369 Comm Guide - GE Grid Solutions OF CONTENTS 369 MOTOR MANAGEMENT RELAY– INSTRUCTION MANUAL...
Transcript of 369 Comm Guide - GE Grid Solutions OF CONTENTS 369 MOTOR MANAGEMENT RELAY– INSTRUCTION MANUAL...
GE Multilin
215 Anderson Avenue, Markham, Ontario, Canada L6E 1B3
Tel: (905) 294-6222, 1-800-547-8629 (North America)Fax: (905) 201-2098
Internet: http://www.GEmultilin.com
369 Motor Management RelayCommunications Guide
369 Revision: 3.4x
Manual P/N: 1601-9046-A4
Publication Number: GEK-113493C
Copyright © 2010 GE Multilin
GE Consumer & IndustrialMultilin
*1601-9046-A4*
GE Multilin's Quality Management System is registered to
ISO9001:2000
QMI # 005094UL # A3775
© 2010 GE Multilin Incorporated. All rights reserved.
GE Multilin 369 Motor Management Relay Communications Guide for revision 3.4x.
369 Motor Management Relay, is a registered trademark of GE Multilin Inc.
The contents of this manual are the property of GE Multilin Inc. This documentation is furnished on license and may not be reproduced in whole or in part without the permission of GE Multilin. The content of this manual is for informational use only and is subject to change without notice.
Part numbers contained in this manual are subject to change without notice, and should therefore be verified by GE Multilin before ordering.
Part number: 1601-9046-A4 (July 2010)
TABLE OF CONTENTS
369 MOTOR MANAGEMENT RELAY– INSTRUCTION MANUAL TOC–1
Table of Contents
OVERVIEW .........................................................................................................................................1ELECTRICAL INTERFACE .....................................................................................................1PROFIBUS COMMUNICATIONS .........................................................................................2DEVICENET COMMUNICATIONS .......................................................................................2MODBUS COMMUNICATIONS ...........................................................................................2MODBUS/TCP COMMUNICATIONS .................................................................................3
PROFIBUS-DP COMMUNICATIONS .........................................................................................6PROFIBUS COMMUNICATION OPTIONS ..........................................................................6369 RELAY PROFIBUS-DP PARAMETERIZATION ...........................................................6369 RELAY PROFIBUS-DP CONFIGURATION ................................................................6369 RELAY PROFIBUS-DP DIAGNOSTICS ..................................................................11PROFIBUS-DP LOSS OF COMMUNICATION TRIP .......................................................18
PROFIBUS-DPV1 COMMUNICATIONS ................................................................................19369 RELAY PROFIBUS-DPV1 PARAMETERIZATION ..................................................19369 RELAY PROFIBUS CONFIGURATION .....................................................................19369 RELAY PROFIBUS INPUT DATA ............................................................................20369 RELAY PROFIBUS OUTPUT DATA ........................................................................21369 RELAY PROFIBUS DIAGNOSTICS ..........................................................................22369 RELAY PROFIBUS-DPV1 ACYCLICAL COMMUNICATION ..................................22369 RELAY PROFIBUS-DPV1 LOSS OF COMMUNICATION TRIP ............................23
DEVICENET PROTOCOL ............................................................................................................ 24DEVICENET COMMUNICATIONS ....................................................................................24POLL DATA ......................................................................................................................25CHANGE OF STATE (COS) .............................................................................................27IDENTITY OBJECT (CLASS CODE 01H) ..........................................................................28MESSAGE ROUTER (CLASS CODE 02H) ........................................................................28DEVICENET OBJECT (CLASS CODE 03H) .....................................................................28ASSEMBLY OBJECT (CLASS CODE 04H) .......................................................................29DEVICENET CONNECTION OBJECT (CLASS CODE 05H) ............................................31ACKNOWLEDGE HANDLER OBJECT (CLASS CODE 2BH) ...........................................32I/O DATA INPUT MAPPING OBJECT (CLASS CODE A0H) ..........................................32I/O DATA OUTPUT MAPPING OBJECT (CLASS CODE A1H) ......................................33PARAMETER DATA INPUT MAPPING OBJECT (CLASS CODE B0H) ............................33DEVICENET LOSS OF COMMUNICATION TRIP ............................................................41DEVICENET DATA FORMATS .........................................................................................42
MODBUS RTU PROTOCOL .......................................................................................................46DATA FRAME FORMAT AND DATA RATE .....................................................................46DATA PACKET FORMAT ..................................................................................................46ERROR CHECKING ..........................................................................................................47CRC-16 ALGORITHM ....................................................................................................47TIMING .............................................................................................................................48SUPPORTED MODBUS FUNCTIONS ..............................................................................48ERROR RESPONSES ........................................................................................................48MODBUS COMMANDS ...................................................................................................49
MEMORY MAP ...............................................................................................................................51MEMORY MAP INFORMATION .......................................................................................51USER DEFINABLE MEMORY MAP AREA .......................................................................51EVENT RECORDER ..........................................................................................................52WAVEFORM CAPTURE ....................................................................................................52
TOC–2 369 MOTOR MANAGEMENT RELAY– INSTRUCTION MANUAL
TABLE OF CONTENTS
MOTOR START DATA LOGGER ......................................................................................52DATA LOGGER .................................................................................................................53MODBUS MEMORY MAP ................................................................................................54FORMAT CODES ........................................................................................................... 131
CHANGE NOTES ........................................................................................................................ 163REVISION HISTORY ...................................................................................................... 163
WARRANTY ................................................................................................................................. 165WARRANTY INFORMATION ......................................................................................... 165
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG–1
369 Motor Management Relay
Communications Guide
GE Consumer & IndustrialMultilin
Communications Guide
1 Overview
1.1 Electrical Interface The hardware or electrical interface is one of the following:
• one of three 2-wire RS485 ports from the rear terminal connector,
• the RS232 from the front panel connector
• a fibre optic connection.
In a 2-wire RS485 link, data flow is bidirectional. Data flow is half-duplex for both the RS485 and the RS232 ports. That is, data is never transmitted and received at the same time. RS485 lines should be connected in a daisy chain configuration (avoid star connections) with a terminating network installed at each end of the link, i.e. at the master end and at the slave farthest from the master. The terminating network should consist of a 120 ohm resistor in series with a 1 nF ceramic capacitor when used with Belden 9841 RS485 wire. The value of the terminating resistors should be equal to the characteristic impedance of the line. This is approximately 120 ohms for standard #22 AWG twisted pair wire. Shielded wire should always be used to minimize noise. Polarity is important in RS485 communications. Each '+' terminal of every 369 must be connected together for the system to operate. See the 369 Instruction Manual, chapter 3 for details on correct serial port wiring.
When using a fibre optic link the Tx from the 369 should be connected to the Rx of the Master device and the Rx from the 369 should be connected to the Tx of the Master device.
CG2 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
OVERVIEW CGCOMMUNICATIONS GUIDE
1.2 Profibus CommunicationsThe 369 Motor Management Relay supports both Profibus-DP (order code P) and Profibus-DPV1 (order code P1) communication interfaces as slave that can be read and written to/from a Profibus-DP/V1 master. The Profibus-DP/V1 Master must read the GSD (Device Master Data) file of the 369 for the purposes of configuration and parameterization.
• The GSD file for the Profibus-DP option is 369_090C.gse.
• The GSD file for the Profibus-DPV1 option is 369_09E6.gse.
• The relay supports the following configurations and indications:
• Fieldbus type: PROFIBUS-DP (IEC 61158 Type 3, and IEC 61784)
• Auto baud rate detection 9.6Kbit - 12Mbit.
• Address range: 1-126, setting via EnerVista 369 Setup software or front keypad.
• Input data: 220 bytes - cyclical.
• Extended Diagnostic data: 26 bytes - non-cyclical.
• Sections 2.2 to 2.4 pertain to the Profibus-DP option.
• In addition to the above, the Profibus-DPV1 (P1) option supports:
• Fieldbus type: Profibus-DPV1 (IEC 61158 Type 3, and IEC 61784)
• Acyclic read/write between a Master (Class1/Class2) and the 369 slave according to the DPV1 extensions of IEC 61158.
• Output Data: 2 bytes - cyclical.
Sections 3.1 to 3.6 of this manual pertain to the Profibus-DPV1 option.
1.3 DeviceNet CommunicationsThe 369 Motor Management Relay supports the optional DeviceNet protocol as slave that can be read by a DeviceNet master. The device can be added to a DeviceNet list by adding the 369.eds file in the scanner list. The EDS file can be generated using the EnerVista 369 Setup program.
The relay supports following configuration.
• Field bus type: DeviceNet
• Functions supported: Explicit, Polled, COS and Cyclic IO messaging
• Baud Rate: 125, 250 and 500 kbps, programmable through software or relay front keypad
• Mac ID: 0 to 63, programmable through software or relay front keypad
See section 4: DeviceNet Protocol, for complete details.
1.4 Modbus CommunicationsThe 369 implements a subset of the AEG Modicon Modbus RTU serial communication standard. Many popular programmable controllers support this protocol directly with a suitable interface card allowing direct connection of relays. Although the Modbus protocol is hardware independent, the 369 interfaces include three 2-wire RS485 ports and one
CGCOMMUNICATIONS GUIDE OVERVIEW
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG3
RS232 port. Modbus is a single master, multiple slave protocol suitable for a multi-drop configuration as provided by RS485 hardware. In this configuration up to 32 slaves can be daisy-chained together on a single communication channel.
The 369 is always a slave. It cannot be programmed as a master. Computers or PLCs are commonly programmed as masters. The Modbus protocol exists in two versions: Remote Terminal Unit (RTU, binary) and ASCII. Only the RTU version is supported by the 369. Monitoring, programming and control functions are possible using read and write register commands.
1.5 Modbus/TCP Communications
Modbus/TCP Option:
When configured with the “E” Option, the 369 can connect to Ethernet networks via the rear RJ45 connection, using the Modbus/TCP protocol as detailed in the document “Open Modbus / TCP Specification” by Andy Swales, Release 1.0, 29 March 1999 (a search via the internet can produce a free copy of this document).
This description contains information to the location of Setting registers for configuring the 369 for a LAN connection, and the physical connection of the 369. Information pertaining to the application of an IED over Ethernet is beyond the scope of this manual and users should consult their Network Administrators for configuration details.
Note The implementation of this option is for the intention of data retrieval and device configuration. The 369 does not support firmware upgrade via this connection.
Setpoints Configuration:
The user needs to configure the following settings for interface to a LAN: IP ADDRESS, SUBNET MASK, and GATEWAY ADDRESS. Each setting contains 4 octets. The user configures the octets as shown in the following example:
IP ADDRESS: “127.0.0.1”SUBNET MASK: “255.255.255.252”GATEWAY ADDRESS: “127.0.0.1”
SETPOINT MEMORY MAPADDRESS
DATA VALUE(DEC)
IP ADDRESS OCTET1 0x101C 127IP ADDRESS OCTET2 0x101D 0
IP ADDRESS OCTET3 0x101E 0IP ADDRESS OCTET4 0x101F 1SUBNET MASK OCTET1 0x1020 255
SUBNET MASK OCTET2 0x1021 255SUBNET MASK OCTET3 0x1022 255
SUBNET MASK OCTET4 0x1023 252GATEWAY ADDRESS OCTET1 0x1024 127GATEWAY ADDRESS OCTET2 0x1025 0
GATEWAY ADDRESS OCTET3 0x1026 0
CG4 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
OVERVIEW CGCOMMUNICATIONS GUIDE
These settings can also be configured via the keypad under the S1 369 SETUP 369 COMMUNICATIONS path.
Physical Connection:
The 369 can be connected to an Ethernet LAN via the RJ45 connector at the back of the 369.
Ethernet Loss Of Communication Trip
The 369 can detect a failure in communication activity with the MODBUS Master through Ethernet port. The Ethernet Loss of Communications feature can be used to trip any combination of output relays.
When equipped with the Ethernet option, the 369 can be configured to check for MODBUS TCP/IP activity, and raise an alarm and trip an output relay if activity is not detected within the configured delay. Delays of 0.25 to 10.00 seconds may be configured by the user.
If the “Fieldbus Loss of Comms” function is enabled , the 369 considers an Ethernet loss of communication to have occurred in the following conditions:
1. Link failure (break in physical connection)
2. If valid MODBUS packets are not received within the configured delay period. Invalid MODBUS packets, such as ones that contain the wrong slave ID, are not considered valid. Please note that an ICMP PING message is not a valid MODBUS packet
3. If packets cannot be received because of buffer overflows or lack of queue space, the delay timer will continue to decrement, and will not be reset until valid packets are received. If the queues / buffers cannot be recovered within the configured delay, the Loss of Communication alarm will be raised, and any configured relays shall trip.
A delay of 0.25 sec to 10.00 sec in steps of 0.25 sec can be programmed to delay the output relay activation. To avoid false trips, it is advised to set the trip delay greater than MODBUS timeout delay.
This feature can be programmed for Latched or Unlatched operation.
If programmed as Latched:
The “Fieldbus Loss of Comms” trip will remain latched until the communication with the Modbus Master through Ethernet port is (re) established AND the latched trip is manually reset or remotely reset via Modbus communications.
If programmed as Unlatched:
Any programmed output relays for this feature will be activated until communication with the Modbus master through Ethernet port is active. Once communication is active, the trip condition will be cleared and the assigned output relays will automatically de-activate.
The setpoints associated with this feature are:
1. Fieldbus Loss of Comms Enable
2. Fieldbus Loss of Comms Delay
GATEWAY ADDRESS OCTET4 0x1027 1
SETPOINT MEMORY MAPADDRESS
DATA VALUE(DEC)
CGCOMMUNICATIONS GUIDE OVERVIEW
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG5
3. Assign Loss of Comms Relay
Refer to the 369 Instruction Manual, chapter 5: 369 Relay Communications for more information on these setpoints.
CG6 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
PROFIBUS-DP COMMUNICATIONS CGCOMMUNICATIONS GUIDE
2 Profibus-DP Communications
2.1 Profibus Communication OptionsThe 369 Motor Management Relay supports either Profibus-DP (order code P) or Profibus-DPV1 (order code P1) communication interfaces as slave that can be read and written to/from a Profibus-DP/V1 master. The Profibus-DP/V1 Master must read the GSD (Device Master Data) file of the 369 for the purposes of configuration and parameterization.
• The GSD file for the Profibus-DP option is 369_090C.GSE.
• The GSD file for the Profibus-DPV1 option is 369_09E6.GSE.
Sections 2.2 to 2.4 pertain to the Profibus-DP option.
Sections 3.1 to 3.6 of this manual pertain to the Profibus-DPV1 option.
2.2 369 Relay Profibus-DP ParameterizationThe 369 Motor Management Relay supports mandatory parametrization. The relay keeps its user parameter data / setpoints in a non-volatile memory and does not need device related parametrization during startup of the DP master. The EnerVista 369 Setup software is the best tool for user parametrization of the 369 device.
2.3 369 Relay Profibus-DP ConfigurationThe Profibus-DP basic configuration has one DP master and one DP slave. In a typical bus segment up to 32 stations can be connected (a repeater has to be used if more than 32 stations operate on a bus). The end nodes on a Profibus-DP network must be terminated to avoid reflections on the bus line.
The bus address for the relay as Profibus-DP node can be set using the S1 369 RELAY SETUP 369 RELAY COMMUNICATIONS PROFIBUS ADDRESS setpoint or via the EnerVista 369 Setup software, which extends address range from 1 to 126. Address 126 is used only for commissioning purposes and should not be used to exchange user data.
The media for the fieldbus is a twisted pair copper cable along with 9-pin SUB-D connector, which connects the bus to the 369 socket on the back of the relay. The 369 Motor Management Relay has autobaud support. The baud rates and other slave specific information needed for configuration are contained in 369_090C.gs* which is used by a network configuration program.
The 369 Motor Management Relay as a DP slave transfers fast process data to the DP master according to master-slave principle. The 369 Motor Management Relay is a modular device, supporting up to 8 input modules.
During the configuration session, all modules have to be selected in order to get the entire area of 110 words of input data. There are no output data for processing. The following diagram shows the possible DP Master Class 2 configuration menu:
CGCOMMUNICATIONS GUIDE PROFIBUS-DP COMMUNICATIONS
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG7
FIGURE CG–1: Slave Configuration
Table CG–1: Profibus Input Data (Sheet 1 of 5)
OFFSET CYCLIC DATA (ACTUAL VALUES)
LENGTH (BYTES)
MINIMUM MAXIMUM STEP VALUE
UNITS FORMAT CODE
DEFAULT
VALUE HEX VALUE HEX
0 MotorStatus 2 0 0000 4 0004 1 – F133 0
2 TC_Used 2 0 0000 100 0064 1 % F1 0
4 Time_to_Trip 2 –1 FFFF 65500 FFDC 1 s F20 –1
6 OverloadLT 2 0 0000 50000 C350 1 s F1 0
8 StartsHourLT[5] 2 0 0000 60 003C 1 min F1 0
10 TimeBetween StartsLT 2 0 0000 500 01F4 1 min F1 0
12 RestartBlock LT 2 0 0000 50000 C350 1 s F1 0
14 StartInhibitLT 2 0 0000 60 003C 1 min F1 0
16 AccessSwitch Status 2 0 0000 1 0001 1 – F131 0
18 SpeedSwitch Status 2 0 0000 1 0001 1 – F131 0
20 SpareSwitch Status 2 0 0000 1 0001 1 – F131 0
22 DiffSwitch Status 2 0 0000 1 0001 1 – F131 0
24 EmergencySwitch status 2 0 0000 1 0001 1 – F131 0
26 ResetSwitch Status 2 0 0000 1 0001 1 – F131 0
CG8 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
PROFIBUS-DP COMMUNICATIONS CGCOMMUNICATIONS GUIDE
28 TripRelayStatus 2 0 0000 1 0001 1 N/A F150 2
30 AlarmRelayStatus 2 0 0000 1 0001 1 N/A F150 2
32 Aux1RelayStatus 2 0 0000 1 0001 1 N/A F150 2
34 Aux2RelayStatus 2 0 0000 1 0001 1 N/A F150 2
36 Ia 2 0 0000 65535 FFFF 1 A F1 0
38 Ib 2 0 0000 65535 FFFF 1 A F1 0
40 Ic 2 0 0000 65535 FFFF 1 A F1 0
42 AveragePhaseCurrent 2 0 0000 65535 FFFF 1 A F1 0
44 MotorLoad 2 0 0000 2000 07D0 1 xFLA F3 0
46 CurrentUnbalance 2 0 0000 100 0064 1 % F1 0
48 U/B Biased Motor Load 2 0 0000 2000 07D0 1 xFLC F3 0
50 GroundCurrent 2 0 0000 50000 C350 1 A F23 0
52 Vab 2 0 0000 65000 FDE8 1 V F1 0
54 Vbc 2 0 0000 65000 FDE8 1 V F1 0
56 Vca 2 0 0000 65000 FDE8 1 V F1 0
58 Van 2 0 0000 65000 FDE8 1 V F1 0
60 Vbn 2 0 0000 65000 FDE8 1 V F1 0
62 Vcn 2 0 0000 65000 FDE8 1 V F1 0
64 AvgLineVoltage 2 0 0000 65000 FDE8 1 V F1 0
66 AvgPhaseVoltage 2 0 0000 65000 FDE8 1 V F1 0
68 Frequency 2 0 0000 12000 2EE0 1 Hz F3 0
70 BackSpinFrequency 2 1 0001 12000 2EE0 1 Hz F3 0
72 PowerFactor 2 –99 FF9D 100 0064 1 – F21 0
74 RealPower–kW 2 –32000 8300 32000 7D00 1 kW F4 0
76 RealPower–hp 2 0 0000 65000 FDE8 1 hp F1 0
78 ReactivePower 2 –32000 8300 32000 7D00 1 kvar F4 0
80 ApparentPower 2 0 0000 65000 FDE8 1 kVA F1 0
82 MWh 2 0 0000 65535 FFFF 1 MWh F1 0
84 PositiveMvarh 2 0 0000 65535 FFFF 1 Mvarh F1 0
86 NegativeMvarh 2 0 0000 65535 FFFF 1 Mvarh F1 0
88 HottestStatorRtd 2 0 0000 12 000C 1 F2 0
Table CG–1: Profibus Input Data (Sheet 2 of 5)
OFFSET CYCLIC DATA (ACTUAL VALUES)
LENGTH (BYTES)
MINIMUM MAXIMUM STEP VALUE
UNITS FORMAT CODE
DEFAULT
VALUE HEX VALUE HEX
CGCOMMUNICATIONS GUIDE PROFIBUS-DP COMMUNICATIONS
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG9
90 HottestStatorRtdTemp 2 –40 FFD8 200 00C8 1 °C F4 –42
92 LocalRtd1 2 –40 FFD8 200 00C8 1 °C F4 –42
94 LocalRtd2 2 –40 FFD8 200 00C8 1 °C F4 –42
96 LocalRtd3 2 –40 FFD8 200 00C8 1 °C F4 –42
98 LocalRtd4 2 –40 FFD8 200 00C8 1 °C F4 –42
100 LocalRtd5 2 –40 FFD8 200 00C8 1 °C F4 –42
102 LocalRtd6 2 –40 FFD8 200 00C8 1 °C F4 –42
104 LocalRtd7 2 –40 FFD8 200 00C8 1 °C F4 –42
106 LocalRtd8 2 –40 FFD8 200 00C8 1 °C F4 –42
108 LocalRtd9 2 –40 FFD8 200 00C8 1 °C F4 –42
110 LocalRtd10 2 –40 FFD8 200 00C8 1 °C F4 –42
112 LocalRtd11 2 –40 FFD8 200 00C8 1 °C F4 –42
114 LocalRtd12 2 –40 FFD8 200 00C8 1 °C F4 –42
116 CurrentDemand 2 0 0000 50000 C350 1 A F1 0
118 RealPowerDemand 2 0 0000 50000 C350 1 kW F1 0
120 ReactivePowerDemand 2 –32000 8300 32000 7D00 1 kvar F4 0
122 ApparentPowerDemand 2 0 0000 50000 C350 1 kVA F1 0
124 PeakCurrent 2 0 0000 65535 FFFF 1 A F1 0
126 PeakRealPower 2 0 0000 50000 C350 1 kW F1 0
128 PeakReactivePower 2 –32000 8300 32000 7D00 1 kvar F4 0
130 PeakApparentPower 2 0 0000 50000 C350 1 kVA F1 0
132 Va angle 2 0 0000 359 0167 1 o F1 0
134 Vb angle 2 0 0000 359 0167 1 o F1 0
136 Vc angle 2 0 0000 359 0167 1 o F1 0
138 Ia angle 2 0 0000 359 0167 1 o F1 0
140 Ib angle 2 0 0000 359 0167 1 o F1 0
142 Ic angle 2 0 0000 359 0167 1 o F1 0
144 Learned AccelerationTime
2 1 0001 2500 09C4 1 s F2 0
146 Learned StartingCurrent 2 0 0000 65535 FFFF 1 A F1 0
148 Learned StartingCapacity
2 0 0000 100 0064 1 % F1 0
Table CG–1: Profibus Input Data (Sheet 3 of 5)
OFFSET CYCLIC DATA (ACTUAL VALUES)
LENGTH (BYTES)
MINIMUM MAXIMUM STEP VALUE
UNITS FORMAT CODE
DEFAULT
VALUE HEX VALUE HEX
CG10 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
PROFIBUS-DP COMMUNICATIONS CGCOMMUNICATIONS GUIDE
150 Learned RunningCoolTime Constant
2 0 0000 500 01F4 1 min F1 0
152 LearnedStoppedCoolTime Constant
2 0 0000 500 01F4 1 min F1 0
154 Last StartingCapacity 2 0 0000 100 0064 1 % F1 0
156 Learned UnbalanceKfactor
2 0 0000 29 001D 1 – F1 0
158 BSDState 2 0 0000 6 0006 1 – F27 0
160 RawPredictionTimer 2 0 0000 50000 C350 1 s F2 0
162 NumberOfStarts 2 0 0000 50000 C350 1 – F1 0
164 NumberOfRestarts 2 0 0000 50000 C350 1 – F1 0
166 DigitalCounter 2 0 0000 65535 FFFF 1 – F1 0
168 MotorRunningHours 2 0 0000 65535 FFFF 1 hr F1 0
170 RelayOperatingHours 2 0 0000 65535 FFFF 1 hr F1 0
172 Last trip Cause 2 0 0000 169 00A9 1 – F134 0
174 Last trip Date 4 N/A N/A N/A N/A N/A N/A F18 N/A
178 Last trip Time 4 N/A N/A N/A N/A N/A N/A F19 N/A
182 Last pre-trip Ia 2 0 0000 65535 FFFF 1 A F1 0
184 Last pre-trip Ib 2 0 0000 65535 FFFF 1 A F1 0
186 Last pre-trip Ic 2 0 0000 65535 FFFF 1 A F1 0
188 Last pre-trip MotorLoad 2 0 0000 2000 07D0 1 FLA F3 0
190 Last pre-trip Unbalance 2 0 0000 100 0064 1 % F1 0
192 Last pre-trip Ig 2 0 0000 50000 C350 1 A F23 0
194 Last trip HottestStatorRtd
2 0 0000 12 000C 1 – F1 0
196 Last trip HottestStatorTemp
2 –40 FFD8 200 00C8 1 °C F4 0
198 Last pre–trip Vab 2 0 0000 65000 FDE8 1 V F1 0
200 Last pre–trip Vbc 2 0 0000 65000 FDE8 1 V F1 0
202 Last pre–trip Vca 2 0 0000 65000 FDE8 1 V F1 0
204 Last pre–trip Van 2 0 0000 65000 FDE8 1 V F1 0
206 Last pre–trip Vbn 2 0 0000 65000 FDE8 1 V F1 0
Table CG–1: Profibus Input Data (Sheet 4 of 5)
OFFSET CYCLIC DATA (ACTUAL VALUES)
LENGTH (BYTES)
MINIMUM MAXIMUM STEP VALUE
UNITS FORMAT CODE
DEFAULT
VALUE HEX VALUE HEX
CGCOMMUNICATIONS GUIDE PROFIBUS-DP COMMUNICATIONS
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG11
2.4 369 Relay Profibus-DP DiagnosticsThe 369 Motor Management Relay supports both slave mandatory (6 bytes system-wide standardized) and slave specific diagnostic data. If the diagnostics are considered high priority, the PLC/host program will be informed of the fault (alarm or trip) and can call a special error routine.
Diagnostic bytes 1 through 6 represent standard diagnostic data and are formatted as follows.
The extended diagnosis for the relay is composed of 26 bytes (bytes 7 to 32) and contains diagnostic information according to the following table.
208 Last pre–trip Vcn 2 0 0000 65000 FDE8 1 V F1 0
210 Last pre–trip Frequency 2 0 0000 12000 2EE0 1 Hz F3 0
212 Last pre–trip KiloWatts 2 –32000 8300 32000 7D00 1 kW F4 0
214 Last pre–trip KiloVAR 2 –32000 8300 32000 7D00 1 kvar F4 0
216 Last pre–trip KiloVA 2 0 0000 50000 C350 1 kVA F1 0
218 Last pre–trip PowerFactor
2 –99 FF9D 100 0064 1 – F21 0
Table CG–1: Profibus Input Data (Sheet 5 of 5)
OFFSET CYCLIC DATA (ACTUAL VALUES)
LENGTH (BYTES)
MINIMUM MAXIMUM STEP VALUE
UNITS FORMAT CODE
DEFAULT
VALUE HEX VALUE HEX
Table CG–2: Diagnostic bytes 1 through 7
BYTE DESCRIPTION
1 Station Status 1
2 Station Status 2
3 Station Status 3
4 Diagnostic Master Address
5 Identification Number (High Byte)
6 Identification Number (Low Byte)
Table CG–3: Profibus Diagnostics (Sheet 1 of 8)
BIT BYTE FUNCTION
0 to 7 7 Number of Diagnostic Bytes
0 8 SinglePhasingTrip
1 8 SpareSwitchTrip
2 8 EmergencySwitchTrip
CG12 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
PROFIBUS-DP COMMUNICATIONS CGCOMMUNICATIONS GUIDE
3 8 DifferentialSwitchTrip
4 8 SpeedSwitchTrip
5 8 ResetSwitchTrip
6 8 Reserved
7 8 OverloadTrip
8 9 ShortCircuitTrip
9 9 ShortCircuitBackupTrip
10 9 MechanicalJamTrip
11 9 UndercurrentTrip
12 9 CurrentUnbalanceTrip
13 9 GroundFaultTrip
14 9 GroundFaultBackupTrip
15 9 Reserved
16 10 AccelerationTimerTrip
17 10 Rtd1Trip
18 10 Rtd2Trip
19 10 Rtd3Trip
20 10 Rtd4Trip
21 10 Rtd5Trip
22 10 Rtd6Trip
23 10 Rtd7Trip
24 11 Rtd8Trip
25 11 Rtd9Trip
26 11 Rtd10Trip
27 11 Rtd11Trip
28 11 Rtd12Trip
29 11 UnderVoltageTrip
30 11 OverVoltageTrip
31 11 VoltagePhaseReversalTrip
32 12 UnderfrequencyTrip
33 12 OverfrequencyTrip
34 12 LeadPowerFactorTrip
Table CG–3: Profibus Diagnostics (Sheet 2 of 8)
BIT BYTE FUNCTION
CGCOMMUNICATIONS GUIDE PROFIBUS-DP COMMUNICATIONS
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG13
35 12 LagPowerFactorTrip
36 12 PositivekvarTrip
37 12 NegativekvarTrip
38 12 UnderpowerTrip
39 12 ReversePowerTrip
40 13 IncompleteSequenceTrip
41 13 SpareSwitchAlarm
42 13 EmergencySwitchAlarm
43 13 DifferentialSwitchAlarm
44 13 SpeedSwitchAlarm
45 13 ResetSwitchAlarm
46 13 Reserved
47 13 ThermalCapacityAlarm
48 14 OverloadAlarm
49 14 MechanicalJamAlarm
50 14 UndercurrentAlarm
51 14 CurrentUnbalanceAlarm
52 14 GroundFaultAlarm
53 14 UndervoltageAlarm
54 14 OvervoltageAlarm
55 14 OverfrequencyAlarm
56 15 UnderfrequencyAlarm
57 15 LeadPowerFactorAlarm
58 15 LagPowerFactorAlarm
59 15 PositivekvarAlarm
60 15 NegativekvarAlarm
61 15 UnderpowerAlarm
62 15 ReversePowerAlarm
63 15 Rtd1Alarm
64 16 Rtd2Alarm
65 16 Rtd3Alarm
66 16 Rtd4Alarm
Table CG–3: Profibus Diagnostics (Sheet 3 of 8)
BIT BYTE FUNCTION
CG14 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
PROFIBUS-DP COMMUNICATIONS CGCOMMUNICATIONS GUIDE
67 16 Rtd5Alarm
68 16 Rtd6Alarm
69 16 Rtd7Alarm
70 16 Rtd8Alarm
71 16 Rtd9Alarm
72 17 Rtd10Alarm
73 17 Rtd11Alarm
74 17 Rtd12Alarm
75 17 Rtd1HighAlarm
76 17 Rtd2HighAlarm
77 17 Rtd3HighAlarm
78 17 Rtd4HighAlarm
79 17 Rtd5HighAlarm
80 18 Rtd6HighAlarm
81 18 Rtd7HighAlarm
82 18 Rtd8HighAlarm
83 18 Rtd9HighAlarm
84 18 Rtd10HighAlarm
85 18 Rtd11HighAlarm
86 18 Rtd12HighAlarm
87 18 OpenRTDSensorAlarm
88 19 ShortRTDAlarm
89 19 TripCountersAlarm
90 19 StarterFailureAlarm
91 19 CurrentDemandAlarm
92 19 KWDemandAlarm
93 19 KVARDemandAlarm
94 19 KVADemandAlarm
95 19 DigitalCounterAlarm
96 20 OverloadLockoutBlock
97 20 StartInhibitBlock
98 20 StartsHourBlock
Table CG–3: Profibus Diagnostics (Sheet 4 of 8)
BIT BYTE FUNCTION
CGCOMMUNICATIONS GUIDE PROFIBUS-DP COMMUNICATIONS
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG15
99 20 TimeBetweenStartsBlock
100 20 RestartBlock
101 20 Reserved
102 20 BackSpinBlock
103 20 LossofRemoteRTDCommunication
104 21 RemoteRTD1Rtd1Trip
105 21 RemoteRTD1Rtd2Trip
106 21 RemoteRTD1Rtd3Trip
107 21 RemoteRTD1Rtd4Trip
108 21 RemoteRTD1Rtd5Trip
109 21 RemoteRTD1Rtd6Trip
110 21 RemoteRTD1Rtd7Trip
111 21 RemoteRTD1Rtd8Trip
112 22 RemoteRTD1Rtd9Trip
113 22 RemoteRTD1Rtd10Trip
114 22 RemoteRTD1Rtd11Trip
115 22 RemoteRTD1Rtd12Trip
116 22 RemoteRTD2Rtd1Trip
117 22 RemoteRTD2Rtd2Trip
118 22 RemoteRTD2Rtd3Trip
119 22 RemoteRTD2Rtd4Trip
120 23 RemoteRTD2Rtd5Trip
121 23 RemoteRTD2Rtd6Trip
122 23 RemoteRTD2Rtd7Trip
123 23 RemoteRTD2Rtd8Trip
124 23 RemoteRTD2Rtd9Trip
125 23 RemoteRTD2Rtd10Trip
126 23 RemoteRTD2Rtd11Trip
127 23 RemoteRTD2Rtd12Trip
128 24 RemoteRTD3Rtd1Trip
129 24 RemoteRTD3Rtd2Trip
130 24 RemoteRTD3Rtd3Trip
Table CG–3: Profibus Diagnostics (Sheet 5 of 8)
BIT BYTE FUNCTION
CG16 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
PROFIBUS-DP COMMUNICATIONS CGCOMMUNICATIONS GUIDE
131 24 RemoteRTD3Rtd4Trip
132 24 RemoteRTD3Rtd5Trip
133 24 RemoteRTD3Rtd6Trip
134 24 RemoteRTD3Rtd7Trip
135 24 RemoteRTD3Rtd8Trip
136 25 RemoteRTD3Rtd9Trip
137 25 RemoteRTD3Rtd10Trip
138 25 RemoteRTD3Rtd11Trip
139 25 RemoteRTD3Rtd12Trip
140 25 RemoteRTD4Rtd1Trip
141 25 RemoteRTD4Rtd2Trip
142 25 RemoteRTD4Rtd3Trip
143 25 RemoteRTD4Rtd4Trip
144 26 RemoteRTD4Rtd5Trip
145 26 RemoteRTD4Rtd6Trip
146 26 RemoteRTD4Rtd7Trip
147 26 RemoteRTD4Rtd8Trip
148 26 RemoteRTD4Rtd9Trip
149 26 RemoteRTD4Rtd10Trip
150 26 RemoteRTD4Rtd11Trip
151 26 RemoteRTD4Rtd12Trip
152 27 RemoteRTD1Rtd1Alarm
153 27 RemoteRTD1Rtd2Alarm
154 27 RemoteRTD1Rtd3Alarm
155 27 RemoteRTD1Rtd4Alarm
156 27 RemoteRTD1Rtd5Alarm
157 27 RemoteRTD1Rtd6Alarm
158 27 RemoteRTD1Rtd7Alarm
159 27 RemoteRTD1Rtd8Alarm
160 28 RemoteRTD1Rtd9Alarm
161 28 RemoteRTD1Rtd10Alarm
162 28 RemoteRTD1Rtd11Alarm
Table CG–3: Profibus Diagnostics (Sheet 6 of 8)
BIT BYTE FUNCTION
CGCOMMUNICATIONS GUIDE PROFIBUS-DP COMMUNICATIONS
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG17
163 28 RemoteRTD1Rtd12Alarm
164 28 RemoteRTD2Rtd1Alarm
165 28 RemoteRTD2Rtd2Alarm
166 28 RemoteRTD2Rtd3Alarm
167 28 RemoteRTD2Rtd4Alarm
168 29 RemoteRTD2Rtd5Alarm
169 29 RemoteRTD2Rtd6Alarm
170 29 RemoteRTD2Rtd7Alarm
171 29 RemoteRTD2Rtd8Alarm
172 29 RemoteRTD2Rtd9Alarm
173 29 RemoteRTD2Rtd10Alarm
174 29 RemoteRTD2Rtd11Alarm
175 29 RemoteRTD2Rtd12Alarm
176 30 RemoteRTD3Rtd1Alarm
177 30 RemoteRTD3Rtd2Alarm
178 30 RemoteRTD3Rtd3Alarm
179 30 RemoteRTD3Rtd4Alarm
180 30 RemoteRTD3Rtd5Alarm
181 30 RemoteRTD3Rtd6Alarm
182 30 RemoteRTD3Rtd7Alarm
183 30 RemoteRTD3Rtd8Alarm
184 31 RemoteRTD3Rtd9Alarm
185 31 RemoteRTD3Rtd10Alarm
186 31 RemoteRTD3Rtd11Alarm
187 31 RemoteRTD3Rtd12Alarm
188 31 RemoteRTD4Rtd1Alarm
189 31 RemoteRTD4Rtd2Alarm
190 31 RemoteRTD4Rtd3Alarm
191 31 RemoteRTD4Rtd4Alarm
192 32 RemoteRTD4Rtd5Alarm
193 32 RemoteRTD4Rtd6Alarm
194 32 RemoteRTD4Rtd7Alarm
Table CG–3: Profibus Diagnostics (Sheet 7 of 8)
BIT BYTE FUNCTION
CG18 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
PROFIBUS-DP COMMUNICATIONS CGCOMMUNICATIONS GUIDE
2.5 Profibus-DP Loss Of Communication Trip If the 369 detects a problem in communicating with the Profibus master, the Profibus Loss of Communications feature can be used to operate on any combination of output relays.
During parameterization, a Profibus master sets up the communication and monitoring times for the slave including the watchdog time. A Profibus slave uses a watchdog timer to enable it to detect bus inactivity with its master. The watchdog timer is reset every time an error free message is received from the master. If no valid message is received within the time specified during parameterization, the slave assumes a communication error.
If the 369 Profibus communications is offline and not communicating with a master, then the “Fieldbus Loss of Comms” function (if enabled) will activate. This feature can be programmed for Latched or Unlatched operation.
If programmed as Latched:
The “Fieldbus Loss of Comms” output relay will remain latched until communication with the Master is (re) established AND the latched output relay is manually reset or remotely reset via Modbus communications.
If programmed as Unlatched:
Any output relays programmed for this feature will be de-activated once communication is restored; the Loss of Communication condition will be cleared and the assigned output relays will automatically de-activate.
The setpoints associated with this feature are:
1. Fieldbus Loss of Comms Enable
2. Fieldbus Loss of Comms Delay
3. Assigned Fieldbus Loss of Comms Relay
Refer to the 369 Instruction Manual, chapter 5: 369 Relay Communications for more information on these setpoints.
195 32 RemoteRTD4Rtd8Alarm
196 32 RemoteRTD4Rtd9Alarm
197 32 RemoteRTD4Rtd10Alarm
198 32 RemoteRTD4Rtd11Alarm
199 32 RemoteRTD4Rtd12Alarm
Table CG–3: Profibus Diagnostics (Sheet 8 of 8)
BIT BYTE FUNCTION
CGCOMMUNICATIONS GUIDE PROFIBUS-DPV1 COMMUNICATIONS
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG19
3 Profibus-DPV1 Communications
3.1 369 Relay Profibus-DPV1 ParameterizationThe 369 Motor Management Relay supports mandatory parametrization as well as three bytes of user parameter data necessary for DPV1 devices. The relay keeps its user parameter data/setpoints in a non-volatile memory and does not require device related parametrization during startup of the DP/V1 master, with the exception of the DPV1 Enable parameter. To enable the DPV1 acyclical functionality, the DPV1 parameter must be set to “Enable” when configuring the device in your master using the GSD file.
The EnerVista 369 Setup software is the best tool for editing user parametrization (setpoints) of the 369 Relay device.
FIGURE CG–2: User Parameter Setup – Enable DPV1
3.2 369 Relay Profibus ConfigurationThe Profibus-DPV1 basic configuration has one DP/V1 master and one DPV1 slave. In a typical bus segment up to 32 stations can be connected (a repeater has to be used if more then 32 stations operate on a bus). The end nodes on a Profibus-DPV1 network must be terminated to avoid reflections on the bus line.
The bus address for the relay as Profibus-DPV1 node can be set using the S1 369 SETUP 369 COMMUNICATIONS PROFIBUS ADDRESS setpoint or via the EnerVista 369
Setup software, which extends address range from 1 to 126. Address 126 is used only for commissioning purposes and should not be used to exchange user data.
CG20 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
PROFIBUS-DPV1 COMMUNICATIONS CGCOMMUNICATIONS GUIDE
The Profibus media is a twisted-pair copper cable along with 9-pin Sub-D connector, which connects the bus to the 369 Relay socket on the back of the relay. The 369 Motor Management Relay has autobaud support. The baud rates and other slave specific information needed for configuration are contained in the 369_09E6.gse file, which is used by a network configuration program.
The 369 Motor Management Relay as a DPV1 slave transfers fast process data to the DP/V1 master according to master-slave principle. The 369 Relay is a modular device, supporting up to 111 input modules.
Modules define a block size of input data to be read by the master, starting from offset zero. Adding modules in your Master configuration increases the size of the total block of data that the Master will read, making it easy to choose a total block size of data that matches the user's requirements.
3.3 369 Relay Profibus Input DataThere are two options for configuring what data is made available through Profibus Input Data, based on the value of the PROFIBUS CYCLIC IN DATA setpoint (see 369 Instruction Manual, chapter 5 for details). If the PROFIBUS CYCLIC IN DATA setpoint is set to “0” (default map), then the data available to be read matches Table CG–1: Profibus Input Data on page CG–7.
The user can also exactly define the data provided and the order of that data. The Modbus User Definable Memory Map area and the PROFIBUS CYCLIC IN DATA setpoint are used to define this data. The PROFIBUS CYCLIC IN DATA setpoint determines the number of 16-bit registers available to be read through Profibus Input Data and the Modbus User Definable Memory Map is used to determine the data provided and the order of the data.
For example, if the user only wishes to read two 16-bit registers of data (4 bytes), the user selects a number of Input Modules from the GSD file that add up to a total of 4 bytes. When the Profibus Master is reading the Input data, only 4 bytes of Input data will be sent in the communication packet. The number of words should match the PROFIBUS CYCLIC IN DATA setpoint, but it's not necessary. If the number of Input data bytes read from the master is greater than the user has defined with the PROFIBUS CYCLIC IN DATA setpoint, the balance of the data will return zero values.
CGCOMMUNICATIONS GUIDE PROFIBUS-DPV1 COMMUNICATIONS
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG21
FIGURE CG–3: Slave Configuration Example 1 – 4 Bytes of Input Data
FIGURE CG–4: Slave Configuration Example 2 – 220 Bytes of Input Data
3.4 369 Relay Profibus Output DataThe capability to force the output relays states has been implemented in cyclic output data. As cyclic data is continuously written, the 369 looks for a change in the value to execute the force relays command. Refer to the 369 Instruction Manual, chapter 5 for more information about the force output relays feature.
CG22 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
PROFIBUS-DPV1 COMMUNICATIONS CGCOMMUNICATIONS GUIDE
A slave configuration example for 4 bytes of input data and 2 bytes of output data is shown below.
FIGURE CG–5: Slave Configuration Example – 4 Bytes of Input Data, 2 bytes of Output Data
3.5 369 Relay Profibus DiagnosticsThe diagnostic data available for the Profibus-DPV1 option matches Table CG–3: Profibus Diagnostics on page CG–11. When no diagnostic information is available and the master initiates a diagnostics read, the six slave mandatory bytes are read.
3.6 369 Relay Profibus-DPV1 Acyclical CommunicationThe following items have been made available through Profibus-DPV1 acyclical communication. Data is addressed through the use of “slot and index” addressing. Three parameters are required to read or write data from the 369 Relay using a Profibus-DPV1 master:
1. Slot number
2. Index number
3. Data length (number of 16-bit words)
Table CG–4: Profibus Output Data
OFFSET
CYCLIC DATA (ACTUAL VALUES)
LENGTH (BYTES)
MINIMUM MAXIMUM FORMAT CODE
VALUE HEX VALUE HEX
0 Force Output Relays 2 0 0 15 F F141
CGCOMMUNICATIONS GUIDE PROFIBUS-DPV1 COMMUNICATIONS
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG23
Note The value that is written acyclically to either FORCE OUTPUT RELAYS or BLOCK PROTECTION FUNCTIONS must be a 16-bit value. The lower byte contains the bitmask data (as per format codes noted) and the upper byte written must always contain a value of zero.
Refer to the 369 Instruction Manual, chapter 5 for additional information about the force output relays feature. Refer to the 369 Instruction Manual, chapter 5.3.4 for additional information about the protection function blocking feature.
3.7 369 Relay Profibus-DPV1 Loss Of Communication Trip If the 369 detects a problem in communicating with the Profibus master, the Profibus Loss of Communications feature can be used to operate on any combination of output relays. Refer to the following sections for more information regarding this feature:
369 Communications Guide: Section 2.5: Profibus-DP Loss Of Communication Trip
369 Instruction Manual: Chapter 5: 369 Communications (for information regarding the setpoints for this feature).
Table CG–5: Profibus-DPV1 Acyclic Write Data
OBJECT SLOT INDEX LENGTH DESCRIPTION FORMAT
0 0 0 2 bytes Force Output Relays F141
2 2 bytes Block Protection Functions F180
Table CG–6: Profibus-DPV1 Acyclic Read Data
OBJECT SLOT INDEX LENGTH DATA ITEM FORMAT
0 0
0 2 bytes Trip Relay Status F150
2 2 bytes Alarm Relay Status F150
4 2 bytes Aux1 Relay Status F150
6 2 bytes Aux2 Relay Status F150
8 2 bytes Functions Currently Blocked F141
CG24 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
DEVICENET PROTOCOL CGCOMMUNICATIONS GUIDE
4 DeviceNet Protocol
4.1 DeviceNet CommunicationsThe device profile is an extension of the Generic Device Profile (0x00). It is a group 2 only server. The MAC ID and baud rate are programmable through relay front panel or the EnerVista 369 Setup software. The polling function consumes one byte of control data (described under assembly object class 04, instance 96h) and produces data as per Poll Data Group 1, Poll Data Group 2, or the User-Defined poll data (described in assembly object class 04, instance 64h). The COS\CYC operation produces 4 bytes of data as per Class 4, Instance 66h, Attribute 3.
The EDS file for use with a DeviceNet master can be generated using the EnerVista 369 Setup program. The EDS file differs depending on which Poll Group is selected, and by the amount of data being returned for the User-Defined Poll Data. Note that only one version of the EDS file may be used for any one DeviceNet master.
The 369 Motor Management Relay supports following DeviceNet object classes.
DeviceNet Loss Of Communication Trip
If the 369 detects a failure in communicating with the DeviceNet master, the Fieldbus Loss of Communications feature can be used to trip any combination of output relays.
If the 369 DeviceNet communications is offline and not communicating with a master, then the “Fieldbus Loss of Comms” function (if enabled) will activate. This feature can be programmed for Latched or Unlatched operation.
