Relion ® 615 series Feeder Protection and Control REF615 Application Manual

description

REF 615

Transcript of 38ce8f2980f06d7eab5609d6eb798f4c_4_ABB_REF_615_appl_756378_enh

  • Relion 615 series

    Feeder Protection and ControlREF615Application Manual

  • Document ID: 1MRS756378Issued: 2010-09-24

    Revision: HProduct version: 3.0

    Copyright 2010 ABB. All rights reserved

  • CopyrightThis document and parts thereof must not be reproduced or copied without writtenpermission from ABB, and the contents thereof must not be imparted to a thirdparty, nor used for any unauthorized purpose.The software or hardware described in this document is furnished under a licenseand may be used, copied, or disclosed only in accordance with the terms of suchlicense.TrademarksABB and Relion are registered trademarks of ABB Group. All other brand orproduct names mentioned in this document may be trademarks or registeredtrademarks of their respective holders.WarrantyPlease inquire about the terms of warranty from your nearest ABB representative.

    ABB OyDistribution AutomationP.O. Box 699FI-65101 Vaasa, FinlandTelephone: +358 10 2211Facsimile: +358 10 22 41094http://www.abb.com/substationautomation

  • DisclaimerThe data, examples and diagrams in this manual are included solely for the conceptor product description and are not to be deemed as a statement of guaranteedproperties. All persons responsible for applying the equipment addressed in thismanual must satisfy themselves that each intended application is suitable andacceptable, including that any applicable safety or other operational requirementsare complied with. In particular, any risks in applications where a system failure and/or product failure would create a risk for harm to property or persons (including butnot limited to personal injuries or death) shall be the sole responsibility of theperson or entity applying the equipment, and those so responsible are herebyrequested to ensure that all measures are taken to exclude or mitigate such risks.This document has been carefully checked by ABB but deviations cannot becompletely ruled out. In case any errors are detected, the reader is kindly requestedto notify the manufacturer. Other than under explicit contractual commitments, inno event shall ABB be responsible or liable for any loss or damage resulting fromthe use of this manual or the application of the equipment.

  • ConformityThis product complies with the directive of the Council of the EuropeanCommunities on the approximation of the laws of the Member States relating toelectromagnetic compatibility (EMC Directive 2004/108/EC) and concerningelectrical equipment for use within specified voltage limits (Low-voltage directive2006/95/EC). This conformity is the result of tests conducted by ABB inaccordance with the product standards EN 50263 and EN 60255-26 for the EMCdirective, and with the product standards EN 60255-1 and EN 60255-27 for the lowvoltage directive. The IED is designed in accordance with the internationalstandards of the IEC 60255 series.

  • Table of contents

    Section 1 Introduction.......................................................................5This manual........................................................................................5Intended audience..............................................................................5Product documentation.......................................................................6

    Product documentation set............................................................6Document revision history.............................................................7Related documentation..................................................................8

    Symbols and conventions...................................................................8Safety indication symbols..............................................................8Manual conventions.......................................................................9Functions, codes and symbols......................................................9

    Section 2 REF615 overview...........................................................13Overview...........................................................................................13

    Product version history................................................................14PCM600 and IED connectivity package version..........................14

    Operation functionality......................................................................15Optional functions........................................................................15

    Physical hardware............................................................................15Local HMI.........................................................................................17

    Display.........................................................................................17LEDs............................................................................................18Keypad........................................................................................18

    Web HMI...........................................................................................19Authorization.....................................................................................20Communication.................................................................................21

    Section 3 REF615 standard configurations....................................23Standard configurations....................................................................23Connection diagrams........................................................................27Presentation of standard configurations...........................................33Standard configuration A..................................................................33

    Applications.................................................................................33Functions.....................................................................................34

    Default I/O connections..........................................................35Default disturbance recorder settings.....................................36

    Functional diagrams....................................................................37Functional diagrams for protection.........................................37Functional diagrams for disturbance recorder and tripcircuit supervision...................................................................43

    Table of contents

    REF615 1Application Manual

  • Functional diagrams for control and interlocking....................45Standard configuration B..................................................................47

    Applications.................................................................................47Functions.....................................................................................48

    Default I/O connections..........................................................49Default disturbance recorder settings.....................................50

    Functional diagrams....................................................................51Functional diagrams for protection.........................................51Functional diagram for disturbance recorder and tripcircuit supervision...................................................................57Functional diagrams for control and interlocking....................59

    Standard configuration C..................................................................63Applications.................................................................................63Functions.....................................................................................63

    Default I/O connections..........................................................64Default disturbance recorder settings.....................................65

    Functional diagrams....................................................................65Functional diagrams for protection.........................................66Functional diagram for disturbance recorder and tripcircuit supervision...................................................................71Functional diagrams for control and interlocking....................72

    Standard configuration D..................................................................74Applications.................................................................................74Functions.....................................................................................74

    Default I/O connections..........................................................75Default disturbance recorder settings.....................................76

    Functional diagrams....................................................................77Functional diagrams for protection.........................................77Functional diagram for disturbance recorder and tripcircuit supervision...................................................................82Functional diagrams for control and interlocking....................83

    Standard configuration E..................................................................86Applications.................................................................................86Functions.....................................................................................87

    Default I/O connections..........................................................88Default disturbance recorder settings.....................................89

    Functional diagrams....................................................................90Functional diagrams for protection.........................................90Functional diagram for disturbance recorder and tripcircuit supervision...................................................................96Functional diagrams for control and interlocking....................98

    Standard configuration F................................................................103Applications...............................................................................103Functions...................................................................................103

    Table of contents

    2 REF615Application Manual

  • Default I/O connections........................................................105Default disturbance recorder settings...................................106

    Functional diagrams..................................................................107Functional diagrams for protection.......................................107Functional diagram for disturbance recorder and tripcircuit supervision.................................................................116Functional diagrams for control and interlocking..................117

    Standard configuration G................................................................122Applications...............................................................................122Functions...................................................................................122

    Default I/O connections .......................................................124Default disturbance recorder settings...................................125Sensor settings.....................................................................126

    Functional diagrams .................................................................127Functional diagrams for protection ......................................127Functional diagram for disturbance recorder and tripcircuit supervision.................................................................135Functional diagrams for control and interlocking..................137

    Standard configuration H................................................................141Applications...............................................................................141Functions...................................................................................141

    Default I/O connections........................................................143Default disturbance recorder settings...................................144

    Functional diagrams..................................................................145Functional diagrams for protection.......................................145Functional diagram for disturbance recorder and tripcircuit supervision.................................................................153Functional diagrams for control and interlocking..................155

    Section 4 Requirements for measurement transformers..............161Current transformers......................................................................161

    Current transformer requirements for non-directionalovercurrent protection................................................................161

    Current transformer accuracy class and accuracy limitfactor....................................................................................161Non-directional overcurrent protection.................................162Example for non-directional overcurrent protection..............163

    Section 5 IED physical connections.............................................165Inputs..............................................................................................165

    Energizing inputs.......................................................................165Phase currents.....................................................................165Residual current...................................................................165Phase voltages.....................................................................165Residual voltage...................................................................166

    Table of contents

    REF615 3Application Manual

  • Sensor inputs.......................................................................166Auxiliary supply voltage input....................................................166Binary inputs..............................................................................166Optional light sensor inputs.......................................................168

    Outputs...........................................................................................169Outputs for tripping and controlling............................................169Outputs for signalling.................................................................169IRF.............................................................................................171

    Section 6 Glossary.......................................................................173

    Table of contents

    4 REF615Application Manual

  • Section 1 Introduction

    1.1 This manualThe application manual contains application descriptions and setting guidelinessorted per function. The manual can be used to find out when and for what purposea typical protection function can be used. The manual can also be used whencalculating settings.

    1.2 Intended audienceThis manual addresses the protection and control engineer responsible forplanning, pre-engineering and engineering.The protection and control engineer must be experienced in electrical powerengineering and have knowledge of related technology, such as communicationand protocols.

    1MRS756378 H Section 1Introduction

    REF615 5Application Manual

  • 1.3 Product documentation1.3.1 Product documentation set

    Plann

    ing &

    purch

    ase

    Engin

    eerin

    g

    Instal

    ling

    Comm

    ission

    ing

    Opera

    tion

    Maint

    enan

    ce

    Deco

    mmiss

    ioning

    deins

    tallin

    g & di

    spos

    al

    Application manual

    Operation manual

    Installation manual

    Service manual

    Engineering manual

    Commissioning manual

    Communication protocolmanual

    Technical manual

    Plann

    ing &

    purch

    ase

    Engin

    eerin

    g

    Instal

    ling

    Comm

    ission

    ing

    Opera

    tion

    Maint

    enan

    ce

    Deco

    mmiss

    ioning

    deins

    tallin

    g & di

    spos

    al

    Plann

    ing &

    purch

    ase

    Engin

    eerin

    g

    Instal

    ling

    Comm

    ission

    ing

    Opera

    tion

    Maint

    enan

    ce

    Deco

    mmiss

    ioning

    deins

    tallin

    g & di

    spos

    al

    Application manualApplication manual

    Operation manualOperation manual

    Installation manualInstallation manual

    Service manualService manual

    Engineering manualEngineering manual

    Commissioning manualCommissioning manual

    Communication protocolmanualCommunication protocolmanual

    Technical manualTechnical manual

    en07000220.vsdIEC07000220 V1 EN

    Figure 1: The intended use of manuals in different lifecyclesThe engineering manual contains instructions on how to engineer the IEDs usingthe different tools in PCM600. The manual provides instructions on how to set up aPCM600 project and insert IEDs to the project structure. The manual alsorecommends a sequence for engineering of protection and control functions, LHMIfunctions as well as communication engineering for IEC 61850 and othersupported protocols.The installation manual contains instructions on how to install the IED. Themanual provides procedures for mechanical and electrical installation. The chaptersare organized in chronological order in which the IED should be installed.The commissioning manual contains instructions on how to commission the IED.The manual can also be used by system engineers and maintenance personnel forassistance during the testing phase. The manual provides procedures for checkingof external circuitry and energizing the IED, parameter setting and configuration as

