3 - LCI Fundamentals
Transcript of 3 - LCI Fundamentals
7/27/2019 3 - LCI Fundamentals
http://slidepdf.com/reader/full/3-lci-fundamentals 1/17
GEH-6373
Innovation™ Series
AC Drives
Load Commutated Inverter
User’s Manual
7/27/2019 3 - LCI Fundamentals
http://slidepdf.com/reader/full/3-lci-fundamentals 2/17
Innovation™ Series
AC Drives
Publication: GEH-6373
Issue date: 1998-03-31
Load Commutated InverterUser’s Manual
7/27/2019 3 - LCI Fundamentals
http://slidepdf.com/reader/full/3-lci-fundamentals 3/17
© 1998 by General Electric Company, USA.All rights reserved.
Printed in the United States of America.
These instructions do not purport to cover all details or variations in equipment, nor to
provide every possible contingency to be met during installation, operation, and
maintenance. If further information is desired or if particular problems arise that are not
covered sufficiently for the purchaser’s purpose, the matter should be referred to GE
Industrial Control Systems.
This document contains proprietary information of General Electric Company, USA and
is furnished to its customer solely to assist that customer in the installation, testing,
operation, and/or maintenance of the equipment described. This document shall not be
reproduced in whole or in part nor shall its contents be disclosed to any third party
without the written approval of GE Industrial Control Systems.
GeniusTM
, Field ControlTM
, LogicMasterTM
, and Series 90TM
are trademarks
of GE Fanuc Automation North America, Inc.
InnovationTM is a trademark of General Electric Company.
TeflonTM
is a trademark of E.I. DuPont de Nemours and Co., Inc.
Windows® is a registered trademark of Microsoft Corporation.
7/27/2019 3 - LCI Fundamentals
http://slidepdf.com/reader/full/3-lci-fundamentals 4/17
Load Commutated Inverter, User’s Manual GEH-6373
Safety Symbol Legend • a
Safety Symbol Legend
Indicates a procedure, practice, condition, or statement that, if not strictly
observed, could result in personal injury or death.
Indicates a procedure, practice, condition, or statement that, if not strictly
observed, could result in damage to or destruction of equipment.
Note
Indicates an essential or important procedure, practice, condition, or statement.
CAUTION
WARNING
7/27/2019 3 - LCI Fundamentals
http://slidepdf.com/reader/full/3-lci-fundamentals 5/17
GEH-6373 Innovation Series AC Drives
b • Safety Symbol Legend
This equipment contains a potential hazard of electric shock or burn. Only
personnel who are adequately trained and thoroughly familiar with the
equipment and the instructions should install, operate, or maintain this
equipment.
Isolation of test equipment from the equipment under test presents
potential electrical hazards. If the test equipment cannot be grounded to the
equipment under test, the test equipment’s case must be shielded to prevent
contact by personnel.
To minimize hazard of electrical shock or burn, approved grounding
practices and procedures must be strictly followed.
To prevent personal injury or equipment damage caused by equipmentmalfunction, only adequately trained personnel should modify any
programmable machine.
WARNING
WARNING
7/27/2019 3 - LCI Fundamentals
http://slidepdf.com/reader/full/3-lci-fundamentals 6/17
Load Commutated Inverter, User’s Manual GEH-6373
Section 2, Functional Description • 5
2 Functional Description
Section 2 of this manual is a functional description of
the LCI. Its purpose is to provide a basic technical
overview of the operating theory, to help the user bet-ter understand how to run and maintain the drive.
This description requires the reader to be already fa-
miliar with the principles of power conversion and
microprocessor-based control. This section is organ-
ized as follows:
Section Heading Page
2-1. LCI System Basics ........................................... 5
2-1.1. Power Conversion......................................... 5
2-1.2. Excitation Voltage Controller....................... 6
2-1.3. Microprocessor-Based Control ..................... 6
2-2. Power Converter Operation .............................6
2-3. Control Operation ............................................9
2-3.1. Synchronization ............................................9
2-3.2. Commutation................................................. 9
2-3.3. Force Commutated Operation/Modes......... 10
2-3.4. Load Commutated Mode ............................ 10
2-3.5. Torque Control............................................ 13
2-3.6. Phase-Locked Loop..................................... 15
2-4. Dual-Channel, 12-Pulse Configuration.......... 15
2-4.1. Shutdown Operations.................................. 16
2-5. Series 12-Pulse Configuration ....................... 15
2-1. LCI System Basics
The LCI is a static, adjustable frequency drive system.
