Engine
monitoringsystem
3500 engines
-
7/27/2019 3500 Engine Monitoring System
2/15
ECM monitors parameters
and Initiate an action if a specific
operating parameter extends
outside an acceptable range
-
7/27/2019 3500 Engine Monitoring System
3/15
ECM actions
Warning.
Derate . Shutdown.
-
7/27/2019 3500 Engine Monitoring System
4/15
ET
Used to select desired action available for
ECM.
Used to program monitoring level.
Used to program delay time for each
action.
-
7/27/2019 3500 Engine Monitoring System
5/15
Histogram
Displayed by the ET to show the trend of
performance for the engine.
Available for speed, load, lh exhausttemperature and rh exhaust temperature.
-
7/27/2019 3500 Engine Monitoring System
6/15
Start enable out put :-
indicate the engine may crank.
Relay
energized
De-energized
No. of crank cycle reached
-
7/27/2019 3500 Engine Monitoring System
7/15
Shut down notification
Provide indication when the engine control
is shutting down the engine i.e. relay is de-
energized.
-
7/27/2019 3500 Engine Monitoring System
8/15
De-energizing the relay
Relay is de-energized if :-
Engine is shu t downby programmable
monitoring system Remote emergency stopswitch is activated
The customer communication module (CCM)
requested a normal shutdown. CCM request an emergency stopshu tdown.
-
7/27/2019 3500 Engine Monitoring System
9/15
Engine is shutdown by over speed verify
feature.
Engine is in the off or stop state.
Personality module inter lock occurs.
Speeds drop below crank terminate
speed.
-
7/27/2019 3500 Engine Monitoring System
10/15
Fuel consumption adjustment
Adjusting the total fuel consumption.
ECM replacement.
New ECM programming.
allow increment change.
Password.
-
7/27/2019 3500 Engine Monitoring System
11/15
ECM hours increment adjustment :-
Adjusting the hour meter of ECM.
Allow the new ECM to be programmed to
display the correct no. of operating hours.
Allows only increment changes.
Need a password.
-
7/27/2019 3500 Engine Monitoring System
12/15
ECM voltage
ECM warns operatorof low system voltage.
Voltage monitoring
Parameter Default
setting
Warningsetpoint
20 volts
Warning
delay
10 seconds
Hysteresis 2 volts
Security
level
No required
password
-
7/27/2019 3500 Engine Monitoring System
13/15
After cooler coolant temperature
ForSCAC engines:-
WarningDerating
Shutdown
e.g. derate set point :102 degree c.
-
7/27/2019 3500 Engine Monitoring System
14/15
Jacket water after coolingAbove 102 c for 5 sec warning.
*Above 107 c for 5 sec derating.
*Above 107 c for 5 sec shutdown.
*because customers prefer shut down forafter cooler coolant .
-
7/27/2019 3500 Engine Monitoring System
15/15
Engine over speed
Warning.
Shutdown.
Setpoints depend on application and
engine .
Rating of 1200-1400.
Warning and shut down simultaneously.