3-6 NCG Collection and Incineration - · PDF fileNCG Collection and Incineration Ben Lin, ......
Transcript of 3-6 NCG Collection and Incineration - · PDF fileNCG Collection and Incineration Ben Lin, ......
![Page 1: 3-6 NCG Collection and Incineration - · PDF fileNCG Collection and Incineration Ben Lin, ... System Design 5. NCG Equipment 6. ... Normally chevron demisters with vanes](https://reader031.fdocuments.in/reader031/viewer/2022013014/5aa30c2f7f8b9a1f6d8e0bdd/html5/thumbnails/1.jpg)
1
NCG Collection and Incineration
Ben Lin, P.Eng.A. H. Lundberg Systems Limited
Vancouver, B.C., Canada
2008 Kraft Recovery Short Course
Agenda
1. Introduction2. Glossary3. Types of NCG Systems4. System Design5. NCG Equipment6. NCG Incineration
![Page 2: 3-6 NCG Collection and Incineration - · PDF fileNCG Collection and Incineration Ben Lin, ... System Design 5. NCG Equipment 6. ... Normally chevron demisters with vanes](https://reader031.fdocuments.in/reader031/viewer/2022013014/5aa30c2f7f8b9a1f6d8e0bdd/html5/thumbnails/2.jpg)
2
1. Introduction
NCG is an all encompassing term for Kraft mill odourous gases that contain sulphur compounds, organics such as methanol and terpenes, water vapour and air
1. IntroductionKraft mill odourous gases are caused by sulphur compounds originating from:
- digesters- evaporators- turpentine systems - stripping systems- brown stock washers- filtrate tanks- liquor storage tanks
![Page 3: 3-6 NCG Collection and Incineration - · PDF fileNCG Collection and Incineration Ben Lin, ... System Design 5. NCG Equipment 6. ... Normally chevron demisters with vanes](https://reader031.fdocuments.in/reader031/viewer/2022013014/5aa30c2f7f8b9a1f6d8e0bdd/html5/thumbnails/3.jpg)
3
1. Introduction
NCG collection and treatment systems eliminate kraft mill odour by collecting and destroying the gaseous reduced sulphur compounds
1. IntroductionNCG vented to atmosphere can cause injury, environmental damage, and nuisance odour around the mill and surrounding community
Stringent environmental regulations require collection and incineration of these gases
![Page 4: 3-6 NCG Collection and Incineration - · PDF fileNCG Collection and Incineration Ben Lin, ... System Design 5. NCG Equipment 6. ... Normally chevron demisters with vanes](https://reader031.fdocuments.in/reader031/viewer/2022013014/5aa30c2f7f8b9a1f6d8e0bdd/html5/thumbnails/4.jpg)
4
2. Glossary
TRS: Total Reduced Sulphur
General term for Kraft mill odourous bivalent sulphur compounds
– Hydrogen sulphide H2S– Methyl mercaptan CH3SH– Dimethyl sulphide (CH3)2SH– Dimethyl disulphide (CH3)2S2
2. Glossary
CNCG: Concentrated Non-Condensable Gas
Low Volume High Concentration (LVHC)
Consists of Kraft mill odourous gases from digester and evaporator areas
Composed of TRS, wood organics, air and water vapour
![Page 5: 3-6 NCG Collection and Incineration - · PDF fileNCG Collection and Incineration Ben Lin, ... System Design 5. NCG Equipment 6. ... Normally chevron demisters with vanes](https://reader031.fdocuments.in/reader031/viewer/2022013014/5aa30c2f7f8b9a1f6d8e0bdd/html5/thumbnails/5.jpg)
5
2. Glossary
DNCG: Dilute Non-Condensable Gas
High Volume Low Concentration (HVLC)
Collected from BSW, filtrate tanks, liquor tanks
Consists primarily of air with trace TRS, wood organics and water vapour
2. Glossary
SOG: Stripper Off Gas
Product vapours from trim condenser
Consists of methanol, TRS, terpenes, wood organics and water vapour
Target concentration:– 50 wt % combustibles– 50 wt % water vapour
