3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection...

69
PROGRAM SECTION No. SEP-UIP-IPEC Revision No. 0 Page 1 of 69 INDIAN POINT 2 & 3 UNDERGROUND COMPONENTS INSPECTION PLAN ENTERGY NUCLEAR ENGINEERING PROGRAMS APPLICABLE SITES All Sites: 0 Specific Sites: ANO D GGNS D IPEC 1:>!;1 JAF D PLP D PNPS D RBS D VY [] W3 [J HQN f_] Current Revision Safety Related: 0 Yes No Program Section Revision Summary Description of Change 0 I New program section in response to NEI 09·14 for underground/buried equipment inspections. I 1'- ('1) 0 """" ('I) N 0 0 () w 0... 1'- C") 0 "<t (") N 0 0 () UJ a_

Transcript of 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection...

Page 1: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

PROGRAM SECTION No. SEP-UIP-IPEC Revision No. 0

Page 1 of 69

INDIAN POINT 2 & 3

UNDERGROUND COMPONENTS INSPECTION PLAN

ENTERGY NUCLEAR ENGINEERING PROGRAMS

APPLICABLE SITES

All Sites: 0

Specific Sites: ANO D GGNS D IPEC 1:>!;1 JAF D PLP D PNPS D RBS D VY [] W3 [J HQN f_]

Current Revision

Safety Related: 0 Yes

~ No

Program Section Revision Summary

Description of Change

0 I New program section in response to NEI 09·14 for underground/buried equipment inspections.

I

1'­('1) 0

"""" ('I) N 0 0 () w 0...

1'­C") 0 "<t (")

N 0 0 () UJ a_

Page 2: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

PROGRAM SECTION No. SEP-UIP-IPEC Revision No. 0

Page 2 ol69

REVIEW AND CONCURRENCE SHEET

Program Section Title: Indian Point Underground Comgonents Inspection Plan

Prepared By: /) '"

R. C. Lee !< ('~..__..=;;.,.._.. __ Date: -Jf.·.-2-2 .IJ

Reviewed By: A peDonato Date: r/ ;;L

Concurred: Date: .. 4 { 21111

00 ('I) 0

"""" ('I) N 0 0 () w 0...

00 ("") 0 '<t ("")

N 0 0 () UJ a..

Page 3: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

SECTION Main Body Appendix A Appendix B Appendix C Appendix D Appendix E Appendix F Appendix G Appendix H

PROGRAM SECTION No. SEP·UIP-!PEC Revision No. 0

Page 3 of 69

REVISION STATUS SHEET

PAGE NO, 1 - 17 18- 51 52 .. 56 57-59 60 61 .. 62 63-64 65 66

REV, 0 0 0 0 0 0 0 0 0

a> ('I) 0

"""" ('I) N 0 0 () w 0...

(j) ("') 0 "<t ("')

N 0 0 () UJ a..

Page 4: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

PROGRAM SECTION No. SEP-UIP-IPEC Revision No. 0

Page 4 of 69

TABLE OF CONTENTS

Section Title Page

A. PURPOSE 5

B. BACKGROUND 5

c. f1EFERENCES 6

D. DEFINITIONS 7

E. CORROSION OF METAL PIPE 8

F. CURRENT INDUSTRY EFFORTS 8

G. CURRENT ENTERGY EFFORTS 9

H. INSPECTION STRATEGY AND METHODOLOGIES 10

I. OPERATING EXPERIENCE ... 14

J. PROGRAM INTERFACES 17

K. APPENDICES: ............. ., ........................................................................ 18 APPENDIX A: Piping Inspection Information ............... ,. ..................... .,. 19 APPENDIX B: Tank Inspection Information .......................................... 52 APPENDiX C: Sump Inspection Information ......................................... 57 APPENDIX D: Drain Inspection Information .. ., . ., ........ ., .. ., . ., ..... ., ........... 60 APPENDIX E: Cathodic Protection PM Information ............................... 61 APPENDIX F: Component Inspection Data Sheet (Typical) .................. 63 APPENDIX G: Integrated Schedule ..... ., ............................................... 65 APPENDIX H: Program Drawings ......................................................... 66

0

"""" 0

"""" ('I) N 0 0 () w 0...

0 "<t 0 "<t (")

N 0 0 () UJ a..

Page 5: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

A. PURPOSE

PROGRAM SECTION No. SEP-UIP-IPEC Revision No. 0

Page 5 of 69

The purpose of this Program Section is to document the site's inspection plan for underground piping and tanks. The inspection plan development represents a specific commitment milestone in the NEI Industry Initiative that is due by June 30, 2011.

B. BACKGROUND

Many nuclear plant systems contain one or more lines that are underground or buried. These systems may include safety and non-safety service water, circulating water, fire protection, diesel fuel oil, spent-fuel pool cooling water, miscellaneous radioactive lines, off-gas and yard drains. Many buried lines are coated or tape-wrapped with materials such as concrete, coal tar, asphalt-based materials, or epoxy. Although many of these lines were cathodically protected when plants were constructed, in many cases the cathodic protection system may not have been maintained or used consistently. The result is accelerated external degradation at locations where the coating has failed. Additionally, certain systems can be subject to internal corrosion as a result of microbiologically iniluenced corrosion (MIC) and other degradation mechanisms.

Over the past several years there have been instances of inadvertent releases of licensed material due to underground and buried piping leaks from nuclear power plants. While none of these instances have threatened public health and nuclear safety or compromised environmental protection, public confidence in the safe operation of nuclear power plants has been affected and needs to be addressed.

...--

"""'" 0

"""'" ('I) N 0 0 () w 0...

.,.... "<t 0 "<t ("")

N 0 0 () UJ a...

Page 6: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

C. REFERENCES

PROGRAM SECTION No. SEP-UIP-IPEC Revision No. 0

Page 6 of 69

1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007

2. "Buried Piping Integrity Initiative", November 18, 2009 3. NEI 09-14, Rev. 1 "Guideline for the Management of Buried Piping Integrity",

January 201 0 4. "Underground Piping and Tanks Integrity Initiative", September 2010 5. Letter to !vk William Borchardt, NRC Executive Director for Operations, titled

"Industry Initiative on Buried Piping Integrity", dated November 20, 2009 6. EPRI TR-·1 016456, "Recommendations for an Effective Program to Control

the Degradation of Buried Pipe", December 2008 7. Entergy Procedure EN-DC-343, Rev. 2 "Buried Piping and Tanks Inspection

and Monitoring Program'', January 2010 8. Entergy Program CEP-BPT-100, Rev 0 "Buried Piping and Tanks Inspection

and Monitoring", October 2009 9. Entergy Project Report "Guidelines for Management of Reasonable

Assurance of Integrity for Above and Under Ground SSCs Containing Radioactive Material", September 2010

10. Engineering Report ECH-EP-1 0-00001, "Radiological SSG Groundwater initiative Risk Evaluation Criteria", June 2010

11. Entergy Project Summary Report- "Radiological Material leak Prevention to Groundwater of Above and Under Ground Structures, Systems and Components", September 2010

12. EPRI Report IR-201 0-409, "Inspection Methodologies for Buried Pipes and Tanks", June 2010

13. EPRI Report 1019115, "Buried Pipe Guided Wave Examination Reference Document", Oct 2009

14. I P-SMM-EV-1 03, "Petroleum Bulk Storage Tank Program"

N

"""" 0

"""" ('I) N 0 0 () w 0...

N "<t 0 "<t ("")

N 0 0 () UJ a...

Page 7: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

D. DEFINITIONS

PROGRAM SECTION No. SEP·UIP·IPEC Revision No. 0

Page 7 of 69

Buried Piping and Tanks - Piping and tanks that are below grade and in direct contact with the soil or concrete (e.g. a wall penetration or embedded in concrete).

Cathodic Protection {CP} Tile application of a current to the outside swiace of the pipe with the purpose of reducing tile susceptibility of exposed sections of buried pipe (exposure caused by coating deterioration, damage, or voids) to corrosion. The application of a low voltage residual current causes a shift (with respect to the anode) of tile electrolytic potential at pipe exposed sites and thereby places the pipe in a more protected, less corrosive environment.

Direct Examination -- Examination performed so as to be capable of mapping and categorizing corrosion defects. Direct exam may include soil excavations that enable visual testing (VT), and manual measurements [including: ultrasonic testing (UT), radiological testing (RT), pit gage] to be performed. Direct examination can also include "smart pigging".

Indirect inspection - Inspection that provides information on the condition of an underground pipe remotely; from ground level or from an exposed section of pipe that is distant or remote from the pipe section of interest.

Reasonable Assurance (RA) - Reasonable Assurance is obtained when an engineering evaluation {including Fitness--for-Service), indirect inspections, direct examinations, and remediation, if necessary, of underground components is performed. Such a combination of activities will provide a high level of confidence that the structural and leak integrity of the piping systems will be maintained.

Underground Piping and Tanks - Piping and tanks that are below grade and that may or may not be in direct contact with soil or concrete'. This includes piping and tanks that are directly buried and those that are embedded in concrete or located in underground concrete vauits, tunnels, or guard pipes.

* Note: NUREG 1801 {GALL-Rev 2) Section XI.M41 "Buried and Underground Piping and Tan!'ls" makes the following distinction: "Briefly, buried piping and

('I)

"""" 0

"""" ('I) N 0 0 () w 0....

("')

"<t 0 "<t ("')

N 0 0 () UJ a_

Page 8: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

E. CORROSION OF METAL PIPE

PROGRAM SECTION No. SEP-UIP·IPEC Revision No. 0

Page 8 of 69

As coatings become damaged as a result of holiday formation, coal tar enamel embrittlement, tape wrap disbanding, etc., buried piping is directly exposed to soil. Without effective cathodic protection there is increased potential for external corrosion of the metal pipe.

Corrosion mechanisms of metals in buried pipe can be categorized in three broad categories:

1. Wall thinning: This category encompasses electrochemical effects that typically result in general wall loss or local wall loss such as pitting, general corrosion, galvanic corrosion, crevice corrosion, microbiologically influenced corrosion, erosion-corrosion, and preferential weld attack (grooving).

2. Environmental cracking: This category encompasses inter-granular or trans­granular cracks such as stress corrosion cracking, hydrogen induced cracking, and fatigue cracking.

3. Metallurgical effects: This category encompasses all degradation effects that cause a change to the metal microstructure or its mechanical propertiE:s.

F. CURRENT INDUSTRY EFFORTS

The industry, under the Nuclear Energy Institute's (NEI) leadership, established in the summer of 20091he Buried Piping lndustly Task Force {BPITF) that is composed of NEI, Electric Power Research Institute {EPR!), Institute of Nuclear Power Operations (IN PO), American Nuclear Insurers (ANI), and representatives. The BPITF developed the Nuclear Strategic Issues Advisory Committee (NSIAC) Buried Piping Integrity Initiative (approved by the industry's chief nuclear officers in November 2009, Reference 2} and the associated NEI 09-14, "Guideline for the Management of Buried Piping Integrity" (January 2010, Reference 3). The scope of the initiative includes all piping that is below grade, contains any fluid, and is in direct contact with the soil. The initiative was later submitted to the NRC via a letter from NEI (Reference

and tanks and below or are direct contact

with the are safety related or contain licensed materia! or are known to be contaminated with licensed materiaL The Buried Piping Integrity Initiative

and Tanks !ntearitv Initiative"· this """" """" 0

"""" (Y') N 0 0 () w 0...

"<t "<t 0 "<t (")

N 0 0 () UJ a...

Page 9: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

PROGRAM SECTION No. SEP-UIP-IPEC Revision No. 0

Page 9 of 69

The initiative includes commitments for developing an inspection or condition assessment plan by June 30, 2011 for the initial buried piping scope and by December 31, 2012 for the added underground components scope of the initiative. The pian is to provide reasonable assurance of integrity of the associated components and shall include the following key attributes:

identification of underground (below grade and buried ) piping and tanks to be assessed. Potential inspection/assessment techniques .

~ inspection/assessment schedule for underground components based on risk ranking and prioritization,

$ Assessment of cathodic protection, if applicable.

G. CURRENT ENTERGY EFFORTS

Scope was identified and risk ranking criteria were developed to help the Entergy Fleet prioritize the inspections of underground pipes and components subject to degradation initiating from either the inside of the pipe (ID initiated), or the outside of the pipe (OD initiated), or both acting in combination. Impact assessment (based on safety, public risk and economics} and corrosion risk assessment (based on soil resistivity, drainage, material and cathodic protection/coating) were initially completed to determine an inspection priority (high, medium, low). The prioritization is determined by the use of a risk matrix that rates the likelihood of failure against the consequences of failure for a given system, structure, or component (SSC) location. Since radiological SSCs were by definition considered high risk, these were futiher risk ranked relative to one another and characterized as high-high, high-medium, or high-low risk.

The required inspections are selected depending upon the risk ranking. Those components and structures ranked the highest will be addressed with a higher priority and will be examined more extensively. The components and structures ranked in the medium and lowest category may be candidates for initial deferral.

commodities is obtained whEm Fitness-for-Service evaluation, Indirect B:<aminations, and remediation, if necessary, is performed. Such a combination of activities will provide a high level of confidence that the structural and/or

will be maintained. 1.[)

"""" 0

"""" ('I) N 0 0 () w 0....

1.0 "<t 0 "<t ("")

N 0 0 () UJ [l_

Page 10: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

PROGRAM SECTION NO. SEP-UIP-IPEC f~evision No. 0 Page 10 of 69

The RA guidelines establish methods for grouping of similarly designed and constructed piping lines and then prioritizing them for inspection. The RA guidelines provide minimum requirements for indirect inspection and direct examination of piping as well as post assessment techniques to establish Reasonable Assurance of Integrity.

The Entergy-Exelon guidelines for RA are currently being reviewed by an EPRI Technical Advisory Group (TAG), of which Entergy is a member, for use across tile industry and for inclusion in the upcoming revision to NEI 09-14.

H. INSPECTION STRATEGY AND METHODOLOG.IES

Detailed descriptions and discussions have been provided for the various available inspection/examination techniques and tools for buried piping and tanks. These can be found in EPRI Report IR-2010-409 (Reference 12). Specific recommended Inspection/examination methodologies for buried pipes and tanks are summarized herein.

Preferred Inspection Mejl:Jodologies for Piping Option 1: Use of Internal Direct Examination Pig In-line pipeline examination provides the most accurate means of mapping the wall's ttlickness condition. As a result the use of in-line examination plays an important role in developing reasonable assurance of integrity.

