267-2017 Add Nr18 revFINAL - wx.toronto.ca · Michael Pacholok, Chief Purchasing Officer and...

34
Michael Pacholok, Chief Purchasing Officer and Director Purchasing & Materials Management City Hall, 19th Floor, West 100 Queen Street West Toronto, Ontario M5H 2N2 Joanne Kehoe, Manager Construction Services November 8, 2017 Via Website Posting (34 pages) Addendum No. 18 TENDER No. 267-2017 Closing: 12:00 NOON (LOCAL TIME), November 29, 2017 For: the supply of all materials, equipment, labour and supervision necessary for the construction of the new Bessarion Community Centre. Please refer to the above Tender Call document in your possession and be advised of the following: 1.0 CLARIFICATIONS & REVISIONS: Section 4, Scope of Work: Please refer to Architectural Addendum A3 dated November 3, 2017 (218 pages or drawings total) which includes the following documents: i. Electrical Addendum E2 dated November 3, 2017 (33 pages + 26 sheets of AV Drawing Set); Part 1 of 3 (33 pages) issued herein; Part 2 of 3 of the Electrical Addendum E2 (20 drawing sheets) will be included in Addendum No. 19. Part 3 of 3 of the Electrical Addendum E2 (6 drawing sheets) will be included in Addendum No. 20. The complete architectural addendum and the associated sub-consultant addenda (i.e. addenda of the other disciplines) included in Architectural Addendum A3 are included in Addenda No. 13 through 20. Refer to these addenda and be governed accordingly. All other aspects of the Tender remain the same. Please attach this addendum to your RFT document and be governed accordingly. Bidders must acknowledge receipt of all addenda on the space provided on the Tender Call Cover Page as per the Process Terms and Conditions, Section 1, Item 8 - Addenda, of the Tender Call document. Should you have any questions regarding this addendum, please contact Mike Voelker at [email protected]. Yours truly, Joanne Kehoe, Manager, Construction Services Purchasing and Materials Management 1 of 34

Transcript of 267-2017 Add Nr18 revFINAL - wx.toronto.ca · Michael Pacholok, Chief Purchasing Officer and...

Page 1: 267-2017 Add Nr18 revFINAL - wx.toronto.ca · Michael Pacholok, Chief Purchasing Officer and Director Purchasing & Materials Management City Hall, 19th Floor, West 100 Queen Street

Michael Pacholok, Chief Purchasing Officer and Director

Purchasing & Materials Management City Hall, 19th Floor, West 100 Queen Street West Toronto, Ontario M5H 2N2

Joanne Kehoe, Manager Construction Services

November 8, 2017 Via Website Posting (34 pages)

Addendum No. 18

TENDER No. 267-2017 Closing: 12:00 NOON (LOCAL TIME), November 29, 2017

For: the supply of all materials, equipment, labour and supervision necessary for

the construction of the new Bessarion Community Centre.

Please refer to the above Tender Call document in your possession and be advised of the following:

1.0 CLARIFICATIONS & REVISIONS: Section 4, Scope of Work:

Please refer to Architectural Addendum A3 dated November 3, 2017 (218 pages or drawings total) which includes the following documents:

i. Electrical Addendum E2 dated November 3, 2017 (33 pages + 26 sheets of AV Drawing Set);

Part 1 of 3 (33 pages) issued herein;

Part 2 of 3 of the Electrical Addendum E2 (20 drawing sheets) will be included in Addendum No. 19.

Part 3 of 3 of the Electrical Addendum E2 (6 drawing sheets) will be included in Addendum No. 20.

The complete architectural addendum and the associated sub-consultant addenda (i.e. addenda of the other disciplines) included in Architectural Addendum A3 are included in Addenda No. 13 through 20. Refer to these addenda and be governed accordingly.

All other aspects of the Tender remain the same.

Please attach this addendum to your RFT document and be governed accordingly. Bidders must acknowledge receipt of all addenda on the space provided on the Tender Call Cover Page as per the Process Terms and Conditions, Section 1, Item 8 - Addenda, of the Tender Call document.

Should you have any questions regarding this addendum, please contact Mike Voelker at [email protected].

Yours truly,

Joanne Kehoe, Manager, Construction Services Purchasing and Materials Management

1 of 34

Page 2: 267-2017 Add Nr18 revFINAL - wx.toronto.ca · Michael Pacholok, Chief Purchasing Officer and Director Purchasing & Materials Management City Hall, 19th Floor, West 100 Queen Street

4211 Yonge Street Suite 500 Toronto Ontario M2P 2A9 416 487 8151 f 416 487 9104 smithandandersen.com

Victoria Vancouver Kelowna Calgary Edmonton Winnipeg London Toronto Ottawa Halifax

AD

DE

ND

UM

PROJECT NAME: BESSARION COMMUNITY CENTRE

COMPANY: MJM Architects

ATTENTION: Olga Pushkar

PROJECT NO.: 14327.000.E.001 DATE: 2017-11-03

ADDENDUM NO.: ADD-E-02 ISSUED BY: DureShana Sachwani

The following amendments are hereby made as part of the Contract Documents. The following revisions and/or additions shall be made to contract documents and the cost shall be included in the Tender Price.