If the “Fieldbus Loss of Comms” function is enabled , the 369 considers a DeviceNet loss of communication to have occurred in the following conditions:
1. Online; not connected
2. Critical link failure
3. Connection timeout.
Table CG–7: DeviceNet Object Classes
CLASS Object
01h Identity
02h Message Router
03h DeviceNet
04h Assembly
05h Connection
2Bh Acknowledge Handler
A0h IO data Input Mapping
A1h IO data Output Mapping
B0h Parameter Data input Mapping
CGCOMMUNICATIONS GUIDE DEVICENET PROTOCOL
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG25
Note Critical link failure is caused by failure of CAN_H or CAN_L bus. To re-establish communication after recovery of critical link faliure, the 369 Fieldbus comms interface must be reset. This can be done without recycling the control power to the 369 by using "RESET FIELDBUS COMMS INTERFACE" command under setting S1 369 SETUP\369 COMMUNICATIONS\ . Refer to section 5.2.3 for more details.
A delay of 0.25 sec to 10.00 sec in steps of 0.25 sec can be programmed to delay the output relay activation.
This feature can be programmed for Latched or Unlatched operation.
If programmed as Latched:
The “DeviceNet Loss of Comms” trip will remain latched until the communication with the Master is (re) established AND the latched trip is manually reset or remotely reset via Modbus communications.
If programmed as Unlatched:
Any programmed output relays for this feature will be activated until communication is active. Once communication is active, the trip condition will be cleared and the assigned output relays will automatically de-activate.
The setpoints associated with this feature are:
1. Fieldbus Loss of Comms Enable
2. Fieldbus Loss of Comms Delay
3. Assign Loss of Comms Relay
Refer to the 369 Instruction Manual, chapter 5: 369 Relay Communications for more information on these setpoints.
4.2 Poll DataThe polling function consumes one byte of control data and produces data as per Poll Data Group 1, Poll Data Group 2, or the User-Defined poll data. The control data format is as follows:
Bit Position Name Value
0 Motor Start 0.1
1 Motor Stop 0.1
2 Fault Reset 0.1
3 Reserved -
4 Reserved -
5 Reserved -
6 Reserved -
7 Reserved -
CG26 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
DEVICENET PROTOCOL CGCOMMUNICATIONS GUIDE
For execution of DeviceNet control commands, one of the switch assignments should be set to “DeviceNet Control” and be closed.
The motor start command energizes the output relay set with the START CONTROL RELAY setpoint. The motor stop command energizes the trip relay. The fault reset command resets the latched trip and alarm conditions, provided the cause of alarm/trip is removed. The commands are executed continuously as long as the control bits are high. When two or more commands are executed simultaneously, only one will be executed. The command hierarchy for execution is given below.
1. Motor stop
2. Fault reset
3. Motor start
Note The corresponding command bit should be high for more than 500 ms to execute the command.
The Polled input bytes can be selected from two predefined groups of parameters or one group of user-defined parameters with the “DeviceNet Input Poll Data Group” setpoint. The list of parameters in each group is given below:
Table CG–8: Poll Data Group 1
Byte Description Length Units Format Default
1 Motor Status 1 - F172 0
2 Digital Input Status 1 - F173 0
3 Digital Output Status 1 - F174 0
4 Flag Change State 1 - F175 0
5 Thermal Capacity Used 1 % UINT 0
6 (low), 7 (high) Time to Trip 2 seconds F20 -1
Table CG–9: Poll Data Group 2
Byte Description Length Units Format Default
1 Motor Status - Stopped, Starting, Running, Tripped
1 - F172 0
2,3 Cause of Last Trip 2 - F134 0
4,5 Average Phase Current 2 A F1 0
6,7 Ground Current 2 A F23 0
8,9 Average Line Voltage 2 V F1 0
10,11 Real Power (kW) 2 kW F4 0
12,13 Power Factor 2 - F21 0
CGCOMMUNICATIONS GUIDE DEVICENET PROTOCOL
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG27
User-Defined Poll Data
The user can also define exactly which data will be provided and the order in which that data is given. The Modbus User Definable Memory Map area (refer to Section 9.6.2: User Definable Memory Map Area on page 9–34) and the “User-Defined Data Size” setpoint are used to define this data and data size. The “User-Defined Data Size” setpoint determines the number of 16-bit registers available to be read through DeviceNet Poll Input Data and the Modbus User Definable Memory Map is used to determine the data provided and the order of the data.
For example, if the user only wishes to read two 16-bit registers of data (4 bytes), the user sets the “DeviceNet Input Poll Data Group” setpoint to “User-Defined” and then programs a value of ‘2’ for the “User-Defined Data Size” setpoint. When the DeviceNet master reads the Poll Input data, 4 bytes of Input data will be read as follows.
Note that the Explicit message data provided both via Class 04, Instance 64h, Attribute 03 and Class A0h, Instance 01, Attribute 01 will match the the Poll data configuration.
4.3 Change of State (COS)The COS data is described under class 4, instance 66h, attribute 3. The following data is provided:
14 Local Hottest Stator RTD Number 2 - F1 0
15,16 Local Hottest Stator RTD Temperature 2 °c F4 0
17 Digital Input Status - Access Switch, Speed Switch, Spare Switch, Differential Switch, Emergency Switch, Reset Switch
1 - F173 0
18 Digital Output Status - Trip Relay, Alarm Relay, Aux Relay 1, Aux Relay 2
1 - F174 0
Table CG–9: Poll Data Group 2
Byte Description Length Units Format Default
Byte Description Length
1 (Hi), 2 (Lo) User Defined Memory Map Register 1 1 word3 (Hi), 4 (lo) User Defined Memory Map Register 2 1 word
Byte Description Length Units Format Default
1 Motor Status 1 - F172 0
2 Digital Input Status 1 - F173 0
3 Digital Output Status 1 - F174 0
4 Flag Change State 1 - F175 0
CG28 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
DEVICENET PROTOCOL CGCOMMUNICATIONS GUIDE
4.4 Identity Object (class code 01h)Identity object, Class code 01h, Services.
Identity object, Class code 01h, Attributes.
Identity object, Class code 01h, Instance 01h, Attributes.
The USINT and UINT data types are defined as follows: USINT = Unsigned integer byte (range 0 to 255); UINT = Unsigned integer word (range 0 to 65535).
4.5 Message Router (class code 02h)The message router (class code 2) object provides a messaging connection point through which a client may address a service to any object or instance residing in the physical device. There is no external visible interface to the message router object.
4.6 DeviceNet Object (class code 03h)DeviceNet object, Class code 03h, Services:
DeviceNet object, Class Code 03h, Attributes:
DeviceNet object, Class Code 03h, Instance 01h, Attributes:
CODE SERVICES AVAILABLE TO THIS OBJECT
NAME DESCRIPTION
0x05 Reset Reset the device to power up configuration
0x0E Get_Attribute_Single Returns the contents of the given attribute
ATTRIBUTE ACCESS NAME/DESCRIPTION DATA TYPE VALUE
01h Get Revision of Identity object UINT 1
ATTRIBUTE ACCESS NAME/DESCRIPTION DATA TYPE VALUE
01h Get Vendor ID UINT 928
02h Get Device Type UINT 003h Get Product Code UINT 5304h Get Revision (Major, Minor) USINT (2) 2.20
05h Get Status F178 ---
07h Get Product Name Short-String369 Motor Management Relay
CODE SERVICES AVAILABLE TO THIS OBJECT
NAME DESCRIPTION
0x0E Get_Attribute_Single Returns the contents of the given attribute
ATTRIBUTE ACCESS NAME/DESCRIPTION DATA TYPE VALUE
01h Get Revision of DeviceNet object USINT 2
ATTRIBUTE ACCESS NAME/DESCRIPTION DATA TYPE VALUE
01h Get MAC ID USINT 0 to 63
CGCOMMUNICATIONS GUIDE DEVICENET PROTOCOL
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG29
The USINT and UINT data types are defined as follows: USINT = Unsigned integer byte (range 0 to 255); UINT = Unsigned integer word (range 0 to 65535).
4.7 Assembly Object (class code 04h)Assembly object, Class code 04h, Services:
Assembly object, Class code 04h, Attributes.
Assembly object, Class code 04h, Instance 64h, Attributes.
Assembly object, Class code 04h, Instance 65h, Attributes.
Assembly object, Class code 04h, Instance 66h, Attributes.
02h Get Baud Rate USINT 0 = 125 kbps, 1 = 250 kbps,2 = 500 kbps
05h GetAllocation choice BYTE
Bit 0: explicit messagingBit 1: polled I/OBit 4: COS I/OBit 5: cyclic I/OBit 6: acknowledge suppression
Master’s MAC ID USINT 0 to 63: address;255 = unallocated
ATTRIBUTE ACCESS NAME/DESCRIPTION DATA TYPE VALUE
CODE SERVICES AVAILABLE TO THIS OBJECT
NAME DESCRIPTION
0x0E Get_Attribute_Single Returns the contents of the given attribute0X10 Set_Attribute_Single Sets the contents of the given attribute
ATTRIBUTE ACCESS NAME/DESCRIPTION DATA TYPE VALUE
01h Get Revision of Assembly object UINT 202h Get Maximum instance number UINT 150
ATTRIBUTE ACCESS NAME/DESCRIPTION DATA TYPE VALUE
03h Get Motor data1
1. The data available through this Class/Instance/Attribute will depend on which Poll Group isused (see section 4.2: Poll Data).
bytes (7) see below
ATTRIBUTE ACCESS NAME/DESCRIPTION DATA TYPE VALUE
03h Get Flag change state byte see below
DATA FORMATS, FLAG CHANGE STATE
BIT POSITION NAME VALUES
0 Trip/alarm flag 0 = no change; 1 = trip or alarm1 to 7 Reserved ---
ATTRIBUTE ACCESS NAME/DESCRIPTION DATA TYPE VALUE
03h Get Digital data bytes (4) see below
DATA FORMATS, DIGITAL DATA
BYTE DESCRIPTION LENGTH UNITS FORMAT DEFAULT
1 Motor status 1 byte --- F172 0
CG30 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
DEVICENET PROTOCOL CGCOMMUNICATIONS GUIDE
Assembly object, Class code 04h, Instance 67h, Attributes.
Assembly object, Class code 04h, Instance 68h, Attributes.
Assembly object, Class code 04h, Instance 96h, Attributes.
For execution of DeviceNet control commands, one of the switch assignments should be set to “DeviceNet Control” and be closed.
The motor start command energizes the output relay set with the START CONTROL RELAY setpoint. The motor stop command energizes the trip relay. The fault reset command resets the latched trip and alarm conditions, provided the cause of alarm/trip is removed. The commands are executed continuously as long as the control bits are high. When two or more commands are executed simultaneously, only one will be executed. The command hierarchy for execution is given below.
1. Motor stop2. Fault reset3. Motor start
The corresponding command bit should be high for more than 500 ms to execute the command.
2 Digital input status 1 byte --- F173 03 Digital output status 1 byte --- F174 0
4 Flag change state 1 byte --- F175 0
ATTRIBUTE ACCESS NAME/DESCRIPTION DATA TYPE VALUE
03h Get Thermal capacity used USINT %
ATTRIBUTE ACCESS NAME/DESCRIPTION DATA TYPE DATA FORMAT VALUE
03h Get Time to trip Word F20 –1 second
ATTRIBUTE ACCESS NAME/DESCRIPTION DATA TYPE VALUE
03h Set Control byte 1 byte see below
DATA FORMATS, CONTROL BYTE
BIT POSITION NAME VALUE
0 Motor start 0, 1
1 Motor stop 0, 12 Fault reset 0, 13 Reserved ---
4 Reserved ---5 Reserved ---6 Reserved ---
7 Reserved ---
DATA FORMATS, DIGITAL DATA
BYTE DESCRIPTION LENGTH UNITS FORMAT DEFAULT
CGCOMMUNICATIONS GUIDE DEVICENET PROTOCOL
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG31
4.8 DeviceNet Connection Object (class code 05h)The connection objects manage the characteristics of each communication connection. There are two instances of the connection object in the device: explicit connection (<50 ms response) and input/output connection poll (<10 ms response).
Connection Object, Class Code 05h, Services:
Connection Object, Class Code 05h, Instance 01h (explicit message connection):
Connection Object, Class Code 05h, Instance 02h (polled input/output connection):
CODE NAME AND DESCRIPTION OF SERVICES AVAILABLE TO THIS OBJECT
0x05 Reset the connection - restart timer
0x0E Get_Attribute_Single: Returns the contents of the given attribute.0x10 Set_Attribute_Single: Sets the contents of the given attribute
ATTRIBUTE ACCESS NAME/DESCRIPTION DATA TYPE
VALUE
01h Get State BYTE 0x0302h Get Instance_type BYTE 0x00, 0x01
03h Get Export class trigger BYTE 0x83
04h Get Produced connection ID UINT 10xxxxxx011, xxxxxx = MAC ID
05h Get Consumed connection ID UINT 10xxxxxx011, xxxxxx = MAC ID
06h Get Initial comm. characteristics UINT 0x21
07h Get Produced connection size UINT 0x12
08h Get Consumed connection size UINT 0x12
09h Get/Set Expected package rate UINT 0x00
0Ch Get/Set Watchdog timeout action USINT0 = transition to time-out1 = auto delete, 2 = auto reset3 = deferred delete
0Dh Get Produced path length UINT 0x0000
0Eh Get Produced path BYTE [6] <null>0Fh Get Consumed path length UINT 0x000010h Get Consumed path BYTE [6] <null>
11h Get Production inhibit timer UINT 0x0000
ATTRIBUTE ACCESS NAME/DESCRIPTION DATA TYPE VALUE
01h Get State BYTE 0x03
02h Get Instance_type BYTE 0x0103h Get Export class trigger BYTE 0x80, 0x8204h Get Produced connection ID UINT MAC ID
05h Get Consumed connection ID UINT MAC ID06h Get Initial comm. characteristics UINT 0x01, 0xF1
07h Get Produced connection size UINT 0x0108h Get Consumed connection size UINT 0x0109h Get/Set Expected package rate UINT 0x00
0Ch Get/Set Watchdog timeout action UINT 0x00
CG32 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
DEVICENET PROTOCOL CGCOMMUNICATIONS GUIDE
4.9 Acknowledge Handler Object (class code 2Bh)Acknowledge Handler Object, Class Code 2Bh, Services:
Acknowledge Handler object, Class code 2Bh, Attributes.
Acknowledge Handler object, Class code 2Bh, Instance 01h, Attributes:
4.10 I/O Data Input Mapping Object (class code A0h)I/O Data Input Mapping Object, Class code A0h, Services:
Input/Output Data Input Mapping object, Class code A0h, Attributes.
I/O Data Input Mapping object, Class code A0h, Instance 01h, Attributes:
0Dh Get Produced path length UINT 0x0006
0Eh Get Produced path BYTE [6] <null>0Fh Get Consumed path length UINT 0x000610h Get Consumed path BYTE [6] <null>
11h Get Production inhibit timer UINT 0x0000
ATTRIBUTE ACCESS NAME/DESCRIPTION DATA TYPE VALUE
CODE NAME DESCRIPTION
0x0E Get_Attribute_Single Returns the contents of the given attribute0x10 Set_Attribute_Single Sets the contents of the given attribute
ATTRIBUTE ACCESS NAME/DESCRIPTION DATA TYPE VALUE
01h Get Revision of Acknowledge Handler object UINT 1
02h Get Maximum instance number UINT 1
ATTRIBUTE ACCESS NAME/DESCRIPTION DATA TYPE VALUE
01h Get Acknowledge timer UINT 16 ms02h Get Retry limit USINT 1
CODE NAME DESCRIPTION
0x0E Get_Attribute_Single Returns the contents of the given attribute
ATTRIBUTE ACCESS NAME/DESCRIPTION DATA TYPE VALUE
01h Get Revision of I/O Data Input Mapping object UINT 1
ATTRIBUTE ACCESS NAME/DESCRIPTION DATA TYPE DATA FORMAT
01h Get Motor data1
1. The data available through this Class/Instance/Attribute will depend on which Poll Group is used(see section 4.2: Poll Data)
bytes (7) see below
02h Get Flag change state byte F17503h Get Digital data bytes (4) see below
04h Get Thermal capacity used USINT %05h Get Time to trip Word F20
CGCOMMUNICATIONS GUIDE DEVICENET PROTOCOL
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG33
4.11 I/O Data Output Mapping Object (class code A1h)I/O Data Output Mapping Object, Class code A1h, Services:
I/O Data Input Mapping object, Class code A0h, Instance 01h, Attributes:
4.12 Parameter Data Input Mapping Object (class code B0h)Parameter Data Input Mapping object, Class code B0h, Services:
Parameter Data Input Mapping object, Class code B0h, Attributes.
Parameter Data Input Mapping object, Class code B0h, Instance 01h, Attributes:
DATA FORMATS, DIGITAL DATA
BYTE DESCRIPTION LENGTH UNITS FORMAT DEFAULT
1 Motor status 1 byte --- F172 02 Digital input status 1 byte --- F173 0
3 Digital output status 1 byte --- F174 04 Flag change state 1 byte --- F175 0
CODE NAME DESCRIPTION
0x0E Get_Attribute_Single Returns the contents of the given attribute
0x10 Set_Attribute_Single Sets the contents of the given attribute
ATTRIBUTE ACCESS NAME/DESCRIPTION DATA TYPE DATA FORMAT
01h Set Control byte 1 byte see below
DATA FORMATS, CONTROL BYTE
BIT POSITION NAME VALUES
0 Motor start 0, 11 Motor stop 0, 1
2 Fault reset 0, 13 Reserved ---4 Reserved ---
5 Reserved ---6 Reserved ---7 Reserved ---
CODE NAME DESCRIPTION
0x0E Get_Attribute_Single Returns the contents of the given attribute
ATTRIBUTE ACCESS NAME/DESCRIPTION DATA TYPE VALUE
01h Get Revision of Identity object UINT 1
ATTRIBUTE ACCESS NAME/DESCRIPTION DATA TYPE VALUE
01h Get Currents bytes (10) see below02h Get Current angles bytes (6) see below
03h Get Motor load bytes (6) see below04h Get Line voltages bytes (8) see below05h Get Phase voltages bytes (8) see below
CG34 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
DEVICENET PROTOCOL CGCOMMUNICATIONS GUIDE
06h Get Phase voltage angles bytes (6) see below
07h Get Frequency bytes (2) see below08h Get BSD state and frequency bytes (6) see below09h Get Power bytes (10) see below
0Ah Get Energy bytes (6) see below
0Bh Get Local hottest stator RTD and temperature bytes (4) see below
0Ch Get Local RTD temperatures bytes (24) see below0Dh Get Demand bytes (8) see below0Eh Get Peak values bytes (8) see below
0Fh Get Learned data bytes (14) see below10h Get Motor statistics bytes (8) see below11h Get Cause of trip bytes (2) see below
12h Get Last trip date and time bytes (8) see below13h Get Last pre-trip currents bytes (8) see below14h Get Last pre-trip motor load bytes (4) see below
15h Get Pre-trip local hottest stator RTD and temperature bytes (4) see below
16h Get Last pre-trip line voltages bytes (6) see below17h Get Last pre-trip phase voltages bytes (6) see below
18h Get Last pre-trip frequency bytes (2) see below19h Get Last pre-trip power bytes (8) see below1Ah Get Trip diagnostic data bytes (6) see below
1Bh Get Alarm diagnostic data bytes (8) see below1Ch Get Start block status data bytes (18) see below1Dh Get Actual values bytes (202) see below
ATTRIBUTE ACCESS NAME/DESCRIPTION DATA TYPE VALUE
DATA FORMATS FOR CLASS CODE B0H, INSTANCE 1 (Sheet 1 of 8)
ATTRIBUTE BYTES DESCRIPTION LENGTH FORMAT VALUE/UNIT
01hCURRENTS
1,2 (low, high) Phase Current Ia 16 bits UINT A3,4 (low, high) Phase Current Ib 16 bits UINT A
5,6 (low, high) Phase Current Ic 16 bits UINT A
7,8 (low, high) Average phase current Iav 16 bits UINT A
9,10 (low, high) Ground current Ig 16 bits F23 0.1 × A or 0.01 × A
02hCURRENT ANGLES
1,2 (low, high) Ia angle 16 bits UINT degrees3,4 (low, high) Ib angle 16 bits UINT degrees5,6 (low, high) Ic angle 16 bits UINT degrees
03hMOTOR LOAD
1,2 (low, high) Motor load 16 bits F3 0.01 × FLA3,4 (low, high) Current unbalance 16 bits UINT %
5,6 (low, high) Unbalanced biased motor load (Ieq) 16 bits F3 0.01 × FLA
04hLINE VOLTAGES
1,2 (low, high) Voltage Vab 16 bits UINT V3,4 (low, high) Voltage Vbc 16 bits UINT V
5,6 (low, high) Voltage Vca 16 bits UINT V7,8 (low, high) Average line voltage 16 bits UINT V
CGCOMMUNICATIONS GUIDE DEVICENET PROTOCOL
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG35
05hPHASE VOLTAGES
1,2 (low, high) Voltage Van 16 bits UINT V3,4 (low, high) Voltage Vbn 16 bits UINT V
5,6 (low, high) Voltage Vcn 16 bits UINT V
7,8 (low, high) Average phase voltage 16 bits UINT V
06hPHASE VOLTAGE ANGLES
1,2 (low, high) Va angle 16 bits UINT degrees3,4 (low, high) Vb angle 16 bits UINT degrees5,6 (low, high) Vc angle 16 bits UINT degrees
07hFREQUENCY 1,2 (low, high) Frequency 16 bits F3 × 0.01 Hz
08hBSD STATE AND FREQ.
1,2 (low, high) BSD state 16 bits F27 --3,4 (low, high) Backspin frequency 16 bits F3 × 0.01 Hz
5,6 (low, high) Backspin prediction timer 16 bits F1 s
09hPOWER
1,2 (low, high) Power factor 16 bits F21 × 0.01 PF3,4 (low, high) Real power (kW) 16 bits F4 kW
5,6 (low, high) Real power (hp) 16 bits UINT hp7,8 (low, high) Reactive power 16 bits F4 kvar9,10 (low, high) Apparent power 16 bits UINT kVA
0AhENERGY
1,2 (low, high) MWh 16 bits UINT MWh3,4 (low, high) Positive Mvarh 16 bits UINT Mvarh5,6 (low, high) Negative Mvarh 16 bits UINT Mvarh
0BhRTD TEMP-ERATURE
1,2 (low, high) Local hottest stator RTD 16 bits UINT ---
3,4 (low, high) Local hottest stator RTD temperature 16 bits F4 °C
0ChLOCAL RTD TEMP-ERATURE
1,2 (low, high) Local RTD 1 temperature 16 bits F4 °C
3,4 (low, high) Local RTD 2 temperature 16 bits F4 °C
5,6 (low, high) Local RTD 3 temperature 16 bits F4 °C
7,8 (low, high) Local RTD 4 temperature 16 bits F4 °C
9,10 (low, high) Local RTD 5 temperature 16 bits F4 °C
11,12 (low, high) Local RTD 6 temperature 16 bits F4 °C
13,14 (low, high) Local RTD 7 temperature 16 bits F4 °C
15,16 (low, high) Local RTD 8 temperature 16 bits F4 °C
17,18 (low, high) Local RTD 9 temperature 16 bits F4 °C
19,20 (low, high) Local RTD 10 temperature 16 bits F4 °C
21,22 (low, high) Local RTD 11 temperature 16 bits F4 °C
23,24 (low, high) Local RTD 12 temperature 16 bits F4 °C
DATA FORMATS FOR CLASS CODE B0H, INSTANCE 1 (Sheet 2 of 8)
ATTRIBUTE BYTES DESCRIPTION LENGTH FORMAT VALUE/UNIT
CG36 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
DEVICENET PROTOCOL CGCOMMUNICATIONS GUIDE
0DhDEMAND
1,2 (low, high) Current demand 16 bits UINT A3,4 (low, high) Real power demand 16 bits UINT kW
5,6 (low, high) Reactive power demand 16 bits UINT kvar
7,8 (low, high) Apparent power demand 16 bits UINT kVA
0EhPEAK DEMAND
1,2 (low, high) Peak current demand 16 bits UINT A
3,4 (low, high) Peak real power demand 16 bits UINT kW
5,6 (low, high) Peak reactive power demand 16 bits UINT kvar
7,8 (low, high) Peak apparent power demand 16 bits UINT kVA
0FhLEARNED DATA
1,2 (low, high) Learned acceleration time 16 bits F2 x 0.1 seconds
3,4 (low, high) Learned starting current 16 bits UINT A
5,6 (low, high) Learned starting capacity 16 bits UINT %
7,8 (low, high) Learned running cool time constant 16 bits UINT minutes
9,10 (low, high) Learned stopped cool time constant 16 bits UINT minutes
11,12 (low, high) Last starting capacity 16 bits UINT %
13,14 (low, high) Learned unbalance k-factor 16 bits UINT --
10hMOTOR STATISTICS
1,2 (low, high) Number of starts 16 bits UINT --
3,4 (low, high) Number of restarts 16 bits UINT --5,6 (low, high) Digital counter 16 bits UINT --7,8 (low, high) Motor running hours 16 bits UINT hours
11hCAUSE OF LAST TRIP
1,2 (low, high) Cause of last trip 16 bits F134 --
12hLAST PRE-TRIP DATE AND TIME.
1 to 4(low, high) Last trip date 32 bits F18 --
5 to 8(low, high) Last trip time 32 bits F19 --
13hLAST PRE-TRIP CURRENTS
1,2 (low, high) Last pre-trip Ia 16 bits UINT A
3,4 (low, high) Last pre-trip Ib 16 bits UINT A5,6 (low, high) Last pre-trip Ic 16 bits UINT A7,8 (low, high) Last pre-trip Ig 16 bits F2 0.1 × A
14hLAST PRE-TRIP MOTOR LOAD
1,2 (low, high) Last pre-trip motor load 16 bits F3 × 0.01 FLA
3,4 (low, high) Last pre-trip unbalance 16 bits UINT %
15hPRE-TRIP STATOR RTD TEMP.
1,2 (low, high) Local pre-trip hottest stator RTD 16 bits UINT ---
3,4 (low, high)Local pre-trip hottest stator RTD temperature
16 bits F4 °C
DATA FORMATS FOR CLASS CODE B0H, INSTANCE 1 (Sheet 3 of 8)
ATTRIBUTE BYTES DESCRIPTION LENGTH FORMAT VALUE/UNIT
CGCOMMUNICATIONS GUIDE DEVICENET PROTOCOL
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG37
16hLAST PRE-TRIP LINE VOLTAGES
1,2 (low, high) Last pre-trip Vab 16 bits UINT volts3,4 (low, high) Last pre-trip Vbc 16 bits UINT volts
5,6 (low, high) Last pre-trip Vca 16 bits UINT volts
17hLAST PRE-TRIP PHASE VOLTAGES
1,2 (low, high) Last pre-trip Van 16 bits UINT volts
3,4 (low, high) Last pre-trip Vbn 16 bits UINT volts5,6 (low, high) Last pre-trip Vcn 16 bits UINT volts
18hLAST PRE-TRIP FREQ.
1,2 (low, high) Last pre-trip frequency 16 bits F3 × 0.01 Hz
19hLAST PRE-TRIP POWER
1,2 (low, high) Last pre-trip kilowatts 16 bits F4 kW
3,4 (low, high) Last pre-trip kvar 16 bits F4 kvar5,6 (low, high) Last pre-trip KVA 16 bits UINT kVA
7,8 (low, high) Last pre-trip power factor 16 bits F21 × 0.01 PF
1AhTRIP DIAG. 6 bytes Trip diagnostic data 48 bits F176
1BhALARM DIAG. 8 bytes Alarm diagnostic
data 64 bits F177
1ChSTART BLOCK STATUS
1,2 (low, high) Overload lockout timer 16 bits UINT minutes
3,4 (low, high) Starts timer [1] 16 bits UINT minutes5,6 (low, high) Starts timer [2] 16 bits UINT minutes
7,8 (low, high) Starts timer [3] 16 bits UINT minutes9,10 (low, high) Starts timer [4] 16 bits UINT minutes11,12 (low, high) Starts timer [5] 16 bits UINT minutes
13,14 (low, high) Time between starts timer 16 bits UINT minutes
15,16 (low, high) Restart block timer 16 bits UINT seconds17,16 (low, high) Start inhibit timer 16 bits UINT minutes
1DhACTUAL VALUES
1,2 (low, high) Phase current Ia 16 bits UINT A
3,4 (low, high) Phase current Ib 16 bits UINT A5,6 (low, high) Phase current Ic 16 bits UINT A
7,8 (low, high) Average phase current Iav 16 bits UINT A
9,10 (low, high) Ground current Ig 16 bits F23 0.1 × A or 0.01 × A11,12 (low, high) Ia angle 16 bits UINT degrees
13,14 (low, high) Ib angle 16 bits UINT degrees15,16 (low, high) Ic angle 16 bits UINT degrees17,18 (low, high) Motor load 16 bits F3 × 0.01 FLA
19,20 (low, high) Current unbalance 16 bits UINT %
21,22 (low, high) Unbalanced biased motor load (Ieq) 16 bits F3 0.01 × FLA
23,24 (low, high) Voltage Vab 16 bits UINT V
DATA FORMATS FOR CLASS CODE B0H, INSTANCE 1 (Sheet 4 of 8)
ATTRIBUTE BYTES DESCRIPTION LENGTH FORMAT VALUE/UNIT
CG38 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
DEVICENET PROTOCOL CGCOMMUNICATIONS GUIDE
1DhACTUAL VALUEScontinued
25,26 (low, high) Voltage Vbc 16 bits UINT V
27,28 (low, high) Voltage Vca 16 bits UINT V
29,30 (low, high) Average line voltage 16 bits UINT V31,32 (low, high) Voltage Van 16 bits UINT V
33,34 (low, high) Voltage Vbn 16 bits UINT V35,36 (low, high) Voltage Vcn 16 bits UINT V
37,38 (low, high) Average phase voltage 16 bits UINT V
39,40 (low, high) Va angle 16 bits UINT degrees41,42 (low, high) Vb angle 16 bits UINT degrees43,44 (low, high) Vc angle 16 bits UINT degrees
45,46 (low, high) Frequency 16 bits F3 × 0.01 Hz47,48 (low, high) BSD state 16 bits F27 --49,50 (low, high) Backspin frequency 16 bits F3 × 0.01 Hz
51,52 (low, high) Backspin prediction timer 16 bits F1 seconds
53,54 (low, high) Power factor 16 bits F21 × 0.01 PF55,56 (low, high) Real power (kW) 16 bits F4 kW
57,58 (low, high) Real power (hp) 16 bits UINT hp59,60 (low, high) Reactive power 16 bits F4 kvar61,62 (low, high) Apparent power 16 bits UINT kVA
63,64 (low, high) MWh 16 bits UINT MWh65,66 (low, high) Positive Mvarh 16 bits UINT Mvarh67,68 (low, high) Negative Mvarh 16 bits UINT Mvarh
69,70 (low, high) Local Hottest stator RTD 16 bits UINT ---
1DhACTUAL VALUEScontinued
71,72 (low, high) Local Hottest stator RTD temperature 16 bits F4 °C
73,74 (low, high) Local RTD 1 temperature 16 bits F4 °C
75,76 (low, high) Local RTD 2 temperature 16 bits F4 °C
77,78 (low, high) Local RTD 3 temperature 16 bits F4 °C
79,80 (low, high) Local RTD 4 temperature 16 bits F4 °C
81,82 (low, high) Local RTD 5 temperature 16 bits F4 °C
83,84 (low, high) Local RTD 6 temperature 16 bits F4 °C
85,86 (low, high) Local RTD 7 temperature 16 bits F4 °C
87,88 (low, high) Local RTD 8 temperature 16 bits F4 °C
DATA FORMATS FOR CLASS CODE B0H, INSTANCE 1 (Sheet 5 of 8)
ATTRIBUTE BYTES DESCRIPTION LENGTH FORMAT VALUE/UNIT
CGCOMMUNICATIONS GUIDE DEVICENET PROTOCOL
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG39
89,90 (low, high) Local RTD 9 temperature 16 bits F4 °C
91,92 (low, high) Local RTD 10 temperature 16 bits F4 °C
93,94 (low, high) Local RTD 11 temperature 16 bits F4 °C
95,96 (low, high) Local RTD 12 temperature 16 bits F4 °C
97,98 (low, high) Current demand 16 bits UINT A99,100 (low, high) Real power demand 16 bits UINT kW101,102 (low, high)
Reactive power demand 16 bits F4 kvar
103, 104 (low, high)
Apparent power demand 16 bits UINT kVA
105, 106 (low, high)
Peak current demand 16 bits UINT A
107, 108 (low, high)
Peak real power demand 16 bits UINT kW
109, 110 (low, high)
Peak reactive power demand 16 bits F4 kvar
111,112 (low, high)
Peak apparent power demand 16 bits UINT kVA
113,114 (low, high)
Learned acceleration time 16 bits F2 × 0.1 seconds
115,116 (low, high)
Learned starting current 16 bits UINT A
117,118 (low, high)
Learned starting capacity 16 bits UINT %
1DhACTUAL VALUEScontinued
119,120 (low, high)
Learned running cool time constant 16 bits UINT minutes
121,122 (low, high)
Learned stopped cool time constant 16 bits UINT minutes
123,124 (low, high)
Last starting capacity 16 bits UINT %
125,126 (low, high)
Learned unbalance k-factor 16 bits UINT --
127,128 (low, high) Number of starts 16 bits UINT --
129,130 (low, high) Number of restarts 16 bits UINT --
131,132 (low, high) Digital counter 16 bits UINT --
133,134 (low, high) Motor running Hours 16 bits UINT hours
135,136 (low, high) Cause of last trip 16 bits F134 --
137 to 140 (low, high) Last trip date 32 bits F18 --
141 to 144 (low, high) Last trip time 32 bits F19 --
145, 146 (low, high) Last pre-trip Ia 16 bits UINT A
DATA FORMATS FOR CLASS CODE B0H, INSTANCE 1 (Sheet 6 of 8)
ATTRIBUTE BYTES DESCRIPTION LENGTH FORMAT VALUE/UNIT
CG40 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
DEVICENET PROTOCOL CGCOMMUNICATIONS GUIDE
147, 148 (low, high) Last pre-trip Ib 16 bits UINT A
149, 150 (low, high) Last Pre-trip Ic 16 bits UINT A
151, 152 (low, high) Last Pre-trip Ig 16 bits F2 × 0.1 A
153, 154 (low, high)
Last pre-trip motor load 16 bits F3 × 0.01 FLA
155, 156 (low, high)
Last pre-trip unbalance 16 bits UINT %
157, 158 (low, high)
Last pre-trip local hottest stator RTD 16 bits UINT ---
159, 160 (low, high)
Last pre-trip local hottest stator RTD temperature
16 bits F4 °C
161, 162 (low, high) Last pre-trip Vab 16 bits UINT volts
163, 164 (low, high) Last pre-trip Vbc 16 bits UINT volts
165, 166 (low, high) Last pre-trip Vca 16 bits UINT volts
167, 168 (low, high) Last pre-trip Van 16 bits UINT volts
1DhACTUAL VALUEScontinued
169, 170 (low, high) Last pre-trip Vbn 16 bits UINT volts
171, 172 (low, high) Last pre-trip Vcn 16 bits UINT volts
173, 174 (low, high)
Last pre-trip frequency 16 bits F3 × 0.01 Hz
175, 176 (low, high)
Last pre-trip kilowatts 16 bits F4 kW
177, 178 (low, high) Last pre-trip kvar 16 bits F4 kvar
179, 180 (low, high) Last pre-trip KVA 16 bits UINT kVA
181, 182 (low, high)
Last pre-trip power factor 16 bits F21 × 0.01 PF
183 to 188 Trip diagnostic data 48 bits F176
189 to 196 Alarm diagnostic data 64 bits F177
197, 198 (low, high)
Overload lockout timer 16 bits UINT minutes
199, 200 (low, high) Starts timer [1] 16 bits UINT minutes
201, 202 (low, high) Starts timer [2] 16 bits UINT minutes
203, 204 (low, high) Starts timer [3] 16 bits UINT minutes
205, 206 (low, high) Starts timer [4] 16 bits UINT minutes
207, 208 (low, high) Starts timer [5] 16 bits UINT minutes
DATA FORMATS FOR CLASS CODE B0H, INSTANCE 1 (Sheet 7 of 8)
ATTRIBUTE BYTES DESCRIPTION LENGTH FORMAT VALUE/UNIT
CGCOMMUNICATIONS GUIDE DEVICENET PROTOCOL
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG41
4.13 DeviceNet Loss Of Communication Trip If the 369 detects a problem in communicating with the DeviceNet master, the DeviceNet Loss of Communications feature can be used to operate on any combination of output relays.
If the 369 DeviceNet communications is offline and not communicating with a master, then the “Fieldbus Loss of Comms” function (if enabled) will activate. This feature can be programmed for Latched or Unlatched operation.
If programmed as Latched:
The “Fieldbus Loss of Comms” output relay will remain latched until communication with the Master is (re) established AND the latched output relay is manually reset or remotely reset via Modbus communications.
If programmed as Unlatched:
Any output relays programmed for this feature will be de-activated once communication is restored; the Loss of Communications condition will be cleared and the assigned output relays will automatically de-activate.
The setpoints associated with this feature are:
1. Fieldbus Loss of Comms Enable
2. Fieldbus Loss of Comms Delay
3. Assigned Fieldbus Loss of Comms Relay
Refer to the 369 Instruction Manual, Chapter 5: 369 Relay Communications for more information on these setpoints.
209, 210 (low, high)
Time between starts timer 16 bits UINT minutes
211, 212 (low, high) Restart block timer 16 bits UINT seconds
213, 214 (low, high) Start inhibit timer 16 bits UINT minutes
DATA FORMATS FOR CLASS CODE B0H, INSTANCE 1 (Sheet 8 of 8)
ATTRIBUTE BYTES DESCRIPTION LENGTH FORMAT VALUE/UNIT
CG42 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
DEVICENET PROTOCOL CGCOMMUNICATIONS GUIDE
4.14 DeviceNet Data Formats
FORMAT VALUE NAME/DESCRIPTION
F167 Network status: unsigned 16 bit integer
0 Power off / Not online1 Online, Connected
2 Link failure3 Not defined
F168 Connection status: unsigned 16 bit integer
0 Nonexistent1 Configuring
2 (Not used)3 Established4 Timed out
5 Deferred deleteF170 DeviceNet baud rate: unsigned 16 bit integer
0 125 kbps1 250 kbps2 500 kbps
F172 Motor status: Unsigned 8 bit integer
Bit 0 Stopped
Bit 1 StartingBit 2 RunningBit 3 Overloaded
Bit 4 TrippedBits 5 to 7 Reserved
F173 Digital input status: unsigned 8 bit integer
Bit 0 Access Switch Status0 = Open, 1= Closed
Bit 1 Speed Switch Status0 = Open, 1= Closed
Bit 2 Spare Switch Status0 = Open, 1= Closed
Bit 3 Differential Switch Status0 = Open, 1= Closed
Bit 4 Emergency Switch status0 = Open, 1= Closed
Bit 5 Reset Switch Status0 = Open, 1= Closed
Bit 6 ReservedBit 7 Reserved
F174 Output relay status: unsigned 8 bit integer
Bit 0 Trip Relay Status0 = De-energized, 1 = Energized
Bit 1 Alarm Relay Status0 = De-energized, 1 = Energized
Bit 2 Aux1 Relay Status0 = De-energized, 1 = Energized
Bit 3 Aux2 Relay Status0 = De-energized, 1 = Energized
CGCOMMUNICATIONS GUIDE DEVICENET PROTOCOL
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG43
Bits 4 to 7 ReservedF175 Flag change state: unsigned 8 bit integer
Bit 0 Trip/Alarm status; 1= operated
Bits 1 to 7 ReservedF176 Relay trips: bitmask
Byte 1 Bit 0 Single Phasing TripBit 1 Spare Switch Trip
Bit 2 Emergency Switch TripBit 3 Differential Switch TripBit 4 Speed Switch Trip
Bit 5 Reset Switch TripBit 6 ReservedBit 7 Overload Trip
Byte 2 Bit 0 Short Circuit TripBit 1 Short Circuit Backup TripBit 2 Mechanical Jam Trip
Bit 3 Undercurrent TripBit 4 Current Unbalance TripBit 5 Ground Fault Trip
Bit 6 Ground Fault Backup TripBit 7 Reserved
Byte 3 Bit 0 Acceleration Timer Trip
Bit 1 RTD 1 TripBit 2 RTD 2 TripBit 3 RTD 3 Trip
Bit 4 RTD 4 TripBit 5 RTD 5 TripBit 6 RTD 6 Trip
Bit 7 RTD 7 TripByte 4 Bit 0 RTD 8 Trip
Bit 1 RTD 9 Trip
Bit 2 RTD 10 TripBit 3 RTD 11 TripBit 4 RTD 12 Trip
Bit 5 Undervoltage TripBit 6 Overvoltage TripBit 7 Voltage Phase Reversal Trip
F176ctd. Byte 5 Bit 0 Underfrequency Trip
Bit 1 Overfrequency TripBit 2 Lead Power Factor Trip
Bit 3 Lag Power Factor TripBit 4 Positive kvar TripBit 5 Negative kvar Trip
Bit 6 Underpower TripBit 7 Reverse Power Trip
FORMAT VALUE NAME/DESCRIPTION
CG44 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
DEVICENET PROTOCOL CGCOMMUNICATIONS GUIDE
Byte 6 Bit 0 Incomplete Sequence Trip
Bit 1 ReservedBit 2 ReservedBit 3 Reserved
Bit 4 ReservedBit 5 Reserved
Bit 6 ReservedBit 7 Reserved
F177 Relay alarms: bitmask
Byte 1 Bit 0 Spare Switch AlarmBit 1 Emergency Switch Alarm
Bit 2 Differential Switch AlarmBit 3 Speed Switch AlarmBit 4 Reset Switch Alarm
Bit 5 ReservedBit 6 Thermal Capacity AlarmBit 7 Overload Alarm
Byte 2 Bit 0 Mechanical Jam AlarmBit 1 Undercurrent AlarmBit 2 Current Unbalance Alarm
Bit 3 Ground Fault AlarmBit 4 Undervoltage AlarmBit 5 Overvoltage Alarm
Bit 6 Overfrequency AlarmBit 7 Underfrequency Alarm
Byte 3 Bit 0 Lead Power Factor Alarm
Bit 1 Lag Power Factor AlarmBit 2 Positive kvar AlarmBit 3 Negative kvar Alarm
Bit 4 Underpower AlarmBit 5 Reverse Power AlarmBit 6 RTD 1 Alarm
Bit 7 RTD 2 AlarmF177ctd. Byte 4 Bit 0 RTD 3 Alarm
Bit 1 RTD 4 AlarmBit 2 RTD 5 Alarm
Bit 3 RTD 6 AlarmBit 4 RTD 7 AlarmBit 5 RTD 8 Alarm
Bit 6 RTD 9 AlarmBit 7 RTD 10 Alarm
Byte 5 Bit 0 RTD 11 AlarmBit 1 RTD 12 AlarmBit 2 RTD 1 High Alarm
FORMAT VALUE NAME/DESCRIPTION
CGCOMMUNICATIONS GUIDE DEVICENET PROTOCOL
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG45
Bit 3 RTD 2 High Alarm
Bit 4 RTD 3 High AlarmBit 5 RTD 4 High AlarmBit 6 RTD 5 High Alarm
Bit 7 RTD 6 High AlarmByte 6 Bit 0 RTD 7 High Alarm
Bit 1 RTD 8 High AlarmBit 2 RTD 9 High AlarmBit 3 RTD 10 High Alarm
Bit 4 RTD 11 High AlarmBit 5 RTD 12 High AlarmBit 6 Open RTD Sensor Alarm
Bit 7 Short RTD AlarmByte 7 Bit 0 Trip Counters Alarm
Bit 1 Starter Failure Alarm
Bit 2 Current Demand AlarmBit 3 kW Demand AlarmBit 4 kvar Demand Alarm
Bit 5 kVA Demand AlarmBit 6 Digital Counter AlarmBit 7 Overload Lockout Block
Byte 8 Bit 0 Start Inhibit BlockBit 1 Starts Hour BlockBit 2 Time Between Starts Block
Bit 3 Restart BlockBit 4 ReservedBit 5 Back-Spin Block
Bit 6 Loss of Remote RTD Communication
Bit 7 Spare Switch AlarmF178 DeviceNet Communication status: unsigned 16 bit
integer
Bit 0 0 = not owned,1 = owned by master
Bit 1 Reserved
Bit 2 0 = factory default, 1= configured
Bits 3 to 7 Reserved
Bit 8 1 = Minor recoverable faultBit 9 1 = Minor unrecoverable faultBit 10 1 = Major recoverable fault
Bit 11 1 = Major unrecoverable faultBits 12 to 15 Reserved
FORMAT VALUE NAME/DESCRIPTION
CG46 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MODBUS RTU PROTOCOL CGCOMMUNICATIONS GUIDE
5 Modbus RTU Protocol
5.1 Data Frame Format and Data Rate One data frame of an asynchronous transmission to or from an 369 is default to 1 start bit, 8 data bits, and 1 stop bit . This produces a 10 bit data frame. This is important for transmission through modems at high bit rates (11 bit data frames are not supported by Hayes modems at bit rates of greater than 300 bps). The parity bit is optional as odd or even. If it is programmed as odd or even, the data frame consists of 1 start bit, 8 data bits, 1 parity bit, and 1 stop bit.
Modbus protocol can be implemented at any standard communication speed. The 369 RS485, fiber optic and RS232 ports support operation at 1200, 2400, 4800, 9600, and 19200 baud.
5.2 Data Packet Format A complete request/response sequence consists of the following bytes (transmitted as separate data frames):
Master Request Transmission:
SLAVE ADDRESS - 1 byteFUNCTION CODE - 1 byteDATA - variable number of bytes depending on FUNCTION CODECRC - 2 bytes
Slave Response Transmission:
SLAVE ADDRESS - 1 byteFUNCTION CODE - 1 byteDATA - variable number of bytes depending on FUNCTION CODECRC - 2 bytes
SLAVE ADDRESS: This is the first byte of every transmission. It represents the user-assigned address of the slave device that is to receive the message sent by the master. Each slave device must be assigned a unique address and only the addressed slave will respond to a transmission that starts with its address. In a master request transmission the SLAVE ADDRESS represents the address of the slave to which the request is being sent. In a slave response transmission the SLAVE ADDRESS represents the address of the slave that is sending the response. Note: A master transmission with a SLAVE ADDRESS of 0 indicates a broadcast command. Broadcast commands can be used for specific functions.
FUNCTION CODE: This is the second byte of every transmission. The modbus protocol defines function codes of 1 to 127. The 369 implements some of these functions. In a master request transmission the FUNCTION CODE tells the slave what action to perform. In a slave response transmission if the FUNCTION CODE sent from the slave is the same as the FUNCTION CODE sent from the master indicating the slave performed the function as requested. If the high order bit of the FUNCTION CODE sent from the slave is a 1 (i.e. if the FUNCTION CODE is > 127) then the slave did not perform the function as requested and is sending an error or exception response.