These instrumented vehicles (called pigs) require access and possibly exit points in the piping system to enable deployment. Additionally, the deployment of the vehicle is best suited to certain piping configurations that should be assessed and determined prior to use of this method (Reference 12),

Option 2: Use of Guided Wave Indirect Inspection The guided wave approach provides rapid assessment of wall loss over relatively long runs of pipe. The guided wave inspection may be performed without taking the process pipe out-of-service. The guided wave inspection is limited to approximately 50 feet of pipe in either direction, and is limited to detecting pits and remaining wall thickness. Readings beyond a flange cannot be performed

has fJ.ono.tr;::;(flrtn~ to

(0

"""" 0

"""" ('I) N 0 0 () w 0....

<D '<t 0 '<t ("")

N 0 0 () UJ a..

Page 11: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

PROGRAM SECTION No. SEP-UIP-!PEC Revision No. 0 Page 11 of 69

The locations for pe1iorming inspection will be based on the results of a soil survey to determine the most adverse locations, together with above grade survey to detect potential coating damage, to determine inspection locations.

At inspection locations, local NDE of the pipe shall be performed together with guided wave inspection.

Option 3: Use of Local Pipe Direct Examination NDE Pipe direct examination NDE utilizes direct measurement at exposed sections of the pipe. The locations for pe1iorming examinations will be based on the results of a soil survey to determine the most adverse locations, together with above grade survey, to detect potential coating damage to determine examination locations.

Pipe Line Grouping Grouping of pipes for inspection is recommended in order to reduce the overall inspection cost and duration. Pipes can be grouped based on attributes such as pipe material, coating type, soil/backfill, age, operating parameters, size, process fluid, cathodic protection, and others. The specific grouping parameters will depend on the specific features of ihe components. The grouping of pipes with similar attributes may allow the results of the inspection to be extrapolated from one pipe to the others in the group, therefore reducing the number of excavations and cost. Completed direct examinations and results may be able to be applied to the entire underground line and to other pipes in the grouping. The Fitness for­Service Engineering Evaluation will be able to use this information to calculate remaining life and the time until the next scheduled inspection.

Guidelines relative to grouping for inspection are outlined within Attachment B of Reference 9, "Fleet Guidance for the Determination of Reasonable Assurance for Structural and/or Leakage Integrity for High Risk Underground Piping".

8 groups were identified for the site:

I'­

""" 0

"""" ('I) N 0 0 () w 0...

1'­"<t 0 "<t ("")

N 0 0 () UJ a..

Page 12: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

Pipe Une inspection Locations

PROGRAM SECTION No. SEP-UIP-IPEC Revision No. 0 Page 12 of 69

Excavations should be performed to maximize the potential to obtain information for the subject pipe and for other pipes that can be exposed in the same excavation. Several pipes being excavated in one location is preferred, but not required. Excavations shall be large enough such that a direct examination shall assess a minimum 10 feet length of pipe, if feasible. Inspection locations should be selected considering the risk ranking criteria and other information such as:

Results of risk ranking. Inspections st1ould be distributed among the higher ranked locations. Locations where piping goes through penetrations into vaults or other structures. This includes pipe that is both encased and not encased in concrete. Locations where the pipe enters or exits the soiL Locations of dissimilar materials in contact without use of insulating kits.

e Locations where the pipe enters or exits water. • Results of ID visual examinations.

Results of CP surveys and coating surveys. Select locations where CP and coating surveys cannot be performed or are questionable. Results of any remote inspections that have been performed. Plant or industry operating experience.

• Trending of past inspection results. Opportunistic inspections during maintenance activities (e.g., open valves).

• Cost and access can be considered when the risk rankings are similar.

The inspection and examination to be performed on an underground pipe or tank should be defined based on the expectation of susceptibility and the risk ranking results. The decision and basis for the decision on for inspections and examinations should be documented.

Specific guidelines for inspection of buried piping are outlined within Attachment B of Reference 9, "Fleet Guidance for the Determination of ~1easonabie Assurance for Structural and/or Leakage Integrity for High Risk Underground Piping".

Tank inspection should be performed on a prescribed inspection schedule as outlined in a PM, or as required by existing plant or state programs. The tank

the wall thickness utilize inspection data to

00

"""" 0

"""" ('I) N 0 0 () w a..

00 "<t 0 "<t ("")

N 0 0 () UJ a...

Page 13: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

PROGRAM SECTION No. SEP-UIP-IPEC Revision No. 0 Page 13 of 69

determine corrosion rate. Inspection methodologies are outlined within Reference i 2. Strategy for -~-~t§_rjgr Building and Storm Drains Relative to reasonable assurance of integrity of exterior building and storm drains, the inspection strategy should be performed as a plant facilities' action to inspect for clogging, debris, and basic functionality. Establishing basic functionality of storm drains is important since the design of such systems, often utilizing bell and spigot concrete or cast ductile iron pipe, can be susceptible to leakage as a result of joint separation from settlement or soil erosion undermining the support of the pipe.

The site will establish a PM frequency for this SSC. As an example, an initial inspection frequency can be established and adjusted based on the results of inspection for continuity. If the pipe has been in place for a number of years and has not be subjected to ground surface disturbances, then a longer inspection period beyond the initial inspection could be warranted and justified. Drainage piping subject to local vicinity excavation from site const1uction activities, haul path loading, or soil erosion (as examples), may warrant a shortE:r inspection period to ensure continuity of flow, PM frequency to ensure flow path (removing any clogging from site debris} may be warranted on a shorter cycle to that for establishing continuity, based on specific site conditions.

Mitigation and leak management strategies should be implemented if !he drains are found to be leaking or sever;~ly degraded.

Strategy for In-Building FIQ.Q!:.JdL§)D..§ In-building floor drains located at the lower elevations of buildings and structures, and accessible and inaccessible tunnels and vaults are typically embedded within the structures concrete and have soil on the outside of the structure or in direct contact with the soiL

Relative to reasonable assurance of integrity of interior fioor drains, the strategy should be performed to inspect for clogging, debris, and ensure basic continuity and functionality. Provided the interior floor drains are protected with a floor grate, the potentia! for repeat clogging is effectively eliminated. For f!oor drains embedded within the structures concrete, the assurance of integrity inspection

and ieak management strategies shall be if the floor drains are found to be !eakina or severely degraded. Such mitigation

drain and imoiE:mentina alternate a>

"""" 0

"""" ('I) N 0 0 () w 0....

(j) "<t 0 "<t (")

N 0 0 () UJ a...

Page 14: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

Strategy for Cathodic Protection

PROGRAM SECTION No. SEP-UIP-IPEC Revision No. 0 Page 14 of 69

An effective cathodic protection system is essential to minimize underground piping corrosion. However, most Entergy plant's cathodic protection systems were initially installed during plant construction and were rarely maintained. and in some cases abandoned thereafter rendering the systems incapable of providing the needed corrosion protection. In addition, many site modifications rendering t~1e underground piping network even more complex were implemented since initial plant construction without evaluating the required potential updates to the system. Therefore, it is recommended to conduct an Area Potential and Earth Current (APEC) Survey to analyze and implement needed improvements to the corrosion control (coatings) and cathodic protection effectiveness of the station.

Once the system modifications are implemented, the system will be maintained via recurring PMs based on vendor recommendations.

L OPERATING EXPERIENCE (OE)

The Underground Piping and Tanks Engineering Team examined operating experience via condition repo1i LO-HONL0-2008-15. This CR examined Entergy, nuclear industry, and petro-chemical industry events relating to underground and buried piping. Each site subsequently proposed inspection locations to verify underground/buried equipment fidelity (e.g. LO-HQNL0-2008-15 CA 387 through 395).

For this inspection plan, the OE lessons-learned examined are summarized below in the form of inspection goals (e.g., items to consider when making detailed inspection procedures) and inspection criteria. In general, LO-HONL0-2008- i 5 revealed that most underground and buried piping failures dealt primarily with legacy issues (e.g., equipment not being originally installed, operated, or maintained properly) and not pipeline aging per se. By using this insight, sma!ier inspection goals and criteria have been developed for use in inspection procedures.

0 1.[) 0

"""" ('I) N 0 0 () w 0...

0 1.0 0 '<t ('"") N 0 0 () UJ a...

Page 15: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

PROGRAM SECTION No. SEP·UIP-IPEC Revision No. 0 Page 15 of 69

Table 1 - Inspection Goals

to select final inspection site buried pipe penetrations

or complex installations.

2. Determine if available cathodic protection has been operated properly prior to performing inspection. This includes proper voltages, run time, and periodic maintenance.

3. Be alert for potential mechanical sneak circuits (e.g. piping failures caused bv more than one stressor, or a not-so-obvious stressor) that may exist in the inspection path. These include:

Previous leakage events that change underground soil conditions and create failures in adjacent equipment.

improper material pairing (e.g. aluminum on concrete base causing external corrosion)

Potentia! stray current effects from nearby equipment impacting failed equipment

External inspection of l;ne with high internal stressors such as F AC (condensate return to condenser).

improper construction of protective trenches leading to barrier breach after line failure.

Basis

OE revealed that building penetration challenged pipe integrity.

OE has revealed that many cathodic protection systems are improperly installed or improperly operated. Making this determination prior to excavation can prepare the inspection team for needed corrective action and operab;lity contingencies.

Approximately 35% of events in LO­HQNL0-2008-00015 were caused by multiple stressors that defeated in­place barriers. These events can be characterized as:

1. Proximitv failures (one event causing damage to adjacent equipment. This could be one leak that causes another leak or stray current).

2. ~fll~il?..§.li.§.Oi§ (evaporation and subseauent condensation outside the barrier, moat/drain cleanliness issues leadina to defeated barrier, internal vers<JS external corrosion as the main driver).

Note that Design, Construction, Ops, and Maintenance activities have initiated events.

Reference

OE30462

OE28063

OE27897

CR-PNP-2007-21

OE706l

CR-ANO-C-2008-1734

OE 5305

OE12844

OE13794

OE14132

OE15323

OE21958

OE25092

OE25410

OE26571

OE29'133

OE30462

OE30589

OE311'18

OE31269

SER 4-81

DOT experience

...--1.[) 0

"""" ('I) N 0 0 () w 0...

.,.... 1.0 0 "<t ("")

N 0 0 () UJ a..

Page 16: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

Goal

4. Utilize underground construction photographs (if available).

5. Examine line history and operating events that may provide equipment integrity insights.

6. Consider soil pH measurements at several depths.

7. Consider water table changes and impact on corrosion rates.

PROGRAM SECTION No. SEP-UIP-IPEC Revision No. 0 Page 16 of 69

Basis ~

HJ>Yo v• '"

Such photographs can provide insights OE30589 on potential failure locations and help prepare lor contingency planning.

Some OE shows that lines may have OE13794 been used in multiple ways and/or have

OE12844 significantly deviated from normal operation. These deltas could cause OE21958 unexpected line integrity performance.

OE15323

Soil can experience surface OE"l2844 contamination from salt and other

OE13794 chemicals. TaKing pH measurements at several depths can help determine the License Renewal potential for change. RAis

Soil chemistry changes (depending on Corrosion Principles soil moisture content) and corrosion +Water Tabie rates can significantly increase with profi!es. intermittent wetting and drying.

N 1.[) 0

"""" (Y') N 0 0 () w 0...

N 1.0 0 '<t (")

N 0 0 () UJ a...

Page 17: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

Table 2-- Generic Inspection Criteria

PROGRAM SECTION No. SEP·UiP·iPEC Revision No. 0 Page 17 of 69

1 inspection Criteria Basis Reference I

1. Ensure buried lines meet proper depths for adequate freeze protection, This can be accomplished by visual verification of depth, and visual verification for lack of freeze/thaw damage.

' Some pipe failures have occurred from improper burial depths.

CR-IP3-2009-00584

2. Inspect coatings for holidays and Some coating failures have resulted OE9163 proper installation. Consider using from aging. However, most coating E12 q License Renewal coating removal iaiiures result from improper installation ° lLS guidance from GALL Rev 2, which are (poor backfill, improper preparation, OE17575 based on line length and needed poor care, not installed, or improper OE

18 96 inspection frequencies. Examine the coating choice). 5

line for both general corrosion and OE23565 corrosion, and attempt to take '?"

measurements (or alternate OE~o997 thickness measurements) where OE27146 practicaL The acceptance criterion for pipe operability is primarily based on OE27897 minimum wall thickness since buried OE29020 piping is well supported by earth. n ~ However, gross pitting or genera! OE,:9,33 corrosion may require structural OE29126 analvsis.

- OE30927

DOT

3. Verify proper material installation Improper design or construction have OE28063 according_ to original and/or revised lead to improper material installation OEiBiag spec:f1cat:on.

4. Verify prop original and/or revised specification.

J, PROGRAI\II_lt:!_t_t;_Bf~E&

SEP~SW~001

Course backfiil has caused coat:ng failures.

IPEC Fire Protection Program per EN-DC-3aO

OE14585

OE27i46

OE29126

J

(Y') 1.[) 0

"""" (Y') N 0 0 () w 0....

(") 1.0 0 "<t (")

N 0 0 () UJ a..

Page 18: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

K. APPENDICES

PROGRAM SECTION No. SEP·UIP·IPEC Revision No. 0 Page 18 of 69

APPENDIX A: Piping Inspection Information APPENDIX 8: Tank Inspection Information APPENDIX C: Sump Inspection Information APPENDIX D: Drain Inspection Information APPENDIX E: Cathodic Protection PM information APPENDIX F: Component Inspection Data Sheet (Typical) APPENDIX G: Integrated Schedule APPENDIX H: Program Drawings

"""" 1.[) 0

"""" ('I) N 0 0 () w 0....

"<t 1.0 0 "<t ("')

N 0 0 () UJ a..

Page 19: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

APPENDIX A INSPECTION EXCEL SPREADSHEET

PROGRAM SECTION No. SEP·UIP-IPEC Revision No. 0 Page 19 of '70

!Q§fill£lli?J:L~1t!ai!§,gy A combination of indirect inspections and direct examinations will be pertormed in accordance for the Determination or Reasonable Assurance for Structural and/or Leakage Integrity for

Piping" (Reference 9). The results of the indirect inspections (e.g. above ground DCVG and/or cause the prescribed location above to be moved.

that will be used and where {e.g., guided wave at wall penetrations and then coating guided wave at excavation point; above ground DCVG and then coating inspection; NDE and

excavation point). If above ground inspection is not relevant, describe contingency.

==:..=.:...:-=:="=""·~-~··Explain why the actual 10ft location is selected (e.g. access, shoring, depth, CP protection). the uncovered lines is not being directly examined.

EXC1, EXC2, EXC3, etc.