It uses application-specific, microprocessor-based
software to control the speed of a synchronous ma-
chine (motor or generator). The basic LCI is a 6-pulse
configuration that consists of two functional sections:
a power converter assembly and a control assembly
Figure 2-1 is a simplified one-line diagram of a single
channel LCI. Sections 2-1.1 through 2-1.3 describe the
function of the components shown. Sections 2-5 and
2-6 cover 12-pulse configurations.
2-1.1. Power Conversion
The LCI power converter is made up of a rectifier
that feeds an inverter through a dc link reactor. A
transformer isolates the LCI from the ac system bus
and provides the correct voltage at the rectifier termi-nals. The transformer’s internal impedance limits the
magnitude of any downstream bus faults.
The rectifier is a line commutated, phase-controlled
thyristor bridge that functions as a source converter.
Its microprocessor-controlled gating produces a vari-
able dc voltage output to the dc link reactor. The re-
actor smoothes the current and keeps it continuous
over the system’s operating range.
The reactor output is fed to the inverter, which is a
load commutated thyristor bridge. The inverter is also
microprocessor-controlled and functions as a loadconverter (see section 2-2.1.1). The inverter produces
a variable frequency ac output to a synchronous mo-
tor’s stator terminals.
ACLINE
ISOLATIONTRANSFORMER
RECTIFIER(SOURCE)
DC LINKREACTOR
INVERTER(LOAD)
SYNCHRONOUS MACHINE
FIELD
MICRO-PROCESSOR –
BASED CONTROL
EXCITATION
VOLTAGE
CONTROLLER
Figure 2-1. Simplified LCI System One-Line Diagram
7/27/2019 3 - LCI Fundamentals
http://slidepdf.com/reader/full/3-lci-fundamentals 7/17
GEH-6373 Innovation Series AC Drives
6 • Section 2, Functional Description
2-1.1.1. Power Flow Reversal . The LCI’s rectifier
and inverter bridges use the same power hardware and
are both controlled by microprocessor-based elec-
tronics. Their functions can be reversed by reversing
their power flow. In this case, the synchronous motor
is braked by pumping its energy back into the ac line.
Because of this reversing capability, the line sidebridge (labeled rectifier in Figure 2-1), can also be
called the source converter ; the machine side bridge
(labeled inverter ) can be called the load converter.
2-1.2. Excitation Voltage Controller
The synchronous motor field is usually excited by a
brushless exciter coupled to the motor shaft. The
brushless exciter is a wound rotor induction motor. Its
rotor voltage is rectified to supply field current to the
synchronous motor.
The LCI control cabinet includes a static excitationvoltage controller to supply stator voltage for the
brushless exciter. The LCI’s electronic control (see
section 2-1.3) gates/controls this voltage controller.
This controls the excitation to produce the required
machine flux. It also provides field overcurrent and
undercurrent protection.
For applications with slip-ring excitation, the LCI
supports control of a dc bridge exciter from the same
control hardware as the brushless exciter uses.
For applications using an external ac or dc exciter,
the control fully supports any external excitation that
is compatible with a simple set of control signaling.
2-1.3. Microprocessor-Based Control
(Refer to Figure 2-3.) The LCI’s microprocessor-
based electronics control firing of both the source and
load bridges. It processes input signals for this func-
tion as follows:
• Attenuated source and load bus voltage signals:
– To synchronize source and load thyristor firing
– For voltage feedback
– For overvoltage and undervoltage detection
• Attenuated source and load current signals from
current transducers:
– For regulator current feedback
– Electronic overcurrent detection
– Software-implemented fault detection
• Speed reference signal
• Process commands, such as stop and start
The LCI control evaluates the process commands and
internal status signals to determine whether the LCI
should be in a stopped, started, alarmed, or faulted
condition.