CGCOMMUNICATIONS GUIDE MODBUS RTU PROTOCOL
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG47
DATA: This will be a variable number of bytes depending on the FUNCTION CODE. This may be actual values, setpoints, or addresses sent by the master to the slave or by the slave to the master. Data is sent MSByte first followed by the LSByte.
CRC: This is a two byte error checking code. CRC is sent LSByte first followed by the MSByte.
5.3 Error Checking The RTU version of Modbus includes a two byte CRC-16 (16 bit cyclic redundancy check) with every transmission. The CRC-16 algorithm essentially treats the entire data stream (data bits only; start, stop and parity ignored) as one continuous binary number. This number is first shifted left 16 bits and then divided by a characteristic polynomial (11000000000000101B). The 16 bit remainder of the division is appended to the end of the transmission, LSByte first. The resulting message including CRC, when divided by the same polynomial at the receiver will give a zero remainder if no transmission errors have occurred.
If an 369 Modbus slave device receives a transmission in which an error is indicated by the CRC-16 calculation, the slave device will not respond to the transmission. A CRC-16 error indicates than one or more bytes of the transmission were received incorrectly and thus the entire transmission should be ignored in order to avoid the 369 performing any incorrect operation.
The CRC-16 calculation is an industry standard method used for error detection. An algorithm is included here to assist programmers in situations where no standard CRC-16 calculation routines are available.
5.4 CRC-16 AlgorithmOnce the following algorithm is complete, the working register "A" will contain the CRC value to be transmitted. Note that this algorithm requires the characteristic polynomial to be reverse bit ordered. The MSbit of the characteristic polynomial is dropped since it does not affect the value of the remainder. The following symbols are used in the algorithm:
--> data transferA 16 bit working registerAL low order byte of AAH high order byte of ACRC 16 bit CRC-16 valuei, j loop counters(+) logical exclusive or operatorDi i-th data byte (i = 0 to N-1)G 16 bit characteristic polynomial = 1010000000000001 with MSbit dropped and bit order
reversedshr(x) shift right (the LSbit of the low order byte of x shifts into a carry flag, a '0' is shifted into the
MSbit of the high order byte of x, all other bits shift right one location
The algorithm is as follows:
1. FFFF hex --> A
CG48 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MODBUS RTU PROTOCOL CGCOMMUNICATIONS GUIDE
2. 0 --> i
3. 0 --> j
4. Di (+) AL --> AL
5. j+1 --> j
6. shr(A)
7. is there a carry? No: go to 8.
Yes: G (+) A --> A
8. is j = 8? No: go to 5.
Yes: go to 9.
9. i+1 --> i
10. is i = N? No: go to 3.
Yes: go to 11.
11. A --> CRC
5.5 TimingData packet synchronization is maintained by timing constraints. The receiving device must measure the time between the reception of characters. If three and one half character times elapse without a new character or completion of the packet, then the communication link must be reset (i.e. all slaves start listening for a new transmission from the master). Thus at 9600 baud a delay of greater than 3.5 × 1 / 9600 × 10 = 3.65 ms will cause the communication link to be reset.
5.6 Supported Modbus FunctionsThe following Modbus functions are supported by the 369:
• 03 - Read Setpoints and Actual Values
• 04 - Read Setpoints and Actual Values
• 05 - Execute Operation
• 06 - Store Single Setpoint
• 07 - Read Device Status
• 08 - Loopback Test
• 16 - Store Multiple Setpoints
For detailed Modbus function code descriptions, refer to the Modicon Modbus Protocol Reference guide.
5.7 Error ResponsesWhen an 369 detects an error other than a CRC error, a response will be sent to the master. The MSbit of the FUNCTION CODE byte will be set to 1 (i.e. the function code sent from the slave will be equal to the function code sent from the master plus 128). The following byte will be an exception code indicating the type of error that occurred.
Transmissions received from the master with CRC errors will be ignored by the 369 Relay. The slave response to an error (other than CRC error) will be:
CGCOMMUNICATIONS GUIDE MODBUS RTU PROTOCOL
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG49
SLAVE ADDRESS - 1 byteFUNCTION CODE - 1 byte (with MSbit set to 1)EXCEPTION CODE - 1 byteCRC - 2 bytes
The 369 implements the following exception response codes.
• 01 - ILLEGAL FUNCTION:
The function code transmitted is not one of the functions supported by the 369 Relay.
• 02 - ILLEGAL DATA ADDRESS:
The address referenced in the data field transmitted by the master is not an allowable address for the 369 Relay.
• 03 - ILLEGAL DATA VALUE:
The value referenced in the data field transmitted by the master is not within range for the selected data address.
5.8 Modbus CommandsThe following commands can be sent to Modbus address 0x0080 (format code F31). Commands 1 to 4 can also be sent using Modbus function code 5 (Execute Operation).
• Command 1 (Remote Reset 369): Modbus Command 1 will attempt to clear the status of protection elements and output relay states.
• Command 2 (Motor Start): Modbus Command 2 will activate the programmed start relay, as long as it is not currently active and the stop relay is not currently active.
• Command 3 (Motor Stop): Modbus Command 3 will activate the trip relay as long as it is not currently active and the start relay is not currently active.
• Command 4 (Waveform Trigger): Modbus Command 4 will trigger the waveform capture trace memory.
• Command 6 (Clear Trip Counters): Modbus Command 6 will clear all trip counters.
• Command 7 (Clear Last Trip Data): Modbus Command 7 will clear the last trip data.
• Command 10 (Clear RTD Maximums): Modbus Command 10 will initialize all RTD (and Remote RTD, if applicable) maximum data to default values.
• Command 11 (Reset Motor Info): Modbus Command 11 will clear the number of motor starts, number of motor restarts, motor running hours, and number of restart attempts. It will also clear all learned motor statistics and Data Logger data.
• Command 12 (Clear/Reset All Data): Modbus Command 12 will clear all event data, trip counters, last trip data, peak demand data, RTD maximums data, motor statistics data, Data Logger data, and all energy data.
• Command 20 (Protection Function Blocking): This command must be sent using Modbus function code 10h (Store Multiple Setpoints). This allows the 369 to accept the two required 16-bit values in one transmission. The first data word is the command number (20). The 2nd data word contains the bitmask information for which functions to block/unblock as per format code F180.
CG50 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MODBUS RTU PROTOCOL CGCOMMUNICATIONS GUIDE
When this command is sent to the 369, the protection function blocking setpoints (Modbus addresses 1520 to 1528) are updated accordingly. For example, for Bit 0 in the 2nd data word, the setpoint value for Block Undercurrent/Underpower at address 1521 will be modified to contain either a “1” or “0”, depending on the bit value.
Refer to the 369 Instruction Manual, chapter 5: Block Functions for additional information about the protection function blocking feature.
• Command 21 (Force Output Relays): Modbus Command 20 must be sent using Modbus function code 10h (Store Multiple Setpoints). This allows the 369 to accept the two required 16-bit values in one transmission. The first data word is the command number (21). The 2nd data word contains the bitmask information for which relays to energize/de-energize as per format code F141.
The purpose of this command is to allow the control of the output relay status, regardless of the motor status (running, stopped, etc.). Only relays that have been programmed under the ASSIGN COMMS FORCE RELAYS setpoint can be forced using this command.
Refer to the 369 Instruction Manual, chapter 5: Force Output Relays for more information about the force output relays feature.
• Command 24 (Clear Data Logger Data): This command will clear all the existing data presently available in the Data Logger feature. Please refer to the 369 Instruction Manual, chapter 6: Data Logger and 6.6: Data Logger for more information on the Data Logger feature.
CGCOMMUNICATIONS GUIDE MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG51
6 Memory Map
6.1 Memory Map InformationThe data stored in the 369 is grouped as setpoints and actual values. Setpoints can be read and written by a master computer. Actual Values are read-only. All setpoints and actual values are stored as two-byte values. That is, each register address is the address of a two-byte value. Addresses are listed in hexadecimal. Data values (setpoint ranges, increments, factory values) are in decimal.
Note Many Modbus communications drivers add 40001d to the actual address of the register addresses. For example: if address 0h was to be read, 40001d would be the address required by the Modbus communications driver; if address 320h (800d) was to be read, 40801d would be the address required by the Modbus communications driver.
6.2 User Definable Memory Map AreaThe 369 has a powerful feature, called the User Definable Memory Map, which allows a computer to read up to 125 non-consecutive data registers (setpoints or actual values) by using one Modbus packet. It is often necessary for a master computer to continuously poll various values in each of the connected slave relays. If these values are scattered throughout the memory map, reading them would require numerous transmissions and would burden the communication link. The User Definable Memory Map can be programmed to join any memory map address to one in the block of consecutive User Map locations, so that they can be accessed by reading these consecutive locations.
The User Definable area has two sections:
1. A Register Index area (memory map addresses 0180h-01FCh) that contains 125 Actual Values or Setpoints registers.
2. A Register area (memory map addresses 0100h-017Ch) that contains the data at the addresses in the Register Index.
Register data that is separated in the rest of the memory map may be remapped to adjacent register addresses in the User Definable Registers area. This is accomplished by writing to register addresses in the User Definable Register Index area. This allows for improved through-put of data and can eliminate the need for multiple read command sequences. For example, if the values of Average Phase Current (register address 0306h) and Hottest Stator RTD Temperature (register address 0320h) are required to be read from an 369, their addresses may be remapped as follows:
1. Write 0306h to address 0180h (User Definable Register Index 0000) using function code 06 or 16.
2. Write 0320h to address 0181h (User Definable Register Index 0001) using function code 06 or 16.
A read (function code 03 or 04) of registers 0100h (User Definable Register 0000) will return the Phase A Current and register 0101h (User Definable Register 0001) will return Hottest Stator RTD Temperature.
CG52 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP CGCOMMUNICATIONS GUIDE
6.3 Event RecorderThe 369 event recorder data starts at address 3000h. Address 3003h is a pointer to the event of interest (1 representing the oldest event and 512 representing the latest event. To retrieve event 1, write ‘1’ to the Event Record Selector (3003h) and read the data from 3004h to 3022h. To retrieve event 2, write ‘2’ to the Event Record Selector (3003h) and read the data from 3004h to 3022h. All 512 events may be retrieved in this manner. The time and date stamp of each event may be used to ensure that all events have been retrieved in order without new events corrupting the sequence of events (event 3 should be more recent than event 2, event 2 should be more recent than event 1, etc.).
The digital counter will be displayed when one of the digital inputs has been set up as a digital counter. The digital counter can be cleared with the S1 369 SETUP CLEAR/PRESET DATA PRESET DIGITAL COUNTER setpoint. When the digital counter has exceeded 65535, it will automatically be reset by the 369 Relay relay to 0.
6.4 Waveform CaptureThe 369 stores 16 cycles of A/D samples each time a trip occurs in a trace buffer. The Trace Memory Trigger is set up in S1 Preferences and determines how many pre-trip and post-trip cycles are stored. The trace buffer is time and date stamped and may be correlated to a trip in the event record. 7 waveforms are captured this way when a trip occurs. These are the 3 phase currents, ground current and 3 voltage waveforms. The last three captured records are retained by the 369. This information is stored in volatile memory and will be lost if power is cycled to the relay.
To access the captured waveforms, select the captured record by writing to the Trace Memory Buffer Selector (address 30F5h), then select waveform of interest by writing its trace memory channel (see following table) to the Trace Memory Channel Selector (address 30F6h). Then read the trace memory data from address 3100h to 31FFh. The values read are in actual amperes or volts.
6.5 Motor Start Data LoggerWhen a motor start status condition is detected by the 369 relay, the MOTOR START DATA LOGGER is triggered and begins to sample and record the following parameters at a rate of 1 sample every 200ms:
• True RMS values of the Phase A, B and C Currents (Ia, Ib, and Ic).
• True RMS value of the Ground current (Ig).
• Current Unbalance (%).
TRACE MEMORYCHANNEL
WAVEFORM TRACE MEMORYCHANNEL
WAVEFORM
0 Phase A current 4 Phase A voltage1
1. For an Open Delta VT connection channel 4 contains Vab data and channel 6 contains Vcb data.
1 Phase B current 5 Phase B voltage
2 Phase C current 6 Phase C voltage1
3 Ground current
CGCOMMUNICATIONS GUIDE MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG53
• True RMS values of the Phase A-N, B-N, and C-N voltages (Van, Vbn, and Vcn) if VT CONNECTION TYPE is set to Wye.True RMS values of the Phase A-B, B-C and C-A voltages (Vab, Vbc, and Vca) if VT CONNECTION TYPE is set to Delta.
• Thermal Capacity Used (%).
• Frequency.
• Breaker/Contactor Contact Input Status
• Motor Speed (low/high).
1 second of pre-trigger data and 29 seconds of post-trigger data are recorded. The data logger ignores all subsequent triggers and continues to record data until the active record is finished.
A total of 6 logs are stored in the relay. Log #1 is the baseline log, it is written only by the first start after clearing the MOTOR START DATA LOGGER (see the 369 Instruction Manual, chapter 5: Clear/Preset Data). Logs #2 to 6 are rolling buffers of the last 5 motor starts. Each new log automatically shifts the rolling buffer and overwrites the oldest log, #2.
Log files are formatted using CSV (comma delimited values). The files can be downloaded and displayed via EnerVista 369 Setup software. All files are stored in non-volatile memory; information is retained when power to the relay is lost.
6.6 Data LoggerThe Data Logger allows up to 16 channels of data parameters (refer to Modbus format code F189 for the available parameters) to be continually recorded at a defined rate of between 1 and 3600 seconds. The 369 has allocated 32k bytes of RAM for Data Log storage. All data will be lost upon loss of the 369 control power.
Internal to the 369, the memory structure is partitioned into 256 blocks containing 64 two-byte registers. Blocks 0 and 1 have been allocated for the Header data, and Blocks 2-255 have been allocated to the logged data. In order to access the Log data and read it via the "Data Logger Data" Modbus addresses 0x3281 to 0x32C0, a Block index value is stored to the Data Log Memory Access Block Number at Modbus address 0x1E23. The data obtained from the Data Logger Data registers will differ depending on the Block index value stored.
Each entry into a Data Log is called a Record. The Record size will vary in size depending upon the how many channels the user wishes to use. In addition to the actual logged data itself, the Data Logger contains what is called the Header, which can be read from Modbus address 0x3200 to 0x3278. The Data Log Header contains the following read-only information:
• Log Time Interval: This is the interval at which the data log will store entries (1~3600s).
• Log Record Size: This is the size of each Record entry into the Data Log. It is based upon how many channels have been selected to use.
• Log Total Possible Records: This value indicates the maximum number of potential records available, which depends on the record size.
• Total Logs Since Last Clear: This value indicates the number of Logs that have been generated since the Data Logger was last cleared. Although it's maximum range is 65535, the 369 will only retain up to the latest 50 records.
CG54 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP CGCOMMUNICATIONS GUIDE
• Total Logs Presently Used: This value indicates the total number of Logs that have been captured and are presently available in the 369.
• Total Records Presently Used: This is the number of records that have been written into the Data Log and are presently available in the 369.
• Log Status: This reports the current status of the Data Logger (Running or Stopped).
• Log Time Remaining Until Next Reading: This is a counter showing how much time remains until the next record is to be written into the Data Log (1~3600s).
• Data Logger Percentage Full: Indicates what percentage of the total available memory is used.
• Pointer To Next Record To Write: This value points to the internal data address of the location of the next record to be written.
• Pointer To Log (1-50) Starting Address : This value points to the internal data address of the location of each of the potential 50 records.
• Log (1-50) Number of Records: This value provides the number of records that each of the 50 potential Logs contain.
• Log (1-50) Start/Stop Method: This value is used to indicate the method by which each log was started and stopped. If the bit value for the Start is zero, it was started by a motor start event. Refer to Modbus format code F191 for more information on the format of this data.
6.7 Modbus Memory Map
Table CG–10: MEMORY MAP (Sheet 1 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
PRODUCT ID (ADDRESSES 0000 TO 007F)PRODUCT ID
0000 GE Multilin Product Code - - - - F1 530001 Product Hardware Revision 1 26 1 N/A F15 A0002 Firmware Revision N/A N/A N/A N/A F16 N/A0003 Installed Modifications 0 65535 1 N/A F14 00004 Boot Revision 0 999 1 - F1 00005 Boot Modification Number - - - - - -0006 Reserved - - - - - -0007 Reserved - - - - - -0008 Order Code 0 65535 1 N/A F13 0↓ ↓ - - - - - -000F Modify Options 0 N/A - N/A N/A -
0010Modify Options Passcode Characters 1 and 2
32 127 1 - F1 " "
↓ ↓ - - - - - -
0017Modify Options Passcode Characters 15 and 16
32 127 1 - F1 " "
--- --- - - - - - -0020 Serial Number character 1 and 2 N/A N/A N/A ASCII F22 N/A0021 Serial Number character 3 and 4 N/A N/A N/A ASCII F22 N/A0022 Serial Number character 5 and 6 N/A N/A N/A ASCII F22 N/A
CGCOMMUNICATIONS GUIDE MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG55
0023 Serial Number character 7 and 8 N/A N/A N/A ASCII F22 N/A
0024 Serial Number character 9 and 10 N/A N/A N/A ASCII F22 N/A
0025 Serial Number character 11 and 12 N/A N/A N/A ASCII F22 N/A
0026 Main Firmware Build Date N/A N/A N/A - F18 N/A0028 Main Firmware Build Time N/A N/A N/A - F19 N/A... Reserved - - - - - -
0040 Manufacturing Date 1995 2094 1 - F18 Jan.1,1999
... Reserved - - - - - -SETPOINT ACCESS
0050 Keypad Access Level 0 1 1 N/A F162 00051 Comm Access Level 0 1 1 N/A F162 0
0052 Access Password Character 1 and 2 32 127 1 - F1 " "
0053 Access Password Character 3 and 4 32 127 1 - F1 " "
0054 Access Password Character 5 and 6 32 127 1 - F1 " "
0055 Access Password Character 7 and 8 32 127 1 - F1
0056 Encrypted Access Password 1 and 2 32 127 1 - F1 “AI”
0057 Encrypted Access Password 3 and 4 32 127 1 - F1 “KF”
0058 Encrypted Access Password 5 and 6 32 127 1 - F1 “BA”
0059 Encrypted Access Password 7 and 8 32 127 1 - F1 IK”
... Reserved - - - - - -COMMANDS (ADDRESSES 0080 TO 00FB)
0080 Command Function Code 0 21 1 - F31 00081 Reserved
0082 RRTD 1 Command Function Code 0 4 1 - F31 0
0083 RRTD 2 Command Function Code 0 4 1 - F31 0
0084 RRTD 3 Command Function Code 0 4 1 - F31 0
0085 RRTD 4 Command Function Code 0 4 1 - F31 0
... ReservedREAL TIME CLOCK
00F0 Time (2 words) valid time N/A - F19 -00F2 Date (2 words) valid date N/A - F18 -... Reserved
PROFIBUS COMMUNICATIONS
00FC Fieldbus Loss of Comms Enable 0 2 1 - F115 0 (Off)00FD Fieldbus Loss of Comms Delay 25 1000 250 msec F2 25
00FE Assign Fieldbus Loss of Comms Relay 0 15 1 - F169 0 (None)
00FF Profibus Cyclic Input Data Configuration 0 110 1 - F1 0
Table CG–10: MEMORY MAP (Sheet 2 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CG56 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP CGCOMMUNICATIONS GUIDE
USER MAP (ADDRESSES 0100 TO 017F)
0100 User Map Value # 1 --- --- --- --- --- ---↓ ↓017C User Map Value # 125 --- --- --- --- --- ---... Reserved0180 User Map Address # 1 0 3FFF 1 hex F1 0↓ ↓01FC User Map Address # 125 0 3FFF 1 hex F1 0... Reserved
ACTUAL VALUES (ADDRESSES 0200 TO 0FFF)MOTOR STATUS
0200 Motor Status 0 4 1 - F133 00201 Motor Thermal Capacity Used 0 100 1 % F1 0
0202 Estimated Time to Trip on Overload -1 65500 1 s F20 -1
AUTORESTART
0203 Restart Attempts 0 20000 1 - F1 -0204 Restart Total Delay 0 65535 1 sec. F1 -0205 Restart In Progress 0 1 1 Y/N F1 -
0206 UVR Power Loss Time 0 40000 1 0.1 s F2 Read Only
MOTOR SPEED STATUS
0207 Motor Speed Status 0 2 1 N/A F186 0... Reserved
LAST TRIP DATA
0220 Cause of Last Trip 0 276 1 - F134 00221 Last Trip Time (2 words) N/A N/A N/A N/A F19 -0223 Last Trip Date (2 words) N/A N/A N/A N/A F18 -0225 Last Trip Motor Speed 0 2 1 N/A F186 -0226 Phase A Pre-Trip Current 0 65535 1 A F1 00228 Phase B Pre-Trip Current 0 65535 1 A F1 0022A Phase C Pre-Trip Current 0 65535 1 A F1 0022C Motor Load Pre - Trip 0 2000 1 FLA F3 0022D Current Unbalance Pre - Trip 0 100 1 % F1 0022E Ground Current Pre - Trip 0 50000 1 A F2 0... Reserved - - - - - -
0233 Hottest Stator RTD Owner During Trip 0 5 1 N/A F165 0
0234 Hottest Stator RTD During Trip 0 12 1 - F1 0
0235 Pre-Trip Temperature of Hottest Stator RTD -40 200 1 °C F4 0
0236 Pre-Trip Voltage Vab 0 65000 1 V F1 00237 Pre-Trip Voltage Vbc 0 65000 1 V F1 00238 Pre-Trip Voltage Vca 0 65000 1 V F1 00239 Pre-Trip Voltage Van 0 65000 1 V F1 0023A Pre-Trip Voltage Vbn 0 65000 1 V F1 0023B Pre-Trip Voltage Vcn 0 65000 1 V F1 0023C Pre-Trip System Frequency 0 12000 1 Hz F3 0023D Pre-Trip Real Power -32000 32000 1 kW F4 0023E Pre-Trip Reactive Power -32000 32000 1 kvar F4 0023F Pre-Trip Apparent Power 0 50000 1 kVA F1 00240 Pre-Trip Power Factor -99 100 1 - F21 0
Table CG–10: MEMORY MAP (Sheet 3 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CGCOMMUNICATIONS GUIDE MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG57
... Reserved - - - - - -ALARM STATUS
0260General Spare Switch Alarm Status orStarter Monitor Alarm/Trip Status
0 4 1 - F123 0
0261 General Emergency Restart Switch Alarm Status 0 4 1 - F123 0
0262 General Differential Switch Alarm Status 0 4 1 - F123 0
0263 General Speed Switch Alarm Status 0 4 1 - F123 0
0264 General Reset Switch Alarm Status 0 4 1 - F123 0
... Reserved0267 Thermal Capacity Alarm 0 4 1 - F123 00268 Overload Alarm Status 0 4 1 - F123 00269 Mechanical Jam Alarm Status 0 4 1 - F123 0026A Undercurrent Alarm Status 0 4 1 - F123 0026B Current Unbalance Alarm Status 0 4 1 - F123 0026C Ground Fault Alarm Status 0 4 1 - F123 0... Reserved026F Undervoltage Alarm Status 0 4 1 - F123 00270 Overvoltage Alarm Status 0 4 1 - F123 00271 Overfrequency Alarm Status 0 4 1 - F123 00272 Underfrequency Alarm Status 0 4 1 - F123 0... Reserved0275 Lead Power Factor Alarm Status 0 4 1 - F123 00276 Lag Power Factor Alarm Status 0 4 1 - F123 00277 Positive kvar Alarm Status 0 4 1 - F123 00278 Negative kvar Alarm Status 0 4 1 - F123 00279 Underpower Alarm Status 0 4 1 - F123 0027A Reverse Power Alarm Status 0 4 1 - F123 0... Reserved027D Local RTD #1 Alarm Status 0 4 1 - F123 0027E Local RTD #2 Alarm Status 0 4 1 - F123 0027F Local RTD #3 Alarm Status 0 4 1 - F123 00280 Local RTD #4 Alarm Status 0 4 1 - F123 00281 Local RTD #5 Alarm Status 0 4 1 - F123 00282 Local RTD #6 Alarm Status 0 4 1 - F123 00283 Local RTD #7 Alarm Status 0 4 1 - F123 00284 Local RTD #8 Alarm Status 0 4 1 - F123 00285 Local RTD #9 Alarm Status 0 4 1 - F123 00286 Local RTD #10 Alarm Status 0 4 1 - F123 00287 Local RTD #11 Alarm Status 0 4 1 - F123 00288 Local RTD #12 Alarm Status 0 4 1 - F123 00289 Local RTD #1 High Alarm Status 0 4 1 - F123 0028A Local RTD #2 High Alarm Status 0 4 1 - F123 0028B Local RTD #3 High Alarm Status 0 4 1 - F123 0028C Local RTD #4 High Alarm Status 0 4 1 - F123 0028D Local RTD #5 High Alarm Status 0 4 1 - F123 0028E Local RTD #6 High Alarm Status 0 4 1 - F123 0
Table CG–10: MEMORY MAP (Sheet 4 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CG58 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP CGCOMMUNICATIONS GUIDE
028F Local RTD #7 High Alarm Status 0 4 1 - F123 00290 Local RTD #8 High Alarm Status 0 4 1 - F123 00291 Local RTD #9 High Alarm Status 0 4 1 - F123 00292 Local RTD #10 High Alarm Status 0 4 1 - F123 00293 Local RTD #11 High Alarm Status 0 4 1 - F123 00294 Local RTD #12 High Alarm Status 0 4 1 - F123 00295 Broken / Open RTD Alarm Status 0 4 1 - F1230296 Short / Low Temp Alarm Status 0 1 1 - F1230297 Reserved0298 Trip Counter Alarm Status 0 4 1 - F123 00299 Starter Failure Alarm 0 4 1 - F123 0029A Current Demand Alarm Status 0 4 1 - F123 0029B kW Demand Alarm Status 0 4 1 - F123 0029C kvar Demand Alarm Status 0 4 1 - F123 0029D kVA Demand Alarm Status 0 4 1 - F123 0029E Self Test Alarm 0 4 1 - F123 0
START BLOCK STATUS
02C0 Overload Lockout Timer 0 9999 1 min F1 002C1 Start Timer 1 0 60 1 min F1 002C2 Start Timer 2 0 60 1 min F1 002C3 Start Timer 3 0 60 1 min F1 002C4 Start Timer 4 0 60 1 min F1 002C5 Start Timer 5 0 60 1 min F1 002C6 Time Between Starts Timer 0 500 1 min F1 002C7 Restart Block Timer 0 50000 1 s F1 002C8 Reserved02C9 Start Inhibit Timer 0 500 1 min F1 002CA Starts Per Hour Lockout Timer 0 60 1 min F1 0... Reserved
DIGITAL INPUT STATUS
02D0 Access 0 1 1 - F131 002D1 Speed 0 1 1 - F131 002D2 Spare 0 1 1 - F131 002D3 Differential Relay 0 1 1 - F131 002D4 Emergency Restart 0 1 1 - F131 002D5 Reset 0 1 1 - F131 0... Reserved
OUTPUT RELAY STATUS
02E0 Trip 0 1 1 N/A F150 002E1 Alarm 0 1 1 N/A F150 002E2 Aux.1 0 1 1 N/A F150 002E3 Aux.2 0 1 1 N/A F150 0... Reserved
369 DIGITAL INPUT AND OUTPUT RELAY STATUS
02E6 Digital Input and Output Relay Status N/A N/A N/A N/A F192 0
... ReservedREAL TIME CLOCK
02F0 Date (Read Only) N/A N/A N/A N/A F18 N/A02F4 Time (Read Only) N/A N/A N/A N/A F19 N/A... Reserved
Table CG–10: MEMORY MAP (Sheet 5 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CGCOMMUNICATIONS GUIDE MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG59
FIELDBUS SPECIFICATION STATUS
02F8 Explicit Connection Status 0 5 1 N/A F168 0
02F9 Input/Output Polled Connection Status 0 5 1 N/A F168 0
02FA Network Status 0 3 1 N/A F167 0... Reserved
CURRENT METERING
0300 Phase A Current 0 65535 1 A F1 00302 Phase B Current 0 65535 1 A F1 00304 Phase C Current 0 65535 1 A F1 00306 Average Phase Current 0 65535 1 A F1 00308 Motor Load 0 2000 1 × FLA F3 00309 Current Unbalance 0 100 1 % F1 0030A Unbalaced Biased Motor Load 0 9999 1 × FLA F3 0030B Ground Current 0 65535 1 A F23 0... Reserved - - - - - -
OVERALL STATOR RTD
031C Overall Hottest Stator RTD Owner 0 5 1 N/A F165 0
031D Overall Hottest Stator RTD Number 0 12 1 N/A F1 0
031E Overall Hottest Stator RTD Temperature –40 200 1 °C F4 -
TEMPERATURE
031F Local Hottest Stator RTD Number 0 12 1 - F1 0
0320 Local Hottest Stator RTD Temperature –40 200 1 °C F4 40
0321 Local RTD #1 Temperature –40 200 1 °C F4 400322 Local RTD #2 Temperature –40 200 1 °C F4 400323 Local RTD #3 Temperature –40 200 1 °C F4 400324 Local RTD #4 Temperature –40 200 1 °C F4 400325 Local RTD #5 Temperature –40 200 1 °C F4 400326 Local RTD #6 Temperature –40 200 1 °C F4 400327 Local RTD #7 Temperature –40 200 1 °C F4 400328 Local RTD #8 Temperature –40 200 1 °C F4 400329 Local RTD #9 Temperature –40 200 1 °C F4 40032A Local RTD #10 Temperature –40 200 1 °C F4 40032B Local RTD #11 Temperature –40 200 1 °C F4 40032C Local RTD #12 Temperature –40 200 1 °C F4 40... Reserved
VOLTAGE METERING
0360 Vab 0 65535 1 V F1 00361 Vbc 0 65535 1 V F1 00362 Vca 0 65535 1 V F1 00363 Average Line Voltage 0 65535 1 V F1 00364 Van 0 65535 1 V F1 00365 Vbn 0 65535 1 V F1 00366 Vcn 0 65535 1 V F1 00367 Average Phase Voltage 0 65535 1 V F1 00368 System Frequency 0 12000 1 Hz F3 0
Table CG–10: MEMORY MAP (Sheet 6 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CG60 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP CGCOMMUNICATIONS GUIDE
BACKSPIN METERING
0369 Backspin Frequency (a value of “0” represents ‘low signal’) 0 12000 1 Hz F3 0
036A Backspin Detection State 0 6 1 - F27 0036B Backspin Prediction Timer 0 50000 1 s F1 0... Reserved
POWER METERING
0370 Power Factor –99 100 1 - F21 00371 Real Power –32000 32000 1 kW F4 00373 Real Power 0 42912 1 hp F1 00374 Reactive Power –32000 32000 1 kvar F4 00376 Apparent Power 0 65000 1 kVA F1 00377 Positive MegaWatthours 0 65535 1 MWh F1 00379 Positive Megavarhours 0 65535 1 Mvarh F1 0037B Negative Megavarhours 0 65535 1 Mvarh F1 0037D Positive KiloWatthours 0 999 1 kWh F1 0037F Positive Kilovarhours 0 999 1 kvarh F1 00381 Negative Kilovarhours 0 999 1 kvarh F1 0... Reserved
DEMAND METERING
0390 Current Demand 0 65535 1 A F1 00392 Real Power Demand 0 32000 1 kW F1 00394 Reactive Power Demand 0 32000 1 kvar F1 00396 Apparent Power Demand 0 65000 1 kVA F1 00397 Peak Current Demand 0 65535 1 A F1 00399 Peak Real Power Demand 0 32000 1 kW F1 0039B Peak Reactive Power Demand 0 32000 1 kvar F1 0039D Peak Apparent Power Demand 0 65000 1 kVA F1 0... Reserved
MOTOR DATA (0 = OFF)
03C0 Learned Acceleration Time 1 2500 1 s F2 003C1 Learned Starting Current 0 65535 1 A F1 003C2 Learned Starting Capacity 0 100 1 % F1 0
03C3 Learned Running Cool Time Constant 0 500 1 min F1 0
03C4 Learned Stopped Cool Time Constant 0 500 1 min F1 0
03C5 Last Starting Current 0 65535 1 A F1 003C6 Last Starting Capacity 0 100 1 % F1 003C7 Last Acceleration Time 1 2500 1 s F2 003C8 Average Motor Load Learned 0 2000 1 x FLA F3 003C9 Learned Unbalance k factor 0 29 1 - F1 0
03CA Average Run Time After Start (Days) 0 65535 1 days F1 0
03CB Average Run Time After Start (Minutes) 1440 1 minutes F1 0
03CC Date of Record - - - - F19 -
03CE Number of Enhanced Learned Records 0 65535 1 F1 0
LOCAL RTD MAXIMUMS
03E0 Local RTD # 1 Max. Temperature -40 200 1 °C F4 4003E1 Local RTD # 2 Max. Temperature -40 200 1 °C F4 40
Table CG–10: MEMORY MAP (Sheet 7 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CGCOMMUNICATIONS GUIDE MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG61
03E2 Local RTD # 3 Max. Temperature -40 200 1 °C F4 4003E3 Local RTD # 4 Max. Temperature -40 200 1 °C F4 4003E4 Local RTD # 5 Max. Temperature -40 200 1 °C F4 4003E5 Local RTD # 6 Max. Temperature -40 200 1 °C F4 4003E6 Local RTD # 7 Max. Temperature -40 200 1 °C F4 4003E7 Local RTD # 8 Max. Temperature -40 200 1 °C F4 4003E8 Local RTD # 9 Max. Temperature -40 200 1 °C F4 40
03E9 Local RTD # 10 Max. Temperature -40 200 1 °C F4 40
03EA Local RTD # 11 Max. Temperature -40 200 1 °C F4 40
03EB Local RTD # 12 Max. Temperature -40 200 1 °C F4 40
... ReservedTRIP COUNTERS
0430 Total Number of Trips 0 50000 1 - F1 0... Reserved0433 Switch Trips 0 50000 1 - F1 0... Reserved0436 Overload Trips 0 50000 1 - F1 00437 Short Circuit Trips 0 50000 1 - F1 00438 Mechanical Jam Trips 0 50000 1 - F1 00439 Undercurrent Trips 0 50000 1 - F1 0043A Current Unbalance Trips 0 50000 1 - F1 0043B Single Phase Trips043C Ground Fault Trips 0 50000 1 - F1 0043D Acceleration Trips 0 50000 1 - F1 0... Reserved043F Undervoltage Trips 0 50000 1 - F1 00440 Overvoltage Trips 0 50000 1 - F1 00441 Phase Reversal Trips 0 50000 1 - F1 00442 Under Frequency Trips 0 50000 1 - F1 00443 Over Frequency Trips 0 50000 1 - F1 0... Reserved0446 Lead Power Factor Trips 0 50000 1 - F1 00447 Lag Power Factor Trips 0 50000 1 - F1 00448 Positive Reactive Power Trips 0 50000 1 - F1 00449 Negative Reactive Power Trips 0 50000 1 - F1 0044A Underpower Trips 0 50000 1 - F1 0044B Reverse Power Trips 0 50000 1 - F1 0... Reserved044E Stator RTD Trips 0 50000 1 - F1 0044F Bearing RTD Trips 0 50000 1 - F1 00450 Other RTD Trips 0 50000 1 - F1 00451 Ambient RTD Trips 0 50000 1 - F1 0
0452 UVR Undervoltage Trip Counters 0 50000 1 - F1 Read Only
... Reserved0454 Incomplete Sequence Trips 0 50000 1 - F1 0... Reserved0457 Trip Counters Last Cleared N/A N/A N/A N/A F18 N/A
Table CG–10: MEMORY MAP (Sheet 8 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CG62 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP CGCOMMUNICATIONS GUIDE
... ReservedMOTOR STATISTICS
0470 Number of Motor Starts 0 50000 1 - F1 00471 Number of Emergency Restarts 0 50000 1 - F1 00472 Reserved - - - - - -0473 Digital Counter 0 65535 1 - F1 0... Reserved04A0 Motor Running Hours 0 65535 1 hr. F1 0... Reserved
PHASORS
0500 Va Angle 0 359 1 degrees F1 00501 Vb Angle 0 359 1 degrees F1 00502 Vc Angle 0 359 1 degrees F1 00503 Ia Angle 0 359 1 degrees F1 00504 Ib Angle 0 359 1 degrees F1 00505 Ic Angle 0 359 1 degrees F1 0... Reserved
REMOTE RTD ACTUAL VALUES (ADDRESSES 0600 TO 1FFF)RRTD 1 TEMPERATURES
0600 RRTD 1 - Hottest Stator Number 0 12 1 - F1 0
0601 RRTD 1 - Hottest Stator Temperature -40 200 1 °C F4 40
0602 RRTD 1 - RTD #1 Temperature -40 200 1 °C F4 400603 RRTD 1 - RTD #2 Temperature -40 200 1 °C F4 400604 RRTD 1 - RTD #3 Temperature -40 200 1 °C F4 400605 RRTD 1 - RTD #4 Temperature -40 200 1 °C F4 400606 RRTD 1 - RTD #5 Temperature -40 200 1 °C F4 400607 RRTD 1 - RTD #6 Temperature -40 200 1 °C F4 400608 RRTD 1 - RTD #7 Temperature -40 200 1 °C F4 400609 RRTD 1 - RTD #8 Temperature -40 200 1 °C F4 40060A RRTD 1 - RTD #9 Temperature -40 200 1 °C F4 40060B RRTD 1 - RTD #10 Temperature -40 200 1 °C F4 40060C RRTD 1 - RTD #11 Temperature -40 200 1 °C F4 40060D RRTD 1 - RTD #12 Temperature -40 200 1 °C F4 40... Reserved
RRTD 2 TEMPERATURES
0610 RRTD 2 - RTD - Hottest Stator Number 0 12 1 - F1 0
0611 RRTD 2 - RTD - Hottest Stator Temperature -40 200 1 °C F4 40
0612 RRTD 2 - RTD #1Temperature -40 200 1 °C F4 400613 RRTD 2 - RTD #2 Temperature -40 200 1 °C F4 400614 RRTD 2 - RTD #3 Temperature -40 200 1 °C F4 400615 RRTD 2 - RTD #4 Temperature -40 200 1 °C F4 400616 RRTD 2 - RTD #5 Temperature -40 200 1 °C F4 400617 RRTD 2 - RTD #6 Temperature -40 200 1 °C F4 400618 RRTD 2 - RTD #7 Temperature -40 200 1 °C F4 400619 RRTD 2 - RTD #8 Temperature -40 200 1 °C F4 40061A RRTD 2 - RTD #9 Temperature -40 200 1 °C F4 40061B RRTD 2 - RTD #10 Temperature -40 200 1 °C F4 40061C RRTD 2 - RTD #11 Temperature -40 200 1 °C F4 40
Table CG–10: MEMORY MAP (Sheet 9 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CGCOMMUNICATIONS GUIDE MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG63
061D RRTD 2 - RTD #12 Temperature -40 200 1 °C F4 40... Reserved
RRTD 3 TEMPERATURES
0620 RRTD 3 - RTD - Hottest Stator Number 0 12 1 - F1 0
0621 RRTD 3 - RTD - Hottest Stator Temperature -40 200 1 °C F4 40
0622 RRTD 3 - RTD #1 Temperature -40 200 1 °C F4 400623 RRTD 3 - RTD #2 Temperature -40 200 1 °C F4 400624 RRTD 3 - RTD #3 Temperature -40 200 1 °C F4 400625 RRTD 3 - RTD #4 Temperature -40 200 1 °C F4 400626 RRTD 3 - RTD #5 Temperature -40 200 1 °C F4 400627 RRTD 3 - RTD #6 Temperature -40 200 1 °C F4 400628 RRTD 3 - RTD #7 Temperature -40 200 1 °C F4 400629 RRTD 3 - RTD #8 Temperature -40 200 1 °C F4 40062A RRTD 3 - RTD #9 Temperature -40 200 1 °C F4 40062B RRTD 3 - RTD #10 Temperature -40 200 1 °C F4 40062C RRTD 3 - RTD #11 Temperature -40 200 1 °C F4 40062D RRTD 3 - RTD #12 Temperature -40 200 1 °C F4 40... Reserved
RRTD 4 TEMPERATURES
0630 RRTD 4 - RTD- Hottest Stator Number 0 12 1 - F1 0
0631 RRTD 4 - RTD- Hottest Stator Temperature -40 200 1 °C F4 40
0632 RRTD 4 - RTD#1 Temperature -40 200 1 °C F4 400633 RRTD 4 - RTD#2 Temperature -40 200 1 °C F4 400634 RRTD 4 - RTD#3 Temperature -40 200 1 °C F4 400635 RRTD 4 - RTD#4 Temperature -40 200 1 °C F4 400636 RRTD 4 - RTD#5 Temperature -40 200 1 °C F4 400637 RRTD 4 - RTD#6 Temperature -40 200 1 °C F4 400638 RRTD 4 - RTD#7 Temperature -40 200 1 °C F4 400639 RRTD 4 - RTD#8 Temperature -40 200 1 °C F4 40063A RRTD 4 - RTD#9 Temperature -40 200 1 °C F4 40063B RRTD 4 - RTD#10 Temperature -40 200 1 °C F4 40063C RRTD 4 - RTD#11 Temperature -40 200 1 °C F4 40063D RRTD 4 - RTD#12 Temperature -40 200 1 °C F4 40
LOSS OF RRTD COMMUNICATIONS
063E Lost RRTD Communications alarm 0 4 1 - F123 0
063F Actively Communicating RRTDs 0 15 - - F183 -RRTD 1 ALARM STATUS
0650 RRTD 1 - RTD #1 Alarm Status 0 4 1 - F123 00651 RRTD 1 - RTD #2 Alarm Status 0 4 1 - F123 00652 RRTD 1 - RTD #3 Alarm Status 0 4 1 - F123 00653 RRTD 1 - RTD #4 Alarm Status 0 4 1 - F123 00654 RRTD 1 - RTD #5 Alarm Status 0 4 1 - F123 00655 RRTD 1 - RTD #6 Alarm Status 0 4 1 - F123 00656 RRTD 1 - RTD #7 Alarm Status 0 4 1 - F123 00657 RRTD 1 - RTD #8 Alarm Status 0 4 1 - F123 00658 RRTD 1 - RTD #9 Alarm Status 0 4 1 - F123 00659 RRTD 1 - RTD #10 Alarm Status 0 4 1 - F123 0
Table CG–10: MEMORY MAP (Sheet 10 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CG64 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP CGCOMMUNICATIONS GUIDE
065A RRTD 1 - RTD #11 Alarm Status 0 4 1 - F123 0065B RRTD 1 - RTD #12 Alarm Status 0 4 1 - F123 0
065C RRTD 1 - RTD #1 High Alarm Status 0 4 1 - F123 0
065D RRTD 1 - RTD #2 High Alarm Status 0 4 1 - F123 0
065E RRTD 1 - RTD #3 High Alarm Status 0 4 1 - F123 0
065F RRTD 1 - RTD #4 High Alarm Status 0 4 1 - F123 0
0660 RRTD 1 - RTD #5 High Alarm Status 0 4 1 - F123 0
0661 RRTD 1 - RTD #6 High Alarm Status 0 4 1 - F123 0
0662 RRTD 1 - RTD #7 High Alarm Status 0 4 1 - F123 0
0663 RRTD 1 - RTD #8 High Alarm Status 0 4 1 - F123 0
0664 RRTD 1 - RTD #9 High Alarm Status 0 4 1 - F123 0
0665 RRTD 1 - RTD #10 High Alarm Status 0 4 1 - F123 0
0666 RRTD 1 - RTD #11 High Alarm Status 0 4 1 - F123 0
0667 RRTD 1 - RTD #12 High Alarm Status 0 4 1 - F123 0
0668 RRTD 1 - Broken / Open RTD Alarm Status 0 4 1 - F123 0
0669 RRTD 1 - Short / Low Temp Alarm Status 0 1 1 - F123 0
066A RRTD 1 - Digital Input 6 Alarm Status 0 4 1 - F123 0
066B RRTD 1 - Digital Input 2 Alarm Status 0 4 1 - F123 0
066C RRTD 1 - Digital Input 5 Alarm Status 0 4 1 - F123 0
066D RRTD 1 - Digital Input 4 Alarm Status 0 4 1 - F123 0
066E RRTD 1 - Digital Input 1 Alarm Status 0 4 1 - F123 0
066F RRTD 1 - Digital Input 3 Alarm Status 0 4 1 - F123 0
RRTD 2 ALARM STATUS
0670 RRTD 2 - RTD #1 Alarm Status 0 4 1 - F123 00671 RRTD 2 - RTD #2 Alarm Status 0 4 1 - F123 00672 RRTD 2 - RTD #3 Alarm Status 0 4 1 - F123 00673 RRTD 2 - RTD #4 Alarm Status 0 4 1 - F123 00674 RRTD 2 - RTD #5 Alarm Status 0 4 1 - F123 00675 RRTD 2 - RTD #6 Alarm Status 0 4 1 - F123 00676 RRTD 2 - RTD #7 Alarm Status 0 4 1 - F123 00677 RRTD 2 - RTD #8 Alarm Status 0 4 1 - F123 00678 RRTD 2 - RTD #9 Alarm Status 0 4 1 - F123 00679 RRTD 2 - RTD #10 Alarm Status 0 4 1 - F123 0067A RRTD 2 - RTD #11 Alarm Status 0 4 1 - F123 0067B RRTD 2 - RTD #12 Alarm Status 0 4 1 - F123 0
Table CG–10: MEMORY MAP (Sheet 11 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CGCOMMUNICATIONS GUIDE MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG65
067C RRTD 2 - RTD #1 High Alarm Status 0 4 1 - F123 0
067D RRTD 2 - RTD #2 High Alarm Status 0 4 1 - F123 0
067E RRTD 2 - RTD #3 High Alarm Status 0 4 1 - F123 0
067F RRTD 2 - RTD #4 High Alarm Status 0 4 1 - F123 0
0680 RRTD 2 - RTD #5 High Alarm Status 0 4 1 - F123 0
0681 RRTD 2 - RTD #6 High Alarm Status 0 4 1 - F123 0
0682 RRTD 2 - RTD #7 High Alarm Status 0 4 1 - F123 0
0683 RRTD 2 - RTD #8 High Alarm Status 0 4 1 - F123 0
0684 RRTD 2 - RTD #9 High Alarm Status 0 4 1 - F123 0
0685 RRTD 2 - RTD #10 High Alarm Status 0 4 1 - F123 0
0686 RRTD 2 - RTD #11 High Alarm Status 0 4 1 - F123 0
0687 RRTD 2 - RTD #12 High Alarm Status 0 4 1 - F123 0
0688 RRTD 2 - Broken / Open RTD Alarm Status 0 4 1 - F123 0
0689 RRTD 2 - Short / Low Temp Alarm Status 0 1 1 - F123 0
068A RRTD 2 - Digital Input 6 Alarm Status 0 4 1 - F123 0
068B RRTD 2 - Digital Input 2 Alarm Status 0 4 1 - F123 0
068C RRTD 2 - Digital Input 5 Alarm Status 0 4 1 - F123 0
068D RRTD 2 - Digital Input 4 Alarm Status 0 4 1 - F123 0
068E RRTD 2 - Digital Input 1 Alarm Status 0 4 1 - F123 0
068F RRTD 2 - Digital Input 3 Alarm Status 0 4 1 - F123 0
RRTD 3 ALARM STATUS
0690 RRTD 3 - RTD #1 Alarm Status 0 4 1 - F123 00691 RRTD 3 - RTD #2 Alarm Status 0 4 1 - F123 00692 RRTD 3 - RTD #3 Alarm Status 0 4 1 - F123 00693 RRTD 3 - RTD #4 Alarm Status 0 4 1 - F123 00694 RRTD 3 - RTD #5 Alarm Status 0 4 1 - F123 00695 RRTD 3 - RTD #6 Alarm Status 0 4 1 - F123 00696 RRTD 3 - RTD #7 Alarm Status 0 4 1 - F123 00697 RRTD 3 - RTD #8 Alarm Status 0 4 1 - F123 00698 RRTD 3 - RTD #9 Alarm Status 0 4 1 - F123 00699 RRTD 3 - RTD #10 Alarm Status 0 4 1 - F123 0069A RRTD 3 - RTD #11 Alarm Status 0 4 1 - F123 0069B RRTD 3 - RTD #12 Alarm Status 0 4 1 - F123 0
069C RRTD 3 - RTD #1 High Alarm Status 0 4 1 - F123 0
Table CG–10: MEMORY MAP (Sheet 12 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CG66 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP CGCOMMUNICATIONS GUIDE
069D RRTD 3 - RTD #2 High Alarm Status 0 4 1 - F123 0
069E RRTD 3 - RTD #3 High Alarm Status 0 4 1 - F123 0
069F RRTD 3 - RTD #4 High Alarm Status 0 4 1 - F123 0
06A0 RRTD 3 - RTD #5 High Alarm Status 0 4 1 - F123 0
06A1 RRTD 3 - RTD #6 High Alarm Status 0 4 1 - F123 0
06A2 RRTD 3 - RTD #7 High Alarm Status 0 4 1 - F123 0
06A3 RRTD 3 - RTD #8 High Alarm Status 0 4 1 - F123 0
06A4 RRTD 3 - RTD #9 High Alarm Status 0 4 1 - F123 0
06A5 RRTD 3 - RTD #10 High Alarm Status 0 4 1 - F123 0
06A6 RRTD 3 - RTD #11 High Alarm Status 0 4 1 - F123 0
06A7 RRTD 3 - RTD #12 High Alarm Status 0 4 1 - F123 0
06A8 RRTD 3 - Broken / Open RTD Alarm Status 0 4 1 - F123 0
06A9 RRTD 3 - Short / Low Temp Alarm Status 0 1 1 - F123 0
06AA RRTD 3 - Digital Input 6 Alarm Status 0 4 1 - F123 0
06AB RRTD 3 - Digital Input 2 Alarm Status 0 4 1 - F123 0
06AC RRTD 3 - Digital Input 5 Alarm Status 0 4 1 - F123 0
06AD RRTD 3 - Digital Input 4 Alarm Status 0 4 1 - F123 0
06AE RRTD 3 - Digital Input 1 Alarm Status 0 4 1 - F123 0
06AF RRTD 3 - Digital Input 3 Alarm Status 0 4 1 - F123 0
RRTD 4 ALARM STATUS
06B0 RRTD 4 - RTD #1 Alarm Status 0 4 1 - F123 006B1 RRTD 4 - RTD #2 Alarm Status 0 4 1 - F123 006B2 RRTD 4 - RTD #3 Alarm Status 0 4 1 - F123 006B3 RRTD 4 - RTD #4 Alarm Status 0 4 1 - F123 006B4 RRTD 4 - RTD #5 Alarm Status 0 4 1 - F123 006B5 RRTD 4 - RTD #6 Alarm Status 0 4 1 - F123 006B6 RRTD 4 - RTD #7 Alarm Status 0 4 1 - F123 006B7 RRTD 4 - RTD #8 Alarm Status 0 4 1 - F123 006B8 RRTD 4 - RTD #9 Alarm Status 0 4 1 - F123 006B9 RRTD 4 - RTD #10 Alarm Status 0 4 1 - F123 006BA RRTD 4 - RTD #11 Alarm Status 0 4 1 - F123 006BB RRTD 4 - RTD #12 Alarm Status 0 4 1 - F123 0
06BC RRTD 4 - RTD #1 High Alarm Status 0 4 1 - F123 0
06BD RRTD 4 - RTD #2 High Alarm Status 0 4 1 - F123 0
Table CG–10: MEMORY MAP (Sheet 13 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CGCOMMUNICATIONS GUIDE MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG67
06BE RRTD 4 - RTD #3 High Alarm Status 0 4 1 - F123 0
06BF RRTD 4 - RTD #4 High Alarm Status 0 4 1 - F123 0
06C0 RRTD 4 - RTD #5 High Alarm Status 0 4 1 - F123 0
06C1 RRTD 4 - RTD #6 High Alarm Status 0 4 1 - F123 0
06C2 RRTD 4 - RTD #7 High Alarm Status 0 4 1 - F123 0
06C3 RRTD 4 - RTD #8 High Alarm Status 0 4 1 - F123 0
06C4 RRTD 4 - RTD #9 High Alarm Status 0 4 1 - F123 0
06C5 RRTD 4 - RTD #10 High Alarm Status 0 4 1 - F123 0
06C6 RRTD 4 - RTD #11 High Alarm Status 0 4 1 - F123 0
06C7 RRTD 4 - RTD #12 High Alarm Status 0 4 1 - F123 0
06C8 RRTD 4 - Broken / Open RTD Alarm Status 0 4 1 - F123 0
06C9 RRTD 4 - Short / Low Temp Alarm Status 0 1 1 - F123 0
06CA RRTD 4 - Digital Input 6 Alarm Status 0 4 1 - F123 0
06CB RRTD 4 - Digital Input 2 Alarm Status 0 4 1 - F123 0
06CC RRTD 4 - Digital Input 5 Alarm Status 0 4 1 - F123 0
06CD RRTD 4 - Digital Input 4 Alarm Status 0 4 1 - F123 0
06CE RRTD 4 - Digital Input 1 Alarm Status 0 4 1 - F123 0
06CF RRTD 4 - Digital Input 3 Alarm Status 0 4 1 - F123 0
RRTD 1 MAXIMUM TEMPERATURES
0700 RRTD 1 - RTD # 1 Max. Temperature -40 200 1 °C F4 40
0701 RRTD 1 - RTD # 2 Max. Temperature -40 200 1 °C F4 40
0702 RRTD 1 - RTD # 3 Max. Temperature -40 200 1 °C F4 40
0703 RRTD 1 - RTD # 4 Max. Temperature -40 200 1 °C F4 40
0704 RRTD 1 - RTD # 5 Max. Temperature -40 200 1 °C F4 40
0705 RRTD 1 - RTD # 6 Max. Temperature -40 200 1 °C F4 40
0706 RRTD 1 - RTD # 7 Max. Temperature -40 200 1 °C F4 40
0707 RRTD 1 - RTD # 8 Max. Temperature -40 200 1 °C F4 40
0708 RRTD 1 - RTD # 9 Max. Temperature -40 200 1 °C F4 40
0709 RRTD 1 - RTD # 10 Max. Temperature -40 200 1 °C F4 40
Table CG–10: MEMORY MAP (Sheet 14 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CG68 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP CGCOMMUNICATIONS GUIDE
070A RRTD 1 - RTD # 11 Max. Temperature -40 200 1 °C F4 40
070B RRTD 1 - RTD # 12 Max. Temperature -40 200 1 °C F4 40
... ReservedRRTD 2 MAXIMUM TEMPERATURES
0710 RRTD 2 - RTD # 1 Max. Temperature -40 200 1 °C F4 40
0711 RRTD 2 - RTD # 2 Max. Temperature -40 200 1 °C F4 40
0712 RRTD 2 - RTD # 3 Max. Temperature -40 200 1 °C F4 40
0713 RRTD 2 - RTD # 4 Max. Temperature -40 200 1 °C F4 40
0714 RRTD 2 - RTD # 5 Max. Temperature -40 200 1 °C F4 40
0715 RRTD 2 - RTD # 6 Max. Temperature -40 200 1 °C F4 40
0716 RRTD 2 - RTD # 7 Max. Temperature -40 200 1 °C F4 40
0717 RRTD 2 - RTD # 8 Max. Temperature -40 200 1 °C F4 40
0718 RRTD 2 - RTD # 9 Max. Temperature -40 200 1 °C F4 40
0719 RRTD 2 - RTD # 10 Max. Temperature -40 200 1 °C F4 40
071A RRTD 2 - RTD # 11 Max. Temperature -40 200 1 °C F4 40
071B RRTD 2 - RTD # 12 Max. Temperature -40 200 1 °C F4 40
... ReservedRRTD 3 MAXIMUM TEMPERATURES
0720 RRTD 3 - RTD # 1 Max. Temperature -40 200 1 °C F4 40
0721 RRTD 3 - RTD # 2 Max. Temperature -40 200 1 °C F4 40
0722 RRTD 3 - RTD # 3 Max. Temperature -40 200 1 °C F4 40
0723 RRTD 3 - RTD # 4 Max. Temperature -40 200 1 °C F4 40
0724 RRTD 3 - RTD # 5 Max. Temperature -40 200 1 °C F4 40
0725 RRTD 3 - RTD # 6 Max. Temperature -40 200 1 °C F4 40
0726 RRTD 3 - RTD # 7 Max. Temperature -40 200 1 °C F4 40
0727 RRTD 3 - RTD # 8 Max. Temperature -40 200 1 °C F4 40
0728 RRTD 3 - RTD # 9 Max. Temperature -40 200 1 °C F4 40
0729 RRTD 3 - RTD # 10 Max. Temperature -40 200 1 °C F4 40
072A RRTD 3 - RTD # 11 Max. Temperature -40 200 1 °C F4 40
072B RRTD 3 - RTD # 12 Max. Temperature -40 200 1 °C F4 40
... Reserved
Table CG–10: MEMORY MAP (Sheet 15 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CGCOMMUNICATIONS GUIDE MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG69
RRTD 4 MAXIMUM TEMPERATURES
0730 RRTD 4 - RTD # 1 Max. Temperature -40 200 1 °C F4 40
0731 RRTD 4 - RTD # 2 Max. Temperature -40 200 1 °C F4 40
0732 RRTD 4 - RTD # 3 Max. Temperature -40 200 1 °C F4 40
0733 RRTD 4 - RTD # 4 Max. Temperature -40 200 1 °C F4 40
0734 RRTD 4 - RTD # 5 Max. Temperature -40 200 1 °C F4 40
0735 RRTD 4 - RTD # 6 Max. Temperature -40 200 1 °C F4 40
0736 RRTD 4 - RTD # 7 Max. Temperature -40 200 1 °C F4 40
0737 RRTD 4 - RTD # 8 Max. Temperature -40 200 1 °C F4 40
0738 RRTD 4 - RTD # 9 Max. Temperature -40 200 1 °C F4 40
0739 RRTD 4 - RTD # 10 Max. Temperature -40 200 1 °C F4 40
073A RRTD 4 - RTD # 11 Max. Temperature -40 200 1 °C F4 40
073B RRTD 4 - RTD # 12 Max. Temperature -40 200 1 °C F4 40
... ReservedRRTD 1 TRIP COUNTER
0800 RRTD 1 - Stator RTD Trips 0 50000 1 - F1 00801 RRTD 1 - Bearing RTD Trips 0 50000 1 - F1 00802 RRTD 1 - Other RTD Trips 0 50000 1 - F1 00803 RRTD 1 - Ambient RTD Trips 0 50000 1 - F1 00804 RRTD 1 - Digital Input Trips 0 50000 1 - F1 0... Reserved
RRTD 2 TRIP COUNTER
0810 RRTD 2 - Stator RTD Trips 0 50000 1 - F1 00811 RRTD 2 - Bearing RTD Trips 0 50000 1 - F1 00812 RRTD 2 - Other RTD Trips 0 50000 1 - F1 00813 RRTD 2 - Ambient RTD Trips 0 50000 1 - F1 00814 RRTD 2 - Digital Input Trips 0 50000 1 - F1 0... Reserved
RRTD 3 TRIP COUNTER
0820 RRTD 3 - Stator RTD Trips 0 50000 1 - F1 00821 RRTD 3 - Bearing RTD Trips 0 50000 1 - F1 00822 RRTD 3 - Other RTD Trips 0 50000 1 - F1 00823 RRTD 3 - Ambient RTD Trips 0 50000 1 - F1 00824 RRTD 3 - Digital Input Trips 0 50000 1 - F1 0... Reserved
RRTD 4 TRIP COUNTER
0830 RRTD 4 - Stator RTD Trips 0 50000 1 - F1 00831 RRTD 4 - Bearing RTD Trips 0 50000 1 - F1 00832 RRTD 4 - Other RTD Trips 0 50000 1 - F1 00833 RRTD 4 - Ambient RTD Trips 0 50000 1 - F1 00834 RRTD 4 - Digital Input Trips 0 50000 1 - F1 0... Reserved
Table CG–10: MEMORY MAP (Sheet 16 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CG70 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP CGCOMMUNICATIONS GUIDE
RRTD 1 DIGITAL INPUT STATUS
0840 Digital Input 3 0 1 1 - F131 00841 Digital Input 4 0 1 1 - F131 00842 Digital Input 6 0 1 1 - F131 00843 Digital Input 5 0 1 1 - F131 00844 Digital Input 2 0 1 1 - F131 00845 Digital Input 1 0 1 1 - F131 0... Reserved
RRTD 2 DIGITAL INPUT STATUS
0850 Digital Input 3 0 1 1 - F131 00851 Digital Input 4 0 1 1 - F131 00852 Digital Input 6 0 1 1 - F131 00853 Digital Input 5 0 1 1 - F131 00854 Digital Input 2 0 1 1 - F131 00855 Digital Input 1 0 1 1 - F131 0... Reserved
RRTD 3 DIGITAL INPUT STATUS
0860 Digital Input 3 0 1 1 - F131 00861 Digital Input 4 0 1 1 - F131 00862 Digital Input 6 0 1 1 - F131 00863 Digital Input 5 0 1 1 - F131 00864 Digital Input 2 0 1 1 - F131 00865 Digital Input 1 0 1 1 - F131 0... Reserved
RRTD 4 DIGITAL INPUT STATUS
0870 Digital Input 3 0 1 1 - F131 00871 Digital Input 4 0 1 1 - F131 00872 Digital Input 6 0 1 1 - F131 00873 Digital Input 5 0 1 1 - F131 00874 Digital Input 2 0 1 1 - F131 00875 Digital Input 1 0 1 1 - F131 0... Reserved
RRTD 1 OUTPUT RELAY STATUS
0880 RRTD 1 - Trip 0 2 1 N/A F150 20881 RRTD 1 - Alarm 0 2 1 N/A F150 20882 RRTD 1 - Aux. 1 0 2 1 N/A F150 20883 RRTD 1 - Aux. 2 0 2 1 N/A F150 2
RRTD 1 DIGITAL INPUT AND OUTPUT RELAY STATUS
0884 RRTD1 Digital Input & Output Relay Status N/A N/A N/A N/A F193 0
... ReservedRRTD 2 OUTPUT RELAY STATUS
0890 RRTD 2 - Trip 0 2 1 N/A F150 20891 RRTD 2 - Alarm 0 2 1 N/A F150 20892 RRTD 2 - Aux. 1 0 2 1 N/A F150 20893 RRTD 2 - Aux. 2 0 2 1 N/A F150 2
RRTD 2 DIGITAL INPUT AND OUTPUT RELAY STATUS
0894 RRTD2 Digital Input & Output Relay Status N/A N/A N/A N/A F193 0
... ReservedRRTD 3 OUTPUT RELAY STATUS
08A0 RRTD 3 - Trip 0 2 1 N/A F150 2
Table CG–10: MEMORY MAP (Sheet 17 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CGCOMMUNICATIONS GUIDE MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG71
08A1 RRTD 3 - Alarm 0 2 1 N/A F150 208A2 RRTD 3 - Aux. 1 0 2 1 N/A F150 208A3 RRTD 3 - Aux. 2 0 2 1 N/A F150 2
RRTD 3 DIGITAL INPUT AND OUTPUT RELAY STATUS
08A4 RRTD3 Digital Input & Output Relay Status N/A N/A N/A N/A F193 0
... ReservedRRTD 4 OUTPUT RELAY STATUS
08B0 RRTD 4 - Trip 0 2 1 N/A F150 208B1 RRTD 4 - Alarm 0 2 1 N/A F150 208B2 RRTD 4 - Aux. 1 0 2 1 N/A F150 208B3 RRTD 4 - Aux. 2 0 2 1 N/A F150 2
RRTD 4 DIGITAL INPUT AND OUTPUT RELAY STATUS
08B4 RRTD4 Digital Input & Output Relay Status N/A N/A N/A N/A F193 0
... ReservedCOMMUNICATIONS MODULE
08C0 Ethernet Module Status 0 65535 1 N/A F164 -
08C1 Fieldbus Module Software Revision - - - - F16 -
... ReservedPROTECTION FUNCTION BLOCKING
08D0 Protection Functions Currently Blocked 0 256 1 N/A F180 0
... ReservedSETPOINTS (ADDRESSES 1000 TO 1FFF)
DISPLAY PREFERENCES
1000 Default Message Cycle Time 5 100 1 s F1 201001 Default Message Timeout 10 900 1 s F1 3001002 Reserved1003 Flash Message 1 10 1 s F1 21004 Temperature Display Units 0 1 1 - F100 01005 Energy Unit Display 0 1 1 - F166 0... Reserved
EVENT RECORDS
1006 Motor Running Events 0 1 1 - F103 01007 Motor Stopped Events 0 1 1 - F103 0
WAVEFORM CAPTURE
1008 Trigger Position 0 100 1 % F1 20... Reserved
369 COMMUNICATIONS
100F Reset Fieldbus Comms Interface 0 1 1 - F103 01010 Slave Address 1 254 1 - F1 2541011 Computer RS232 Baud Rate 0 4 1 - F101 41012 Computer RS232 Parity 0 2 1 - F102 01013 Channel 1 Parity 0 2 1 - F102 01014 Channel 1 Baud Rate 0 4 1 - F101 41015 Channel 2 Parity 0 2 1 - F102 01016 Channel 2 Baud Rate 0 4 1 - F101 41017 Channel 3 Parity 0 2 1 - F102 01018 Channel 3 Baud Rate 0 4 1 - F101 41019 Channel 3 Connection 0 1 1 - F151 0
Table CG–10: MEMORY MAP (Sheet 18 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CG72 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP CGCOMMUNICATIONS GUIDE
101A Channel 3 Application 0 1 1 - F149 0101B Profibus Slave Address 1 126 1 - F1 125101C IP Address Octet 1 0 255 1 - F1 127101D IP Address Octet 2 0 255 1 - F1 0101E IP Address Octet 3 0 255 1 - F1 0101F IP Address Octet 4 0 255 1 - F1 11020 Subnet Mask Octet 1 0 255 1 - F1 2551021 Subnet Mask Octet 2 0 255 1 - F1 2551022 Subnet Mask Octet 3 0 255 1 - F1 2551023 Subnet Mask Octet 4 0 255 1 - F1 01024 Gateway Address Octet 1 0 255 1 - F1 1271025 Gateway Address Octet 2 0 255 1 - F1 01026 Gateway Address Octet 3 0 255 1 - F1 01027 Gateway Address Octet 4 0 255 1 - F1 11028 DeviceNet MAC ID 0 63 1 - F1 631029 DeviceNet Baud Rate 0 2 1 - F170 0... Reserved
REAL TIME CLOCK
1030 Date (2 words) valid date N/A - F18 -1034 Time (2 words) valid time N/A - F19 -... Reserved
DEFAULT MESSAGES
1041 Default to Current Metering 0 1 1 - F103 01042 Default to Motor Load 0 1 1 - F103 0
1043 Default to Delta Voltage Metering 0 1 1 - F103 0
1044 Default to Power Factor 0 1 1 - F103 01045 Default to Positive Watthours 0 1 1 - F103 01046 Default to Real Power 0 1 1 - F103 01047 Default to Reactive Power 0 1 1 - F103 01048 Default to Hottest Stator RTD 0 1 1 - F103 01049 Default to Text Message 1 0 1 1 - F103 0104A Default to Text Message 2 0 1 1 - F103 0104B Default to Text Message 3 0 1 1 - F103 0104C Default to Text Message 4 0 1 1 - F103 0104D Default to Text Message 5 0 1 1 - F103 0
104E Default to Hottest Stator RTD Temperature 0 1 1 - F103 0
104F Default to Unbalace Biased Motor Load 0 1 1 - F103 0
... Reserved - - - - - -MESSAGE SCRATCHPAD
1060 1st & 2nd Character of 1st Scratchpad Message 32 127 1 - F1 ’T’
↓ ↓
1073 39th & 40th Character of 1st Scratchpad Message 32 127 1 - F1 " "
1074 1st & 2nd Character of 2nd Scratchpad Message 32 127 1 - F1 ’T’
↓ ↓
1087 39th & 40th Character of 2nd Scratchpad Message 32 127 1 - F1 " "
Table CG–10: MEMORY MAP (Sheet 19 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CGCOMMUNICATIONS GUIDE MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG73
1088 1st & 2nd Character of 3rd Scratchpad Message 32 127 1 - F1 ’T’
↓ ↓
109B 39th & 40th Character of 3rd Scratchpad Message 32 127 1 - F1 " "
109C 1st & 2nd Character of 4th Scratchpad Message 32 127 1 - F1 ’T’
↓ ↓
10AF 39th & 40th Character of 4th Scratchpad Message 32 127 1 - F1 " "
10B0 1st & 2nd Character of 5th Scratchpad Message 32 127 1 - F1 ’T’
↓ ↓
10C3 39th & 40th Character of 5th Scratchpad Message 32 127 1 - F1 " "
... ReservedCLEAR PRESET DATA
1130 Clear Last Trip Data 0 1 1 - F103 01131 Clear Peak Demand Data 0 1 1 - F103 01132 Clear RTD Maximums 0 1 1 - F103 01133 Preset Positive MWh 0 65535 1 MWh F1 01134 Clear Trip Counters 0 1 1 - F103 01135 Preset Digital Counter 0 65535 1 - F1 01136 Clear Event Records 0 1 1 - F103 01137 Preset Positive Mvarh 0 65535 1 Mvarh F1 01138 Preset Negative Mvarh 0 65535 1 Mvarh F1 01139 Preset Number Of Motor Starts 0 50000 1 - F1 0
113A Preset Number Of Emergency Restarts 0 50000 1 - F1 0
113B Preset Motor Running Hours 0 65535 1 - F1 0
113C Preset Autorestart Start Attempts 0 50000 1 - F1 0
... Reserved1140 Clear Motor Data 0 1 1 - F103 01141 Reserved - - - - - -1142 Clear All Data 0 1 1 - F103 01143 RRTD 1 - Preset Digital Counter 0 65535 1 - F1 01144 RRTD 2 - Preset Digital Counter 0 65535 1 - F1 01145 RRTD 3 - Preset Digital Counter 0 65535 1 - F1 01146 RRTD 4 - Preset Digital Counter 0 65535 1 - F1 01147 Clear Energy Data 0 1 1 - F103 0... Reserved
CT/VT SETUP
1180 Phase CT Primary 1 5000 1 A F1 5001181 Motor Full Load Amps 1 5000 1 A F1 101182 Ground CT Type 0 3 1 - F104 21183 Ground CT Primary 1 5000 1 A F1 100... Reserved
1190 Enable Two Speed Motor Protection 0 1 1 N/A F103 0
1191 Speed 2 Phase CT Primary 1 5000 1 A F1 50001192 Speed 2 Motor Full Load Amps 1 5000 1 A F1 10
Table CG–10: MEMORY MAP (Sheet 20 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CG74 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP CGCOMMUNICATIONS GUIDE
... Reserved
11A0 Voltage Transformer Connection Type 0 2 1 - F106 0
11A1 Voltage Transformer Ratio 100 24000 1 - F3 3511A2 Motor Rated Voltage 100 20000 1 V F1 4160... Reserved11C0 Nominal Frequency 0 2 1 - F107 011C1 System Phase Sequence 0 1 1 - F124 0
11C2 Speed 2 System Phase Sequence 0 1 1 - F124 0
... ReservedSERIAL COMM CONTROL
11C8 Serial Communication Control 0 1 1 - F103 011C9 Assign Start Control Relays 0 7 1 - F113 2... Reserved
REDUCED VOLTAGE
11CF Start Control Relay Timer 10 100 5 s F2 1011D0 Reduced Voltage Starting 0 1 1 - F103 011D1 Assign Start Control Relays 0 7 1 - F113 411D2 Transition On 0 2 1 - F108 0
11D3 Incomplete Sequence Trip Relays 0 6 1 - F111 0
11D4 Reduced Voltage Start Level 25 300 1 % FLA F1 10011D5 Reduced Voltage Start Timer 1 500 1 s F1 200
AUTORESTART
11D6 Autorestart 0 1 1 - F103 011D7 Total Restarts 0 65000 1 starts F1 111D8 Restart Delay 0 20000 1 sec. F1 6011D9 Progressive Delay 0 20000 1 sec. F1 011DA Hold Delay 0 20000 1 sec. F1 011DB Bus Valid 0 1 1 - F103 011DC Bus Valid Level 15 100 1 %VT F1 10011DD Reserved - - - - - -11DE Autorestart Attempt Events 0 1 1 - F103 011DF Autorestart Success Events 0 1 1 - F103 011E0 Autorestart Aborted Events 0 1 1 - F103 0... Reserved
UNDERVOLTAGE AUTORESTART
11F0 Enable UVR 0 1 1 - F30 0 (Off)11F1 UVR Pickup Level 50 100 1 x RATED F3 6511F2 UVR Assign Trip Relays 0 7 1 - F111 011F3 UVR Trip Delay 0 2550 1 x 0.1s F2 011F4 UVR Restoration Level 50 100 1 x RATED F3 90
11F5 Immediate Restart Power Loss Time 0 500 100 ms F1 0 (Off)
11F6 Delay1 Restart Power Loss Time 0 100 1 x 0.1s F2 0 (Off)
11F7 Delay2 Restart Power Loss Time 0 3601 1 sF1 (3601=Unlimited)
0 (Off)
11F8 Delay1 Restart Time Delay 0 12000 2 x 0.1s F2 2011F9 Delay2 Restart Time Delay 0 12000 2 x 0.1s F2 10011FA UVR Setup Time 0 12000 1 x 0.1s F2 100
Table CG–10: MEMORY MAP (Sheet 21 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CGCOMMUNICATIONS GUIDE MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG75
DIGITAL COUNTER
12E6 First Character of Counter Name 32 127 1 - F1 “G”
12F2 First Character of Counter Unit Name 32 127 1 - F1 ‘U’
12F8 Counter Type 0 1 1 - F114 012F9 Digital Counter Alarm 0 2 1 - F115 012FA Assign Alarm Relays 0 6 1 - F113 012FB Counter Alarm Level 0 65535 1 - F1 10012FD Reserved - - - - - -12FE Record Alarms as Events 0 1 1 - F103 0
EMERGENCY
1330 1st & 2nd Character of Emergency Switch Name 32 127 1 - F22 ’G’
1340 General Emergency Switch Type 0 1 1 - F116 0
1341 General Emergency Switch Block Input From Start 0 5000 1 s F1 0
1342 General Emergency Switch Alarm 0 2 1 - F115 0
1343 General Emergency Switch Alarm Relays 0 6 1 - F113 0
1344 General Emergency Switch Alarm Delay 1 50000 1 100ms F2 50
1345 General Emergency Switch Alarm Events 0 1 1 - F103 0
1346 General Emergency Switch Trip 0 2 1 - F115 0
1347 General Emergency Switch Trip Relays 0 6 1 - F111 0
1348 General Emergency Switch Trip Delay 1 50000 1 100ms F2 50
1349 Emergency Switch Assignable Function 0 7 1 - F110 0
... ReservedDIFFERENTIAL
1370 1st & 2nd Character of Differential Switch Name 32 127 1 - F22 ’G’
1380 General Differential Switch Type 0 1 1 - F116 0
1381 General Differential Switch Block Input From Start 0 5000 1 s F1 0
1382 General Differential Switch Alarm 0 2 1 - F115 0
1383 General Differential Switch Alarm Relays 0 7 1 - F113 1
1384 General Differential Switch Alarm Delay 1 50000 1 100ms F2 50
1385 General Differential Switch Alarm Events 0 1 1 - F103 0
1386 General Differential Switch Trip 0 2 1 - F115 0
1387 General Differential Switch Trip Relays 0 7 1 - F111 1
1388 General Differential Switch Trip Delay 1 50000 1 100ms F2 50
1389 Differential Switch Assignable Function 0 7 1 - F157 0
138A Assign Differential Switch Trip Relays 0 7 1 - F111 1
... Reserved
Table CG–10: MEMORY MAP (Sheet 22 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CG76 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP CGCOMMUNICATIONS GUIDE
SPEED
13A0 1st & 2nd Character of Speed Switch Name 32 127 1 - F22 ’G’
13B0 General Speed Switch Type 0 1 1 - F116 0
13B1 General Speed Switch Block Input from Start 0 5000 1 s F1 0
13B2 General Speed Switch Alarm 0 2 1 - F115 0
13B3 General Speed Switch Alarm Relays 0 7 1 - F113 1
13B4 General Speed Switch Alarm Delay 1 50000 1 100ms F2 50
13B5 General Speed Switch Alarm Events 0 1 1 - F103 0
13B6 General Speed Switch Trip 0 2 1 - F115 0
13B7 General Speed Switch Trip Relays 0 7 1 - F111 1
13B8 General Speed Switch Trip Delay 1 50000 1 100ms F2 50
13B9 Speed Switch Assignable Function 0 7 1 - F158 0
13BA Speed Switch Delay 5 1000 5 100ms F2 2013BB Assign Speed Switch Trip Relays 0 7 1 - F111 1... Reserved
RESET
13D0 1st & 2nd Character of Reset Switch Name 32 127 1 - F22 ’G’
13E0 General Reset Switch Type 0 1 1 - F116 0
13E1 General Reset Switch Block Input From Start 0 5000 1 s F1 0
13E2 General Reset Switch Alarm 0 2 1 - F115 0
13E3 General Reset Switch Alarm Relays 0 7 1 - F113 1
13E4 General Reset Switch Alarm Delay 1 50000 1 100ms F2 50
13E5 General Reset Switch Alarm Events 0 1 1 - F103 0
13E6 General Reset Switch Trip 0 2 1 - F115 013E7 General Reset Switch Trip Relays 0 7 1 - F111 113E8 General Reset Switch Trip Delay 1 50000 1 100ms F2 50
13E9 Reset Switch Assignable Function 0 7 1 - F160 0
... ReservedSPARE
1400 1st & 2nd Character of Spare Switch Name 32 127 1 - F22 ’G’
1410 General Spare Switch Type 0 1 1 - F116 0
1411 General Spare Switch Block Input From Start 0 5000 1 s F1 0
1412 General Spare Switch Alarm 0 2 1 - F115 0
1413 General Spare Switch Alarm Relays 0 7 1 - F113 1
1414 General Spare Switch Alarm Delay 1 50000 1 100ms F2 50
1415 General Spare Switch Alarm Events 0 1 1 - F103 0
1416 General Spare Switch Trip 0 1 1 - F115 0
Table CG–10: MEMORY MAP (Sheet 23 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CGCOMMUNICATIONS GUIDE MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG77
1417 General Spare Switch Trip Relays 0 7 1 - F111 11418 General Spare Switch Trip Delay 1 50000 1 100 ms F2 50
1419 Spare Switch Assignable Function 0 7 1 - F159 0
141A Starter Aux Contact Type 0 1 1 - F109 0
141B Starter Operation Monitor Delay Time 0 60 1 seconds F1 0 (Off)
141C Starter Operation Monitor Type 0 2 1 - F115 0 (Off)141D Starter Operation Monitor Relays 0 15 1 - F169 0 (None)... Reserved
OUTPUT RELAY SETUP
1500 Trip Relay Reset Mode 0 2 1 - F117 01501 Alarm Relay Reset Mode 0 2 1 - F117 01502 Aux 1 Relay Reset Mode 0 2 1 - F117 01503 Aux 2 Relay Reset Mode 0 2 1 - F117 01504 Trip Relay Operation 0 1 1 - F161 01505 Alarm Relay Operation 0 1 1 - F161 11506 Aux1 Relay Operation 0 1 1 - F161 11507 Aux2 Relay Operation 0 1 1 - F161 0... Reserved
FORCE OUTPUT RELAYS
1510 Assign Communications Force Relays 0 15 1 N/A F169 0
1511 Trip Communications Force Relay Output Type 0 1 1 - F181 0
1512 Trip Pulsed Output Dwell Time 5 50000 1 100 ms F2 5
1513 Alarm Communications Force Relay Output Type 0 1 1 - F181 0
1514 Alarm Pulsed Output Dwell Time 5 50000 1 100 ms F2 5
1515 Aux1 Communications Force Relay Output Type 0 1 1 - F181 0
1516 Aux1 Pulsed Output Dwell Time 5 50000 1 100 ms F2 5
1517 Aux2 Communications Force Relay Output Type 0 1 1 - F181 0
1518 Aux2 Pulsed Output Dwell Time 5 50000 1 100 ms F2 5... Reserved
PROTECTION FUNCTION BLOCKING
1520 Log Blocking Events 0 1 1 N/A F30 01521 Block Undercurrent/Underpower 0 1 1 N/A F30 01522 Block Current Unbalance 0 1 1 N/A F30 01523 Block Incomplete Sequence 0 1 1 N/A F30 01524 Block Thermal Model 0 1 1 N/A F30 01525 Block Short Circuit and Backup 0 1 1 N/A F30 01526 Block Overload Alarm 0 1 1 N/A F30 01527 Block Ground Fault 0 1 1 N/A F30 0
1528 Block Starts Per Hour and Time Between Starts 0 1 1 N/A F30 0
... ReservedTHERMAL MODEL (0 = Off)
1581 Overload Pickup Level 101 125 1 0.01xFLA F3 101
1582 Assign Thermal Capacity Trip Relay 0 7 1 - F111 1
Table CG–10: MEMORY MAP (Sheet 24 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CG78 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP CGCOMMUNICATIONS GUIDE
1583 Unbalance k Factor (0=Learned) 0 29 1 - F1 01584 Running Cool Time Constant 1 500 1 min F1 151585 Stopped Cool Time Constant 1 500 1 min F1 301586 Hot/Cold Safe Stall Ratio 1 100 1 - F3 1001587 RTD Biasing 0 1 1 - F103 01588 RTD Bias Minimum 0 198 1 °C F1 401589 RTD Bias Mid Point 0 199 1 °C F1 120158A RTD Bias Maximum 0 200 1 °C F1 155158B Thermal Capacity Alarm 0 2 1 - F115 0
158C Assign Thermal Capacity Alarm Relays 0 7 1 - F113 1
158D Thermal Capacity Alarm Level 1 100 1 % used F1 75158E Thermal Capacity Alarm Events 0 1 1 - F103 0158F Enable Learned Cool Time 0 1 1 - F103 01590 Enable Unbalance Biasing 0 1 1 - F103 01591 Motor Load Averaging Interval 3 60 3 cycles F1 3... Reserved15AE Select Curve Style 0 1 1 - F128 0
O/L CURVE SETUP
15AF Standard Overload Curve Number 1 15 1 - F1 4
15B0 Time to Trip at 1.01 x FLA 0 65534 1 s F1 1741515B2 Time to Trip at 1.05 x FLA 0 65534 1 s F1 341515B4 Time to Trip at 1.10 x FLA 0 65534 1 s F1 166715B6 Time to Trip at 1.20 x FLA 0 65534 1 s F1 79515B8 Time to Trip at 1.30 x FLA 0 65534 1 s F1 50715BA Time to Trip at 1.40 x FLA 0 65534 1 s F1 36515BC Time to Trip at 1.50 x FLA 0 65534 1 s F1 28015BE Time to Trip at 1.75 x FLA 0 65534 1 s F1 17015C0 Time to Trip at 2.00 x FLA 0 65534 1 s F1 11715C2 Time to Trip at 2.25 x FLA 0 65534 1 s F1 8615C4 Time to Trip at 2.50 x FLA 0 65534 1 s F1 6715C6 Time to Trip at 2.75 x FLA 0 65534 1 s F1 5315C8 Time to Trip at 3.00 x FLA 0 65534 1 s F1 4415CA Time to Trip at 3.25 x FLA 0 65534 1 s F1 3715CC Time to Trip at 3.50 x FLA 0 65534 1 s F1 3115CE Time to Trip at 3.75 x FLA 0 65534 1 s F1 2715D0 Time to Trip at 4.00 x FLA 0 65534 1 s F1 2315D2 Time to Trip at 4.25 x FLA 0 65534 1 s F1 2115D4 Time to Trip at 4.50 x FLA 0 65534 1 s F1 1815D6 Time to Trip at 4.75 x FLA 0 65534 1 s F1 1615D8 Time to Trip at 5.00 x FLA 0 65534 1 s F1 1515DA Time to Trip at 5.50 x FLA 0 65534 1 s F1 1215DC Time to Trip at 6.00 x FLA 0 65534 1 s F1 1015DE Time to Trip at 6.50 x FLA 0 65534 1 s F1 915E0 Time to Trip at 7.00 x FLA 0 65534 1 s F1 715E2 Time to Trip at 7.50 x FLA 0 65534 1 s F1 615E4 Time to Trip at 8.00 x FLA 0 65534 1 s F1 615E6 Time to Trip at 10.0 x FLA 0 65534 1 s F1 615E8 Time to Trip at 15.0 x FLA 0 65534 1 s F1 6
Table CG–10: MEMORY MAP (Sheet 25 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CGCOMMUNICATIONS GUIDE MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG79
15EA Time to Trip at 20.0 x FLA 0 65534 1 s F1 6... Reserved
SHORT CIRCUIT TRIP (0 = INSTANTANEOUS TIME DELAY)
1640 Short Circuit Trip 0 1 1 - F115 01641 Reserved1642 Assign Short Circuit Trip Relays 0 7 1 - F111 11643 Short Circuit Trip Level 20 200 1 × CT F2 1001644 Short Circuit Trip Delay 0 255.00 0.01 s F3 01645 Short Circuit Trip Backup 0 2 1 - F115 0
1646 Assign Short Circuit Backup Relays 0 3 1 - F119 1
1647 Add Short Circuit Trip Backup Delay 0 25500 0.01 s F3 20
... ReservedOVERLOAD ALARM
1650 Overload Alarm 0 2 1 - F115 0
1651 Overload Alarm Level 101 150 1 0.01 × FLA F3 101
1652 Assign Overload Alarm Relays 0 7 1 - F113 11653 Overload Alarm Delay 0 600 1 s F2 101654 Overload Alarm Events 0 1 1 - F103 0... Reserved
MECHANICAL JAM
1660 Mechanical Jam Alarm 0 2 1 - F115 01661 Assign Alarm Relays 0 7 1 - F113 1
1662 Mechanical Jam Alarm Level 101 600 1 0.01 × FLA F3 150
1663 Mechanical Jam Alarm Delay 5 1250 5 s F2 101664 Mechanical Jam Alarm Events 0 1 1 - F103 01665 Mechanical Jam Trip 0 2 1 - F115 01666 Assign Trip Relays 0 7 1 - F111 1
1667 Mechanical Jam Trip Level 101 600 1 0.01 × FLA F3 150
1668 Mechanical Jam Trip Delay 5 1250 5 s F2 10... Reserved - - - - - -
UNDERCURRENT
1670 Block Undercurrent from Start 0 15000 1 s F1 01671 Undercurrent Alarm 0 2 1 - F115 0
1672 Assign Undercurrent Alarm Relays 0 7 1 - F113 1
1673 Undercurrent Alarm Level 10 99 1 0.01 × FLA F3 70
1674 Undercurrent Alarm Delay 1 255 1 s F1 11675 Undercurrent Alarm Events 0 1 1 - F103 01676 Undercurrent Trip 0 2 1 - F115 01677 Assign Undercurrent Trip Relays 0 7 1 - F111 1
1678 Undercurrent Trip Level 10 99 1 0.01 × FLA F3 70
1679 Undercurrent Trip Delay 1 255 1 s F1 1... Reserved
CURRENT UNBALANCE
1680 Block Unbalance From Start 0 5000 1 s F1 01681 Current Unbalance Alarm 0 2 1 - F115 0
Table CG–10: MEMORY MAP (Sheet 26 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CG80 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP CGCOMMUNICATIONS GUIDE
1682 Assign Unbalance Alarm Relays 0 7 1 - F113 11683 Unbalance Alarm Level 4 30 1 % F1 151684 Unbalance Alarm Delay 1 255 1 s F1 11685 Unbalance Alarm Events 0 1 1 - F103 01686 Current Unbalance Trip 0 2 1 - F115 01687 Assign Unbalance Trip Relays 0 7 1 - F111 11688 Unbalance Trip Level 4 30 1 % F1 201689 Unbalance Trip Delay 1 255 1 s F1 1... Reserved
GROUND FAULT
16A1 Ground Fault Alarm 0 2 1 - F115 0
16A2 Assign Ground Fault Alarm Relays 0 7 1 - F113 1
16A3 Ground Fault Alarm Pickup 10 100 1 0.1 × CT F3 10
16A4 GF Alarm Pickup for GE Multilin 50:0.025 CT 25 2500 1 Amps F3 25
16A5 Ground Fault Alarm Delay 0 255.00 0.01 s F3 016A6 Ground Fault Alarm Events 0 1 1 - F103 016A7 Ground Fault Trip 0 2 1 - F 115 016A8 Assign Ground Fault Trip Relays 0 7 1 - F 111 116A9 Ground Fault Trip Pickup 10 100 1 0.1 × CT F3 20
16AA GF Trip Pickup for GE Multilin 50:0.025 CT 25 2500 1 0.1 × CT F3 25
16AB Ground Fault Trip Delay 0 255.00 0.01 s F3 016AC Ground Fault Trip Backup 0 1 1 - F115 016AD Ground Fault Trip Backup Relays 0 3 1 - F119 3316AE Ground Fault Trip Backup Delay 0.10 255.00 0.01 s F3 0.20... Reserved
ACCELERATION TRIP
16D0 Acceleration Trip 0 1 1 - F115 016D1 Assign Trip Relays 0 7 1 - F111 116D2 Acceleration Timer From Start 10 2500 1 1s F1 100... Reserved - - - - - -16E0 Enable Single Shot Restart 0 1 1 - F103 016E1 Enable Start Inhibit 0 1 1 - F103 0
16E2 Maximum Starts/Hour Permissible 0 5 1 - F1 0
16E3 Time Between Starts 0 500 1 min F1 1016E4 Restart Block 0 50000 1 s F1 016E5 Assign Block Relays 0 7 1 - F111 3... Reserved
BACKSPIN DETECTION
1780 Enable Back-Spin Start Inhibit 0 1 1 - F103 01781 Minimum Permissible Frequency 0 999 1 Hz F3 100... Reserved1784 Enable Prediction Algorithm 0 1 1 - F103 11785 Assign Backspin Inhibit Relays 0 7 1 - F111 11786 Number of Motor Poles 2 16 2 - F1 2... Reserved
LOCAL RTD #1
1790 Local RTD #1 Application 0 4 1 - F121 0
Table CG–10: MEMORY MAP (Sheet 27 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CGCOMMUNICATIONS GUIDE MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG81
1791 Local RTD #1 High Alarm 0 2 1 - F115 01792 Local RTD #1 High Alarm Relays 0 7 1 - F113 21793 Local RTD #1 High Alarm Level 1 200 1 °C F1 1301794 Local RTD #1 Alarm 0 2 1 - F115 01795 Local RTD #1 Alarm Relays 0 7 1 - F113 11796 Local RTD #1 Alarm Level 1 200 1 °C F1 1301797 Record RTD #1 Alarms as Events 0 1 1 - F103 01798 Local RTD #1 Trip 0 2 1 - F115 01799 Enable RTD #1 Trip Voting 0 13 1 - F122 1179A Local RTD #1 Trip Relays 0 7 1 - F111 1179B Local RTD #1 Trip Level 1 200 1 °C F1 130179C Local RTD #1 RTD Type 0 3 1 - F120 0
17A0 First Character of Local RTD #1 Name 32 127 1 - F1 ’R’
↓ ↓ - - - - - -
17A3 8th Character of Local RTD #1 Name 32 127 1 - F1 " "
... ReservedLOCAL RTD #2
17B0 Local RTD #2 Application 0 4 1 - F121 017B1 Local RTD #2 High Alarm 0 2 1 - F115 017B2 Local RTD #2 High Alarm Relays 0 7 1 - F113 217B3 Local RTD #2 High Alarm Level 1 200 1 °C F1 13017B4 Local RTD #2 Alarm 0 2 1 - F115 017B5 Local RTD #2 Alarm Relays 0 7 1 - F113 117B6 Local RTD #2 Alarm Level 1 200 1 °C F1 13017B7 Record RTD #2 Alarms as Events 0 1 1 - F103 017B8 Local RTD #2 Trip 0 2 1 - F 115 017B9 Enable RTD #2 Trip Voting 0 13 1 - F122 117BA Local RTD #2 Trip Relays 0 7 1 - F111 117BB Local RTD #2 Trip Level 1 200 1 °C F1 13017BC Local RTD #2 RTD Type 0 3 1 - F120 0
17C0 First Character of Local RTD #2 Name 32 127 1 - F1 ’R’
↓ ↓
17C3 8th Character of Local RTD #2 Name 32 127 1 - F1 " "
... ReservedLOCAL RTD #3
17D0 Local RTD #3 Application 0 4 1 - F121 017D1 Local RTD #3 High Alarm 0 2 1 - F115 017D2 Local RTD #3 High Alarm Relays 0 7 1 - F113 217D3 Local RTD #3 High Alarm Level 1 200 1 °C F1 13017D4 Local RTD #3 Alarm 0 2 1 - F115 017D5 Local RTD #3 Alarm Relays 0 7 1 - F113 117D6 Local RTD #3 Alarm Level 1 200 1 °C F1 13017D7 Record RTD #3 Alarms as Events 0 1 1 - F103 017D8 Local RTD #3 Trip 0 2 1 - F115 017D9 Enable RTD #3 Trip Voting 0 13 1 - F122 117DA Local RTD #3 Trip Relays 0 7 1 - F111 117DB Local RTD #3 Trip Level 1 200 1 °C F1 130
Table CG–10: MEMORY MAP (Sheet 28 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CG82 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP CGCOMMUNICATIONS GUIDE
17DC Local RTD #3 RTD Type 0 3 1 - F120 0
17E0 First Character of Local RTD #3 Name 32 127 1 - F1 ’R’
↓ ↓
17E3 8th Character of Local RTD #3 Name 32 127 1 - F1 " "
... ReservedLOCAL RTD #4
17F0 Local RTD #4 Application 0 4 1 - F121 017F1 Local RTD #4 High Alarm 0 2 1 - F115 017F2 Local RTD #4 High Alarm Relays 0 7 1 - F113 217F3 Local RTD #4 High Alarm Level 1 200 1 °C F1 13017F4 Local RTD #4 Alarm 0 2 1 - F115 017F5 Local RTD #4 Alarm Relays 0 7 1 - F113 117F6 Local RTD #4 Alarm Level 1 200 1 °C F1 13017F7 Enable RTD #4 Alarms as Events 0 1 1 - F103 017F8 Local RTD #4 Trip 0 2 1 - F115 017F9 Enable RTD #4 Trip Voting 0 13 1 - F122 117FA Local RTD #4 Trip Relays 0 7 1 - F111 117FB Local RTD #4 Trip Level 1 200 1 °C F1 13017FC Local RTD #4 RTD Type 0 3 1 - F120 0
1800 First Character of Local RTD #4 Name 32 127 1 - F1 ’R’
↓ ↓
1803 8th Character of Local RTD #4 Name 32 127 1 - F1 " "
... ReservedLOCAL RTD #5
1810 Local RTD #5 Application 0 4 1 - F121 01811 Local RTD #5 High Alarm 0 2 1 - F115 01812 Local RTD #5 High Alarm Relays 0 7 1 - F113 11813 Local RTD #5 High Alarm Level 1 250 1 °C / °F F1 1301814 Local RTD #5 Alarm 0 2 1 - F115 01815 Local RTD #5 Alarm Relays 0 7 1 - F113 11816 Local RTD #5 Alarm Level 1 200 1 °C F1 1301817 Record RTD #5 Alarms as Events 0 1 1 - F103 01818 Local RTD #5 Trip 0 2 1 - F115 01819 Enable RTD #5 Trip Voting 0 13 1 - F122 1181A Local RTD #5 Trip Relays 0 7 1 - F111 1181B Local RTD #5 Trip Level 1 200 1 °C F1 130181C Local RTD #5 RTD Type 0 3 1 - F120 0
1820 First Character of Local RTD #5 Name 32 127 1 - F1 ’R’
↓ ↓
1823 8th Character of Local RTD #5 Name 32 127 1 - F1 " "
... ReservedLOCAL RTD #6
1830 Local RTD #6 Application 0 4 1 - F121 01831 Local RTD #6 High Alarm 0 2 1 - F115 01832 Local RTD #6 High Alarm Relays 0 7 1 - F113 21833 Local RTD #6 High Alarm Level 1 200 1 °C F1 130
Table CG–10: MEMORY MAP (Sheet 29 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CGCOMMUNICATIONS GUIDE MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG83
1834 Local RTD #6 Alarm 0 2 1 - F115 01835 Local RTD #6 Alarm Relays 0 7 1 - F113 11836 Local RTD #6 Alarm Level 1 200 1 °C F1 1301837 Record RTD #6 Alarms as Events 0 1 1 - F103 01838 Local RTD #6 Trip 0 2 1 - F115 01839 Enable RTD #6 Trip Voting 0 13 1 - F122 1183A Local RTD #6 Trip Relays 0 7 1 - F111 1183B Local RTD #6 Trip Level 1 200 1 °C F1 130183C Local RTD #6 RTD Type 0 3 1 - F120 0
1840 First Character of Local RTD #6 Name 32 127 1 - F1 ’R’
↓ ↓
1843 8th Character of Local RTD #6 Name 32 127 1 - F1 " "
... ReservedLOCAL RTD #7
1850 Local RTD #7 Application 0 4 1 - F121 01851 Local RTD #7 High Alarm 0 2 1 - F115 01852 Local RTD #7 High Alarm Relays 0 7 1 - F113 21853 Local RTD #7 High Alarm Level 1 200 1 °C F1 1301854 Local RTD #7 Alarm 0 2 1 - F115 01855 Local RTD #7 Alarm Relays 0 7 1 - F113 11856 Local RTD #7 Alarm Level 1 200 1 °C F1 1301857 Record RTD #7 Alarms as Events 0 1 1 - F103 01858 Local RTD #7 Trip 0 2 1 - F115 01859 Enable RTD #7 Trip Voting 0 13 1 - F122 1185A Local RTD #7 Trip Relays 0 7 1 - F111 1185B Local RTD #7 Trip Level 1 200 1 °C F1 130185C Local RTD #7 RTD Type 0 3 1 - F120 0
1860 First Character of Local RTD #7 Name 32 127 1 - F1 ’R’
↓ ↓
1863 8th Character of Local RTD #7 Name 32 127 1 - F1 " "
1864 ReservedLOCAL RTD #8
1870 Local RTD #8 Application 0 4 1 - F121 01871 Local RTD #8 High Alarm 0 2 1 - F115 01872 Local RTD #8 High Alarm Relays 0 7 1 - F113 21873 Local RTD #8 High Alarm Level 1 200 1 °C F1 1301874 Local RTD #8 Alarm 0 2 1 - F115 01875 Local RTD #8 Alarm Relays 0 7 1 - F113 11876 Local RTD #8 Alarm Level 1 200 1 °C F1 1301877 Record RTD #8 Alarms as Events 0 1 1 - F103 01878 Local RTD #8 Trip 0 2 1 - F115 01879 Enable RTD #8 Trip Voting 0 13 1 - F122 1187A Local RTD #8 Trip Relays 0 7 1 - F111 1187B Local RTD #8 Trip Level 1 200 1 °C F1 130187C Local RTD #8 RTD Type 0 3 1 - F120 0
1880 First Character of Local RTD #8 Name 32 127 1 - F1 ’R’
Table CG–10: MEMORY MAP (Sheet 30 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CG84 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP CGCOMMUNICATIONS GUIDE
↓ ↓
1883 8th Character of Local RTD #8 Name 32 127 1 - F1 " "
1884 ReservedLOCAL RTD #9
1890 Local RTD #9 Application 0 4 1 - F121 01891 Local RTD #9 High Alarm 0 2 1 - F115 01892 Local RTD #9 High Alarm Relays 0 7 1 - F113 21893 Local RTD #9 High Alarm Level 1 200 1 °C F1 1301894 Local RTD #9 Alarm 0 2 1 - F115 01895 Local RTD #9 Alarm Relays 0 7 1 - F113 11896 Local RTD #9 Alarm Level 1 200 1 °C F1 1301897 Record RTD #9 Alarms as Events 0 1 1 - F103 01898 Local RTD #9 Trip 0 2 1 - F115 01899 Enable RTD #9 Trip Voting 0 13 1 - F122 1189A Local RTD #9 Trip Relays 0 7 1 - F111 1189B Local RTD #9 Trip Level 1 200 1 °C F1 130189C Local RTD #9 RTD Type 0 3 1 - F120 0
18A0 First Character of Local RTD #9 Name 32 127 1 - F1 ’R’
↓ ↓
18A3 8th Character of Local RTD #9 Name 32 127 1 - F1 " "
18A4 ReservedLOCAL RTD #10
18B0 Local RTD #10 Application 0 4 1 - F121 018B1 Local RTD #10 High Alarm 0 2 1 - F115 0
18B2 Local RTD #10 High Alarm Relays 0 7 1 - F113 2
18B3 Local RTD #10 High Alarm Level 1 200 1 °C F1 13018B4 Local RTD #10 Alarm 0 2 1 - F115 018B5 Local RTD #10 Alarm Relays 0 7 1 - F113 118B6 Local RTD #10 Alarm Level 1 200 1 °C F1 130
18B7 Record RTD #10 Alarms as Events 0 1 1 - F103 0
18B8 Local RTD #10 Trip 0 2 1 - F115 018B9 Enable RTD #10 Trip Voting 0 13 1 - F122 118BA Local RTD #10 Trip Relays 0 7 1 - F111 118BB Local RTD #10 Trip Level 1 200 1 °C F1 13018BC Local RTD #10 RTD Type 0 3 1 - F120 0
18C0 First Character of Local RTD #10 Name 32 127 1 - F1 ’R’
↓ ↓18C3 8th Character of RTD #10 Name 32 127 1 - F1 " "... Reserved
LOCAL RTD #11
18D0 Local RTD #11 Application 0 4 1 - F121 018D1 Local RTD #11 High Alarm 0 2 1 - F115 0
18D2 Local RTD #11 High Alarm Relays 0 7 1 - F113 2
18D3 Local RTD #11 High Alarm Level 1 200 1 °C F1 13018D4 Local RTD #11 Alarm 0 2 1 - F115 0
Table CG–10: MEMORY MAP (Sheet 31 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CGCOMMUNICATIONS GUIDE MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG85
18D5 Local RTD #11 Alarm Relays 0 7 1 - F113 118D6 Local RTD #11 Alarm Level 1 200 1 °C F1 13018D7 Record RTD #11 Alarm Events 0 1 1 - F103 018D8 Local RTD #11 Trip 0 2 1 - F115 018D9 Enable RTD #11 Trip Voting 0 13 1 - F122 118DA Local RTD #11 Trip Relays 0 7 1 - F111 118DB Local RTD #11 Trip Level 1 200 1 °C F1 13018DC Local RTD #11 RTD Type 0 3 1 - F120 0
18E0 First Character of Local RTD #11 Name 32 127 1 - F1 ’R’
↓ ↓
18E3 8th Character of Local RTD #11 Name 32 127 1 - F1 " "
... ReservedLOCAL RTD #12
18F0 Local RTD #12 Application 0 4 1 - F121 018F1 Local RTD #12 High Alarm 0 2 1 - F115 0
18F2 Local RTD #12 High Alarm Relays 0 7 1 - F113 2
18F3 Local RTD #12 High Alarm Level 1 200 1 °C F1 13018F4 Local RTD #12 Alarm 0 2 1 - F115 018F5 Local RTD #12 Alarm Relays 0 7 1 - F113 118F6 Local RTD #12 Alarm Level 1 200 1 °C F1 130
18F7 Record RTD #12 Alarms as Events 0 1 1 - F103 0
18F8 Local RTD #12 Trip 0 2 1 - F115 018F9 Enable RTD #12 Trip Voting 0 13 1 - F122 118FA Local RTD #12 Trip Relays 0 7 1 - F111 118FB Local RTD #12 Trip Level 1 200 1 °C F1 13018FC Local RTD #12 RTD Type 0 3 1 - F120 0
1900 First Character of Local RTD #12 Name 32 127 1 - F1 ’R’
↓ ↓
1903 8th Character of Local RTD #12 Name 32 127 1 - F1 " "
... ReservedOPEN RTD ALARM
1B20 Open RTD Alarm 0 2 1 - F115 01B21 Assign Alarm Relays 0 7 1 - F113 11B22 Open RTD Alarm Events 0 1 1 - F103 0
SHORT/LOW TEMPERATURE RTD ALARM
1B23 Short / Low Temp RTD Alarm 0 2 1 - F115 01B24 Assign Alarm Relays 0 7 1 - F113 11B25 Short / Low Temp Alarm Events 0 1 1 - F103 0... Reserved - - - - - -
LOSS OF REMOTE RTD COMMUNICATIONS
1B30 Loss RRTD Comm Alarm 0 2 1 - F115 01B31 Loss RRTD Comm Alarm Relays 0 7 1 - F113 11B32 Loss RRTD Comm Alarm Events 0 1 1 - F103 0... Reserved
Table CG–10: MEMORY MAP (Sheet 32 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CG86 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP CGCOMMUNICATIONS GUIDE
UNDERVOLTAGE
1B60 Undervoltage Active If Motor Stopped 0 1 1 - F103 0
1B61 Undervoltage Alarm 0 2 1 - F115 01B62 Assign Alarm Relays 0 7 1 - F113 11B63 Undervoltage Alarm Pickup 50 99 1 × Rated F3 85
1B64 Starting Undervoltage Alarm Pickup 50 99 1 × Rated F3 85
1B65 Undervoltage Alarm Delay 0 2550 1 0.1s F2 301B66 Undervoltage Alarm Events 0 1 1 - F103 01B67 Undervoltage Trip 0 2 1 - F115 01B68 Undervoltage Trip Relays 0 7 1 - F111 11B69 Undervoltage Trip Pickup 50 99 1 × Rated F3 80
1B6A Starting Undervoltage Trip Pickup 50 99 1 × Rated F3 80
1B6B Undervoltage Trip Delay 0 2550 1 0.1s F2 10... Reserved
OVERVOLTAGE
1B80 Overvoltage Alarm 0 2 1 - F115 01B81 Overvoltage Alarm Relays 0 7 1 - F113 11B82 Overvoltage Alarm Pickup 101 125 1 x Rated F3 1051B83 Overvoltage Alarm Delay 0 2550 1 s F2 101B84 Overvoltage Alarm Events 0 1 1 - F103 01B85 Overvoltage Trip 0 1 1 - F103 01B86 Overvoltage Trip Relays 0 7 1 - F111 11B87 Overvoltage Trip Pickup 101 125 1 x Rated F3 1101B88 Overvoltage Trip Delay 0 2550 1 s F2 10... Reserved
PHASE REVERSAL
1BA0 Phase Reversal Trip 0 2 1 - F115 01BA1 Assign Trip Relays 0 7 1 - F111 1... Reserved - - - - - -
OVERFREQUENCY
1BB0 Block Overfrequency on Start 0 5000 1 s F1 11BB1 Overfrequency Alarm 0 2 1 - F115 01BB2 Assign Alarm Relays 0 7 1 - F113 11BB3 Overfrequency Alarm Level 2000 7000 1 Hz F3 60501BB4 Overfrequency Alarm Delay 0 2550 1 s F2 101BB5 Overfrequency Alarm Events 0 1 1 - F103 01BB6 Overfrequency Trip 0 1 1 - F103 01BB7 Assign Trip Relays 0 7 1 - F111 11BB8 Overfrequency Trip Level 2000 7000 1 Hz F3 60501BB9 Overfrequency Trip Delay 0 2550 1 s F2 10... Reserved - - - - - -
UNDERFREQUENCY
1BC0 Block Underfrequency on Start 0 5000 1 s F1 11BC1 Underfrequency Alarm 0 2 1 - F115 01BC2 Assign Alarm Relays 0 7 1 - F113 11BC3 Underfrequency Alarm Level 2000 7000 1 Hz F3 59501BC4 Underfrequency Alarm Delay 0 2550 1 s F2 101BC5 Underfrequency Alarm Events 0 1 1 - F103 0
Table CG–10: MEMORY MAP (Sheet 33 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CGCOMMUNICATIONS GUIDE MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG87
1BC6 Underfrequency Trip 0 2 1 - F115 01BC7 Assign Trip Relays 0 7 1 - F111 11BC8 Underfrequency Trip Level 2000 7000 1 Hz F3 59501BC9 Underfrequency Trip Delay 0 2550 1 s F2 10... Reserved
LEAD POWER FACTOR
1BD0 Block Lead Power Factor From Start 0 5000 1 s F1 1
1BD1 Lead Power Factor Alarm 0 2 1 - F115 0
1BD2 Assign Lead Power Factor Alarm Relays 0 7 1 - F113 1
1BD3 Lead Power Factor Alarm Level 5 99 1 - F3 301BD4 Lead Power Factor Alarm Delay 1 2550 1 s F2 101BD5 Lead Power Factor Alarm Events 0 1 1 - F103 01BD6 Lead Power Factor Trip 0 2 1 - F115 01BD7 Lead Power Factor Trip Relays 0 7 1 - F111 11BD8 Lead Power Factor Trip Level 5 99 1 - F3 101BD9 Lead Power Factor Trip Delay 1 2550 1 s F2 10... Reserved
LAG POWER FACTOR
1BE0 Block Lag Power Factor From Start 0 5000 1 s F1 1
1BE1 Lag Power Factor Alarm 0 2 1 - F115 0
1BE2 Assign Lag Power Factor Alarm Relays 0 7 1 - F113 1
1BE3 Lag Power Factor Alarm Level 5 99 1 - F3 851BE4 Lag Power Factor Alarm Delay 1 2550 1 s F2 101BE5 Lag Power Factor Alarm Events 0 1 1 - F103 01BE6 Lag Power Factor Trip 0 2 1 - F115 0
1BE7 Assign Lag Power Factor Trip Relays 0 7 1 - F111 1
1BE8 Lag Power Factor Trip Level 5 99 1 - F3 801BE9 Lag Power Factor Trip Delay 1 2550 1 s F2 10... Reserved
POSITIVE REACTIVE POWER
1BF0 Block Positive kvar Element From Start 0 5000 1 s F1 1
1BF1 Positive kvar Alarm 0 2 1 - F115 01BF2 Assign Alarm Relays 0 7 1 - F113 11BF3 Positive kvar Alarm Level 1 25000 1 kvar F1 101BF4 Positive kvar Alarm Delay 1 2550 1 s F2 101BF5 Positive kvar Alarm Events 0 1 1 - F103 01BF6 Positive kvar Trip 0 1 1 - F103 01BF7 Assign Trip Relays 0 7 1 - F111 11BF8 Positive kvar Trip Level 1 25000 1 kvar F1 251BF9 Positive kvar Trip Delay 1 2550 1 s F2 10... Reserved
NEGATIVE REACTIVE POWER
1C00 Block Negative kvar Element from Start 0 5000 1 s F1 1
1C01 Negative kvar Alarm 0 2 1 - F115 01C02 Assign Alarm Relays 0 7 1 - F113 1
Table CG–10: MEMORY MAP (Sheet 34 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CG88 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP CGCOMMUNICATIONS GUIDE
1C03 Negative kvar Alarm Level 1 25000 1 kvar F1 101C04 Negative kvar Alarm Delay 1 2550 1 s F2 101C05 Negative kvar Alarm Events 0 1 1 - F103 01C06 Negative kvar Trip 0 1 1 - F103 01C07 Assign Trip Relays 0 7 1 - F111 11C08 Negative kvar Trip Level 1 25000 1 kvar F1 251C09 Negative kvar Trip Delay 1 2550 1 s F2 10... Reserved
UNDERPOWER
1C10 Block Underpower From Start 0 15000 1 s F1 01C11 Underpower Alarm 0 2 1 - F115 01C12 Assign Alarm Relays 0 7 1 - F113 11C13 Underpower Alarm Level 1 25000 1 kW F1 21C14 Underpower Alarm Delay 5 2550 1 s F2 11C15 Underpower Alarm Events 0 1 1 - F103 01C16 Underpower Trip 0 2 1 - F115 01C17 Underpower Trip Relays 0 7 1 - F111 11C18 Underpower Trip Level 1 25000 1 kW F1 11C19 Underpower Trip Delay 5 2550 1 s F1 1... Reserved
REVERSE POWER
1C20 Block Reverse Power From Start 0 50000 1 s F1 01C21 Reverse Power Alarm 0 2 1 - F115 01C22 Assign Alarm Relays 0 7 1 - F113 11C23 Reverse Power Alarm Level 1 25000 1 kW F1 21C24 Reverse Power Alarm Delay 5 300 1 s F2 11C25 Reverse Power Alarm Events 0 1 1 - F103 01C26 Reverse Power Trip 0 2 1 - F115 01C27 Assign Trip Relays 0 7 1 - F111 11C28 Reverse Power Trip Level 1 25000 1 kW F1 11C29 Reverse Power Trip Delay 5 300 1 s F2 1... Reserved
ENHANCED MOTOR LEARNED DATA
1C70 Number of Starts to Average 1 5 1 - F1 5
1C71 Access Learned Data Record Number 0 65535 1 - F1 0
TRIP COUNTER
1C80 Trip Counter Alarm 0 2 1 - F115 01C81 Assign Alarm Relays 0 7 1 - F113 11C82 Alarm Pickup Level 0 50000 1 - F1 251C83 Trip Counter Alarm Events 0 1 1 - F103 0... Reserved
STARTER FAILURE
1C90 Starter Failure Alarm 0 2 1 - F115 01C91 Starter Type 0 1 1 - F125 01C92 Assign Alarm Relays 0 7 1 - F113 11C93 Starter Failure Delay 10 1000 10 ms F1 1001C94 Starter Failure Alarm Events 0 1 1 - F103 0... Reserved
CURRENT DEMAND
1CD0 Current Demand Period 5 90 1 min F1 15
Table CG–10: MEMORY MAP (Sheet 35 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CGCOMMUNICATIONS GUIDE MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG89
1CD1 Current Demand Alarm 0 2 1 - F115 01CD2 Assign Alarm Relays 0 7 1 - F113 11CD3 Current Demand Alarm Limit 0 65000 1 A F1 1001CD5 Current Demand Alarm Events 0 1 1 - F103 0... Reserved
KW DEMAND
1CE0 kW Demand Period 5 90 1 min F1 151CE1 kW Demand Alarm 0 2 1 - F115 01CE2 Assign Alarm Relays 0 7 1 - F113 11CE3 kW Demand Alarm Limit 1 50000 1 kW F1 1001CE4 kW Demand Alarm Events 0 1 1 - F103 0... Reserved
KVAR DEMAND
1CF0 kvar Demand Period 5 90 1 min F1 151CF1 kvar Demand Alarm 0 2 1 - F115 01CF2 Assign Alarm Relays 0 7 1 - F113 11CF3 kvar Demand Alarm Limit 1 50000 1 kvar F1 1001CF4 kvar Demand Alarm Events 0 1 1 - F103 0... Reserved
KVA DEMAND
1D00 kVA Demand Period 5 90 1 min F1 151D01 kVA Demand Alarm 0 2 1 - F115 01D02 Assign Alarm Relays 0 7 1 - F113 11D03 kVA Demand Alarm Limit 1 50000 1 kVA F1 1001D04 kVA Demand Alarm Events 0 1 1 - F103 0... Reserved
SELF-TEST RELAY
1D06 Assign Service Relay 0 7 1 - F113 0... Reserved
ANALOG OUTPUTS
1D40 Enable Analog Output 1 0 1 1 - F103 0
1D41 Assign Analog Output 1 Output Range 0 2 1 - F26 0
1D42 Assign Analog Output 1 Parameter 0 35 1 - F127 0
1D43 Analog Output 1 Minimum TBD TBD 1 - F1 01D44 Analog Output 1 Maximum TBD TBD 1 - F1 01D45 Enable Analog Output 2 0 1 1 - F103 0
1D46 Assign Analog Output 2 Output Range 0 2 1 - F26 0
1D47 Assign Analog Output 2 Parameter 0 35 1 - F127 0
1D48 Analog Output 2 Minimum TBD TBD 1 - F1 01D49 Analog Output 2 Maximum TBD TBD 1 - F1 01D4A Enable Analog Output 3 0 1 1 - F103 0
1D4B Assign Analog Output 3 Output Range 0 2 1 - F26 0
1D4C Assign Analog Output 3 Parameter 0 35 1 - F127 0
1D4D Analog Output 3 Minimum TBD TBD 1 - F1 01D4E Analog Output 3 Maximum TBD TBD 1 - F1 01D4F Enable Analog Output 4 0 1 1 - F103 0
Table CG–10: MEMORY MAP (Sheet 36 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CG90 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP CGCOMMUNICATIONS GUIDE
1D50 Assign Analog Output 4 Output Range 0 2 1 - F26 0
1D51 Assign Analog Output 4 Parameter 0 35 1 - F127 0
1D52 Analog Output 4 Minimum TBD TBD 1 - F1 01D53 Analog Output 4 Maximum TBD TBD 1 - F1 0
SPEED 2 O/L CURVE SETUP
1DC0 Speed 2 Standard Overload Curve Number 1 15 1 - F1 4
1DC1 Speed 2 Time to Trip at 1.01 x FLA 0 65534 1 s F1 17415
1DC2 Speed 2 Time to Trip at 1.05 x FLA 0 65534 1 s F1 3415
1DC3 Speed 2 Time to Trip at 1.10 x FLA 0 65534 1 s F1 1667
1DC4 Speed 2 Time to Trip at 1.20 x FLA 0 65534 1 s F1 795
1DC5 Speed 2 Time to Trip at 1.30 x FLA 0 65534 1 s F1 507
1DC6 Speed 2 Time to Trip at 1.40 x FLA 0 65534 1 s F1 365
1DC7 Speed 2 Time to Trip at 1.50 x FLA 0 65534 1 s F1 280
1DC8 Speed 2 Time to Trip at 1.75 x FLA 0 65534 1 s F1 170
1DC9 Speed 2 Time to Trip at 2.00 x FLA 0 65534 1 s F1 117
1DCA Speed 2 Time to Trip at 2.25 x FLA 0 65534 1 s F1 86
1DCB Speed 2 Time to Trip at 2.50 x FLA 0 65534 1 s F1 67
1DCC Speed 2 Time to Trip at 2.75 x FLA 0 65534 1 s F1 53
1DCD Speed 2 Time to Trip at 3.00 x FLA 0 65534 1 s F1 44
1DCE Speed 2 Time to Trip at 3.25 x FLA 0 65534 1 s F1 37
1DCF Speed 2 Time to Trip at 3.50 x FLA 0 65534 1 s F1 31
1DD0 Speed 2 Time to Trip at 3.75 x FLA 0 65534 1 s F1 27
1DD1 Speed 2 Time to Trip at 4.00 x FLA 0 65534 1 s F1 23
1DD2 Speed 2 Time to Trip at 4.25 x FLA 0 65534 1 s F1 21
1DD3 Speed 2 Time to Trip at 4.50 x FLA 0 65534 1 s F1 18
1DD4 Speed 2 Time to Trip at 4.75 x FLA 0 65534 1 s F1 16
1DD5 Speed 2 Time to Trip at 5.00 x FLA 0 65534 1 s F1 15
1DD6 Speed 2 Time to Trip at 5.50 x FLA 0 65534 1 s F1 12
1DD7 Speed 2 Time to Trip at 6.00 x FLA 0 65534 1 s F1 10
1DD8 Speed 2 Time to Trip at 6.50 x FLA 0 65534 1 s F1 9
Table CG–10: MEMORY MAP (Sheet 37 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CGCOMMUNICATIONS GUIDE MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG91
1DD9 Speed 2 Time to Trip at 7.00 x FLA 0 65534 1 s F1 7
1DDA Speed 2 Time to Trip at 7.50 x FLA 0 65534 1 s F1 6
1DDB Speed 2 Time to Trip at 8.00 x FLA 0 65534 1 s F1 6
1DDC Speed 2 Time to Trip at 10.0 x FLA 0 65534 1 s F1 6
1DDD Speed 2 Time to Trip at 15.0 x FLA 0 65534 1 s F1 6
1DDE Speed 2 Time to Trip at 20.0 x FLA 0 65534 1 s F1 6
... ReservedSPEED 2 UNDERCURRENT
1DF0 Speed 2 Block Undercurrent from Start 0 15000 1 s F1 0
1DF1 Speed 2 Undercurrent Alarm 0 2 1 - F115 0
1DF2 Speed 2 Assign Undercurrent Alarm Relays 0 7 1 - F113 1
1DF3 Speed 2 Undercurrent Alarm Level 10 99 1 0.01 × F
LA F3 70
1DF4 Speed 2 Undercurrent Alarm Delay 1 255 1 s F1 1
1DF5 Speed 2 Undercurrent Alarm Events 0 1 1 - F103 0
1DF6 Speed 2 Undercurrent Trip 0 2 1 - F115 0
1DF7 Speed 2 Assign Undercurrent Trip Relays 0 7 1 - F111 1
1DF8 Speed 2 Undercurrent Trip Level 10 99 1 0.01 × FLA F3 70
1DF9 Speed 2 Undercurrent Trip Delay 1 255 1 s F1 1... Reserved
SPEED 2 ACCELERATION
1E00 Speed 2 Acceleration Timer from Start 10 2500 10 s F2 100
1E01 Speed 2 Acceleration Timer from Speed 1 to 2 20 2500 1 s F2 200
1E02 Speed 2 Speed Switch Time Delay 5 1000 5 100 ms F2 20
DATA LOGGER
1E20 Start/Stop Data Log 0 2 1 - F1870 (=Select Command)
1E21 Log Interval 1 3600 1 - F1 3600
1E22 Recording Type 0 1 1 - F188 0 (=Run To Fill)
1E23 Data Log Memory Access Block Number 0 255 1 - F1 0, 1 (=null)
1E24 Channel 1 Log Assignment 0 102 1 - F189 0 (=None)1E25 Channel 2 Log Assignment 0 102 1 - F189 0 (=None)1E26 Channel 3 Log Assignment 0 102 1 - F189 0 (=None)1E27 Channel 4 Log Assignment 0 102 1 - F189 0 (=None)1E28 Channel 5 Log Assignment 0 102 1 - F189 0 (=None)1E29 Channel 6 Log Assignment 0 102 1 - F189 0 (=None)1E2A Channel 7 Log Assignment 0 102 1 - F189 0 (=None)1E2B Channel 8 Log Assignment 0 102 1 - F189 0 (=None)
Table CG–10: MEMORY MAP (Sheet 38 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CG92 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP CGCOMMUNICATIONS GUIDE
1E2C Channel 9 Log Assignment 0 102 1 - F189 0 (=None)1E2D Channel 10 Log Assignment 0 102 1 - F189 0 (=None)1E2E Channel 11 Log Assignment 0 102 1 - F189 0 (=None)1E2F Channel 12 Log Assignment 0 102 1 - F189 0 (=None)1E30 Channel 13 Log Assignment 0 102 1 - F189 0 (=None)1E31 Channel 14 Log Assignment 0 102 1 - F189 0 (=None)1E32 Channel 15 Log Assignment 0 102 1 - F189 0 (=None)1E33 Channel 16 Log Assignment 0 102 1 - F189 0 (=None)... Reserved
TEST OUTPUT RELAYS
1F80 Force Trip Relay 0 2 1 - F150 01F81 Force Trip Relay Duration 1 300 1 s F1 01F82 Force AUX1 Relay 0 2 1 - F150 01F83 Force AUX1 Relay Duration 1 300 1 s F1 01F84 Force AUX2 Relay 0 2 1 - F150 01F85 Force AUX2 Relay Duration 1 300 1 s F1 01F86 Force Alarm Relay 0 2 1 - F150 01F87 Force Alarm Relay Range 1 300 1 s F1 0... Reserved
TEST ANALOG OUTPUTS
1F90 Force Analog Outputs 0 1 1 - F126 01F91 Analog Output 1 Forced Value 0 100 1 % range F1 01F92 Analog Output 2 Forced Value 0 100 1 % range F1 01F93 Analog Output 3 Forced Value 0 100 1 % range F1 01F94 Analog Output 4 Forced Value 0 100 1 % range F1 0... Reserved
REMOTE RTD SLAVE ADDRESSES
1FF0 RRTD1 - Slave Address 0 254 1 - F1 01FF1 RRTD2 - Slave Address 0 254 1 - F1 01FF2 RRTD3 - Slave Address 0 254 1 - F1 01FF3 RRTD4 - Slave Address 0 254 1 - F1 0... Reserved
RRTD 1 – RTD #1
2000 RRTD 1 - RTD #1 Application 0 4 1 - F121 02001 RRTD 1 - RTD #1 High Alarm 0 2 1 - F115 0
2002 RRTD 1 - RTD #1 High Alarm Relays 0 7 1 - F113 2
2003 RRTD 1 - RTD #1 High Alarm Level 1 200 1 °C F1 130
2004 RRTD 1 - RTD #1 Alarm 0 2 1 - F115 02005 RRTD 1 - RTD #1 Alarm Relays 0 7 1 - F113 12006 RRTD 1 - RTD #1 Alarm Level 1 200 1 °C F1 130
2007 Record RRTD 1 - RTD #1 Alarms as Events 0 1 1 - F103 0
2008 RRTD 1 - RTD #1 Trip 0 2 1 - F115 0
2009 Enable RRTD 1 - RTD #1 Trip Voting 0 13 1 - F122 1
200A RRTD 1 - RTD #1 Trip Relays 0 7 1 - F111 1200B RRTD 1 - RTD #1 Trip Level 1 200 1 °C F1 130200C RRTD 1 - RTD #1 RTD Type 0 3 1 - F120 0... Reserved
Table CG–10: MEMORY MAP (Sheet 39 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CGCOMMUNICATIONS GUIDE MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG93
2010 First Character of RRTD 1 - RTD #1 Name 32 127 1 - F1 ’R’
↓ ↓
2013 8th Character of RRTD 1 - RTD #1 Name 32 127 1 - F1 " "
2014 ReservedRRTD 1 – RTD #2
2020 RRTD 1 - RTD #2 Application 0 4 1 - F121 02021 RRTD 1 - RTD #2 High Alarm 0 2 1 - F115 0
2022 RRTD 1 - RTD #2 High Alarm Relays 0 7 1 - F113 2
2023 RRTD 1 - RTD #2 High Alarm Level 1 200 1 °C F1 130
2024 RRTD 1 - RTD #2 Alarm 0 2 1 - F115 02025 RRTD 1 - RTD #2 Alarm Relays 0 7 1 - F113 12026 RRTD 1 - RTD #2 Alarm Level 1 200 1 °C F1 130
2027 Record RRTD 1 - RTD #2 Alarms as Events 0 1 1 - F103 0
2028 RRTD 1 - RTD #2 Trip 0 2 1 - F115 0
2029 Enable A Remote RTD #2 Trip Voting 0 13 1 - F122 1
202A RRTD 1 - RTD #2 Trip Relays 0 7 1 - F111 1202B RRTD 1 - RTD #2 Trip Level 1 200 1 °C F1 130202C RRTD 1 - RTD #2 RTD Type 0 3 1 - F120 0... Reserved
2030 First Character of RRTD 1 - RTD #2 Name 32 127 1 - F1 ’R’
↓ ↓
2033 8th Character of RRTD 1 - RTD #2 Name 32 127 1 - F1 " "
2034 ReservedRRTD 1 – RTD #3
2040 RRTD 1 - RTD #3 Application 0 4 1 - F121 02041 RRTD 1 - RTD #3 High Alarm 0 2 1 - F115 0
2042 RRTD 1 - RTD #3 High Alarm Relays 0 7 1 - F113 2
2043 RRTD 1 - RTD #3 High Alarm Level 1 200 1 °C F1 130
2044 RRTD 1 - RTD #3 Alarm 0 2 1 - F115 02045 RRTD 1 - RTD #3 Alarm Relays 0 7 1 - F113 12046 RRTD 1 - RTD #3 Alarm Level 1 200 1 °C F1 130
2047 Record RRTD 1 - RTD #3 Alarms as Events 0 1 1 - F103 0
2048 RRTD 1 - RTD #3 Trip 0 2 1 - F115 0
2049 Enable RRTD 1 - RTD #3 Trip Voting 0 13 1 - F122 1
204A RRTD 1 - RTD #3 Trip Relays 0 7 1 - F111 1204B RRTD 1 - RTD #3 Trip Level 1 200 1 °C F1 130204C RRTD 1 - RTD #3 RTD Type 0 3 1 - F120 0
2050 First Character of RRTD 1 - RTD # Name 32 127 1 - F1 ’R’
↓ ↓
2053 8th Character of RRTD 1 - RTD #3 Name 32 127 1 - F1 " "
Table CG–10: MEMORY MAP (Sheet 40 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CG94 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP CGCOMMUNICATIONS GUIDE
... ReservedRRTD 1 – RTD #4
2060 RRTD 1 - RTD #4 Application 0 4 1 - F121 02061 RRTD 1 - RTD #4 High Alarm 0 2 1 - F115 0
2062 RRTD 1 - RTD #4 High Alarm Relays 0 7 1 - F113 2
2063 RRTD 1 - RTD #4 High Alarm Level 1 200 1 °C F1 130
2064 RRTD 1 - RTD #4 Alarm 0 2 1 - F115 02065 RRTD 1 - RTD #4 Alarm Relays 0 7 1 - F113 12066 RRTD 1 - RTD #4 Alarm Level 1 200 1 °C F1 130
2067 Record RRTD 1 - RTD #4 Alarms as Events 0 1 1 - F103 0
2068 RRTD 1 - RTD #4 Trip 0 2 1 - F115 0
2069 Enable RRTD 1 - RTD #4 Trip Voting 0 13 1 - F122 1
206A RRTD 1 - RTD #4 Trip Relays 0 7 1 - F111 1206B RRTD 1 - RTD #4 Trip Level 1 200 1 °C F1 130206C RRTD 1 - RTD #4 RTD Type 0 3 1 - F120 0
2070 First Character of RRTD 1 - RTD #4 Name 32 127 1 - F1 ’R’
↓ ↓
2073 8th Character of RRTD 1 - RTD #4 Name 32 127 1 - F1 " "
2074 ReservedRRTD 1 – RTD #5
2080 RRTD 1 - RTD #5 Application 0 4 1 - F121 02081 RRTD 1 - RTD #5 High Alarm 0 2 1 - F115 0
2082 RRTD 1 - RTD #5 High Alarm Relays 0 7 1 - F113 2
2083 RRTD 1 - RTD #5 High Alarm Level 1 200 1 °C F1 130
2084 RRTD 1 - RTD #5 Alarm 0 2 1 - F115 02085 RRTD 1 - RTD #5 Alarm Relays 0 7 1 - F113 12086 RRTD 1 - RTD #5 Alarm Level 1 200 1 °C F1 130
2087 Record RRTD 1 - RTD #5 Alarms as Events 0 1 1 - F103 0
2088 RRTD 1 - RTD #5 Trip 0 2 1 - F115 0
2089 Enable RRTD 1 - RTD #5 Trip Voting 0 13 1 - F122 1
208A RRTD 1 - RTD #5 Trip Relays 0 7 1 - F111 1208B RRTD 1 - RTD #5 Trip Level 1 200 1 °C F1 130208C RRTD 1 - RTD #5 RTD Type 0 3 1 - F120 0
2090 First Character of RRTD 1 - RTD #5 Name 32 127 1 - F1 ’R’
↓ ↓
2093 8th Character of RRTD 1 - RTD #5 Name 32 127 1 - F1 " "
... ReservedRRTD 1 – RTD #6
20A0 RRTD 1 - RTD #6 Application 0 4 1 - F121 020A1 RRTD 1 - RTD #6 High Alarm 0 2 1 - F115 0
20A2 RRTD 1 - RTD #6 High Alarm Relays 0 7 1 - F113 1
Table CG–10: MEMORY MAP (Sheet 41 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CGCOMMUNICATIONS GUIDE MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG95
20A3 RRTD 1 - RTD #6 High Alarm Level 1 200 1 °C F1 130
20A4 RRTD 1 - RTD #6 Alarm 0 2 1 - F115 020A5 RRTD 1 - RTD #6 Alarm Relays 0 7 1 - F113 120A6 RRTD 1 - RTD #6 Alarm Level 1 200 1 °C F1 130
20A7 Record RRTD 1 - RTD #6 Alarms as Events 0 1 1 - F103 0
20A8 RRTD 1 - RTD #6 Trip 0 2 1 - F115 0
20A9 Enable RRTD 1 - RTD #6 Trip Voting 0 13 1 - F122 1
20AA RRTD 1 - RTD #6 Trip Relays 0 7 1 - F111 120AB RRTD 1 - RTD #6 Trip Level 1 200 1 °C F1 13020AC RRTD 1 - RTD #6 RTD Type 0 3 1 - F120 0
20B0 First Character of RRTD 1 - RTD #6 Name 32 127 1 - F1 ’R’
↓ ↓
20B3 8th Character of RRTD 1 - RTD #6 Name 32 127 1 - F1 " "
... ReservedRRTD 1 – RTD #7
20C0 RRTD 1 - RTD #7 Application 0 4 1 - F121 020C1 RRTD 1 - RTD #7 High Alarm 0 2 1 - F115 0
20C2 RRTD 1 - RTD #7 High Alarm Relays 0 7 1 - F113 2
20C3 RRTD 1 - RTD #7 High Alarm Level 1 200 1 °C F1 130
20C4 RRTD 1 - RTD #7 Alarm 0 2 1 - F115 020C5 RRTD 1 - RTD #7 Alarm Relays 0 7 1 - F113 120C6 RRTD 1 - RTD #7 Alarm Level 1 200 1 °C F1 130
20C7 Record RRTD 1 - RTD #7 Alarms as Events 0 1 1 - F103 0
20C8 RRTD 1 - RTD #7 Trip 0 2 1 - F115 0
20C9 Enable RRTD 1 - RTD #7 Trip Voting 0 13 1 - F122 1
20CA RRTD 1 - RTD #7 Trip Relays 0 7 1 - F111 120CB RRTD 1 - RTD #7 Trip Level 1 200 1 °C F1 13020CC RRTD 1 - RTD #7 RTD Type 0 3 1 - F120 0
20D0 First Character of RRTD 1 - RTD #7 Name 32 127 1 - F1 ’R’
↓ ↓
20D3 8th Character of RRTD 1 - RTD #7 Name 32 127 1 - F1 " "
... ReservedRRTD 1 – RTD #8
20E0 RRTD 1 - RTD #8 Application 0 4 1 - F121 020E1 RRTD 1 - RTD #8 High Alarm 0 2 1 - F115 0
20E2 RRTD 1 - RTD #8 High Alarm Relays 0 7 1 - F113 2
20E3 RRTD 1 - RTD #8 High Alarm Level 1 200 1 °C F1 130
20E4 RRTD 1 - RTD #8 Alarm 0 2 1 - F115 020E5 RRTD 1 - RTD #8 Alarm Relays 0 7 1 - F113 120E6 RRTD 1 - RTD #8 Alarm Level 1 200 1 °C F1 130
Table CG–10: MEMORY MAP (Sheet 42 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CG96 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP CGCOMMUNICATIONS GUIDE
20E7 Record RRTD 1 - RTD #8 Alarms as Events 0 1 1 - F103 0
