    Product Specification

    37167C

    LS 4Circuit Breaker Control

    & Protection

    APPLICATIONS

    The LS 4 offers a simple solution for complexswitchgear applications. The LS 4 has theability to operate with up to 14 GCP-31 gensetcontrols and 8 LS 4 circuit breaker controllers.

    Each controlled breaker is equipped with oneLS 4 that measures the three-phase voltage oneither side of the breaker (phase angleconfigurable). Each side of the breaker isdesignated as either a fixed (utility) or variable(genset) source and is labeled A or B. Thispermits the LS 4 to control utility feederbreakers with one fixed source and onevariable source, or tie breakers betweenbusses with two variable sources. The LS 4 isused for breaker protection, synchronization,and load control.

    OPERATION

    All LS 4's communicate via a CAN bus networkto each other and to the GCP genset controls.Discrete input commands are used to operatethe LS 4 in the desired mode. Set-point valuesfor frequency and voltage are transmitted to allgenset controllers on that switchgear segment.The genset controls then adjust the frequencyand voltage of their respective genset toachieve synchronization. The LS 4 will performthe opening and closing of the circuit breakerbased on the discrete inputs it receives.

    DESCRIPTION

    Features True RMS voltage (A and B side)

    True RMS current (A side)

    Synch-check functionality

    Dead bus start functionality

    Synchronous networks functionality Remote control of frequency, voltage,

    and real power

    Zero power transfer control (softload)

    Configurable trip/control set points

    Config. delays for each alarm

    7 configurable relay outputs

    Two-line LC display

    Synchronization over transformerpossible

    Protections ANSI # Overvoltage (59)

    Undervoltage (27) Overfrequency (81O)

    Underfrequency (81U)

    Phase/vector shift (78)

    df/dt ROCOF (81RL)

    Functions Calculation of setpoint values which

    are transmitted to the genset controls(e.g. GCP) for synchronization andload control

    Circuit breaker close command issuedwhen LS 4 is enabled and the two

    sources are synchronized. Open command to the CB with a

    discrete input command or with thedetection of one of the availableprotection functions.

    Flexible solution focomplex breakerconfigurations

    Synch-check relay

    Dead bus startfunctions

    Protection relay

    Synchronizer

    Zero power transfecontrol

    CAN bus basedcommunication

    Breaker protectionand synchronizer isingle digitalcontroller

    True RMS sensing

    Discrete inputs forremote control

    PC and front paneconfigurable

    Programmable relaoutputs

    UL/cUL Listed

    Microprocessor

    technology foraccurate, repeataband reliableoperation

    Programmable twostep threshold setpoints with individutime delays

  • 7/31/2019 37167_C

    2/4

    SPECIFICATIONS

    Accuracy .......................................................................................... Class 1Power supply.............................................................24 Vdc (18 to 30 Vdc)Intrinsic consumption ..................................................................max. 12 WAmbient temperature................................................................ -20 to 70 CAmbient humidity...................................................... 95 %, non-condensing

    Voltage ...........Rated value /: [1] 66/115 Vac or [4] 230/400 VacMaximum value (Vmax): [1] 150 Vac or [4] 300 Vac

    Rated voltage Vph-ground: [1] 150 Vac or [4] 300 Vac

    Rated surge voltage: [1] 2.5 kV or [4] 4.0 kVMeasuring frequency................................................50/60 Hz (40 to 70 Hz)Linear measuring range up to .......................................................1.3VratedInput resistance..................................................... [1] 0.21 M, [4] 0.7 MMax. power consumption per path................................................ < 0.15 WCurrent ........................................................................[1] ../1 A or [5] ../5 ALinear measuring range up to ........................................................ 3.0IratedLoad ............................................................................................. < 0.15 VARated short-time cur. (1 s) ................................[1] 50.0Irated, [5] 10.0IratedDiscrete inputs .............................................................................. isolatedInput range........................................................................18 to 250 Vac/dc

    Input resistance.....................................................................approx. 68 k

    Relay outputs ................................................................................ isolatedContact material...............................................................................AgCdOLoad (GP).................................................24 Vdc@2 Adc, 250 Vac@2 AacInductive time load (PD).......................................................24 Vdc@1 AdcInterface ......................................................................................... isolatedType .................................................................................... CAN bus (CAL)Insulation voltage ....................................................................min. 500 VdcHousing......................................................Type APRANORM DIN 43 700

    Dimensions .........................................................................9672130 mmFront cutout.................................................................................9167 mmConnection................................................ screw/plug terminals depending

    on connector 1.5 mm, 2.5 mm or 4 mmFront.................................................................................insulating surfaceProtection system................................................................................ IP 21Weight........................................ ....... depending on version, approx. 800 gDisturbance test (CE).................................................. tested according to

    applicable EN guidelinesListings ......................................... UL/cUL listed (voltages up to 300 Vac)

    ordinary locations, file E212970

    DIMENSIONS

    2004-11-17 | LS 4 Dimensions ls4ww-4704-ab.skf

    50130

    96

    8

    90

    130

    72

    65

    27

    35

    40

    1

    70 75

    45

    16

    32 17

    X5X1

    Back view withconnecting terminals

    Bottom view

    DIN rail mount option

    (please order bracktesP/N 8923-1023)