IPEC00234055

IPEC00234055

Page 20: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

APPENDIX A PIPING INSPECTION INFORMATION

SEGMENT PIPE GROUP I NUMBER ITEM INSPEC'ri---ii---:-L-=oc~A;;:n;,o"'N-+-- =-li~=

LOCATION JUSTIFICATION

IP2 PIPiNG STARTS NEXT PAGE

IPEC00234056

PROGRAM SECTION NO. SEP-UIP-IPEC Revision No. 0 Page 20 of 69

DESCRIPTION

MISCELLANEOUS NOTES

IPEC00234056

Page 21: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

APPENDIX A PIPING INSPECTION INFORMATION

IPEC00234057

PROGRAM SECTION NO. SEP-UIP-IPEC Revision No. 0 Page 21 of 69

IPEC00234057

Page 22: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

IPEC00234058

SEGMENT NUMBER INSPECT

LOCATION

APPENDIX A PIPING INSPECTION INFORMATION

PIPE GROUP/ ITEM

LOCATION JUSTIFICATION

RISK RANKING PRI

EXCAVATION NUMBER

DIRECT SOIL?

IN-LINE INSP. II

PROGRAM SECTION NO. SEP-UIP-IPEC Revision f\h 0 Page 22 of 69

LENGTH DESCRIPTION

MISCELLANEOUS NOTES

IPEC00234058

Page 23: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

APPENDIX A PIPING INSPECTION INFORMATION

I PEC00234059

PROGRAM SECTION NO. SEP-UIP-IPEC Revision No. 0 Page 23 of 69

DESCRIPTION

IPEC00234059

Page 24: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

APPENDIX A PIPING INSPECTION INFORMATION

RISK RANKING __ (~®._.._.

EXCAVATION NUMBER

PROGRAM SECTION NO. SEP-UIP~IPEC Revision No. 0 Page 24 of 69

. : :; :: .. ::·::: :;~;:;.:·::·: : ::;.;_;,_; :::-::::: ;:.:.:~·~. ~:-: ::·: :::;: ~:(::;._;:"; :. . . ! ·:-:\ :: ;.:: .. :::- =·~:· . .::. ..\. : : :-:.;: ;::. ~-::;:~:;.; ·: i ·:: t'~:: :.~::,):· " .. \::: : .. :·:·:::-:. :·::.:-: :·~·::-:·::.::::~':::: :~:=·::.

:::: 1:.;· :·:;:-:-::: :.:~x::.::: :;::~::J.':r_:

•.•••c·:~::·.·.·::}·~~---~::·.:·.·:I.:·.·.·.·.:::·:.:~.·~·j~J '~< [. ~~:=-• t ';;2\ L ... ~-+"'";~\·~ ~•· j_~~~~~;;·; .. :·:;~~~:::;{:

IPEC00234060

IPEC00234060

Page 25: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

:::~~-:~-~.-~:=~~-:::: . ~ .

~--·.·.«~---"'"':'"':'·-:-.~ ·""''Kff:t1HT:f:"'"'"'l,1.;-;-"'"';-"';-·:;:;::··"'"'"'"'"'"'"':e-.(;-"'«"'"'~:;"'"'~"' :;::::~:~-~--::::~<=~~ .

.. :·-.::.:,::.:·:.::::.-:-::.·

APPENDIX A PIPING INSPECTION INFORMATION

PROGRAM SECTION NO. SEP~UIP·IPEC Revision No. 0 Page 25 of 69

........ ·.···········-·.-.-.·.··········· i,_ ::: -:-· · , t~rt·.-...:~······ · ··· · · · · ··· · · · · .-.-. +,_ ~~~~"""""" "" :·.:.:.::: •'{• ... ·: :·-:: . .:~ ::--:.:}. :-~;;::.

m-'·'·'·'·'·'·'·'·'·'·'·'·'·'·'·'·'.;..,;;:·;~:· :;•..:.,•. ;w,'w,_:::.:v:+· -~~~~"""""'!r--~~"""":"'~~"""":"'~"""":"'~~~"""""'1~~~~~~"""":"'1-o~~~~~"""":"'~~~~

-~-

::~·:~;:·~ .-::::::::.:~:

:x~::: ~. :~·v:·::

··-:··~-; ::: ;' fi::·:~-= .:: t,,_.

·····················t,,"::::. :'::- ·;;·:~:···...;'.'·'·'·'•'·'·'•'·'·'·'•'•'·'•'•'•'··~~~~~~~~~-<--~~~""""""r--~~-i-',;;,.;;;;;.~;.,;,;,:,.,.1--~~-+~~~~~~~~~~~ ;;-·.:: ;::· : .... .... ~~-=.:.-. :-.:.: .... :; :k:';:O, ;-;;.:.::. ~~-=.:-.

···:~::·;··:~:::~:~~-'-'-~+,.;;;;; .. ;;;._ .. "".:;, .. ;;_ ·' .... l···;.;::·~:;·;,;:::·-····;_: ........ ;,,_,,,_ !,;.·--,-::~--?-{.: .. ::~=-=::: .. : .• :-, -..r--~3 .. ::: .. :-~--~ """"'""'""'"':"":"'-+"'7\~\i""Y"":~:~:"':.;~~)":'::~ '*""""'"':"""'+--":"'-.................................... ":"' ......... ~ ::::~ ::::;. -:;:.'?~=- ~:::

·"··:::··:·:::·····~:~:=r:~;~:·N.·t· ..... ~~-~~.:"".:~!~, -~-""":':~~~/: .. ~.-""""-+"""'7""~~~.:~.~ ..... -~"':"":"''-:~ .. "":::t":", "':"":"'-+--":"'":::'~.~~::~~. ":"'+~~:~~~:;~~~=~~--=---+--"':"="':"-.~~~-."':':"'":"':':"':"""~

IPEC00234061

IPEC00234061

Page 26: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

LINE NUMBER DRAWING

OTHER

I PEC00234062

!'lAOINON­RAD

SEGMENT NUMBER INSPECT

LOCATION

APPENDIX A

PROGRAM SECTION NO. SEP-UIP-IPEC Revision No. 0 Page 26 of 69

PIPING INSPECTION INFORMATION PIPE GROUP/

ITEM LOCATION

JUSTIFICATION

RISK RANKING IPRil

EXCAVATION NUMBER

DIRECT 1: ELEVATION i LENGTH

SOIL? (DEPTH) ! IN-LINE I SCHEDULE I FUNDING INSP. # (OJYYYY) I SOURCE

DESCRIPTION

MISCELLANEOUS NOTES

IPEC00234062

Page 27: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

U~<f ~~B?o{~~-::t::·~

.. -~j?.~J\~~::·~~~(:i ... o:·N;i::.~

IPEC00234063

APPENDIX A PIPING INSPECTION INFORMATION

PROGRAM SECTION NO. SEP-UIP-IPEC Revision No. 0 Page 27 of 69

IPEC00234063

Page 28: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

APPENDIX A PIPING INSPECTION INFORMATION

PROGRAM SECTION NO. SEP-UIP-IPEC Revision No. 0 Page 28 of 69

UNIT I LINE RAD I NON· SEGMENT PIPE GROUP I RISK RANKING DIRECT ELEVATION I LENGTH DESCRIPTION 1-··c;:C s;,·v,,;:;SH: 1,E;;:;M;;,---t~~;:;;<U;7M'i7;B;c:E;i;Rc-f·~:.~R~AiZD;;;:·~+~NU;;,:M:::;B~E;,:;R,..-t-.,-,';i-IT~EM:i=.,---+--:=-:::'I~P.;.:;RI~)=--!-7.S7'0:-"iiL::f.?...-+--JQ_~J.I:1)_...J_ ______________ -------················----------------!1

DR.~~!,NG D0RATHWEI.1R'IG .INSPECT INSPECT LOCATION EXCAVATION IN-LINE SCHEDULE II FUNDING MISCELLANEOUS NOTES

'""'"'" -~, l.OCATION JUSTIFICATION NUMBER INSP.# (0/YYYY) SOURCE

IPEC00234064

IPEC00234064

Page 29: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

-·-·-·-·-·-•.•.•.•.•.•.•.•.•.•.•.•.•.•.•.• .... . ·:·:::· :

!P3

LINE NUMBER

STARTS NEXT PAGE

IPEC00234065

SEGMENT NUMBER INSPECT

LOCATION

APPENDIX A PIPING INSPECTION INFORMATION

PIPE GROUP/ ITEM

LOCATION JUSTIFICATION

RISK RANKING (PAl)

EXCAVATION NUMBER

DIRECT I ELEVA110N SOIL? I (DEPTH)

IN-LINE I SCHEDULE INSP.# I (Q/VYYV)

PROGRAM SECTION NO. SEP-UIP-IPEC Revision No. 0 Page 29 of 69

LENGTH

FUNDING SOURCE

DESCRIPTION

MISCELLANEOUS NOTES

IPEC00234065

Page 30: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

APPENDIX A PIPING INSPECTION INFORMATION

PROGRAM SECTION NO. SEP-UIP-IPEC Revision 1\io. 0 Page 30 of 69

I-ii S;;7, UYSN'-;;TIITE~ ll\ll~--1i--;N:;;:U"-'LM~IN6:T.EE;:i. fli:.:-+-R7>A::i.~~;~?:;~:';:Q:.;N-·+-;~:7;EU;:;;GM;:;,MB~EE~NR,;-T - --~~-~!_f~t~~-: .... --~~~-(~;D~~~~--- ----~~~fi:~~----1--~-~~~~~~1~__!_--~-~~~~~--- ---------------~-=S_C_RI~::_~--------------DR.~.~~NG DRAWING IMSPECT INSPECT LOCATION EXCAVATION IN-LINE i SCHEDULE i FUNDING MISCELLANEOUS NOTES

""''" OTHER STRATEGY LOCATION JUSTIFICATION NUMBER INSP.# ! (QIYYYY) i SOURCE

~ B~'.;·::::·;: ... ~·~.: .. ~: :::: ~=:::='::: ::. :;.::~ :~~-~~:: :>'t:~: t~:. :·:r-::/ .: ~=· ; : .. :)·::::· :·::··: -:.:·.···:·:

-~--~~""""T_"""~~--~......;--~-~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~::~~:~~~~~~~~~t~~~~~~~~~~~~~~~~~~l~~~~:::~~~~~~~~}~~~~~~1:~~~~~~~~~;:~~~~i~t;~:~~{~~~~~~~~~~~;:~ :-.,,: 1, :'<::.:· l :,:,:.-. l ::;:.<. 1,

' ~-~:::: ::: ·'·' ·····················..-.·.·-y-·····...-.·.·.-...-.·.······w····r·······""··""···········~'!<""........,--~+--~........,---r-........,---........,~--........,--+........,,..-=~"""'iw-"""'~-~...,.,H~:,,~,8"'~·:"': ,-,"-·'f:"";,"":·;"":,-,_,"':::,-.,,-,.,:'"':.""~:l"".::-,:,-;,"'l>-.,;-,:,·-,:.:·"":::""«"":.::..,.;:_:-«-. -i

: ~ ;~::;::-.::;:: ~~.~ .. ~ c.~/ ~.:::~~~ -:~ :::::?.:{:0· ::.~~:: ·{f{: .. . '.~:.~:._:·_·'.i:.I_:~_=::_:_~~.:.~_}_~~-;~:.-~.~-:~.~.:x_~:~:-~·.;;_:~~-1.~.~-~-' .. ~.: ·.~.:·~·~.:.t_._;_:~:~.:~:._~~-~-~:-~-~-~--'··.·.:~.:.·~--... -~-........,+--=:~"':~~"::::"'~f"'~.?'"':.:-+!~"""~~':""<~"""'--·· • ., ... .,.,,..(.r.;.;.:.;-:.;.;.;.;.;-:-:.;.;o(.;.;-:-:-:!'·:-:-:-:-:-:-:t<-:-:-:-:-:-:-:.:-:..;-:..;..;..;..;..;-:-:-:-:-:-:-:-:-:-:-+:-:-:-::-:..;..;-:..;..;..;..;.;..;..;..;..;.;.;..;l«<««·«<<':«« ...... +W'h""'"""""""¥~~""'"""'"" --~-;_,_.,.-,.-., __ ~--~-.. , ::c«:.::l . i . I .. . i

l :·~:>:. ~~=>"!: . :·~::?~ . '·.=~.·=:~''.· ··''.'·· . . ·: .

• .. <:-. ·.. ;. ~ 1 ~~ l '<'<••••••••••••••••••'!""--·-· ~· 4~.-····~~"'---!"-~~~~----'ww---+---~----<-~-~-t--~~-+-~--'-+=='C""-'"--,--..,.~-,----;.,.---4;

:-.... ·:

-::.:..::: :::-·- :::: .:" ~=·:::.:·;.: -·=:

.. ~~~~· . . ······---:-- :::·.:::=:- .· ~ .... ··:.::=::::-·-·; ~~ ~ ~~ ~"~~""-:"'""""""'"""'""""T,,,,""·· .. ,.., .. ..,"".,;.;:""'~--·:.--:-:--:·· ·•· ;.= .. :::·· =·~:::":.; s-::<:~·: :=-·:::::. :·:·::.:.,:~. fx:::.~ -:::. .,,,.. . ..... ,,,,, ,,.,.,.,,,,,

'·················+----·''Q,;,: ...... j······•::.::::.::...·''~---+~--~-....... ~~........,--~--i-------r-----~+-------+---~+==,_.-.,.,~'C""C":':-~,_.,.---4 :;:- .: :·:::: : r;:>:~>~-- ~,:;:·::-.:::: ~ ~ _:-.~:-;:~~t -·~ . .::.;::{~_;e.*-~;:;: •

~ "'"'#"«"'"""""'"'-.!-!"'"""'"'"'"'"''"""'""·:""'"":; ................ """'"""""'""""· -:-:-:-:-:-:-:-:-:-:-:-:-:-:-:.;.;...~.;... .. N=""'""'"""--=~-"'0=:;:..;;,~0.;.;.:.:...:;:.;:.....:.::.....:.:=="--~--i

.

:::::;~~ ~-.-::::_ .~,,- :• . . . . . . . . . . . :·.. . . . . . . . . . . . . ....

~' ~~~~ ! :;:::~:'H'' '.>:':'\~:;,::·: << l':f""-' ! ~

u ........ -.-.-.-..... -.-........... );-:-:-:-:-:-:~j~}~~;L.:.<""~f·-~-:.1«:}"':~~:...:·::...:.:-cer~+~"""'""""-"'!"'-~-~--'-+----~-~-~-4-~---+-----~,_.=--;"'C'·-=-----~='-'~

:-.::~.

