    H T D / UTELECOM Unit

    High Technology in Refrigeration Devices

    HTD /U --0--PD --GB --00   -- Product Documentation

    Packaged Air Conditioning Unitsfor

    TELECOM Shelters

    GB

  • 8/15/2019 3. Internal Shelter Units HTD

    2/24

  • 8/15/2019 3. Internal Shelter Units HTD

    3/24

    Index

    iHTD/U--0--PD--GB--00  --  05.10.2003

    Index   HTD/U = Design & Technology

    Features and Fortes

    Configuration DIGIT

    Manufacturing Specifications

    Control Software and Hardware

    List of Main Options

    Tests and Reference Standards

    Technical Data

    Dimensional Drawings

    Refrigerant Circuit

  • 8/15/2019 3. Internal Shelter Units HTD

    4/24

  • 8/15/2019 3. Internal Shelter Units HTD

    5/24

    HTU

    FRONT VIEW 

    HTD

    FRONT VIEW 

    HTD/U = Design & Technology

    1HTD/U--0--PD--GB--00 --  05.10.2003

    HTD/U = Design &

    Technology

    HTD/U units

    The units of the series   HTD/U   “HiRefTelecom packaged air conditioning unitsfor indoor applications ” are to be used forthe conditioning of low and mediumpowered telephone exchanges.

    They are designed to be mounted insideshelter.

    Versions

    Thanks to the innovative design and theoriginal solutions,   HTD/U   can be easlyused in the most different configurationsof the destination site. It is available in thefollowing versions:

    D   HTD version:--  Air delivery Downwards;

    D   HTU version:--  Air delivery Upwards.

    Indoor mounting

    The machines are designed for an indoormounting with Plug & Play logic, to reducethe installation times and the need ofspecific professional skills in theinstallation step.

    Direct expansion

    The   HTD/U   package units aremono--block conditioners with directexpansion and air--cooled condenser.The innovative system of air circulationgives a significant improvement of theperformances in different thermal load

    conditions.

    Reduced noise level

    The use of centrifugal fans with 4--polebackward curved blades, together with aScroll--type compressor and a cabinetdesign eliminating every source of innersound reflection and vibrations, makesthis equipmentsuitable also forcity areas.

    Minimized pressure drop

    The whole recirculating and Free--Coolingsection has been designed to limit thepressure drop (air side) and to maximizethe unit performance; for this reason, the

    HTD/U units are featured by the exclusiveequipment with backward curved bladecentrifugal fans (Plug fans), the widesurfaces of the evaporating coils and ofthe intake grilles, in line with the supplystandard of the main phone companies.

    Structure

    All HTD Uunits supporting structure are

    made of thick galvanized sheet steel, andenclosing panels made galvanised sheersteel coated with epoxy polyester powderpaint oven cured at 180  ºC (RAL xxxx). Itis featured by rounded shape edges,according to innovative style trends andthe accident prevention. All structuredetails are entirely produced in--housewith automatic processes integrating theCAD--3D designing (solid modeller) withthe production process (CAM) =CAD--CAM.

    The unit features an exclusive designwhich, combined with a rational layout ofcomponents and extremely compactdimensions, lends it an attractiveappearance.

    Panelling

    The front panels are equipped withhandles for an easy removal forinspections. The unit maintenance can befully made from the front, including theinnovative extractable damper section.This enables a unique flexibility, with unit“On Site Upgrading” and the possibility toaccess and clean the condensatecollecting tray.

    Power supplies

    All units are available with different supplyvoltages, with the option of double powersupply. In this case it is possible to havea 48 VDC solution for the air--conditioningcontrol, even in case of power failure.

    European directives

    The   HTD/U   units are designed andmanufactured according to the Europeandirectives currently in force, and areconsequently marked  E.

  • 8/15/2019 3. Internal Shelter Units HTD

    6/24

    Features and Fortes

    2   HTD/U--0--PD--GB--00 --  05.10.2003

    Features and Fortes

    Design & Technology

    The HTD U

    units introduce a new plantmodel featured by a pleasant designmatched with a rational arrangement ofthe components and an excellentassembly compactness.

    All units are factory tested by usingautomatic systems based on objective“in--out” criteria and are ready to beinstalled and started by simple wiring on

    site.

    Installation

    The HTD U package air--conditioning unitis suitable for all environments exeptaggressive ones. Make sure that the airinlet grilles have more than 0,8 m freespace around. Do not place anyobstacles near the unit and make surethat the air flow is not impeded byobstacles and/or situarions causing backsuction (see Fig. 1).

    The recommended sizes for the power

    cables and emergency line are shown inTab.1.

    Handling

    While the unit is being unloaded andpositioned, utmost care must be taken toavoid abrupt or violent manoeuvres. Theunit must be handled carefully andgently;avoid using machine components asanchorages or holds and always keep it inan upright position. The unit should belifted using the pallet it is packed on; atranspallet or similar conveyance means

    should be used.

    Start--Up

    Preliminary checks

    D   Check that the electrical connectionshave been made properly and that allthe terminals are securely tightened.This check should also be included in aperiodic six--month inspection.

    D   Check that the voltage at the RSTterminals is 400V + 5% and make surethe yellow indicator light of the phasesequence relay is on. The phase

    sequence relay is positioned on theelectric control board; if thesequenceisnot duly observed, it will not enable themachine to start.

    D   Make sure there are no refrigerant leaksthat may have been caused byaccidental impacts during transportand/or installation.

    D   Check the power supply to thecrankcase heating elements (ifpresent).

    First time starting

    Attention: 

    The unit is fil led with HFC R407Crefrigerant. This refrigerant belongs to

     group I (no toxic- no dangerous)according to EN Norm378 and accordingthe specification contained into CEE law 

     n5 2037/00.D   Install the unit in the computer room.D   Connect the power supply and the

    earth connection to themain switchandto the main earth connection.

    The starting procedure is operated bypressing the key “ON” on the controlkeyboard.

    Noise levels

    The HTD U units include theexclusiveuseof ventilation solutions, featured by a lowemitted noise level making theseconditioners compatible with cityinstallations.The support structure, thepanels and the fastening systems aredesigned to reduce vibrations and theirtransmission as low frequency soundemissions as much as possible.

    Energy efficiency

    The highest possible energy efficiencyhas been the main target in the wholethermo--dynamic and aeraulic designing.The refrigerating circuit is featured by theuse of “rolling piston” or “Scroll”compressors with top reliability and(optional) possibility of replacing thetraditional with an electronically --controlled electric valve: this brings areduced energy consumption by 50%when the outer temperature lowers below20!C and, above all, when the directfree--cooling is not possible.The aerauliccircuit implies the use of centrifugal fanswith backward curved blades, featuredby a very high reaction degree, it is thuspossible to remove the scroll and therelevant energy losses in thedynamic--statical conversion; all used

    fans can be equipped with “brushless”motor with permanent magnets andrelevant switching electronics, that canbe directly powered by an emergencymains at 48VDC or 24VDC. In this case,the dc motor efficiency matches with thefan efficiency, thus reaching outstandingenergy results (over 45%).

    The Freecooling in simultaneousoperation contributes remarkably toreduce energy costs in the range of outer

    temperatures between the inner set pointand TFT (Total Free -- Coolingtemperature).

    Emergency situations

    All units can be equipped with dualsupply: main supply and “DC” supply.

    S   Main supply:

    -- Compressor

    -- Heating

    -- Condensing section fan

    S   24VDC or 48VDC supply:

    -- evaporating section fan-- Microprocessor

    -- Damper servomotor

    In case of mains failure, a voltagepresence relay signals this to the “mP”control that, together with the ventilationand Free--Cooling section, continues tobe powered by back--up batteries. Thisensures the air--conditioning control evenwith possible inner temperature variationsfrom the set--point values.

    Manufacturing features

    All electric, aeraulic and refrigeratingcomponents are assembled inside themachine cabinet and cannot beaccessed from outside, without removingthe panels. The machine has a min.protection degree IP 44 and theprotection grilles of the rotary partscomply with the accident preventionsection of the norms EN 60335; as option,a further protecting grille for thecondensing section fan front is available.

  • 8/15/2019 3. Internal Shelter Units HTD

    7/24

    Features and Fortes

    3HTD/U--0--PD--GB--00 --  05.10.2003

    Upgrading

    The HTD Useries is developed on threedimensional “frames” This enables theupgrading of the basic radio stations dueto the implementation of newtransmissionstandards, and therefore to the increasedinner thermal load.

    Fig. 1 -- Service Area (top view)

         1     0     0     0    m    m200mm

         3     0     0     0    m    m

         I    n     d    o

        o    r

          O    u     t     d    o    o    r

    UNIT UNIT

    Tab.1 -- Cables Sizes

    UNIT MODEL MAINS POWER SUPPLY CABLE TYPE UPS EMERGENCY LINE CABLE TYPE

    HTD/U 045

    HTD/U 056

    HTD/U 073

    230V / 1Ph / 50Hz 2 x 6mm2 + T x 6mm2 48VDC / 230VAC 2 x 2,5mm2

    HTD/U 090

    HTD/U 105

    HTD/U 120

    HTD/U 150

    HTD/U 170

    400V / 3Ph + N / 50Hz 4 x 6mm2 + T x 6mm2 48VDC / 230VAC 2 x 4,0mm2

  • 8/15/2019 3. Internal Shelter Units HTD

    8/24

    Configuration DIGIT

    4   HTD/U--0--PD--GB--00 --  05.10.2003

    Configuration DIGIT

    The numerous constructiveoptions may be selected using the configuration scheme illustrated below.

    4 50H

    Family:HiRef Telecom Unit

    D   D version: Air delivery downwards

    D   U version: Air delivery upwards

    Refrigerating capacity“kW x 10”

    No. of refrigeratingcircuits

    ConfigurationDIGITS

    T D 0   1 1 65432 7 8 9 10 11 12

    1   Supply + (Auxiliary)   0   230V / 1Ph / 50Hz

    1   230V / 1Ph / 50Hz + [24VDC]

    2   230V / 1Ph / 50Hz + [48VDC]

    3   230V / 1Ph / 50Hz + [230V / 1Ph / 50Hz]

    4   400V / 3Ph + N / 50Hz

    5   400V / 3Ph + N / 50Hz + [24VDC]

    6   400V / 3Ph + N / 50Hz + [48VDC]

    7   400V / 3Ph + N / 50Hz + [230V / 1Ph / 50Hz]

    2 Control   0   BASIC

    B   ADVANCED [with local user interface]

    D   ADVANCED [without local user interface]

    3 Refrigerating cycle options   0   R407C

    1   R407C + electronic thermal expansion valve

    2   R22

    3   R22 + electronic thermal expansion valve

    4 Cabinet options   E   Painted galvanized sheet RAL7035

    5 Electric re--heating   0   Heaters -- NO

    1   Heaters -- YES

    6 Free--Cooling   0   Without Free--Cooli ng

    G   Modulating Free--Coolin g 0--10V

    H   Free--Cooling with spring return

    7 Air f il tration   0   G2 Filter [Standard]

    1   G3 Filter

    2   G4 Filter

    7   G2 Filter + Clogged filter sensor

    8   G3 Filter + Clogged filter sensor

    9   G4 Filter + Clogged filter sensor

    8 Condensation control   0   None

    M   On / Off

    N   Modulating fan speed [with pressure sensor]

    9 Serial communication   0   None

    1 (*) Serial card RS232 Modem

    2   Serial card RS485

    10 Coils   0   Copper tubes / alu fins [Standard]

    C   Epoxy coated condenser coil

    E   Epoxy coated evaporator coil

    11 Packaging   0   Standard

    1   Wooden crate with cardboard

    2   Seaworthy

    12 Special   0   Standard

    S   Special

    (*) - only for ADVANCED control

  • 8/15/2019 3. Internal Shelter Units HTD

    9/24

    Manufacturing Specifications

    5HTD/U--0--PD--GB--00 --  05.10.2003

    Manufacturing Specifications

    Structure

    The HTD Useries units are dedicated tothe indoor use with temperatures rangingbetween –20!C (under condensationcontrol) and +45!C. The entire innerstructure is made up of hotelectro--galvanized sheet with highthickness, and the outer paneling is insmooth 5005 aluminum alloy or, uponrequest, in galvanized sheet painted withepoxy--polyester powders RAL xxxx,oven--cured at 180!C. If painted, the

    colour of the units depends on thecustomer’s specifications for re--orderbatches of more than 20 pieces. Theinnovative global design of the machineenables a complete front accessibilitywhereas the outstanding possibility ofextracting/fitting the damper fromthe frontoffers the double chance of upgrading onsite of the machines originally without theFree--Cooling option, and it offers theaccessibility to theevaporatingcoil andtothe condensate collection tray, too.

    Refrigerating circuit

    The refrigerating circuit is entirely in housemanufactured, using welders certifiedaccording to the Directive PED 97/23 onpressurized containers, and all relevantcomponents are certified according to thesame directive.The exclusive rotary or scroll--type usedcompressors are available in the versionfor fluids type HFC (R407C; R134a); forthe non--EEC countries signing theMontreal Protocol, in the version withHCFC R22.

    The machine standard equipment

    includes a thermostatic lamination valveand a vacuum start device: this device isenclosed in the Scroll compressor or is

    outside in the versions with single--phaserotary compressor/s.The circuit is completed with anti--aciddryer filter with molecular sieve, a flowindicator and pressure intakes for themaintenance and/or inspectionoperations.

    Evaporating fan section

    The   HTD U units are fitted withcentrifugal--type fans, with (tilted)backward curved blades and singleintake. These fans are featured bydiverging blade ducts and by a high outerdiameter/inner diameter ratio, enabling toachieve an outstanding aeraulicefficiency; further, a high output speed

    and therefore a launch over seven meterscan be reached through their positiontowards the delivery grille. All machinescan be equipped with fans powered bybrushless motors with permanentmagnets, DC supplied at 48V, and in thiscase, combined with the ADVANCEDmicroprocessor. Therefore, it is possibleto pilot directly the rotating speed suitingit to the different operating conditions,such as: de--humidification, energysaving, etc.

    Finned pack evaporator

    With its dimensions 25x21.65 and a 3/8”pipe it is composed of 0.10--mm thickaluminum fins and copper pipesexpanded on the same for a completecontact. The design criteria privileges thefront section with the advantage ofreduced losses on the air side, while theexchange surface is sized so as to avoidde--humidification at the project ratedconditions. The condensate collectiontray can be accessed from the unit frontfor cleaning, and can be in galvanizedsheet or, as option, in austenitic stainless

    steel AISI 304L. A special flat metallicprefilter protects the evaporating coilagainst dirt: the prefilter can be easly

    checked and can be removed from theunit front for cleaning or replacing.

    Recirculation air filtration

    The filter is located upstream HTD(downstream HTU) the condensing coiland can be easily extracted by removingthe front panel dedicated to the

    filter/damper section. Thanks to itsposition, it filters both the recirculationandthefreshair in case of Free--Cooling: in thelatter case, on the fresh air ejectionsection, a metal filter prevents the nestinginside the container of small animals orinsects. The washable synthetic--typefiber filter, with efficiency EU2, is installedin a galvanized sheet frame for an easymaintenance.

    Condensing fan section

    All used 4--pole motors limit the soundemissions, and are outer rotor type to

    improve the energy efficiency and reducethe magnetic noise.

    Condenser with finned pack

    With geometry 25x21.65 and a 3/8” pipeit is composed of 0.10--mm thickaluminum fins and copper pipesexpanded on the same for a completecontact. The design criteria privileges thefront section with the advantage ofreduced losses on the air side, so that it ispossible to use 6--pole fans withminimized emitted sound power. The

    condensing coil can be equipped with ametal filter that can be easily removedfrom oneof themachine sides:this double

  • 8/15/2019 3. Internal Shelter Units HTD

    10/24

    Manufacturing Specifications

    6   HTD/U--0--PD--GB--00 --  05.10.2003

    access enables the maintenance even incase of double installation on thecontainer wall. A special flat metallicprefilter protects the condensing coilagainst dirt: the prefilter can be easlychecked and can be removed from theunit front for cleaning or replacing.

    Electric board

    It is located in a separate cabinet hiddenon the front side by the recirculation airbefore it is cooled by the evaporating coil:this aspect is extremely important for boththe component cooling and, at the sametime, for preventing the condensation on

    the bottom side of the board. Allon--boardsystems comply with the EEC Directive“Low tension 73/23” and with the relatednorms. The access to the electric board ispossible with operating unit as it iscompletely separated from the air flow;the protection degree with open panel isIP20.

    Packing

    The HTD Uunits are packed on woodenpallet with anti--shock cardboard anglesand upper protection incardboard/polystyrene. In the end, thewhole packing is wrapped with protectiontransparent polythene film.

    Application fieldHTD U units are to be used within theoperating limits stated in this manual;failure to comply with said limits willinvalidate the warranties provided in thecontract of sale (Tab.2).

    Tab.2 -- Field of Applications

    MODEL: HTD/U 045 056 073 090 105 120 150 170

    Power supply   V / Ph / F  230VAC  + / --10% / 1Ph / 50Hz

    24VDC  + / --16% -- 48VDC + / --16%

    400VAC + / --10% / 3Ph+N / 50Hz

    24 VDC  + / --  16% -- 48 VDC + / --  16%

    Minimum outdoor temperature   ºC   --20

    Maximum outdoor temperature   ºC   45 46 45 46 46 45

    Min. indoor temperature / humidity   ºC / R.H.   19 / 30%

    Max. indoor temperature / humidity   ºC / R.H.   35 / 50%

    Storage conditions   ºC / R.H.  --10 / 90%

    +55 / 90%

  • 8/15/2019 3. Internal Shelter Units HTD

    11/24

    Manufacturing Specifications

    7HTD/U--0--PD--GB--00 --  05.10.2003

    Interconnectivity

    All units can be connected with remotesupervision systems by the use of“Gateway”. When using the “mP” controlof the “ADVANCED” type, there is thepossibility of piloting directly a GSMmodem able to send and receive SMSmessages.

    Up to max. 6 units can be connected forthe stand--by – rotation control, with mPBASIC, in LAN (Local Area Networking),while up to max. 15 units can beconnected with ADVANCED type mP,sharing the operating parameters andenabling the stand--by rotation andre--start of the installed machines.

    The interconnection possibilities,according to control type, aresummarized in the two tables below(Tab.3 and Tab.4).

    Tab.3 -- mP ADVANCED

    PROTOCOL SERIAL CARD GATEWAY NOTES

    Not necessary RS485 network connection

    Proprietary Carel RS485   RS485 / RS232 converter

    (PC485KIT)   Connection with the supervision PC

    Modbus" RS485 Not necessary RS485 network connection

    BACnett   RS485   Gateway BACnett   RS485 network connection

    "  LON RS485   For the dedicated programming, contact

    LonWorksLON RS485

    Not necessary  ,

    HiRef S.p.A.

    Trend Trend serial Not necessary  For the dedicated programming, contact

    HiRef S.p.A.

    Tcp / Ip RS485 Gateway TCP / IP Ethernet network connection

    GSMRS232 GSM modem

      For the dedicated programming, contact

    HiRef S.p.A.

    RS485 control local network PlantWatch + GSM modem PlantWatch operates as concentrator

    Tab.4 -- mP BASIC

    PROTOCOL SERIAL CARD GATEWAY NOTES

    Not necessary RS485 network connection

    Proprietary Carel RS485   RS485 / RS232 converter

    (PC485KIT)  Connection with the supervision PC

    Modbus" RS485 Gateway Modbus" RS485 network connection

    BACnett   RS485   Gateway BACnett   RS485 network connection

    LonWorks" -- --   --

    Trend -- --   --

    Tcp / Ip RS485 Gateway TCP / IP Ethernet network connection

    GSM RS485 control local network PlantWatch + GSM modem PlantWatch operates as concentrator

  • 8/15/2019 3. Internal Shelter Units HTD

    12/24

    Manufacturing Specifications

    8   HTD/U--0--PD--GB--00 --  05.10.2003

    Tab.5 -- HTD -- Machine Main Components

    REF. DESCRIPTION

    1 Compressor

    2 Evaporator

    3 Evaporator fan

    4 Evaporator air filter

    5 Condenser

    6 Condenser fans

    7 Condenser air filter

    8 Electrical heaters

    9 Free--Cooling damper

    10 Motor (Free--Cooling damper)

    11 Electric board

    1

    Fig. 2 -- HTD -- Machine main components

    3

    7

    2

    4

    8

    6

    5

    10

    10

    9

    11

  • 8/15/2019 3. Internal Shelter Units HTD

    13/24

    Fig. 3 -- Mechanical cooling Fig. 4 -- Free -- Cooling

    IndoorOutdoor   IndoorOutdoor

    MACHINE FUNCTIONAL SCHEMES

    Conditioned air flow

    Exhaust air flow

    Free--Cooling air flow

    Condensing air flow

    1

    2

    4

    5a

    3

    1

    2

    3

    4

    5b

    IndoorOutdoor

    Fig. 5 -- Mechanical cooling Fig. 6 -- Free -- Cooling

    IndoorOutdoor

    Conditioned air flow

    Exhaust air flow

    Free--Cooling air flow

    Condensing air flow

    4

    5a

    3

    1

    2

    1

    2

    4

    5b

    3

    Manufacturing Specifications

    9HTD/U--0--PD--GB--00 --  05.10.2003

    Tab.6 -- HTU -- Functional Parts

    REF. DESCRIPTION

    1 Evaporator

    2 Evaporator fan

    3 Condenser

    4 Condenser fan

    5a Free--Cooling damper [closed]

    5b Free--Cooling damper [open]

    Tab.7 -- HTD -- Functional Parts

    REF. DESCRIPTION

    1 Evaporator

    2 Evaporator fan

    3 Condenser

    4 Condenser fan

    5a Free--Cooling damper [closed]

    5b   Free--Cooling damper [open]

  • 8/15/2019 3. Internal Shelter Units HTD

    14/24

    Control Software and Hardware

    10   HTD/U--0--PD--GB--00 --  05.10.2003

    Control Software and

    Hardware

    BASIC [Carel  ìAC] + ADVANCED[Carel pCO2]

    The HTD/U units can be supplied with twomicroprocessor control levels:

    S   BASIC with user interface 4x20 LCD

    S   ADVANCED

    Optional configuration:

    -- with user interface 4x20 LCD

    -- with built--in display 4x20 LCD

    For the ADVANCED controls, a remotedisplay is available too, and can bepositioned up to 200 m far with a simpleplug--in connection with phone--typecable.

    All microprocessors, BASIC, ADVANCEDand ADVANCED with built--in display4x20 LCD, enable to control completelythe units, such as:

    S   Sensors

    -- room temperature to keep the inner

    set--point

    -- outer temperature to pilot the

    Free--Cooling damper

    -- delivery temperature to prevent the

    risks of thermal shocks of the room

    electronic equipment

    -- condensing pressure (optional)

    -- evaporating pressure (optional)S   Functions:

    -- room temperature management

    -- reading of the relative humidity

    (optional)

    -- control of the air outlet min.

    temperature in the environment

    -- control of the air de--humidification by

    reducing the fan speed (with optional

    sensor and with optional dc fans)

    -- heating (optional)

    -- alarm control equipped with clean

    contacts for the remote connections

    of visual and sound systems-- stand--by management of two units.

    The LAN connection by the

    ADVANCED microprocessor,

    ensures other functions such as

    SMART, Free--Cooling, modem

    sharing, etc.

    -- clean contacts for every other type of

    alarm (optional)

    -- from the microprocessor it is possible

    to select the automatic restart after a

    voltage lack

    -- min. time between two compressor

    start --ups

    -- remote interface,up to 200m, directly

    connected using a LAN connection

    (for mP ADVANCED)

    -- possibility of connecting the unit with

    a supervision system (optional)

    -- 2 password levels to access the unit

    configuration

    -- clock card for recording the evendate and time

    -- hour--counter to enable a scheduled

    maintenance of the fans,

    compressors and filters

    -- automatic switching between two

    compressors for each unit with

    double refrigerating circuit. The

    algorithm can be selected to achieve

    the “one in operation – one in stand

    by” strategy or to achieve a balanced

    operating time between two circuits.

    The second circuit, too, is started

    when exceeding the preset set--pointtemperature, independently from the

    selected control strategy.

    Note:    the ADVANCED control is available for all units with double circuit, only.

    mP ADVANCED[Carel pCO2] technical data

    S   Flash memory: 1 MByte expandable to 16 MByte. . . . . . . . . . .

    S   RAM memory: 256 kByte expandable to 1 MByte. . . . . . . . . . .

    S   Parameter memory: 2 kByte. . . . . . .

    S   Analog inputs: B4 -- B5 = two inputs for NTC probes (--50 # 100!C), PT1000 (--100 # 200!C) / clean inputs. . . . . . . . . . .

    B1 -- B2 -- B3 = three inputs for NTC probes (--50!C # 100!C); voltage 0 # 1 V dc / 0 # 10 V dc,

    current 0 # 20 mA / 4 # 20 mA

    S   Analog outputs: Y1 -- Y4 = four opto--insulated outputs 0 # 10 V dc, max. load 10 mA (1 k$). . . . . . . . . .

    S   Digital inputs: ID1 -- ID8 = eight opto--insulated inputs 24 V ac 50/60 Hz / 24 V dc. . . . . . . . . . . .

    S   Digital outputs: No.1 # No. 8 = electro--mechanical relays. . . . . . . . . . .

  • 8/15/2019 3. Internal Shelter Units HTD

    15/24

    Control Software and Hardware

    11HTD/U--0--PD--GB--00 --  05.10.2003

    mP BASIC[Carel ìAC] technical data

    S   Analog inputs: B1 -- B2 -- B4 = three inputs for NTC temperature probes (10 k$ a 25!C). . . . . . . . . . .

    B3 = one input for humidity/pressure probe (0 # 1 V dc / 4 # 20 mA) + V = probe supply

    output (14 V dc, 30 mA max.)

    S   Analog outputs: Y1 = output 0 # 10 V dc, not opto--insulated, referred to the supply potential G0, max. load. . . . . . . . . .

    10 mA (1 k$)

    Y2 = phase disconnection output

    S   Digital inputs: ID1 -- ID10 = ten non--optoinsulated inputs referred to the supply potential G0, supplied. . . . . . . . . . . .

    with 24 V ac, current absorbed by each input 6.5 mA at 24 V ac

    S   Digital outputs: OUT1 -- 5 = 5 SSR, 24 V ac, 1 A, with min. current 20mA. . . . . . . . . . .

    OUT6 -- C6 = 1 relay, 220 V ac

    OUT7 -- C7 = 1 relay, 220 V ac

  • 8/15/2019 3. Internal Shelter Units HTD

    16/24

    Free--Cooling: capacity of two units

    Free--Cooling: capacity of one unit

    RoomSet Point

    FFT 2FFT 1

    Coolingcapacity

    True containerthermal

    requirement

    Room air

    temperatureFig. 7 -- Operating diagram

    List of the Main Options

    12   HTD/U--0--PD--GB--00 --  05.10.2003

    List of the Main Options

    1 ADVANCED microprocessor

    Programmable microprocessorwith 16 bitand high performances.

    2 Air differential pressure switch

    3 Double supplyS   AC main supply from the mains:

    -- Compressor/s

    -- Fan/s of the condensing

    section

    -- Heating

    S   Auxiliary supply 48 VDC

    (24 V DC, upon request):

    -- Microprocessor

    -- Evaporating section fan

    Note:  it is possible to activate the fanspeed control to enable the coilenergy saving during itsoperation.

    -- Damper servomotor

    4 Refrigerant R134a

    For extreme outdoor conditions up to+45!C.

    5 Free--Cooling with damper

    Thanks to the unit designing principle, it ispossible to carry out the “upgrading onsite” on the units not equipped with theFree--Cooling option.

    6 ETV--T “ElectronicThermostatic ValveTechnology”

    For applications where the directFree--Cooling is not possible.This solution enables to reduce theenergy consumption up to 50%compared to the standard units when theoutdoor temperature is below 20!C.

    7 Humidity sensor

    For the enthalpic control in theFree--Cooling situations (combined withthe mP ADVANCED control).

    8 Condensation control

    9 InterconnectivityS   Serial port:

    -- RS232

    -- RS485S   Communication protocol:

    -- Carel

    -- Modbus%

    -- LonWorks%

    -- BACnett

    -- TCP--IP

    -- GSM modem (complete

    management through SMS

    Services).

    Free--Cooling TechnologyThe innovative Free--Cooling systemenables to reach outstanding efficiencylevels, above all when operatingsimultaneously with the mechanicalcooling: this situation, in many central

    European climate areas, represents over50% of the yearly total hours.

    The damper is further designed to beintegrally extracted, thus enabling acomplete maintenance possibility as wellas the access to the condensatecollection tray.

    The HTD Udesigning concept enablesthe upgrading on site of units notequipped with the Free--Cooling option;this is important in such cases where it isnecessary to have a unit stock at

    disposal.

    The temperature sensors installed atdelivery, intake and fresh air controlcompletely the damper, improving itsenergy efficiency and avoiding the risk ofinlet air at temperatures lower than thelimit allowed by the electronic equipment.

    In case of combination with DUAL supply,mains + DC UPS, the Free--Cooling canenable to control the climate even inemergency situations and, if the two unitsare reciprocally connected, it canimplement all strategies for avoiding to

    lose the control of the inner set point of thecontainer (see Fig. 7).

  • 8/15/2019 3. Internal Shelter Units HTD

    17/24

    List of the Main Options

    13HTD/U--0--PD--GB--00 --  05.10.2003

    Damper servomotor withspring return

    It positions the dampers completely openor completely closed at the customer’schoice in case of power lack: with anoperation signal connected with a fire

    alarm, the damper is usually positionedclosed, to enable the operation of theautomatic switching--off systems.This option must be defined at the order.

    Clogged filter sensor

    This differential pressure sensor detectsthe filter clogging and generates an alarmdisplayed by the microprocessor control.

    Heating

    It is performed by using heaters inextruded aluminum, with high thermalexchange surface: this aspect enables tomatch reduced thermal inertias with

    reduced surface temperatures, to theadvantage of a full use safety. Eachheating element is protected by a safetythermostat directly acting on the supply.

    Outer paneling

    The standard supply includes panels inpainted galvanized sheetmetal RAL7035.

    Surface treatments on finnedcoils

    An efficient protection against corrosiveagents is guaranteed by thecopper--copper version, the cataphoresisprotection and the use of hydrophilepre--treated aluminum: the protectiongrade is reported in the mentioned order.

    Refrigerants

    According to the norm EEC 2037/00, theHTD U units can operate with:

    S  HFC R407C as standard

    S  HFC R134a (optional)S   HCFC R22 Export non--EEC in the

    countries signing the Montreal

    protocol

    The unit is supplied: tested and ready tobe started up on the site.

    Alarms

    It reports high and low priority alarms onclean contacts. In case of ADVANCEDmicroprocessor, it is possible to have asubdivision of the alarm type in the

    terminal board of the electric panel and,generally, it is possible to arrange Customsolutions according to the different supplystandards of the phone companies.

    Air distribution grilles

    The wall--mounted air distributions grillesare made of extruded aluminum, withsingle row of adjustable fins andaccident--prevention protection net on thedelivery. In case of Free--Cooling unit, afurther net is arranged on the air outlet toprevent the unwished entry of small

    animals and/or insects.

  • 8/15/2019 3. Internal Shelter Units HTD

    18/24

    Tests and Reference Standards

    14   HTD/U--0--PD--GB--00 --  05.10.2003

    Tests and ReferenceStandards

    Safety

    The HTD Uunits have been designed,manufactured and tested according tothe directives of the European Union:

    D   98/37/EC(former 89/392/EEC, 91/368/EEC,93/68/EEC)

    D   89/336/EECD   73/23/EEC

    Electric boards

    The electric boards comply withEN 60204--1.

    Electro--magneticcompatibility

    The   HTD U units complies with thefollowing EMC standards:

    S   EN 50081--1, Emissions

    (”Generic emission standard, Part 1:

    residential, commercial and light

    industrial”, January 1992)

    S   EN 50082--2, Electro--magnetic

    compatibility

    (”Generic emission standard,

    Part 2: industrial environment”,

    March 1995)

    Conformity

    Each HTD Uunit is supplied completewith test certificate and conformitycertificate according to the Directives ofthe European Union.The units are “  E”marked.

  • 8/15/2019 3. Internal Shelter Units HTD

    19/24

    Technical Data

    15HTD/U--0--PD--GB--00  --  05.10.2003

    Technical Data

    Tab.8 -- Performance table

    MODEL: HTD/U 045 056 073 090 105 120 150 170

    Refrigerant   [Ashrae]   R407C

    Total cooling capacity

    [I.T. 27ºC; R.H. 40% / O.T. 35ºC]  kW   4.50 5.60 7.10 8.97 10.85 11.85 14.98 17.20

    Power supply [standard]   V / Ph / F   230 / 1 / 50 400 / 3+N / 50

    Power supply [option 1]   V / Ph / F   -- 400 / 3+N / 50 230 / 1 / 50 --

    Power supply [option 2]   V / Ph / F  230/1/50+

    230/1/50  400 / 3+N / 50 + 230 / 1 / 50

    Power supply [option 3]   V / Ph / F   230 / 1 / 50 + 48 VDC 400 / 3+N / 50 + 48 VDC

    Power supply [option 4]   V / Ph / F   -- 400/3+N/50 + 48VDC 230 / 1 / 50 + 48 VDC --

    Total absorbed power   W   1810 2330 2990 3950 4400 5000 6040 7030

    Total absorbed current   A   8.3 14.3 13.6 11.8 12.5 13.6 17.8 18.6

    FLA   A   15.1 16.0 19.6 17.5 17.5 19.5 21.7 25.7

    LRA   A   30 47 61 40 46 50 65 74

    Indoor fan/s absorbed power

    -- 230V / 1Ph / 50Hz  W   108 310 470 520

    Indoor fan/s absorbed power

    -- 48VDC [option]  W   100 260 350 450

    Indoor air flow   m3 /h   1450 2100 3020 3800

    Indoor air flow

    -- Free Cooling [40 Pa]

      m3 /h   1320 1320 1980 2850 2810 2810 3550 3550

    Free Cooling temperature ºC 17.8 15.5 17.0 18.2 16.3 15.4 15.3 13.6

    Air filter efficiency   --   G 3

    Sound power level   dB(A)   69 72

    Sound pressure level

    [10m in free field]  dB(A)   58 61

    Type   Rotary ScrollCompressor

    No.   1

    Refrigerating circuit   No.   1

    Oil charge [each compressor]   dm3 0.44 1.00 1.00 1.10 1.10 1.10 1.36 1.65

    Indoor coil front surface   m2 0.30 0.38 0.42

    Outdoor coil front surface   m2 0.33 0.45 0.52

    Condenser air flow   m3 /h   2250 3750 4700

    Condenser fan -- HTU

    -- HTD  No.

      1

    1

    1

    2

    2

    2

    Width x Height x Depth   mm   800 x 1850 x 550 1000 x 1850 x 550 1160 x 1850 x 550

    Weight   kg   120 128 135 195 200 210 245 250

     FLA = Max. operating current.

    LRA = Pickup current.

  • 8/15/2019 3. Internal Shelter Units HTD

    20/24

    Dimensional Drawings

    16   HTD/U--0--PD--GB--00 --  05.10.2003

    Dimensional Drawings

    MOD. HTD 045 -- 056 -- 073 -- 090 -- 105 -- 120 -- 150 -- 170

    FRONT VIEW SIDE VIEW  

    TOP VIEW 

    45

         3     7 .     5

         3     7 .     5

         2     6     3

         2     6     3 .     5

         2     3     8

         1     0     4     8

    550

         2     6     3

         2     6     3 .     5

         2     3     8

         1     0     4     8

    85

         1     0     1

         5     5

         1     8     5     0

    A

    65   B   80

    C   300 300D E

    REAR VIEW 

    A   B   C D E

    HTD 090 --105--120

    HTD 150 --170

    HTD 045 --056--073   800

    1000

    1160

    655

    855

    1015

    250

    135

    150

    250

    130

    260

    --

    135

    150

    MODELS

    A

         4     5

         5     5     0

  • 8/15/2019 3. Internal Shelter Units HTD

    21/24

    Dimensional Drawings

    17HTD/U--0--PD--GB--00 --  05.10.2003

    MOD. HTU 045 -- 056 -- 073 -- 090 -- 105 -- 120 -- 150 -- 170

         3     0

         9     4     6

         9     4     6

         1     0     1

    310230 460

         3     3     5

         2     3     7

         3     0     1

    65 655 80

    550

         2     3     7

         3     6     0

         2     6     2

         4     5

         5     5

    85

    A

         1     8     5     0

         4     3

         2     5     0

         2     5     7

    100 100

    FRONT VIEW SIDE VIEW  

    TOP VIEW 

    REAR VIEW 

         4     5

         9     4     6

    300

         2     6     2

         2     3     7

         3     6     0

    65 80

    REAR VIEW 

    A

    B

    C ED   300

         1     8     5     0

    HTU 045--056--073--150--170

    HTU 090--105--120

    A   B   C D E

    HTU 090 --105--120

    HTU 150 --170

    HTU 045 --056--073   800

    1000

    1160

    655

    --

    1015

    150

    --

    150

    350

    --

    260

    --

    --

    150

    MODELS F

    600

    1000

    800

    A

    F

  • 8/15/2019 3. Internal Shelter Units HTD

    22/24

    Refrigerant Circuit

    18   HTD/U--0--PD--GB--00 --  05.10.2003

    Refrigerant Circuit

    MOD. HTD/U 045 -- 056 -- 073 -- 090 -- 105 -- 120 -- 150 -- 170

    P

    M

    P

    M

    4

    2

    5

    6

    3

    9

    8

    1

    7

    Tab.9 -- Refrigerant Circuit

    REF. DESCRIPTION REF. DESCRIPTION

    1   Compressor 6 Sight glass

    2 Condenser 7 Low pressure switch (LP)

    3 Thermostatic valve 8 High pressure switch (HP)

    4 Evaporator 9 Condensing pressure probe

    5 Filter dryer

  • 8/15/2019 3. Internal Shelter Units HTD

    23/24

  • 8/15/2019 3. Internal Shelter Units HTD

    24/24

    H     T     D     /     U   -   -     0   -   -     P

         D   -   -      G     B   -   -     0     0   -   -     0     5 .     1

         0 .     2

         0     0     3

    High Technology in Refrigeration Devices

    HiRef S.p.A   Via Umbria, 5/c -- 35043 Monselice (PD) – Italy

    Tel. +39 0429 784683 -- Fax +39 0429 701447

    e--mail: [email protected] -- Web: http://www.hiref.it

     r up