1.0 SPECIFICATIONS

1.1 26 05 63 – Access Doors and Accessibility (Attached)

1.1.1 Replace specifications with the attached.

2.0 SCHEDULES

2.1 Fire Alarm Schedule (Attached)

2.1.1 Add fire alarm monitoring points for Emergency gas shutoff. Refer to attached schedule for details.

2.2 Loose Starter Schedule (Attached)

2.2.1 Remove all Pool Pumps from schedule, as the Pool contractor supplies all pool related starters.

2.2.2 Add starter for EF-L4-04 to schedule.

2.3 LP-P1XA (Attached)

2.3.1 Revise Circuit no. 18 ‘SPARE’ to read ‘Emergency gas shutoff’.

2.4 RP-1EC (Attached)

2.4.1 Revise Circuit no. 60 ‘FFH-01-02, 03’ to read ‘FC-01-01, 02’.

2.5 RP-2EC (Attached)

2.5.1 Revise Circuit no. 36 ‘Lobby G200 FFH-02-02’ to read ‘FC-02-01’.

2 of 34

Page 3: 267-2017 Add Nr18 revFINAL - wx.toronto.ca · Michael Pacholok, Chief Purchasing Officer and Director Purchasing & Materials Management City Hall, 19th Floor, West 100 Queen Street

2 ADDENDUM

2.6 RP-2ED (Attached)

2.6.1 Revise Circuit no. 38 ‘FFH-02-03’ to read ‘FC-02-02’.

2.7 RP-4EA (Attached)

2.7.1 Revise Circuit no. 28 ‘SPARE’ to read ‘EF-L4-04’.

2.8 RP-P1EB (Attached)

2.8.1 Revise Circuit no. 49 ‘Boiler Room (P119) DHWH-P1-02, 01 Control’ to read ‘SPARE’.

2.8.2 Add one(1) 20A-2 pole breaker at circuit 143, 145 for Heat tracing.

3.0 DRAWINGS

3.1 E100-SITE PLAN (Attached)

3.1.1 Add three (3) junction boxes for heat tracing as bubbled, feed from RP-P1EB.

3.2 E200-SINGLE LINE DIAGRAM (Attached)

3.2.1 Revised two (2) breaker sizes for P-PL-P2-05 and P-PL-P2-06 from 20A to 25A, as per coordination with mechanical. As bubbled.

3.2.2 Revised rating for P-PL-P2-07 from 5HP to 1.5HP, as bubbled.

3.2.3 Revised rating for P-PL-P2-08 from 5HP to 1.5HP, as bubbled.

3.2.4 Revised rating for P-PL-P2-09 from 2.7HP to 1.5HP, as bubbled.

3.2.5 Revised rating for P-PL-P2-10 from 2.7HP to 1.5HP, as bubbled.

3.3 E302B LEVEL P1-POWER AND SYSTEM (Attached)

3.3.1 Add one (1) junction box for Emergency gas shut off, as bubbled in Boiler Room P119, feed from LP-P1XA.

3.3.2 Delete two (2) direct connections for DHWH-P1-01 and 02 Controls, as bubbled Boiler Room P119.

3.4 E303A LEVEL 01-POWER AND SYSTEM (Attached)

3.4.1 Delete two (2) direct connections for FFH-01-02 and FFH-01-03 in TPA Vestibule G100A.

3.4.2 Add two (2) direct connections for FC-01-01 and FC-01-02 in TPA Vestibule G100A and Entrance Vestibule as bubbled, feed from RP-1EC.

3.5 E304A LEVEL 02-POWER AND SYSTEM (Attached)

3.5.1 Delete one (1) direct connection for FFH-02-01in Lobby G200.

3.5.2 Add one (1) direct connection for FC-02-01 in Lobby G200 as bubbled, feed from RP-2EC.

3 of 34

Page 4: 267-2017 Add Nr18 revFINAL - wx.toronto.ca · Michael Pacholok, Chief Purchasing Officer and Director Purchasing & Materials Management City Hall, 19th Floor, West 100 Queen Street

3 ADDENDUM

3.6 E304B LEVEL 02-POWER AND SYSTEM (Attached)

3.6.1 Delete one (1) direct connection for FFH-02-03 in Vestibule G201.

3.6.2 Add one (1) direct connection for FC-02-02 in Vestibule G201 as bubbled, feed from RP-2ED.

3.7 E305A LEVEL 03-POWER AND SYSTEM (Attached)

3.7.1 Delete ceiling mounted AV speakers and replaced with wall mounted AV speakers in Dance Studio R330 and Fitness Studio R329 as bubbled.

3.8 E403B LEVEL 01-LIGHTING (Attached)

3.8.1 Revise two (2) fixture type from recessed to wall mounted in Exit Stair D, as bubbled.

3.9 E500-PART PLANS AND DETAILS (Attached)

3.9.1 Add one (1) motor connection with starter for EF-L4-04 as bubbled in Room R406, detail 14/E500, feed from RP-4EA.

3.10 AV Drawing Package (Attached)

3.10.1 Refer to attached AV drawing package issued for infrastructure coordination only.

4.0 CLARIFICATION

4.1.1 Coordination with Mechanical Addendum ADD-M-02 dated 2017.10.27

4.1.2 Coordination with Architectural Drawings.

4.1.3 Provide AV drawings for infrastructure coordination.

END OF ELECTRICAL ADDENDUM

4 of 34

Page 5: 267-2017 Add Nr18 revFINAL - wx.toronto.ca · Michael Pacholok, Chief Purchasing Officer and Director Purchasing & Materials Management City Hall, 19th Floor, West 100 Queen Street

Bessarion Community Centre Section 26 05 63.00

100 Woodsy Park Lane, Toronto Access Doors and Accessibility

Project #14327.000.E.001 Page 1 of 2

November 3, 2017 Issued for ADD-E-03

1. General

1.1. WORK INCLUDED

1.1.1. Section 26 05 01.00 – GENERAL INSTRUCTIONS FOR ELECTRICAL SECTIONS.

1.1.2. Section 26 05 04.00 – SUBMITTALS/SHOP DRAWINGS.

1.2. SHOP DRAWINGS AND PRODUCT DATA

1.2.1. Submit Shop Drawings and product data in accordance with Section 26 05 04.00 – SUBMITTALS/SHOP DRAWINGS.

1.2.2. Submit drawings showing size, type and location of all access doors, for review, before installation.

2. Products

2.1. MATERIALS

2.1.1. Access doors shall be WB Doors WB RDW 410 Series. Coordinate with other trades on site. All access doors on site shall be from the same manufacturer.