-·-·---·~·~---:-:-:."'~.-. _..,;:::--_· ........... ~-...... -~--~~""""~,.......-~.~"·""""'""'"'1"'"'"'"'"'"'"'""...,;...;---"!"'-----t-----~+-~--¥~---~-"'="""'"'-~--~~--~

IPEC00234066

IPEC00234066

Page 31: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

APPENDIX A PIPING INSPECTION INFORMATION

IPEC00234067

PROGRAM SECTION NO. SEP-UIP-IPEC Revision No. 0 Page 31 of 69

DESCRIPTION

IPEC00234067

Page 32: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

SEGMENT NUMBER INSPECT

LOCATION

APPENDIX A PIPING INSPECTION INFORMATION

PIPE GROUP/ ITEM

LOCATION JUSTIFICATION

RISK RANKING PRI

EXCAVATION NUMBER

DIRECT SOIL?

IN-LINE INSP.#

M••••••••••••••••'"'' ::: ••:•••••J•••••,::•:;;•••,•:•· .•. ·.'"*':.· =-=-r:. ~:Tmm,,: 'mmlmm~mm ;':.~~~., ~:·:}·:·:·::;

;:·::.·::.::·:·

PROGRAM SECTION NO. SEP-UIP-IPEC Revision No. 0 Page 32 of 69

LENGTH OESCfiiPTION

MISCELLANEOUS NOTES

Run of piping in soutrlf.H1y direction to WHUT flit @ EL. 49' (:::p::-:ox).

··:.~-=::~•·~~·-··••::· ..... [ ....... ,... 1., .• :. l ~··l))mmmmm1~'~:~•· 1 ·:~:::::::·:: ·f·· . ~ ~ :

:::~;::~~:~~

:;:::..:::-·-· : :

:::-:: .. :-:::.;: ' . ""t·······················~t"'"'"'""'~·~-~~~-~~--~--+----~~~~~~~=~~,.-.-t

:~ -{:~ .-~ {: :: <~ ~: ::·:?:-~-:: :! -N::~.

""•'•'•'•'•'•'m,·,·.wuluu,_,.,.,,.,,.,.,.,~.,,.,,,,,,,.,.,.,...,'~t "'C:'~""'--..-.wj~""'"""':"'uu-4..,;,~--..,;,-+--"':"'..,;,""""~"""""""""""-+""""""""""""+,;""""""""..,;;,:;;<;;~,;:;;;:;;,;;:;;;;,.,.@;;:;;;%""""""~' -:;::.;:;: ; ... ;::.. .i.: ·:>:"iH''· '~:. :;•:•;,:,';.:::;: :i:,,. 1 :

:;::~~=:::~:-::::~· -:=~­:::;:;.~:-~..:-::·

..... :..,.....:;:=;.:;;_-.;,-_..;;=.;;;.;--.;,. .... ---4------u:;+-'.....-............................................................ «-:-:-:-:-:-:-:-:-:-:-:-:-:-:-:-:-:-:-:-~o:-:-:-:-:-:-:-:-:-:-:-:-:-:-:~· ~+---~--~.;-..,;..--~":':'"~-'--~...,..==r..,..-~.,.,---t · .. · ... ·.:.· .· .·.· .· .. · .. ,.... :· . ~':, ~::L 4 ;:·- -:::· :_ :-: :-:· ~: (~·:·

D;:'>'• ~:: ,' ::.::=·:: .·: :·:.·: :}·:.:·,~:. 'd::~ ·:{::.:·: ;;': :~-~ ~:: ~-:.~· ::~ •'' •'•'' M ...-,: .:.~;:,• ,; '•:·:.:":•>:·:·: ~·:··~·::i::::,: . ' : ~<:=;.~~ -:::: t ~-- .;;:'/' -:::· ~::·:-;:·:.:-:,;,:_:::-

-.·,······························-.:····oc·:~::rt?-.;~-~-- · · · ·r · · · · ·:···-·-· ._.,._._._':':>" • ······-·····-<:···············----... ,,.,.,. ... ~---.-.. -.......... ., ..... .t. .• ,. .... " ••• -.-.-.-.-••• -•••.•

.. ::: :-~:.:~:·· :::;.::::.. ~ . __ , __ : .-: : .·. ' :-:. :·~:·::-, ::·:':::::::: :. :~ :'-~--~\ :~-;,:_;.. :: ~:.:;·;:-. :::~-::·:;: t:=-.:.:>:. ·.:. :.::: =~---.·::·:-:3 ::·: .=::::=·:.:·::-:·::.::;_:: :-~

: .;J r",~J~r:=-_j~~J~:~J.:>',,::J _ t£~:;~~;?;;;:::~i~L

IPEC00234068

IPEC00234068

Page 33: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

APPENDIX A PIPING INSPECTION INFORMATION

··················-:~:":·--··t·················~~-~-~

"~~~~-~~--~~.:~.: .. !

I PEC00234069

PROGRAM SECTION NO. SEP~UIP-IPEC Revision No. 0 Page 33 of 69

DESCRIPTION

MISCELLANEOUS NOTES

IPEC00234069

Page 34: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

APPENDIX A

PROGRAM SECTION NO. SEPwUJP-IPEC Revision No. 0 Page 34 of 69

PIPING INSPECTION INFORMATI'!!i!O~N~~,.......------------LENGTH DESCRIP110N

MISCELLANEOUS NOTES FUNDING SOURCE

~~~~~·.W.'.'.'.'.',W~-.-w•»~w•••""'""'''''''''"~¥~•~~~~~~~~~=~~==~ :· =-·: :-:-::: .:::·::::·r <>::-::::·~:::_:·.·.· =~=·=:::: =:::· ?-.~~-=-~! :·: : .. ::::::. .·, ·'·.· .:~ :: ::::·: :·:::::::: ;~:- i:<: :'::··::~::::: ~:.:::.t: =·::.:-: :.:::_: .. :::::::. :· ··:·f::: :::.:E .. ::.:;-'.·f:"' . -:~·:::::·· .. ::::.:;:.-:-:·:·<. ::;·. :-::.:·-:.:-:;·. -:::: :::L ::·.: .-:;.·

----~':,_,':,: ... y ••• ··'l ...... :'. ~-:' .'''. =~: .... ~ .. ···'1· ................. ·l· ............ ':'."?''::·::·;::: =~~'?''':·? ;:t:·:'. :·:~·:':':'::·:·::: ........... . f:-<::::::;..::: ~-=·~:: .:::::··: :::: :--:---~~ :·:.-:::-:- :·:-:·::;.;~-:=<;: ~-:·:: (:·::·:{ :;:_. =·~ .:~.::-;·:-:~:::·::::- :-:

... "':' . ,.. -+..,.,.,.;.";.;.;.'·';;;.;./':.;.,.' ~~~~~~~~.

·.·.·.·:.;~::~:::~,:-~:~:::.·.l __ .. ,r,: ... :j;~~J~; .. ~J,····'~ ;·;':',, .. \!J.;~;:;;: :;:;:::.::-::::;: ::~:~~::~:-.~=--. !)::::::~::<:: ::· -~- : ~~~F-?.\f? ~:~:?~-f·~~~: -~-~{> :;~:;::::~·:}·

·:::::·::~:·::::. <:::~:::· :;::~: m.:::-:::: : -:= <:::~:.:.::. : · -~~-~~::~.:. .. "' .. "' . ..._~..._;;.,;;.::::;,;. .... >:.;,;. . ..._4--,~:: ~:. ~~,~=~"';~"'= J~, .:...--+·,l-"""' = ~=~::--· .. ----~_,l,. """"~~~~~"""f"'t~~:cr7 · · · ·

: =: ... l ...... ;%j~~~~J..:t~..:..:;.;;.:t~:~;:5L.:~2~t:~;~;:::~J;:ii~5;,: .. ~::2.·:~·~:-.:i .• :~.'.· ••• ......... ·.t-=· ~.:· .. "',.": ~-·······+-···············::::-···:"'"'···--·-·T"""'..,"""~"-·:_:-'::/ ... ""'-+----"',-:::.:.'-':.:~---.;.....--'<":--:"':·::--,_ -----+-~\,.::· .. :--::-~---.;.,'7~.;,.:·.~~, ~---<--.~-::·.:.":.~~. - T ...

:: .::;:: .. ·:· :

. . . . . . . . . . . . . . . . . . . . . . . . -. \::ii: ;:: :. . . . -·- .... ·.:_::::: ~:::::.. . ... :>• •• :; :~:l::~6: ·::~~;~:

::=:·=·· .. ::..

<=::::: -::: ...

-..... -... ; .. : .... ~ ... ::.·· .. . .. :.:·:.:::·:··:

IPEC00234070

IPEC00234070

Page 35: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

IPEC00234071

APPENDIX A

PROGRAM SECTION NO. SEP-UIP-IPEC Revision No. 0 Page 35 of 69

PIPING INSPECTION INFORMATION

DESCRIPTION ,~~=-+--=~-----------------------11

MISCELI.ANEOUS NOTES

IPEC00234071

Page 36: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

APPENDIX A PIPING INSPECTION INFORMATION

IPEC00234072

PROGRAM SECTION NO. SEP-UIP-IPEC Revision No" 0 Page 36 of 69

OESCRIPT10N

IPEC00234072

Page 37: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

APPENDIX A PIPING INSPECTION INFORMATION

PROGRAM SECTION NO. SEP·UIP-lPEC Revision No. 0 Page 37 of 69

SEGMENT PIPE GROUP I RISK RANKING DIRECT I ELEVATI LENGTH DESCRIPTION

r··-;•;i;';;~:';.;;c--f--:i~:;';;~i;:~;';;~i;:~O:i~:-t--.L0;:6<~~A11~MC-;O:;:;N;--+~E""Xv.C::'A;.PV7;~ii;ITI'-O"'N"t--l~~¥rlr£---l .. s~gff{JS;t.L""E+""F"'U"'N"'D"'Ir"'~G~+---------------I LOCATION JUSTIFICATION NUMBER INSP. Jt I (Q/YYVY SOUBCE MISCELLANEOUS NOTES

: ....... r~·~ ... r---.,.,~:··.:·:······::~·:·;.:~"i ... 4 ... ,=-r··· . ·; ... ;,.......... .. .......... .,....,....,;.,;"""" .......... ~I{~.·~;?.?:?""""" .................. ~ .................... ,..,....,.. ..... ~ ..

_j:·;,::·i·;~~\·=·-F:~r?~:i~::~;:.:"t==~~2~_.·'!,· _;;;~"'~"'· __ ,i"""'~:_:;~-~'·:_:,_=· -_~=:_·_·· ... !_·. · __ ··;.,.:~:_.:_· --<--'-----!---~~~-'*"'--""""""*" .. :.•: -:::·::..: ..• ·:-:::

·::.: ';.:-: ;: : :.:... .:· ~:·::::-:-~: -~ ::-·;.:-:::~:~.:

~~~~~~~~~~~~~~~-i

IPEC00234073

IPEC00234073

Page 38: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

~- : ::~:~.::::-:-.-::~.=::~-~ ~ . I r----····-:---·-·=---~--T·--···--·--"'""" ":""-:-:

:;:·:<:::;:::~ : l :=:::::::=·=·f ,:,,:~:i·n==·· [ %:=:. 1 : ··:•;:·: :-:·: . .:'. -~; ;. :.

~•••• · · · ........... ··~--~~:;~;;~;~~~:~~::~•T HNNN~~ . ·.· : :

APPENDIX A PIPING INSPECTION INFORMATION

PROGRAM SECTION NO. SEP~UIP-lPEC Revision No. 0 Page 38 of 69

DESCRIPTlON

MISCELLANEOUS NOTES

t.· "":~T~:~::;.;.~·:~,~~;:~~··;I;.~;~;-·:~:t;;;·;:~.:::::: ~~:·= .. : -:::~8~:~ ... :::: ... ::: (/ :·:': ·: ''···'":'::·: :;::';:::;:;·M·:: ";.,';;::Lf:.:~t:-mm

w.•.•.•.•.•.•.•.•.•.•.•.•.•.•.•.•-'.-~·"""""'·'·'·'·•••.~•.•.••••••••••••••••·""''""~~~~--~--r------.......... ~-

=~-·'2.~~£,j_,fi~, •1• .. ~ r ?;:~i J ::~·-:,:~; ~~~~ :,~~~;~~:~§1~~~,:~;. : . '~:~;~;,:,;;·· , .. ,.,;,, . . l . '>'x . l . .. . . .. r . l t-1::~, '''·'<\ I:. f<m;>:,:=:~W::::,::. :::;,.,,_,,~,:.;<~:=:"=<·'''''''' : ::~::~;:;~;, .· .·.· • ! <w ·-~~" --L .. :' ,_ L ; •• =' l <·.···.. l

:-:.... ~ :.:·$~··.:. . . . . ~:~.: .. ~~ ~:: :.. -, : -::: : :::-:~ ~~- .... r.·-:-:-:rr~~~~~:-:·r;t~:~~0:·:· ::.::·:;':. : :::-::::; :::.: ?:·:.;: :::.::::::::.::-. . ·:::·:i·-·. . ~ :·:·:·::·:·: :.::-:::; .. •::}:; ...................... ;. ... ,;~:;;·r:·····~·················· -~~-~+-~--~...;.;.;_;~"---·

·::.-:: .. ;: ·:· :.····:=. ~-:=··:~. ::·~.: :-:--. ?-~:.:.... ,. ;.~ ... ~: ~-,:·::~ ::-;.:;~. -:~:-;.;.(:~=· :.:·: ::::.:i. :';{::~:.:·::-:·: :::!::!:J.:·: ::::·:.:-::.

·"""-~--~---~""·""'"""""'"'''''''•L""'"""""~---"'----~-----~

IPEC00234074

IPEC00234074

Page 39: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

:~:=~::·;:-.. ~:-.· ~::::::~~:~:~

APPENDIX A PIPING INSPECTION INFORMATION

DIRECT ELEVATION ---~!~? ______ ... JI?..~~I.I:!L

IN-LINE SCHEDULE QNY

:~::;;,;::-::..-:::. ·>-·-:-:. ~:<::A.

".'.'.'.'.'.' ......... ·.·-·u.t ......... :_~:~:::: .. ·.:-:,L ...... l ............... _ ....... "'""'"'L"'"'""'"'"'"'"'"'"'"'"'"·""'"'"'"'"t"'"'"'"'"'"'"·"'"""'"'-"'-"'""""-t><~"'"'j"'-"'"'""'~~.._.._..,.._.._.._.._.._.._""'"'~l----"""-""'-"'"'"' . ::.:::·:}.:.: -:-:r:. . :>::.::.. -:: ... : :·· l :-.::·~·... ~ -.:..: ?=·;::-:·r: -~ :·::-.>:-~ ~ -~·r:·::: :::. :-:. ~>

PROGRAM SECTION NO. SEP-UIP~IPEC Revision No. 0 Page 39 of 69

LENGTH DESCRIPTION

'·'·'·'·'·'·'·'·'·'·'·'·'·'·'·~~~- .......... "t'-'·'·' .::.

