    easYgen-3200 TrainingSection 3 - Operational Modes

    marked

    CERTIFICATE ofDesign Assessment

    byABSAmerican Bureau of Shipping & Affiliated Companies

  • 8/13/2019 37397 a EG3200 Section 3 Operation (NXPowerLite)

    2/42

    Proprietary Information

    Proprietary Information

    ContentsDynamicsLCDTM

    Status Menu

    Parameter Menu

    Passw ord Protect ion

    FlexAppTM

    Operation Modes (Auto , Manual, Stop)

    Start / Stop

    FAQ

    slide 3

    6

    14

    18

    23

    29

    32

    37

  • 8/13/2019 37397 a EG3200 Section 3 Operation (NXPowerLite)

    3/42

    3

    Proprietary Information

    DynamicsLCDTM

    The 320x240 pixel graphic interactive LC display provides soft keyswhose functionality changes depending on application (see FlexAppTM)and operation.

    Delta / Wye

    Voltage

    Automatic

    Manual

    STOP

    Alarm screen

    Configure

    parameter

    Additional

    measured values

    Acknowledge

    centralized alarm

    Change operation

    modes

    Engine start / stop Breaker control

    DynamicsLCDTM

    Status menu

    Parameter

    Password

    FlexAppTM

    Start / Stop

    FAQ

    Operation

    Parameter Menu

  • 8/13/2019 37397 a EG3200 Section 3 Operation (NXPowerLite)

    4/42

    4

    Proprietary Information

    Single line diagram

    and operation mode

    Last alarm

    The display topography:DynamicsLCD

    TM

    DynamicsLCDTM

    Status menu

    Parameter

    Password

    FlexAppTM

    Current operation

    i.e. Cranking, loading,

    start pause, etc.

    Start / Stop

    FAQ

    Operation

    Parameter Menu

  • 8/13/2019 37397 a EG3200 Section 3 Operation (NXPowerLite)

    5/42

    5

    Proprietary Information

    Symbol meanings in the single line diagram

    Delayed engine monitoring expired

    Engine speed detected

    Voltage detected

    Rotation field counter clockwise

    Rotation field clockwise

    DynamicsLCDTM

    Import/Export Mains power

    DynamicsLCDTM

    Status menu

    Parameter

    Password

    FlexAppTM

    Start / Stop

    FAQ

    Operation

    Parameter Menu

  • 8/13/2019 37397 a EG3200 Section 3 Operation (NXPowerLite)

    6/42

    6

    Proprietary Information

    Navigation through the screensmeasured values

    Advance to Next Screen

    Screen Name

    Select subdirectory

    Status Menu

    DynamicsLCDTM

    Status menu

    Parameter

    Password

    FlexAppTM

    Start / Stop

    FAQ

    Operation

    Parameter Menu

  • 8/13/2019 37397 a EG3200 Section 3 Operation (NXPowerLite)

    7/42

    7

    Proprietary Information

    Setpoints

    Status Menu

    DynamicsLCDTM

    Status menu

    Parameter

    Password

    FlexAppTM

    Start / Stop

    FAQ

    Operation

    Parameter Menu

  • 8/13/2019 37397 a EG3200 Section 3 Operation (NXPowerLite)

    8/42

    8

    Proprietary Information

    Status Menu

    Synchroscope

    DynamicsLCDTM

    Status menu

    Parameter

    Password

    FlexAppTM

    Start / Stop

    FAQ

    Operation

    Parameter Menu

  • 8/13/2019 37397 a EG3200 Section 3 Operation (NXPowerLite)

    9/42

    9

    Proprietary Information

    Status Menu

    Event History

    DynamicsLCDTM

    Status menu

    Parameter

    Password

    FlexAppTM

    Start / Stop

    FAQ

    Operation

    Parameter Menu

  • 8/13/2019 37397 a EG3200 Section 3 Operation (NXPowerLite)

    10/42

    10

    Proprietary Information

    Status Menu

    Counters and Service

    DynamicsLCDTM

    Status menu

    Parameter

    Password

    FlexAppTM

    Start / Stop

    FAQ

    Operation

    Parameter Menu

  • 8/13/2019 37397 a EG3200 Section 3 Operation (NXPowerLite)

    11/42

    11

    Proprietary Information

    Status Menu

    Measured Values

    DynamicsLCDTM

    Status menu

    Parameter

    Password

    FlexAppTM

    Start / Stop

    FAQ

    Operation

    Parameter Menu

  • 8/13/2019 37397 a EG3200 Section 3 Operation (NXPowerLite)

    12/42

    12

    Proprietary Information

    Status Menu

    Version and Time

    DynamicsLCDTM

    Status menu

    Parameter

    Password

    FlexAppTM

    Start / Stop

    FAQ

    Operation

    Parameter Menu

  • 8/13/2019 37397 a EG3200 Section 3 Operation (NXPowerLite)

    13/42

    13

    Proprietary Information

    Online

    diagram

    visible

    Status Menu

    DynamicsLCDTM

    Status menu

    Parameter Menu

    Password

    FlexAppTM

    Start / Stop

    FAQ

    Operation

  • 8/13/2019 37397 a EG3200 Section 3 Operation (NXPowerLite)

    14/42

    14

    Proprietary Information

    Navigation through the parameter screens

    Press Parameter soft key

    Screen Name

    Select subdirectory

    Parameter Menu

    DynamicsLCDTM

    Status menu

    Parameter

    Password

    FlexAppTM

    Start / Stop

    FAQ

    Operation

    Parameter Menu

  • 8/13/2019 37397 a EG3200 Section 3 Operation (NXPowerLite)

    15/42

    15

    Proprietary Information

    Navigation through the parameter screens

    Pathway to

    this screen

    System overview Parameter

    Screen name

    Parameter Menu

    DynamicsLCDTM

    Status menu

    Password

    FlexAppTM

    Start / Stop

    FAQ

    Operation

    Parameter Menu

  • 8/13/2019 37397 a EG3200 Section 3 Operation (NXPowerLite)

    16/42

    16

    Proprietary Information

    Change a Parameter

    Move black cursor

    line up and down

    Press Enter soft key to select

    parameter to be changed

    Parameter Menu

    DynamicsLCDTM

    Status menu

    Password

    FlexAppTM

    Start / Stop

    FAQ

    Operation

    Parameter Menu

  • 8/13/2019 37397 a EG3200 Section 3 Operation (NXPowerLite)

    17/42

    17

    Proprietary Information

    Changing a Parameter

    Other parameters are

    cleared from display

    Old value

    Select value + / - soft keys

    Move cursor if value

    is numeric

    Parameter Menu

    DynamicsLCDTM

    Status menu

    Parameter Menu

    Password

    FlexAppTM

    Start / Stop

    FAQ

    Operation

    New value

  • 8/13/2019 37397 a EG3200 Section 3 Operation (NXPowerLite)

    18/42

    18

    Proprietary Information

    Password ProtectionThree levels of password protection enable multiple users

    with varying degrees of access

    Password protection valid for 2 hoursLevel 1/End user 0001

    Level 2/Temporary commissioning (random number+200)*3

    Level 3/Commissioning 0003

    DynamicsLCDTM

    Status menu

    FlexAppTM

    Start / Stop

    Operation

    FAQ

    Parameter Menu

    Password

  • 8/13/2019 37397 a EG3200 Section 3 Operation (NXPowerLite)

    19/42

    19

    Proprietary Information

    Password Protection

    Possible ways to access a parameter:

    Hardware Enter Password for:

    HMI Pushbuttons Display

    RS-232 ToolKit No password required

    RS-232 Modbus Serial 1 (RS-232)

    RS-485 Modbus Serial 2 (RS-485)

    CAN 1 CANopen CAN 1

    DynamicsLCDTM

    Status menu

    Parameter Menu

    Password

    FlexAppTM

    Start / Stop

    Operation

    FAQ

  • 8/13/2019 37397 a EG3200 Section 3 Operation (NXPowerLite)

    20/42

    20

    Proprietary Information

    Navigation through the parameter screens

    System Overview Parameter

    Password Protection

    DynamicsLCDTM

    Status menu

    FlexAppTM

    Start / Stop

    FAQ

    Operation

    Password Screen

    Parameter Menu

    Password

  • 8/13/2019 37397 a EG3200 Section 3 Operation (NXPowerLite)

    21/42

    21

    Proprietary Information

    Password Protection

    Randomly generated number

    To access to this interface,

    Enter code here

    Current level of access

    Password protection valid for 2 hours

    Level 1/End user 0001

    Level 2/Temporary commissioning (random number+200)*3

    Level 3/Commissioning 0003

    DynamicsLCDTM

    Status menu

    Parameter

    Password

    FlexAppTM

    Start / Stop

    FAQ

    Operation

  • 8/13/2019 37397 a EG3200 Section 3 Operation (NXPowerLite)

    22/42

    22

    Proprietary Information

    Individual parameters cannot be viewed or edited if

    the password has not been entered or has expired.

    Names for submenus are always

    displayed

    Password Protection

    DynamicsLCDTM

    Status menu

    Parameter

    Password

    FlexAppTM

    Start / Stop

    FAQ

    Operation

  • 8/13/2019 37397 a EG3200 Section 3 Operation (NXPowerLite)

    23/42

    23

    Proprietary Information

    There are four application modes available:

    FlexApp

    TM

    [GCB/MCB] [GCB/MCB open/close {2oc}]

    [GCB] [GCB open/close {1oc}]

    [GCB open] [GCB open {1o}]

    [none] [0-CB-Mode {0}]

    Parameter name: in product spec:

    DynamicsLCDTM

    Status menu

    Parameter

    Password

    FlexAppTM

    Start / Stop

    FAQ

    Operation

  • 8/13/2019 37397 a EG3200 Section 3 Operation (NXPowerLite)

    24/42

    24

    Proprietary Information

    Two breaker mode

    Mains/utility breaker (MCB) and generator breaker (GCB)

    Generator protection for shutdown and GCB opencommand

    Single or multiple genset operation

    GCB & MCB open closecommand

    Automatic mains failure (AMF) / emergency mode

    Fixed Input Fixed Output

    DI 8 reply GCB (B contacts) DO 6/7 GCB close / open

    DI 7 reply MCB (B contacts) DO 8/9 MCB close / open

    FlexAppTM- The 4 Application Modes - [GCB/MCB]

    DynamicsLCDTM

    Status menu

    Parameter

    Password

    FlexAppTM

    Start / Stop

    FAQ

    Operation

  • 8/13/2019 37397 a EG3200 Section 3 Operation (NXPowerLite)

    25/42

    25

    Proprietary Information

    One breaker mode

    Generator breaker (GCB) control

    Generator protection for shutdown and GCB opencommand

    Single or multiple genset operation

    GCB open/closecommand

    Fixed Input Fixed Output

    DI 8 reply GCB (B contacts) DO 6/7 GCB close / open

    DI 7 reply mains parallel

    Grey= breaker status only:

    MCB control is external

    FlexAppTM- The 4 Application Modes - [GCB]

    DynamicsLCDTM

    Status menu

    Parameter

    Password

    FlexAppTM

    Start / Stop

    FAQ

    Operation

  • 8/13/2019 37397 a EG3200 Section 3 Operation (NXPowerLite)

    26/42

    26

    Proprietary Information

    Breaker open mode

    Generator breaker open only

    Generator protection for shutdown and GCB opencommand

    Single or multiple genset operation

    GCB opencommand (shunt trip)

    Fixed Input Fixed Output

    DI 8 reply GCB (B contact) DO 7 GCB open

    DI 7 reply MCB (mains parallel)

    FlexAppTM- The 4 Application Modes - [GCB open]

    DynamicsLCDTM

    Status menu

    Parameter

    Password

    FlexAppTM

    Start / Stop

    FAQ

    Operation

  • 8/13/2019 37397 a EG3200 Section 3 Operation (NXPowerLite)