    Section 1 1MRS756378 HIntroduction

    6 REF615Application Manual

  • well as verifying settings by secondary injection. The manual describes the processof testing an IED in a substation which is not in service. The chapters are organizedin chronological order in which the IED should be commissioned.The operation manual contains instructions on how to operate the IED once it hasbeen commissioned. The manual provides instructions for monitoring, controllingand setting the IED. The manual also describes how to identify disturbances andhow to view calculated and measured power grid data to determine the cause of afault.The service manual contains instructions on how to service and maintain the IED.The manual also provides procedures for de-energizing, de-commissioning anddisposal of the IED.The application manual contains application descriptions and setting guidelinessorted per function. The manual can be used to find out when and for what purposea typical protection function can be used. The manual can also be used whencalculating settings.The technical manual contains application and functionality descriptions and listsfunction blocks, logic diagrams, input and output signals, setting parameters andtechnical data sorted per function. The manual can be used as a technical referenceduring the engineering phase, installation and commissioning phase, and duringnormal service.The communication protocol manual describes a communication protocolsupported by the IED. The manual concentrates on vendor-specific implementations.The point list manual describes the outlook and properties of the data pointsspecific to the IED. The manual should be used in conjunction with thecorresponding communication protocol manual.

    Some of the manuals are not available yet.

    1.3.2 Document revision historyDocument revision/date Product version HistoryA/2007-12-20 1.0 First releaseB/2008-02-08 1.0 Content updatedC/2008-07-02 1.1 Content updated to correspond to the

    product versionD/2009-03-04 2.0 Content updated to correspond to the

    product versionE/2009-07-03 2.0 Content updated

    Table continues on next page

    1MRS756378 H Section 1Introduction

    REF615 7Application Manual

  • Document revision/date Product version HistoryF/2010-06-11 3.0 Content updated to correspond to the

    product versionG/2010-06-29 3.0 Terminology correctedH/2010-09-24 3.0 Content corrected

    Download the latest documents from the ABB web site http://www.abb.com/substationautomation.

    1.3.3 Related documentationName of the document Document IDModbus Communication Protocol Manual 1MRS756468DNP3 Communication Protocol Manual 1MRS756709IEC 60870-5-103 Communication Protocol Manual 1MRS756710IEC 61850 Engineering Guide 1MRS756475Engineering Manual 1MRS757121Installation Manual 1MRS756375Operation Manual 1MRS756708Technical Manual 1MRS756887

    1.4 Symbols and conventions1.4.1 Safety indication symbols

    The electrical warning icon indicates the presence of a hazardwhich could result in electrical shock.

    The warning icon indicates the presence of a hazard which couldresult in personal injury.

    The caution icon indicates important information or warning relatedto the concept discussed in the text. It might indicate the presenceof a hazard which could result in corruption of software or damageto equipment or property.

    Section 1 1MRS756378 HIntroduction

    8 REF615Application Manual

  • The information icon alerts the reader to important facts andconditions.

    The tip icon indicates advice on, for example, how to design yourproject or how to use a certain function.

    Although warning hazards are related to personal injury, it should be understoodthat operation of damaged equipment could, under certain operational conditions,result in degraded process performance leading to personal injury or death.Therefore, comply fully with all warning and caution notices.

    1.4.2 Manual conventionsConventions used in IED manuals. A particular convention may not be used in thismanual. Abbreviations and acronyms in this manual are spelled out in the glossary. The

    glossary also contains definitions of important terms. Push button navigation in the LHMI menu structure is presented by using the

    push button icons, for example:To navigate between the options, use and .

    HMI menu paths are presented in bold, for example:Select Main menu/Settings.

    LHMI messages are shown in Courier font, for example:To save the changes in non-volatile memory, select Yes and press .

    Parameter names are shown in italics, for example:The function can be enabled and disabled with the Operation setting.

    Parameter values are indicated with quotation marks, for example:The corresponding parameter values are "On" and "Off".

    IED input/output messages and monitored data names are shown in Courierfont, for example:When the function starts, the START output is set to TRUE.

    1.4.3 Functions, codes and symbolsTable 1: REF615 Functions, codes and symbolsFunction IEC 61850 IEC 60617 IEC-ANSIProtectionThree-phase non-directionalovercurrent protection, low stage,instance 1

    PHLPTOC1 3I> (1) 51P-1 (1)

    Three-phase non-directionalovercurrent protection, high stage,instance 1

    PHHPTOC1 3I>> (1) 51P-2 (1)

    Table continues on next page

    1MRS756378 H Section 1Introduction

    REF615 9Application Manual

  • Function IEC 61850 IEC 60617 IEC-ANSIThree-phase non-directionalovercurrent protection, high stage,instance 2

    PHHPTOC2 3I>> (2) 51P-2 (2)

    Three-phase non-directionalovercurrent protection, instantaneousstage, instance 1

    PHIPTOC1 3I>>> (1) 50P/51P (1)

    Three-phase directional overcurrentprotection, low stage, instance 1 DPHLPDOC1 3I> -> (1) 67-1 (1)Three-phase directional overcurrentprotection, low stage, instance 2 DPHLPDOC2 3I> -> (2) 67-1 (2)Three-phase directional overcurrentprotection, high stage DPHHPDOC1 3I>> -> 67-2Non-directional earth-fault protection,low stage, instance 1 EFLPTOC1 Io> (1) 51N-1 (1)Non-directional earth-fault protection,low stage, instance 2 EFLPTOC2 Io> (2) 51N-1 (2)Non-directional earth-fault protection,high stage, instance 1 EFHPTOC1 Io>> (1) 51N-2 (1)Non-directional earth-fault protection,instantaneous stage EFIPTOC1 Io>>> 50N/51NDirectional earth-fault protection, lowstage, instance 1 DEFLPDEF1 Io> -> (1) 67N-1 (1)Directional earth-fault protection, lowstage, instance 2 DEFLPDEF2 Io> -> (2) 67N-1 (2)Directional earth-fault protection, highstage DEFHPDEF1 Io>> -> 67N-2Admittance based earth-faultprotection, instance 1 EFPADM1 Yo> -> (1) 21YN (1)Admittance based earth-faultprotection, instance 2 EFPADM2 Yo> -> (2) 21YN (2)Admittance based earth-faultprotection, instance 3 EFPADM3 Yo> -> (3) 21YN (3)Transient / intermittent earth-faultprotection INTRPTEF1 Io> -> IEF 67NIEFNon-directional (cross-country) earthfault protection, using calculated Io EFHPTOC1 Io>> (1) 51N-2 (1)Negative-sequence overcurrentprotection, instance 1 NSPTOC1 I2> (1) 46 (1)Negative-sequence overcurrentprotection, instance 2 NSPTOC2 I2> (2) 46 (2)Phase discontinuity protection PDNSPTOC1 I2/I1> 46PDResidual overvoltage protection,instance 1 ROVPTOV1 Uo> (1) 59G (1)Residual overvoltage protection,instance 2 ROVPTOV2 Uo> (2) 59G (2)Residual overvoltage protection,instance 3 ROVPTOV3 Uo> (3) 59G (3)Three-phase undervoltage protection,instance 1 PHPTUV1 3U< (1) 27 (1)

    Table continues on next page

    Section 1 1MRS756378 HIntroduction

    10 REF615Application Manual

  • Function IEC 61850 IEC 60617 IEC-ANSIThree-phase undervoltage protection,instance 2 PHPTUV2 3U< (2) 27 (2)Three-phase undervoltage protection,instance 3 PHPTUV3 3U< (3) 27 (3)Three-phase overvoltage protection,instance 1 PHPTOV1 3U> (1) 59 (1)Three-phase overvoltage protection,instance 2 PHPTOV2 3U> (2) 59 (2)Three-phase overvoltage protection,instance 3 PHPTOV3 3U> (3) 59 (3)Positive-sequence undervoltageprotection, instance 1 PSPTUV1 U1< (1) 47U+ (1)Negative-sequence overvoltageprotection, instance 1 NSPTOV1 U2> (1) 47O- (1)Frequency protection, instance 1 FRPFRQ1 f>/f/f/fF 49F

    Circuit breaker failure protection CCBRBRF1 3I>/Io>BF 51BF/51NBFThree-phase inrush detector INRPHAR1 3I2f> 68Master trip, instance 1 TRPPTRC1 Master Trip (1) 94/86 (1)Master trip, instance 2 TRPPTRC2 Master Trip (2) 94/86 (2)Arc protection, instance 1 ARCSARC1 ARC (1) 50L/50NL (1)Arc protection, instance 2 ARCSARC2 ARC (2) 50L/50NL (2)Arc protection, instance 3 ARCSARC3 ARC (3) 50L/50NL (3)ControlCircuit-breaker control CBXCBR1 I O CB I O CBDisconnector position indication,instance 1 DCSXSWI1 I O DC (1) I O DC (1)Disconnector position indication,instance 2 DCSXSWI2 I O DC (2) I O DC (2)Disconnector position indication,instance 3 DCSXSWI3 I O DC (3) I O DC (3)Earthing switch indication ESSXSWI1 I O ES I O ESAuto-reclosing DARREC1 O -> I 79Synchronism and energizing check SECRSYN1 SYNC 25Condition monitoringCircuit-breaker condition monitoring SSCBR1 CBCM CBCMTrip circuit supervision, instance 1 TCSSCBR1 TCS (1) TCM (1)Trip circuit supervision, instance 2 TCSSCBR2 TCS (2) TCM (2)Current circuit supervision CCRDIF1 MCS 3I MCS 3IFuse failure supervision SEQRFUF1 FUSEF 60