;-:,::\ 1: ,;; ,.,.,,_,~ ,,,., :·.···'''·' ,::,:,:=: .• :':" ,:: ,,.,,,,.,·.

~ .it;~;l;;~<mim"';;:"i:~; ~rwum------------4 ·:. , ''"' ·····p,.,;,;,'::~·;:;.;;:;;-·~···;.:;:.;;.:,:;;·,;·,:,:"rmu~:;:,:mmTm";;~;~;;.;:;,-~;mmrmm~:,;;.::;;:mmmtumu;;.;;.;'' ···«········· ... ···T~--~~:;;~;~? ... r-~--

~ ==-~=·~::, ·~- :;:::~:::; .. ,,:; l ..

::;:~:;:::::;~

::S.-~W-':Z~~-;- } B .. :::·<:·· "! . ;.;.; ..:-.:-:·=: .•. ::-: . :--~ .... \ . ·~·:: ·~::::~·t: ,; . ~:::.;·~:··=· . ·~·:~::~. ~ ::': .. :

............ ·.·.·.·.·.·.·.·············~······ ... ·~~~~:·::~·:·::·~······~··················•·:·~'?'~~-: ...... ~-: ........................ : ...................................................... ~ .................................................. :-...................................... t .............. ot ........ ot ... ..

. ··::::~;~::~::::: . ~ : ~ : ~ :;: ''<'·'' ~ ,.,,.,.:. i ,, . .,.; ~ :'i.'.'· i i,:;.o l t·:':':

·w··:·.:·,:,:,:::;:····-1 ,,,.{:,,,,t_:,,,.,,;~·r-;:;;;::;;:::;:, ~;,~, <:.: l'l''" :i N:M: ·~m:: ·~~,~~~~:i-~0.~~~~~~~~~~~~~~,~~--~~----~~~~-+----~+---~~~~~~~~~

~:·:~:::::::;;: :;:~:·:=:. . ~-~.=~~- . ~~ ~~:::.::; . ~:~::~~ .. ,• .. · .. _::::. ::: .; ............... ~-~o{o!:o{o{o{«-{o{00:o{o{1"""""""~""""""""""""""""""""f""""""""""""~""""""""""-:-:1-:-:-:-:-:-:-:-:-:-:-:-:-:-:-:-:-:-:-: ~·-:-:-:-:~~:~~ .. ;~~:;.·

: : >:.<:·:-.: ·:= ···: •. j : ··: ..... ~ A/ >:>H:)~ ·* j ::-~:(:::::: ~ ·r!:.::: ~ : ~:. :·~ :·:.: •.•.•.•.•.•.•.• . ..:·.-~·.-..... ~·.-.•.•.•.

:::: ···:.

:..•.••, .·-:• .. ·:

IPEC00234075

IPEC00234075

Page 40: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

_·_·_-.:~;.:}, mr ·=:·

=:·>:-.:.:::.· ..

APPENDIX A

PROGRAM SECTION NO. SEP-UIP-IPEC Revision No. 0 Page 40 of 69

PIPING INSPECTION INFORMAT~IOi-:!N~~'I""""""""-.,.---------""""'11

,il.ii'~i'§ ~

LENGTH

FUNDING SOURCE

DESCRIPTiON

MISCELLANEOUS NOTES

N·::···:·:·:·:···:·······;--"T' .. :':':·:;:-···'-'·'·+·-·-·-·-·-·-·-·-·-·-·-·-·-·-·-·-·- •""-'~~------+----+~~,__~ .... ".l.."'"'"'""~ ........ ------"-==""--------t :·:-:>•>:-:.: •. :··· .. ' : . : ~~ ... ~.. :·{.'.::. ~-;;,.::.. ~-;_:f.. ~ -::.:.:·:~ :: ::•::'-"· ••••••·• ~ .............. -•.•.• -•.• , •.•. ·.····""""·;.......----;-------~~ .... ,. .... ,..,., ... :.:-·-:-:-:..;..;..;..;.T,,_ ........ .,.._.,.._.._ ~- :: ~ .. -: .................................................. ._ • ._.._._

., ... , __ \'''" L:;·~~::;'''·'';::= --~ ,.,;:,, i .>\ i "'"t: ~-- ,...L.""::~.~:~.,.,--""'""',';.......""'., .. ~=· .... ::~----*i """'"",:~-!>,.. ... -=_~: _=::~ .. - -t,; _,·, __ -~·----. _, -~-o(-.t:_.,;!'·J;~;- :::::;;:~~;:::::·: ::;::::~~::~==:~=::::;. ~.:::::: .;:::.=~~:-=· ::;::;:;=:; . ••• ~ •• .., .•• •••••• •••••· • :: ~ ~l': f:;.. ... ::;::.<r .• _l'',:,· •. -.. ; •. ·._. ''·· 1. .:,'_::; __ .,::_.,t.·:.~~~, •. ~.:··_:_._:_),::_:_:_:_~~~-~.:_.:t_'.:_.'.::.:,~_.~: .. '_~.:;-,:~-~-·--:~.:~.'.:_.~.'.·~--~: .. ·.~_-:f_:.'_.~:_,~.::_~~--;:_:;_,~.~.:.>,1:_:.~~-::=~--;·_·.~~-:-~_::

'~tD;'; . f.: :tn;:;:;:;::.:.K (:~;'{, J,_·.. N:';\ r . _,'_·,-.~,,_·_,"_'_-,· ___ , 1,':. '"·~ •m~~·~;;;<::~;~;;·""""+""'""l';,';'' .. '' _,;;:.: ~~~--:--~=-:-c:-"""""''"'''"'''" :.:.: <"::'·;..::·: .. :;;; , j':, ·U .. · .. ·'.::_.: ·._',::,.: ~:·:- l,:~ ~':. :.~{_._' .'.:_.-_-·~.·:;·.-:: .. •. : .. :::.::·-:_·:·'.·::::.::~:::. :;:{: :~·:::.::·: ::::::(::.:-::·:·: :;::::.:·:·:~:::.;:

.. =···-·· -·~··"· ~~- .· ::):::c-~:-: -:- ·;;·::::·~ :::. f~ ;:·:.::~:: ::···-:>::x:- :::.. :·:~:.:::-:-:·: ::=:-::x::::: ::::::.:~ :_:: .• :: :.:...· . . . (;; ~-=· :': :=::; : .;:_::.:·:-:::::.-:-:·:-:: :{:;:~ :':-:.:=·:-: ;.;.;;::;::

·o;·····:=::=:::··:···::·:-·········-·+--- ·:.::;:·.:--: .::~--..-..···t, ···················-·.···········~........................ ~ "T.· ~', ~~~~1:,~""t,""'"'"'"'"'"'-------:•;;:·:-:~ k":~ : :.•;•/•. :••;;:/•, •"'{o'N, p,); :::..:-?.-:::.:.

:;:.·:.:.::\:'-(:::- .;:_ ... . •:

............ ,.,•,•,•,•,•,•,•,-.•,•,•;,~-. .-. ..... ] ..................... _..;,.__._. __ """'----~~--~-... ~-

IPEC00234076

IPEC00234076

Page 41: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

PROGRAM SECTION NO. SEP-UIP-IPEC Revision No. 0 Page 41 of 69

APPENDIX A PIPING INSPECTION INFORMATION

SEGMENT PIPE GROUP I RISK RANKING DIRECT NUMBER ITEM PAl SOIL?

J-·""~·~;;,~y.~~T,;:i;i;:··+···;,;i;:i-;ii'";<:;;····j-··j"-'N~S;:;PE:;;C::;T::-+---:L-:O="c'-'A;:,:T:;,IO"'N""' -+--,E"'X"'c"'A""'V"iA!:TI"'O:;-Nrll-7-iiN:;.:·;.:;LI;;cN;;,;E-~~;:;; LOCATION JUSTIFiCATION NUMBER INSP.#

DESCRIPTION

MISCELLANEOUS NOTES

}':, ~---------------------r---------~~~---- - \vra .• , OD strffeners@ 6'-6'' cente;~ +---+----~·----+---~t~"""~·T""""'""

'· .-: ... :.:·, ~-~ .. ~~. :-{.=.::.. ~·;,:,::. ~.;:.•:::. ' • ~· .~. • ~ :· ·~_;';;_··:·~;;_;:: .. ·;;_··=·,... . ......,""'('".-.•,•,-.•,•,•,•,•,•,•,•,•,•,•,•,""J------~----~"'*'!, ~--"<"<W-~<»<~"<«< ~<~---<l--~---1}-"""'----:iC"""-· ...,·-~~--""':~~: .-....-..-.•.•.o.o.•.•.•.•.•.•.•.•.•.•.•·"'""'"'"'"'"'""'"":"C"""':'""'-i

~ ~ ::~::: ~:;:~·~::::· {~::::-::~~~~:::.~~ -~>~:~:~:~:?,: ::::i~:::::-. ~=:,.~:~::::~~: ! : 1':.: ~~ .. :~_:;- Y-:t ·:~:~:>:::::~:::~~ ~;:~ ::-:;.;.:::::::~:;:::::::;:~::· :1:::::.::::::;:.:::~::.:.::~~:-=~::.::

.;: .: {:~::; l: :•:«··:;.:,c,--:,:'.'~:·<:l::;,: ::~~::~:::~.·:~:~::~,::::. *«::!t A_:: ::t'":'·:t~f: ~:; ~- ~ K:··:~~·:.;:t ::q::~:~~{}".i:·::::~:~~~ ~~:~::} {c~.~~: ~~::.<:~::~:::··~~~::"·::::::::~:":':-:::·::

:- -~:: -';ol;«•:•:•,•:•.o;o;o;o;o:--:-•:•««L~w:~-~-~-":"'h-"""-~~"""~-----+-"""---.,...r""':'":"""""""-+":"""-~~+-,.,...;<•"<•.<<':"'!<«<«;<• ___ """';,;;;;;;;;;;;;.;;:;.,="""--"'~ ....... :'::,;:,~:::-i: .•....•. J .... :~1~r;;;;~l .. " .. i ..... :::.:: .. ::::::::·:::.:: .. .,! .. -. .. «;::~:«««« ________ ";;_~::~:------+------+----'---'-i-----';...,"""'--'-,.,...;,.--'-4~~~t'7~~~~··~"~·-::':~":':':'~~~"J:':""i

(:; .. ;;~ ~:.:·

·::::.:: :{:

....... ~ .. ~---:~· ..... ·.·-+·······:·:···· .. ·. ·~·. :.::.:. :·~:·:';· .. ~:·:-::. =··::..:: =·~.=.=·: ·.o;.o;.o;·~r. ~~~~~~;::~~ol;ol;~~~~~~ .;.· .. : ... ::..;: : .. :..::.:: .. .:.> :

w.•.•.•.•.•.•.•.·.······•···":'~--~-----·~----· ~ .. ·mT•··············~4---~~-~-,_,--+-----...,;..----+--=--~":':";.;.7';';""+---"""""""''""·"""'""""''"""""".w'""'"'"C"""-C"""":"',.....j

., , :::.:, , I ''·~~,~~it~~;;:;;;;;::;::;t:::i:::·::r:~:~:;::~:::;~:'P!fft'; ::····· ~ 1.~ -~~ .... ~....-.-:-:.-:-:~-:-:-:.!'-:-:.-:-:-:-:-:-:-:-:-:-:-:-:-:-::-::<-:·:-:+-:~~ ... ~--f<-'*".,;;;;;.;~~~-C"""-4~~~;,;;;;;;,;...,~=~==,«:;;.<:.-..i='---"'<t

.. ttt& .... -!'-"""'=;,;;;....""""li-". ~· 8:::~.. . ~ :~ ... ~;:;~ ~

··;.:··

.. ···:;.:·:· :::

:-:::: ::::::·: ..................... ~ ...................... ; ..................... .;. ..................................... l. .......................... __ ......,; _____ ........;:-----~-----+----~-----·.:...::·::.:;;.;:(:.:;:::;' ..... ·.;'""'-':·;::'·<·~~~ •••••••••••••••••.•.••.•.•.• ·,.,

:.::.:_:;·: . ·::::: .. :: . . ·:··, · .. -:·::· :·: '. t :··~.:.:·. l :·~.:,::. ··-:-·-·... ~~~:~- ~-~;·;:, ~·::.:~

'w.w.·.····''·'""""~----'l'<~------..;.....-~•~•-• ''"c"""'t"'"c'<"'«<<<l<~;::;t,:;~;}:<;:<·~<'"'"WWW

?: ~~ ·:;:;::,:,::7""""i~=~"""""~.,_.,.~+~~~+--~,....,.~~~~.,......,.."""""'~"""""'~~~,.,...;,......w..~~"""""""""'"+--~·,;;';"~''''~:;,<,,~~::w:;,.:;;,;;;;;,~~~

~<W l ··· ··.: · =··:. : .. ::: .·.:-· :J. ,:.. ,.. ~.:·i r-:~: .: :-:::·::.:·i ·;::::; ·::.:· ·:::··· : :: :: ·:

v.,,,,,,,,,,,,,.,w~,--·;._w,w,,v,,,,,,,,,,,,,,,,,,,"""'i----........ ---'""""'--+--"""'--+-...,.,.,....-.;....'~-:..:_;''.,..· ;_:.:;,..-{:_<<_:· '"*'-""'--""·~-·;-:;.:::_:·::-;:·::_''··~'::: :::,~:~::;i:~~~~~;:;<· ;;;;,.'~;,.:_.,~·/u•,:_· _. ·~"-' --{

-.-.. :·::·:::::: ........ -~.-. ...,,-.""t,[l~.;.~ .......... ..:..-.-..::;: .... :.:~::.;:;.;.;,.;.;..,· ""'-"""'·=·~o;.:·:=.w. ~""""~-u::;.-"'::::o;.~~._~w:,.~--"''"-''-~.....,.;.---e:-~._:i:;,., _.;....._...;.;·;;;.~:.,_~'-""""-....;,;~~c.;:·::.,;.· _ _... _______ _

IPEC00234077

IPEC00234077

Page 42: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

APPENDIX A PIPING INSPECTION INFORMATION

SEGMENT PIPE GROUP I RISK RANKING DIRECT i ELEVATION

~-~::::~·ii'c:,~,---c--":::=;~,::c=-+··-,,;,c;,:;:,",·-+·-:~~~{}-- ···a:o~*ofl ____ ··-E"xc~v~l~ioN·--- ·-i~lN~ ! s~:;~~lE LOCA'nON JUSTIFICATION NUMBER INSP.# (QIYYYY)

:::_,· .... -.·-: .. '· ::.·::-:. -::::-·-· :·-.::: :·.: :=· .• =: ::.: :=-~=:A =~~ · ::~·i::-:.:r

PROGRAM SECTION NO. SEP-UIP-IPEC Revision No. 0 Page 42 of 69

LENGTH

FUNDING SOURCE

DESCRIPTION

MISCELLANEOUS NOTES

--~- •• :.·:;-.········) ... ~-:n::.:~:~···· .. <····:.::·:.:········ .. ·r~·:.?•'·,~·~"*"'""' . ;;~,; ........ r·· . ~ .. ·<·""·""··········w.·.· ... ·~--r-~-r--r.,...,...,.,...~~~.,...,...,.,...-r-M'f:'{:::i'~l'':;~n~.~:r-::';~~~;;::::::::r::;4

: ~-~- {;:(-;'$~ -:.:::::-:.::·::;:.:·:?== ;:-::::::: :-:~ ~: :_:-:;:• .• ;:{:;·::.:: :::::::: :::.: l ~:>.:.:-::::::::.:·::-: -::·: :}!:: •.•;::::·::·: -:::<:. ::::.:_:~::;:; .. :: ·:::-::::·:;~::: =:-:·::_:.