If in a started condition, the control provides gate sig-
nals to the thyristor bridges and the excitation voltage
controller. These signals are low-level and are condi-
tioned in the power bridge circuitry to provide the
necessary isolation and power level.
2-2. Power Converter Operation
Note
The system elementary diagrams contain de-tails on the source and load bridge configu-
ration for each customer requisition.
The power bridges are 6-pulse, 2-way types. (See sec-
tions 2-4 and 2-5 for 12-pulse bridge configurations.)
The elementary diagram shows the physical arrange-
ment of the thyristors (SCRs) in the power bridges.
The bridge legs fire in the order that they are num-
bered (see Figure 2-2). The synchronous machine sta-
tor voltages transfer the source converter current from
one leg to the next.
1
CONDUCTS
3
CONDUCTS
5
CONDUCTS
FIRE 1 FIRE 3 FIRE 5 FIRE 1
CONDUCTS
2 4
CONDUCTS
6
CONDUCTS
6
FIRE 2 FIRE 4 FIRE 6 FIRE 2
120
1
CONDUCTS
CONDUCTS
Figure 2-2. Bridge Leg Conduction Sequence
7/27/2019 3 - LCI Fundamentals
http://slidepdf.com/reader/full/3-lci-fundamentals 8/17
Load Commutated Inverter, User’s Manual GEH-6373
Section 2, Functional Description • 7
Figure 2-3. LCI Control Block Diagram
Microcomputer
(DSPC Board)
High Speed I/O(ADMA/DDTB Board)
Innovation Series Controller(UCVA Board)(Option)
Genius Bus
Series 90 Protocol(SNPA Board)
(Option)
Series 90-30 PLC(Option)
Field I/O
Fiber-Optic Gate & Status
Current Feedback
Voltage Feedback
Fiber-Optic Gate & Status
Current Feedback
Voltage Feedback
Fiber-Optic Gate & Status
Current Feedback
Voltage Feedback
Fiber-Optic Gate & Status
Current Feedback
Voltage Feedback
Gate, Current, & Voltage Signals
Source A Bridge Control(FCGD Board)
Source B Bridge Control(FCGD Board)(Option)
Load A Bridge Control(FCGD Board)
Internal (AC/DC) ExciterControl(FCGE Board) (Option)
Load B Bridge Control(FCGD Board)
(Option)
7/27/2019 3 - LCI Fundamentals
http://slidepdf.com/reader/full/3-lci-fundamentals 9/17
GEH-6373 Innovation Series AC Drives
8 • Section 2, Functional Description
Figure 2-4 shows the process of switching motor/
inverter current from one leg to the next. The princi-
ples apply to both the rectifier bridge and inverter
bridge. This phase-controlled switching is based on
the following two thyristor characteristics:
• When the voltage across the thyristor is positive, it
can be triggered into conduction.
• It does not permit current flow in the reverse di-
rection. Thus, in an alternating voltage circuit, thy-
ristor conduction stops and reverse voltage begins
to appear when the current becomes zero.
Figure 2-4. Load Converter Voltage and Current
7/27/2019 3 - LCI Fundamentals
http://slidepdf.com/reader/full/3-lci-fundamentals 10/17
Load Commutated Inverter, User’s Manual GEH-6373
Section 2, Functional Description • 9
Current transfer must be completed before voltage
crossover with a positive margin angle. This angle
must be long enough to allow the previously conduct-
ing leg thyristors to recover to their blocking state be-
fore forward voltage is applied.
This is why the fundamental component of current
must lead the voltage for the inverter/motor, but lagthe voltage for the rectifier/source. For successful
commutation, angle α = 180° − β = 180° − µ − γ must
always be less than 180°, with a practical limit at
155°. A practical minimum value for β for the inverter
bridge is 25°. Therefore, the motor power-factor angle
is always greater than zero.
The LCI control system must conform to the charac-
teristics of the synchronous machine operating at
leading power factor. Figure 2-5 shows a phasor dia-
gram for a synchronous machine operating at leading
power factor.
Figure 2-5. LCI-Driven Synchronous Motor Diagram; Leading Power Factor
With a fixed amount of field excitation, the machine
voltage characteristic is mainly a function of the rotor
field-excitation, E f 1, and the de-magnetizing action of
direct-axis current. This produces the I D X AD2 voltage
in opposition to the voltage produced by field excita-
tion.
