 24

Page 13: 3M Cold Shrink QS4 Integrated Splice Kit QS4-15JCN-4/0-500...3M Cold Shrink QS4 Integrated Splice Body QS4-15JCN-4/0-500 (1 ea.) b. Constant Force Springs (4 ea.) c. 3M Red Compound

78-8141-5583-0-A 13

6.9 Place another mastic strip over the solder blocks. Press the mastic strips around the solder blocks and onto the cable jacket. If tails overlap at the solder blocks, place a piece of mastic between them (Figure 25).

Second Mastic Strip

Figure 25

7.0 Install JacketNote: Jacketing is not optional.

7.1 Wrap a roll of slightly stretched Scotch® Rubber Mastic Tape 2228, 2" x 36" around cable jacket at edge of cut neutrals (tacky side toward cable) (Figure 26). Stretch and tear off last 1–2" (25–50 mm) of mastic (Figure 27). If grounding was applied, apply tape over mastic strips.

2" rubber mastic 2" rubber mastic

Figure 26

Stretch and tear off last 1–2" (25–50 mm) of rubber mastic

Figure 27

Page 14: 3M Cold Shrink QS4 Integrated Splice Kit QS4-15JCN-4/0-500...3M Cold Shrink QS4 Integrated Splice Body QS4-15JCN-4/0-500 (1 ea.) b. Constant Force Springs (4 ea.) c. 3M Red Compound

14 78-8141-5583-0-A

7.2 Remove the clear plastic wrap. Install the rejacketing tube by twisting the tube (not the yellow liner) from side to side to start the movement. Then slide and unroll the tube over the constant force springs and rubber mastic. (Figure 28). Repeat on other side.

Twist to break seal,then slide tube

Liner

Figure 28

7.3 Cut off yellow liners and discard.

Figure 29

7.4 Connect optional grounding.

Note: In applications where the splice is regularly exposed to high levels of ultra-violet radiation (i.e. direct sunlight), wrap two half-lapped layers of Scotch® Super 33+™ Vinyl Electrical Tape or Scotch® Vinyl Electrical Tape Super 88 over the re-jacketing tube.

Page 15: 3M Cold Shrink QS4 Integrated Splice Kit QS4-15JCN-4/0-500...3M Cold Shrink QS4 Integrated Splice Body QS4-15JCN-4/0-500 (1 ea.) b. Constant Force Springs (4 ea.) c. 3M Red Compound

78-8141-5583-0-A 15

Crimping Tool - Die Sets (number of crimps/end)

3M™ Connector Number

Conductor Size (AWG or kcmil)

Burndy Thomas & Betts Corp.Square D Co. Anderson Div.

MD6 MY29 Y34A Y35, Y39, Y45*, Y46* Y1000** TBM 5 TBM 8 TBM 12 TBM 15

VC6-3**VC6-FT**

VC8C**

10008 (Cu) 4/0 BG(3) 4/0(1) A28R(2) U28RT(2) --- Purple(2) Purple(2) --- 54H(2) (2) ---

20008 (Al/Cu) 4/0 W660(4) 4/0(2) A28AR(2) U28ART(2) (1) --- White(4) --- 66(4) (2) ---

11008 (Cu) 4/0 BG(4) 4/0(2) A28R(3) U28RT(3) --- Purple(3) Purple(3) --- 54H(3) (3) ---

CI-4/0 (Al/Cu) 4/0 W-249(3) --- --- U28ART(2) --- --- Blue(4) --- 76(2) (2) ---

10009 (Cu) 250 W166(3) 250(1) A29R(2) U29RT(2) --- Yellow(2) Yellow(2) --- 62(2) (2) ---

20009 (Al/Cu) 250 W249(3) --- A29AR(2) U29ART(2) (1) --- --- 71H(2) 71H(2) (3) ---

11009 (Cu) 250 W166(4) 250(2) A29R(3) U29RT(3) --- Yellow(3) Yellow(3) --- 62(3) (3) ---

CI-250 (Al/Cu) 250 --- --- --- U31ART(2) --- --- --- 87H(2) 87H(2) (2) ---

10010 (Cu) 300 --- --- A30R(3) U30RT(2) --- --- White(2) --- 66(2) (2) ---

20010 (Al/Cu) 300 --- --- A30AR(2) U30ART(2) (1) --- --- 76H(3) 76(1) (2) ---

11010 (Cu) 300 --- --- A30R(3) U30RT(3) --- --- White(3) --- 66(3) (3) ---

CI-300 (Al/Cu) 300 --- --- --- U31ART(2) --- --- --- 87H(2) 87H(2) (2) ---

10011 (Cu) 350 --- --- A31R(2) U31RT(2) --- --- Red(3) --- 71H(3) (2) ---

20011 (Al/Cu) 350 --- --- --- U31ART(2) (1) --- --- 87H(3) 87H(3) (2) ---

11011 (Cu) 350 --- --- A31R(3) U31RT(3) --- --- Red(4) --- 71H(4) (3) ---

CI-350 (Al/Cu) 350 --- --- --- U31ART(2) --- --- --- 87H(2) 87H(2) (3) ---

20012 (Al/Cu) 400 --- --- --- U32ART(4) (1) --- --- 94H(4) 94H(4) (2) (2)

10014 (Cu) 500 --- --- A34R(2) U34RT(2) --- --- Brown(3) --- 87H(3) (2) ---

20014 (Al/Cu) 500 --- --- --- U34ART(4) (1) --- --- 106H(3) 106H(3) (2) (2)

11014 (Cu) 500 --- --- A34R(4) U34RT(3) --- --- Brown(4) --- 87H(4) (3) ---

CI-500 (Al/Cu) 500 --- --- --- U34ART(3) --- --- --- --- 106H(3) (3) ---

*Y45 and Y46 accept all Y35 dies ("U Series"). For Y45, use PT6515 adapter. For Y46, use PUADP adapter.

**Anderson VC6-3, VC6-FT, VC8C and Burndy Y1000 require no die set.

Page 16: 3M Cold Shrink QS4 Integrated Splice Kit QS4-15JCN-4/0-500...3M Cold Shrink QS4 Integrated Splice Body QS4-15JCN-4/0-500 (1 ea.) b. Constant Force Springs (4 ea.) c. 3M Red Compound

3M, Super33+ and Scotch are trademarks of 3M Company.

All other trademarks are property of their respective owners.

Important NoticeAll statements, technical information, and recommendations related to 3M's products are based on information believed to be reliable, but the accuracy or completeness is not guaranteed. Before using this product, you must evaluate it and determine if it is suitable for your intended application. You assume all risks and liability associated with such use. Any statements related to the product which are not contained in 3M's current publications, or any contrary statements contained on your purchase order shall have no force or effect unless expressly agreed upon, in writing, by an authorized officer of 3M.

Warranty; Limited Remedy; Limited Liability. This product will be free from defects in material and manufacture at the time of purchase. 3M MAKES NO OTHER WARRANTIES INCLUDING, BUT NOT LIMITED TO, ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. If this product is defective within the warranty period stated above, your exclusive remedy shall be, at 3M's option, to replace or repair the 3M product or refund the purchase price of the 3M product. Except where prohibited by law, 3M will not be liable for any indirect, special, incidental or consequential loss or damage arising from this 3M product, regardless of the legal theory asserted.

3Electrical Markets Division6801 River Place Blvd. Austin, TX 78726-9000 800.245.3573Fax 800.245.0329www.3M.com/electrical

Please Recycle. Printed in USA.© 3M 2013. All Rights Reserved.78-8141-5583-0-A