    Front view

    Configuration port

    Configuration port

    Configuration port

    PRODUCT NUMBERS P/N

    LS 4 version voltage input current input Product Number P/N

    LS411B 100 Vac ../1 A 8440-1032LS415B 100 Vac ../5 A 8440-1031LS441B 400 Vac ../1 A 8440-1030LS445B 400 Vac ../5 A 8440-1006

  • 7/31/2019 37167_C

    3/4

  • 7/31/2019 37167_C

    4/4

    InternationalWoodwardPO Box 1519Fort Collins CO, USA80522-15191000 East Drake RoadFort Collins CO 80525Ph: +1 (970) 482-5811Fax: +1 (970) 498-3058

    Europe

    Woodward Governor CompanyLeonhard-Reglerbau GmbHHandwerkstrasse 2970565 Stuttgart, GermanyPh: +49 (0) 711 789 54-0Fax: +49 (0) 711 789 54-100

    Distributors & ServiceWoodward has an internationalnetwork of distributors andservice facilities. For yournearest representative, call theFort Collins plant or see theWorldwide Directory on ourwebsite.

    Corporate HeadquartersRockford IL, USAPh: +1 (815) 877-7441

    www.woodward.com/power

    Subject to technicalmodifications.

    This document is distributed forinformational purposes only. It is notto be construed as creating orbecoming part of any WoodwardGovernor Company contractual orwarranty obligation unless expresslystated in a written sales contract.

    We appreciate your commentsabout the content of ourpublications. Please send commentsincluding the document numberbelow [email protected]

    Woodward GovernorCompany

    All Rights Reserved

    37167C - 06/4/S

    WIRING DIAGRAM

    Subject to technical modifications.

    3/(4)

    3/(4)

    Relay 2

    Relay 1

    Relay 3

    2005-11-23 | LS4 Wiring Diagramls4ww-4705-ap.s kf

    The socket for the PC configuration is locatedon the side of the unit. This is where the directconfiguration cable DPC must be plugged in.

    System

    [B] LS4

    (CircuitBreakerControl)

    Disconnector

    e.g. PLC

    InterfaceCAN bus(Guidance Level)

    CAN-L

    CAN-H

    GND

    CAN-L

    CAN-H

    3/(4)

    Sys

    tem[A]

    Relay 4

    Relay 5

    Relay 6

    Relay 8Synchronization(impulse relay)

    CAN-L

    CAN-H

    GND

    CAN-L

    CAN-H

    LS4.1

    7

    CAN-L

    CAN-H

    GND

    CAN-L

    CAN-H

    LS4.1

    9

    CAN-L

    CAN-H

    GND

    CAN-L

    CAN-H

    LS4.x

    GCP-31.x

    GCP-31.1

    GW4CAN-L

    CAN-H

    GND

    CAN-L

    CAN-H

    CAN-L

    CAN-H

    GND

    CAN-L

    CAN-H

    CAN-L

    CAN-H

    GND

    CAN-L

    CAN-H

    R R

    X5

    X4

    X3

    X2

    X1

    29

    Relay 7

    28

    27

    26

    25

    24

    23

    22

    21

    20

    19

    16

    15

    14

    13

    12

    11

    10

    9

    CAN-L

    CAN-H

    GND

    CAN-L

    CAN-H

    LS4.1

    8

    GCP-31.2

    CAN-L

    CAN-H

    GND

    CAN-L

    CAN-H

    44

    45

    73

    74

    75

    30

    31

    32

    70

    71

    72

    5

    6

    7

    8

    43

    42

    41

    40

    4

    3

    2

    1

    Voltage - System [B] - L3

    Voltage - System [B] - L2

    Voltage - System [B] - L1

    Blocking of watchdog funct. /remote acknowledgment

    0 Vdc

    Common

    Enable CB

    Reply: CB is open

    Common

    Reply: Isolation switch is open

    Command: open CB

    Current - System [A] - L1s2/x2 (l)

    Current - System [A] - L2

    Current - System [A] - L3

    s1/x1 (k)

    (Voltage - System [A] - N)

    Voltage - System [A] - L1

    Voltage - System [A] - L2

    Voltage - System [A] - L3

    Measuringvoltagethree-wire orfour-wire system

    Batteryor

    anotherpowersupply

    Terminal3

    0/73ispos.orneg.signal

    #

    CB

    3/(4)

    S1/X1 (K)

    S2/X2 (L) s2/x2 (l)

    s1/x1 (k)L1

    3

    #

    24 Vdc

    S1/X1 (K)

    S2/X2 (L) s2/x2 (l)

    s1/x1 (k)L2

    S1/X1 (K)

    S2/X2 (L) s2/x2 (l)

    s1/x1 (k)L3

    s1/x1 (k)

    s2/x2 (l)

    s1/x1 (k)

    s2/x2 (l)

    Formoreinfo

    rmationcontact: