Introduction Relay:
Zones limit The nominal shape of the 7SA610 characteristic curve is shown in the following image.
7SA610 characteristic curve It is a characteristic polygonal curve with the following features: Directional-1: - 45°; Directional-2: 135°;
India
Knowledge Is Power SM DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
Settings are: - Values X1, X2, X3,X1B or X1L; - Values R1, R2, R3, R1B or R1L for multiphase faults - Values R1E, R2E, R3E, R1BE, R1LE, for single phase faults. .Trip time 1ph: T1,T2, T3; for trip time with mono phase faults. .Trip time >1ph: T1,T2, T3; for trip time with multi phase faults. According to the setting, the dedicated subroutine: Calculates the equations of the lines that define the nominal curve; Calculates the intersections between these lines and the corresponding angles; Given a line, that passes through the axis origin and is inclined of a certain angle referred to the R axis, calculates the intersections with the characteristic curve in terms of resistance and reactance: these are the nominal values that the test subroutine must compute. Relay Settings: R1 = 1.363 Ohms R1E = 10.613 Ohms X1 = 0.569 Ohms R2 = 1.468 Ohms R2E = 10.72 Ohms X2 = 1.09088 Ohms R3 = 1.8 Ohms R3E = 11.05 Ohms X3 = 2.764 Ohms Line Angle = 78 degree Inclination Angle = 78 degree RE/RL = 0.77 XE/XL = 3.01
India
Knowledge Is Power SM DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
TEST CIRCUIT OF 7SA610 relay
I1
I2
I3
VA
VB
VC
Ln1
India
Knowledge Is Power SM DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
Before the distance relay test start, output voltage and current are zero. When the program is started, three healthy voltages are applied for a second. After this, the program begins with the test of the general start (if requested); then the faults simulation begins to check the zone limits. Faults are generated as follows. Phase to ground fault: on the selected phase (AN, BN, CN) the voltage decreases while the current becomes the fault current; the voltages of the other two phases are modified. Two-phase fault on the pairs AB, BC, CA. With this selection: The amplitude and the angle of the voltages will be automatically modified to simulate a two-phase fault without ground. The two currents (IA & IB) are equal in module but opposite in phase. Three-phase fault: The three voltages have the same module, and also the three currents. After the relay tripping, the fault lasts for a programmable time (corresponding to the breaker opening delay) before returning to healthy conditions. Before starting with a new fault, healthy values are kept for a programmable time, to allow the reset of the relay under test.
India
Knowledge Is Power SM DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
How to Export the relay settings for Test from DIGSI software?
Double click on “Setting Group A”
India
Knowledge Is Power SM DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
Now, Open address “0013”
India
Knowledge Is Power SM DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
It shows the zone settings like Zone Z1/Z2/Z3/Z4/Z5.
Now, Zone Z1 settings are; 1301 = Forward 1302---- R1 = 1.363 Ohms 1303---- X1 = 0.569 Ohms 1304---- R1E = 10.619 Ohms 1305---- T1 = 0 seconds
India
Knowledge Is Power SM DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
Zone Z2
Now, Zone Z2 settings are; 1311 = Forward 1312---- R2 = 1.468 Ohms 1313---- X2 = 1.099 Ohms 1314---- R2E = 10.720 Ohms 1315---- T2 for SLG = 0.3 seconds 1316---- T2 for LL & L-L-L = 0.3 seconds
India
Knowledge Is Power SM DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
Now, Zone Z3 settings are; 1321 = Forward 1322---- R3 = 1.8 Ohms 1323---- X3 = 2.764 Ohms 1324---- R3E = 11.05 Ohms 1325---- T3 for SLG = 1.0 seconds
India
Knowledge Is Power SM DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
Press on “Graph” button
India
Knowledge Is Power SM DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
It shows graph for zones
Z1, Z2, Z3 are for LL & L-L-L faults Z1E, Z2E & Z3E are for SLG fault
India
Knowledge Is Power SM DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
Press on “Export” button to export RIO file
India
Knowledge Is Power SM DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
Save file as a “RIO” file in “C” drive
India
Knowledge Is Power SM DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
Now, open the F6TEST software
India
Knowledge Is Power SM DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
Select database
India
Knowledge Is Power SM DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
Create new relay (Ctrl + A) or double click on existing DB
India
Knowledge Is Power SM DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
Click on “Relay parameters” Tab
Press “Import” button to import RIO file
India
Knowledge Is Power SM DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
Open existing RIO file
India
Knowledge Is Power SM DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
Rename file as “K_T_1”.