20E8 RRTD 1 - RTD #8 Trip 0 2 1 - F115 0
20E9 Enable RRTD 1 - RTD #8 Trip Voting 0 13 1 - F122 1
20EA RRTD 1 - RTD #8 Trip Relays 0 7 1 - F111 120EB RRTD 1 - RTD #8 Trip Level 1 200 1 °C F1 13020EC RRTD 1 - RTD #8 RTD Type 0 3 1 - F120 0
20F0 First Character of RRTD 1 - RTD #8 Name 32 127 1 - F1 ’R’
↓ ↓
20F3 8th Character of RRTD 1 - RTD #8 Name 32 127 1 - F1 " "
... ReservedRRTD 1 – RTD #9
2100 RRTD 1 - RTD #9 Application 0 4 1 - F121 02101 RRTD 1 - RTD #9 High Alarm 0 2 1 - F115 0
2102 RRTD 1 - RTD #9 High Alarm Relays 0 7 1 - F113 2
2103 RRTD 1 - RTD #9 High Alarm Level 1 200 1 °C F1 130
2104 RRTD 1 - RTD #9 Alarm 0 2 1 - F115 02105 RRTD 1 - RTD #9 Alarm Relays 0 7 1 - F113 12106 RRTD 1 - RTD #9 Alarm Level 1 200 1 °C F1 130
2107 Record RRTD 1 - RTD #9 Alarms as Events 0 1 1 - F103 0
2108 RRTD 1 - RTD #9 Trip 0 2 1 - F115 0
2109 Enable RRTD 1 - RTD #9 Trip Voting 0 13 1 - F122 1
210A RRTD 1 - RTD #9 Trip Relays 0 7 1 - F111 1210B RRTD 1 - RTD #9 Trip Level 1 200 1 °C F1 130210C RRTD 1 - RTD #9 RTD Type 0 3 1 - F120 0
2110 First Character of RRTD 1 - RTD #9 Name 32 127 1 - F1 ’R’
↓ ↓
2113 8th Character of RRTD 1 - RTD #9 Name 32 127 1 - F1 " "
... ReservedRRTD 1 – RTD #10
2120 RRTD 1 - RTD #10 Application 0 4 1 - F121 02121 RRTD 1 - RTD #10 High Alarm 0 2 1 - F115 0
2122 RRTD 1 - RTD #10 High Alarm Relays 0 7 1 - F113 2
2123 RRTD 1 - RTD #10 High Alarm Level 1 200 1 °C F1 130
2124 RRTD 1 - RTD #10 Alarm 0 2 1 - F115 02125 RRTD 1 - RTD #10 Alarm Relays 0 7 1 - F113 12126 RRTD 1 - RTD #10 Alarm Level 1 200 1 °C F1 130
2127 Record RRTD 1 - RTD #10 Alarms as Events 0 1 1 - F103 0
2128 RRTD 1 - RTD #10 Trip 0 2 1 - F115 0
2129 Enable RRTD 1 - RTD#10 Trip Voting 0 13 1 - F122 1
212A RRTD 1 - RTD #10 Trip Relays 0 7 1 - F111 1
Table CG–10: MEMORY MAP (Sheet 43 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CGCOMMUNICATIONS GUIDE MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG97
212B RRTD 1 - RTD #10 Trip Level 1 200 1 °C F1 130212C RRTD 1 - RTD #10 RTD Type 0 3 1 - F120 0
2130 First Character of RRTD 1 - RTD #10 Name 32 127 1 - F1 ’R’
↓ ↓
2133 8th Character of RRTD 1 - RTD #10 Name 32 127 1 - F1 " "
... ReservedRRTD 1 – RTD #11
2140 RRTD 1 - RTD #11 Application 0 4 1 - F121 02141 RRTD 1 - RTD #11 High Alarm 0 2 1 - F115 0
2142 RRTD 1 - RTD #11 High Alarm Relays 0 7 1 - F113 2
2143 RRTD 1 - RTD #11 High Alarm Level 1 200 1 °C F1 130
2144 RRTD 1 - RTD #11 Alarm 0 2 1 - F115 02145 RRTD 1 - RTD #11 Alarm Relays 0 7 1 - F113 12146 RRTD 1 - RTD #11 Alarm Level 1 200 1 °C F1 130
2147 Record RRTD 1 - RTD #11 Alarms as Events 0 1 1 - F103 0
2148 RRTD 1 - RTD #11 Trip 0 2 1 - F115 0
2149 Enable RRTD 1 - RTD #11 Trip Voting 0 13 1 - F122 1
214A RRTD 1 - RTD #11 Trip Relays 0 7 1 - F111 1214B RRTD 1 - RTD #11 Trip Level 1 200 1 °C F1 130214C RRTD 1 - RTD #11 RTD Type 0 3 1 - F120 0
2150 First Character of RRTD 1 - RTD #11 Name 32 127 1 - F1 ’R’
↓ ↓
2153 8th Character of RRTD 1 - RTD #11 Name 32 127 1 - F1 " "
... ReservedRRTD 1 – RTD #12
2160 RRTD 1 - RTD #12 Application 0 4 1 - F121 02161 RRTD 1 - RTD #12 High Alarm 0 2 1 - F115 0
2162 RRTD 1 - RTD #12 High Alarm Relays 0 7 1 - F113 2
2163 RRTD 1 - RTD #12 High Alarm Level 1 200 1 °C F1 130
2164 RRTD 1 - RTD #12 Alarm 0 2 1 - F115 02165 RRTD 1 - RTD #12 Alarm Relays 0 7 1 - F113 12166 RRTD 1 - RTD #12 Alarm Level 1 200 1 °C F1 130
2167 Record RRTD 1 - RTD #12 Alarms as Events 0 1 1 - F103 0
2168 RRTD 1 - RTD #12 Trip 0 2 1 - F115 0
2169 Enable RRTD 1 - RTD #12 Trip Voting 0 13 1 - F122 1
216A RRTD 1 - RTD #12 Trip Relays 0 7 1 - F111 1216B RRTD 1 - RTD #12 Trip Level 1 200 1 °C F1 130216C RRTD 1 - RTD #12 RTD Type 0 3 1 - F120 0
2170 First Character of RRTD 1 - RTD #12 Name 32 127 1 - F1 ’R’
↓ ↓
Table CG–10: MEMORY MAP (Sheet 44 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CG98 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP CGCOMMUNICATIONS GUIDE
2173 8th Character of RRTD 1 - RTD #12 Name 32 127 1 - F1 " "
... ReservedRRTD 1 – OPEN RTD ALARM
2180 RRTD A - Open RTD Alarm 0 2 1 - F115 02181 RRTD A - Assign Alarm Relays 0 7 1 - F113 12182 RRTD A - Open RTD Alarm Events 0 1 1 - F103 0
RRTD 1 – SHORT/LOW TEMPERATURE RTD ALARM
2183 RRTD A - Short / Low Temp RTD Alarm 0 2 1 - F115 0
2184 RRTD A - Assign Alarm Relays 0 7 1 - F113 1
2185 RRTD A - Short / Low Temp Alarm Events 0 1 1 - F103 0
... Reserved - - - - - -RRTD 2 – RTD #1
2200 RRTD 2 - RTD #1 Application 0 4 1 - F121 02201 RRTD 2 - RTD #1 High Alarm 0 2 1 - F115 0
2202 RRTD 2 - RTD #1 High Alarm Relays 0 7 1 - F113 2
2203 RRTD 2 - RTD #1 High Alarm Level 1 200 1 °C F1 130
2204 RRTD 2 - RTD #1 Alarm 0 2 1 - F115 02205 RRTD 2 - RTD #1 Alarm Relays 0 7 1 - F113 12206 RRTD 2 - RTD #1 Alarm Level 1 200 1 °C F1 130
2207 Record RRTD 2 - RTD #1 Alarms as Events 0 1 1 - F103 0
2208 RRTD 2 - RTD #1 Trip 0 2 1 - F115 0
2209 Enable RRTD 2 - RTD #1 Trip Voting 0 13 1 - F122 1
220A RRTD 2 - RTD #1 Trip Relays 0 7 1 - F111 1220B RRTD 2 - RTD #1 Trip Level 1 200 1 °C F1 130220C RRTD 2 - RTD #1 RTD Type 0 3 1 - F120 0
2210 First Character of RRTD 2 - RTD #1 Name 32 127 1 - F1 ’R’
↓ ↓
2213 8th Character of RRTD 2 - RTD #1 Name 32 127 1 - F1 " "
... ReservedRRTD 2 – RTD #2
2220 RRTD 2 - RTD #2 Application 0 4 1 - F121 02221 RRTD 2 - RTD #2 High Alarm 0 2 1 - F115 0
2222 RRTD 2 - RTD #2 High Alarm Relays 0 7 1 - F113 2
2223 RRTD 2 - RTD #2 High Alarm Level 1 200 1 °C F1 130
2224 RRTD 2 - RTD #2 Alarm 0 2 1 - F115 02225 RRTD 2 - RTD #2 Alarm Relays 0 7 1 - F113 12226 RRTD 2 - RTD #2 Alarm Level 1 200 1 °C F1 130
2227 Record RRTD 2 - RTD #2 Alarms as Events 0 1 1 - F103 0
2228 RRTD 2 - RTD #2 Trip 0 2 1 - F115 0
2229 Enable A Remote RTD #2 Trip Voting 0 13 1 - F122 1
222A RRTD 2 - RTD #2 Trip Relays 0 7 1 - F111 1
Table CG–10: MEMORY MAP (Sheet 45 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CGCOMMUNICATIONS GUIDE MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG99
222B RRTD 2 - RTD #2 Trip Level 1 200 1 °C F1 130222C RRTD 2 - RTD #2 RTD Type 0 3 1 - F120 0
2230 First Character of RRTD 2 - RTD #2 Name 32 127 1 - F1 ’R’
↓ ↓
2233 8th Character of RRTD 2 - RTD #2 Name 32 127 1 - F1 " "
... ReservedRRTD 2 – RTD #3
2240 RRTD 2 - RTD #3 Application 0 4 1 - F121 02241 RRTD 2 - RTD #3 High Alarm 0 2 1 - F115 0
2242 RRTD 2 - RTD #3 High Alarm Relays 0 7 1 - F113 2
2243 RRTD 2 - RTD #3 High Alarm Level 1 200 1 °C F1 130
2244 RRTD 2 - RTD #3 Alarm 0 2 1 - F115 02245 RRTD 2 - RTD #3 Alarm Relays 0 7 1 - F113 12246 RRTD 2 - RTD #3 Alarm Level 1 200 1 °C F1 130
2247 Record RRTD 2 - RTD #3 Alarms as Events 0 1 1 - F103 0
2248 RRTD 2 - RTD #3 Trip 0 2 1 - F115 0
2249 Enable RRTD 2 - RTD #3 Trip Voting 0 13 1 - F122 1
224A RRTD 2 - RTD #3 Trip Relays 0 7 1 - F111 1224B RRTD 2 - RTD #3 Trip Level 1 200 1 °C F1 130224C RRTD 2 - RTD #3 RTD Type 0 3 1 - F120 0
2250 First Character of RRTD 2 - RTD # Name 32 127 1 - F1 ’R’
↓ ↓
2253 8th Character of RRTD 2 - RTD #3 Name 32 127 1 - F1 " "
... ReservedRRTD 2 – RTD #4
2260 RRTD 2 - RTD #4 Application 0 4 1 - F121 02261 RRTD 2 - RTD #4 High Alarm 0 2 1 - F115 0
2262 RRTD 2 - RTD #4 High Alarm Relays 0 7 1 - F113 2
2263 RRTD 2 - RTD #4 High Alarm Level 1 200 1 °C F1 130
2264 RRTD 2 - RTD #4 Alarm 0 2 1 - F115 02265 RRTD 2 - RTD #4 Alarm Relays 0 7 1 - F113 12266 RRTD 2 - RTD #4 Alarm Level 1 200 1 °C F1 130
2267 Record RRTD 2 - RTD #4 Alarms as Events 0 1 1 - F103 0
2268 RRTD 2 - RTD #4 Trip 0 2 1 - F115 0
2069 Enable RRTD 2 - RTD #4 Trip Voting 0 13 1 - F122 1
226A RRTD 2 - RTD #4 Trip Relays 0 7 1 - F111 1226B RRTD 2 - RTD #4 Trip Level 1 200 1 °C F1 130226C RRTD 2 - RTD #4 RTD Type 0 3 1 - F120 0
2270 First Character of RRTD 2 - RTD #4 Name 32 127 1 - F1 ’R’
↓ ↓
Table CG–10: MEMORY MAP (Sheet 46 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CG100 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP CGCOMMUNICATIONS GUIDE
2273 8th Character of RRTD 2 - RTD #4 Name 32 127 1 - F1 " "
... ReservedRRTD 2 – RTD #5
2280 RRTD 2 - RTD #5 Application 0 4 1 - F121 02281 RRTD 2 - RTD #5 High Alarm 0 2 1 - F115 0
2282 RRTD 2 - RTD #5 High Alarm Relays 0 7 1 - F113 2
2283 RRTD 2 - RTD #5 High Alarm Level 1 200 1 °C F1 130
2284 RRTD 2 - RTD #5 Alarm 0 2 1 - F115 02285 RRTD 2 - RTD #5 Alarm Relays 0 7 1 - F113 12286 RRTD 2 - RTD #5 Alarm Level 1 200 1 °C F1 130
2287 Record RRTD 2 - RTD #5 Alarms as Events 0 1 1 - F103 0
2288 RRTD 2 - RTD #5 Trip 0 2 1 - F115 0
2289 Enable RRTD 2 - RTD #5 Trip Voting 0 13 1 - F122 1
228A RRTD 2 - RTD #5 Trip Relays 0 7 1 - F111 1228B RRTD 2 - RTD #5 Trip Level 1 200 1 °C F1 130228C RRTD 2 - RTD #5 RTD Type 0 3 1 - F120 0
2290 First Character of RRTD 2 - RTD #5 Name 32 127 1 - F1 ’R’
↓ ↓
2293 8th Character of RRTD 2 - RTD #5 Name 32 127 1 - F1 " "
... ReservedRRTD 2 – RTD #6
22A0 RRTD 2 - RTD #6 Application 0 4 1 - F121 022A1 RRTD 2 - RTD #6 High Alarm 0 2 1 - F115 0
22A2 RRTD 2 - RTD #6 High Alarm Relays 0 7 1 - F113 1
22A3 RRTD 2 - RTD #6 High Alarm Level 1 200 1 °C F1 130
22A4 RRTD 2 - RTD #6 Alarm 0 2 1 - F115 022A5 RRTD 2 - RTD #6 Alarm Relays 0 7 1 - F113 122A6 RRTD 2 - RTD #6 Alarm Level 1 200 1 °C F1 130
22A7 Record RRTD 2 - RTD #6 Alarms as Events 0 1 1 - F103 0
22A8 RRTD 2 - RTD #6 Trip 0 2 1 - F115 0
22A9 Enable RRTD 2 - RTD #6 Trip Voting 0 13 1 - F122 1
22AA RRTD 2 - RTD #6 Trip Relays 0 7 1 - F111 122AB RRTD 2 - RTD #6 Trip Level 1 200 1 °C F1 13022AC RRTD 2 - RTD #6 RTD Type 0 3 1 - F120 0
22B0 First Character of RRTD 2 - RTD #6 Name 32 127 1 - F1 ’R’
↓ ↓
22B3 8th Character of RRTD 2 - RTD #6 Name 32 127 1 - F1 " "
... ReservedRRTD 2 – RTD #7
22C0 RRTD 2 - RTD #7 Application 0 4 1 - F121 022C1 RRTD 2 - RTD #7 High Alarm 0 2 1 - F115 0
Table CG–10: MEMORY MAP (Sheet 47 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CGCOMMUNICATIONS GUIDE MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG101
22C2 RRTD 2 - RTD #7 High Alarm Relays 0 7 1 - F113 2
22C3 RRTD 2 - RTD #7 High Alarm Level 1 200 1 °C F1 130
22C4 RRTD 2 - RTD #7 Alarm 0 2 1 - F115 022C5 RRTD 2 - RTD #7 Alarm Relays 0 7 1 - F113 122C6 RRTD 2 - RTD #7 Alarm Level 1 200 1 °C F1 130
22C7 Record RRTD 2 - RTD #7 Alarms as Events 0 1 1 - F103 0
22C8 RRTD 2 - RTD #7 Trip 0 2 1 - F115 0
22C9 Enable RRTD 2 - RTD #7 Trip Voting 0 13 1 - F122 1
22CA RRTD 2 - RTD #7 Trip Relays 0 7 1 - F111 122CB RRTD 2 - RTD #7 Trip Level 1 200 1 °C F1 13022CC RRTD 2 - RTD #7 RTD Type 0 3 1 - F120 0
22D0 First Character of RRTD 2 - RTD #7 Name 32 127 1 - F1 ’R’
↓ ↓
22D3 8th Character of RRTD 2 - RTD #7 Name 32 127 1 - F1 ’ ’
... ReservedRRTD 2 – RTD #8
22E0 RRTD 2 - RTD #8 Application 0 4 1 - F121 022E1 RRTD 2 - RTD #8 High Alarm 0 2 1 - F115 0
22E2 RRTD 2 - RTD #8 High Alarm Relays 0 7 1 - F113 2
22E3 RRTD 2 - RTD #8 High Alarm Level 1 200 1 °C F1 130
22E4 RRTD 2 - RTD #8 Alarm 0 2 1 - F115 022E5 RRTD 2 - RTD #8 Alarm Relays 0 7 1 - F113 122E6 RRTD 2 - RTD #8 Alarm Level 1 200 1 °C F1 130
22E7 Record RRTD 2 - RTD #8 Alarms as Events 0 1 1 - F103 0
22E8 RRTD 2 - RTD #8 Trip 0 2 1 - F115 0
22E9 Enable RRTD 2 - RTD #8 Trip Voting 0 13 1 - F122 1
22EA RRTD 2 - RTD #8 Trip Relays 0 7 1 - F111 122EB RRTD 2 - RTD #8 Trip Level 1 200 1 °C F1 13022EC RRTD 2 - RTD #8 RTD Type 0 3 1 - F120 0
22F0 First Character of RRTD 2 - RTD #8 Name 32 127 1 - F1 ’R’
↓ ↓
22F3 8th Character of RRTD 2 - RTD #8 Name 32 127 1 - F1 ’ ’
... ReservedRRTD 2 – RTD #9
2300 RRTD 2 - RTD #9 Application 0 4 1 - F121 02301 RRTD 2 - RTD #9 High Alarm 0 2 1 - F115 0
2302 RRTD 2 - RTD #9 High Alarm Relays 0 7 1 - F113 2
2303 RRTD 2 - RTD #9 High Alarm Level 1 200 1 °C F1 130
2304 RRTD 2 - RTD #9 Alarm 0 2 1 - F115 02305 RRTD 2 - RTD #9 Alarm Relays 0 7 1 - F113 1
Table CG–10: MEMORY MAP (Sheet 48 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CG102 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP CGCOMMUNICATIONS GUIDE
2306 RRTD 2 - RTD #9 Alarm Level 1 200 1 °C F1 130
2307 Record RRTD 2 - RTD #9 Alarms as Events 0 1 1 - F103 0
2308 RRTD 2 - RTD #9 Trip 0 2 1 - F115 0
2309 Enable RRTD 2 - RTD #9 Trip Voting 0 13 1 - F122 1
230A RRTD 2 - RTD #9 Trip Relays 0 7 1 - F111 1230B RRTD 2 - RTD #9 Trip Level 1 200 1 °C F1 130230C RRTD 2 - RTD #9 RTD Type 0 3 1 - F120 0
2310 First Character of RRTD 2 - RTD #9 Name 32 127 1 - F1 ’R’
↓ ↓
2313 8th Character of RRTD 2 - RTD #9 Name 32 127 1 - F1 " "
... ReservedRRTD 2 – RTD #10
2320 RRTD 2 - RTD #10 Application 0 4 1 - F121 02321 RRTD 2 - RTD #10 High Alarm 0 2 1 - F115 0
2322 RRTD 2 - RTD #10 High Alarm Relays 0 7 1 - F113 2
2323 RRTD 2 - RTD #10 High Alarm Level 1 200 1 °C F1 130
2324 RRTD 2 - RTD #10 Alarm 0 2 1 - F115 02325 RRTD 2 - RTD #10 Alarm Relays 0 7 1 - F113 12326 RRTD 2 - RTD #10 Alarm Level 1 200 1 °C F1 130
2327 Record RRTD 2 - RTD #10 Alarms as Events 0 1 1 - F103 0
2328 RRTD 2 - RTD #10 Trip 0 2 1 - F115 0
2329 Enable RRTD 2 - RTD#10 Trip Voting 0 13 1 - F122 1
232A RRTD 2 - RTD #10 Trip Relays 0 7 1 - F111 1232B RRTD 2 - RTD #10 Trip Level 1 200 1 °C F1 130232C RRTD 2 - RTD #10 RTD Type 0 3 1 - F120 0
2330 First Character of RRTD 2 - RTD #10 Name 32 127 1 - F1 ’R’
↓ ↓
2333 8th Character of RRTD 2 - RTD #10 Name 32 127 1 - F1 " "
... ReservedRRTD 2 – RTD #11
2340 RRTD 2 - RTD #11 Application 0 4 1 - F121 02341 RRTD 2 - RTD #11 High Alarm 0 2 1 - F115 0
2342 RRTD 2 - RTD #11 High Alarm Relays 0 7 1 - F113 2
2343 RRTD 2 - RTD #11 High Alarm Level 1 200 1 °C F1 130
2344 RRTD 2 - RTD #11 Alarm 0 2 1 - F115 02345 RRTD 2 - RTD #11 Alarm Relays 0 7 1 - F113 12346 RRTD 2 - RTD #11 Alarm Level 1 200 1 °C F1 130
2347 Record RRTD 2 - RTD #11 Alarms as Events 0 1 1 - F103 0
2348 RRTD 2 - RTD #11 Trip 0 2 1 - F115 0
2349 Enable RRTD 2 - RTD #11 Trip Voting 0 13 1 - F122 1
Table CG–10: MEMORY MAP (Sheet 49 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CGCOMMUNICATIONS GUIDE MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG103
234A RRTD 2 - RTD #11 Trip Relays 0 7 1 - F111 1234B RRTD 2 - RTD #11 Trip Level 1 200 1 °C F1 130234C RRTD 2 - RTD #11 RTD Type 0 3 1 - F120 0
2350 First Character of RRTD 2 - RTD #11 Name 32 127 1 - F1 ’R’
↓ ↓
2353 8th Character of RRTD 2 - RTD #11 Name 32 127 1 - F1 ’’
... ReservedRRTD 2 – RTD #12
2360 RRTD 2 - RTD #12 Application 0 4 1 - F121 02361 RRTD 2 - RTD #12 High Alarm 0 2 1 - F115 0
2362 RRTD 2 - RTD #12 High Alarm Relays 0 7 1 - F113 2
2363 RRTD 2 - RTD #12 High Alarm Level 1 200 1 °C F1 130
2364 RRTD 2 - RTD #12 Alarm 0 2 1 - F115 02365 RRTD 2 - RTD #12 Alarm Relays 0 7 1 - F113 12366 RRTD 2 - RTD #12 Alarm Level 1 200 1 °C F1 130
2367 Record RRTD 2 - RTD #12 Alarms as Events 0 1 1 - F103 0
2368 RRTD 2 - RTD #12 Trip 0 2 1 - F115 0
2369 Enable RRTD 2 - RTD #12 Trip Voting 0 13 1 - F122 1
236A RRTD 2 - RTD #12 Trip Relays 0 7 1 - F111 1236B RRTD 2 - RTD #12 Trip Level 1 200 1 °C F1 130236C RRTD 2 - RTD #12 RTD Type 0 3 1 - F120 0
2370 First Character of RRTD 2 - RTD #12 Name 32 127 1 - F1 ’R’
↓ ↓
2373 8th Character of RRTD 2 - RTD #12 Name 32 127 1 - F1 " "
... ReservedRRTD 2 – OPEN RTD ALARM
2380 RRTD B - Open RTD Alarm 0 2 1 - F115 02381 RRTD B - Assign Alarm Relays 0 7 1 - F113 12382 RRTD B - Open RTD Alarm Events 0 1 1 - F103 0
RRTD 2 – SHORT/LOW TEMPERATURE RTD ALARM
2383 RRTD B - Short / Low Temp RTD Alarm 0 2 1 - F115 0
2384 RRTD B - Assign Alarm Relays 0 7 1 - F113 1
2385 RRTD B - Short / Low Temp Alarm Events 0 1 1 - F103 0
... Reserved - - - - - -RRTD 3 – RTD #1
2400 RRTD 3 - RTD #1 Application 0 4 1 - F121 02401 RRTD 3 - RTD #1 High Alarm 0 2 1 - F115 0
2402 RRTD 3 - RTD #1 High Alarm Relays 0 7 1 - F113 2
2403 RRTD 3 - RTD #1 High Alarm Level 1 200 1 °C F1 130
2404 RRTD 3 - RTD #1 Alarm 0 2 1 - F115 02405 RRTD 3 - RTD #1 Alarm Relays 0 7 1 - F113 12406 RRTD 3 - RTD #1 Alarm Level 1 200 1 °C F1 130
Table CG–10: MEMORY MAP (Sheet 50 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CG104 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP CGCOMMUNICATIONS GUIDE
2407 Record RRTD 3 - RTD #1 Alarms as Events 0 1 1 - F103 0
2408 RRTD 3 - RTD #1 Trip 0 2 1 - F115 0
2409 Enable RRTD 3 - RTD #1 Trip Voting 0 13 1 - F122 1
240A RRTD 3 - RTD #1 Trip Relays 0 7 1 - F111 1240B RRTD 3 - RTD #1 Trip Level 1 200 1 °C F1 130240C RRTD 3 - RTD #1 RTD Type 0 3 1 - F120 0
2410 First Character of RRTD 3 - RTD #1 Name 32 127 1 - F1 ’R’
↓ ↓
2413 8th Character of RRTD 3 - RTD #1 Name 32 127 1 - F1 " "
2414 ReservedRRTD 3 – RTD #2
2420 RRTD 3 - RTD #2 Application 0 4 1 - F121 02421 RRTD 3 - RTD #2 High Alarm 0 2 1 - F115 0
2422 RRTD 3 - RTD #2 High Alarm Relays 0 7 1 - F113 2
2423 RRTD 3 - RTD #2 High Alarm Level 1 200 1 °C F1 130
2424 RRTD 3 - RTD #2 Alarm 0 2 1 - F115 02425 RRTD 3 - RTD #2 Alarm Relays 0 7 1 - F113 12426 RRTD 3 - RTD #2 Alarm Level 1 200 1 °C F1 130
2427 Record RRTD 3 - RTD #2 Alarms as Events 0 1 1 - F103 0
2428 RRTD 3 - RTD #2 Trip 0 2 1 - F115 0
2429 Enable RRTD 3 - RTD #2 Trip Voting 0 13 1 - F122 1
242A RRTD 3 - RTD #2 Trip Relays 0 7 1 - F111 1242B RRTD 3 - RTD #2 Trip Level 1 200 1 °C F1 130242C RRTD 3 - RTD #2 RTD Type 0 3 1 - F120 0
2430 First Character of RRTD 3 - RTD #2 Name 32 127 1 - F1 ’R’
↓ ↓
2433 8th Character of RRTD 3 - RTD #2 Name 32 127 1 - F1 " "
... ReservedRRTD 3 – RTD #3
2440 RRTD 3 - RTD #3 Application 0 4 1 - F121 02441 RRTD 3 - RTD #3 High Alarm 0 2 1 - F115 0
2442 RRTD 3 - RTD #3 High Alarm Relays 0 7 1 - F113 2
2443 RRTD 3 - RTD #3 High Alarm Level 1 200 1 °C F1 130
2444 RRTD 3 - RTD #3 Alarm 0 2 1 - F115 02445 RRTD 3 - RTD #3 Alarm Relays 0 7 1 - F113 12446 RRTD 3 - RTD #3 Alarm Level 1 200 1 °C F1 130
2447 Record RRTD 3 - RTD #3 Alarms as Events 0 1 1 - F103 0
2448 RRTD 3 - RTD #3 Trip 0 2 1 - F115 0
2449 Enable RRTD 3 - RTD #3 Trip Voting 0 13 1 - F122 1
244A RRTD 3 - RTD #3 Trip Relays 0 7 1 - F111 1
Table CG–10: MEMORY MAP (Sheet 51 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CGCOMMUNICATIONS GUIDE MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG105
244B RRTD 3 - RTD #3 Trip Level 1 200 1 °C F1 130244C RRTD 3 - RTD #3 RTD Type 0 3 1 - F120 0
2450 First Character of RRTD 3 - RTD # Name 32 127 1 - F1 ’R’
↓ ↓
2453 8th Character of RRTD 3 - RTD #3 Name 32 127 1 - F1 " "
... ReservedRRTD 3 – RTD #4
2460 RRTD 3 - RTD #4 Application 0 4 1 - F121 02461 RRTD 3 - RTD #4 High Alarm 0 2 1 - F115 0
2462 RRTD 3 - RTD #4 High Alarm Relays 0 7 1 - F113 2
2463 RRTD 3 - RTD #4 High Alarm Level 1 200 1 °C F1 130
2464 RRTD 3 - RTD #4 Alarm 0 2 1 - F115 02465 RRTD 3 - RTD #4 Alarm Relays 0 7 1 - F113 12466 RRTD 3 - RTD #4 Alarm Level 1 200 1 °C F1 130
2467 Record RRTD 3 - RTD #4 Alarms as Events 0 1 1 - F103 0
2468 RRTD 3 - RTD #4 Trip 0 2 1 - F115 0
2469 Enable RRTD 3 - RTD #4 Trip Voting 0 13 1 - F122 1
246A RRTD 3 - RTD #4 Trip Relays 0 7 1 - F111 1246B RRTD 3 - RTD #4 Trip Level 1 200 1 °C F1 130246C RRTD 3 - RTD #4 RTD Type 0 3 1 - F120 0
2470 First Character of RRTD 3 - RTD #4 Name 32 127 1 - F1 ’R’
↓ ↓
2473 8th Character of RRTD 3 - RTD #4 Name 32 127 1 - F1 " "
... ReservedRRTD 3 – RTD #5
2480 RRTD 3 - RTD #5 Application 0 4 1 - F121 02481 RRTD 3 - RTD #5 High Alarm 0 2 1 - F115 0
2482 RRTD 3 - RTD #5 High Alarm Relays 0 7 1 - F113 2
2483 RRTD 3 - RTD #5 High Alarm Level 1 200 1 °C F1 130
2484 RRTD 3 - RTD #5 Alarm 0 2 1 - F115 02485 RRTD 3 - RTD #5 Alarm Relays 0 7 1 - F113 12486 RRTD 3 - RTD #5 Alarm Level 1 200 1 °C F1 130
2487 Record RRTD 3 - RTD #5 Alarms as Events 0 1 1 - F103 0
2488 RRTD 3 - RTD #5 Trip 0 2 1 - F115 0
2489 Enable RRTD 3 - RTD #5 Trip Voting 0 13 1 - F122 1
248A RRTD 3 - RTD #5 Trip Relays 0 7 1 - F111 1248B RRTD 3 - RTD #5 Trip Level 1 200 1 °C F1 130248C RRTD 3 - RTD #5 RTD Type 0 3 1 - F120 0
2490 First Character of RRTD 3 - RTD #5 Name 32 127 1 - F1 ’R’
↓ ↓
Table CG–10: MEMORY MAP (Sheet 52 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CG106 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP CGCOMMUNICATIONS GUIDE
2493 8th Character of RRTD 3 - RTD #5 Name 32 127 1 - F1 " "
... ReservedRRTD 3 – RTD #6
24A0 RRTD 3 - RTD #6 Application 0 4 1 - F121 024A1 RRTD 3 - RTD #6 High Alarm 0 2 1 - F115 0
24A2 RRTD 3 - RTD #6 High Alarm Relays 0 7 1 - F113 1
24A3 RRTD 3 - RTD #6 High Alarm Level 1 200 1 °C F1 130
24A4 RRTD 3 - RTD #6 Alarm 0 2 1 - F115 024A5 RRTD 3 - RTD #6 Alarm Relays 0 7 1 - F113 124A6 RRTD 3 - RTD #6 Alarm Level 1 200 1 °C F1 130
24A7 Record RRTD 3 - RTD #6 Alarms as Events 0 1 1 - F103 0
24A8 RRTD 3 - RTD #6 Trip 0 2 1 - F115 0
24A9 Enable RRTD 3 - RTD #6 Trip Voting 0 13 1 - F122 1
24AA RRTD 3 - RTD #6 Trip Relays 0 7 1 - F111 124AB RRTD 3 - RTD #6 Trip Level 1 200 1 °C F1 13024AC RRTD 3 - RTD #6 RTD Type 0 3 1 - F120 0
24B0 First Character of RRTD 3 - RTD #6 Name 32 127 1 - F1 ’R’
↓ ↓
24B3 8th Character of RRTD 3 - RTD #6 Name 32 127 1 - F1 " "
... ReservedRRTD 3 – RTD #7
24C0 RRTD 3 - RTD #7 Application 0 4 1 - F121 024C1 RRTD 3 - RTD #7 High Alarm 0 2 1 - F115 0
24C2 RRTD 3 - RTD #7 High Alarm Relays 0 7 1 - F113 2
24C3 RRTD 3 - RTD #7 High Alarm Level 1 200 1 °C F1 130
24C4 RRTD 3 - RTD #7 Alarm 0 2 1 - F115 024C5 RRTD 3 - RTD #7 Alarm Relays 0 7 1 - F113 124C6 RRTD 3 - RTD #7 Alarm Level 1 200 1 °C F1 130
24C7 Record RRTD 3 - RTD #7 Alarms as Events 0 1 1 - F103 0
24C8 RRTD 3 - RTD #7 Trip 0 2 1 - F115 0
24C9 Enable RRTD 3 - RTD #7 Trip Voting 0 13 1 - F122 1
24CA RRTD 3 - RTD #7 Trip Relays 0 7 1 - F111 124CB RRTD 3 - RTD #7 Trip Level 1 200 1 °C F1 13024CC RRTD 3 - RTD #7 RTD Type 0 3 1 - F120 0
24D0 First Character of RRTD 3 - RTD #7 Name 32 127 1 - F1 ’R’
↓ ↓
24D3 8th Character of RRTD 3 - RTD #7 Name 32 127 1 - F1 " "
... ReservedRRTD 3 – RTD #8
24E0 RRTD 3 - RTD #8 Application 0 4 1 - F121 024E1 RRTD 3 - RTD #8 High Alarm 0 2 1 - F115 0
Table CG–10: MEMORY MAP (Sheet 53 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CGCOMMUNICATIONS GUIDE MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG107
24E2 RRTD 3 - RTD #8 High Alarm Relays 0 7 1 - F113 2
24E3 RRTD 3 - RTD #8 High Alarm Level 1 200 1 °C F1 130
24E4 RRTD 3 - RTD #8 Alarm 0 2 1 - F115 024E5 RRTD 3 - RTD #8 Alarm Relays 0 7 1 - F113 124E6 RRTD 3 - RTD #8 Alarm Level 1 200 1 °C F1 130
24E7 Record RRTD 3 - RTD #8 Alarms as Events 0 1 1 - F103 0
24E8 RRTD 3 - RTD #8 Trip 0 2 1 - F115 0
24E9 Enable RRTD 3 - RTD #8 Trip Voting 0 13 1 - F122 1
24EA RRTD 3 - RTD #8 Trip Relays 0 7 1 - F111 124EB RRTD 3 - RTD #8 Trip Level 1 200 1 °C F1 13024EC RRTD 3 - RTD #8 RTD Type 0 3 1 - F120 0
24F0 First Character of RRTD 3 - RTD #8 Name 32 127 1 - F1 ’R’
↓ ↓
24F3 8th Character of RRTD 3 - RTD #8 Name 32 127 1 - F1 " "
... ReservedRRTD 3 – RTD #9
2500 RRTD 3 - RTD #9 Application 0 4 1 - F121 02501 RRTD 3 - RTD #9 High Alarm 0 2 1 - F115 0
2502 RRTD 3 - RTD #9 High Alarm Relays 0 7 1 - F113 2
2503 RRTD 3 - RTD #9 High Alarm Level 1 200 1 °C F1 130
2504 RRTD 3 - RTD #9 Alarm 0 2 1 - F115 02505 RRTD 3 - RTD #9 Alarm Relays 0 7 1 - F113 12506 RRTD 3 - RTD #9 Alarm Level 1 200 1 °C F1 130
2507 Record RRTD 3 - RTD #9 Alarms as Events 0 1 1 - F103 0
2508 RRTD 3 - RTD #9 Trip 0 2 1 - F115 0
2509 Enable RRTD 3 - RTD #9 Trip Voting 0 13 1 - F122 1
250A RRTD 3 - RTD #9 Trip Relays 0 7 1 - F111 1250B RRTD 3 - RTD #9 Trip Level 1 200 1 °C F1 130250C RRTD 3 - RTD #9 RTD Type 0 3 1 - F120 0
2510 First Character of RRTD 3 - RTD #9 Name 32 127 1 - F1 ’R’
↓ ↓
2513 8th Character of RRTD 3 - RTD #9 Name 32 127 1 - F1 " "
... ReservedRRTD 3 – RTD #10
2520 RRTD 3 - RTD #10 Application 0 4 1 - F121 02521 RRTD 3 - RTD #10 High Alarm 0 2 1 - F115 0
2522 RRTD 3 - RTD #10 High Alarm Relays 0 7 1 - F113 2
2523 RRTD 3 - RTD #10 High Alarm Level 1 200 1 °C F1 130
2524 RRTD 3 - RTD #10 Alarm 0 2 1 - F115 02525 RRTD 3 - RTD #10 Alarm Relays 0 7 1 - F113 1
Table CG–10: MEMORY MAP (Sheet 54 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CG108 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP CGCOMMUNICATIONS GUIDE
2526 RRTD 3 - RTD #10 Alarm Level 1 200 1 °C F1 130
2527 Record RRTD 3 - RTD #10 Alarms as Events 0 1 1 - F103 0
2528 RRTD 3 - RTD #10 Trip 0 2 1 - F115 0
2529 Enable RRTD 3 - RTD#10 Trip Voting 0 13 1 - F122 1
252A RRTD 3 - RTD #10 Trip Relays 0 7 1 - F111 1252B RRTD 3 - RTD #10 Trip Level 1 200 1 °C F1 130252C RRTD 3 - RTD #10 RTD Type 0 3 1 - F120 0
2530 First Character of RRTD 3 - RTD #10 Name 32 127 1 - F1 ’R’
↓ ↓
2533 8th Character of RRTD 3 - RTD #10 Name 32 127 1 - F1 " "
... ReservedRRTD 3 – RTD #11
2540 RRTD 3 - RTD #11 Application 0 4 1 - F121 02541 RRTD 3 - RTD #11 High Alarm 0 2 1 - F115 0
2542 RRTD 3 - RTD #11 High Alarm Relays 0 7 1 - F113 2
2543 RRTD 3 - RTD #11 High Alarm Level 1 200 1 °C F1 130
2544 RRTD 3 - RTD #11 Alarm 0 2 1 - F115 02545 RRTD 3 - RTD #11 Alarm Relays 0 7 1 - F113 12546 RRTD 3 - RTD #11 Alarm Level 1 200 1 °C F1 130
2547 Record RRTD 3 - RTD #11 Alarms as Events 0 1 1 - F103 0
2548 RRTD 3 - RTD #11 Trip 0 2 1 - F115 0
2549 Enable RRTD 3 - RTD #11 Trip Voting 0 13 1 - F122 1
254A RRTD 3 - RTD #11 Trip Relays 0 7 1 - F111 1254B RRTD 3 - RTD #11 Trip Level 1 200 1 °C F1 130254C RRTD 3 - RTD #11 RTD Type 0 3 1 - F120 0
2550 First Character of RRTD 3 - RTD #11 Name 32 127 1 - F1 ’R’
↓ ↓
2553 8th Character of RRTD 3 - RTD #11 Name 32 127 1 - F1 " "
... ReservedRRTD 3 – RTD #12
2560 RRTD 3 - RTD #12 Application 0 4 1 - F121 02561 RRTD 3 - RTD #12 High Alarm 0 2 1 - F115 0
2562 RRTD 3 - RTD #12 High Alarm Relays 0 7 1 - F113 2
2563 RRTD 3 - RTD #12 High Alarm Level 1 200 1 °C F1 130
2564 RRTD 3 - RTD #12 Alarm 0 2 1 - F115 02565 RRTD 3 - RTD #12 Alarm Relays 0 7 1 - F113 12566 RRTD 3 - RTD #12 Alarm Level 1 200 1 °C F1 130
2567 Record RRTD 3 - RTD #12 Alarms as Events 0 1 1 - F103 0
2568 RRTD 3 - RTD #12 Trip 0 2 1 - F115 0
2569 Enable RRTD 3 - RTD #12 Trip Voting 0 13 1 - F122 1
Table CG–10: MEMORY MAP (Sheet 55 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CGCOMMUNICATIONS GUIDE MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG109
256A RRTD 3 - RTD #12 Trip Relays 0 7 1 - F111 1256B RRTD 3 - RTD #12 Trip Level 1 200 1 °C F1 130256C RRTD 3 - RTD #12 RTD Type 0 3 1 - F120 0
2570 First Character of RRTD 3 - RTD #12 Name 32 127 1 - F1 ’R’
↓ ↓
2573 8th Character of RRTD 3 - RTD #12 Name 32 127 1 - F1 " "
... ReservedRRTD 3 – OPEN RTD ALARM
2580 RRTD 3 - Open RTD Alarm 0 2 1 - F115 02581 RRTD 3 - Assign Alarm Relays 0 7 1 - F113 12582 RRTD 3 - Open RTD Alarm Events 0 1 1 - F103 0
RRTD 3 – SHORT/LOW TEMPERATURE RTD ALARM
2583 RRTD 3 - Short / Low Temp RTD Alarm 0 2 1 - F115 0
2584 RRTD 3 - Assign Alarm Relays 0 7 1 - F113 1
2585 RRTD 3 - Short / Low Temp Alarm Events 0 1 1 - F103 0
... Reserved - - - - - -RRTD 4 – RTD #1
2600 RRTD 4 - RTD #1 Application 0 4 1 - F121 02601 RRTD 4 - RTD #1 High Alarm 0 2 1 - F115 0
2602 RRTD 4 - RTD #1 High Alarm Relays 0 7 1 - F113 2
2603 RRTD 4 - RTD #1 High Alarm Level 1 200 1 °C F1 130
2604 RRTD 4 - RTD #1 Alarm 0 2 1 - F115 02605 RRTD 4 - RTD #1 Alarm Relays 0 7 1 - F113 12606 RRTD 4 - RTD #1 Alarm Level 1 200 1 °C F1 130
2607 Record RRTD 4 - RTD #1 Alarms as Events 0 1 1 - F103 0
2608 RRTD 4 - RTD #1 Trip 0 2 1 - F115 0
2609 Enable RRTD 4 - RTD #1 Trip Voting 0 13 1 - F122 1
260A RRTD 4 - RTD #1 Trip Relays 0 7 1 - F111 1260B RRTD 4 - RTD #1 Trip Level 1 200 1 °C F1 130260C RRTD 4 - RTD #1 RTD Type 0 3 1 - F120 0
2610 First Character of RRTD 4 - RTD #1 Name 32 127 1 - F1 ’R’
↓ ↓
2613 8th Character of RRTD 4 - RTD #1 Name 32 127 1 - F1 " "
.... ReservedRRTD 4 – RTD #2
2620 RRTD 4 - RTD #2 Application 0 4 1 - F121 02621 RRTD 4 - RTD #2 High Alarm 0 2 1 - F115 0
2622 RRTD 4 - RTD #2 High Alarm Relays 0 7 1 - F113 2
2623 RRTD 4 - RTD #2 High Alarm Level 1 200 1 °C F1 130
2624 RRTD 4 - RTD #2 Alarm 0 2 1 - F115 02625 RRTD 4 - RTD #2 Alarm Relays 0 7 1 - F113 12626 RRTD 4 - RTD #2 Alarm Level 1 200 1 °C F1 130
Table CG–10: MEMORY MAP (Sheet 56 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CG110 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP CGCOMMUNICATIONS GUIDE
2627 Record RRTD 4 - RTD #2 Alarms as Events 0 1 1 - F103 0
2628 RRTD 4 - RTD #2 Trip 0 2 1 - F115 0
2629 Enable A Remote RTD #2 Trip Voting 0 13 1 - F122 1
262A RRTD 4 - RTD #2 Trip Relays 0 7 1 - F111 1262B RRTD 4 - RTD #2 Trip Level 1 200 1 °C F1 130262C RRTD 4 - RTD #2 RTD Type 0 3 1 - F120 0
2630 First Character of RRTD 4 - RTD #2 Name 32 127 1 - F1 ’R’
↓ ↓
2633 8th Character of RRTD 4 - RTD #2 Name 32 127 1 - F1 " "
... ReservedRRTD 4 – RTD #3
2640 RRTD 4 - RTD #3 Application 0 4 1 - F121 02641 RRTD 4 - RTD #3 High Alarm 0 2 1 - F115 0
2642 RRTD 4 - RTD #3 High Alarm Relays 0 7 1 - F113 2
2643 RRTD 4 - RTD #3 High Alarm Level 1 200 1 °C F1 130
2644 RRTD 4 - RTD #3 Alarm 0 2 1 - F115 02645 RRTD 4 - RTD #3 Alarm Relays 0 7 1 - F113 12646 RRTD 4 - RTD #3 Alarm Level 1 200 1 °C F1 130
2647 Record RRTD 4 - RTD #3 Alarms as Events 0 1 1 - F103 0
2648 RRTD 4 - RTD #3 Trip 0 2 1 - F115 0
2649 Enable RRTD 4 - RTD #3 Trip Voting 0 13 1 - F122 1
264A RRTD 4 - RTD #3 Trip Relays 0 7 1 - F111 1264B RRTD 4 - RTD #3 Trip Level 1 200 1 °C F1 130264C RRTD 4 - RTD #3 RTD Type 0 3 1 - F120 0
2650 First Character of RRTD 4 - RTD # Name 32 127 1 - F1 ’R’
↓ ↓
2653 8th Character of RRTD 4 - RTD #3 Name 32 127 1 - F1 " "
... ReservedRRTD 4 – RTD #4
2660 RRTD 4 - RTD #4 Application 0 4 1 - F121 02661 RRTD 4 - RTD #4 High Alarm 0 2 1 - F115 0
2662 RRTD 4 - RTD #4 High Alarm Relays 0 7 1 - F113 2
2663 RRTD 4 - RTD #4 High Alarm Level 1 200 1 °C F1 130
2664 RRTD 4 - RTD #4 Alarm 0 2 1 - F115 02665 RRTD 4 - RTD #4 Alarm Relays 0 7 1 - F113 12666 RRTD 4 - RTD #4 Alarm Level 1 200 1 °C F1 130
2667 Record RRTD 4 - RTD #4 Alarms as Events 0 1 1 - F103 0
2668 RRTD 4 - RTD #4 Trip 0 2 1 - F115 0
2669 Enable RRTD 4 - RTD #4 Trip Voting 0 13 1 - F122 1
266A RRTD 4 - RTD #4 Trip Relays 0 7 1 - F111 1
Table CG–10: MEMORY MAP (Sheet 57 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CGCOMMUNICATIONS GUIDE MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG111
266B RRTD 4 - RTD #4 Trip Level 1 200 1 °C F1 130266C RRTD 4 - RTD #4 RTD Type 0 3 1 - F120 0
2670 First Character of RRTD 4 - RTD #4 Name 32 127 1 - F1 ’R’
↓ ↓
2673 8th Character of RRTD 4 - RTD #4 Name 32 127 1 - F1 " "
... ReservedRRTD 4 – RTD #5
2680 RRTD 4 - RTD #5 Application 0 4 1 - F121 02681 RRTD 4 - RTD #5 High Alarm 0 2 1 - F115 0
2682 RRTD 4 - RTD #5 High Alarm Relays 0 7 1 - F113 2
2683 RRTD 4 - RTD #5 High Alarm Level 1 200 1 °C F1 130
2684 RRTD 4 - RTD #5 Alarm 0 2 1 - F115 02685 RRTD 4 - RTD #5 Alarm Relays 0 7 1 - F113 12686 RRTD 4 - RTD #5 Alarm Level 1 200 1 °C F1 130
2687 Record RRTD 4 - RTD #5 Alarms as Events 0 1 1 - F103 0
2688 RRTD 4 - RTD #5 Trip 0 2 1 - F115 0
2689 Enable RRTD 4 - RTD #5 Trip Voting 0 13 1 - F122 1
268A RRTD 4 - RTD #5 Trip Relays 0 7 1 - F111 1268B RRTD 4 - RTD #5 Trip Level 1 200 1 °C F1 130268C RRTD 4 - RTD #5 RTD Type 0 3 1 - F120 0
2690 First Character of RRTD 4 - RTD #5 Name 32 127 1 - F1 ’R’
↓ ↓
2693 8th Character of RRTD 4 - RTD #5 Name 32 127 1 - F1 " "
... ReservedRRTD 4 – RTD #6
26A0 RRTD 4 - RTD #6 Application 0 4 1 - F121 026A1 RRTD 4 - RTD #6 High Alarm 0 2 1 - F115 0
26A2 RRTD 4 - RTD #6 High Alarm Relays 0 7 1 - F113 1
26A3 RRTD 4 - RTD #6 High Alarm Level 1 200 1 °C F1 130
26A4 RRTD 4 - RTD #6 Alarm 0 2 1 - F115 026A5 RRTD 4 - RTD #6 Alarm Relays 0 7 1 - F113 126A6 RRTD 4 - RTD #6 Alarm Level 1 200 1 °C F1 130
26A7 Record RRTD 4 - RTD #6 Alarms as Events 0 1 1 - F103 0
26A8 RRTD 4 - RTD #6 Trip 0 2 1 - F115 0
26A9 Enable RRTD 4 - RTD #6 Trip Voting 0 13 1 - F122 1
26AA RRTD 4 - RTD #6 Trip Relays 0 7 1 - F111 126AB RRTD 4 - RTD #6 Trip Level 1 200 1 °C F1 13026AC RRTD 4 - RTD #6 RTD Type 0 3 1 - F120 0
26B0 First Character of RRTD 4 - RTD #6 Name 32 127 1 - F1 ’R’
↓ ↓
Table CG–10: MEMORY MAP (Sheet 58 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CG112 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP CGCOMMUNICATIONS GUIDE
26B3 8th Character of RRTD 4 - RTD #6 Name 32 127 1 - F1 " "
... ReservedRRTD 4 – RTD #7
26C0 RRTD 4 - RTD #7 Application 0 4 1 - F121 026C1 RRTD 4 - RTD #7 High Alarm 0 2 1 - F115 0
26C2 RRTD 4 - RTD #7 High Alarm Relays 0 7 1 - F113 2
26C3 RRTD 4 - RTD #7 High Alarm Level 1 200 1 °C F1 130
26C4 RRTD 4 - RTD #7 Alarm 0 2 1 - F115 026C5 RRTD 4 - RTD #7 Alarm Relays 0 7 1 - F113 126C6 RRTD 4 - RTD #7 Alarm Level 1 200 1 °C F1 130
26C7 Record RRTD 4 - RTD #7 Alarms as Events 0 1 1 - F103 0
26C8 RRTD 4 - RTD #7 Trip 0 2 1 - F115 0
26C9 Enable RRTD 4 - RTD #7 Trip Voting 0 13 1 - F122 1
26CA RRTD 4 - RTD #7 Trip Relays 0 7 1 - F111 126CB RRTD 4 - RTD #7 Trip Level 1 200 1 °C F1 13026CC RRTD 4 - RTD #7 RTD Type 0 3 1 - F120 0
26D0 First Character of RRTD 4 - RTD #7 Name 32 127 1 - F1 ’R’
↓ ↓
26D3 8th Character of RRTD 4 - RTD #7 Name 32 127 1 - F1 " "
... ReservedRRTD 4 – RTD #8
26E0 RRTD 4 - RTD #8 Application 0 4 1 - F121 026E1 RRTD 4 - RTD #8 High Alarm 0 2 1 - F115 0
26E2 RRTD 4 - RTD #8 High Alarm Relays 0 7 1 - F113 2
26E3 RRTD 4 - RTD #8 High Alarm Level 1 200 1 °C F1 130
26E4 RRTD 4 - RTD #8 Alarm 0 2 1 - F115 026E5 RRTD 4 - RTD #8 Alarm Relays 0 7 1 - F113 126E6 RRTD 4 - RTD #8 Alarm Level 1 200 1 °C F1 130
26E7 Record RRTD 4 - RTD #8 Alarms as Events 0 1 1 - F103 0
26E8 RRTD 4 - RTD #8 Trip 0 2 1 - F115 0
26E9 Enable RRTD 4 - RTD #8 Trip Voting 0 13 1 - F122 1
26EA RRTD 4 - RTD #8 Trip Relays 0 7 1 - F111 126EB RRTD 4 - RTD #8 Trip Level 1 200 1 °C F1 13026EC RRTD 4 - RTD #8 RTD Type 0 3 1 - F120 0
26F0 First Character of RRTD 4 - RTD #8 Name 32 127 1 - F1 ’R’
↓ ↓
26F3 8th Character of RRTD 4 - RTD #8 Name 32 127 1 - F1 " "
... ReservedRRTD 4 – RTD #9
2700 RRTD 4 - RTD #9 Application 0 4 1 - F121 02701 RRTD 4 - RTD #9 High Alarm 0 2 1 - F115 0
Table CG–10: MEMORY MAP (Sheet 59 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CGCOMMUNICATIONS GUIDE MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG113
2702 RRTD 4 - RTD #9 High Alarm Relays 0 7 1 - F113 2
2703 RRTD 4 - RTD #9 High Alarm Level 1 200 1 °C F1 130
2704 RRTD 4 - RTD #9 Alarm 0 2 1 - F115 02705 RRTD 4 - RTD #9 Alarm Relays 0 7 1 - F113 12706 RRTD 4 - RTD #9 Alarm Level 1 200 1 °C F1 130
2707 Record RRTD 4 - RTD #9 Alarms as Events 0 1 1 - F103 0
2708 RRTD 4 - RTD #9 Trip 0 2 1 - F115 0