::-::. (:.:- :: ::: -:- ,: l :_:;.;~ ;~.;:: :.::·;.::;: ?.;:;:·· .;:-:·.:·:.':·:,::~. ;~:::t·-::::::~:.::::. ~::::~:- .. :·:.:~::·::

: : ·+---+-------+-----+----+-----~--4--· ...... ··.··.··.·· .. ·:~,-~:.:•.:• .. ·.•'.''·''.'.''-'' .. •·-··.·.•'.''.'.''.' .. '.''.· .. >.::.:.·.· ........... ··.'.''-'-':.•'.''.''.·'.'.'·-·-·-··-·-·· ·······;:······:·······:~············-~.-..... :~:::.::· : ."f~·-•.•.•.• . ...;.•.•.•.•.·.····························... ~ ~~ • • ... ;::.:.:::.

IPEC00234078

IPEC00234078

Page 43: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

SEGMENT NUMBER INSPECT

l.OCATION

APPENDIX A PIPING INSPECTION INFORMATION

PIPE GROUP/ ITEM

LOCATION JUSTIFICATION

PROGRAM SECTION NO. SEP-UIP·IPEC Revision No. 0 Page 43 of 69

DESCRIPTION

................ J ;,o;, .. ::--·~.-.¥··············--·--i----~-----+-----~--~---.......... --~----.;...;;;~.;;.:._.---4 ··: ·.,:;·:<· : .. ::: ~·:.:::~ ~·:.:/, ~~~·.·~. ::·~:·::! :-~:J-:, :·,, •. , ::::

•,•,•,;,;,;~;,;,;;.,.,•.•~~; ~~::.0.....·0m:'•''•'•mw.··~+~~~........;r--~~~~.......;;~~~~~+~~~+~~~~~~~""""~~=~~~""7'~~~~~~--j

;:~:::;:~-:i:~~<~~ ~::::~~. {.. :: ~::~~:E:~ ~:

·--+~~K~""'~:<"=".;:·"". ~-.--.• ..,..,,.,,..,"'"'"'""'"'"'"'"+-'""'""'WW«""'~"'·· ~~~+~~+~~d........,.,..."""'d.,.......,..z:.t~~%2'\~!.:::::ti~L~ ~~> :~-~:;:~~_:;~~.. ~/r-L. ~ ;X;:;t.:. ;:

.. tmm ... ~·""· ~~'"""';"".~'"':,''..,"~+-· , ' ::-;f.;\ :::.' f::i~-:~::

...... ·.·-·-······:···:··········-· ... .;,~ ......... .J. .... -.-.-. ·.......J--1--: .·-::-.--4------·--l.'~-·········---··------------~.l. -------l,~ ........ ~}~.:~: .. :~~:. ;:J.:-=~-=·-~.,-=-=-=-=-=-=-=-=-=-=.,-=-=-=-=-=.,-+.,.,-=.,~~~~~L~~~-=~~~~~~~~~~~.,~~~!~~~:~~~~;~_:::~t~~~~~t-.~~;~~~~""""

....... (.:::.~L: .... -.-.- :.:::·-::.:.:::: :::: -::-:::=:. ···:·y. . ~~""h"T··················T~~r~-~~---r~-r:::---::.:~--T"?T~:;;;s;:;;;;:7;;;;:;;-:;:;;;;::;s-1

IPEC00234079

IPEC00234079

Page 44: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

SEGMENT NUMBER INSPECT

!.OCATION

APPENDIX A PIPING INSPECTION INFORMATION

PIPE GROUP/ ITEM

LOCATION ,JIJSTIFICATION

RISK RANKiNG (PRI

EXCAVATION NUMBER

PROGRAM SECTION NO. SEP-UIP-IPEC Revision No. 0 Page 44 of 69

DESCRIPTION

MISCELLANEOUS NOTES

,,,:,;;'; b0L~ ~-.ll-l_-_-,:.':,.~-.~~·.-.~-~-~+"'l-.~.-,--. -. -,.-< ... -.,--.-.4---,-,.,.-,.---+--,-.,,.-.,,---+~~~:;;~=:.' : ' ~ ~ 1,':,: .:~::: .. t::~-?~::::· -:~;:::-:;~~:::,:~:.--=~ ~>~:::.:-:~;: :::.~~·:::~: ~=:{;,-::::<·: l· ::;~:: -::>~::::::: ·S:> ~ tt (;: ~ ··.·::~· :~::~:::·::~:;:,::~) ::::~-:;:<:::·:::~:~:::.::~:::::· :5;:;;.~:. :--...::5:~::::~::::::-:

=> ::· <::;::~· •• ··'r .. ·': -::. ;=~=:.::::,~; .. ::::~:.(::: ,~.· ~:::.=:.:~. ::> ;: ::·=·:f::::. ~=: .t·~~~~:~~ ·::·:::.::-:: K=<:r·.:::::- ::::>) :::. ::::::=>=~~:::::{ :;:~~=-=~:r~~·.:::::::::: <~:.;::. :.:-~=: <==::~~= :~::~{-:::~:~~=·=·=-::::::. : :;~:~~q~~ ~H~3 $:~~::~~;:::;:>:~ ~~:~;~.;~:~:::~~::~-:~~~~~~~:-: (}~:: :~:~;f:::;::::~:::;: :~:;· ~: ~ ·

-~«-t-«-:'9W".W.::,,-« .. ''!::':C<-i''· .. <l>\:f;:l.:;:l.:.

+~,~-=~;x"·~~WNN~<•·~+~--~+~~~~---t~~"-----t-~--+--"---...;...;,..-~.....;..+-""""'::::7"~~~:t"" · .. ·,· ... ::;::.

:: : .

.... m~-.. :·::·~rm~·~::::::=:::·:::::···· , ;.,,,l J: ,,,.,, ~ ,.,,,,.

1

. :·<'·" 'T"'~"'--1:.-..... ':~·':';.:'' ........ 1

..... :';':'·:;.,:,~::~L?~;;;;.c;,i;z:i;;:~~,~L~:::,:::,~ , ..... : ... '~~~:~ ...... L~~~-~:~~~:~~:J ... :::~~:.=:~_=:~~~: .. J .. , .. ,~~-~'""'" "''"'::,~-~:::~,: ....... L~~:::~~~~ .. ---~ . -~ _,·t~ I ll~.~~;;::~·,~, l .. :_:ld>HJ.. ... wt'~'"~;=;:;;p,=;;;j~J,:;~;~;~=::;~,,;t~~''';'' , ,, •

>.:·.:: ~= :. ~i~~~-;.;; .. :'; .. : ... : ··: .. & 1 ... : t>;~. l k~. '!·. """·-" i :,<.:~ .. t. __ , .. ,;1 ,,~;::,,.;""'l,.,--.. ~,i, : M::::;:::~:t,;;:;:~;~;~;;,t=::::;,;~~;;:.:•:::::~<;; :i:-:,. ·::. • . • . .·, • .. ;::: -:.. ::~ .. --~~- } •. . · ~:·: ::~·::: .•: . :-·= i{~:-: { ): . :- . :: ~1 ::· :;·:-::·::} -:::. -..-:~:·~:.;:.::.: :.i ::·:·:.; ::.:~·- ::.:;::t·· ... :>:·:.;:·:.::· • • .

: . : . :: =~::.::- ;, ••. ~=·· "-'••'•'•'••••.._. ......... ,:-..-.~'-'•'•W•'•'•'•'•'•'•'•'•'•'•'•'•'•'•'•'•'•'•·~~':':':""'-..;.-~~----i-~~~-~--+-'7'"7'-l--"":""":'-~-:-----~0:J:.;;,:.-.;.,.,.,.,.,.,.,.,",·""·"

:.~:;::;;• :: .~:. ! !·;,.'.:: :·:_:;·;-:;_, ;:~;_::, ~~_:,;:: ;·.;.:;=:_ :··::·,•:. }•.:: ;:•:•;.:·:····:,; •:·:);;.· ••• ;•:.:~~!.;{;-;. ;~-:.;:: ::·;.;·::;;.;(•:·:·: V• :·:·;.;:

..... ,:::::L ...... ..,.. ,,.,,,,.,,,.,, .... j................... ;''.; '""-""''1'""""''-"~-"~""~~~-~rr~: .. -~~"'""'~""""''i~"""~""""'r--"'T::ftitit:i:);:E:T:;t:;#:::«:'--"'1 ., .:' :}::::(; : l ~.:;::;;:; ->'=4~ 'X:'i~

(

I PEC00234080

IPEC00234080

Page 45: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

IPEC00234081

APPENDIX A

PROGRAM SECTION NO. SEP-UIP-IPEC Revision No. 0 Page 45 of 69

PIPING INSPECTION INFORMATIO'!!!!N~!'!"!"!"""""""""""'~""""""""""""--"""""""""""'--LENGTH

FUNDING SOURCE

DESCRIF1TION

MISCELLANEOUS NOTES

IPEC00234081

Page 46: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

APPENDIX A PIPING INSPECTION INFORMATION

PROGRAM SECTION NO. SEP-UIP-IPEC Fievision No. 0 Page 46 of 69

PIPE GROUP I RISK RANKING DIRECT ELEVATION LENGTH DESCRIPTION ITEM P!!I.L.._

.-~~~"~~t-~~~~-t-~~,~~;--t-~~~~t--.L'O~C~A~T~IO~N~-t~E~X~C~AVATION S01]:1____ __ __ {Q~f:!!:l)_ ------------------- -------------------~---~----~----~-------------~-------1! IN-LINE SCHEDULE FUNDING MISCELLANEOUS NOTES

JUSTIFICATION NUMBER INSP.# (QIYYYY) SOURCE

"~··::;::· : "''··''''' ., .. ,,.:,:.; ~,,.,.,. "' . ~>::•;:; ' ~-+,, ·=:~~:~~~~::::::t·.'· ::::::;~~::::~:r,,~~:::,~~:;=:~tl :::::~.::.~::· ::~~i:{·f·

::::::::~~::;?, :~=~~;;-~ .f·. ;.:_,_;~.. ~~;:~~ :·;·:=-~ -, :x,;;, : ~ {U~· ~ ~=:f., ~-~· (~

~';:·:.:.:··< . . ' ! ~ l .................... ·,·,···············-.v--···~·················.,..·.················ ... ·.·,·,•..r,;JJ..;;.I,.oi.J.J.•.;;.;;.;;.:.-.-.-. ........................... ~--.-.-.-.-..:.;;,;..J;.t,.t,.J;J.J;.t,JJ..:;,;,; ......... ,. .... +'" ....................... ,; ........... .N;N;~----~~~"""::C"""~""""--""?'--:"':""'":""':~---,C"""--,=---:--=--,1' ........ ~- . . . • f~. :: :·.{;'• :-:~:::.::·: (:.::.5'"::::::::::::-: ~ .. :::..;;: ::::<:·: :::::.::.:::·.::;:· ;..- :·· .•.. : . ·-:::::-.:.:;_::.::.: ~. :~.:: .. '!; .~ •.. :::~:-::··:;-:.:; ~. :;~·:.!·::.::;:._:~~:: {-~: ... ·.·.····' .. ·. -=~:::~:· ~···"~·· ..

· -+----~----+-----~---+--.......:.:.,-"'---j---~-~·w····-':.:c':c':L~.';:;:::,:,: . .'.o~';.'~, ................. -·-·-······-.:... :;;:~:::::·~:· ............ +-··· --,

::~.;::.: · .. · .~~~~,~-*~~~~~~~~----~

~ "'':,·:·,:::::;;;····A~· ~-::~,;~::'~:·::·1·~w·••·••••·~~;w...,~,,~,,ii~\· ~. ~

: ...... ··~· ... ·.;. '•

::-.::-:::;:::::::::·:

-.·.:.-............... : ... :.:-:-:-:-:-:-:.L, .......... ~~~~~t;L.: ........ L.-:-:-:-:-..... -: .. .;..: .... . : :~: .. :::·; .. :;,:. . ·~+--"""-~----"""""""'~"""'"""""""""""""+-"""""""""""~~~~":0'""""'-"""""""""""'~-""""""'"""""'"""""""'--"""'--""'4 ·:·.; .. :·· ?·:;:;~ .. ~:. c-·w~: ·~ ?,;~::<:.:~::?,·: ··:·:::::;- :::.;:: :::·-:~· _.:-. :: :;:. ::-.:·:·: .. · ·.::·:::: 3:::::::.:

'::·:·::.:.:-::: ,w........,._•,•,•,•,•,•,•,•,•,•,•,•,•,•,•,•,·-+-----,;.....-----~· '"'"'"""'"'"'"'"'"'"'"'"'"'"'"'"'"""'*"."'"""'"'"'"'"'"'"'"'"""'"'"'"'"'"'..(....., ~w·~....:.:..:...... ... _. ......... ~..-... ..-................................................ +-"'"'"'"'"'"'"'"'"'"'"'"'"'"'"'"'"'"'"'"'"'"'"'"'"'"'"'"'"'"'"'"'"'"'"'"'"'....-..-..-..-..-----~ ·x~::::·?· .

~ ~ ~ .. ... ::": : i·i':::, : ,.,;,~ ,·,:;,:·, l

,. ~ ~ l

, ................... L::=·:T:~:::: .. :~~:.~:~_J __ "~:;f:."@.L, ___ « ___ """'-----""""---""""-""""'"""'-"""'""""'--"""'"""'-""""'-""""""~;:;;;;:"~·~~"'""~--~

········~

···.··:··:.::-. ;:-:-·.-·:-..

IPEC00234082

IPEC00234082

Page 47: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

APPENDIX A PIPING INSPECTION INFORMATION

I PEC00234083

PROGRAM SECTION NO. SEP-UIP-IPEC Revision No. 0 Page 47 of 69

DESCRIPTION

IPEC00234083

Page 48: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

APPENDIX A PIPING INSPECTION INFORMATION

PIPE GROUP I RISK RANKING

·~

PROGRAM SECTION NO. SEP-UIP-IPEC Revision No. 0 Page 48 of 69

""''-"';'·''·'"'"''''ummmu-;,'"""='7,' ~+_,_=:----1~~:7""~0""""" .......... ,.:: ....... , 1 .. ·:::=:: .. :::.::·=:·· '''"' =·<,·=~ ·. "<'<' : ·<'F' ::·;='~ ::;,·,\ .. t~~;E=··=~<: r~~·=;px~,':;.;3.'''''·~

·····::::,:::::,:~:·····ri:._, ...... ~-~~~:: l!, ,.,;;,.·,:,"'.:.=0ui""'~"'i-"'·:'i""<.--+---,"'.,."'.,,:....,...,.,.....wf·:,.,....._;.;.··:;.;.::i:.;;',,....·. "'" .. l"'"':::·:«··<«· ·~ . """""""~"""* - •--~-c:u::__ :,'·(,

:::::~::;::;. ;::-. ..:>;=:~;:·:;:. - ·~....,..,..-: .......... -- .:

~~):::~:~:::~-~:~f~(: ... -. ~:~·:•~ .. "'·=~-.-:""' ... """"!r· -....,,:---:::""':::.-.....;r----:~.-:: ... :':", --~--·::.8::::: -<-<-t-~~-+-.....;"-::':':~-""""w-:..<:':':";---l...:....~ ....... 1 .. ~~ttt;~~;-,.,r~~=:.;:::·;:(::=:-:·= .. :":~;~~1 .._ ... :: .... : ........ : ;:':~.=:;,:;. .......... : .... : .... : .. ,:.:::;: ... 1:-.,._;=-""""'--.....;;,;;.;.,. __ "'!-_.....;=:....,...-+-.;,·

·:::}: ......

IPEC00234084

IPEC00234084

Page 49: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

PROGRAM SECTION NO. SEP-UIP-IPEC Revision No. 0 Page 49 of 69

APPENDIX A PIPING INSPECTION INFORMATION

············:·······r~::~::·:·:·:::·::·T··:·::::::::,·::;--T------:::~:,------·r----·.~~:::.:::.:;·:--·~r--------:::;~:--------r----~~~~--·····r···;;;:;;:~;·;;:···r····~;:;·::······r·····:~~~;;;~;;·;.;;;;·:;E;;~;:~:;;,~~:~: .. ~.:~,, ..................... ~ .. '""TY"""""""~···················""""!-----+-----~---~---~--..........;----+----;,;..;..;,~

.• ·: • •. ::-.:: ~ :>: .• :. :-~-·.::.. ?-: .. ::~ ~:~.:·.:..

•, ·:·· ·::.:·. ::-:::. ::::_;;._::·· i·~.:.~. ::; :::-::::.:::. ·:· :_.::):h' ·{::-::::: .(:::: ~:· . i .. . . ... ..... : . :::.: :,:·::.:::;:.:> ~;:,::.x::.:x·:: ... .,.-.-.-.-.-.-..... -.- ... -.- ... -....... -.i······~~-:r:r?·~··;:··· ····r ......... · · · · · · · · · · · · · · ... 1 ................................................. 1 ................................................................ ~ ...................................................... 1 ............................................ T ................................... -: ....................... r ................................................. 1 ....................................................................................................... .

·.: ' : . :.:·: . : .. ' ,:. ~ =-<· .. , •. , .. ·:. ! ::;: .•·. ~ ;.:.:·. ~ •.. ; .. :>. l ' .. • .. :::: :~.:·: .. · I , ; . . . . : ~ ' ~ l ·······::·············,;.~[""'""'""'"'"""~

I PEC00234085

4~inch Aux Steam Condensate !'eturn !ine Irorn !P1. Excavated and found heavily

corroded in 2007. Associated burled a~lncn (entire length)

IPEC00234085

Page 50: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

SEGMENT NUMBER INSPECT

I.OCATION

APPENDIX A PIPING INSPECTION INFORMATION

PIPE GROUP/ ITEM

LOCATION ,JUSTIFICATION

RISK RANKING PRI

EXCAVATION NUMBER

DIRECT SOIL?

IN-LINE INSP,#

PROGRAM SECTION NO. SEP-UIP-IPEC Revision No. 0 Page 50 of 69

LENGTH

FUNDING SOURCE

DESCFUP110N

MISCELLANEOUS NOTES

:· :::·:?.:.::.::·

·····················t.~ o;:;·.::,: .... ~·'t·'·"················-"'·'-"'N4~~~~ry-.~~~~~4~~~~~ry..~~~""""i~~~~~~~~~~~~~~...;.:.:...:..;;,;..:.;"'-'-. ~~"-;~\

l"

::::-::::::.;:: :·.::-··:·.• ::

'-·················r·- ·~,,,,.:,,~::::······; .................... ..1 .:·: .. :·,·,·:.

I PEC00234086

IPEC00234086

Page 51: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

s~~~';(M LINE RAO/NON· NUMBER RAO

OR::;~NG D~~~~~G i~~:ii~v 1-~~~;)-

9321··F· 41943

9321·1'· 4181:i

9321-f· 41823

IPEC00234087

APPENDIX A

PROGRAM SECTION NO. SEP~UIP-IPEC Revis1on No. 0 Page 51 of 69

PIPING INSPECTION INFORMATION

---~iirii---+---~~;:~;;~:-~----1--~:~~;~;~:~--+----~~~; .. _ ELEVATION LENGTH i DESCRIPTION (DEPTH) ·······-···---·-+·--···-··-···----···scHEDULE. ~~~~~~ j MISCELLANEOUS NOTES LOCATION JUSTIFICATION i NUMBER INSP. il (atYYYY)

N/A F /PIPE 4 EXEMPT (L-L) YES NiA N/A Polabl" Water- Cold line !o PAB

N/A N/A N/A YES N/A N/A

IPEC00234087

Page 52: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

APPENDIX B

PROGRAM SECTiON NO. SEP-UIP-IPEC Revision No. 0 Page 52 of 69

TANK INSPECTION INFORMATION DESCRIPTI'?.~--------+-T-'A--"N-"K-'.9_~0UP /ITEM RISK RANKING jf.J:!_9~--+' ---- MISCELLANEOUS N_Q!~:.:::S ___ _

SCHEDULE (Cl/YYYY) FUNDING SOURCE PMID NUMBER' PMIO DESCRIPTION'

........ ; ....... . :}:': ::::.:(;:·:::·. :::::.: .::: -i · · · · · · · · · · · r .::::~~: :: .:.:·!-::: =: ::.: :-: ::::;:·:::-=-:\:::::··;:;~ ·::: ( ~ :_~ · ;){ ::·- :_.:.=~:::-.:.:.:: =

;-,· .. · .. . . -~<-::>::·:. -.;-.;-.:-.:.:?:~<.~:;~: ..;_.,,., .. -........ "" ::<:-:v:::::·: ::::: :·;: wo';-"-">')'" :::'i : .. ·.::-:-·o.;:.: :>:::;.(·:::·~~-:.v: :) ·:·.-:-::.::-. -:::·:·:r :'~~-~-.:~. ----~

. ·:cr?~:;:rrr~-~-~-~-~-~-1~---·_· __ ·_ .(~~:.}::f::i_-~-~-~-~-~-~-~-~~r:~:~rt~J:~5-;tr:~~::t:_>_;>_._-_:=.:=_;:_._'.~:.--_',-=~=,~:_.t_-,~:::::::~r:E:::f:: .. .'.'N •• :.._·,-,_=: .... ·.··········· ...... ri~:~?) .................. -"=,,: .............. _ :·:-... ~~~~:; ... : . : ~ .. .. . . . . . . .. .. .. .... . ............................. ..

- •• ·:;.~~-~:-:=-: ::~::::.:::::;:::-::::::~::;-,~:~. ::=:::::::.:~·~::·: ~:::=.:~.

w.•.•.•.•W•·······w ;o_:~~<=.i.~ (}Mi '"["" :W:,;>;:;·;·:i.<i:l,"~"~~~«•-.;..;.;..=;_;.;;.::.;.

·:.···

······:·· . -::.:x::::::t:~~:·:·:· .. ~ ::::i::: ::.:: · · · · · • • • • • • • • • • ~- • · · · · ·::::;: .. ::::}}!·T~ i .-=~U · · · · · · · · · ·1· i:=~.-~ :: ::..-:::~·:-:-:_.:;: -": :·. ;:: .. ~ .. ::=_.;::::_.;: · .. : .. ~· ·::: ::?:·:~:: t · ;.): ~-:-~ :_::: ::: :-:.:-·-- ··-·.· · ·

!'-~-=f" :: -\=::~::·:=:~:~::>_ f:~l: ~~::~:~-{:::~::::~:>::=~~:-t.-~· ~~:Gf:f,N-Y~\t~:::::::~:::~~:::.

·:;-:/~·;;~: -·-··-\'t_····_·_ ... _ .... _·=·~·;::::·':«•••••~:L ... :.;~;;:•::;~~:::·.=:::·=i;;,;:;::=';~~-:''::.;:: .... · .. w····l····::::.~·-;-··-;;'c;;:;~c,;·~~~c,;::~c;~~-····-•-· .. · .. ••W<±•••••• ,,,;:"'C ~~t~]~~~~:'' : ·:. ;:::·:-: :.:~=:-:·:::: ::-::: ·.;_.; :::.~::: ·:· :~:·:.::-.

_._ .. _--_,_-:·_· '"""_,__-··=···: ··-·-·-··:;~: .. ~;:i.:;·~······ -----·-·r·-·· . .,.;:;;,.,._..,.._""=::~"_.:· .... ' .... ·--r ...... :::""-~r:::~·~~-······-.·?~1-:: {-:::~~~-: ·=:?: ~~~:::-:;::{#1~:-t~~:;~.-:::::<:-:t::::::: ·-"'"'"'"' ..

;;(:";.;:-\:::·;~::::·(.::;::·.

i,e,~i:X,:;,:. ::;;::::,:,.,::.:;,:,:;.::,=,:·;·:':('C~~.;~;""-:"'·.:,0;;.·:.:"'· """-~-

~.:t.:::~::~·-;. ~;:: .. ~·~-:;

··~·;. ... ,~L::0.:.T::r:::~c:r:~;:zg~ ,_,,,_,,,,,,, ',,,., -·= ,""!,~,~:_-__ -___ "r,_-__ ::::-~:-:_~---"'"'""._.....~ ·.;: ··: ::~.:.:;:;·:·: : :::(?~~:~

I PEC00234088

IPEC00234088

Page 53: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

·.;.· ·.·:::.: ·.::.::.::::-~ •.wh~.w~u•••••••••••.•••.•.•.•.•.•.•:•.•.•.•.•.•.•.•.•.· •. ~~__;;;.;;;;;;;,.;......

IPEC00234089

APPENDIX B

PROGRAM SECTION NO. SEP-UIP-IPEC Revision No. 0 Page 53 of 69

TANK INSPECTION INFORMATION RISK RANKING PRI 1 ----·················_!!I.I§CELLANEOUS NOTES

PMID NUMBER' PMID DESCRIPTION'

:: ·.::~:·~ :_,:~:-:_:·::~·:;:::.:·::.: ·:~ ==-~= ::·:·:-::::;.:: .. : ·.:-~::::: ::;:··: :•'( -.:=:~:·:--:<:<

.