    Table continues on next page

    1MRS756378 H Section 1Introduction

    REF615 11Application Manual

  • Function IEC 61850 IEC 60617 IEC-ANSIMeasurementDisturbance recorder RDRE1 - -Three-phase current measurement,instance 1 CMMXU1 3I 3ISequence current measurement CSMSQI1 I1, I2, I0 I1, I2, I0Residual current measurement,instance 1 RESCMMXU1 Io InThree-phase voltage measurement VMMXU1 3U 3UResidual voltage measurement RESVMMXU1 Uo VnSequence voltage measurement VSMSQI1 U1, U2, U0 U1, U2, U0Three-phase power and energymeasurement, including power factor PEMMXU1 P, E P, EFrequency measurement FMMXU1 f f

    Section 1 1MRS756378 HIntroduction

    12 REF615Application Manual

  • Section 2 REF615 overview

    2.1 OverviewREF615 is a dedicated feeder IED (intelligent electronic device) designed for theprotection, control, measurement and supervision of utility substations andindustrial power systems including radial, looped and meshed distribution networkswith or without distributed power generation. REF615 is a member of ABBsRelion product family and part of its 615 protection and control product series.The 615 series IEDs are characterized by their compactness and withdrawable-unitdesign.Re-engineered from the ground up, the 615 series has been designed to unleash thefull potential of the IEC 61850 standard for communication and interoperabilitybetween substation automation devices.The IED provides main protection for overhead lines and cable feeders indistribution networks. The IED is also used as back-up protection in applications,where an independent and redundant protection system is required.Depending on the chosen standard configuration, the IED is adapted for theprotection of overhead line and cable feeders in isolated neutral, resistance earthed,compensated and solidly earthed networks. Once the standard configuration IEDhas been given the application-specific settings, it can directly be put into service.The 615 series IEDs support a range of communication protocols including IEC61850 with GOOSE messaging, IEC 60870-5-103, Modbus and DNP3.

    1MRS756378 H Section 2REF615 overview

    REF615 13Application Manual

  • 2.1.1 Product version historyProduct version Product history1.0 Product released1.1 IRIG-B

    Support for parallel protocols added: IEC 61850 and Modbus X130 BIO added: optional for variants B and D CB interlocking functionality enhanced TCS functionality in HW enhanced Non-volatile memory added

    2.0 Support for DNP3 serial or TCP/IP Support for IEC 60870-5-103 Voltage measurement and protection Power and energy measurement New standard configurations E and F Disturbance recorder upload via WHMI Fuse failure supervision

    3.0 New configurations G and H Additions to configurations A, B, E and F Application configurability support Analog GOOSE support Large display with single line diagram Enhanced mechanical design Increased maximum amount of events and fault records Admittance-based earth-fault protection Frequency measurement and protection Synchronism and energizing check Combi sensor inputs Multi-port Ethernet option

    2.1.2 PCM600 and IED connectivity package version Protection and Control IED Manager PCM600 Ver. 2.3 or later REF615 Connectivity Package Ver. 3.0 or later

    Parameter Setting Firmware Update Disturbance Handling Signal Monitoring Lifecycle Traceability Signal Matrix Communication Management IED Configuration Migration Configuration Wizard Label Printing IED User Management Application Configuration Graphical Display Editor

    Section 2 1MRS756378 HREF615 overview

    14 REF615Application Manual

  • Download connectivity packages from the ABB web site http://www.abb.com/substationautomation

    2.2 Operation functionality2.2.1 Optional functions

    Arc protection Autoreclosing Modbus TCP/IP or RTU/ASCII IEC 60870-5-103 DNP3 TCP/IP or serial Admittance-based earth-fault or directional earth-fault protection

    (configuration A, B, E, F and G only)

    2.3 Physical hardwareThe IED consists of two main parts: plug-in unit and case. The content depends onthe ordered functionality.Table 2: Plug-in unit and caseMain unit Slot ID Content optionsPlug-inunit

    - HMI Small (4 lines, 16 characters)Large (8 lines, 16 characters)

    X100 Auxiliary power/BOmodule

    48-250 V DC/100-240 V AC; or 24-60 V DC2 normally-open PO contacts1 change-over SO contacts1 normally-open SO contact2 double-pole PO contacts with TCS1 dedicated internal fault output contact

    X110 BI/O module Only with configurations B, D, E, F, G and H:8 binary inputs4 SO contacts

    X120 AI/BI module Only with configurations A and B:3 phase current inputs (1/5 A)1 residual current input (1/5 A or 0.2/1 A)1)1 residual voltage input (60-120 V)3 binary inputsOnly with configurations C, D, E, F and H:3 phase current inputs (1/5 A)1 residual current input (1/5 A or 0.2/1 A)1)4 binary inputs

    Table continues on next page

    1MRS756378 H Section 2REF615 overview

    REF615 15Application Manual

  • Main unit Slot ID Content optionsCase X130 AI/BI module Only with configurations E and F:

    3 phase voltage inputs (60-120 V)1 residual voltage input (60-120 V)4 binary inputs

    Sensor inputmodule

    Only with configuration G:3 combi sensor inputs (three-phase current and voltage)1 residual current input (0.2/1 A)1)

    AI/BI module Only with configuration H:3 phase voltage inputs (60-210 V)1 residual voltage input (60-210 V)1 reference voltage input for SECRSYN1 (60-210 V)4 binary inputs

    Optional BI/Omodule

    Optional for configurations B and D:6 binary inputs3 SO contacts

    X000 Optionalcommunicationmodule

    See technical manual for details about different type ofcommunication modules.

    1) The 0.2/1 A input is normally used in applications requiring sensitive earth-fault protection andfeaturing core-balance current transformers.

    Rated values of the current and voltage inputs are basic setting parameters of theIED. The binary input thresholds are selectable within the range 18176 V DC byadjusting the binary input setting parameters.The connection diagrams of different hardware modules are presented in this manual.

    See the installation manual for more information about the case andthe plug-in unit.

    Table 3: Number of physical connections in standard configurationsConf. Analog channels Binary channels

    CT VT Combi sensor BI BOA 4 1 - 3 6B 4 - - 11 (17)1) 10 (13)1)C 4 1 - 4 6D 4 - - 12 (18)1) 10 (13)1)E 4 52) - 16 10F 4 52) - 16 10G 1 - 33) 8 10H 4 5 - 16 10

    1) With optional BIO module2) One of the five channels reserved for future applications3) Combi sensor inputs for three-phase current and voltage

    Section 2 1MRS756378 HREF615 overview

    16 REF615Application Manual

  • 2.4 Local HMI

    REF615

    Overcurrent

    Dir. earth-fault

    Voltage protection

    Phase unbalance

    Thermal overload

    Breaker failure

    Disturb. rec. Triggered

    CB condition monitoring

    Supervision

    Arc detected

    Autoreclose shot in progr.

    A070704 V3 EN

    Figure 2: Example of 615 series LHMIThe LHMI of the IED contains the following elements: Display Buttons LED indicators Communication port

    The LHMI is used for setting, monitoring and controlling.

    2.4.1 DisplayThe LHMI includes a graphical display that supports two character sizes. Thecharacter size depends on the selected language. The amount of characters androws fitting the view depends on the character size.

    1MRS756378 H Section 2REF615 overview

    REF615 17Application Manual

  • Table 4: Characters and rows on the viewCharacter size Rows in view Characters on rowSmall, mono-spaced (6x12pixels)

    5 rows10 rows with large screen

    20

    Large, variable width (13x14pixels)

    4 rows8 rows with large screen

    min 8

    The display view is divided into four basic areas.1 2

    3 4

    A070705 V2 EN

    Figure 3: Display layout1 Header2 Icon3 Content4 Scroll bar (displayed when needed)

    2.4.2 LEDsThe LHMI includes three protection indicators above the display: Ready, Start andTrip.There are also 11 matrix programmable LEDs on front of the LHMI. The LEDscan be configured with PCM600 and the operation mode can be selected with theLHMI, WHMI or PCM600.

    2.4.3 KeypadThe LHMI keypad contains push-buttons which are used to navigate in differentviews or menus. With the push-buttons you can give open or close commands toone object in the primary circuit, for example, a circuit breaker, a contactor or adisconnector. The push-buttons are also used to acknowledge alarms, resetindications, provide help and switch between local and remote control mode.

    Section 2 1MRS756378 HREF615 overview

    18 REF615Application Manual

  • A071176 V1 EN

    Figure 4: LHMI keypad with object control, navigation and command push-buttons and RJ-45 communication port

    2.5 Web HMIThe WHMI enables the user to access the IED via a web browser. The supportedweb browser version is Internet Explorer 7.0 or later.

    WHMI is disabled by default.

    WHMI offers several functions. Programmable LEDs and event lists System supervision Parameter settings Measurement display Disturbance records Phasor diagram Single-line diagram

    The menu tree structure on the WHMI is almost identical to the one on the LHMI.

    1MRS756378 H Section 2REF615 overview

    REF615 19Application Manual

  • A070754 V3 EN

    Figure 5: Example view of the WHMIThe WHMI can be accessed locally and remotely. Locally by connecting your laptop to the IED via the front communication port. Remotely over LAN/WAN.

    2.6 AuthorizationThe user categories have been predefined for the LHMI and the WHMI, each withdifferent rights and default passwords.The default passwords can be changed with Administrator user rights.

    User authorization is disabled by default but WHMI always usesauthorization.