![Page 6: 3-6 NCG Collection and Incineration - · PDF fileNCG Collection and Incineration Ben Lin, ... System Design 5. NCG Equipment 6. ... Normally chevron demisters with vanes](https://reader031.fdocuments.in/reader031/viewer/2022013014/5aa30c2f7f8b9a1f6d8e0bdd/html5/thumbnails/6.jpg)
6
3. Types of NCG Systems
Concentrated (LVHC)
Dilute (HVLC)
Chip Bin Gas
Stripper Off Gas
3.1 CNCG SystemsLow Volume High Concentration
(LVHC)
![Page 7: 3-6 NCG Collection and Incineration - · PDF fileNCG Collection and Incineration Ben Lin, ... System Design 5. NCG Equipment 6. ... Normally chevron demisters with vanes](https://reader031.fdocuments.in/reader031/viewer/2022013014/5aa30c2f7f8b9a1f6d8e0bdd/html5/thumbnails/7.jpg)
7
CNCG - General
NCG released during the Kraft pulping process are noxious and have a very low threshold of odour detectability
TRS is generated in the pulp digesters when wood is cooked with Kraft liquor (sodium sulphide, Na2S, in the liquor reacts with a methyl group in the lignin in an oxygen deficient environment)
CNCG Composition
781444Nitrogen
2003Oxygen
1046Water
703047TRS
MaximumMinimumAverageCompound
![Page 8: 3-6 NCG Collection and Incineration - · PDF fileNCG Collection and Incineration Ben Lin, ... System Design 5. NCG Equipment 6. ... Normally chevron demisters with vanes](https://reader031.fdocuments.in/reader031/viewer/2022013014/5aa30c2f7f8b9a1f6d8e0bdd/html5/thumbnails/8.jpg)
8
CNCG SystemCNCG systems typically collect gases from the digesters, evaporators, turpentine recovery system and foul condensate tank
CNCG is typically disposed of by incineration in the lime kiln, power boiler, recovery boiler or dedicated incinerator
US Cluster Rules state that CNCG sources must be collected and destroyed with only 1% downtime
NCG is
CORROSIVE
![Page 9: 3-6 NCG Collection and Incineration - · PDF fileNCG Collection and Incineration Ben Lin, ... System Design 5. NCG Equipment 6. ... Normally chevron demisters with vanes](https://reader031.fdocuments.in/reader031/viewer/2022013014/5aa30c2f7f8b9a1f6d8e0bdd/html5/thumbnails/9.jpg)
9
Materials of Construction
Mild steel corrodes quickly
FRP experience is mixed
300 Series stainless steel works well
NCG is
T I C
![Page 10: 3-6 NCG Collection and Incineration - · PDF fileNCG Collection and Incineration Ben Lin, ... System Design 5. NCG Equipment 6. ... Normally chevron demisters with vanes](https://reader031.fdocuments.in/reader031/viewer/2022013014/5aa30c2f7f8b9a1f6d8e0bdd/html5/thumbnails/10.jpg)
10
NCG Toxicity
Highly Toxic– Responsible for a number of injuries and deaths
250 to 800 ppm of H2S exposure– Severe sickness, permanent damage to
respiratory system and mucous membranes
1000 ppm of H2S exposure– 30 minutes is fatal
TRS concentration in CNCG systems– 100,000 to 500,000 ppm
NCG VentsMake them
![Page 11: 3-6 NCG Collection and Incineration - · PDF fileNCG Collection and Incineration Ben Lin, ... System Design 5. NCG Equipment 6. ... Normally chevron demisters with vanes](https://reader031.fdocuments.in/reader031/viewer/2022013014/5aa30c2f7f8b9a1f6d8e0bdd/html5/thumbnails/11.jpg)
11
NCG System ToxicitySystem vents directed to a high point clear of well-travelled areas– E.g. up the side of recovery boiler stack
Design with ejector near incineration point– Ensure entire collection system is kept under
vacuum
Leaks must be fixed immediately
Scott air packs must be used when entering areas with high TRS concentrations
![Page 12: 3-6 NCG Collection and Incineration - · PDF fileNCG Collection and Incineration Ben Lin, ... System Design 5. NCG Equipment 6. ... Normally chevron demisters with vanes](https://reader031.fdocuments.in/reader031/viewer/2022013014/5aa30c2f7f8b9a1f6d8e0bdd/html5/thumbnails/12.jpg)