2.1.2. Doors in solid walls shall be 14 U.S. gauge, prime painted steel door panel, rust resistant concealed hinges and screwdriver operated lock.

2.1.3. Doors in plaster partitions or ceiling shall be 16 US gauge, prime painted steel, concealed hinges and screwdriver operated lock.

2.1.4. Doors in drywall partitions or ceiling shall be20 US gauge, prime painted steel, concealed hinges and screwdriver operated lock.

2.1.5. Access doors in fire rated walls or ceilings shall be ULC labeled with insulated door panel, concealed hinge, self-closing, self-latching, and prime painted. Provide master key operated catch in areas accessible to the public.

2.1.6. All doors in tiled walls shall be 16 US gauge, stainless steel, type 304 with #4 satin finish, concealed hinges, wall frame and screw driver operated lock.

2.1.7. Minimum size of doors shall be 300 mm x 450 mm. Wherever possible 600 mm x 600 mm doors shall be used.

3. Execution

3.1. INSTALLATION

3.1.1. All parts of the installation requiring periodic maintenance shall be accessible. Wherever pull boxes, junction boxes and other appurtenances are concealed by building construction, access doors shall be furnished by this section and installed under the respective Trade Sections (i.e. masonry, plaster, drywall, tile, etc.). This section is responsible for the proper location of the access doors.

3.1.2. Wherever possible, items requiring access shall be located in easily accessible areas (i.e. exposed or T-bar ceilings).

3.1.3. Group items in order to minimize the number of access doors required.

5 of 34

Page 6: 267-2017 Add Nr18 revFINAL - wx.toronto.ca · Michael Pacholok, Chief Purchasing Officer and Director Purchasing & Materials Management City Hall, 19th Floor, West 100 Queen Street

Bessarion Community Centre Section 26 05 63.00

100 Woodsy Park Lane, Toronto Access Doors and Accessibility

Project #14327.000.E.001 Page 2 of 2

November 3, 2017 Issued for ADD-E-03

3.1.4. Each access door shall be installed to provide complete access to equipment for maintenance and servicing.

3.1.5. Make any changes to locations of access doors as directed by the Engineer’s Representative.

3.1.6. The final installed locations of all access doors shall be shown on the As-Built Record Drawings.

END OF SECTION

6 of 34

Page 7: 267-2017 Add Nr18 revFINAL - wx.toronto.ca · Michael Pacholok, Chief Purchasing Officer and Director Purchasing & Materials Management City Hall, 19th Floor, West 100 Queen Street

PROJECT NAME: Bessarion Community Centre

Project number: 14327.000.E.001Date: 2017.11.03

Description

Mech. Labels

AXX-0X X PARKING LEVEL P3 ZONE P03-01 DETECTION DEVICES

AXX-0X X PARKING LEVEL P2 ZONE P02-01 DETECTION DEVICES

AXX-0X X PARKING LEVEL P1 ZONE P01-01 DETECTION DEVICES

AXX-0X X LEVEL 01 ZONE L01-01 DETECTION DEVICES

AXX-0X X LEVEL 01 ZONE L01-02 DETECTION DEVICES

AXX-0X X LEVEL 02 ZONE L02-01 DETECTION DEVICES

AXX-0X X LEVEL 02 ZONE L02-02 DETECTION DEVICES

AXX-0X X LEVEL 03 ZONE L03-01 DETECTION DEVICES

AXX-0X X LEVEL 03 ZONE L03-02 DETECTION DEVICES

AXX-0X X LEVEL 04 ZONE L04-01 DETECTION DEVICES

AXX-0X X LEVEL 04 ZONE L04-02 DETECTION DEVICES

AXX-0X X PARKING LEVEL P1 DRY SPRINKLER VALVE ACV#1 SPRINKLER DEVICE

AXX-0X X PARKING LEVEL P2 DRY SPRINKLER VALVE ACV#2 SPRINKLER DEVICE

AXX-0X X PARKING LEVEL P3 DRY SPRINKLER VALVE ACV#3 SPRINKLER DEVICE

AXX-0X X ABOVE GRADE RISER ALARM CHECK VALVE ACV#4 SPRINKLER DEVICE

AXX-0X X PARKING LEVEL P3 FLOW SWITCH FS-P02-01 SPRINKLER DEVICE

AXX-0X X PARKING LEVEL P2 FLOW SWITCH FS-P02-02 SPRINKLER DEVICE

AXX-0X X PARKING LEVEL P1 FLOW SWITCH FS-P02-03 SPRINKLER DEVICE

AXX-0X X ABOVE GRADE RISER FLOW SWITCH FS-P02-04 SPRINKLER DEVICE

AXX-0X X LEVEL 01 AND LOBBY STAIRS SPRINKLER FLOW SWITCHFS-L01-01 SPRINKLER DEVICE

AXX-0X X LEVEL 01 WINDOW SPRINKLER FLOW SWITCH FS-L01-02 SPRINKLER DEVICE

AXX-0X X LEVEL 02 SPRINKLER FLOW SWITCH FS-L02-01 SPRINKLER DEVICE

AXX-0X X LEVEL 02 WINDOW SPRINKLER FLOW SWITCH FS-L02-02 SPRINKLER DEVICE

AXX-0X X LEVEL 03 SPRINKLER FLOW SWITCH FS-L03-01 SPRINKLER DEVICE

AXX-0X X LEVEL 03 WINDOW SPRINKLER FLOW SWITCH FS-L03-02 SPRINKLER DEVICE

AXX-0X X LEVEL 04 SPRINKLER FLOW SWITCH FS-L04-01 SPRINKLER DEVICE

AXX-0X X LEVEL 04 WINDOW SPRINKLER FLOW SWITCH FS-L04-02 SPRINKLER DEVICE

AXX-0X X ABOVE GRADE RISER FLOW SWITCH FS-P02-04 SPRINKLER DEVICE

AXX-0X X MAIN ELECTRICAL ROOM (P115) DETECTION DEVICES

AXX-0X X STAIR A ABOVE GRADE DETECTION DEVICES

AXX-0X X STAIR A BELOW GRADE DETECTION DEVICES

AXX-0X X STAIR B ABOVE GRADE DETECTION DEVICES

AXX-0X X STAIR B BELOW GRADE DETECTION DEVICES

AXX-0X X STAIR C ABOVE GRADE DETECTION DEVICES

AXX-0X X STAIR C BELOW GRADE DETECTION DEVICES

AXX-0X X STAIR D ABOVE GRADE DETECTION DEVICES

AXX-0X X STAIR D BELOW GRADE DETECTION DEVICES

AXX-0X X STAIR E DETECTION DEVICES

AXX-0X X STAIR F DETECTION DEVICES

AXX-0X X TPA ELEVATOR #1 PIT DETECTOR DETECTION DEVICES

AXX-0X X TPA ELEVATOR #1 TOP OF SHAFT DETECTOR DETECTION DEVICES

AXX-0X X TPA ELEVATOR #2 PIT DETECTOR DETECTION DEVICES

AXX-0X X TPA ELEVATOR #2 TOP OF SHAFT DETECTOR DETECTION DEVICES

AXX-0X X BCC ELEVATOR #3 PIT DETECTOR DETECTION DEVICES

AXX-0X X BCC ELEVATOR #3 TOP OF SHAFT DETECTOR DETECTION DEVICES

AXX-0X X BCC ELEVATOR #4 PIT DETECTOR DETECTION DEVICES

AXX-0X X BCC ELEVATOR #4 TOP OF SHAFT DETECTOR DETECTION DEVICES

AXX-0X X TPA ELEVATOR MACHINE ROOM DETECTION DEVICES

AXX-0X X BCC ELEVATOR MACHINE ROOM DETECTION DEVICES

AXX-0X X TPA MAIN ELECT ROOM (P116) DETECTION DEVICES

AXX-0X X MAIN COMMUNICATIONS ROOM (P118) DETECTION DEVICES

AXX-0X X LIBRARY ELECT ROOM - SOUTH (L117) DETECTION DEVICES

AXX-0X X LIBRARY COMMS ROOM - SOUTH (L118) DETECTION DEVICES

AXX-0X X ELECTRICAL CLOSET - NORTH (A120) DETECTION DEVICES

AXX-0X X ELECTRICAL AND COMMUNICATION ROOM - CENTRE (G102) DETECTION DEVICES

AXX-0X X GENERATOR ROOM (G122) DETECTION DEVICES

FIRE ALARM SCHEDULEZ

on

e N

o.

Ala

rm

Su

pe

rvis

ory

Co

ntr

ol/M

on

ito

r

Annunciator Label

Alarm Zones

11/2/2017 1 of 5

7 of 34

Page 8: 267-2017 Add Nr18 revFINAL - wx.toronto.ca · Michael Pacholok, Chief Purchasing Officer and Director Purchasing & Materials Management City Hall, 19th Floor, West 100 Queen Street

PROJECT NAME: Bessarion Community Centre

Project number: 14327.000.E.001Date: 2017.11.03

Description

Mech. Labels

FIRE ALARM SCHEDULEZ

on

e N

o.

Ala

rm

Su

pe

rvis

ory

Co

ntr

ol/M

on

ito

r

Annunciator Label

Alarm ZonesAXX-0X X ELECT SWICTH VAULT ROOM (G113) DETECTION DEVICES

AXX-0X X CHILD CARE ELECT. AND COMMS ROOM - SOUTH (C210) DETECTION DEVICES

AXX-0X X CHILD CARE COMMS AND SECURITY ROOM - CENTRE (C204A) DETECTION DEVICES

AXX-0X X ELEC AND COMMS ROOM - CENTRE (R202) DETECTION DEVICES

AXX-0X X ELECTRICAL CLOSET - NORTH (R211) DETECTION DEVICES

AXX-0X X ELECT ROOM - CENTER (R406) DETECTION DEVICES

AXX-0X X ELECTRICAL ROOM - SOUTH (R332) DETECTION DEVICES

AXX-0X X ELECTRICAL CLOSET - CENTRE (R301A) DETECTION DEVICES

AXX-0X X COMMUNICATIONS ROOM - CENTRE (R301B) DETECTION DEVICES

AXX-0X X ELECTRICAL CLOSET - NORTH (R311) DETECTION DEVICES

AXX-0X X RTU-03 DUCT SMOKE DETECTOR RTU-03 DETECTION DEVICES

AXX-0X X RTU-05 DUCT SMOKE DETECTOR RTU-05 DETECTION DEVICES

AXX-0X X AHU-03 DUCT SMOKE DETECTOR AHU-03 DETECTION DEVICES

SPARE

SPARE

SVXX-0X X INCOMING INLET SHUT OFF VALVE SV-P02.01 SPRINKLER DEVICE

SVXX-0X X INCOMING OUTLET SHUT OFF VALVE SV-P02.02 SPRINKLER DEVICE

SVXX-0X X PARKING LEVEL P3 SUPERVISED VALVE (DRY) SV-P02.03 SPRINKLER DEVICE

SVXX-0X X PARKING LEVEL P3 SUPERVISED VALVE (DRY) SV-P02.04 SPRINKLER DEVICE

SVXX-0X X PARKING LEVEL P3 SUPERVISED VALVE (DRY) SV-P02.05 SPRINKLER DEVICE

SVXX-0X X ABOVE GRADE RISER SUPERVISED VALVE SV-P02.06 SPRINKLER DEVICE

SVXX-0X X FIRE PUMP ASSEMBLY BY-PASS INLET SV-P02.07 SPRINKLER DEVICE

SVXX-0X X FIRE PUMP ASSEMBLY BY-PASS OUTLET SV-P02.08 SPRINKLER DEVICE

SVXX-0X X FIRE PUMP INLET SHUT OFF VALVE SV-P02.09 SPRINKLER DEVICE

SVXX-0X X FIRE PUMP OUTLET SHUT OFF VALVE SV-P02.10 SPRINKLER DEVICE

SVXX-0X X JOCKEY PUMP INLET SHUT OFF VALVE SV-P02.11 SPRINKLER DEVICE

SVXX-0X X JOCKEY PUMP OUTLET SHUT OFF VALVE SV-P02.12 SPRINKLER DEVICE

SVXX-0X X FIRE STAND PIPE SIAMESE CONNECTION SV-P02.13 SPRINKLER DEVICE

SVXX-0X X FIRE STANDPIPE RISER (NORTH) SV-P02.14 SPRINKLER DEVICE

SVXX-0X X LEVEL 1 AND LOBBY STAIRS SUPERVISED VALVE SV-L01.01 SPRINKLER DEVICE

SVXX-0X X LEVEL 1 WINDOW SPRNK SUPERVISED VALVE SV-L01.02 SPRINKLER DEVICE

SVXX-0X X FIRE STANDPIPE RISER (NORTH) SV-L01.03 SPRINKLER DEVICE

SVXX-0X X FIRE STANDPIPE RISER (STAIR D) SV-L01.04 SPRINKLER DEVICE

SVXX-0X X FIRE STANDPIPE RISER (CENTRAL) SV-L01.05 SPRINKLER DEVICE

SVXX-0X X FIRE STANDPIPE RISER (CENTRAL) SV-L01.06 SPRINKLER DEVICE

SVXX-0X X FIRE STANDPIPE RISER (CENTRAL) SV-L01.07 SPRINKLER DEVICE

SVXX-0X X FIRE STANDPIPE RISER (SOUTH) SV-L01.08 SPRINKLER DEVICE

SVXX-0X X FIRE STANDPIPE RISER (SOUTH - STAIR B) SV-L01.09 SPRINKLER DEVICE

SVXX-0X X LEVEL 2 ZONE SV-L02.01 SPRINKLER DEVICE

SVXX-0X X LEVEL 2 WINDOW SPRINKLER ZONE SV-L02.02 SPRINKLER DEVICE

Supervisory Zones

11/2/2017 2 of 5

8 of 34

Page 9: 267-2017 Add Nr18 revFINAL - wx.toronto.ca · Michael Pacholok, Chief Purchasing Officer and Director Purchasing & Materials Management City Hall, 19th Floor, West 100 Queen Street

PROJECT NAME: Bessarion Community Centre

Project number: 14327.000.E.001Date: 2017.11.03

Description

Mech. Labels

FIRE ALARM SCHEDULEZ

on

e N

o.

Ala

rm

Su

pe

rvis

ory

Co

ntr

ol/M

on

ito

r

Annunciator Label

Alarm ZonesSVXX-0X X LEVEL 3 ZONE SV-L03.01 SPRINKLER DEVICE

SVXX-0X X LEVEL 3 WINDOW SPRINKLER ZONE SV-L03.02 SPRINKLER DEVICE

SVXX-0X X LEVEL 4 ZONE SV-L04.01 SPRINKLER DEVICE

SVXX-0X X LEVEL 4 WINDOW SPRINKLER ZONE SV-L04.02 SPRINKLER DEVICE

SVXX-0X X PARKING LEVEL P1 DRY SPRKR LOW PRESSURE PS-XX.0X SUPERVISED DEVICE

SVXX-0X X PARKING LEVEL P2 DRY SPRKR LOW PRESSURE PS-XX.0X SUPERVISED DEVICE

SVXX-0X X PARKING LEVEL P3 DRY SPRKR LOW PRESSURE PS-XX.0X SUPERVISED DEVICE

SVXX-0X X SPRINKLER ROOM LOW TEMPERATURE SENSOR SUPERVISED DEVICE

SVXX-0X X JOCKEY PUMP LOSS OF POWER SUPERVISED DEVICE

SVXX-0X X P2 DRY SPRINKLER COMPRESSOR LOSS OF POWER SUPERVISED DEVICE

SVXX-0X X FIRE PUMP RUNNING SUPERVISED DEVICE

SVXX-0X X FIRE PUMP LOSS OF POWER SUPERVISED DEVICE

SVXX-0X X FIRE PUMP LOSS OF PHASE SUPERVISED DEVICE

SVXX-0X X FIRE PUMP PHASE REVERSAL SUPERVISED DEVICE

SVXX-0X X FIRE PUMP CONTROLLER CONNECTED TO ALT. SOURCE SUPERVISED DEVICE

SVXX-0X X GENERATOR #1 RUNNING SUPERVISED DEVICE

SVXX-0X X GENERATOR #1 TROUBLE SUPERVISED DEVICE

SVXX-0X X GENERATOR #2 RUNNING SUPERVISED DEVICE

SVXX-0X X GENERATOR #2 TROUBLE SUPERVISED DEVICE

SVXX-0X X MAIN FUEL TANK LOW FUEL SUPERVISED DEVICE

SVXX-0X X NATURAL GAS GENSET PRV VALVE SUPERVISED DEVICE

SVXX-0X X NATURAL GAS INCOMING PRV VALVE SUPERVISED DEVICE

SVXX-0X X CARBON MONOXIDE DETECTORS SUPERVISED DEVICE

SVXX-0X X CONNECTED BUILDING FIRE ALARM STATUS SUPERVISED DEVICE

SVXX-0X X HEAT TRACING (Sprinkler lines) SUPERVISED DEVICE

SVXX-0X X HEAT TRACING (Exterior Exit paths) SUPERVISED DEVICE

SVXX-0X X HEAT TRACING (Exterior Exit paths) SUPERVISED DEVICE

SVXX-0X X HEAT TRACING (Exterior Exit paths) SUPERVISED DEVICE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

C-XX X AV SYSTEM SHUTDOWN INTERFACE (TO ALL SYSTEMS) Aux. Contact (Control)

C-XX X SIGNAL TO BAS Aux. Contact (Control)

C-XX X SIGNAL TO FIRE DEPARTMENT Aux. Contact (Control)

C-XX X LIGHTING CONTROL INTERFACE Aux. Contact (Control)

C-XX X SECURITY MASTER KEY SWITCH Aux. Contact (Control)

C-XX X HEAT TRACE MONITORING (ALL SPRINKLER PIPES) Aux. Contact (Monitor)

C-XX X HEAT TRACE MONITORING (EXTERIOR WALKWAYS) Aux. Contact (Monitor)

C-XX X HEAT TRACE MONITORING (PARKING RAMP) Aux. Contact (Monitor)

C-XX X FIRE ALARM SHUT DOWN AHU-01 Aux. Contact (Control)

C-XX X FIRE ALARM SHUT DOWN SF-AHU-01 Aux. Contact (Control)

C-XX X FIRE ALARM SHUT DOWN RF-AHU-01 Aux. Contact (Control)

C-XX X FIRE ALARM SHUT DOWN AHU-02 Aux. Contact (Control)

C-XX X FIRE ALARM SHUT DOWN AHU-03 Aux. Contact (Control)

C-XX X FIRE ALARM SHUT DOWN SF-AHU-03 Aux. Contact (Control)

C-XX X FIRE ALARM SHUT DOWN RF-AHU-03 Aux. Contact (Control)

C-XX X FIRE ALARM SHUT DOWN AHU-04 Aux. Contact (Control)

C-XX X FIRE ALARM SHUT DOWN SF-AHU-04 Aux. Contact (Control)

C-XX X FIRE ALARM SHUT DOWN RF-AHU-04 Aux. Contact (Control)

C-XX X FIRE ALARM SHUT DOWN RTU-01 Aux. Contact (Control)

C-XX X FIRE ALARM SHUT DOWN RTU-02 Aux. Contact (Control)

Auxiliary Control/Monitoring points

11/2/2017 3 of 5

9 of 34

Page 10: 267-2017 Add Nr18 revFINAL - wx.toronto.ca · Michael Pacholok, Chief Purchasing Officer and Director Purchasing & Materials Management City Hall, 19th Floor, West 100 Queen Street

PROJECT NAME: Bessarion Community Centre

Project number: 14327.000.E.001Date: 2017.11.03

Description

Mech. Labels

FIRE ALARM SCHEDULEZ

on

e N

o.

Ala

rm

Su

pe

rvis

ory

Co

ntr

ol/M

on

ito

r

Annunciator Label

Alarm ZonesC-XX X FIRE ALARM SHUT DOWN RTU-03 Aux. Contact (Control)

C-XX X FIRE ALARM SHUT DOWN RTU-04 Aux. Contact (Control)

C-XX X FIRE ALARM SHUT DOWN RTU-05 Aux. Contact (Control)

C-XX X FIRE ALARM SHUT DOWN RTU-06 Aux. Contact (Control)

C-XX X FIRE ALARM SHUT DOWN - ALL POOL PUMPS Aux. Contact (Control)

C-XX X FIRE ALARM START UP SF-P3-02 Aux. Contact (Control)

C-XX X FIRE ALARM START UP SF-P2-02 Aux. Contact (Control)

C-XX X FIRE ALARM START UP SF-P2-01 Aux. Contact (Control)

C-XX X TPA ELEVATOR #1 CONTROL FA MACHINE ROOM STATUS Aux. Contact (Control)

C-XX X TPA ELEVATOR #1 CONTROL FA RECALL FLOOR STATUS Aux. Contact (Control)

C-XX X TPA ELEVATOR #1 CONTROL FA ALT RECALL FLOOR STATUS Aux. Contact (Control)

C-XX X TPA ELEVATOR #2 CONTROL FA MACHINE ROOM STATUS Aux. Contact (Control)

C-XX X TPA ELEVATOR #2 CONTROL FA RECALL FLOOR STATUS Aux. Contact (Control)

C-XX X TPA ELEVATOR #2 CONTROL FA ALT RECALL FLOOR STATUS Aux. Contact (Control)

C-XX X BCC ELEVATOR #3 CONTROL FA MACHINE ROOM STATUS Aux. Contact (Control)

C-XX X BCC ELEVATOR #3 CONTROL FA RECALL FLOOR STATUS Aux. Contact (Control)

C-XX X BCC ELEVATOR #3 CONTROL FA ALT RECALL FLOOR STATUS Aux. Contact (Control)

C-XX X BCC ELEVATOR #4 CONTROL FA MACHINE ROOM STATUS Aux. Contact (Control)

C-XX X BCC ELEVATOR #4 CONTROL FA RECALL FLOOR STATUS Aux. Contact (Control)

C-XX X BCC ELEVATOR #4 CONTROL ALT RECALL FLOOR STATUS Aux. Contact (Control)

C-XX X TPA ELEVATOR #1 FA TOP OF SHAFT STATUS Aux. Contact (Control)

C-XX X TPA ELEVATOR #1 FA PIT DETECTOR STATUS Aux. Contact (Control)

C-XX X TPA ELEVATOR #2 FA TOP OF SHAFT STATUS Aux. Contact (Control)

C-XX X TPA ELEVATOR #2 FA PIT DETECTOR STATUS Aux. Contact (Control)

C-XX X BCC ELEVATOR #3 FA TOP OF SHAFT STATUS Aux. Contact (Control)

C-XX X BCC ELEVATOR #3 FA PIT DETECTOR STATUS Aux. Contact (Control)

C-XX X BCC ELEVATOR #4 FA TOP OF SHAFT STATUS Aux. Contact (Control)

C-XX X BCC ELEVATOR #4 PIT DETECTOR STATUS Aux. Contact (Control)

C-XX X TPA ELEVATOR #1 RECALL

C-XX X TPA ELEVATOR #2 RECALL

C-XX X BCC ELEVATOR #3 RECALL

C-XX X BCC ELEVATOR #4 RECALL

C-XX X EXTERIOR CONVENTIONAL PULL STATION. Aux. Contact (Monitor)

C-XX X KITCHEN HOOD SURPRESSION SYSTEM MONITORING Aux. Contact (Monitor)

C-XX X HEAT TRACING (DRUM DRIPS) Aux. Contact (Monitor)

C-XX X HEAT TRACING (GUTTER SNOW MELTING) Aux. Contact (Monitor)

C-XX X EMERGENCY GAS SHUT OFF Aux. Contact (Monitor)

SPARE

SPARE

SPARE

SPARE

X FIRE ALARM ANNUNCIATOR

FIRE ALARM PASSIVE GRAPHIC

1.

2.

3.

4.

5.

Notes:

Accessories

External Tie-ins

Connect to Existing Building Fire Alarm Contoller

Connect to Security System Controller

Connect to Air Handiling Unit Controller

Third Party Monitoring Station

Connect to Elevator Controller

11/2/2017 4 of 5

10 of 34

Page 11: 267-2017 Add Nr18 revFINAL - wx.toronto.ca · Michael Pacholok, Chief Purchasing Officer and Director Purchasing & Materials Management City Hall, 19th Floor, West 100 Queen Street

PROJECT NAME: Bessarion Community Centre

Project number: 14327.000.E.001Date: 2017.11.03

Description

Mech. Labels

FIRE ALARM SCHEDULEZ

on

e N

o.

Ala

rm

Su

pe

rvis

ory

Co

ntr

ol/M

on

ito

r

Annunciator Label

Alarm Zones

11/2/2017 5 of 5

11 of 34

Page 12: 267-2017 Add Nr18 revFINAL - wx.toronto.ca · Michael Pacholok, Chief Purchasing Officer and Director Purchasing & Materials Management City Hall, 19th Floor, West 100 Queen Street

PANEL: LP-P1XA LOCATION: P115 ELECT ROOM

PROJECT NAME: BESSARION COMMUNITY CENTRE

PROJECT #: 14327.000.E.001 FED FROM: PP-P1XA

TYPE/ DESCRIPTION D.F CONN. DEMAND BKR CCT Φ CCT BKR DEMAND CONN. D.F DESCRIPTION TYPE/

INFO [%] LOAD [W] LOAD [W] [A] NO. NO. [A] LOAD [W] LOAD [W] [%] INFO

LTS Sump Pit Room (R307), Water Treatment (P306) 100 192 192 20 1 A 2 20 987 987 100

Irrigation Room (P114), Mech Vest (P112), Elect

Room (P115), BCC Elev Vest (P102), Service

Vest (P117), Boiler Room (P119), Pool Filtration

(P206), Main Comm Room (P118) LTS

LTS

BCC Elev Machine (P304), CC Elev 3 (Elev 3),

BCC Elev Vest (P302) 100 149 149 20 3 B 4 20 960 960 100 Pool Service Tunnel (P120), LTS

LTS

BCC Elev Vest (P202), Muriatic Acid (P205),

Sprinkler Water Meter (P210), Stair D Vest

(P20d) 100 168 168 20 5 C 6 20 391 391 100 Pool Mechanical Room (P207) LTS

LTS P2 Exit Signs 100 36 36 20 7 A 8 20 90 90 100 P1 Exit Signs LTS

LTS Stair D (STR D) (P2-L4) 100 672 672 20 9 B 10 20 100

LTS Stair D (STR D) (P2-L4) Exit Lts 100 6 6 20 11 C 12 20 100

LTS Stair L (STR L) (L2-L3) 100 174 174 20 13 A 14 15 100

LTS P2 Room 100 64 64 20 15 B 16 15 185 246 75 P2 Excess Pressure Pump (Sprinkler Water Rm) D.C

