389H NO 24 Load Calc Project

download 389H NO 24 Load Calc Project

of 15

Transcript of 389H NO 24 Load Calc Project

  • 8/6/2019 389H NO 24 Load Calc Project

    1/15

    Objectives

    Discus final project

    Load calculation

  • 8/6/2019 389H NO 24 Load Calc Project

    2/15

    Final ProjectGroup 1:

    Heather Smith

    Tommy Beales

    Matt Leos

    Group 2:

    Patrick Gorman

    Kenny Greaves

    Matt McCarthy

    Group 3:

    Sarah JohnsonJocelyn Citty

    Tobias Nilsson

    Group 4:

    Zaid Arzate

    Brian BurchamJustin Barrett

    Group 5:

    Nick Williams

    Stephen Mathai

    Kevin Carbonnier

    Group 6:

    Marcus Allen

    Josh Atkins

    Matt Larson

    Group 7:

    StephenF

    ridleyShahrukh Gaziani

    Margaret Lawson

    Group 8:

    Marwa Zaatari

    Megan Gunther

    Elena Nirlo

    Group 9:Gregory Arcangeli

    Andrew Hoisington

    Adam Keeling

    Individual projects

    Neil Woodson

    Wesley Cole

    Sami Kolahdoozan

    Gautam Salhotra

  • 8/6/2019 389H NO 24 Load Calc Project

    3/15

    Project topics

    1) VAV system design

    Fresh air requirements and recirculation rate calculation

    Selection of zonal and central HVAC components based on cooling and heating load components

    For zones: VAV boxes, reheaters, reheater plumbing

    For whole system: AHU and components, chiller & cooling tower, boiler, and electric power requirement Control description sequence of operation

    Heat recovery system and or economizers

    2) DOAS system design

    Fresh air requirement and split between air and hydronic loads (sensible and latent cooling loads) Selection of zonal and central HVAC components based on cooling and heating load components

    For zones: fan coils and plumbing

    For whole system: AHU and components, chiller & cooling tower, boiler, and electric power requirement

    Control description sequence of operation

    Heat recovery system and or economizers

  • 8/6/2019 389H NO 24 Load Calc Project

    4/15

    Project topics

    3) Cooling systems and distribution

    Air cooled condenser vs. water cooled condenser (energy performance analysis)

    Design of plumbing systems for campus and pumping stations

    Control of centralized system

    Saving with variable speed pumps

    4) Duct Design (in Revit)

    - Diffuser selection, design of local and central duct system components

    - Spacing issues and difference between round and square ducts

    - Difference between manual calculation and calculation by Revit (for a section of the duct system)

    - Balancing and fan selection

    - Life cycle analysis and optimization (fan power consumption vs. system cost)

  • 8/6/2019 389H NO 24 Load Calc Project

    5/15

    DOAS with multi-split systems

    Fresh air?

  • 8/6/2019 389H NO 24 Load Calc Project

    6/15

    DOAS fresh air configurations

  • 8/6/2019 389H NO 24 Load Calc Project

    7/15

    DOAS fresh air configurations

  • 8/6/2019 389H NO 24 Load Calc Project

    8/15

    Cooling and Heating Loads

    (F

    or Project)

    Zone orientation

    Commercial building

  • 8/6/2019 389H NO 24 Load Calc Project

    9/15

    Cooling and Heating Loads

    (F

    or Project)Cooling and heating load for each zone and whole building:

    Fresh air requirement based on number of occupants:

    To provide acceptable IAQ in the building, ventilation system supply minimal amount offresh air is in all spaces (except plenums)that produce 0.2 ACH.

  • 8/6/2019 389H NO 24 Load Calc Project

    10/15

    Cooling Load Calculation

    Mostly computer based

    Handouts for manual calculation http://www.ce.utexas.edu/prof/Novoselac/classes/ARE346N/Handouts/heatloss_table_2008.doc

    http://www.ce.utexas.edu/prof/Novoselac/classes/ARE346N/Handouts/ASHRAE_%20Gains_Calculation_Tables.doc

  • 8/6/2019 389H NO 24 Load Calc Project

    11/15

    Heat Recovery Sensible and

    Enthalpy wheel

  • 8/6/2019 389H NO 24 Load Calc Project

    12/15

    EconomizerEconomizer (fresh air volume flow rate control)

    mixing

    damper

    fresh air

    T & RH sensors

    recirc. air

    Controlled device is damper

    - Damper for the air

    - Valve for the liquids

  • 8/6/2019 389H NO 24 Load Calc Project

    13/15

    Economizer cooling regime

    How to control the fresh air volume flow rate?

    % fresh air

    Minimum for ventilation

    100%

    If TOA < Tset-point Supply more fresh air than the minimum required

    The question is how much?

    Open the damper for the fresh air

    and compare the Troom with the Tset-point .Open till you get the Troom = Tset-pointIf you have 100% fresh air and your still need cooling use cooling coil.

    What are the priorities: - Control the dampers and then the cooling coils or - Control the valves ofcooling coil and then the dampers ?

    Defend by SEQUENCE OF OERATION the set of operation which HVAC designer provides to the automatic control engineer

  • 8/6/2019 389H NO 24 Load Calc Project

    14/15

    Economizer cooling regime

    Example of SEQUENCE OF OERATIONS:

    If TOA < Tset-point open the fresh air damper the maximum position

    Then, if Tindoor air < Tset-point start closing the cooling coil valve

    If cooling coil valve is closed and T indoor air < Tset-point start closing the damper till you get T indoor air = T set-pointOther variations are possible

  • 8/6/2019 389H NO 24 Load Calc Project

    15/15

    Desiccant wheel

    Figure 3 A desiccant-based cooling system combined with regenerative heat exchanger, vapor compression cooling, andevaporative humidifier (hybrid system).