As shown, an increase in stator current I S results in
higher direct-axis current, which increases I D X AD3.
This, in turn, decreases the motor voltage E G4 avail-
able for commutation, thereby increasing displacement
angle θ . This increase of angle θ further increases
stator current, and so on, until equilibrium is reached
at a new operating point.
In actual practice, the motor field excitation is fixed in
the speed range of approximately 0 – 10%. It is con-
trolled to produce a desired profile of motor flux at
higher speeds.
At speeds greater than 10%, the LCI operates in a
flux-regulated mode. It adjusts the output of its static
exciter voltage controller (EVC) to maintain motorflux at the desired level.
2-3. Control Operation
2-3.1. Synchronization
When operating in any mode (see sections 2-3.3 and
2-3.4), the electronic control must synchronize firing
of both the source and the load converters. It synchro-
nizes these to the ac line and synchronous machine
bus voltages, respectively, using attenuated bus-to-
ground signals as its primary feedback. The controlcombines these inputs to produce line-to-line analog
voltages for both converters. It then integrates these
voltages to obtain flux signals.
The flux signals’ zero-crossings are then used in syn-
chronizing the phase-locked loop for firing control of
both converters. At low speed, before the phase-
locked loop is effective on the load side and if tach
position mode is not enabled, the zero-crossing marks
are used as a timing reference for firing in force com-
mutated operation.
2-3.2. Commutation
The LCI’s source side converter always operates line
commutated. Therefore, the ac line voltage transfers
conduction from one thyristor to the next. The load
side converter may operate either force commutated
(see section 2-3.3) or load commutated (see section
2-3.4), depending on motor speed and flux level.
As the synchronous machine’s rotor (field) rotates, the
near-sinusoidal shaped field flux cuts the stator wind-
ings. This produces a set of three sinusoidal voltages
in the stator. These sinusoidal voltages are angularlydisplaced by 120 electrical degrees. The magnitude of
this counter-electromotive force (cemf) is proportional
to speed and field strength.
At low speeds, the induced emf is insufficient to
commutate the thyristors in the load side converter.
Therefore, in this mode, the load converter must oper-
ate force commutated.
DIRECT AXIS
QUADRATUREAXIS
IS
ID
EG
EFIQ
IQXAQ
ID XAD
θ
7/27/2019 3 - LCI Fundamentals
http://slidepdf.com/reader/full/3-lci-fundamentals 11/17
GEH-6373 Innovation Series AC Drives
10 • Section 2, Functional Description
2-3.3. Force Commutated Operation/Modes
Force commutated operation is used:
• When starting the synchronous motor from zero
• During low speed until the motor cemf is sufficient
for load commutation
(See Figure 2-6.) In force commutated operation, con-duction of the load converter is stopped by phasing the
source converter to inversion limit until the dc link
(reactor) current is zero. Thus, the dc link current is
chopped into 60°-wide segments of motor frequency
(angle).
There are several modes of force commutated opera-
tion. These can be separated into two types:
• Modes where the digital pulse tach is used to track
rotor position
• Modes where the tach is not used
During initial startup (commissioning) of the LCI, the
tach is deselected until initial operating checks are
completed.
2-3.3.1. Starting Without Tach. In this mode, the
starting current must be large enough to accelerate the
motor to about .5 Hz in one or two inverter firings.
This is approximately the minimum frequency at
which the LCI can reliably sense motor flux and begin
to control torque and speed.
When a start from standstill is initiated, the LCI ap-plies a fixed current level at a fixed frequency to the
motor’s stator. The frequency is set by tuneup
STFREQ and the starting current level is set by tuneup
CRSTART (see section 5).
When the LCI control senses that flux has reached
sufficient magnitude, it transitions into the segment
firing mode of forced commutated operation. In this
mode:
• Inverter firing is synchronized to crossovers of the
motor flux
• The motor is operated near unity power factor to
obtain maximum torque
• Inverter firing is adjustable in 30° steps or seg-
ments
• The speed regulator becomes active
At approximately 5% of motor speed, the load phase-
locked loop can lock. Inverter firing resolution in-
creases to 0.35°, ending segment firing mode.