    Section 2 1MRS756378 HREF615 overview

    20 REF615Application Manual

  • Table 5: Predefined user categoriesUsername User rightsVIEWER Read only accessOPERATOR Selecting remote or local state with (only locally)

    Changing setting groups Controlling Clearing indications

    ENGINEER Changing settings Clearing event list Clearing disturbance records Changing system settings such as IP address, serial baud rate

    or disturbance recorder settings Setting the IED to test mode Selecting language

    ADMINISTRATOR All listed above Changing password Factory default activation

    For user authorization for PCM600, see PCM600 documentation.

    2.7 CommunicationThe IED supports a range of communication protocols including IEC 61850, IEC60870-5-103, Modbus and DNP3. Operational information and controls areavailable through these protocols. However, some communication functionality,for example, horizontal communication between the IEDs, is only enabled by theIEC 61850 communication protocol.The IEC 61850 communication implementation supports all monitoring andcontrol functions. Additionally, parameter settings, disturbance recordings andfault records can be accessed using the IEC 61850 protocol. Disturbance recordingsare available to any Ethernet-based application in the standard COMTRADE fileformat. The IED can send and receive binary signals from other IEDs (so calledhorizontal communication) using the IEC61850-8-1 GOOSE profile, where thehighest performance class with a total transmission time of 3 ms is supported.Further, the IED supports sending and receiving of analog values using GOOSEmessaging. The IED meets the GOOSE performance requirements for trippingapplications in distribution substations, as defined by the IEC 61850 standard. TheIED can simultaneously report events to five different clients on the station bus.The IED can support five simultaneous clients. If PCM600 reserves one clientconnection, only four client connections are left, for example, for IEC 61850 andModbus.

    1MRS756378 H Section 2REF615 overview

    REF615 21Application Manual

  • All communication connectors, except for the front port connector, are placed onintegrated optional communication modules. The IED can be connected to Ethernet-based communication systems via the RJ-45 connector (100Base-TX) or the fibre-optic LC connector (100Base-FX). An optional serial interface is available forRS-232/RS-485 communication.If connection to a serial bus is required, the 10-pinRS-485 screw-terminal or the fibre-optic ST connector can be used.

    Managed Ethernet switchwith RSTP support

    Managed Ethernet switchwith RSTP support

    RED615 REF615 RET615 REU615 REM615

    Client BClient A

    Network

    Network

    GUID-AB81C355-EF5D-4658-8AE0-01DC076E519C V1 EN

    Figure 6: Self-healing Ethernet ring solution

    The Ethernet ring solution supports the connection of up to thirty615 series IEDs. If more than 30 IEDs are to be connected, it isrecommended that the network is split into several rings with nomore than 30 IEDs per ring.

    Section 2 1MRS756378 HREF615 overview

    22 REF615Application Manual

  • Section 3 REF615 standard configurations

    3.1 Standard configurationsREF615 is available in eight alternative standard configurations. The standardsignal configuration can be altered by means of the graphical signal matrix or theoptional graphical application functionality of the Protection and Control IEDManager PCM600. Further, the application configuration functionality of PCM600supports the creation of multi-layer logic functions using various logical elements,including timers and flip-flops. By combining protection functions with logicfunction blocks, the IED configuration can be adapted to user-specific applicationrequirements.

    Table 6: Standard configurationsDescription Std. conf.Non-directional overcurrent and directional earth-fault protection A and BNon-directional overcurrent and non-directional earth-fault protection C and DNon-directional overcurrent and directional earth-fault protection with phase-voltage basedmeasurements EDirectional overcurrent and directional earth-fault protection with phase-voltage basedmeasurements, undervoltage and overvoltage protection FDirectional overcurrent and directional earth-fault protection, phase-voltage based protection andmeasurement functions, sensor inputs GNon-directional overcurrent and non-directional earth-fault protection, phase-voltage and frequencybased protection and measurement functions, synchro-check H

    Table 7: Supported functionsFunctionality A B C D E F G HProtection1)Three-phase non-directional overcurrentprotection, low stage, instance 1 - - Three-phase non-directional overcurrentprotection, high stage, instance 1 - - Three-phase non-directional overcurrentprotection, high stage, instance 2 - - Three-phase non-directional overcurrentprotection, instantaneous stage, instance 1 Three-phase directional overcurrentprotection, low stage, instance 1 - - - - - -Three-phase directional overcurrentprotection, low stage, instance 2 - - - - - -

    Table continues on next page

    1MRS756378 H Section 3REF615 standard configurations

    REF615 23Application Manual

  • Functionality A B C D E F G HThree-phase directional overcurrentprotection, high stage - - - - - -Non-directional earth-fault protection, lowstage, instance 1 - - 3) 3) - - - 3)

    Non-directional earth-fault protection, lowstage, instance 2 - - 3) 3) - - - 3)

    Non-directional earth-fault protection, highstage, instance 1 - - 3) 3) - - - 3)

    Non-directional earth-fault protection,instantaneous stage - - 3) 3) - - - 3)

    Directional earth-fault protection, lowstage, instance 1 2)3)5) 2)3)5) - - 2)3)4) 2)3)4) 2)3)6) -Directional earth-fault protection, lowstage, instance 2 2)3)5) 2)3)5) - - 2)3)4) 2)3)4) 2)3)6) -Directional earth-fault protection, highstage 2)3)5) 2)3)5) - - 2)3)4) 2)3)4) 2)3)6) -Admittance based earth-fault protection,instance 1 2)3)5) 2)3)5) - - 2)3)4) 2)3)4) 2)3)6) -Admittance based earth-fault protection,instance 2 2)3)5) 2)3)5) - - 2)3)4) 2)3)4) 2)3)6) -Admittance based earth-fault protection,instance 3 2)3)5) 2)3)5) - - 2)3)4) 2)3)4) 2)3)6) -Transient / intermittent earth-faultprotection 5)7) 5)7) - - 5)7) 5)7) -Non-directional (cross-country) earth faultprotection, using calculated Io 8) 8) - - 8) 8) 8) -Negative-sequence overcurrentprotection, instance 1 Negative-sequence overcurrentprotection, instance 2 Phase discontinuity protection Residual overvoltage protection, instance1 5) 5) - - 4) 4) 6) 4)

    Residual overvoltage protection, instance2 5) 5) - - 4) 4) 6) 4)

    Residual overvoltage protection, instance3 5) 5) - - 4) 4) 6) 4)

    Three-phase undervoltage protection,instance 1 - - - - - Three-phase undervoltage protection,instance 2 - - - - - Three-phase undervoltage protection,instance 3 - - - - - Three-phase overvoltage protection,instance 1 - - - - - Three-phase overvoltage protection,instance 2 - - - - - Three-phase overvoltage protection,instance 3 - - - - -

    Table continues on next page

    Section 3 1MRS756378 HREF615 standard configurations

    24 REF615Application Manual

  • Functionality A B C D E F G HPositive-sequence undervoltageprotection, instance 1 - - - - - -Negative-sequence overvoltageprotection, instance 1 - - - - - -Frequency protection, instance 1 - - - - - - - Frequency protection, instance 2 - - - - - - - Frequency protection, instance 3 - - - - - - - Three-phase thermal protection forfeeders, cables and distributiontransformers

    -

    Circuit breaker failure protection Three-phase inrush detector Master trip, instance 1 Master trip, instance 2 Arc protection, instance 1 o o o o o o o oArc protection, instance 2 o o o o o o o oArc protection, instance 3 o o o o o o o oControlCircuit-breaker control Disconnector position indication, instance1 - - Disconnector position indication, instance2 - - Disconnector position indication, instance3 - - Earthing switch indication - - Auto-reclosing o o o o o o o oSynchronism and energizing check - - - - - - - Condition monitoringCircuit-breaker condition monitoring - - Trip circuit supervision, instance 1 Trip circuit supervision, instance 2 Current circuit supervision - - - - Fuse failure supervision - - - - MeasurementDisturbance recorder Three-phase current measurement,instance 1 Sequence current measurement Residual current measurement, instance 1 Three-phase voltage measurement - - - - Residual voltage measurement - - - Sequence voltage measurement - - - -

    Table continues on next page

    1MRS756378 H Section 3REF615 standard configurations

    REF615 25Application Manual

  • Functionality A B C D E F G HThree-phase power and energymeasurement, including power factor - - - - Frequency measurement - - - - - - - = Included, = Optional at the time of the order

    1) Note that all directional protection functions can also be used in non-directional mode.2) Admittance based E/F can be selected as an alternative to directional E/F when ordering.3) Io selectable by parameter, Io measured as default.4) Uo selectable by parameter, Uo measured as default.5) Uo measured is always used.6) Uo calculated is always used.7) Io measured is always used.8) Io selectable by parameter, Io calculated as default.

