8/11/2019 2nd Floor Column civil
1/6
-
8/11/2019 2nd Floor Column civil
2/6
Elastic modulus, Zy(cm3) 1570
Plastic modulus, Sx(cm3) 4690
Area of section, A (cm2) 300
BS 5950-1: 2000
Web thickness, t = 18.5< 40 mm, py= 265 N/mm2
Flange thickness, T = 30.2 < 40 mm, py= 265 N/mm2
The parameter, Flange, b/T = 6.54 < 9 Class 1 PlasticWeb, d/t = 15.7 < Class 3 Semi compactHence, the section is categorized as semi compact.
Table 9
Table 11
Effective length
Assume partially restrained in direction at both ends
LEx= LEy= 0.85L = 2975 mm
Slenderness ()
Column curve
Rolled H-section (Thickness 40mm)
Buckling about x-axis >> Table 24, curve (b)
Buckling about y-axis >> Table 24, curve (c )
Table 23
-
8/11/2019 2nd Floor Column civil
3/6
Compressive strength
x-axis:
Py = 265 N/mm
2
Curve (b) >> pcx= 263 N/mm2
Y-axis:
= 29.17Px = 265 N/mm
2
Curve (c ) >> pcy= 246 N/mm2
Get the minimum pc, so the pc= 246 N/mm2
Compression resistance (Pc)
Pc= Agpc
Pc= (300 x 102)(246 x 10-3) = 7380 KN > Fc[Safe!]
Overall buckling check
Since, Mx= 0, My= 4.72 KNm,
[]
For External column
Axial
The maximum axial load, Fc= (2025.99) + (572.77 + 31.68 + 338.94) + (60 x 3.5 x
10-2) = 2971.48 KN
Pc= Agpc, Assume pc= 150 N/mm2 and Pc= 2971.48 KN
-
8/11/2019 2nd Floor Column civil
4/6
2971.48 = Agx 150
Ag= 198.10 cm2
Use UC 254 x 254 x 167
Nominal moments
Mx= 0 (the loads are balanced about x-x axis)
My= [572.77 x (100 + t/2)]/2
= [572.77 x (100 + 19.2/2)]/2 = 31.39 KNm
Element UC 254 x 254 x 167
Depth of section, D (mm) 289.1
Web thickness, t (mm) 19.2
Flange thickness, T (mm) 31.7
Ratio for buckling flange, b/T 4.17
Ratio for buckling web, d/t 10.4
Radius of gyration, rx(cm) 11.9
Radius of gyration, ry(cm) 6.79
Elastic modulus, Zy(cm3) 741
Plastic modulus, Sx(cm3) 2420
Area of section, A (cm2) 212
BS 5950-1: 2000
Web thickness, t = 19.2 < 40 mm, py= 265 N/mm2
Flange thickness, T = 31.7 < 40 mm, py= 265 N/mm2
The parameter,
Table 9
Table 11
-
8/11/2019 2nd Floor Column civil
5/6
Flange, b/T = 4.17 < 9 Class 1 PlasticWeb, d/t = 10.4 < Class 3 Semi compactHence, the section is categorized as semi compact.
Effective length
Assume partially restrained in direction at both ends
LEx= LEy= 0.85L = 2975 mm
Slenderness ()
Column curve
Rolled H-section (Thickness 40mm)
Buckling about x-axis >> Table 24, curve (b)
Buckling about y-axis >> Table 24, curve (c )
Compressive strength
x-axis:
Py = 265 N/mm
2
Curve (b) >> pcx= 258 N/mm2
Y-axis:
= 43.81Px = 265 N/mm
2
Curve (c ) >> pcy= 237 N/mm2
Get the minimum pc, so the pc= 237 N/mm2
Table 23
-
8/11/2019 2nd Floor Column civil
6/6
Compression resistance (Pc)
Pc= Agpc
Pc= (212 x 102)(237 x 10-3) = 5024.4 KN > F
c[Safe!]
Overall buckling check
Since, Mx= 0, My= 31.39 KNm,
[]