Force commutated operation continues until the syn-
chronous motor reaches a frequency with enough emf
to commutate the load side converter. At this point,
the control changes to load commutated operation.2-3.3.2. Starting With Tach . For LCIs using a pulse
tach for applications with high starting torque, the tach
pulses are counted to keep track of the rotor position.
Starting from standstill does not depend on zero-
crossings of motor flux.
The LCI ramps up stator current until it detects shaft
rotation. At that point, it freezes current and fires the
thyristors based on the rotor position determined from
the tach count. This continues for several firings to
ensure that the motor is rotating. Then the speed
regulator is enabled.
The speed regulator then controls stator current to
produce the correct torque to accelerate the motor as
required. Force commutated operation continues until
there is enough motor cemf to commutate the load
side converter.
2-3.4. Load Commutated Mode
Load commutated operation (mode) requires that the
motor be operated at a leading power factor. This
ensures commutation of the load converter.
The LCI control keeps the motor power factor, and
therefore torque-per-ampere, as high as possible. It
does this by firing the load converter as close to the
inversion limit as possible, while maintaining suffi-
cient margin for successful commutation of current
from one thyristor to the next.
For successful commutation, the volts-seconds re-
quired are proportional to product of the load current
and motor inductance. The LCI controls commutation
and firing time by processing the following three val-
ues:• Motor (load) current
• Motor commutating inductance (a constant stored
in the microprocessor system memory)
• Available volt-seconds from the integrated line-to-
line motor voltages
7/27/2019 3 - LCI Fundamentals
http://slidepdf.com/reader/full/3-lci-fundamentals 12/17
Load Commutated Inverter, User’s Manual GEH-6373
Section 2, Functional Description • 11
Using the current and inductance, the control
calculates the amount of commutation volt-seconds
required. The control then uses this value of volt-
seconds and the latest calculation of available volt-
seconds to determine the latest possible time to fire.
This gives a specified margin after commutation com-
pletes.
0IA
+
-
IB
0
+
-
-
0IC
+
0ILINK
-
+
34
45 6
5 61
12
23
LOAD CONVERTERLEGS CONDUCTING
FIRING TO ESTABLISH
PHASE-ON OCCURS
WITH FIRING OF A NEW
THYRISTOR LEG PAIR.
FIRING LEVELTO MAINTAINLINK AND MOTOR
INVERTING TOSHUTOFF
0
+
-
LINK VOLTAGEAT SOURCE
THYRISTOR BRIDGEOUTPUT
0
+
-
LINKCURRENT
OUTLINED AREA ABOVESHOWN IN DETAILWITH SOURCECONTROLLING ACTION
Figure 2-6. Forced Commutation Firing Mode
7/27/2019 3 - LCI Fundamentals
http://slidepdf.com/reader/full/3-lci-fundamentals 13/17
GEH-6373 Innovation Series AC Drives
12 • Section 2, Functional Description
Figure 2-7 shows the relationship of the system volt-
ages, currents, and flux waves. The commutating
“notch” identified in the A-C line-to-line voltage is
equal in amplitude to the simultaneous commutating
“bump” on the B-C voltage. The corresponding notch
in the A-B voltage is twice this amplitude (A and B
are the two lines commutating together at this instant);
the notch area is twice the commutating inductanceper phase times the current. The voltage at the com-
mutating point, where the lines are temporarily con-
nected by the thyristor legs, is practically zero during
commutation; the line-to-line voltage is only the for-
ward voltage drops of the conducting thyristor legs.
At high load on the motor, the apparent power factor
“seen” by the power source increases. This is because
the source converter firing angle advances (is reduced)
to obtain more current. The harmonics in the current
and the resultant harmonics in the voltage, caused by
commutation notching, decreases.
The fundamental control strategy is to increase motorcurrent in response to a load torque increase. The dc
link voltage on the source side is then increased, rais-
ing motor current so that it keeps motor speed con-
stant.
EXCESS VOLT-SECONDS AFTER COMMUTATION(COMMUTATION MARGIN)
POWER FACTOR ANGLE,BETWEEN CENTERS OFVOLTAGE & CURRENT WAVES
LOAD LINE-NEUTRAL VOLTAGES
CURRENT INTO LOAD,NUMBERS REPRESENTINVERTER LEGSCONDUCTING & COMMUTATING
ANGLE OF OVERLAP, µ(COMMUTATION ANGLE)MARGIN ANGLE, γ
LOAD LINE-LINE VOLTAGES
COMMUTATING VOLT-SECONDS=COMMUTATING INDUCTANCE X
STATOR CURRENT
PEAK VOLT-SECONDS AVAILABLE
(READ BY PROCESSOR TOCALCULATE LATEST TIME FOR NEXTFIRING)
LOAD "FLUX" WAVES
Figure 2-7. Load Voltage and Current in Load Commutated Mode
7/27/2019 3 - LCI Fundamentals
http://slidepdf.com/reader/full/3-lci-fundamentals 14/17
S ect i on2 ,F unct i onal Descr i pt i on•
1 3
F i g ur e2 - 8 .L C I S y s t em
R e
g ul a t or B l o c k Di a gr am
7/27/2019 3 - LCI Fundamentals
http://slidepdf.com/reader/full/3-lci-fundamentals 15/17
GEH-6373 Innovation Series AC Drives
14 • Section 2, Functional Description
The torque command signal is applied to both the
source and load side control. Since motor torque is a
function of flux, current, and the angle between them,
torque can be controlled either of two ways:
• By adjusting stator current magnitude from the
source side at a fixed load firing angle
• By maintaining a constant current and varying the
displacement angle (firing delay angle) on the load
side
However, at any one time, only one of these means can
actively control the torque.
The torque command to the source side control is ap-
plied to a maximum and minimum current limiter. The
minimum current level is set to maintain continuous
current in the dc link. The minimum current is usually
set at 0.2 per unit (pu) of rated dc current.
The minimum current limit also affects the load firingangle (therefore, motor power factor) whenever the
torque command produced by the speed regulator is less
than the minimum current limit. In this case, the load
firing angle (and motor power factor) is varied as a
function of the torque command, while stator current is
held constant. Thus, torque is controlled by adjusting
motor power factor whenever the torque command is
lower than minimum current limit.
The minimum current limit may also be dynamically
increased by the action of the voltage limit regulator.
This regulator reduces stator voltage by simultaneouslyincreasing current and decreasing power factor. The
voltage limit regulator is used mostly in applications
where the field excitation is fixed.
When the torque command is greater than the mini-
mum current limit, the load firing angle functions as
follows:
• If motoring, the load angle is at its inversion limit.
• If regenerating (braking), the load angle is at its
rectifying limit.
When motoring, the load control adjusts the firingdelay angle to be as late as possible to maintain a
fixed commutation safety margin (usually 20°). This
fire-as-late-as-possible control adapts to changes in
stator current and voltage to maintain the margin angle
constant.
To regenerate the drive, the load side thyristors fire
full advance (point “X” in Figure 2-9). At this time,
the source side controls current by reversing the dc
voltage to match the rectified motor voltage.
VAN VBN VCNX
Y
Z
I N T E G R A T
E D
L I N E - T O - L I N E V O L T A G E
VCA VAB VBC
X =
CELL 1FULL
ADVANCE
Y =
CELL 1
FULL
RETARD
Z =
INVERSION
LIMIT L I N E - T O - N E U T R A L V O L T
A G E
Figure 2-9. Flux Wave Zero-Crossing
The drive current command is the greater of the ab-
solute value of the torque command (from the speed
regulator) and the minimum current limit. The current
command is compared with current feedback and the
error is applied to the current regulator.
The current regulator controls the firing of the thyris-
tors in the source converter (rectifier). Thus, the
source control adjusts the dc link voltage as required
to produce the current and torque needed to drive the
load.
Note
The load firing control reverses the polarity
of dc link voltage if braking torque is re-
quired.
7/27/2019 3 - LCI Fundamentals
http://slidepdf.com/reader/full/3-lci-fundamentals 16/17
Load Commutated Inverter, User’s Manual GEH-6373
Section 2, Functional Description • 15
2-3.6. Phase-Locked Loop Operation
The source and load controls use a phase-locked loop
(PLL) to track bus voltage angle. This enables the LCI
to fire the thyristors at specific angular displacements
from the ac bus voltages.