Press “Apply” button
India
Knowledge Is Power SM DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
How to open RIO file in F6TEST?
This is the “K_T_1” file & press “show” button
India
Knowledge Is Power SM DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
It shows zone settings
India
Knowledge Is Power SM DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
Compensation settings are automatically imported
RE/RL & XE/XL
India
Knowledge Is Power SM DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
Click on “TestPlan”
Now, Open test plan
India
Knowledge Is Power SM DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
Module type: Z-Char Open Z-char module for characteristic test
India
Knowledge Is Power SM DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
Open “Test Elements” Tab Select setting file “K_T_1”
India
Knowledge Is Power SM DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
Open “Test Configuration” Tab “Test method” Tab
Select “Test Method type” (Constant I, Constant V & Constant Z)
India
Knowledge Is Power SM DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
Open “Test Timing & Trigger selection” Select “time option” (Cycles, Milliseconds, Seconds)
Select Trigger type: AB, BC & CA
India
Knowledge Is Power SM DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
Click on “Test Lines” Tab
Select option: “Radial Lines” Enter the boundary (say 0 – 20 degree insteps of 10 degrees)
India
Knowledge Is Power SM DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
Click on “Test” Tab. Select “AB” fault
Select fault type: AB, BC & CA Phasor shows; magnitude & angle of fault voltage & current
India
Knowledge Is Power SM DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
Results (BC-Fault):
Blue line shows “Expected boundary” & Green points shows actual operating boundary
India
Knowledge Is Power SM DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
Results (CA-Fault):
India
Knowledge Is Power SM DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
Now, select “Ph-N” fault in “Test Elements” Tab
India
Knowledge Is Power SM DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
Test Method: Constant Current
Select “separate arc resistance” options
India
Knowledge Is Power SM DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
Fault type: AN, BN, CN & TRIGGER: Open to Close
India
Knowledge Is Power SM DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
Test Lines for Fault Type: Ph-N Test Lines Method: Radial Lines
Enter Angle Boundary & delta steps
India
Knowledge Is Power SM DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
Click on “Test” Tab
Fault type: AN Results
India
Knowledge Is Power SM DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
Results: BN-Fault
India
Knowledge Is Power SM DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
Results: CN-Fault
India
Knowledge Is Power SM DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
Time Test:
Module Type: Z-TIME Double click on “Time test”
India
Knowledge Is Power SM DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
Fault type: “Ph-Ph” in “Test Elements” Tab
India
Knowledge Is Power SM DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
Test Method: Constant Current
India
Knowledge Is Power SM DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
Fault type: AB, BC, CA TRIGGER NAME TRIGGER CONDITION: Open to Close
India
Knowledge Is Power SM DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
Click on “Add boundary Test Points” button
Z Angle %Zone “Expected Time” for zone operation
India
Knowledge Is Power SM DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
Results (AB-Fault): Graph shows in “R-X” Plane
%Zone = 94.9% to 105% It should be operated on 94.9% & not operated on 105%
India
Knowledge Is Power SM DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
Results (AB-Fault):
Graph shows in “Z-T” Plane
India
Knowledge Is Power SM DATE 1/01/2006
Apparatus Maintenance and Power Management For Energy Delivery
DOBLE ENGINEERING PVT LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA-390 015 DOBLE ENGINEERING COMPANY, 85-WALNET STREET, WATERTOWN, USA
www.doble.com
DOBLE ENGINEERING PVT LTD 305-SAKAR, OLD PADRA ROAD
VADODARA-390 015, INDIA PH: +91 265 655 77 15 Cell: +91 94267 47545
Email: [email protected] Website: www.doble.com