--_"'"'_·_*.=,-'_·"'·::.:~:-~: ::: ::::.~:·::_: .. : ~:;:.: :~: ::::.:: :.~:::-:··:x:~: ~~~r:~:= ~;:::::: ~~~~~=>:~-~=~: ~:~:~~:~~~~::=~::

~~~~~~~~~~~--~--~--~~.~.~ .. ~~~«~~~~~~~~--------~~~ ~\ ·::::K:::5.~:~·:: t:;:~~:-:·

· · · · · · · ·: · ~~-~; ·{;;~-~-::·:·:::;.i ·;;·:;::;-::::;:~~:;:::;:;··::::t:r:·--~}~-- :·:::: ::;=~: :::.>~:::-:.:: :: -~"""'-~~~.;;;C::';:,''-·.;;''':..' ---···-" --""'·~·'';;;.;"''~::;.;;;:::;~:<;;;-~-~: J;));.L~i1i1i~~;:;=''-"'·'''''''" ·::':::::·:->:

IPEC00234089

Page 54: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

IPEC00234090

PROGRAM SECTION NO. SEP-UIP-IPEC Revision No. 0 Page 54 of 69

IPEC00234090

Page 55: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

APPENDIX B

IPEC00234091

PROGRAM SECTION NO. SEP-UIP-IPEC Revision No. 0 Page 55 of 69

IPEC00234091

Page 56: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

-·=·····

I PEC00234092

APPENDIX B TANK INSPECTION INFORMATION

•• £1)SK RANKtr~? PRI)'

PMID NU!iiii3Efl'

PROGRAM SECTION NO. SEP-UiP-IPEC Revision No. 0 Page 56 of 69

__ _..::1\i::::!I~.CELLANEO~~ NOTES

PM!D DESCRIPTION'

tightness tests, using approved NYS DEC test method. (IP2 is categorized as a Major Oil Storage Facility (MOSF.) leak tests, utilizing pressurelvacuum/UT method, and satisfy Westchester County Dept of Heaith (WCDOH) tank

categorized as a Petroieum Bulk Storage (PBS) lacilily.) !P-SMM-EV-103, "Petroleum Bulk Storage Tank Program''

IPEC00234092

Page 57: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

APPENDIX C SUMP INSPECTION INFORMATION

DESCRIPTION SUMP GROUP /ITE!ill RISK RANKING (PAl)

FUNDING SOURCE PMID NUMBER'

IPEC00234093

PROGRAM SECTION NO. SEP-UIP-IPEC Rev. No. 0

Page 57 of 69

MISCELLANEOUS NOTES

PMID DESCRIPTION'

IPEC00234093

Page 58: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

SUMPNUMSE!l

INSPECTION STRATECW

IPEC00234094

DESCRIPTION

SCHEDULE (QIYYYY)

APPENDIX C SUMP INSPECTION INFORMATION

SUMP GROUP /ITEM RISK RANKING (PRI}

FUNDING SOURCE PMID NUMBER'

PROGRAM SECTION NO. SEP-UIP-IPEC Rev. No.O

Page 58 of 69

MISCEI.LANEOUS NOTES

PMIO DESCRIPTION'

IPEC00234094

Page 59: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

APPENDIX C SUMP INSPECTION INFORMATION

PROGRAM SECTION NO. SEP-UIP-IPEC Rev. No. 0

Page 59 of 69

S~~~~M SUMP NUMBER DESCRIPnON SUMP GROUP I ITEM RISK RANKING (PAl) MISCELLANEOUS NOTES

DHI<~~~; PID ----j~~~!~~~~l SCHEDULE {QfYYYY) F~~;~-NG SOURCE PMiD NUMBER' PM;~-~~~~;;·;;:;;;-~~-------------------1

or potentially contaminated are included.

IPEC00234095

IPEC00234095

Page 60: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

DESCRIPTION

IPEC00234096

APPENDIX D

PROGRAM SECTION NO. SEP-IUP-IPEC Revision No. 0 Page 60 ol 69

DRAIN INSPECTION INFORMATION

KING(Pfll) MISCELLANEOUS NOTES --------~-------------- ------------------------1

NUMBER PMID DESCRiPTION

~:::~.:"o.::~·: ~:. ·······································

IPEC00234096

Page 61: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

APPENDIX E

PROGRAM SECTION NO. SEP-UIP-IPEC Revision No. 0 Page 61 of 69

CATHODIC PROTECTION..;.P:Mr.:ljN~F~O~R~~rgJ_As.[N.!TGIO(E~. ~~tl!:' +==:::1~~~~]'23~===~ ··- ____ _rn MISCEU.ANEOUS NOTES

PMID NUMBER2 PMID DESCRIPTION'

: 1 Cf'i?. ·-· ·:-::DP3::_ ·:.::·:-:~::::- :=::;;;.::-:-::: ::~: ::-::-:~::~:::: -~-:. ::::.=:::: --------------------------------------------------------------r----

=-= :··.::·-~--::·:·: ·:~=-::·: -:·:.;·::

:: : ~::P:::~ .-.-· ~:~;(fH ~.-:: ::::~:;:::· ::::::::~:::::. :~::~:-:~;:.::;::::: :~:. :;:':::~:)

;~=~:::-~=~::~~ ·-:·:.:~:~<:$_:/.;::~::::~:::· ~J: ::::<:::;:.;:..<:;::::~:

:'":'~r,,· .,. ... "'«",;" .. ""~..N:·• .. .;; ...... -..,. .... ",.,;,;"""'!""'!'!""" ....... '!'!'!'!'!'!'!'!~----:'!'!'!"""",..."·:~-........ -,..-.-

... •.•C•.•C•C•C•.•C•.•C•.•.•.•.•.•.•~~-~~·.w.•.•.wt~-"'~-----------+---------~----------"------~'~'"''«~"''"''"«<«•"''"«•'«'~~'~"

~·-=~:-:: : ·:

~ ..... ·.:;·:;;:::;;;;::;;;;·~'~--~:--i:::~~;~············;;:,·;·,;:;;.;.:,~·~;.:;:·;,;;,:.::::::::::::~~:,---::~J=~~~~«.~ .. ~ .. -.. · """"""""-""""""""""""""""""--+:--------....,..-....,......,......,......,......,..-'-:~:_~)-----! ·: .}::::::.::.·~ ?~-~;:~t:·;-~::_::~~.::;.,~.. ~::;;:~.~-~ ·: ~~ (:~&~~-~: ~:

............. ~ ... «-t .... « ..... : .......................... r,,· ...................................................... -:-:.-:··

: .::·:·:=:-: ::·.:·r· ~·::.:.::::::·::·::::-: ·: ~-:>:·:·=: ~.;:_::. ~::.=.::: : ~ :::r:~ ·-· ·:~:DP3=: ;··· . .:::." · .. ·-.:·:· ·.: ···":: .. ,: ... ~ .. ·.".::

--~--------M---------..;..-------""""!""""·'······························································'"··························································-·.-.-.•.•.•.•.•.•.•.•.•. ~ ':.,.·-::.~·::.:-:_::- ·:·.~·:::::· .?~ .-"\ .. ::;:.;::::. :;;:-: :::-::-:::• ~::·~=·

···.···.··.·:·.·.·.••.·.~·-'"'~'"'*'"''"''"''"''"'"''·'·'·'·'·'·'·'·'·'·'·'·'·'·'·'·'·'·'·'·; •.•. •.•.•.•.•.• . ......, __________ ry _________ ,_,,.._,_,.,_,.,_,._,_,_..,., __ <+~~..,... .... .,.,.,.,.,.,.,.,'\"'\"'\"0:_._..,~.,.,..._.,......,......,......,......,......,......,......,......,~~-f :: ~:P :: ~:k;;.:~:· ~.:::f ~·::.:.:;;::~:~:::::..-· :: ·::{:-::,::::

:·::=-.-:·-::··· : ·: :: :.:·:·: :::=:·: ·::.: =·:·:::·~;·:: r::::>:~:. ~ :·: ::. : ....... . _________ .... .;. ................. ~~~~-+---------t---------------4 : ;:;:-·:: : :; . :;: ~ :··:: .:=. =··:;:" ::: ~ ~.:.:~:

w.•.•·····•··.•.•.•.••.•.•.•.•.•.•.•.· .• ~~w.•mm.•.w.~.w-• "'"'""""'"'!"""~~~,...........,~:----~~,...........,""""~~~~~~

· :··· ! :J::~:=.::::: ~::;:_:.-~·-:=::::X?~~::::-:=~~:;:.:~~~~:::~:::~· :;:;::::::i;:::~::~::=.::· ~:;~:: ·. ~{:/.:.

. . . . . . . . .::; ,:,:,: . ..... ,.,,"',.,;,:,:: ;;::.;;;;,, + ................... :,;,:;,;::;;,: ... , ..... ··<·········-r··········-··--·;;;;:;················1···<····· ····::::::::::;:;.;:;;:;::::::;· ........ ···r:::~;~:::;;::{~;;;;:;t;;J~d t:l··_,·_=~_=:_::_=~_-:.-_?_-:_=~_ ;_=~_.;_:;_ :_ ·_:~_.;_;_=:_=;_:~_-:_~_:;_ -; _:_;:.~. ·_ ·_ ·_ · __ ·_ ·_ ·_ ·_ ·_ · __ · __ ·_ ·_

-+--==--·w+-·--muumu«««««<««««« ••••••••• ••••• •

:,,,, .. , ·• . ·:=::: ·,,:.c::=i= .... --.-.-.· · ... '.' .. _.''_.=:.:.=_:._ .. · ... =: .. _·_.,·.: · .. · {·=':',.==c:,=::~.'''''''"'''·.' .. ,'.:=_.:_,_·' .. ' .. '· .. ~:.·:':'.''' ................. .:.. (::f' ·························:,,······ · .' .. =· .,~ ····· · · ... · · · · · · · · · ~'. ·':'c;::l\';)/P::":it:;;_;:'::•:,\D\;,·:,:,:·,:.:,:,;::,;,: :::;,:; ,,,, ·'' ' ' ~::=.~~!-.-~ :·==::-:::::::::-::; .. :·~ -:}

y •• :: •••• :: •• ::.:.::: •••• ;.;::.: •• ,-· --·······-·····················.· •• ·,-···········"""""""""'""'""~---...M--------=-------......N...·;;;;·····:;;;..;;;·'· ·==±!£:;;;;:;;;~?;; .......... .,."'" ..................................... .

IPEC00234097

IPEC00234097

Page 62: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

IPEC00234098

APPENDIX E CATHODIC PROTECTION PM INFORMATION

PROGRAM SECTION NO. SEP~UIP-IPEC Revision No. 0 Page 62 of 69

GROUP/ITEM

FUNDING SOURCE

RISK RANKING {PRI)' _ ---------------------~1_§2._~)-LANEOUS NOTES

PMID NUMBER' Pi\1110 DESCRIP110N'

IPEC00234098

Page 63: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

PROGRAM SECTION No. SEP-UIP-IPEC Revision No. 0 Page 63 of 69

APPENDIX F Page 1 of 2 Component Inspection Data Sheet, Typical

SCOPE

System Number/Description:

Line/Tank Number:

Component Number:

Segment Number{s):

Segment Location:

Drawing Number(s):

Inspection Priority:

Basis for Scope Selection:

WORK MANAGEMENT

Engineering Change:

PM!WO Number:

Clearance Number:

LCO Number:

Condition Report Number:

________ , __________ _

-----------------------~--,---

------------------------PRE-INSPECTION VERIFICATIONS

Previous Inspection (Y/N)

Cathodic Protection (YIN)

Coating (YIN) Type: ----­

Backfill Type:----------

Job Safety Hazards Analysis

Functional (YIN) Rectifier Number:

Soil Analysis (Y/N)

Contains Rock (Y/N)

Radionuclide (Y /N)

Permit ~\lumber:---------------------------~-­

Permit Number, --------------------..

Asbestos Abatement Lead Paint a> a> 0

"""" ('I) N 0 0 () w 0....

(j) (j) 0 "<t (")

N 0 0 () UJ a..

Page 64: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

PROGRAM SECTION No. SEP-UIP~IPEC Revision No. 0 Page 64 of 69

APPENDIX F Page 2 of 2 Component Inspection Data Sheet, Typical

SCHEDULE

Online (YiN)

Scheduled Start Date:

Scheduled Finish Date:

INSPECTION METHOD(S)

Divisional Week: ___ _

Actual Start Date:

Actual Finish Date:

Indirect Inspection Coating Holiday Detection (Y/N) Method:---------

Internal Inspection Pig (YIN) Vendor: -------------------- Pipe Cleaning (Y/N)

Visual: VT-1 (YIN) VT-2 (Y/N) VT-3 (YIN)

Direct Local NDE (Y/N)

Ultrasonic/Guided Wave (YIN)

Method:---------

Other:------------

M&TEITOOLS

M~I-~. Digital Light Meter:

Ultrasonic Meter:

Transducer{s):

Holiday Detector:

Pit Gauge:

Tools

List all required:

Expiration: _____ _

Expiration: _____ _

Expiration: _____ _

Expiration:·-----­

Expiration:

Date:~~----0 0 .......

"""" ('I) N 0 0 () w 0...

0 0 .,... "<t ("')

N 0 0 () UJ a..

Page 65: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

PROGRAM SECTION No. SEP-UIP-IPEC Revision No, 0 Page 65 ol 69

APPENDIXG INTEGRATED SCHEDULE

r-[~iSPECTIONiimT________ mTiNENU~IBER!S! I DATE SCiiEDULED l wo # I

EXCt-3

~-~·- --~~~g~~?---

EXC3-3

..., '-~-· .~, ..... '. - ,..,,_,.,. ,....,_,.,,..,.... -~," '~' 6·inch WD Une 252 (R\Ivv1 uv't!tt!vw v ... 1 vvnv 1 J 3,;nch Sl Line 161 (SIP <Etum to the RWST} 12-inch S! Line !81 (RWST to Cont. Spray Pump::.} 16-inch Sl Line 155 (RWSTto RHR Pumps)

6-inch AUX STM Line 561

JCl2011 NiA

ADDITIONAL EXCAVATION SITES TO BE SELECTED BASED ON APEC SURVEY RESULTS AND SiTE SOIL .1\NALYSIS.

....... 0 ....... -.;:t ('I) N 0 0 () w 0...

.,.... 0 .,.... "<t ("')

N 0 0 () UJ a..

Page 66: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

PROGRAM SECTION No. SEP-UiP-IPEC Revision No. 0 Page 66 of 69

APPENDIX H PROGRAM DRAWINGS

EXC1-3: IP3@ NW Corner of the WHUT Pit

Reference: drawing 9321-F-26313

See legend below for line description:

from Refueling Water Storage Tank (NORTH)

*N ~

Buned lines continue to the Fuel Storage Building on the Left (WEST). PAB is at lower left

A 15 it (N-S) x 20 It (E-W) x 8ft (deep) excavation (grade is at approx. El. 54ft) wili uncover the following lines:

N 0 ......

"""" ('I) N 0 0 () w a..

N 0 .,.... '<t ('")

N 0 0 () UJ a..

Page 67: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

PROGRAM SECTION NO. SEP-UlP-lPEC Revision No. 0 Page 67 of 69

APPENDIX H PROGRAM DRAWINGS

EXC2-2: IP2 West Side of the Turbine Building

Reference: Drawing 9321-2700 Co-ordinated excavation with installation of EC 25313 Lines to be inspected 24-inch SW Lines 408 and 409

lengtt·1 circumference. At the access point location, the of

tN I

EL 8'-6'', and the access point is at 4'6" downstream of a vertical rise ot T-6" from excavation will be 10 ft (E-W) x 12 ft (N-Sl x 10 ft deep.

Line 408) is at 1'-0". The

('I) 0 ......

"""" ('I) N 0 0 () w a..

("") 0 ..-'<t ("")

N 0 0 () UJ [l_

Page 68: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

PROGRAM SECTION No. SEP-UIP-IPEC Revision No. 0 Page 68 of 69

APPENDIX H PROGRAM DRAWINGS

EXC3-3: BURIED LINES FROM THE IP3 CST TO THE AFW PUMP BLDG.

IP3· YARD AREA

"""" 0 ...--

"""" ('I) N 0 0 () w 0...

"<t 0 ..... "<t ("")

N 0 0 () UJ a..

Page 69: 3 UNDERGROUND COMPONENTS INSPECTION …1. NEI 07-07, Final "Industry Ground Water Protection Initiative Final Guidance Document". August 2007 2. "Buried Piping Integrity Initiative",

PROGRAM SECTION No. SEP·UIP·WEC Revision No. 0 Page 69 of 69

APPENDIX H PROGR.AM DRAWINGS

ADDITIONAL EXCAVATION SITES TO BE SELECTED BASED ON APEC SURVEY AND SITE SOIL ANALYSIS.

1.[) 0 .......

"""" ('I) N 0 0 () w 0...

1.0 0 .,.... "<t ("")

N 0 0 () UJ a...