2709 Enable RRTD 4 - RTD #9 Trip Voting 0 13 1 - F122 1
270A RRTD 4 - RTD #9 Trip Relays 0 7 1 - F111 1270B RRTD 4 - RTD #9 Trip Level 1 200 1 °C F1 130270C RRTD 4 - RTD #9 RTD Type 0 3 1 - F120 0
2710 First Character of RRTD 4 - RTD #9 Name 32 127 1 - F1 ’R’
↓ ↓
2713 8th Character of RRTD 4 - RTD #9 Name 32 127 1 - F1 " "
... ReservedRRTD 4 – RTD #10
2720 RRTD 4 - RTD #10 Application 0 4 1 - F121 02721 RRTD 4 - RTD #10 High Alarm 0 2 1 - F115 0
2722 RRTD 4 - RTD #10 High Alarm Relays 0 7 1 - F113 2
2723 RRTD 4 - RTD #10 High Alarm Level 1 200 1 °C F1 130
2724 RRTD 4 - RTD #10 Alarm 0 2 1 - F115 02725 RRTD 4 - RTD #10 Alarm Relays 0 7 1 - F113 12726 RRTD 4 - RTD #10 Alarm Level 1 200 1 °C F1 130
2727 Record RRTD 4 - RTD #10 Alarms as Events 0 1 1 - F103 0
2728 RRTD 4 - RTD #10 Trip 0 2 1 - F115 0
2729 Enable RRTD 4 - RTD#10 Trip Voting 0 13 1 - F122 1
272A RRTD 4 - RTD #10 Trip Relays 0 7 1 - F111 1272B RRTD 4 - RTD #10 Trip Level 1 200 1 °C F1 130272C RRTD 4 - RTD #10 RTD Type 0 3 1 - F120 0
2730 First Character of RRTD 4 - RTD #10 Name 32 127 1 - F1 ’R’
↓ ↓
2733 8th Character of RRTD 4 - RTD #10 Name 32 127 1 - F1 " "
... ReservedRRTD 4 – RTD #11
2740 RRTD 4 - RTD #11 Application 0 4 1 - F121 02741 RRTD 4 - RTD #11 High Alarm 0 2 1 - F115 0
2742 RRTD 4 - RTD #11 High Alarm Relays 0 7 1 - F113 2
2743 RRTD 4 - RTD #11 High Alarm Level 1 200 1 °C F1 130
2744 RRTD 4 - RTD #11 Alarm 0 2 1 - F115 02745 RRTD 4 - RTD #11 Alarm Relays 0 7 1 - F113 1
Table CG–10: MEMORY MAP (Sheet 60 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CG114 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP CGCOMMUNICATIONS GUIDE
2746 RRTD 4 - RTD #11 Alarm Level 1 200 1 °C F1 130
2747 Record RRTD 4 - RTD #11 Alarms as Events 0 1 1 - F103 0
2748 RRTD 4 - RTD #11 Trip 0 2 1 - F115 0
2749 Enable RRTD 4 - RTD #11 Trip Voting 0 13 1 - F122 1
274A RRTD 4 - RTD #11 Trip Relays 0 7 1 - F111 1274B RRTD 4 - RTD #11 Trip Level 1 200 1 °C F1 130274C RRTD 4 - RTD #11 RTD Type 0 3 1 - F120 0
2750 First Character of RRTD 4 - RTD #11 Name 32 127 1 - F1 ’R’
↓ ↓
2753 8th Character of RRTD 4 - RTD #11 Name 32 127 1 - F1 " "
... ReservedRRTD 4 – RTD #12
2760 RRTD 4 - RTD #12 Application 0 4 1 - F121 02761 RRTD 4 - RTD #12 High Alarm 0 2 1 - F115 0
2762 RRTD 4 - RTD #12 High Alarm Relays 0 7 1 - F113 2
2763 RRTD 4 - RTD #12 High Alarm Level 1 200 1 °C F1 130
2764 RRTD 4 - RTD #12 Alarm 0 2 1 - F115 02765 RRTD 4 - RTD #12 Alarm Relays 0 7 1 - F113 12766 RRTD 4 - RTD #12 Alarm Level 1 200 1 °C F1 130
2767 Record RRTD 4 - RTD #12 Alarms as Events 0 1 1 - F103 0
2768 RRTD 4 - RTD #12 Trip 0 2 1 - F115 0
2769 Enable RRTD 4 - RTD #12 Trip Voting 0 13 1 - F122 1
276A RRTD 4 - RTD #12 Trip Relays 0 7 1 - F111 1276B RRTD 4 - RTD #12 Trip Level 1 200 1 °C F1 130276C RRTD 4 - RTD #12 RTD Type 0 3 1 - F120 0
2770 First Character of RRTD 4 - RTD #12 Name 32 127 1 - F1 ’R’
↓ ↓
2773 8th Character of RRTD 4 - RTD #12 Name 32 127 1 - F1 " "
... ReservedRRTD 4 – OPEN RTD ALARM
2780 RRTD 4- Open RTD Alarm 0 2 1 - F115 02781 RRTD 4 - Assign Alarm Relays 0 7 1 - F113 12782 RRTD 4 - Open RTD Alarm Events 0 1 1 - F103 0
RRTD 4 – SHORT/LOW TEMPERATURE RTD ALARM
2783 RRTD 4 - Short / Low Temp RTD Alarm 0 2 1 - F115 0
2784 RRTD 4 - Assign Alarm Relays 0 7 1 - F113 1
2785 RRTD 4 - Short / Low Temp Alarm Events 0 1 1 - F103 0
... Reserved - - - - - -RRTD 1 – OUTPUT RELAY SETUP
27A0 Trip Relay Reset Mode 0 2 1 - F117 027A1 Alarm Relay Reset Mode 0 2 1 - F117 027A2 Aux 1 Relay Reset Mode 0 2 1 - F117 0
Table CG–10: MEMORY MAP (Sheet 61 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CGCOMMUNICATIONS GUIDE MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG115
27A3 Aux 2 Relay Reset Mode 0 2 1 - F117 027A4 Trip Relay Operation 0 1 1 - F161 027A5 Alarm Relay Operation 0 1 1 - F161 127A6 Aux1 Relay Operation 0 1 1 - F161 127A7 Aux2 Relay Operation 0 1 1 - F161 0... Reserved
RRTD 2 – OUTPUT RELAY SETUP
27B0 Trip Relay Reset Mode 0 2 1 - F117 027B1 Alarm Relay Reset Mode 0 2 1 - F117 027B2 Aux 1 Relay Reset Mode 0 2 1 - F117 027B3 Aux 2 Relay Reset Mode 0 2 1 - F117 027B4 Trip Relay Operation 0 1 1 - F161 027B5 Alarm Relay Operation 0 1 1 - F161 127B6 Aux1 Relay Operation 0 1 1 - F161 127B7 Aux2 Relay Operation 0 1 1 - F161 0... Reserved
RRTD 3 – OUTPUT RELAY SETUP
27C0 Trip Relay Reset Mode 0 2 1 - F117 027C1 Alarm Relay Reset Mode 0 2 1 - F117 027C2 Aux 1 Relay Reset Mode 0 2 1 - F117 027C3 Aux 2 Relay Reset Mode 0 2 1 - F117 027C4 Trip Relay Operation 0 1 1 - F161 027C5 Alarm Relay Operation 0 1 1 - F161 127C6 Aux1 Relay Operation 0 1 1 - F161 127C7 Aux2 Relay Operation 0 1 1 - F161 0... Reserved
RRTD 4 – OUTPUT RELAY SETUP
27D0 Trip Relay Reset Mode 0 2 1 - F117 027D1 Alarm Relay Reset Mode 0 2 1 - F117 027D2 Aux 1 Relay Reset Mode 0 2 1 - F117 027D3 Aux 2 Relay Reset Mode 0 2 1 - F117 027D4 Trip Relay Operation 0 1 1 - F161 027D5 Alarm Relay Operation 0 1 1 - F161 127D6 Aux1 Relay Operation 0 1 1 - F161 127D7 Aux2 Relay Operation 0 1 1 - F161 0... Reserved
RRTD 1 – ANALOG OUTPUTS
27E0 Enable Analog Output 1 0 1 1 - F103 0
27E1 Assign Analog Output 1 Output Range 0 2 1 - F26 0
27E2 Assign Analog Output 1 Parameter 12 24 1 - F127 13
27E3 Analog Output 1 Minimum -40 200 1 - F4 -4027E4 Analog Output 1 Maximum -40 200 1 - F4 20027E5 Enable Analog Output 2 0 1 1 - F103 0
27E6 Assign Analog Output 2 Output Range 0 2 1 - F26 0
27E7 Assign Analog Output 2 Parameter 12 24 1 - F127 13
27E8 Analog Output 2 Minimum -40 200 1 - F4 -4027E9 Analog Output 2 Maximum -40 200 1 - F4 200
Table CG–10: MEMORY MAP (Sheet 62 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CG116 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP CGCOMMUNICATIONS GUIDE
27EA Enable Analog Output 3 0 1 1 - F103 0
27EB Assign Analog Output 3 Output Range 0 2 1 - F26 0
27EC Assign Analog Output 3 Parameter 12 24 1 - F127 13
27ED Analog Output 3 Minimum -40 200 1 - F4 -4027EE Analog Output 3 Maximum -40 200 1 - F4 20027EF Enable Analog Output 4 0 1 1 - F103 0
27F0 Assign Analog Output 4 Output Range 0 2 1 - F26 0
27F1 Assign Analog Output 4 Parameter 12 24 1 - F127 13
27F2 Analog Output 4 Minimum -40 200 1 - F4 -4027F3 Analog Output 4 Maximum -40 200 1 - F4 200... Reserved
RRTD 2 – ANALOG OUTPUTS
2800 Enable Analog Output 1 0 1 1 - F103 0
2801 Assign Analog Output 1 Output Range 0 2 1 - F26 0
2802 Assign Analog Output 1 Parameter 12 24 1 - F127 13
2803 Analog Output 1 Minimum -40 200 1 - F4 -402804 Analog Output 1 Maximum -40 200 1 - F4 2002805 Enable Analog Output 2 0 1 1 - F103 0
2806 Assign Analog Output 2 Output Range 0 2 1 - F26 0
2807 Assign Analog Output 2 Parameter 12 24 1 - F127 13
2808 Analog Output 2 Minimum -40 200 1 - F4 -402809 Analog Output 2 Maximum -40 200 1 - F4 200280A Enable Analog Output 3 0 1 1 - F103 0
280B Assign Analog Output 3 Output Range 0 2 1 - F26 0
280C Assign Analog Output 3 Parameter 12 24 1 - F127 13
280D Analog Output 3 Minimum -40 200 1 - F4 -40280E Analog Output 3 Maximum -40 200 1 - F4 200280F Enable Analog Output 4 0 1 1 - F103 0
2810 Assign Analog Output 4 Output Range 0 2 1 - F26 0
2811 Assign Analog Output 4 Parameter 12 24 1 - F127 13
2812 Analog Output 4 Minimum -40 200 1 - F4 -402813 Analog Output 4 Maximum -40 200 1 - F4 200... Reserved
RRTD 3 – ANALOG OUTPUTS
2820 Enable Analog Output 1 0 1 1 - F103 0
2821 Assign Analog Output 1 Output Range 0 2 1 - F26 0
2822 Assign Analog Output 1 Parameter 12 24 1 - F127 13
2823 Analog Output 1 Minimum -40 200 1 - F4 -402824 Analog Output 1 Maximum -40 200 1 - F4 2002825 Enable Analog Output 2 0 1 1 - F103 0
Table CG–10: MEMORY MAP (Sheet 63 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CGCOMMUNICATIONS GUIDE MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG117
2826 Assign Analog Output 2 Output Range 0 2 1 - F26 0
2827 Assign Analog Output 2 Parameter 12 24 1 - F127 13
2828 Analog Output 2 Minimum -40 200 1 - F4 -402829 Analog Output 2 Maximum -40 200 1 - F4 200282A Enable Analog Output 3 0 1 1 - F103 0
282B Assign Analog Output 3 Output Range 0 2 1 - F26 0
282C Assign Analog Output 3 Parameter 12 24 1 - F127 13
282D Analog Output 3 Minimum -40 200 1 - F4 -40282E Analog Output 3 Maximum -40 200 1 - F4 200282F Enable Analog Output 4 0 1 1 - F103 0
2830 Assign Analog Output 4 Output Range 0 2 1 - F26 0
2831 Assign Analog Output 4 Parameter 12 24 1 - F127 13
2832 Analog Output 4 Minimum -40 200 1 - F4 -402833 Analog Output 4 Maximum -40 200 1 - F4 200... Reserved
RRTD 4 – ANALOG OUTPUTS
2840 Enable Analog Output 1 0 1 1 - F103 0
2841 Assign Analog Output 1 Output Range 0 2 1 - F26 0
2842 Assign Analog Output 1 Parameter 12 24 1 - F127 13
2843 Analog Output 1 Minimum -40 200 1 - F4 -402844 Analog Output 1 Maximum -40 200 1 - F4 2002845 Enable Analog Output 2 0 1 1 - F103 0
2846 Assign Analog Output 2 Output Range 0 2 1 - F26 0
2847 Assign Analog Output 2 Parameter 12 24 1 - F127 13
2848 Analog Output 2 Minimum -40 200 1 - F4 -402849 Analog Output 2 Maximum -40 200 1 - F4 200284A Enable Analog Output 3 0 1 1 - F103 0
284B Assign Analog Output 3 Output Range 0 2 1 - F26 0
284C Assign Analog Output 3 Parameter 12 24 1 - F127 13
284D Analog Output 3 Minimum -40 200 1 - F4 -40284E Analog Output 3 Maximum -40 200 1 - F4 200284F Enable Analog Output 4 0 1 1 - F103 0
2850 Assign Analog Output 4 Output Range 0 2 1 - F26 0
2851 Assign Analog Output 4 Parameter 12 24 1 - F127 13
2852 Analog Output 4 Minimum -40 200 1 - F4 -402853 Analog Output 4 Maximum -40 200 1 - F4 2002854 Reserved
RRTD 1 – DIGITAL INPUT 2
2860 1st & 2nd Character of Digital Input 2 Name 32 127 1 - F22 ’GE’
Table CG–10: MEMORY MAP (Sheet 64 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CG118 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP CGCOMMUNICATIONS GUIDE
↓ ↓
2865 11th & 12th Character of Digital Input 2 Name 32 127 1 - F22 ’GE’
2870 Digital Input 2 Type 0 1 1 - F116 02871 Reserved2872 Digital Input 2 Alarm 0 2 1 - F115 02873 Digital Input 2 Alarm Relays 0 6 1 - F113 02874 Digital Input 2 Alarm Delay 1 50000 1 100ms F2 502875 Digital Input 2 Alarm Events 0 1 1 - F103 02876 Digital Input 2 Trip 0 2 1 - F115 02877 Digital Input 2 Trip Relays 0 6 1 - F111 02878 Digital Input 2 Trip Delay 1 50000 1 100ms F2 50
2879 Digital Input 2 Assignable Function 0 3 1 - F163 0
--- ReservedRRTD 1 – DIGITAL INPUT 5
2880 1st & 2nd Character of Digital Input 5 Name 32 127 1 - F22 ’GE’
↓ ↓
2885 11th & 12th Character of Digital Input 5 Name 32 127 1 - F22 ’GE’
2890 Digital Input 5 Type 0 1 1 - F116 02891 Reserved2892 Digital Input 5 Alarm 0 2 1 - F115 02893 Digital Input 5 Alarm Relays 0 6 1 - F113 02894 Digital Input 5 Alarm Delay 1 50000 1 100ms F2 502895 Digital Input 5 Alarm Events 0 1 1 - F103 02896 Digital Input 5 Trip 0 2 1 - F115 02897 Digital Input 5 Trip Relays 0 6 1 - F111 02898 Digital Input 5 Trip Delay 1 50000 1 100ms F2 50
2899 Digital Input 5 Assignable Function 0 3 1 - F163 0
... ReservedRRTD 1 – DIGITAL INPUT 4
28A0 1st & 2nd Character of Digital Input 4 Name 32 127 1 - F22 ’GE’
↓ ↓
28A5 11th & 12th Character of Digital Input 4 Name 32 127 1 - F22 ’GE’
28B0 Digital Input 4 Type 0 1 1 - F116 028B1 Reserved28B2 Digital Input 4 Alarm 0 2 1 - F115 028B3 Digital Input 4 Alarm Relays 0 6 1 - F113 028B4 Digital Input 4 Alarm Delay 1 50000 1 100ms F2 5028B5 Digital Input 4 Alarm Events 0 1 1 - F103 028B6 Digital Input 4 Trip 0 2 1 - F115 028B7 Digital Input 4 Trip Relays 0 6 1 - F111 028B8 Digital Input 4 Trip Delay 1 50000 1 100ms F2 50
28B9 Digital Input 4 Assignable Function 0 3 1 - F163 0
... Reserved
Table CG–10: MEMORY MAP (Sheet 65 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CGCOMMUNICATIONS GUIDE MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG119
RRTD 1 – DIGITAL INPUT 1
28C0 1st & 2nd Character of Digital Input 1 Name 32 127 1 - F22 ’GE’
↓ ↓
28C5 11th & 12th Character of Digital Input 1 Name 32 127 1 - F22 ’GE’
28D0 Digital Input 1 Type 0 1 1 - F116 028D1 Reserved28D2 Digital Input 1 Alarm 0 2 1 - F115 028D3 Digital Input 1 Alarm Relays 0 6 1 - F113 028D4 Digital Input 1 Alarm Delay 1 50000 1 100ms F2 5028D5 Digital Input 1 Alarm Events 0 1 1 - F103 028D6 Digital Input 1 Trip 0 2 1 - F115 028D7 Digital Input 1 Trip Relays 0 6 1 - F111 028D8 Digital Input 1 Trip Delay 1 50000 1 100ms F2 50
28D9 Digital Input 1 Assignable Function 0 3 1 - F163 0
... ReservedRRTD 1 – DIGITAL INPUT 6
28E0 1st & 2nd Character of Digital Input 6 Name 32 127 1 - F22 ’GE’
↓ ↓
28E5 11th & 12th Character of Digital Input 6 Name 32 127 1 - F22 ’GE’
28F0 Digital Input 6 Type 0 1 1 - F116 028F1 Reserved28F2 Digital Input 6 Alarm 0 2 1 - F115 028F3 Digital Input 6 Alarm Relays 0 6 1 - F113 028F4 Digital Input 6 Alarm Delay 1 50000 1 100ms F2 5028F5 Digital Input 6 Alarm Events 0 1 1 - F103 028F6 Digital Input 6 Trip 0 2 1 - F115 028F7 Digital Input 6 Trip Relays 0 6 1 - F111 028F8 Digital Input 6 Trip Delay 1 50000 1 100ms F2 50
28F9 Digital Input 6 Assignable Function 0 3 1 - F163 0
... ReservedRRTD 1 – DIGITAL INPUT 3
2900 1st & 2nd Character of Digital Input 3 Name 32 127 1 - F22 ’GE’
↓ ↓
2905 11th & 12th Character of Digital Input 3 Name 32 127 1 - F22 ’GE’
2910 Digital Input 3 Type 0 1 1 - F116 02911 Reserved2912 Digital Input 3 Alarm 0 2 1 - F115 02913 Digital Input 3 Alarm Relays 0 6 1 - F113 02914 Digital Input 3 Alarm Delay 1 50000 1 100ms F2 502915 Digital Input 3 Alarm Events 0 1 1 - F103 02916 Digital Input 3 Trip 0 2 1 - F115 02917 Digital Input 3 Trip Relays 0 6 1 - F111 02918 Digital Input 3 Trip Delay 1 50000 1 100ms F2 50
2919 Digital Input 3 Assignable Function 0 3 1 - F163 0
Table CG–10: MEMORY MAP (Sheet 66 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CG120 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP CGCOMMUNICATIONS GUIDE
... ReservedRRTD 2 – DIGITAL INPUT 2
2920 1st & 2nd Character of Digital Input 2 Name 32 127 1 - F22 ’GE’
↓ ↓
2925 11th & 12th Character of Digital Input 2 Name 32 127 1 - F22 ’GE’
2930 Digital Input 2 Type 0 1 1 - F116 02931 Reserved2932 Digital Input 2 Alarm 0 2 1 - F115 02933 Digital Input 2 Alarm Relays 0 6 1 - F113 02934 Digital Input 2 Alarm Delay 1 50000 1 100ms F2 502935 Digital Input 2 Alarm Events 0 1 1 - F103 02936 Digital Input 2 Trip 0 2 1 - F115 02937 Digital Input 2 Trip Relays 0 6 1 - F111 02938 Digital Input 2 Trip Delay 1 50000 1 100ms F2 50
2939 Digital Input 2 Assignable Function 0 3 1 - F163 0
... ReservedRRTD 2 – DIGITAL INPUT 5
2940 1st & 2nd Character of Digital Input 5 Name 32 127 1 - F22 ’GE’
↓ ↓
2945 11th & 12th Character of Digital Input 5 Name 32 127 1 - F22 ’GE’
2950 Digital Input 5 Type 0 1 1 - F116 02951 Reserved2952 Digital Input 5 Alarm 0 2 1 - F115 02953 Digital Input 5 Alarm Relays 0 6 1 - F113 02954 Digital Input 5 Alarm Delay 1 50000 1 100ms F2 502955 Digital Input 5 Alarm Events 0 1 1 - F103 02956 Digital Input 5 Trip 0 2 1 - F115 02957 Digital Input 5 Trip Relays 0 6 1 - F111 02958 Digital Input 5 Trip Delay 1 50000 1 100ms F2 50
2959 Digital Input 5 Assignable Function 0 3 1 - F163 0
... ReservedRRTD 2 – DIGITAL INPUT 4
2960 1st & 2nd Character of Digital Input 4 Name 32 127 1 - F22 ’GE’
↓ ↓
2965 11th & 12th Character of Digital Input 4 Name 32 127 1 - F22 ’GE’
2970 Digital Input 4 Type 0 1 1 - F116 02971 Reserved2972 Digital Input 4 Alarm 0 2 1 - F115 02973 Digital Input 4 Alarm Relays 0 6 1 - F113 02974 Digital Input 4 Alarm Delay 1 50000 1 100ms F2 502975 Digital Input 4 Alarm Events 0 1 1 - F103 02976 Digital Input 4 Trip 0 2 1 - F115 02977 Digital Input 4 Trip Relays 0 6 1 - F111 02978 Digital Input 4 Trip Delay 1 50000 1 100ms F2 50
Table CG–10: MEMORY MAP (Sheet 67 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CGCOMMUNICATIONS GUIDE MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG121
2979 Digital Input 4 Assignable Function 0 3 1 - F163 0
... ReservedRRTD 2 – DIGITAL INPUT 1
2980 1st & 2nd Character of Digital Input 1 Name 32 127 1 - F22 ’GE’
↓ ↓
2985 11th & 12th Character of Digital Input 1 Name 32 127 1 - F22 ’GE’
2990 Digital Input 1 Type 0 1 1 - F116 02991 Reserved2992 Digital Input 1 Alarm 0 2 1 - F115 02993 Digital Input 1 Alarm Relays 0 6 1 - F113 02994 Digital Input 1 Alarm Delay 1 50000 1 100ms F2 502995 Digital Input 1 Alarm Events 0 1 1 - F103 02996 Digital Input 1 Trip 0 2 1 - F115 02997 Digital Input 1 Trip Relays 0 6 1 - F111 02998 Digital Input 1 Trip Delay 1 50000 1 100ms F2 50
2999 Digital Input 1 Assignable Function 0 3 1 - F163 0
... ReservedRRTD 2 – DIGITAL INPUT 6
29A0 1st & 2nd Character of Digital Input 6 Name 32 127 1 - F22 ’GE’
↓ ↓
29A5 11th & 12th Character of Digital Input 6 Name 32 127 1 - F22 ’GE’
29B0 Digital Input 6 Type 0 1 1 - F116 029B1 Reserved29B2 Digital Input 6 Alarm 0 2 1 - F115 029B3 Digital Input 6 Alarm Relays 0 6 1 - F113 029B4 Digital Input 6 Alarm Delay 1 50000 1 100ms F2 5029B5 Digital Input 6 Alarm Events 0 1 1 - F103 029B6 Digital Input 6 Trip 0 2 1 - F115 029B7 Digital Input 6 Trip Relays 0 6 1 - F111 029B8 Digital Input 6 Trip Delay 1 50000 1 100ms F2 50
29B9 Digital Input 6 Assignable Function 0 3 1 - F163 0
... ReservedRRTD 2 – DIGITAL INPUT 3
29C0 1st & 2nd Character of Digital Input 3 Name 32 127 1 - F22 ’GE’
↓ ↓
29C5 11th & 12th Character of Digital Input 3 Name 32 127 1 - F22 ’GE’
29D0 Digital Input 3 Type 0 1 1 - F116 029D1 Reserved29D2 Digital Input 3 Alarm 0 2 1 - F115 029D3 Digital Input 3 Alarm Relays 0 6 1 - F113 029D4 Digital Input 3 Alarm Delay 1 50000 1 100ms F2 5029D5 Digital Input 3 Alarm Events 0 1 1 - F103 029D6 Digital Input 3 Trip 0 2 1 - F115 029D7 Digital Input 3 Trip Relays 0 6 1 - F111 0
Table CG–10: MEMORY MAP (Sheet 68 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CG122 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP CGCOMMUNICATIONS GUIDE
29D8 Digital Input 3 Trip Delay 1 50000 1 100ms F2 50
29D9 Digital Input 3 Assignable Function 0 3 1 - F163 0
... ReservedRRTD 3 – DIGITAL INPUT 2
29E0 1st & 2nd Character of Digital Input 2 Name 32 127 1 - F22 ’GE’
↓ ↓
29E5 11th & 12th Character of Digital Input 2 Name 32 127 1 - F22 ’GE’
29F0 Digital Input 2 Type 0 1 1 - F116 029F1 Reserved29F2 Digital Input 2 Alarm 0 2 1 - F115 029F3 Digital Input 2 Alarm Relays 0 6 1 - F113 029F4 Digital Input 2 Alarm Delay 1 50000 1 100ms F2 5029F5 Digital Input 2 Alarm Events 0 1 1 - F103 029F6 Digital Input 2 Trip 0 2 1 - F115 029F7 Digital Input 2 Trip Relays 0 6 1 - F111 029F8 Digital Input 2 Trip Delay 1 50000 1 100ms F2 50
29F9 Digital Input 2 Assignable Function 0 3 1 - F163 0
... ReservedRRTD 3 – DIGITAL INPUT 5
2A00 1st & 2nd Character of Digital Input 5 Name 32 127 1 - F22 ’GE’
↓ ↓
2A05 11th & 12th Character of Digital Input 5 Name 32 127 1 - F22 ’GE’
2A10 Digital Input 5 Type 0 1 1 - F116 02A11 Reserved2A12 Digital Input 5 Alarm 0 2 1 - F115 02A13 Digital Input 5 Alarm Relays 0 6 1 - F113 02A14 Digital Input 5 Alarm Delay 1 50000 1 100ms F2 502A15 Digital Input 5 Alarm Events 0 1 1 - F103 02A16 Digital Input 5 Trip 0 2 1 - F115 02A17 Digital Input 5 Trip Relays 0 6 1 - F111 02A18 Digital Input 5 Trip Delay 1 50000 1 100ms F2 50
2A19 Digital Input 5 Assignable Function 0 3 1 - F163 0
... ReservedRRTD 3 – DIGITAL INPUT 4
2A20 1st & 2nd Character of Digital Input 4 Name 32 127 1 - F22 ’GE’
↓ ↓
2A25 11th & 12th Character of Digital Input 4 Name 32 127 1 - F22 ’GE’
2A30 Digital Input 4 Type 0 1 1 - F116 02A31 Reserved2A32 Digital Input 4 Alarm 0 2 1 - F115 02A33 Digital Input 4 Alarm Relays 0 6 1 - F113 02A34 Digital Input 4 Alarm Delay 1 50000 1 100ms F2 502A35 Digital Input 4 Alarm Events 0 1 1 - F103 02A36 Digital Input 4 Trip 0 2 1 - F115 0
Table CG–10: MEMORY MAP (Sheet 69 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CGCOMMUNICATIONS GUIDE MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG123
2A37 Digital Input 4 Trip Relays 0 6 1 - F111 02A38 Digital Input 4 Trip Delay 1 50000 1 100ms F2 50
2A39 Digital Input 4 Assignable Function 0 3 1 - F163 0
... ReservedRRTD 3 – DIGITAL INPUT 1
2A40 1st & 2nd Character of Digital Input 1 Name 32 127 1 - F22 ’GE’
↓ ↓
2A45 11th & 12th Character of Digital Input 1 Name 32 127 1 - F22 ’GE’
2A50 Digital Input 1 Type 0 1 1 - F116 02A51 Reserved2A52 Digital Input 1 Alarm 0 2 1 - F115 02A53 Digital Input 1 Alarm Relays 0 6 1 - F113 02A54 Digital Input 1 Alarm Delay 1 50000 1 100ms F2 502A55 Digital Input 1 Alarm Events 0 1 1 - F103 02A56 Digital Input 1 Trip 0 2 1 - F115 02A57 Digital Input 1 Trip Relays 0 6 1 - F111 02A58 Digital Input 1 Trip Delay 1 50000 1 100ms F2 50
2A59 Digital Input 1 Assignable Function 0 3 1 - F163 0
... ReservedRRTD 3 – DIGITAL INPUT 6
2A60 1st & 2nd Character of Digital Input 6 Name 32 127 1 - F22 ’GE’
↓ ↓
2A65 11th & 12th Character of Digital Input 6 Name 32 127 1 - F22 ’GE’
2A70 Digital Input 6 Type 0 1 1 - F116 02A71 Reserved2A72 Digital Input 6 Alarm 0 2 1 - F115 02A73 Digital Input 6 Alarm Relays 0 6 1 - F113 02A74 Digital Input 6 Alarm Delay 1 50000 1 100ms F2 502A75 Digital Input 6 Alarm Events 0 1 1 - F103 02A76 Digital Input 6 Trip 0 2 1 - F115 02A77 Digital Input 6 Trip Relays 0 6 1 - F111 02A78 Digital Input 6 Trip Delay 1 50000 1 100ms F2 50
2A79 Digital Input 6 Assignable Function 0 3 1 - F163 0
... ReservedRRTD 3 – DIGITAL INPUT 3
2A80 1st & 2nd Character of Digital Input 3 Name 32 127 1 - F22 ’GE’
↓ ↓
2A85 11th & 12th Character of Digital Input 3 Name 32 127 1 - F22 ’GE’
2A90 Digital Input 3 Type 0 1 1 - F116 02A91 Reserved2A92 Digital Input 3 Alarm 0 2 1 - F115 02A93 Digital Input 3 Alarm Relays 0 6 1 - F113 02A94 Digital Input 3 Alarm Delay 1 50000 1 100ms F2 502A95 Digital Input 3 Alarm Events 0 1 1 - F103 0
Table CG–10: MEMORY MAP (Sheet 70 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CG124 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP CGCOMMUNICATIONS GUIDE
2A96 Digital Input 3 Trip 0 2 1 - F115 02A97 Digital Input 3 Trip Relays 0 6 1 - F111 02A98 Digital Input 3 Trip Delay 1 50000 1 100ms F2 50
2A99 Digital Input 3 Assignable Function 0 3 1 - F163 0
... ReservedRRTD 4 – DIGITAL INPUT 2
2AA0 1st & 2nd Character of Digital Input 2 Name 32 127 1 - F22 ’GE’
↓ ↓
2AA5 11th & 12th Character of Digital Input 2 Name 32 127 1 - F22 ’GE’
2AB0 Digital Input 2 Type 0 1 1 - F116 02AB1 Reserved2AB2 Digital Input 2 Alarm 0 2 1 - F115 02AB3 Digital Input 2 Alarm Relays 0 6 1 - F113 02AB4 Digital Input 2 Alarm Delay 1 50000 1 100ms F2 502AB5 Digital Input 2 Alarm Events 0 1 1 - F103 02AB6 Digital Input 2 Trip 0 2 1 - F115 02AB7 Digital Input 2 Trip Relays 0 6 1 - F111 02AB8 Digital Input 2 Trip Delay 1 50000 1 100ms F2 50
2AB9 Digital Input 2 Assignable Function 0 3 1 - F163 0
... ReservedRRTD 4 – DIGITAL INPUT 5
2AC0 1st & 2nd Character of Digital Input 5 Name 32 127 1 - F22 ’GE’
↓ ↓
2AC5 11th & 12th Character of Digital Input 5 Name 32 127 1 - F22 ’GE’
2AD0 Digital Input 5 Type 0 1 1 - F116 02AD1 Reserved2AD2 Digital Input 5 Alarm 0 2 1 - F115 02AD3 Digital Input 5 Alarm Relays 0 6 1 - F113 02AD4 Digital Input 5 Alarm Delay 1 50000 1 100ms F2 502AD5 Digital Input 5 Alarm Events 0 1 1 - F103 02AD6 Digital Input 5 Trip 0 2 1 - F115 02AD7 Digital Input 5 Trip Relays 0 6 1 - F111 02AD8 Digital Input 5 Trip Delay 1 50000 1 100ms F2 50
2AD9 Digital Input 5 Assignable Function 0 3 1 - F163 0
... ReservedRRTD 4 – DIGITAL INPUT 4
2AE0 1st & 2nd Character of Digital Input 4 Name 32 127 1 - F22 ’GE’
↓ ↓
2AE5 11th & 12th Character of Digital Input 4 Name 32 127 1 - F22 ’GE’
2AF0 Digital Input 4 Type 0 1 1 - F116 02AF1 Reserved2AF2 Digital Input 4 Alarm 0 2 1 - F115 02AF3 Digital Input 4 Alarm Relays 0 6 1 - F113 02AF4 Digital Input 4 Alarm Delay 1 50000 1 100ms F2 50
Table CG–10: MEMORY MAP (Sheet 71 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CGCOMMUNICATIONS GUIDE MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG125
2AF5 Digital Input 4 Alarm Events 0 1 1 - F103 02AF6 Digital Input 4 Trip 0 2 1 - F115 02AF7 Digital Input 4 Trip Relays 0 6 1 - F111 02AF8 Digital Input 4 Trip Delay 1 50000 1 100ms F2 50
2AF9 Digital Input 4 Assignable Function 0 3 1 - F163 0
... ReservedRRTD 4 – DIGITAL INPUT 1
2B00 1st & 2nd Character of Digital Input 1 Name 32 127 1 - F22 ’GE’
↓ ↓
2B05 11th & 12th Character of Digital Input 1 Name 32 127 1 - F22 ’GE’
2B10 Digital Input 1 Type 0 1 1 - F116 02B11 Reserved2B12 Digital Input 1 Alarm 0 2 1 - F115 02B13 Digital Input 1 Alarm Relays 0 6 1 - F113 02B14 Digital Input 1 Alarm Delay 1 50000 1 100ms F2 502B15 Digital Input 1 Alarm Events 0 1 1 - F103 02B16 Digital Input 1 Trip 0 2 1 - F115 02B17 Digital Input 1 Trip Relays 0 6 1 - F111 02B18 Digital Input 1 Trip Delay 1 50000 1 100ms F2 50
2B19 Digital Input 1 Assignable Function 0 3 1 - F163 0
... ReservedRRTD 4 – DIGITAL INPUT 6
2B20 1st & 2nd Character of Digital Input 6 Name 32 127 1 - F22 ’GE’
↓ ↓
2B25 11th & 12th Character of Digital Input 6 Name 32 127 1 - F22 ’GE’
2B30 Digital Input 6 Type 0 1 1 - F116 02B31 Reserved2B32 Digital Input 6 Alarm 0 2 1 - F115 02B33 Digital Input 6 Alarm Relays 0 6 1 - F113 02B34 Digital Input 6 Alarm Delay 1 50000 1 100ms F2 502B35 Digital Input 6 Alarm Events 0 1 1 - F103 02B36 Digital Input 6 Trip 0 2 1 - F115 02B37 Digital Input 6 Trip Relays 0 6 1 - F111 02B38 Digital Input 6 Trip Delay 1 50000 1 100ms F2 50
2B39 Digital Input 6 Assignable Function 0 3 1 - F163 0
... ReservedRRTD 4 – DIGITAL INPUT 3
2B40 1st & 2nd Character of Digital Input 3 Name 32 127 1 - F22 ’GE’
↓ ↓
2B45 11th & 12th Character of Digital Input 3 Name 32 127 1 - F22 ’GE’
2B50 Digital Input 3 Type 0 1 1 - F116 02B51 Reserved2B52 Digital Input 3 Alarm 0 2 1 - F115 02B53 Digital Input 3 Alarm Relays 0 6 1 - F113 0
Table CG–10: MEMORY MAP (Sheet 72 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CG126 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP CGCOMMUNICATIONS GUIDE
2B54 Digital Input 3 Alarm Delay 1 50000 1 100ms F2 502B55 Digital Input 3 Alarm Events 0 1 1 - F103 02B56 Digital Input 3 Trip 0 2 1 - F115 02B57 Digital Input 3 Trip Relays 0 6 1 - F111 02B58 Digital Input 3 Trip Delay 1 50000 1 100ms F2 50
2B59 Digital Input 3 Assignable Function 0 3 1 - F163 0
... ReservedRRTD 1 – TEST OUPUT RELAYS
2B60 Force Trip Relay 0 2 1 - F150 02B61 Force Trip Relay Duration 0 300 1 s F1 02B62 Force AUX1 Relay 0 2 1 - F150 02B63 Force AUX1 Relay Duration 0 300 1 s F1 02B64 Force AUX2 Relay 0 2 1 - F150 02B65 Force AUX2 Relay Duration 0 300 1 s F1 02B66 Force Alarm Relay 0 2 1 - F150 02B67 Force Alarm Relay Range 01 300 1 s F1 0... Reserved
RRTD 2 – TEST OUPUT RELAYS
2B70 Force Trip Relay 0 2 1 - F150 02B71 Force Trip Relay Duration 0 300 1 s F1 02B72 Force AUX1 Relay 0 2 1 - F150 02B73 Force AUX1 Relay Duration 0 300 1 s F1 02B74 Force AUX2 Relay 0 2 1 - F150 02B75 Force AUX2 Relay Duration 0 300 1 s F1 02B76 Force Alarm Relay 0 2 1 - F150 02B77 Force Alarm Relay Range 0 300 1 s F1 0... Reserved
RRTD 3 – TEST OUPUT RELAYS
2B80 Force Trip Relay 0 2 1 - F150 02B81 Force Trip Relay Duration 0 300 1 s F1 02B82 Force AUX1 Relay 0 2 1 - F150 02B83 Force AUX1 Relay Duration 0 300 1 s F1 02B84 Force AUX2 Relay 0 2 1 - F150 02B85 Force AUX2 Relay Duration 0 300 1 s F1 02B86 Force Alarm Relay 0 2 1 - F150 02B87 Force Alarm Relay Range 0 300 1 s F1 0... Reserved
RRTD 4 – TEST OUPUT RELAYS
2B90 Force Trip Relay 0 2 1 - F150 02B91 Force Trip Relay Duration 0 300 1 s F1 02B92 Force AUX1 Relay 0 2 1 - F150 02B93 Force AUX1 Relay Duration 0 300 1 s F1 02B94 Force AUX2 Relay 0 2 1 - F150 02B95 Force AUX2 Relay Duration 0 300 1 s F1 02B96 Force Alarm Relay 0 2 1 - F150 02B97 Force Alarm Relay Range 0 300 1 s F1 0... Reserved
RRTD 1 – TEST ANALOG OUTPUTS
2BA0 Force Analog Outputs 0 1 1 - F126 02BA1 Analog Output 1 Forced Value 0 100 1 % range F1 0
Table CG–10: MEMORY MAP (Sheet 73 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CGCOMMUNICATIONS GUIDE MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG127
2BA2 Analog Output 2 Forced Value 0 100 1 % range F1 02BA3 Analog Output 3 Forced Value 0 100 1 % range F1 02BA4 Analog Output 4 Forced Value 0 100 1 % range F1 0... Reserved
RRTD 2 – TEST ANALOG OUTPUTS
2BB0 Force Analog Outputs 0 1 1 - F126 02BB1 Analog Output 1 Forced Value 0 100 1 % range F1 02BB2 Analog Output 2 Forced Value 0 100 1 % range F1 02BB3 Analog Output 3 Forced Value 0 100 1 % range F1 02BB4 Analog Output 4 Forced Value 0 100 1 % range F1 0... Reserved
RRTD 3 – TEST ANALOG OUTPUTS
2BC0 Force Analog Outputs 0 1 1 - F126 02BC1 Analog Output 1 Forced Value 0 100 1 % range F1 02BC2 Analog Output 2 Forced Value 0 100 1 % range F1 02BC3 Analog Output 3 Forced Value 0 100 1 % range F1 02BC4 Analog Output 4 Forced Value 0 100 1 % range F1 0... Reserved
RRTD 4 – TEST ANALOG OUTPUTS
2BD0 Force Analog Outputs 0 1 1 - F126 02BD1 Analog Output 1 Forced Value 0 100 1 % range F1 02BD2 Analog Output 2 Forced Value 0 100 1 % range F1 02BD3 Analog Output 3 Forced Value 0 100 1 % range F1 02BD4 Analog Output 4 Forced Value 0 100 1 % range F1 0... Reserved
RRTD 1 – DIGITAL COUNTER
2BE0 First Character of Counter Name 32 127 1 - F1 “G”
2BEC First Character of Counter Unit Name 32 127 1 - F1 ‘U’
2BF2 Counter Type 0 1 1 - F114 02BF3 Digital Counter Alarm 0 2 1 - F115 02BF4 Assign Alarm Relays 0 6 1 - F113 02BF5 Counter Alarm Level 0 65535 1 - F1 1002BF7 Reserved - - - - - -2BF8 Record Alarms as Events 0 1 1 - F103 0... Reserved
RRTD 2 – DIGITAL COUNTER
2C00 First Character of Counter Name 32 127 1 - F1 “G”
2C0C First Character of Counter Unit Name 32 127 1 - F1 ‘U’
2C12 Counter Type 0 1 1 - F114 02C13 Digital Counter Alarm 0 2 1 - F115 02C14 Assign Alarm Relays 0 6 1 - F113 02C15 Counter Alarm Level 0 65535 1 - F1 1002C17 Reserved - - - - - -2C18 Record Alarms as Events 0 1 1 - F103 0... Reserved
RRTD 3 – DIGITAL COUNTER
2C20 First Character of Counter Name 32 127 1 - F1 “G”
2C2C First Character of Counter Unit Name 32 127 1 - F1 ‘U’
Table CG–10: MEMORY MAP (Sheet 74 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CG128 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP CGCOMMUNICATIONS GUIDE
2C32 Counter Type 0 1 1 - F114 02C33 Digital Counter Alarm 0 2 1 - F115 02C34 Assign Alarm Relays 0 6 1 - F113 02C35 Counter Alarm Level 0 65535 1 - F1 1002C37 Reserved - - - - - -2C38 Record Alarms as Events 0 1 1 - F103 0... Reserved
RRTD 4 – DIGITAL COUNTER
2C40 First Character of Counter Name 32 127 1 - F1 “G”
2C4C First Character of Counter Unit Name 32 127 1 - F1 ‘U’
2C52 Counter Type 0 1 1 - F114 02C53 Digital Counter Alarm 0 2 1 - F115 02C54 Assign Alarm Relays 0 6 1 - F113 02C55 Counter Alarm Level 0 65535 1 - F1 1002C57 Reserved - - - - - -2C58 Record Alarms as Events 0 1 1 - F103 0... Reserved
EVENT RECORDER / TRACE MEMORY / MOTOR START DATA LOGGER (ADDRESSES 3000 TO 3FFF)EVENT RECORDER
3000 Event Recorder Last Reset (2 words) N/A N/A N/A N/A F18 N/A
3002 Total Number of Events Since Last Clear 0 65535 1 N/A F1 0
3003 Event Record Selector (1=oldest, 512=newest) 1 512 1 N/A F1 1
3004 Cause of Event 0 281 1 - F134 03005 Time of Event (2 words) N/A N/A N/A N/A F19 N/A3007 Date of Event (2 words) N/A N/A N/A N/A F18 N/A3009 Motor Speed During Event 0 2 1 N/A F186 N/A... Reserved300B Event Phase A Current 0 65535 1 A F1 0300C Event Phase B Current 0 65535 1 A F1 0300D Event Phase C Current 0 65535 1 A F1 0300E Event Motor Load 0 2000 1 FLA F3 0300F Event Current Unbalance 0 100 1 % F1 03010 Event Ground Current 0 50000 1 A F23 03011 Event Hottest Stator RTD Owner 0 5 1 N/A F165 03012 Event Hottest Stator RTD 0 12 1 - F1 0
3013 Event Temperature of Hottest Stator RTD -40 200 1 o C F4 0
... Reserved301A Event Voltage Vab 0 20000 1 V F1 0301B Event Voltage Vbc 0 20000 1 V F1 0301C Event Voltage Vca 0 20000 1 V F1 0301D Event Voltage Van 0 20000 1 V F1 0301E Event Voltage Vbn 0 20000 1 V F1 0301F Event Voltage Vcn 0 20000 1 V F1 03020 Event System Frequency 0 12000 1 Hz F3 03021 Event Real Power -32000 32000 1 kW F4 03022 Event Reactive Power -32000 32000 1 kvar F4 03023 Event Apparent Power 0 50000 1 kVA F1 0
Table CG–10: MEMORY MAP (Sheet 75 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CGCOMMUNICATIONS GUIDE MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG129
3024 Event Power Factor -99 100 1 - F21 0... Reserved
WAVEFORM CAPTURE / MOTOR START DATA LOGGER
30EF Buffer Memory Access Type 0 2 1 - F184 0 (Trace Memory)
30F0 Trace Memory Clear Date N/A N/A N/A N/A F18 N/A30F2 Trace Memory Clear Time N/A N/A N/A N/A F19 N/A
30F4 Trace Memory Triggers Since Last Clear 0 65535 1 - F1 0
30F5Trace Memory Buffer Selector 0 3 1 - F1 0
Motor Start Log Buffer Selector 0 6 1 - F1 0 (None Selected)
30F6Trace Memory Channel Selector 0 6 1 - F1 0Motor Start Log Channel Selector 0 11 1 - F1 0 (None
Selected)
30F7Trace Memory Trigger Date N/A N/A N/A N/A F18 N/AMotor Start Log Trigger Date N/A N/A N/A N/A F18 N/A
30F9Trace Memory Trigger Time N/A N/A N/A N/A F19 N/AMotor Start Log Trigger Time N/A N/A N/A N/A F19 N/A
30FB1Trace Memory Trigger Cause 0 2 1 - F85 N/ANumber of Recorded Motor Start Logs 0 6 1 - F1 0
30FC1Trace Memory Trigger Index 0 100 1 % F1 N/AMotor Start Log Phase Voltage Type 0 1 1 - F185 N/A
... Reserved
3100First Trace Memory Sample -32767 32767 1 - F4 N/AFirst Memory Sample -32767 32767 1 - F4 N/A
↓ ↓
31FFLast Trace Memory Sample -32767 32767 1 - F4 N/ALast Memory Sample -32767 32767 1 - F4 N/A
DATA LOGGER LOG HEADER
3200 Log Time Interval 1 3600 1 s F1 36003201 Log Record Size 0 16 - Words F1 N/A3202 Log Total Possible Records 0 16256 1 - F1 N/A3203 Total Logs Since Last Clear 0 65535 1 - F1 03204 Total Logs Presently Used 0 50 1 - F1 03205 Total Records Presently Used 0 16256 1 - F1 0
3206 Log Status 0 1 1 - F190 0 = Stopped
3207 Log Time Until next Reading 1 3600 1 s F1 36003208 Data Logger Percentage Full 0 100 1 % F1 03209 Date of Latest Record - - - - F18 -320B Time of Latest record - - - - F19 -
320D Address Pointer To Next Record To Write 0 16255 1 - F1 0
320E Pointer to 1st Log Start Address 0 16255 1 - F1 N/A320F 1st Log Number of Records 0 16256 1 - F1 N/A... ... ... ... ... ... ... ...
