Product Specification
37167C
LS 4Circuit Breaker Control
& Protection
APPLICATIONS
The LS 4 offers a simple solution for complexswitchgear applications. The LS 4 has theability to operate with up to 14 GCP-31 gensetcontrols and 8 LS 4 circuit breaker controllers.
Each controlled breaker is equipped with oneLS 4 that measures the three-phase voltage oneither side of the breaker (phase angleconfigurable). Each side of the breaker isdesignated as either a fixed (utility) or variable(genset) source and is labeled A or B. Thispermits the LS 4 to control utility feederbreakers with one fixed source and onevariable source, or tie breakers betweenbusses with two variable sources. The LS 4 isused for breaker protection, synchronization,and load control.
OPERATION
All LS 4's communicate via a CAN bus networkto each other and to the GCP genset controls.Discrete input commands are used to operatethe LS 4 in the desired mode. Set-point valuesfor frequency and voltage are transmitted to allgenset controllers on that switchgear segment.The genset controls then adjust the frequencyand voltage of their respective genset toachieve synchronization. The LS 4 will performthe opening and closing of the circuit breakerbased on the discrete inputs it receives.
DESCRIPTION
Features True RMS voltage (A and B side)
True RMS current (A side)
Synch-check functionality
Dead bus start functionality
Synchronous networks functionality Remote control of frequency, voltage,
and real power
Zero power transfer control (softload)
Configurable trip/control set points
Config. delays for each alarm
7 configurable relay outputs
Two-line LC display
Synchronization over transformerpossible
Protections ANSI # Overvoltage (59)
Undervoltage (27) Overfrequency (81O)
Underfrequency (81U)
Phase/vector shift (78)
df/dt ROCOF (81RL)
Functions Calculation of setpoint values which
are transmitted to the genset controls(e.g. GCP) for synchronization andload control
Circuit breaker close command issuedwhen LS 4 is enabled and the two
sources are synchronized. Open command to the CB with a
discrete input command or with thedetection of one of the availableprotection functions.
Flexible solution focomplex breakerconfigurations
Synch-check relay
Dead bus startfunctions
Protection relay
Synchronizer
Zero power transfecontrol
CAN bus basedcommunication
Breaker protectionand synchronizer isingle digitalcontroller
True RMS sensing
Discrete inputs forremote control
PC and front paneconfigurable
Programmable relaoutputs
UL/cUL Listed
Microprocessor
technology foraccurate, repeataband reliableoperation
Programmable twostep threshold setpoints with individutime delays
-
7/31/2019 37167_C
2/4
SPECIFICATIONS
Accuracy .......................................................................................... Class 1Power supply.............................................................24 Vdc (18 to 30 Vdc)Intrinsic consumption ..................................................................max. 12 WAmbient temperature................................................................ -20 to 70 CAmbient humidity...................................................... 95 %, non-condensing
Voltage ...........Rated value /: [1] 66/115 Vac or [4] 230/400 VacMaximum value (Vmax): [1] 150 Vac or [4] 300 Vac
Rated voltage Vph-ground: [1] 150 Vac or [4] 300 Vac
Rated surge voltage: [1] 2.5 kV or [4] 4.0 kVMeasuring frequency................................................50/60 Hz (40 to 70 Hz)Linear measuring range up to .......................................................1.3VratedInput resistance..................................................... [1] 0.21 M, [4] 0.7 MMax. power consumption per path................................................ < 0.15 WCurrent ........................................................................[1] ../1 A or [5] ../5 ALinear measuring range up to ........................................................ 3.0IratedLoad ............................................................................................. < 0.15 VARated short-time cur. (1 s) ................................[1] 50.0Irated, [5] 10.0IratedDiscrete inputs .............................................................................. isolatedInput range........................................................................18 to 250 Vac/dc
Input resistance.....................................................................approx. 68 k
Relay outputs ................................................................................ isolatedContact material...............................................................................AgCdOLoad (GP).................................................24 Vdc@2 Adc, 250 Vac@2 AacInductive time load (PD).......................................................24 Vdc@1 AdcInterface ......................................................................................... isolatedType .................................................................................... CAN bus (CAL)Insulation voltage ....................................................................min. 500 VdcHousing......................................................Type APRANORM DIN 43 700
Dimensions .........................................................................9672130 mmFront cutout.................................................................................9167 mmConnection................................................ screw/plug terminals depending
on connector 1.5 mm, 2.5 mm or 4 mmFront.................................................................................insulating surfaceProtection system................................................................................ IP 21Weight........................................ ....... depending on version, approx. 800 gDisturbance test (CE).................................................. tested according to
applicable EN guidelinesListings ......................................... UL/cUL listed (voltages up to 300 Vac)
ordinary locations, file E212970
DIMENSIONS
2004-11-17 | LS 4 Dimensions ls4ww-4704-ab.skf
50130
96
8
90
130
72
65
27
35
40
1
70 75
45
16
32 17
X5X1
Back view withconnecting terminals
Bottom view
DIN rail mount option
(please order bracktesP/N 8923-1023)
Front view
Configuration port
Configuration port
Configuration port
PRODUCT NUMBERS P/N
LS 4 version voltage input current input Product Number P/N
LS411B 100 Vac ../1 A 8440-1032LS415B 100 Vac ../5 A 8440-1031LS441B 400 Vac ../1 A 8440-1030LS445B 400 Vac ../5 A 8440-1006
-
7/31/2019 37167_C
3/4
-
7/31/2019 37167_C
4/4
InternationalWoodwardPO Box 1519Fort Collins CO, USA80522-15191000 East Drake RoadFort Collins CO 80525Ph: +1 (970) 482-5811Fax: +1 (970) 498-3058
Europe
Woodward Governor CompanyLeonhard-Reglerbau GmbHHandwerkstrasse 2970565 Stuttgart, GermanyPh: +49 (0) 711 789 54-0Fax: +49 (0) 711 789 54-100
Distributors & ServiceWoodward has an internationalnetwork of distributors andservice facilities. For yournearest representative, call theFort Collins plant or see theWorldwide Directory on ourwebsite.