    27/42

    27

    Proprietary Information

    Base mode

    No breaker control

    Single or multiple genset operation

    Generator and engine protection

    All breaker control is external

    Fixed Input

    DI 8 reply GCB (B contact)

    DI 7 reply MCB (mains parallel)

    FlexAppTM- The 4 Application Modes - [none]

    DynamicsLCDTM

    Status menu

    Parameter

    Password

    FlexAppTM

    Start / Stop

    FAQ

    Operation

  • 8/13/2019 37397 a EG3200 Section 3 Operation (NXPowerLite)

    28/42

    28

    Proprietary Information

    It is possible to not

    display mains data

    FlexAppTM

    Application mode [GCB]

    Application mode [GCB/MCB]

    DynamicsLCDTM

    Status menu

    Parameter

    Password

    FlexAppTM

    Start / Stop

    FAQ

    Operation

  • 8/13/2019 37397 a EG3200 Section 3 Operation (NXPowerLite)

    29/42

    29

    Proprietary Information

    Automatic mode

    Manual mode

    Stop mode

    Operation Modes

    Changing the operation mode may

    be performed via:

    the HMI soft keys

    the LogicsManager

    DynamicsLCDTM

    Status menu

    Parameter

    Password

    FlexAppTM

    Start / Stop

    FAQ

    Operation

  • 8/13/2019 37397 a EG3200 Section 3 Operation (NXPowerLite)

    30/42

    30

    Proprietary Information

    Changing the operation mode via HMI soft keys

    Automatic

    Manual

    STOP

    Operation Modes

    DynamicsLCDTM

    Status menu

    Parameter

    Password

    FlexAppTM

    Start / Stop

    FAQ

    Operation

  • 8/13/2019 37397 a EG3200 Section 3 Operation (NXPowerLite)

    31/42

    31

    Proprietary Information

    Changing the operation

    mode via LogicsManager

    Operation Modes

    DynamicsLCDTM

    Status menu

    Parameter

    Password

    FlexAppTM

    Start / Stop

    FAQ

    Operation

  • 8/13/2019 37397 a EG3200 Section 3 Operation (NXPowerLite)

    32/42

  • 8/13/2019 37397 a EG3200 Section 3 Operation (NXPowerLite)

    33/42

    33

    Proprietary Information

    Stop command issued

    Start/run command issued

    Start / Stop in Manual

    DynamicsLCDTM

    Status menu

    Parameter

    Password

    FlexAppTM

    Start / Stop

    FAQ

    Operation

    Unit is trying to close the breaker

    Unit is trying to open the breaker

  • 8/13/2019 37397 a EG3200 Section 3 Operation (NXPowerLite)

    34/42

    34

    Proprietary Information

    Generator:

    Start conditions

    LM: Start in auto is true

    may be used with load dependent start/stop function

    LM: Start w/o load is true LM: Critical mode is true

    Loss of mains {GCB/MCB} (Emergency mode)

    Mains voltage/frequency out of operating range

    Mains rotation field wrong

    Fail to close MCB (if parameter is enabled)

    Stop conditions

    LM: Start conditions are false

    Alarm class C-F detected

    LM: Stop in auto

    LM: Inhibit emergency mode

    Mains:Close MCB: Open MCB:

    Mains are within accepted limits Dependent upon breaker logic

    DI7 is de-energized (MCB is open) For mains decoupling

    LM: Release MCB is true (default DI6)

    Conditions for synchronization or

    dead bus closing are met

    Start / Stop in Auto

    DynamicsLCDTM

    Status menu

    Parameter

    Password

    FlexAppTM

    Start / Stop

    FAQ

    Operation

  • 8/13/2019 37397 a EG3200 Section 3 Operation (NXPowerLite)

    35/42

    35

    Proprietary Information

    Start / Stop in Auto

    DynamicsLCDTM

    Status menu

    Parameter

    Password

    FlexAppTM

    Start / Stop

    FAQ

    Operation

  • 8/13/2019 37397 a EG3200 Section 3 Operation (NXPowerLite)