3270 Pointer to 50th Log Start Address 0 16255 1 F1 N/A
3271 50th Log Number of Records 0 16256 1 - F1 N/A
Table CG–10: MEMORY MAP (Sheet 76 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CG130 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP CGCOMMUNICATIONS GUIDE
3272 Log 1-8 Start/Stop Method 0 FFFF N/A - F191 N/A3273 Log 9-16 Start/Stop Method 0 FFFF N/A - F191 N/A3274 Log 17-24 Start/Stop Method 0 FFFF N/A - F191 N/A3275 Log 25-32 Start/Stop Method 0 FFFF N/A - F191 N/A3276 Log 33-40 Start/Stop Method 0 FFFF N/A - F191 N/A3277 Log 41-48 Start/Stop Method 0 FFFF N/A - F191 N/A3278 Log 49-50 Start/Stop Method 0 FFFF N/A - F191 N/A
DATA LOGGER DATA
3280 Data Log Memory Access Block Number 0 255 1 F1 0
3281 Data Log Register 1 - - - - F1 -3282 Data Log Register 2 - - - - F1 -3283 Data Log Register 3 - - - - F1 -3284 Data Log Register 4 - - - - F1 -... ... ... ... ... ... ... ...32BF Data Log Register 63 - - - - F1 -32C0 Data Log Register 64 - - - - F1 -32C1 Reserved... ... ... ... ... ... ... ...3FFF Reserved
1. Addresses 0x030FB and 0x30FC have different functionality, depending on which functionality is se-lected in address 0x30EF, Waveform Capture, Motor Start Data Logger
Table CG–10: MEMORY MAP (Sheet 77 of 77)ADDR (hex)
DESCRIPTION MIN. MAX. STEP VALUE
UNITS FORMAT CODE
FACTORY DEFAULT
CGCOMMUNICATIONS GUIDE MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG131
6.8 Format Codes
Table CG–11: Memory Map Data Formats (Sheet 1 of 27)
CODE TYPE DEFINITION
F1 16 bits UNSIGNED VALUEExample: 1234 stored as 1234
F2 16 bits UNSIGNED VALUE, 1 DECIMAL PLACEExample: 123.4 stored as 1234
F3 16 bits UNSIGNED VALUE, 2 DECIMAL PLACESExample: 12.34 stored as 1234
F4 16 bits 2’s COMPLEMENT SIGNED VALUEExample: -1234 stored as -1234 (i.e. 64302)
F5 16 bits 2’s COMPLEMENT SIGNED VALUE, 1 DECIMAL PLACESExample: -123.4 stored as -1234 (i.e. 64302)
F6 16 bits 2’s COMPLEMENT SIGNED VALUE, 2 DECIMAL PLACESExample: -12.34 stored as -1234 (i.e. 64302)
F7 16 bits 2’s COMPLEMENT SIGNED VALUE, 3 DECIMAL PLACESExample: -1.234 stored as -1234 (i.e. 64302)
F8 16 bits 2’s COMPLEMENT SIGNED VALUE, 4 DECIMAL PLACESExample: -0.1234 stored as -1234 (i.e. 64302)
F13 16 bits INSTALLED OPTIONS
xxxx xxxx xxxx xxx1 Profibus-DP (0 = Not Installed, 1 = Installed)
xxxx xxxx xxxx xx1x Fiber Optic (0 = Not Installed, 1 = Installed)
xxxx xxxx xxxx x1xx Metering (0 = Not Installed, 1 = Installed)
xxxx xxxx xxxx 1xxx Backspin (0 = Not Installed, 1 = Installed)
xxxx xxxx xxx1 xxxx Local RTD (0 = Not Installed, 1 = Installed)
xxxx xxxx xx1x xxxx Power Supply Type (0 = LO, 1 = HI)
xxxx xxxx 1xxx xxxx Modbus/TCP (0 = Not Installed, 1 = Installed)
xxxx xxx1 xxxx xxxx DeviceNet (0 = Not Installed, 1 = Installed)
xxxx xx1x xxxx xxxx Harsh Environment (0 = Not Installed, 1 = Installed)
xxxx x1xx xxxx xxxx Profibus-DPV1 (0 = Not Installed, 1 = Installed)
xxxx 1xxx xxxx xxxx Enhanced Diagnostics (0 = Not Installed, 1 = Installed)
F15 16 bits HARDWARE REVISION
0000 0000 0000 0001 1 = A
0000 0000 0000 0010 2 = B
0000 0000 0000 0011 3 = C
0000 0000 0001 1010 26 = Z
CG132 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP CGCOMMUNICATIONS GUIDE
F16 16 bits SOFTWARE REVISION
1111 1111 xxxx xxxx Major Revision Number, 0 to 9 in steps of 1
xxxx xxxx 1111 1111Minor Revision Number (two BCD digits), 00 to 99 in steps of 1Example: Revision 2.30 stored as 0230 hex
F18 32 bitsDATE (MM/DD/YYYY)Example: Feb. 20, 1995 stored as 34867142 (i.e. 1st word: 0214, 2nd word 07C6)
1st byte Month (1 to 12)
2nd byte Day (1 to 31)
3rd and 4th byte Year (1998 to 2097)
F19 32 bitsTIME (HH:MM:SS:hh)Example: 2:05pm stored as 235208704 (i.e. 1st word: 0E05, 2nd word 0000)
1st byte Hours (0 to 23)
2nd byte Minutes (0 to 59)
3rd byte Seconds (0 to 59)
4th byte Hundreds of seconds (0 to 99) - Not used by 369
F20 16 bits 2’s COMPLEMENT SIGNED LONG VALUEExample: 1234 stored as 1234. Note: -1 means “Never”
F21 16 bits2’s COMPLEMENT SIGNED VALUE, 2 DECIMAL PLACES (Power Factor)Example: Power Factor of 0.87 lag is used as 87 (i.e. 0057)
< 0 Leading Power Factor - Negative
> 0 Lagging Power Factor - Positive
F22 16 bits TWO 8-BIT CHARACTERS PACKED INTO 16-BIT UNSIGNEDExample: String "AB" stored as 4142 hex.
MSB First Character
LSB Second Character
F23 16 BitsUNSIGNED VALUE (For 1A/5 A CT, 1Decimal Place) (For 50: 0.025 A CT, 2 Decimal Places)Example: For 1A/5A CT, G/F current = 1000.0 AExample: For 50: 0.025 A CT, G/F current = 25.00
F26 16 Bits ANALOG OUTPUT SELECTION
0 0 - 1mA
1 0 - 20 mA
2 4 - 20 mA
F27 16 Bits BACKSPIN DETECTION STATE
0 Motor Running
Table CG–11: Memory Map Data Formats (Sheet 2 of 27)
CODE TYPE DEFINITION
CGCOMMUNICATIONS GUIDE MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG133
1 No Backspin
2 Slowdown
3 Acceleration
4 ---
5 Backspinning
6 Prediction
7 Soon to Restart
F30 16 Bits DISABLE/ENABLE SELECTION
0 Disabled
1 Enabled
F31 16 Bits COMMAND FUNCTION CODES
0 Not in use
1 Reset 369
2 Motor Start
3 Motor Stop
4 Waveform Trigger
5 Reserved
6 Clear Trip Counters
7 Clear Last Trip Data
8 Reserved
9 Reserved
10 Clear RTD Maximums
11 Reset Motor Info
12 Clear/Reset all Data
20 Block/Unblock Protection Functions
21 Force Output Relays
F85 Unsigned 16 bit integer WAVEFORM CAPTURE TRIGGER CAUSE
0 None
1 Manual
2 Automatic
F100 Unsigned 16 bit integer TEMPERATURE DISPLAY UNITS
0 Celsius
Table CG–11: Memory Map Data Formats (Sheet 3 of 27)
CODE TYPE DEFINITION
CG134 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP CGCOMMUNICATIONS GUIDE
1 Fahrenheit
F101 Unsigned 16 bit integer BAUD RATE
0 1200 baud
1 2400 baud
2 4800 baud
3 9600 baud
4 19200 baud
F102 Unsigned 16 bit integer PARITY
0 None
1 Odd
2 Even
F103 Unsigned 16 bit integer OFF/ON OR NO/YES SELECTION
0 Off / No
1 On / Yes
F104 Unsigned 16 bit integer GROUND CT TYPE
0 None
1 1 A Secondary
2 5 A Secondary
3 Multilin CT 50/0.025
F105 Unsigned 16 bit integer CT TYPE
0 None
1 1 A Secondary
2 5 A Secondary
F106 Unsigned 16 bit integer VOLTAGE TRANSFORMER CONNECTION TYPE
0 None
1 Open Delta
2 Wye
F107 Unsigned 16 bit integer NOMINAL FREQUENCY
0 60 Hz
1 50 Hz
2 Variable
F108 Unsigned 16 bit integer REDUCED VOLTAGE STARTING TRANSITION ON
Table CG–11: Memory Map Data Formats (Sheet 4 of 27)
CODE TYPE DEFINITION
CGCOMMUNICATIONS GUIDE MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG135
0 Current Only
1 Current or Timer
2 Current and Timer
F109 Unsigned 16 bit integer STARTER STATUS SWITCH
0 Starter Aux a (52a)
1 Starter Aux b (52b)
F110 Unsigned 16 bit integer EMERGENCY RESTART SWITCH INPUT FUNCTION
0 Off
1 Emergency Switch
2 General Switch
3 Digital Counter
4 Waveform Capture
5 DeviceNet Control
6 Speed Switch1
7 Reserved
F111 Unsigned 16 bit integer TRIP RELAYS
0 none
1 Trip
2 Aux1
3 Aux2
4 Trip & Aux1
5 Trip & Aux2
6 Aux1 & Aux2
7 Trip & Aux1 & Aux2
F112 Unsigned 16 bit integer NOT DEFINED
0
1
F113 Unsigned 16 bit integer ALARM RELAYS
0 None
1 Alarm
2 Aux1
3 Aux2
Table CG–11: Memory Map Data Formats (Sheet 5 of 27)
CODE TYPE DEFINITION
CG136 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP CGCOMMUNICATIONS GUIDE
4 Alarm & Aux1
5 Alarm & Aux2
6 Aux1 & Aux2
7 Alarm & Aux1 & Aux2
F114 Unsigned 16 bit integer COUNTER TYPE
0 Increment
1 Decrement
F115 Unsigned 16 bit integer ALARM/TRIP TYPE SELECTION
0 Off
1 Latched
2 Unlatched
F116 Unsigned 16 bit integer SWITCH TYPE
0 Normally Open
1 Normally Closed
F117 Unsigned 16 bit integer RESET MODE
0 All Resets
1 Remote Reset Only
2 Local Reset Only
F119 Unsigned 16 bit integer BACKUP RELAYS
0 None
1 Aux 1
2 Aux1 & Aux2
3 Aux2
F120 Unsigned 16 bit integer RTD TYPE
0 100 Ohm Platinum
1 120 Ohm Nickel
2 100 Ohm Nickel
3 10 Ohm Copper
F121 Unsigned 16 bit integer RTD APPLICATION
0 None
1 Stator
2 Bearing
Table CG–11: Memory Map Data Formats (Sheet 6 of 27)
CODE TYPE DEFINITION
CGCOMMUNICATIONS GUIDE MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG137
3 Ambient
4 Other
F122 Unsigned 16 bit integer LOCAL/REMOTE RTD VOTING SELECTION
0 Off
1 RTD #1
2 RTD #2
3 RTD #3
4 RTD #4
5 RTD #5
6 RTD #6
7 RTD #7
8 RTD #8
9 RTD #9
10 RTD #10
11 RTD #11
12 RTD #12
13 All Stator
F123 Unsigned 16 bit integer ALARM STATUS
0 Off
1 Not Active
2 Timing Out
3 Active
4 Latched
F124 Unsigned 16 bit integer PHASE ROTATION AT MOTOR TERMINALS
0 ABC
1 ACB
F125 Unsigned 16 bit integer STARTER TYPE
0 Breaker
1 Contactor
F127 Unsigned 16 bit integer ANALOG OUTPUT PARAMETER SELECTION
0 Phase A Current
1 Phase B Current
Table CG–11: Memory Map Data Formats (Sheet 7 of 27)
CODE TYPE DEFINITION
CG138 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP CGCOMMUNICATIONS GUIDE
2 Phase C Current
3 Average Phase Current
4 AB Line Voltage
5 BC Line Voltage
6 CA Line Voltage
7 Average Line Voltage
8 Phase AN Voltage
9 Phase BN Voltage
10 Phase CN Voltage
11 Average Phase Voltage
12 Hottest Stator RTD
13 Local RTD #1
14 Local RTD #2
15 Local RTD #3
16 Local RTD #4
17 Local RTD #5
18 Local RTD #6
19 Local RTD #7
20 Local RTD #8
21 Local RTD #9
22 Local RTD #10
23 Local RTD #11
24 Local RTD #12
25 Power Factor
26 Reactive Power (kvar)
27 Real Power (kW)
28 Apparent Power (KVA)
29 Thermal Capacity Used
30 Relay Lockout Time
31 Reserved
32 Reserved
33 Reserved
Table CG–11: Memory Map Data Formats (Sheet 8 of 27)
CODE TYPE DEFINITION
CGCOMMUNICATIONS GUIDE MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG139
34 Reserved
35 Motor Load
36 MWhrs
F128 Unsigned 16 bit integer CURVE STYLE
0 Standard
1 Custom
F130 Unsigned 16 bit integer DIGITAL INPUT PICKUP TYPE
0 Over
1 Under
F131 Unsigned 16 bit integer INPUT SWITCH STATUS
0 Open
1 Closed
F133 Unsigned 16 bit integer MOTOR STATUS
0 Stopped
1 Starting
2 Running
3 Overloaded
4 Tripped
F134 Unsigned 16 bit integer CAUSE OF EVENT
0 No Event
1 Forced Setpoints Dump
2 Speed Switch Trip
3 Differential Switch Trip
4 Reserved
5 Spare Switch Trip
6 Emergency Switch Trip
7 Unexpected Reset
8 EEPROM Memory
9 Reset Switch Trip
10 Upgrade Default Dump
Table CG–11: Memory Map Data Formats (Sheet 9 of 27)
CODE TYPE DEFINITION
CG140 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP CGCOMMUNICATIONS GUIDE
11 Overload Trip
12 Short Circuit Trip
13 Short Circuit Backup Trip
14 Mechanical Jam Trip
15 Undercurrent Trip
16 Current Unbalance Trip
17 Single Phasing Trip
18 Ground Fault Trip
19 Ground Fault Backup Trip
20 Overload Block
21 Acceleration Timer Trip
22 Start Inhibit Block
23 Starts Hour Block
24 Time Between Starts Block
25 Restart Block
26 Backspin Block
27 Single Shot Restart
28 Undervoltage Trip
29 Overvoltage Trip
30 Voltage Phase Reversal Trip
31 Underfrequency Trip
32 Overfrequency Trip
33 Lead Power Factor Trip
34 Lag Power Factor Trip
35 Positive Kvar Trip
36 Negative Kvar Trip
37 Underpower Trip
38 Reverse Power Trip
Table CG–11: Memory Map Data Formats (Sheet 10 of 27)
CODE TYPE DEFINITION
CGCOMMUNICATIONS GUIDE MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG141
39 RTD1 Trip
40 RTD2 Trip
41 RTD3 Trip
42 RTD4 Trip
43 RTD5 Trip
44 RTD6 Trip
45 RTD7 Trip
46 RTD8 Trip
47 RTD9 Trip
48 RTD10 Trip
49 RTD11 Trip
50 RTD12 Trip
51 Reserved
52 Reserved
53 Spare Switch Alarm
54 Emergency Switch Alarm
55 Diff Switch Alarm
56 Speed Switch Alarm
57 Reset Switch Alarm
58 Reserved
59 Thermal Capacity Alarm
60 Overload Alarm
61 Mechanical Jam Alarm
62 Undercurrent Alarm
63 Current Unbalance Alarm
64 Ground Fault Alarm
65 Undervoltage Alarm
66 Overvoltage Alarm
Table CG–11: Memory Map Data Formats (Sheet 11 of 27)
CODE TYPE DEFINITION
CG142 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP CGCOMMUNICATIONS GUIDE
67 Overfrequency Alarm
68 Underfrequency Alarm
69 Lead Power Factor Alarm
70 Lag Power Factor Alarm
71 Positive Kvar Alarm
72 Negative Kvar Alarm
73 Underpower Alarm
74 Reverse Power Alarm
75 RTD1 Alarm
76 RTD2 Alarm
77 RTD3 Alarm
78 RTD4 Alarm
79 RTD5 Alarm
80 RTD6 Alarm
81 RTD7 Alarm
82 RTD8 Alarm
83 RTD9 Alarm
84 RTD10 Alarm
85 RTD11 Alarm
86 RTD12 Alarm
87 RTD1 Hi Alarm
88 RTD2 Hi Alarm
89 RTD3 Hi Alarm
90 RTD4 Hi Alarm
91 RTD5 Hi Alarm
92 RTD6 Hi Alarm
93 RTD7 Hi Alarm
94 RTD8 Hi Alarm
Table CG–11: Memory Map Data Formats (Sheet 12 of 27)
CODE TYPE DEFINITION
CGCOMMUNICATIONS GUIDE MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG143
95 RTD9 Hi Alarm
96 RTD10 Hi Alarm
97 RTD11 Hi Alarm
98 RTD12 Hi Alarm
99 Reserved
100 Lost RTD Comm Alarm
101 Low RTD Alarm
102 Trip Counter Alarm
103 Current Demand Alarm
104 Kw Demand Alarm
105 Kvar Demand Alarm
106 Kva Demand Alarm
107 Digital Counter Alarm
108 Service Alarm
109 Control Power Lost
110 Control Power App
111 Emergency Restart Closed
112 Emergency Restart Open
113 Start While Blocked
114 Reserved
115 Breaker Failure
116 Welded Contactor
117 Incomplete Sequence Trip
118 Reserved
119 Reserved
120 Reserved
121 RRTD1 RTD1 Trip
122 RRTD1 RTD2 Trip
Table CG–11: Memory Map Data Formats (Sheet 13 of 27)
CODE TYPE DEFINITION
CG144 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP CGCOMMUNICATIONS GUIDE
123 RRTD1 RTD3 Trip
124 RRTD1 RTD4 Trip
125 RRTD1 RTD5 Trip
126 RRTD1 RTD6 Trip
127 RRTD1 RTD7 Trip
128 RRTD1 RTD8 Trip
129 RRTD1 RTD9 Trip
130 RRTD1 RTD10 Trip
131 RRTD1 RTD11 Trip
132 RRTD1 RTD12 Trip
133 RRTD2 RTD1 Trip
134 RRTD2 RTD2 Trip
135 RRTD2 RTD3 Trip
136 RRTD2 RTD4 Trip
137 RRTD2 RTD5 Trip
138 RRTD2 RTD6 Trip
139 RRTD2 RTD7 Trip
140 RRTD2 RTD8 Trip
141 RRTD2 RTD9 Trip
142 RRTD2 RTD10 Trip
143 RRTD2 RTD11 Trip
144 RRTD2 RTD12 Trip
145 RRTD3 RTD1 Trip
146 RRTD3 RTD2 Trip
147 RRTD3 RTD3 Trip
148 RRTD3 RTD4 Trip
149 RRTD3 RTD5 Trip
150 RRTD3 RTD6 Trip
Table CG–11: Memory Map Data Formats (Sheet 14 of 27)
CODE TYPE DEFINITION
CGCOMMUNICATIONS GUIDE MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG145
151 RRTD3 RTD7 Trip
152 RRTD3 RTD8 Trip
153 RRTD3 RTD9 Trip
154 RRTD3 RTD10 Trip
155 RRTD3 RTD11 Trip
156 RRTD3 RTD12 Trip
157 RRTD4 RTD1 Trip
158 RRTD4 RTD2 Trip
159 RRTD4 RTD3 Trip
160 RRTD4 RTD4 Trip
161 RRTD4 RTD5 Trip
162 RRTD4 RTD6 Trip
163 RRTD4 RTD7 Trip
164 RRTD4 RTD8 Trip
165 RRTD4 RTD9 Trip
166 RRTD4 RTD10 Trip
167 RRTD4 RTD11 Trip
168 RRTD4 RTD12 Trip
169 RRTD1 RTD1 Alarm
170 RRTD1 RTD2 Alarm
171 RRTD1 RTD3 Alarm
172 RRTD1 RTD4 Alarm
173 RRTD1 RTD5 Alarm
174 RRTD1 RTD6 Alarm
175 RRTD1 RTD7 Alarm
176 RRTD1 RTD8 Alarm
177 RRTD1 RTD9 Alarm
178 RRTD1 RTD10 Alarm
Table CG–11: Memory Map Data Formats (Sheet 15 of 27)
CODE TYPE DEFINITION
CG146 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP CGCOMMUNICATIONS GUIDE
179 RRTD1 RTD11 Alarm
180 RRTD1 RTD12 Alarm
181 RRTD1 RTD1 Hi Alarm
182 RRTD1 RTD2 Hi Alarm
183 RRTD1 RTD3 Hi Alarm
184 RRTD1 RTD4 Hi Alarm
185 RRTD1 RTD5 Hi Alarm
186 RRTD1 RTD6 Hi Alarm
187 RRTD1 RTD7 Hi Alarm
188 RRTD1 RTD8 Hi Alarm
189 RRTD1 RTD9 Hi Alarm
190 RRTD1 RTD10 Hi Alarm
191 RRTD1 RTD11 Hi Alarm
192 RRTD1 RTD12 Hi Alarm
193 RRTD1 Open RTD Alarm
194 RRTD1 Low RTD Alarm
195 RRTD2 RTD1 Alarm
196 RRTD2 RTD2 Alarm
197 RRTD2 RTD3 Alarm
198 RRTD2 RTD4 Alarm
199 RRTD2 RTD5 Alarm
200 RRTD2 RTD6 Alarm
201 RRTD2 RTD7 Alarm
202 RRTD2 RTD8 Alarm
203 RRTD2 RTD9 Alarm
204 RRTD2 RTD10 Alarm
205 RRTD2 RTD11 Alarm
206 RRTD2 RTD12 Alarm
Table CG–11: Memory Map Data Formats (Sheet 16 of 27)
CODE TYPE DEFINITION
CGCOMMUNICATIONS GUIDE MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG147
207 RRTD2 RTD1 Hi Alarm
208 RRTD2 RTD2 Hi Alarm
209 RRTD2 RTD3 Hi Alarm
210 RRTD2 RTD4 Hi Alarm
211 RRTD2 RTD5 Hi Alarm
212 RRTD2 RTD6 Hi Alarm
213 RRTD2 RTD7 Hi Alarm
214 RRTD2 RTD8 Hi Alarm
215 RRTD2 RTD9 Hi Alarm
216 RRTD2 RTD10 Hi Alarm
217 RRTD2 RTD11 Hi Alarm
218 RRTD2 RTD12 Hi Alarm
219 RRTD2 Open RTD Alarm
220 RRTD2 Low RTD Alarm
221 RRTD3 RTD1 Alarm
222 RRTD3 RTD2 Alarm
223 RRTD3 RTD3 Alarm
224 RRTD3 RTD4 Alarm
225 RRTD3 RTD5 Alarm
226 RRTD3 RTD6 Alarm
227 RRTD3 RTD7 Alarm
228 RRTD3 RTD8 Alarm
229 RRTD3 RTD9 Alarm
230 RRTD3 RTD10 Alarm
231 RRTD3 RTD11 Alarm
232 RRTD3 RTD12 Alarm
233 RRTD3 RTD1 Hi Alarm
234 RRTD3 RTD2 Hi Alarm
Table CG–11: Memory Map Data Formats (Sheet 17 of 27)
CODE TYPE DEFINITION
CG148 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP CGCOMMUNICATIONS GUIDE
235 RRTD3 RTD3 Hi Alarm
236 RRTD3 RTD4 Hi Alarm
237 RRTD3 RTD5 Hi Alarm
238 RRTD3 RTD6 Hi Alarm
239 RRTD3 RTD7 Hi Alarm
240 RRTD3 RTD8 Hi Alarm
241 RRTD3 RTD9 Hi Alarm
242 RRTD3 RTD10 Hi Alarm
243 RRTD3 RTD11 Hi Alarm
244 RRTD3 RTD12 Hi Alarm
245 RRTD3 Open RTD Alarm
246 RRTD3 Low RTD Alarm
247 RRTD4 RTD1 Alarm
248 RRTD4 RTD2 Alarm
249 RRTD4 RTD3 Alarm
250 RRTD4 RTD4 Alarm
251 RRTD4 RTD5 Alarm
252 RRTD4 RTD6 Alarm
253 RRTD4 RTD7 Alarm
254 RRTD4 RTD8 Alarm
255 RRTD4 RTD9 Alarm
256 RRTD4 RTD10 Alarm
257 RRTD4 RTD11 Alarm
258 RRTD4 RTD12 Alarm
259 RRTD4 RTD1 Hi Alarm
260 RRTD4 RTD2 Hi Alarm
261 RRTD4 RTD3 Hi Alarm
262 RRTD4 RTD4 Hi Alarm
Table CG–11: Memory Map Data Formats (Sheet 18 of 27)
CODE TYPE DEFINITION
CGCOMMUNICATIONS GUIDE MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG149
263 RRTD4 RTD5 Hi Alarm
264 RRTD4 RTD6 Hi Alarm
265 RRTD4 RTD7 Hi Alarm
266 RRTD4 RTD8 Hi Alarm
267 RRTD4 RTD9 Hi Alarm
268 RRTD4 RTD10 Hi Alarm
269 RRTD4 RTD11 Hi Alarm
270 RRTD4 RTD12 Hi Alarm
271 RRTD4 Open RTD Alarm
272 RRTD4 Low RTD Alarm
273 Power Failure
274 Software Reset
275 Clock Failure
276 A/D Failure
277 Autorestart Attempt
278 Autorestart Success
279 Autorestart Aborted 1
280 Autorestart Aborted 2
281 Autorestart Aborted 3
282 Autorestart Aborted 4
283 Autorestart Aborted 5
284 Motor Running
285 Motor Stopped
286 Fieldbus Comms Reset
287 RTD 1 Open Alarm
288 RTD 2 Open Alarm
289 RTD 3 Open Alarm
290 RTD 4 Open Alarm
Table CG–11: Memory Map Data Formats (Sheet 19 of 27)
CODE TYPE DEFINITION
CG150 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP CGCOMMUNICATIONS GUIDE
291 RTD 5 Open Alarm
292 RTD 6 Open Alarm
293 RTD 7 Open Alarm
294 RTD 8 Open Alarm
295 RTD 9 Open Alarm
296 RTD 10 Open Alarm
297 RTD 11 Open Alarm
298 RTD 12 Open Alarm
299 Starter Operation Monitor Alarm
300 Starter Operation Monitor Trip
301 Block Undercurrent/Underpower (37)
302 Unblock Undercurrent/Underpower (37)
303 Block Current Unbalance (46)
304 Unblock Current Unbalance (46)
305 Block Incomplete Sequence (48)
306 Unblock Incomplete Sequence (48)
307 Block Thermal Model (49)
308 Unblock Thermal Model (49)
309 Block Short Circuit and Backup (50)
310 Unblock Short Circuit and Backup (50)
311 Block Overload Alarm (51)
312 Unblock Overload Alarm (51)
313 Block Ground Fault (51G)
314 Unblock Ground Fault (51G)
315 Block Starts Per Hour and Time Between Starts (66)
316 Unblock Starts Per Hour and Time Between Starts (66)
317 Fieldbus Loss of Communications
318 UVR Trip
Table CG–11: Memory Map Data Formats (Sheet 20 of 27)
CODE TYPE DEFINITION
CGCOMMUNICATIONS GUIDE MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG151
319 UVR Undervoltage On
320 UVR Undervoltage Off
321 UVR In Progress On
322 UVR In Progress Off
323 UVR Close On
324 UVR Close Off
325 UVR Imm. Restart On
326 UVR Imm. Restart Off
327 UVR Stop On
328 UVR Stop Off
329 Motor Starting
F138 Reserved Reserved
F139 Reserved Reserved
F141 Unsigned 16 bit integer OUTPUT RELAY STATUS
bit 0 Trip
bit 1 Alarm
bit 2 Auxiliary 1
bit 3 Auxiliary 2
F149 Unsigned 16 Bit Integer CHANNEL 3 APPLICATION
0 MODBUS
1 Remote RTD
F150 Unsigned 16 Bit Integer OUTPUT RELAY STATUS
0 De - Energized
1 Energized
F151 Unsigned 16 Bit Integer CHANNEL TYPE
0 RS 485
1 Fiber Optic
F152 Unsigned 16 Bit Integer NUMBER OF RECORDS
0 1 × 64 cycles
1 2 × 32 cycles
Table CG–11: Memory Map Data Formats (Sheet 21 of 27)
CODE TYPE DEFINITION
CG152 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP CGCOMMUNICATIONS GUIDE
2 4 × 16 cycles
3 8 × 8 cycles
F156 Unsigned 16 Bit Integer REMOTE RTD COMMUNICATION STATUS
0 Remote RTD Module Communication Lost
1 Remote RTD Communication on Line
F157 Unsigned 16 Bit Integer DIFFERENTIAL SWITCH INPUT FUNCTION
0 OFF
1 Differential Switch
2 General Switch
3 Digital Counter
4 Waveform Capture
5 DeviceNet Control
6 Reserved
7 Reserved
F158 Unsigned 16 Bit Integer SPEED SWITCH INPUT FUNCTION
0 OFF
1 Speed Switch
2 General Switch
3 Digital Counter
4 Waveform Capture
5 DeviceNet Control
6 Two-speed Monitor1
7 Reserved
F159 Unsigned 16 Bit Integer SPARE SWITCH INPUT FUNCTION
0 OFF
1 Starter Status Switch
2 General Switch
3 Digital Counter
4 Waveform Capture
5 DeviceNet Control
Table CG–11: Memory Map Data Formats (Sheet 22 of 27)
CODE TYPE DEFINITION
CGCOMMUNICATIONS GUIDE MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG153
6 Reserved
7 Reserved
F160 Unsigned 16 Bit Integer RESET SWITCH INPUT FUNCTION
0 OFF
1 Reset Switch
2 General Switch
3 Digital Counter
4 Waveform Capture
5 DeviceNet Control
6 Speed Switch1
7 Reserved
F161 Unsigned 16 Bit Integer OUTPUT RELAY FAILSAFE CODE
0 Failsafe
1 Non Failsafe
F162 Unsigned 16 Bit Integer ACCESS LEVEL
0 Read Only
1 Read / Write
2 Factory Service
F163 Unsigned 16 Bit Integer RRTD DIGITAL INPUT FUNCTION
0 Off
1 undefined
2 General Switch
3 Digital Counter
F164 Unsigned 16 Bit Integer COMMUNICATIONS MODULE STATUS
0x0001 Ethernet Connection OK
0x0002 IP Configuration OK
0x0004 IP Address Error
0x0008 Communications Module Error
0x0010 Network Activity Present
Table CG–11: Memory Map Data Formats (Sheet 23 of 27)
CODE TYPE DEFINITION
CG154 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP CGCOMMUNICATIONS GUIDE
F165 Unsigned 16 Bit Integer OVERALL HOTTEST STATOR RTD OWNER
0 No RTDs programmed or available
1 Remote RTD #1
2 Remote RTD #2
3 Remote RTD #3
4 Remote RTD #4
5 Local 369
F166 Unsigned 16 Bit Integer ENERGY UNIT DISPLAY
0 Mega
1 Kilo
F169 Unsigned 16 Bit Integer TRIP AND ALARM RELAYS
0 None
1 Trip
2 Alarm
3 Aux1
4 Aux2
5 Trip and Alarm
6 Trip and Aux1
7 Trip and Aux2
8 Alarm and Aux1
9 Alarm and Aux2
10 Aux1 and Aux2
11 Trip and Alarm and Aux1
12 Trip and Alarm and Aux2
13 Trip and Aux1 and Aux2
14 Alarm and Aux1 and Aux2
15 All Relays
F180 Unsigned 16 Bit Integer ANSI/IEEE DEVICE
0 37 - Undercurrent/Underpower
1 46 - Current Unbalance
Table CG–11: Memory Map Data Formats (Sheet 24 of 27)
CODE TYPE DEFINITION
CGCOMMUNICATIONS GUIDE MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG155
2 48 - Incomplete Sequence
3 49 - Thermal Model
4 50 - Short Circuit and Backup
5 51 - Overload Alarm
6 51G - Ground Fault
7 66 - Starts Per Hour / Time Between Starts
F181 Unsigned 16 Bit Integer OUTPUT RELAY TYPE
0 Latched
1 Pulsed
F182 Unsigned 16 Bit Integer PROTECTION FUNCTION BLOCKING STATUS
0 Not Blocked
1 Blocked
F183 16 bits ACTIVELY COMMUNICATING RRTDs
xxxx xxxx xxxx 0000 No RRTDs Actively Communicating
xxxx xxxx xxxx xxx1 RRTD1 Communicating
xxxx xxxx xxxx xx1x RRTD2 Communicating
xxxx xxxx xxxx x1xx RRTD3 Communicating
xxxx xxxx xxxx 1xxx RRTD4 Communicating
F184 Unsigned 16 bit Integer DATA RECORD ACCESS TYPE
0 Access Trace Memory data
1 Access Motor Start Data Logger data
F185 Unsigned 16 bit Integer VT CONNECTION TYPE
0 Phase-Neutral Voltage
1 Phase-Phase Voltage
F186 Unsigned 16 bit Integer MOTOR SPEED
0 Not Programmed
1 Speed 1 (Low Speed)
2 Speed 2 (High Speed)
F187 16 bitS START/STOP DATA LOG COMMAND
Table CG–11: Memory Map Data Formats (Sheet 25 of 27)
CODE TYPE DEFINITION
CG156 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP CGCOMMUNICATIONS GUIDE
0 None (Select Command)
1 Start Log
2 Stop Log
F188 16 bitS DATA LOG RECORDING TYPE
0 Run To Fill
1 Circulate
F189 SEE TABLE 9-12 BELOW
F190 16 bitS DATA LOG STATUS
0 Stopped
1 Running
F191 16 bits DATA LOG START/STOP METHOD
xxxx xxxx xxxx xxx1 Log 1/9/17/25/33/41/49 Start Method
xxxx xxxx xxxx xx1x Log 1/9/17/25/33/41/49 Stop Method
xxxx xxxx xxxx x1xx Log 2/10/18/25/34/42/50 Start Method
xxxx xxxx xxxx 1xxx Log 2/10/18/25/34/42/50 Stop Method
xxxx xxxx xxx1 xxxx Log 3/11/19/25/35/43/ Start Method
xxxx xxxx xx1x xxxx Log 3/11/19/25/35/43/ Stop Method
xxxx xxxx x1xx xxxx Log 4/12/20/25/36/44/ Start Method
xxxx xxxx 1xxx xxxx Log 4/12/20/25/36/44/ Stop Method
xxxx xxx1 xxxx xxxx Log 5/13/21/25/37/45/ Start Method
xxxx xx1x xxxx xxxx Log 5/13/21/25/37/45/ Stop Method
xxxx x1xx xxxx xxxx Log 6/14/22/25/38/46/ Start Method
xxxx 1xxx xxxx xxxx Log 6/14/22/25/38/46/ Stop Method
xxx1 xxxx xxxx xxxx Log 7/15/23/25/39/47/ Start Method
xx1x xxxx xxxx xxxx Log 7/15/23/25/39/47/ Stop Method
x1xx xxxx xxxx xxxx Log 8/16/24/25/40/48/ Start Method
1xxx xxxx xxxx xxxx Log 8/16/24/25/40/48/ Stop Method
BIT VALUE
0 Log Started/Stopped From Motor Start/Stop or Run To Fill
1 Log Started/Stopped Manually
F192 Bitmask 369 DIGITAL INPUT AND OUTPUT RELAY STATUS
xxxx xxxx xxxx xxx1 Access Switch
Table CG–11: Memory Map Data Formats (Sheet 26 of 27)
CODE TYPE DEFINITION
CGCOMMUNICATIONS GUIDE MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG157
xxxx xxxx xxxx xx1x Speed Switch
xxxx xxxx xxxx x1xx Spare Switch
xxxx xxxx xxxx 1xxx Differential Switch
xxxx xxxx xxx1 xxxx Emergency Switch
xxxx xxxx xx1x xxxx Remote Reset Switch
xxxx xxx1 xxxx xxxx Trip Relay Status
xxxx xx1x xxxx xxxx Alarm Relay Status
xxxx x1xx xxxx xxxx Aux1 Relay Status
xxxx 1xxx xxxx xxxx Aux2 Relay Status
F193 Bitmask RRTD DIGITAL INPUT AND OUTPUT RELAY STATUS
xxxx xxxx xxxx xxx1 Digital Input 3
xxxx xxxx xxxx xx1x Digital Input 4
xxxx xxxx xxxx x1xx Digital Input 6
xxxx xxxx xxxx 1xxx Digital Input 5
xxxx xxxx xxx1 xxxx Digital Input 2
xxxx xxxx xx1x xxxx Digital Input 1
xxxx xxx1 xxxx xxxx Trip Relay Status
xxxx xx1x xxxx xxxx Alarm Relay Status
xxxx x1xx xxxx xxxx Aux1 Relay Status
xxxx 1xxx xxxx xxxx Aux2 Relay Status
1. Only shown when “ENABLE 2-SPEED MOTOR PROTECTION” is set to “Yes”
Table CG–12: Format Code F189
CODE PARAMETER LIST VALUE
DATA ITEM FORMAT CODE
F189 0 None N/A
1 Motor Thermal Capacity Used F1
2 Digital Input and Output Relays Status F192
3 Phase A Current F1
4 Phase B Current F1
5 Phase C Current F1
6 Average Phase Current F1
7 Motor Load F3
Table CG–11: Memory Map Data Formats (Sheet 27 of 27)
CODE TYPE DEFINITION
CG158 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP CGCOMMUNICATIONS GUIDE
8 Current Unbalance F1
9 Unbalanced Biased Motor Load F3
10 Ground Current F23
11 Vab* F1
12 Vbc* F1
13 Vca* F1
14 Average Line Voltage* F1
15 Van* F1
16 Vbn* F1
17 Vcn* F1
18 Average Phase Voltage* F1
19 System Frequency F3
20 Power Factor F21
21 Real Power (kW) F4
22 Real Power (hp) F1
23 Reactive Power F4
24 Apparent Power F1
25 Positive MegaWatthours F1
26 Positive Megavarhours F1
27 Negative Megavarhours F1
28 Positive KiloWatthours F1
29 Positive Kilovarhours F1
30 Negative Kilovarhours F1
31 Local RTD #1 Temperature F4
32 Local RTD #2 Temperature F4
33 Local RTD #3 Temperature F4
34 Local RTD #4 Temperature F4
35 Local RTD #5 Temperature F4
36 Local RTD #6 Temperature F4
37 Local RTD #7 Temperature F4
38 Local RTD #8 Temperature F4
39 Local RTD #9 Temperature F4
Table CG–12: Format Code F189
CODE PARAMETER LIST VALUE
DATA ITEM FORMAT CODE
CGCOMMUNICATIONS GUIDE MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG159
40 Local RTD #10 Temperature F4
41 Local RTD #11 Temperature F4
42 Local RTD #12 Temperature F4
43 Current Demand F1
44 Real Power Demand F1
45 Reactive Power Demand F1
46 Apparent Power Demand F1
47 Peak Current Demand F1
48 Peak Real Power Demand F1
49 Peak Reactive Power Demand F1
50 Peak Apparent Power Demand F1
51 RRTD 1 - RTD #1 Temperature F4
52 RRTD 1 - RTD #2 Temperature F4
53 RRTD 1 - RTD #3 Temperature F4
54 RRTD 1 - RTD #4 Temperature F4
55 RRTD 1 - RTD #5 Temperature F4
56 RRTD 1 - RTD #6 Temperature F4
57 RRTD 1 - RTD #7 Temperature F4
58 RRTD 1 - RTD #8 Temperature F4
59 RRTD 1 - RTD #9 Temperature F4
60 RRTD 1 - RTD #10 Temperature F4
61 RRTD 1 - RTD #11 Temperature F4
62 RRTD 1 - RTD #12 Temperature F4
63 RRTD 2 - RTD #1 Temperature F4
64 RRTD 2 - RTD #2 Temperature F4
65 RRTD 2 - RTD #3 Temperature F4
66 RRTD 2 - RTD #4 Temperature F4
67 RRTD 2 - RTD #5 Temperature F4
68 RRTD 2 - RTD #6 Temperature F4
69 RRTD 2 - RTD #7 Temperature F4
70 RRTD 2 - RTD #8 Temperature F4
71 RRTD 2 - RTD #9 Temperature F4
Table CG–12: Format Code F189
CODE PARAMETER LIST VALUE
DATA ITEM FORMAT CODE
CG160 369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
MEMORY MAP CGCOMMUNICATIONS GUIDE
72 RRTD 2 - RTD #10 Temperature F4
73 RRTD 2 - RTD #11 Temperature F4
74 RRTD 2 - RTD #12 Temperature F4
75 RRTD 3 - RTD #1 Temperature F4
76 RRTD 3 - RTD #2 Temperature F4
77 RRTD 3 - RTD #3 Temperature F4
78 RRTD 3 - RTD #4 Temperature F4
79 RRTD 3 - RTD #5 Temperature F4
80 RRTD 3 - RTD #6 Temperature F4
81 RRTD 3 - RTD #7 Temperature F4
82 RRTD 3 - RTD #8 Temperature F4
83 RRTD 3 - RTD #9 Temperature F4
84 RRTD 3 - RTD #10 Temperature F4
85 RRTD 3 - RTD #11 Temperature F4
86 RRTD 3 - RTD #12 Temperature F4
87 RRTD 4 - RTD #1 Temperature F4
88 RRTD 4 - RTD #2 Temperature F4
89 RRTD 4 - RTD #3 Temperature F4
90 RRTD 4 - RTD #4 Temperature F4
91 RRTD 4 - RTD #5 Temperature F4
92 RRTD 4 - RTD #6 Temperature F4
93 RRTD 4 - RTD #7 Temperature F4
94 RRTD 4 - RTD #8 Temperature F4
95 RRTD 4 - RTD #9 Temperature F4
96 RRTD 4 - RTD #10 Temperature F4
97 RRTD 4 - RTD #11 Temperature F4
98 RRTD 4 - RTD #12 Temperature F4
Table CG–12: Format Code F189
CODE PARAMETER LIST VALUE
DATA ITEM FORMAT CODE
CGCOMMUNICATIONS GUIDE MEMORY MAP
369 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE CG161
99 RRTD 1 – Digital Input and Output Relays Status F193
100 RRTD 2 – Digital Input and Output Relays Status F193
101 RRTD 3 Digital Input and Output Relays Status F193
102 RRTD 4 Digital Input and Output Relays Status F193
Table CG–12: Format Code F189
CODE PARAMETER LIST VALUE
DATA ITEM FORMAT CODE
369 MOTOR MANAGEMENT RELAY– INSTRUCTION MANUAL A–163
369 Motor Management Relay
Appendix: Revisions
GE Consumer & IndustrialMultilin
Revisions
A.1 Change Notes
A.1.1 Revision History
Table A–1: Revision History
MANUAL P/N RELEASE DATE ECO
1601-9046-A1 (New Manual) 31 March 2008
1601-9046-A2 17 October 2008
1601-9046-A3 13 March 2009
1601-9046-A4 3 June 2010
Table A–2: Major Updates for 369CG-A4
SECTION A3 SECTION A4 CHANGES
New manual revision number: A4
4.1 4.1 New section added in DeviceNet section: DeviceNet Loss of Communication Trip
6.7 6.7 Minor Modbus Map (Fieldbus) changes.
Table A–3: Major Updates for 369CG-A3
SECTION A2 SECTION A3 CHANGES
New manual revision number: A3
N/A 1.6 New section: Ethernet Loss of Communication Trip
A–164 369 MOTOR MANAGEMENT RELAY– INSTRUCTION MANUAL
CHANGE NOTES CHAPTER A: REVISIONS
6.7 6.7 Modbus Map changes (from Profibus to Fieldbus) - three addresses only.
Table A–4: Major Updates for 369CG-A2
SECTION SECTION CHANGES
New manual revision number: A2
4.2 4.2 Tables CG 8 and CG 9 Format Code corrections
Table A–3: Major Updates for 369CG-A3
SECTION A2 SECTION A3 CHANGES
CHAPTER A: REVISIONS WARRANTY
369 MOTOR MANAGEMENT RELAY– INSTRUCTION MANUAL A–165
A.2 Warranty
A.2.1 Warranty Information
GE MULTILIN RELAY WARRANTY
General Electric Multilin (GE Multilin) warrants each relay it manufactures to be free from defects in material and workmanship under normal use and service for a period of 24 months from date of shipment from factory.
In the event of a failure covered by warranty, GE Multilin will undertake to repair or replace the relay providing the warrantor determined that it is defective and it is returned with all transportation charges prepaid to an authorized service centre or the factory. Repairs or replacement under warranty will be made without charge.
Warranty shall not apply to any relay which has been subject to misuse, negligence, accident, incorrect installation or use not in accordance with instructions nor any unit that has been altered outside a GE Multilin authorized factory outlet.
GE Multilin is not liable for special, indirect or consequential damages or for loss of profit or for expenses sustained as a result of a relay malfunction, incorrect application or adjustment.
For complete text of Warranty (including limitations and disclaimers), refer to GE Multilin Standard Conditions of Sale.