The PLL uses the zero-crossings of reconstructed
3-phase flux waves as a timing reference. At eachflux wave crossing, it is possible to determine the an-
gular position within the present cycle of phase A-to-
neutral of the ac bus voltage.
The PLL uses the FCGD board (see Section 3) to
capture the time and polarity of each zero-crossing of
the 3-phase flux waves. The control maintains a run-
ning estimate of electrical degrees based on elapsed
time and rate of change of the electrical angle. As each
zero-crossing occurs, the corresponding electrical de-
grees and timing are compared to the control estimate.
From the comparison, an error in the estimated de-grees is determined and applied to the PLL regulator.
The regulator increases or decreases the rate of change
of the angle, to drive the error toward zero.
The control determines a firing angle for each thy-
ristor. Using the estimated electrical degrees, it calcu-
lates the time when the drive will be at the desired
firing angle. The control then places a firing command
and time to activate into FCGD board registers, which
completes the firing process.
2-4. Dual-Channel, 12-Pulse Configuration
(Refer to Figure 2-10.) A dual-channel, 12-pulse LCI
is configured as two identical, separate 6-pulse drives
operating from a common source. This allows two
motors to be combined into one frame, reducing both
the motor and installation costs.
Twelve-pulse operation best uses the motor and drive
capabilities. It minimizes the harmonics present in
each 6-pulse channel, canceling 5th and 7th harmon-
ics. Other higher-order harmonics also cancel, but
their amplitudes are much smaller.
Note
Refer to the system elementary diagrams for
the exact configuration and detail of each
customer’s system.
The transformers feeding the two drives (channels)
are identical, except their windings are 30° apart. This
design enables the drives to operate as follows:
• With the same current and firing angle
• The firing reference angles shifted by 30° between
the two channels
• Equal source-side converter voltage, but 30° apart
in the two channels
• Reduced harmonic distortion on the power system
and higher harmonic frequencies
Figure 2-10.
Dual-Channel,
12-Pulse LCI
Source Bridge
Load Bridge
Load Bridge
LoadSource Bridge
Exciter
7/27/2019 3 - LCI Fundamentals
http://slidepdf.com/reader/full/3-lci-fundamentals 17/17
GEH-6373 Innovation Series AC Drives
The two motors use a common magnetic frame and a
common field. This causes the load side converter
voltage to be equal in amplitude and frequency be-
tween the two drive channels.
The load motor’s stator winding is separated into two
identical windings, but isolated and phase-shifted 30°.
This reduces the torque pulsation amplitude whileraising the torque pulsation frequency. The result is
smoother torque for equal current.
Inter-channel communication allows one channel to
be master and the other the follower (also called
slave). The follower takes its torque reference from
the master, enabling the two motor winding currents to
be balanced. Thus, the channels deliver equal power,
take equal current, and fire at the same relative firing
angle.
2-4.1. Shutdown Options Some dual-channel, 12-pulse systems allow one chan-
nel to be shut down for maintenance while the motor
continues to run on the other channel (with reduced
torque and usually reduced speed range). When the
out-of-service channel is ready for operation, it can be
returned to service without interrupting the LCI sys-
tem.
However, dual-channel, 12-pulse systems that use a
single control to operate both power converter chan-
nels cannot run with one channel shut down.
2-5. Series Twelve-Pulse Configuration
(Refer to Figure 2-11.) Some LCIs are configured for
series 12-pulse operation of the source converter. This
is done primarily to reduce the harmonic distortion
imposed by the drive on the power system. Twelve-
pulse operation eliminates half the harmonics pro-
duced by a 6-pulse system, starting with the 5th and 7th
harmonics.
Note
Refer to the system elementary diagrams for
the exact configuration and detail of each
customer’s system.
The 12-pulse converter consists of two identical SCR
bridges connected in series. Each bridge is operated at
approximately half the motor voltage. The ac sources
for the two bridges are supplied from delta and wyetransformer secondary windings and displaced in
phase by 30°.
12-PulseSource Bridges
Load
BridgeLoad
Figure 2-11. Series 12-Pulse LCI