12
NCG is
EXPLOSIVE
Combustion PropertiesCombustibles in CNCG are above UEL (Upper explosive limit)– Insufficient oxygen to sustain combustion
Combustibles in DNCG are below LEL (Lower explosive limit)– Insufficient combustibles to sustain combustion
CNCG and DNCG streams should never be combined– Result in explosive mixture
![Page 13: 3-6 NCG Collection and Incineration - · PDF fileNCG Collection and Incineration Ben Lin, ... System Design 5. NCG Equipment 6. ... Normally chevron demisters with vanes](https://reader031.fdocuments.in/reader031/viewer/2022013014/5aa30c2f7f8b9a1f6d8e0bdd/html5/thumbnails/13.jpg)
13
Combustion Properties
502TRS
6.00.8Alpha Pinene
36.56.7Methanol
21.83.9CH3SH
454.3H2S
UEL (vol %)LEL (vol %)Compound
Explosive Range of CNCG
% TRS
5
10
15
20
0 10020 40 60 80
% O
XYG
EN
Explosive Range
NormalRange
![Page 14: 3-6 NCG Collection and Incineration - · PDF fileNCG Collection and Incineration Ben Lin, ... System Design 5. NCG Equipment 6. ... Normally chevron demisters with vanes](https://reader031.fdocuments.in/reader031/viewer/2022013014/5aa30c2f7f8b9a1f6d8e0bdd/html5/thumbnails/14.jpg)
14
Requirements for FiresFuel
Oxygen Ignition
Safe Design
Keep the Air Out AIR
![Page 15: 3-6 NCG Collection and Incineration - · PDF fileNCG Collection and Incineration Ben Lin, ... System Design 5. NCG Equipment 6. ... Normally chevron demisters with vanes](https://reader031.fdocuments.in/reader031/viewer/2022013014/5aa30c2f7f8b9a1f6d8e0bdd/html5/thumbnails/15.jpg)
15
Eliminate Ignition Sources
FANS
TURPENTINE
WELDING
4. System Design
![Page 16: 3-6 NCG Collection and Incineration - · PDF fileNCG Collection and Incineration Ben Lin, ... System Design 5. NCG Equipment 6. ... Normally chevron demisters with vanes](https://reader031.fdocuments.in/reader031/viewer/2022013014/5aa30c2f7f8b9a1f6d8e0bdd/html5/thumbnails/16.jpg)
16
CNCG Volumes
1.3 - 5.250 - 200Evaporator Hotwell
1.0 - 2.0 40 - 80Turpentine System
3.9 - 7.7 150 - 300Continuous digester
2.6 - 5.2100 - 200Batch digester
m3/tonneft3/tonSource
Continuous NCG Collection
SealedSource
PressureVacuumDevice
Vent
FlameArrester
To Ejector
OverflowLoop Seal
![Page 17: 3-6 NCG Collection and Incineration - · PDF fileNCG Collection and Incineration Ben Lin, ... System Design 5. NCG Equipment 6. ... Normally chevron demisters with vanes](https://reader031.fdocuments.in/reader031/viewer/2022013014/5aa30c2f7f8b9a1f6d8e0bdd/html5/thumbnails/17.jpg)
17
Blow Gas Collection
BlowSteam
Accumulator
PrimaryCondenser Pressure
Control
SecondaryCondenser
Vent
PadSteam
To Ejectors
Batch Digesters
Blow Steam CondensersMust Work Properly
![Page 18: 3-6 NCG Collection and Incineration - · PDF fileNCG Collection and Incineration Ben Lin, ... System Design 5. NCG Equipment 6. ... Normally chevron demisters with vanes](https://reader031.fdocuments.in/reader031/viewer/2022013014/5aa30c2f7f8b9a1f6d8e0bdd/html5/thumbnails/18.jpg)
18
NCG Collection
Steam Ejectors
PC
PC
FromBatch
FromContinuous
Vent
MistEliminator
PurgeSteam
FlameArrester
Nozzle
KilnorBoiler
Continuous and
Batch NCG Sources
MUST be separated
![Page 19: 3-6 NCG Collection and Incineration - · PDF fileNCG Collection and Incineration Ben Lin, ... System Design 5. NCG Equipment 6. ... Normally chevron demisters with vanes](https://reader031.fdocuments.in/reader031/viewer/2022013014/5aa30c2f7f8b9a1f6d8e0bdd/html5/thumbnails/19.jpg)
19
Explosive Range of NCG
% TRS
5
10
15
20
0 10020 40 60 80
%O
xyge
n Effects of Steam Flow..
![Page 20: 3-6 NCG Collection and Incineration - · PDF fileNCG Collection and Incineration Ben Lin, ... System Design 5. NCG Equipment 6. ... Normally chevron demisters with vanes](https://reader031.fdocuments.in/reader031/viewer/2022013014/5aa30c2f7f8b9a1f6d8e0bdd/html5/thumbnails/20.jpg)
20
MURPHY’S LAW
If anything CAN possibly go wrong,
sooner or later,
it WILL go wrong
Levels of Protection
1. Keep Air Out
2. Eliminate Ignition Sources
3. Line Protection- Flame Arresters- Rupture Discs
![Page 21: 3-6 NCG Collection and Incineration - · PDF fileNCG Collection and Incineration Ben Lin, ... System Design 5. NCG Equipment 6. ... Normally chevron demisters with vanes](https://reader031.fdocuments.in/reader031/viewer/2022013014/5aa30c2f7f8b9a1f6d8e0bdd/html5/thumbnails/21.jpg)
21
5. NCG Equipment
NCG Equipment
Flame ArrestersPressure vacuum reliefRupture discsMist eliminatorSteam ejectorInjection nozzlesControl / divert valves
![Page 22: 3-6 NCG Collection and Incineration - · PDF fileNCG Collection and Incineration Ben Lin, ... System Design 5. NCG Equipment 6. ... Normally chevron demisters with vanes](https://reader031.fdocuments.in/reader031/viewer/2022013014/5aa30c2f7f8b9a1f6d8e0bdd/html5/thumbnails/22.jpg)
22
Flame Arresters
In-line devices designed to protect against flame propagation or burn-back
Located at each source and at each incineration point
![Page 23: 3-6 NCG Collection and Incineration - · PDF fileNCG Collection and Incineration Ben Lin, ... System Design 5. NCG Equipment 6. ... Normally chevron demisters with vanes](https://reader031.fdocuments.in/reader031/viewer/2022013014/5aa30c2f7f8b9a1f6d8e0bdd/html5/thumbnails/23.jpg)
23
Flame Arresters
Dense corrugated pack acts as heat sink to decrease flame temperature below ignition point
All stainless steel construction
Center pack bolted between flanges for removal
![Page 24: 3-6 NCG Collection and Incineration - · PDF fileNCG Collection and Incineration Ben Lin, ... System Design 5. NCG Equipment 6. ... Normally chevron demisters with vanes](https://reader031.fdocuments.in/reader031/viewer/2022013014/5aa30c2f7f8b9a1f6d8e0bdd/html5/thumbnails/24.jpg)
24
![Page 25: 3-6 NCG Collection and Incineration - · PDF fileNCG Collection and Incineration Ben Lin, ... System Design 5. NCG Equipment 6. ... Normally chevron demisters with vanes](https://reader031.fdocuments.in/reader031/viewer/2022013014/5aa30c2f7f8b9a1f6d8e0bdd/html5/thumbnails/25.jpg)
25
Pressure/ Vacuum Relief
Protect source vessel from excessive pressure and/or vacuum
Prevent air ingress in CNCG system
Mechanical or water-seal PVB
Pressure/vacuum breaker
![Page 26: 3-6 NCG Collection and Incineration - · PDF fileNCG Collection and Incineration Ben Lin, ... System Design 5. NCG Equipment 6. ... Normally chevron demisters with vanes](https://reader031.fdocuments.in/reader031/viewer/2022013014/5aa30c2f7f8b9a1f6d8e0bdd/html5/thumbnails/26.jpg)
26
Rupture Discs
Protect NCG line against overpressure
Carbon (graphite) or stainless steel
Full line size
Located at 100 to 400 foot intervals
Vent lines directed outdoors
May be monitored
![Page 27: 3-6 NCG Collection and Incineration - · PDF fileNCG Collection and Incineration Ben Lin, ... System Design 5. NCG Equipment 6. ... Normally chevron demisters with vanes](https://reader031.fdocuments.in/reader031/viewer/2022013014/5aa30c2f7f8b9a1f6d8e0bdd/html5/thumbnails/27.jpg)
27
Rupture Disc
Mist Eliminator
Removes water droplets before incineration
Normally chevron demisters with vanes
Horizontal flow units more efficient removes 99.5% of all droplets 10 microns or greater
Must drain properly
![Page 28: 3-6 NCG Collection and Incineration - · PDF fileNCG Collection and Incineration Ben Lin, ... System Design 5. NCG Equipment 6. ... Normally chevron demisters with vanes](https://reader031.fdocuments.in/reader031/viewer/2022013014/5aa30c2f7f8b9a1f6d8e0bdd/html5/thumbnails/28.jpg)
28
Mist Eliminator
![Page 29: 3-6 NCG Collection and Incineration - · PDF fileNCG Collection and Incineration Ben Lin, ... System Design 5. NCG Equipment 6. ... Normally chevron demisters with vanes](https://reader031.fdocuments.in/reader031/viewer/2022013014/5aa30c2f7f8b9a1f6d8e0bdd/html5/thumbnails/29.jpg)
29
Steam Ejector
Type of compressor using kinetic energy created by expanding a motive fluid (steam) to entrain and compress a second gas stream (NCG)
No moving parts
As steam passes through nozzle, a vacuum is created at the vapour inlet, pulling the NCG through the ejector
Steam Ejector
Steam expands through a nozzle, converting pressure to velocity energy
Steam contacts NCG in the suction chamber
Mixture enters diffuser, where velocity is reconverted to pressure at ejector discharge
![Page 30: 3-6 NCG Collection and Incineration - · PDF fileNCG Collection and Incineration Ben Lin, ... System Design 5. NCG Equipment 6. ... Normally chevron demisters with vanes](https://reader031.fdocuments.in/reader031/viewer/2022013014/5aa30c2f7f8b9a1f6d8e0bdd/html5/thumbnails/30.jpg)
30
Injection Nozzle
Delivers NCG into incineration point
Not a burner
Combination nozzle with separate annuli for CNCG, SOG, cooling media
Cooling with water or air
![Page 31: 3-6 NCG Collection and Incineration - · PDF fileNCG Collection and Incineration Ben Lin, ... System Design 5. NCG Equipment 6. ... Normally chevron demisters with vanes](https://reader031.fdocuments.in/reader031/viewer/2022013014/5aa30c2f7f8b9a1f6d8e0bdd/html5/thumbnails/31.jpg)
31
![Page 32: 3-6 NCG Collection and Incineration - · PDF fileNCG Collection and Incineration Ben Lin, ... System Design 5. NCG Equipment 6. ... Normally chevron demisters with vanes](https://reader031.fdocuments.in/reader031/viewer/2022013014/5aa30c2f7f8b9a1f6d8e0bdd/html5/thumbnails/32.jpg)
32
Scrubbing NCG
Alkaline scrubbing ahead of incineration can reduce impact on the kiln:– Reduced ring formation, increased
capacity
Impact on power boiler:– Reduced SO2 emissions, reduce corrosion
concerns
Reduces TRS During Venting
![Page 33: 3-6 NCG Collection and Incineration - · PDF fileNCG Collection and Incineration Ben Lin, ... System Design 5. NCG Equipment 6. ... Normally chevron demisters with vanes](https://reader031.fdocuments.in/reader031/viewer/2022013014/5aa30c2f7f8b9a1f6d8e0bdd/html5/thumbnails/33.jpg)
33
Scrubbing NCG
Alkaline Solution
White Liquor
Specialty Chemical
![Page 34: 3-6 NCG Collection and Incineration - · PDF fileNCG Collection and Incineration Ben Lin, ... System Design 5. NCG Equipment 6. ... Normally chevron demisters with vanes](https://reader031.fdocuments.in/reader031/viewer/2022013014/5aa30c2f7f8b9a1f6d8e0bdd/html5/thumbnails/34.jpg)
34
6. NCG Incineration
Minimum Conditionsfor Burning NCG
Temperature 1600 °F (870 °C)Residence time 0.75 secondsExcess oxygen 3 - 4 %
![Page 35: 3-6 NCG Collection and Incineration - · PDF fileNCG Collection and Incineration Ben Lin, ... System Design 5. NCG Equipment 6. ... Normally chevron demisters with vanes](https://reader031.fdocuments.in/reader031/viewer/2022013014/5aa30c2f7f8b9a1f6d8e0bdd/html5/thumbnails/35.jpg)
35
Equipment for Burning NCG
Lime Kiln
Power (Bark) Boiler
Recovery Boiler
Incinerator
Lime Kiln
AdvantagesAdvantages
DisadvantagesDisadvantages
• Traditional• Recovers SO2
• Inefficient• Ring Formation
![Page 36: 3-6 NCG Collection and Incineration - · PDF fileNCG Collection and Incineration Ben Lin, ... System Design 5. NCG Equipment 6. ... Normally chevron demisters with vanes](https://reader031.fdocuments.in/reader031/viewer/2022013014/5aa30c2f7f8b9a1f6d8e0bdd/html5/thumbnails/36.jpg)
36
0
1
2
3
4
10 20 30 40 50TRS ppm
%O
xyge
n
TRS Emissions
Lime Kiln
![Page 37: 3-6 NCG Collection and Incineration - · PDF fileNCG Collection and Incineration Ben Lin, ... System Design 5. NCG Equipment 6. ... Normally chevron demisters with vanes](https://reader031.fdocuments.in/reader031/viewer/2022013014/5aa30c2f7f8b9a1f6d8e0bdd/html5/thumbnails/37.jpg)
37
Power Boilers
AdvantagesAdvantages
DisadvantagesDisadvantages
• Easiest
• Increased SO2• Corrosion
Power Boilers
Ash from Coal and Bark Absorbs SO2
![Page 38: 3-6 NCG Collection and Incineration - · PDF fileNCG Collection and Incineration Ben Lin, ... System Design 5. NCG Equipment 6. ... Normally chevron demisters with vanes](https://reader031.fdocuments.in/reader031/viewer/2022013014/5aa30c2f7f8b9a1f6d8e0bdd/html5/thumbnails/38.jpg)
38
Recovery Boiler
AdvantagesAdvantages
DisadvantagesDisadvantages
• Theoretically Best• Recovers Sulfur
• Adds complexity to boiler operation
Recovery Boiler
![Page 39: 3-6 NCG Collection and Incineration - · PDF fileNCG Collection and Incineration Ben Lin, ... System Design 5. NCG Equipment 6. ... Normally chevron demisters with vanes](https://reader031.fdocuments.in/reader031/viewer/2022013014/5aa30c2f7f8b9a1f6d8e0bdd/html5/thumbnails/39.jpg)
39
Recovery Boiler
H2S converted to SO2 in combustionSO2 is further converted to Na2SO4
Captured as sodium dust fumeRecovered as Na2S in smelt
Incinerator
AdvantagesAdvantages
DisadvantagesDisadvantages
• Least Risk
• Expen$ive• SO2 Emission• Another Stack
![Page 40: 3-6 NCG Collection and Incineration - · PDF fileNCG Collection and Incineration Ben Lin, ... System Design 5. NCG Equipment 6. ... Normally chevron demisters with vanes](https://reader031.fdocuments.in/reader031/viewer/2022013014/5aa30c2f7f8b9a1f6d8e0bdd/html5/thumbnails/40.jpg)
40
Other Considerations
Bigger is better
Uptime
Distance
Politics
![Page 41: 3-6 NCG Collection and Incineration - · PDF fileNCG Collection and Incineration Ben Lin, ... System Design 5. NCG Equipment 6. ... Normally chevron demisters with vanes](https://reader031.fdocuments.in/reader031/viewer/2022013014/5aa30c2f7f8b9a1f6d8e0bdd/html5/thumbnails/41.jpg)
41
Cluster Rule
Requires 99% uptime
Downtime also allowed for “Startup, Shutdown and Malfunction”
All vents must be monitored
Conclusion
Safe, Reliable, andExplosion Free NCG
Systems are Possible