    Section 3 1MRS756378 HREF615 standard configurations

    26 REF615Application Manual

  • 3.2 Connection diagrams

    A071288 V6 EN

    Figure 7: Connection diagram for the A and B configurations [1]

    [1] Additional BIO-module (X110 in the diagram) is included in the IED variant B

    1MRS756378 H Section 3REF615 standard configurations

    REF615 27Application Manual

  • A071290 V5 EN

    Figure 8: Connection diagram for the C and D configurations [2]

    [2] Additional BIO-module (X110 in the diagram) is included in the IED variant D

    Section 3 1MRS756378 HREF615 standard configurations

    28 REF615Application Manual

  • GUID-F7601942-ACF2-47E2-8F21-CD9C1D2BC1F0 V4 EN

    Figure 9: Connection diagram for the E and F configurations

    1MRS756378 H Section 3REF615 standard configurations

    REF615 29Application Manual

  • GUID-5D0135B3-3890-497A-8AAA-0362730C8682 V1 EN

    Figure 10: Connection diagram for the E and F configurations

    Section 3 1MRS756378 HREF615 standard configurations

    30 REF615Application Manual

  • GUID-B70F0C14-52B2-4213-8781-5A7CA1E40451 V1 EN

    Figure 11: Connection diagram for the G configuration

    1MRS756378 H Section 3REF615 standard configurations

    REF615 31Application Manual

  • GUID-E8E2F79F-3DD8-46BD-8DE7-87A30133A7AE V1 EN

    Figure 12: Connection diagram for the H configuration

    Section 3 1MRS756378 HREF615 standard configurations

    32 REF615Application Manual

  • 3.3 Presentation of standard configurationsFunctional diagramsThe functional diagrams describe the IED's functionality from the protection,measuring, condition monitoring, disturbance recording, control and interlockingperspective. Diagrams show the default functionality with simple symbol logicsforming principle diagrams. The external connections to primary devices are alsoshown, stating the default connections to measuring transformers. The positivemeasuring direction of directional protection functions is towards the outgoing feeder.The functional diagrams are divided into sections with each section constitutingone functional entity. The external connections are also divided into sections. Onlythe relevant connections for a particular functional entity are presented in eachsection.Protection function blocks are part of the functional diagram. They are identifiedbased on their IEC 61850 name but the IEC based symbol and the ANSI functionnumber are also included. Some function blocks, such as PHHPTOC, are usedseveral times in the configuration. To separate the blocks from each other, the IEC61850 name, IEC symbol and ANSI function number are appended with a runningnumber, that is an instance number, from one upwards. If the block has no suffixafter the IEC or ANSI symbol, the function block has been used, that is,instantiated, only once. The IEDs internal functionality and the externalconnections are separated with a dashed line presenting the IEDs physical casing.Signal Matrix and Application ConfigurationWith Signal Matrix and Application Configuration in PCM600, it is possible tomodify the standard configuration according to the actual needs. The IED isdelivered from the factory with default connections described in the functionaldiagrams for binary inputs, binary outputs, function-to-function connections andalarm LEDs. The Signal Matrix is used for GOOSE signal input engineering andfor making cross-references between the physical I/O signals and the functionblocks. The Signal Matrix tool cannot be used for adding or removing functionblocks, for example, GOOSE receive function blocks. The ApplicationConfiguration tool is used for these kind of operations. If a function block isremoved with Application Configuration, the function related data disappears fromthe menus as well as from the 61850 data model, with the exception of some basicfunction blocks, which are mandatory and thus cannot be removed from the IEDconfiguration by removing them from the Application Configuration.

    3.4 Standard configuration A3.4.1 Applications

    1MRS756378 H Section 3REF615 standard configurations

    REF615 33Application Manual

  • The standard configuration for non-directional overcurrent and directional earth-fault protection is mainly intended for cable and overhead-line feeder applicationsin isolated and resonant-earthed distribution networks.The IED with a standard configuration is delivered from the factory with defaultsettings and parameters. The end-user flexibility for incoming, outgoing andinternal signal designation within the IED enables this configuration to be furtheradapted to different primary circuit layouts and the related functionality needs bymodifying the internal functionality using PCM600.

    3.4.2 FunctionsTable 8: Functions included in the standard configuration AFunction IEC 61850 IEC ANSIProtectionThree-phase non-directional overcurrentprotection, low stage, instance 1 PHLPTOC1 3I> (1) 51P-1 (1)Three-phase non-directional overcurrentprotection, high stage, instance 1 PHHPTOC1 3I>> (1) 51P-2 (1)Three-phase non-directional overcurrentprotection, high stage, instance 2 PHHPTOC2 3I>> (2) 51P-2 (2)Three-phase non-directional overcurrentprotection, instantaneous stage, instance 1 PHIPTOC1 3I>>> (1) 50P/51P (1)Directional earth-fault protection, low stage,instance 1 DEFLPDEF1 Io> -> (1) 67N-1 (1)Directional earth-fault protection, low stage,instance 2 DEFLPDEF2 Io> -> (2) 67N-1 (2)Directional earth-fault protection, high stage DEFHPDEF1 Io>> -> 67N-2Admittance based earth-fault protection,instance 1 EFPADM1 Yo> -> (1) 21YN (1)Admittance based earth-fault protection,instance 2 EFPADM2 Yo> -> (2) 21YN (2)Admittance based earth-fault protection,instance 3 EFPADM3 Yo> -> (3) 21YN (3)Transient / intermittent earth-fault protection INTRPTEF1 Io> -> IEF 67NIEFNon-directional (cross-country) earth faultprotection, using calculated Io EFHPTOC1 Io>> (1) 51N-2 (1)Negative-sequence overcurrent protection,instance 1 NSPTOC1 I2> (1) 46 (1)Negative-sequence overcurrent protection,instance 2 NSPTOC2 I2> (2) 46 (2)Phase discontinuity protection PDNSPTOC1 I2/I1> 46PDResidual overvoltage protection, instance 1 ROVPTOV1 Uo> (1) 59G (1)Residual overvoltage protection, instance 2 ROVPTOV2 Uo> (2) 59G (2)Residual overvoltage protection, instance 3 ROVPTOV3 Uo> (3) 59G (3)Three-phase thermal protection for feeders,cables and distribution transformers T1PTTR1 3Ith>F 49F

    Table continues on next page

    Section 3 1MRS756378 HREF615 standard configurations

    34 REF615Application Manual

  • Function IEC 61850 IEC ANSICircuit breaker failure protection CCBRBRF1 3I>/Io>BF 51BF/51NBFThree-phase inrush detector INRPHAR1 3I2f> 68Master trip, instance 1 TRPPTRC1 Master Trip (1) 94/86 (1)Master trip, instance 2 TRPPTRC2 Master Trip (2) 94/86 (2)Arc protection, instance 1 ARCSARC1 ARC (1) 50L/50NL (1)Arc protection, instance 2 ARCSARC2 ARC (2) 50L/50NL (2)Arc protection, instance 3 ARCSARC3 ARC (3) 50L/50NL (3)ControlCircuit-breaker control CBXCBR1 I O CB I O CBAuto-reclosing DARREC1 O -> I 79Condition monitoringTrip circuit supervision, instance 1 TCSSCBR1 TCS (1) TCM (1)Trip circuit supervision, instance 2 TCSSCBR2 TCS (2) TCM (2)MeasurementDisturbance recorder RDRE1 - -Three-phase current measurement, instance 1 CMMXU1 3I 3ISequence current measurement CSMSQI1 I1, I2, I0 I1, I2, I0Residual current measurement, instance 1 RESCMMXU1 Io InResidual voltage measurement RESVMMXU1 Uo Vn

    3.4.2.1 Default I/O connectionsTable 9: Default connections for binary inputsBinary input Default usage Connector pinsX120-BI1 Blocking of overcurrent instantaneous stage X120-1,2X120-BI2 Circuit breaker closed position indication X120-3,2X120-BI3 Circuit breaker open position indication X120-4,2

    Table 10: Default connections for binary outputsBinary output Default usage Connector pinsX100-PO1 Close circuit breaker X100-6,7X100-PO2 Circuit breaker failure protection trip to upstream

    breakerX100-8,9

    X100-PO3 Open circuit breaker/trip coil 1 X100-15,16,17,18,19

    X100-PO4 Open circuit breaker/trip coil 2 X100-20,21,22,23,24

    X100-SO1 General start indication X100-10,11,12X100-SO2 General operate indication X100-13,14,15

    1MRS756378 H Section 3REF615 standard configurations

    REF615 35Application Manual

  • Table 11: Default connections for LEDsLED Default usage1 Non-directional overcurrent operate2 Directional/intermittent earth fault operate3 Double (cross country) earth fault or residual overvoltage operate4 Negative seq. overcurrent/phase discontinuity operate5 Thermal overload alarm6 Breaker failure operate7 Disturbance recorder triggered8 Not connected9 Trip circuit supervision alarm10 Arc protection operate11 Auto reclose in progress

    3.4.2.2 Default disturbance recorder settings

    Table 12: Default analog channel selection and text settingsChannel Selection and text1 IL12 IL23 IL34 Io5 Uo6 -7 -8 -9 -10 -11 -12 -

    Additionally, all the digital inputs that are connected by default are also enabledwith the setting. Default triggering settings are selected depending on theconnected input signal type. Typically all protection START signals are selected totrigger the disturbance recorded by default.

    Section 3 1MRS756378 HREF615 standard configurations

    36 REF615Application Manual

  • 3.4.3 Functional diagramsThe functional diagrams describe the default input, output, alarm LED and function-to-function connections. The default connections can be viewed and changed withPCM600 according to the application requirements, if necessary.The analog channels have fixed connections towards the different function blocksinside the IEDs standard configuration. Exceptions from this rule are the 12analog channels available for the disturbance recorder function. These channels arefreely selectable and a part of the disturbance recorders parameter settings.The analog channels are assigned to different functions. The common signalmarked with 3I represents the three phase currents. The signal marked with Iorepresents the measured residual current via a core balance current transformer.The signal marked with Uo represents the measured residual voltage via open deltaconnected voltage transformers.The EFHPTOC protection function block for double (cross-country) earth-faultsuses the calculated residual current originating from the measured phase currents.

    3.4.3.1 Functional diagrams for protection

    The functional diagrams describe the IEDs protection functionality in detail andpicture the factory set default connections.

    1MRS756378 H Section 3REF615 standard configurations

    REF615 37Application Manual

  • A071316 V4 EN

    Figure 13: Overcurrent protectionFour overcurrent stages are offered for overcurrent and short-circuit protection.The instantaneous stage (PHIPTOC1) can be blocked by energizing the binaryinput 1 (X120:1-2). Two negative sequence overcurrent stages (NSPTOC1 andNSPTOC2) are offered for phase unbalance protection. The inrush detectionblocks (INRPHAR1) output BLK2H enables either blocking the function ormultiplying the active settings for any of the described protection function blocks.All operate signals are connected to the Master Trip and to the alarm LEDs. LED 1is used for overcurrent and LED 4 for negative-sequence overcurrent protectionoperate indication. LED 4 is also used for phase discontinuity protection operateindication.