Corporate HeadquartersRockford IL, USAPh: +1 (815) 877-7441
www.woodward.com/power
Subject to technicalmodifications.
This document is distributed forinformational purposes only. It is notto be construed as creating orbecoming part of any WoodwardGovernor Company contractual orwarranty obligation unless expresslystated in a written sales contract.
We appreciate your commentsabout the content of ourpublications. Please send commentsincluding the document numberbelow [email protected]
Woodward GovernorCompany
All Rights Reserved
37167C - 06/4/S
WIRING DIAGRAM
Subject to technical modifications.
3/(4)
3/(4)
Relay 2
Relay 1
Relay 3
2005-11-23 | LS4 Wiring Diagramls4ww-4705-ap.s kf
The socket for the PC configuration is locatedon the side of the unit. This is where the directconfiguration cable DPC must be plugged in.
System
[B] LS4
(CircuitBreakerControl)
Disconnector
e.g. PLC
InterfaceCAN bus(Guidance Level)
CAN-L
CAN-H
GND
CAN-L
CAN-H
3/(4)
Sys
tem[A]
Relay 4
Relay 5
Relay 6
Relay 8Synchronization(impulse relay)
CAN-L
CAN-H
GND
CAN-L
CAN-H
LS4.1
7
CAN-L
CAN-H
GND
CAN-L
CAN-H
LS4.1
9
CAN-L
CAN-H
GND
CAN-L
CAN-H
LS4.x
GCP-31.x
GCP-31.1
GW4CAN-L
CAN-H
GND
CAN-L
CAN-H
CAN-L
CAN-H
GND
CAN-L
CAN-H
CAN-L
CAN-H
GND
CAN-L
CAN-H
R R
X5
X4
X3
X2
X1
29
Relay 7
28
27
26
25
24
23
22
21
20
19
16
15
14
13
12
11
10
9
CAN-L
CAN-H
GND
CAN-L
CAN-H
LS4.1
8
GCP-31.2
CAN-L
CAN-H
GND
CAN-L
CAN-H
44
45
73
74
75
30
31
32
70
71
72
5
6
7
8
43
42
41
40
4
3
2
1
Voltage - System [B] - L3
Voltage - System [B] - L2
Voltage - System [B] - L1
Blocking of watchdog funct. /remote acknowledgment
0 Vdc
Common
Enable CB
Reply: CB is open
Common
Reply: Isolation switch is open
Command: open CB
Current - System [A] - L1s2/x2 (l)
Current - System [A] - L2
Current - System [A] - L3
s1/x1 (k)
(Voltage - System [A] - N)
Voltage - System [A] - L1
Voltage - System [A] - L2
Voltage - System [A] - L3
Measuringvoltagethree-wire orfour-wire system
Batteryor
anotherpowersupply
Terminal3
0/73ispos.orneg.signal
#
CB
3/(4)
S1/X1 (K)
S2/X2 (L) s2/x2 (l)
s1/x1 (k)L1
3
#
24 Vdc
S1/X1 (K)
S2/X2 (L) s2/x2 (l)
s1/x1 (k)L2
S1/X1 (K)
S2/X2 (L) s2/x2 (l)
s1/x1 (k)L3
s1/x1 (k)
s2/x2 (l)
s1/x1 (k)
s2/x2 (l)
Formoreinfo
rmationcontact: