2nd Floor Column civil

download 2nd Floor Column civil

of 6

Transcript of 2nd Floor Column civil

  • 8/11/2019 2nd Floor Column civil

    1/6

  • 8/11/2019 2nd Floor Column civil

    2/6

    Elastic modulus, Zy(cm3) 1570

    Plastic modulus, Sx(cm3) 4690

    Area of section, A (cm2) 300

    BS 5950-1: 2000

    Web thickness, t = 18.5< 40 mm, py= 265 N/mm2

    Flange thickness, T = 30.2 < 40 mm, py= 265 N/mm2

    The parameter, Flange, b/T = 6.54 < 9 Class 1 PlasticWeb, d/t = 15.7 < Class 3 Semi compactHence, the section is categorized as semi compact.

    Table 9

    Table 11

    Effective length

    Assume partially restrained in direction at both ends

    LEx= LEy= 0.85L = 2975 mm

    Slenderness ()

    Column curve

    Rolled H-section (Thickness 40mm)

    Buckling about x-axis >> Table 24, curve (b)

    Buckling about y-axis >> Table 24, curve (c )

    Table 23

  • 8/11/2019 2nd Floor Column civil

    3/6

    Compressive strength

    x-axis:

    Py = 265 N/mm

    2

    Curve (b) >> pcx= 263 N/mm2

    Y-axis:

    = 29.17Px = 265 N/mm

    2

    Curve (c ) >> pcy= 246 N/mm2

    Get the minimum pc, so the pc= 246 N/mm2

    Compression resistance (Pc)

    Pc= Agpc

    Pc= (300 x 102)(246 x 10-3) = 7380 KN > Fc[Safe!]

    Overall buckling check

    Since, Mx= 0, My= 4.72 KNm,

    []

    For External column

    Axial

    The maximum axial load, Fc= (2025.99) + (572.77 + 31.68 + 338.94) + (60 x 3.5 x

    10-2) = 2971.48 KN

    Pc= Agpc, Assume pc= 150 N/mm2 and Pc= 2971.48 KN

  • 8/11/2019 2nd Floor Column civil

    4/6

    2971.48 = Agx 150

    Ag= 198.10 cm2

    Use UC 254 x 254 x 167

    Nominal moments

    Mx= 0 (the loads are balanced about x-x axis)

    My= [572.77 x (100 + t/2)]/2

    = [572.77 x (100 + 19.2/2)]/2 = 31.39 KNm

    Element UC 254 x 254 x 167

    Depth of section, D (mm) 289.1

    Web thickness, t (mm) 19.2

    Flange thickness, T (mm) 31.7

    Ratio for buckling flange, b/T 4.17

    Ratio for buckling web, d/t 10.4

    Radius of gyration, rx(cm) 11.9

    Radius of gyration, ry(cm) 6.79

    Elastic modulus, Zy(cm3) 741

    Plastic modulus, Sx(cm3) 2420

    Area of section, A (cm2) 212

    BS 5950-1: 2000

    Web thickness, t = 19.2 < 40 mm, py= 265 N/mm2

    Flange thickness, T = 31.7 < 40 mm, py= 265 N/mm2

    The parameter,

    Table 9

    Table 11

  • 8/11/2019 2nd Floor Column civil

    5/6

    Flange, b/T = 4.17 < 9 Class 1 PlasticWeb, d/t = 10.4 < Class 3 Semi compactHence, the section is categorized as semi compact.

    Effective length

    Assume partially restrained in direction at both ends

    LEx= LEy= 0.85L = 2975 mm

    Slenderness ()

    Column curve

    Rolled H-section (Thickness 40mm)

    Buckling about x-axis >> Table 24, curve (b)

    Buckling about y-axis >> Table 24, curve (c )

    Compressive strength

    x-axis:

    Py = 265 N/mm

    2

    Curve (b) >> pcx= 258 N/mm2

    Y-axis:

    = 43.81Px = 265 N/mm

    2

    Curve (c ) >> pcy= 237 N/mm2

    Get the minimum pc, so the pc= 237 N/mm2

    Table 23

  • 8/11/2019 2nd Floor Column civil

    6/6

    Compression resistance (Pc)

    Pc= Agpc

    Pc= (212 x 102)(237 x 10-3) = 5024.4 KN > F

    c[Safe!]

    Overall buckling check

    Since, Mx= 0, My= 31.39 KNm,

    []