    Section 3 1MRS756378 HREF615 standard configurations

    38 REF615Application Manual

  • A071318 V5 EN

    Figure 14: Directional earth-fault protectionThree stages are offered for directional earth-fault protection. According to theorder code, the directional earth-fault protection method can be based onconventional directional earth-fault (DEFxPDEF) or admittance criteria(EFPADM). In addition, there is a dedicated protection stage (INTRPTEF) eitherfor transient-based earth-fault protection or for cable intermittent earth-faultprotection in compensated networks.

    1MRS756378 H Section 3REF615 standard configurations

    REF615 39Application Manual

  • A dedicated non-directional earth-fault protection block (EFHPTOC) is intendedfor protection against double earth-fault situations in isolated or compensatednetworks. This protection function uses the calculated residual current originatingfrom the phase currents.All operate signals are connected to the Master Trip as well as to the alarm LEDs.LED 2 is used for directional earth-fault and LED 3 for double earth-faultprotection operate indication.

    GUID-FA4DA9F8-324C-4727-A932-A350F82F3639 V1 EN

    Figure 15: Residual overvoltage protectionThe residual overvoltage protection (ROVPTOV) provides earth-fault protectionby detecting abnormal level of residual voltage. It can be used, for example, as anonselective backup protection for the selective directional earth-faultfunctionality. The operation signal is connected to alarm LED 3.

    Section 3 1MRS756378 HREF615 standard configurations

    40 REF615Application Manual

  • A071320 V5 EN

    Figure 16: Phase discontinuity, thermal overload and circuit breaker failureprotection

    The phase discontinuity protection (PDNPSTOC1) provides protection forinterruptions in the normal three-phase load supply, for example, in downedconductor situations. The operate signal of the phase discontinuity protection isconnected to the Master Trip and also to an alarm LED and the disturbancerecorder. The thermal overload protection (T1PTTR1) provides indication onoverload situations. The operate signal of the phase discontinuity protection isconnected to the Master Trip and also to an alarm LED. LED 4 is used for thephase discontinuity protection operate indication, the same as for negativesequence overcurrent protection operate indication, and LED 5 is used for thethermal overload protection alarm indication.The breaker failure protection (CCBRBRF1) is initiated via the start input by anumber of different protection stages in the IED. The breaker failure protectionfunction offers different operating modes associated with the circuit breakerposition and the measured phase and residual currents. The breaker failureprotection has two operating outputs: TRRET and TRBU. The TRRET operateoutput is used for retripping its own breaker through the Master Trip 2. The TRBUoutput is used to give a back-up trip to the breaker feeding upstream. For thispurpose, the TRBU operate output signal is connected to the output PO2 (X100:8-9). LED 6 is used for back-up (TRBU) operate indication.

    1MRS756378 H Section 3REF615 standard configurations

    REF615 41Application Manual

  • A071322 V5 EN

    Figure 17: Arc protectionArc protection (ARCSARC1...3) and autoreclosing (DARREC1) are included asoptional functions.The arc protection offers individual function blocks for three arc sensors that canbe connected to the IED. Each arc protection function block has two differentoperation modes, with or without the phase and residual current check. Operate

    Section 3 1MRS756378 HREF615 standard configurations

    42 REF615Application Manual

  • signals from the arc protection function blocks are connected to the Master Tripand also to the alarm LED 10 as a common operate indication.The autorecloser is configured to be initiated by operate signals from a number ofprotection stages through the INIT1...5 inputs. It is possible to create individualautoreclose sequences for each input.The autoreclose function can be blocked with the INHIBIT_RECL input. Bydefault, the operation of selected protection functions are connected to this input. Acontrol command to the circuit breaker, either local or remote, also blocks theautoreclose function via the CBXCBR-selected signal.The circuit breaker availability for the autoreclosure sequence is expressed with theCB_RDY input in DARREC1. In the configuration, this signal is not connected toany of the binary inputs. As a result, the function assumes that the breaker isavailable all the time.The autoreclose sequence in progress indication is connected to the alarm LED 11.

    3.4.3.2 Functional diagrams for disturbance recorder and trip circuitsupervision

    1MRS756378 H Section 3REF615 standard configurations

    REF615 43Application Manual

  • A071324 V5 EN

    Figure 18: Disturbance recorderAll start and operate signals from the protection stages are routed to trigger thedisturbance recorder or alternatively only to be recorded by the disturbancerecorder depending on the parameter settings. Additionally, the selectedautorecloser, the ARC protection signals and the three binary inputs from X120 arealso connected.Two separate trip circuit supervision functions are included, TCSSCBR1 for PO3(X100:15-19) and TCSSCBR2 for PO4 (X100:20-24). Both functions are blockedby the Master Trip (TRPPTRC1 and TRPPTRC2) and the circuit breaker opensignal. The TCS alarm indication is connected to LED 9.

    Section 3 1MRS756378 HREF615 standard configurations

    44 REF615Application Manual

  • By default it is expected that there is no external resistor in thecircuit breaker tripping coil circuit connected parallel with circuitbreaker normally open auxiliary contact.

    3.4.3.3 Functional diagrams for control and interlocking

    A071326 V5 EN

    Figure 19: Master tripThe operate signals from the protections are connected to the two trip outputcontacts PO3 (X100:15-19) and PO4 (X100:20-24) via the corresponding MasterTrips TRPPTRC1 and TRPPTRC2. Open control commands to the circuit breakerfrom local or remote CBXCBR1-exe_op or from the auto-recloser DARREC1-open_cb are connected directly to the output PO3 (X100:15-19).TRPPTRC1 and 2 provide the lockout/latching function, event generation and thetrip signal duration setting. If the lockout operation mode is selected, one binaryinput can be reassigned to the RST_LKOUT input of the Master Trip to enableexternal reset with a push button.

    1MRS756378 H Section 3REF615 standard configurations

    REF615 45Application Manual

  • A071328 V4 EN

    Figure 20: Circuit breaker controlThe ENA_CLOSE input, which enables the closing of the circuit breaker, is astatus of the Master Trip in the breaker control function block CBXCBR. The openoperation is always enabled.

    If the ENA_CLOSE signal is completely removed from the breakercontrol function block CBXCBR with PCM600, the functionassumes that the breaker close commands are allowed continuously.

    Section 3 1MRS756378 HREF615 standard configurations

    46 REF615Application Manual

  • A071330 V4 EN

    Figure 21: Alarm indicationThe signal outputs from the IED are connected to give dedicated information on: Start of any protection function SO1 (X100:10-12) Operation (trip) of any protection function SO2 (X100: 13-15)

    TPGAPC are timers and used for setting the minimum pulse length for the outputs.There are four generic timers (TPGAPC1..4) available in the IED. The remainingones not described in the functional diagram are available in PCM600 forconnection where applicable.

    3.5 Standard configuration B3.5.1 Applications

    The standard configuration for non-directional overcurrent and directional earth-fault protection is mainly intended for cable and overhead-line feeder applicationsin isolated and resonant-earthed distribution networks.The IED with a standard configuration is delivered from the factory with defaultsettings and parameters. The end-user flexibility for incoming, outgoing and

    1MRS756378 H Section 3REF615 standard configurations

    REF615 47Application Manual

  • internal signal designation within the IED enables this configuration to be furtheradapted to different primary circuit layouts and the related functionality needs bymodifying the internal functionality using PCM600.

    3.5.2 FunctionsTable 13: Functions included in the standard configuration BFunction IEC 61850 IEC ANSIProtectionThree-phase non-directional overcurrentprotection, low stage, instance 1 PHLPTOC1 3I> (1) 51P-1 (1)Three-phase non-directional overcurrentprotection, high stage, instance 1 PHHPTOC1 3I>> (1) 51P-2 (1)Three-phase non-directional overcurrentprotection, high stage, instance 2 PHHPTOC2 3I>> (2) 51P-2 (2)Three-phase non-directional overcurrentprotection, instantaneous stage, instance 1 PHIPTOC1 3I>>> (1) 50P/51P (1)Directional earth-fault protection, low stage,instance 1 DEFLPDEF1 Io> -> (1) 67N-1 (1)Directional earth-fault protection, low stage,instance 2 DEFLPDEF2 Io> -> (2) 67N-1 (2)Directional earth-fault protection, high stage DEFHPDEF1 Io>> -> 67N-2Admittance based earth-fault protection,instance 1 EFPADM1 Yo> -> (1) 21YN (1)Admittance based earth-fault protection,instance 2 EFPADM2 Yo> -> (2) 21YN (2)Admittance based earth-fault protection,instance 3 EFPADM3 Yo> -> (3) 21YN (3)Transient / intermittent earth-fault protection INTRPTEF1 Io> -> IEF 67NIEFNon-directional (cross-country) earth faultprotection, using calculated Io EFHPTOC1 Io>> (1) 51N-2 (1)Negative-sequence overcurrent protection,instance 1 NSPTOC1 I2> (1) 46 (1)Negative-sequence overcurrent protection,instance 2 NSPTOC2 I2> (2) 46 (2)Phase discontinuity protection PDNSPTOC1 I2/I1> 46PDResidual overvoltage protection, instance 1 ROVPTOV1 Uo> (1) 59G (1)Residual overvoltage protection, instance 2 ROVPTOV2 Uo> (2) 59G (2)Residual overvoltage protection, instance 3 ROVPTOV3 Uo> (3) 59G (3)Three-phase thermal protection for feeders,cables and distribution transformers T1PTTR1 3Ith>F 49FCircuit breaker failure protection CCBRBRF1 3I>/Io>BF 51BF/51NBFThree-phase inrush detector INRPHAR1 3I2f> 68Master trip, instance 1 TRPPTRC1 Master Trip (1) 94/86 (1)Master trip, instance 2 TRPPTRC2 Master Trip (2) 94/86 (2)Arc protection, instance 1 ARCSARC1 ARC (1) 50L/50NL (1)

