389H NO 24 Load Calc Project
-
Upload
wirestylus7130 -
Category
Documents
-
view
218 -
download
0
Transcript of 389H NO 24 Load Calc Project
-
8/6/2019 389H NO 24 Load Calc Project
1/15
Objectives
Discus final project
Load calculation
-
8/6/2019 389H NO 24 Load Calc Project
2/15
Final ProjectGroup 1:
Heather Smith
Tommy Beales
Matt Leos
Group 2:
Patrick Gorman
Kenny Greaves
Matt McCarthy
Group 3:
Sarah JohnsonJocelyn Citty
Tobias Nilsson
Group 4:
Zaid Arzate
Brian BurchamJustin Barrett
Group 5:
Nick Williams
Stephen Mathai
Kevin Carbonnier
Group 6:
Marcus Allen
Josh Atkins
Matt Larson
Group 7:
StephenF
ridleyShahrukh Gaziani
Margaret Lawson
Group 8:
Marwa Zaatari
Megan Gunther
Elena Nirlo
Group 9:Gregory Arcangeli
Andrew Hoisington
Adam Keeling
Individual projects
Neil Woodson
Wesley Cole
Sami Kolahdoozan
Gautam Salhotra
-
8/6/2019 389H NO 24 Load Calc Project
3/15
Project topics
1) VAV system design
Fresh air requirements and recirculation rate calculation
Selection of zonal and central HVAC components based on cooling and heating load components
For zones: VAV boxes, reheaters, reheater plumbing
For whole system: AHU and components, chiller & cooling tower, boiler, and electric power requirement Control description sequence of operation
Heat recovery system and or economizers
2) DOAS system design
Fresh air requirement and split between air and hydronic loads (sensible and latent cooling loads) Selection of zonal and central HVAC components based on cooling and heating load components
For zones: fan coils and plumbing
For whole system: AHU and components, chiller & cooling tower, boiler, and electric power requirement
Control description sequence of operation
Heat recovery system and or economizers
-
8/6/2019 389H NO 24 Load Calc Project
4/15
Project topics
3) Cooling systems and distribution
Air cooled condenser vs. water cooled condenser (energy performance analysis)
Design of plumbing systems for campus and pumping stations
Control of centralized system
Saving with variable speed pumps
4) Duct Design (in Revit)
- Diffuser selection, design of local and central duct system components
- Spacing issues and difference between round and square ducts
- Difference between manual calculation and calculation by Revit (for a section of the duct system)
- Balancing and fan selection
- Life cycle analysis and optimization (fan power consumption vs. system cost)
-
8/6/2019 389H NO 24 Load Calc Project
5/15
DOAS with multi-split systems
Fresh air?
-
8/6/2019 389H NO 24 Load Calc Project
6/15
DOAS fresh air configurations
-
8/6/2019 389H NO 24 Load Calc Project
7/15
DOAS fresh air configurations
-
8/6/2019 389H NO 24 Load Calc Project
8/15
Cooling and Heating Loads
(F
or Project)
Zone orientation
Commercial building
-
8/6/2019 389H NO 24 Load Calc Project
9/15
Cooling and Heating Loads
(F
or Project)Cooling and heating load for each zone and whole building:
Fresh air requirement based on number of occupants:
To provide acceptable IAQ in the building, ventilation system supply minimal amount offresh air is in all spaces (except plenums)that produce 0.2 ACH.
-
8/6/2019 389H NO 24 Load Calc Project
10/15
Cooling Load Calculation
Mostly computer based
Handouts for manual calculation http://www.ce.utexas.edu/prof/Novoselac/classes/ARE346N/Handouts/heatloss_table_2008.doc
http://www.ce.utexas.edu/prof/Novoselac/classes/ARE346N/Handouts/ASHRAE_%20Gains_Calculation_Tables.doc
-
8/6/2019 389H NO 24 Load Calc Project
11/15
Heat Recovery Sensible and
Enthalpy wheel
-
8/6/2019 389H NO 24 Load Calc Project
12/15
EconomizerEconomizer (fresh air volume flow rate control)
mixing
damper
fresh air
T & RH sensors
recirc. air
Controlled device is damper
- Damper for the air
- Valve for the liquids
-
8/6/2019 389H NO 24 Load Calc Project
13/15
Economizer cooling regime
How to control the fresh air volume flow rate?
% fresh air
Minimum for ventilation
100%
If TOA < Tset-point Supply more fresh air than the minimum required
The question is how much?
Open the damper for the fresh air
and compare the Troom with the Tset-point .Open till you get the Troom = Tset-pointIf you have 100% fresh air and your still need cooling use cooling coil.
What are the priorities: - Control the dampers and then the cooling coils or - Control the valves ofcooling coil and then the dampers ?
Defend by SEQUENCE OF OERATION the set of operation which HVAC designer provides to the automatic control engineer
-
8/6/2019 389H NO 24 Load Calc Project
14/15
Economizer cooling regime
Example of SEQUENCE OF OERATIONS:
If TOA < Tset-point open the fresh air damper the maximum position
Then, if Tindoor air < Tset-point start closing the cooling coil valve
If cooling coil valve is closed and T indoor air < Tset-point start closing the damper till you get T indoor air = T set-pointOther variations are possible
-
8/6/2019 389H NO 24 Load Calc Project
15/15
Desiccant wheel
Figure 3 A desiccant-based cooling system combined with regenerative heat exchanger, vapor compression cooling, andevaporative humidifier (hybrid system).