    36/42

    36

    Proprietary Information

    Diesel engine

    - Pre-glow function

    - Fuel or Stop solenoid activation

    - Crank/start circuit control

    Gas engine

    - Ignition

    - Gas valve

    - Crank/start circuit control

    External logic

    - Fuel solenoid as a start request to external controllers

    Start / Stop logic

    DynamicsLCDTM

    Status menu

    Parameter

    Password

    FlexAppTM

    Start / Stop

    FAQ

    Operation

  • 8/13/2019 37397 a EG3200 Section 3 Operation (NXPowerLite)

    37/42

    37

    Proprietary Information

    Frequently Asked Questions

    How can I reset the maintenance counter?

    How can I define the loss of mains condition

    in order to activate the emergency mode?

    FAQ

    DynamicsLCDTM

    Status menu

    Parameter

    Password

    FlexAppTM

    Start / Stop

    FAQ

    Operation

  • 8/13/2019 37397 a EG3200 Section 3 Operation (NXPowerLite)

    38/42

    38

    Proprietary Information

    The maintenance hours counter decreases as the operation hours counter increases.

    The maintenance days counter decreases as the Internal calendar clock increases.

    When a count down timer reaches 0 an alarm is issued. The reset procedure is as follows:

    Enter password (see config. manual)

    Step 1:

    How can I reset the maintenance counter?

    FAQ

    DynamicsLCDTM

    Status menu

    Parameter

    Password

    FlexAppTM

    Start / Stop

    FAQ

    Operation

  • 8/13/2019 37397 a EG3200 Section 3 Operation (NXPowerLite)

    39/42

    39

    Proprietary Information

    Press Next pageCounters and

    service buttons to get to counters screen.

    Next, press the Tool symbol button.

    Step 2:

    How can I reset the maintenance counter?

    Symbol appears only if the

    required password is active

    FAQ

    DynamicsLCDTM

    Status menu

    Parameter

    Password

    FlexAppTM

    Start / Stop

    FAQ

    Operation

  • 8/13/2019 37397 a EG3200 Section 3 Operation (NXPowerLite)

    40/42

    40

    Proprietary Information

    Select counter to reset. Press enter, select YES, press enter.

    Now the alarm may be acknowledged in

    the alarm list.

    Step 3: Step 4:

    How can I reset the maintenance counter?

    FAQ

    DynamicsLCDTM

    Status menu

    Parameter

    Password

    FlexAppTM

    Start / Stop

    FAQ

    Operation

  • 8/13/2019 37397 a EG3200 Section 3 Operation (NXPowerLite)

    41/42

    41

    Proprietary Information

    How can I define the loss of mains condition, in order to activate the

    emergency mode?

    The operating range defines the loss of mains conditions.

    The thresholds from the mains monitoring are used for protection

    purpose, not for the loss of mains detection!

    FAQ

    Adjust the Operating range

    voltage / frequency of the mains

    DynamicsLCDTM

    Status menu

    Parameter

    Password

    FlexAppTM

    Start / Stop

    FAQ

    Operation

  • 8/13/2019 37397 a EG3200 Section 3 Operation (NXPowerLite)

    42/42

    Note:

    Information contained herein is intended for and appropriate to the purposes of this publication/presentation. Woodward reserves the right to update or otherwise revise any portion of this publication at any time. Technical data and

    detailed information is available in Woodward product specs. Specific reliance should be given only to information contained in purchase order(s), other contractual document(s), or information otherwise expressly represented in

    writing by Woodward as correct and accurate for the specific facts, circumstances and applications.

    End of this presentation

    Thank you for your attention

    Other sections are :

    1 Overview

    2 Hardware and I/O

    3 Operational Modes

    4 Configuration and ToolKit

    5 Communication

    6 LogicsManager

    7 Analog Manager

    8 Controller

    9 Synchronization and breaker

    10 Application

    11 Sequencing