    Table continues on next page

    Section 3 1MRS756378 HREF615 standard configurations

    48 REF615Application Manual

  • Function IEC 61850 IEC ANSIArc protection, instance 2 ARCSARC2 ARC (2) 50L/50NL (2)Arc protection, instance 3 ARCSARC3 ARC (3) 50L/50NL (3)ControlCircuit-breaker control CBXCBR1 I O CB I O CBDisconnector position indication, instance 1 DCSXSWI1 I O DC (1) I O DC (1)Disconnector position indication, instance 2 DCSXSWI2 I O DC (2) I O DC (2)Disconnector position indication, instance 3 DCSXSWI3 I O DC (3) I O DC (3)Earthing switch indication ESSXSWI1 I O ES I O ESAuto-reclosing DARREC1 O -> I 79Condition monitoringCircuit-breaker condition monitoring SSCBR1 CBCM CBCMTrip circuit supervision, instance 1 TCSSCBR1 TCS (1) TCM (1)Trip circuit supervision, instance 2 TCSSCBR2 TCS (2) TCM (2)MeasurementDisturbance recorder RDRE1 - -Three-phase current measurement, instance 1 CMMXU1 3I 3ISequence current measurement CSMSQI1 I1, I2, I0 I1, I2, I0Residual current measurement, instance 1 RESCMMXU1 Io InResidual voltage measurement RESVMMXU1 Uo Vn

    3.5.2.1 Default I/O connectionsTable 14: Default connections for binary inputsBinary input Default usage Connector pinsX110-BI2 Directional earth fault protection's basic angle control X110-3,4X110-BI3 Circuit breaker low gas pressure indication X110-5,6X110-BI4 Circuit breaker spring charged indication X110-6,7X110-BI5 Circuit breaker truck in (service position) indication X110-8,9X110-BI6 Circuit breaker truck out (test position) indication X110-10,9X110-BI7 Earthing switch closed indication X110-11,12X110-BI8 Earthing switch open indication X110-13,12X120-BI1 Blocking of overcurrent instantaneous stage X120-1,2X120-BI2 Circuit breaker closed indication X120-3,2X120-BI3 Circuit breaker open indication X120-4,2

    1MRS756378 H Section 3REF615 standard configurations

    REF615 49Application Manual

  • Table 15: Default connections for binary outputsBinary output Default usage Connector pinsX100-PO1 Close circuit breaker X100-6,7X100-PO2 Circuit breaker failure protection trip to upstream

    breakerX100-8,9

    X100-PO3 Open circuit breaker/trip coil 1 X100-15,16,17,18,19

    X100-PO4 Open circuit breaker/trip coil 2 X100-20,21,22,23,24

    X100-SO1 General start indication X100-10,11,12X100-SO2 General operate indication X100-13,14,15X110-SO1 Upstream overcurrent blocking X110-14,15,16X110-SO2 Overcurrent operate alarm X110-17,18,19X110-SO3 Earth fault operate alarm X110-20,21,22

    Table 16: Default connections for LEDsLED Default usage1 Non-directional overcurrent operate2 Directional/intermittent earth fault operate3 Double (cross country) earth fault or residual overvoltage operate4 Negative seq. overcurrent/phase discontinuity operate5 Thermal overload alarm6 Breaker failure operate7 Disturbance recorder triggered8 Circuit breaker condition monitoring alarm9 Trip circuit supervision alarm10 Arc protection operate11 Auto reclose in progress

    3.5.2.2 Default disturbance recorder settings

    Table 17: Default analog channel selection and text settingsChannel Selection and text1 IL12 IL23 IL34 Io5 Uo6 -7 -

    Table continues on next page

    Section 3 1MRS756378 HREF615 standard configurations

    50 REF615Application Manual

  • Channel Selection and text8 -9 -10 -11 -12 -

    Additionally, all the digital inputs that are connected by default are also enabledwith the setting. Default triggering settings are selected depending on theconnected input signal type. Typically all protection START signals are selected totrigger the disturbance recorded by default.

    3.5.3 Functional diagramsThe functional diagrams describe the default input, output, alarm LED and function-to-function connections. The default connections can be viewed and changed withPCM600 according to the application requirements, if necessary.The analog channels have fixed connections towards the different function blocksinside the IEDs standard configuration. Exceptions from this rule are the 12analog channels available for the disturbance recorder function. These channels arefreely selectable and a part of the disturbance recorders parameter settings.The analog channels are assigned to different functions. The common signalmarked with 3I represents the three phase currents. The signal marked with Iorepresents the measured residual current via a core balance current transformer.The signal marked with Uo represents the measured residual voltage via open deltaconnected voltage transformers.The EFHPTOC protection function block for double (cross-country) earth-faultsuses the calculated residual current originating from the measured phase currents.

    3.5.3.1 Functional diagrams for protection

    The functional diagrams describe the IEDs protection functionality in detail andpicture the factory set default connections.

    1MRS756378 H Section 3REF615 standard configurations

    REF615 51Application Manual

  • A071332 V5 EN

    Figure 22: Overcurrent protectionFour overcurrent stages are offered for overcurrent and short-circuit protection.The instantaneous stage (PHIPTOC1) can be blocked by energizing the binaryinput 1 (X120:1-2). Two negative sequence overcurrent stages (NSPTOC1 andNSPTOC2) are offered for phase unbalance protection. The inrush detectionblocks (INRPHAR1) output BLK2H enables either blocking the function ormultiplying the active settings for any of the described protection function blocks.All operate signals are connected to the Master Trip and to the alarm LEDs. LED 1is used for overcurrent and LED 4 for negative-sequence overcurrent protectionoperate indication. LED 4 is also used for phase discontinuity protection operateindication.The upstream blocking from the start of the overcurrent second high stage(PHHPTOC2) is connected to the output SO1 (X110:14-16). This output is usedfor sending a blocking signal to the relevant overcurrent protection stage of theIED at the infeeding bay.

    Section 3 1MRS756378 HREF615 standard configurations

    52 REF615Application Manual

  • A071334 V5 EN

    Figure 23: Directional earth-fault protectionThree stages are offered for directional earth-fault protection. According to theorder code, the directional earth-fault protection method can be based onconventional directional earth-fault (DEFxPDEF) or admittance criteria(EFPADM). In addition, there is a dedicated protection stage (INTRPTEF) eitherfor transient-based earth-fault protection or for cable intermittent earth-faultprotection in compensated networks.A dedicated non-directional earth-fault protection block (EFHPTOC) is intendedfor protection against double earth-fault situations in isolated or compensated

    1MRS756378 H Section 3REF615 standard configurations

    REF615 53Application Manual

  • networks. This protection function uses the calculated residual current originatingfrom the phase currents.The binary input 2 (X110:3-4) is intended for directional earth-fault protectionblocks relay characteristic angle (RCA: 0/-90) or operation mode (I0Sin/I0Cos) change. All operate signals are connected to the Master Trip as well as tothe alarm LEDs. LED 2 is used for directional earth-fault and LED 3 for double earth-fault protection operate indication.

    GUID-B322E1D5-FF56-44AD-A777-9475D65CDCBD V1 EN

    Figure 24: Residual overvoltage protectionThe residual overvoltage protection (ROVPTOV) provides earth-fault protectionby detecting abnormal level of residual voltage. It can be used, for example, as anonselective backup protection for the selective directional earth-faultfunctionality. The operation signal is connected to alarm LED 3.

    Section 3 1MRS756378 HREF615 standard configurations

    54 REF615Application Manual

  • A071320 V5 EN

    Figure 25: Phase discontinuity, thermal overload and circuit breaker failureprotection

    The phase discontinuity protection (PDNPSTOC1) provides protection forinterruptions in the normal three-phase load supply, for example, in downedconductor situations. The operate signal of the phase discontinuity protection isconnected to the Master Trip and also to an alarm LED and the disturbancerecorder. The thermal overload protection (T1PTTR1) provides indication onoverload situations. The operate signal of the phase discontinuity protection isconnected to the Master Trip and also to an alarm LED. LED 4 is used for thephase discontinuity protection operate indication, the same as for negativesequence overcurrent protection operate indication, and LED 5 is used for thethermal overload protection alarm indication.The breaker failure protection (CCBRBRF1) is initiated via the start input by anumber of different protection stages in the IED. The breaker failure protectionfunction offers different operating modes associated with the circuit breakerposition and the measured phase and residual currents. The breaker failureprotection has two operating outputs: TRRET and TRBU. The TRRET operateoutput is used for retripping its own breaker through the Master Trip 2. The TRBUoutput is used to give a back-up trip to the breaker feeding upstream. For thispurpose, the TRBU operate output signal is connected to the output PO2 (X100:8-9). LED 6 is used for back-up (TRBU) operate indication.

    1MRS756378 H Section 3REF615 standard configurations

    REF615 55Application Manual

  • A071338 V6 EN

    Figure 26: Arc protectionArc protection (ARCSARC1...3) and autoreclosing (DARREC1) are included asoptional functions.The arc protection offers individual function blocks for three arc sensors that canbe connected to the IED. Each arc protection function block has two different

    Section 3 1MRS756378 HREF615 standard configurations

    56 REF615Application Manual

  • operation modes, with or without the phase and residual current check. Operatesignals from the arc protection function blocks are connected to the Master Tripand also to the alarm LED 10 as a common operate indication.The autorecloser is configured to be initiated by operate signals from a number ofprotection stages through the INIT1...5 inputs. It is possible to create individualautoreclose sequences for each input.The autoreclose function can be blocked with the INHIBIT_RECL input. Bydefault, the operation of selected protection functions are connected to this input. Acontrol command to the circuit breaker, either local or remote, also blocks theautoreclose function via the CBXCBR-selected signal.The circuit breaker availability for the autoreclosure sequence is expressed with thebinary input 4 (X110:6-7) by connecting the input signal to the CB_RDY input. Incase this signal is completely removed from the autoreclose function block withPCM600, the function assumes that the breaker is available all the time.The autoreclose sequence in progress indication is connected to the alarm LED 11.

    3.5.3.2 Functional diagram for disturbance recorder and trip circuit supervision

    1MRS756378 H Section 3REF615 standard configurations

    REF615 57Application Manual

  • A071324 V5 EN

    Figure 27: Disturbance recorderAll start and operate signals from the protection stages are routed to trigger thedisturbance recorder or alternatively only to be recorded by the disturbancerecorder depending on the parameter settings. Additionally, the selectedautorecloser, the ARC protection signals and the three binary inputs from X120 arealso connected.Two separate trip circuit supervision functions are included, TCSSCBR1 for PO3(X100:15-19) and TCSSCBR2 for PO4 (X100:20-24). Both functions are blockedby the Master Trip (TRPPTRC1 and TRPPTRC2) and the circuit breaker opensignal. The TCS alarm indication is connected to LED 9.

    Section 3 1MRS756378 HREF615 standard configurations

    58 REF615Application Manual

  • By default it is expected that there is no external resistor in thecircuit breaker tripping coil circuit connected parallel with circuitbreaker normally open auxiliary contact.

    3.5.3.3 Functional diagrams for control and interlocking

    A071326 V5 EN

    Figure 28: Master tripThe operate signals from the protections are connected to the two trip outputcontacts PO3 (X100:15-19) and PO4 (X100:20-24) via the corresponding MasterTrips TRPPTRC1 and TRPPTRC2. Open control commands to the circuit breakerfrom local or remote CBXCBR1-exe_op or from the auto-recloser DARREC1-open_cb are connected directly to the output PO3 (X100:15-19).TRPPTRC1 and 2 provide the lockout/latching function, event generation and thetrip signal duration setting. If the lockout operation mode is selected, one binaryinput can be reassigned to the RST_LKOUT input of the Master Trip to enableexternal reset with a push button.

    1MRS756378 H Section 3REF615 standard configurations

    REF615 59Application Manual

  • A071344 V5 EN

    Figure 29: Circuit breaker controlThere are three disconnector status blocks (DCSXSWI13) available in the IED.The remaining two not described in the functional diagram are available inPCM600 for connection where applicable.The binary inputs 5 and 6 of the additional card X110 are used for busbardisconnector (DCSXSWI1) or circuit-breaker truck position indication.Table 18: Device positions indicated by binary inputs 5 and 6Primary device position Input to be energized Input 5 (X110:8-9) Input 6 (X110:10-9)Busbar disconnector closed x Busbar disconnector open xCircuit breaker truck in service position x Circuit breaker truck in test position x

    The binary inputs 7 and 8 (X110:11-13) are designed for the position indication ofthe line-side earth switch.The circuit breaker closing is enabled when the ENA_CLOSE input is activated.The input can be activated by the configuration logic, which is a combination ofthe disconnector or breaker truck and earth-switch position statuses and the statuses

    Section 3 1MRS756378 HREF615 standard configurations

    60 REF615Application Manual

  • of the master trip logics and gas pressure alarm and circuit-breaker spring charging.This combination of interlocking conditions is called LOCAL_FEEDER_READYand is transferred also to the remote end via binary signal transfer. The OKPOSoutput from DCSXSWI defines if the disconnector or breaker truck is definitelyeither open (in test position) or close (in service position). This, together with theopen earth-switch and non-active trip signals, activates the close-enable signal tothe circuit breaker control function block. The open operation is always enabled.The auto-recloser close command signals are directly connected to the outputcontact PO1 (X100:6-7).The ITL_BYPASS input can be used, for example, to always enable the closing ofthe circuit breaker when the circuit breaker truck is in the test position, despite ofthe interlocking conditions being active when the circuit breaker truck is closed inservice position.

    If the ENA_CLOSE signal is completely removed from the breakercontrol function block CBXCBR with PCM600, the functionassumes that the breaker close commands are allowed continuously.

    If REMOTE_FEEDER_READY information is missing, forexample in case of protection communication not connected, itdisables the circuit breaker closing in the local IED.

    The circuit breaker condition monitoring function (SSCBR) supervises the circuitbreaker status based on the binary input information connected and measuredcurrent levels. The function introduces various supervision methods. Thecorresponding supervision alarm signals are routed to LED 8.

    1MRS756378 H Section 3REF615 standard configurations

    REF615 61Application Manual

  • A071346 V5 EN

    Figure 30: Alarm indicationThe signal outputs from the IED are connected to give dedicated information on: Start of any protection function SO1 (X100:10-12) Operation (trip) of any protection function SO2 (X100: 13-15)

    TPGAPC are timers and used for setting the minimum pulse length for the outputs.There are four generic timers (TPGAPC1..4) available in the IED. The remainingones not described in the functional diagram are available in PCM600 forconnection where applicable.

    Section 3 1MRS756378 HREF615 standard configurations

    62 REF615Application Manual

  • 3.6 Standard configuration C3.6.1 Applications

    The standard configuration for non-directional overcurrent and non-directional earth-fault protection is mainly intended for cable and overhead-line feeder applicationsin directly or resistance earthed distribution networks.The IED with a standard configuration is delivered from the factory with defaultsettings and parameters. The end-user flexibility for incoming, outgoing andinternal signal designation within the IED enables this configuration to be furtheradapted to different primary circuit layouts and the related functionality needs bymodifying the internal functionality using PCM600.

    3.6.2 FunctionsTable 19: Functions included in the standard configuration CFunction IEC 61850 IEC ANSIProtectionThree-phase non-directional overcurrentprotection, low stage, instance 1 PHLPTOC1 3I> (1) 51P-1 (1)Three-phase non-directional overcurrentprotection, high stage, instance 1 PHHPTOC1 3I>> (1) 51P-2 (1)Three-phase non-directional overcurrentprotection, high stage, instance 2 PHHPTOC2 3I>> (2) 51P-2 (2)Three-phase non-directional overcurrentprotection, instantaneous stage, instance 1 PHIPTOC1 3I>>> (1) 50P/51P (1)Non-directional earth-fault protection, lowstage, instance 1 EFLPTOC1 Io> (1) 51N-1 (1)Non-directional earth-fault protection, lowstage, instance 2 EFLPTOC2 Io> (2) 51N-1 (2)Non-directional earth-fault protection, highstage, instance 1 EFHPTOC1 Io>> (1) 51N-2 (1)Non-directional earth-fault protection,instantaneous stage EFIPTOC1 Io>>> 50N/51NNegative-sequence overcurrent protection,instance 1 NSPTOC1 I2> (1) 46 (1)Negative-sequence overcurrent protection,instance 2 NSPTOC2 I2> (2) 46 (2)Phase discontinuity protection PDNSPTOC1 I2/I1> 46PDThree-phase thermal protection for feeders,cables and distribution transformers T1PTTR1 3Ith>F 49FCircuit breaker failure protection CCBRBRF1 3I>/Io>BF 51BF/51NBFThree-phase inrush detector INRPHAR1 3I2f> 68Master trip, instance 1 TRPPTRC1 Master Trip (1) 94/86 (1)Master trip, instance 2 TRPPTRC2 Master Trip (2) 94/86 (2)

    Table continues on next page

    1MRS756378 H Section 3REF615 standard configurations

    REF615 63Application Manual

  • Function IEC 61850 IEC ANSIArc protection, instance 1 ARCSARC1 ARC (1) 50L/50NL (1)Arc protection, instance 2 ARCSARC2 ARC (2) 50L/50NL (2)Arc protection, instance 3 ARCSARC3 ARC (3) 50L/50NL (3)ControlCircuit-breaker control CBXCBR1 I O CB I O CBAuto-reclosing DARREC1 O -> I 79Condition monitoringTrip circuit supervision, instance 1 TCSSCBR1 TCS (1) TCM (1)Trip circuit supervision, instance 2 TCSSCBR2 TCS (2) TCM (2)MeasurementDisturbance recorder RDRE1 - -Three-phase current measurement, instance 1 CMMXU1 3I 3ISequence current measurement CSMSQI1 I1, I2, I0 I1, I2, I0Residual current measurement, instance 1 RESCMMXU1 Io In

    3.6.2.1 Default I/O connectionsTable 20: Default connections for binary inputsBinary input Default usage Connector pinsX120-BI1 Blocking of overcurrent instantaneous stage X120-1,2X120-BI2 Circuit breaker closed indication X120-3,2X120-BI3 Circuit breaker open indication X120-4,2X120-BI4 Reset of master trip lockout X120-5,6

    Table 21: Default connections for binary outputsBinary output Default usage Connector pinsX100-PO1 Close circuit breaker X100-6,7X100-PO2 Circuit breaker failure protection trip to upstream

    breakerX100-8,9

    X100-PO3 Open circuit breaker/trip coil 1 X100-15,16,17,18,19

    X100-PO4 Open circuit breaker/trip coil 2 X100-20,21,22,23,24

    X100-SO1 General start indication X100-10,11,12X100-SO2 General operate indication X100-13,14,15

    Section 3 1MRS756378 HREF615 standard configurations

    64 REF615Application Manual

  • Table 22: Default connections for LEDsLED Default usage1 Non-directional overcurrent operate2 Non