BCC Elev. 3 Cab 100 150 150 15 17 C 18 15 200 200 100 Emergency Gas Shut off D.C

BCC Elev. 4 Cab 100 150 150 15 19 A 20 15 100

D.C Sprinkler Heat Trace 50 750 375 20 21 B 22 15 100

50 750 375 2P 23 C 24 15 100

D.C Sprinkler Heat Trace 50 750 375 20 25 A 26 15 100

50 750 375 2P 27 B 28 15 100

D.C Sprinkler Heat Trace 50 750 375 20 29 C 30 15 100

50 750 375 2P 31 A 32 15 100

100 20 33 B 34 15 100

100 20 35 C 36 15 100

100 20 37 A 38 15 100

100 20 39 B 40 15 100

100 20 41 C 42 15 100

PANEL OPTIONS: LOAD A [KW]: 2.38 PHASE VOLTAGE [V]: 120

2 :CSA ENCLOSURE RATING FLUSH LOAD B [KW]: 2.78 LINE VOLTAGE [V]: 208

X FEED THROUGH X SURFACE LOAD C [KW]: 1.67 PHASE: 3Ф

SUB-FEED X TOTAL [KW]: 6.82 WIRE: 4

MAIN BREAKER SPD MAINS [A]: 125

200% RATED NEUTRAL BUS CURRENT A [A]: MAIN BREAKER [A]:

ISOLATED GROUND BUS CURRENT B [A]: 23 I.C. [kA]: 10

CURRENT C [A]: 14

BOLT-ON BREAKER

20

Page 1 of 2

12 of 34

Page 13: 267-2017 Add Nr18 revFINAL - wx.toronto.ca · Michael Pacholok, Chief Purchasing Officer and Director Purchasing & Materials Management City Hall, 19th Floor, West 100 Queen Street

PANEL: LP-P1XA LOCATION: P115 ELECT ROOM

PROJECT NAME: BESSARION COMMUNITY CENTRE

PROJECT #: 14327.000.E.001 FED FROM: PP-P1XA

TYPE/ DESCRIPTION D.F CONN. DEMAND BKR CCT Φ CCT BKR DEMAND CONN. D.F DESCRIPTION TYPE/

INFO [%] LOAD [W] LOAD [W] [A] NO. NO. [A] LOAD [W] LOAD [W] [%] INFO

LEGEND: NOTES:

BAS-Building Automation System R.C-Relay Controlled LTS-Lighting 1. Panel Enclosure To Be Sprinklerproof.

GFCI-Ground Fault Circuit Interrupter M-Motor 2. Panels greater than 66 circuits to be double tub.

AFCI-Arc Fault Circuit Interrupter D.F-Demand Factor 3. Surge Protection Device (SPD) to be in a separate barriered

SPD - Surge Protection Device REC-Receptacle D.C-Direct Connection enclosure with separate cover.

BLO-Breaker Lock-On Device 4. Terminate circuits for BAS in 4"x4" junction box 10' from panel.

HID-High Intensity Discharge

Lighting Breaker

Page 2 of 2

13 of 34

Page 14: 267-2017 Add Nr18 revFINAL - wx.toronto.ca · Michael Pacholok, Chief Purchasing Officer and Director Purchasing & Materials Management City Hall, 19th Floor, West 100 Queen Street

PANEL: RP-1EC LOCATION: G102 ELECT/COMMS

PROJECT NAME: BESSARION COMMUNITY CENTRE

PROJECT #: 14327.000.E.001 FED FROM: PP-P1EA

TYPE/ DESCRIPTION D.F CONN. DEMAND BKR CCT Φ CCT BKR DEMAND CONN. D.F DESCRIPTION TYPE/

INFO [%] LOAD [W] LOAD [W] [A] NO. NO. [A] LOAD [W] LOAD [W] [%] INFO

100 15 1 A 2 15 100

100 15 3 B 4 15 900 900 100 A105, A107 Receptacle REC

REC Office A104 Receptacle 100 600 600 15 5 C 6 15 375 500 75 First Aid Fridge REC

REC Pool Storage Receptacle 100 450 450 15 7 A 8 20 250 1000 25 First Aid Microwave REC

REC Sound Rack 50 600 300 15 9 B 10 20 150 150 100 First Aid REC

REC First Aid/ Guards 100 450 450 15 11 C 12 15 150 600 25 Women/men Change room A112/A108 ADO D.C

REC First Aid /Guards 100 600 600 15 13 A 14 15 100

REC Women/men Change room A112/A108, Custodial 100 600 600 15 15 B 16 15 100

REC Change Room 100 150 150 15 17 C 18 20 588 588 100 Universal Change Room A, A113A LTS

LTS

Guards A111, Men CHG A112, Women CHG

A108, Files/Storage A107, Custodial A106, Pool

Storage A110, Reception Room A101A, Staff

Locker Area A102, Staff Room A105, Office

A104, Reception A101, Aquatic Corridor A103100 902 902 20 19 A 20 15 150 150 100 Change Room REC

D.C Custodial Trap Primer 100 150 150 15 21 B 22 15 100

REC Change Room 100 150 150 15 23 C 24 20 480 1920 25 Universal Change Room Motorized Blinds D.C

15 25 A 26 20 480 1920 25 Universal Change Room Motorized Blinds D.C

REC Universal Change Room Receptacles 100 450 450 15 27 B 28 20 480 1920 25 Universal Change Room Motorized Blinds D.C

REC Change Room Receptacle 100 150 150 15 29 C 30 15 150 150 100 Change Room Receptacle D.C

D.C Change Room Hair Dryer 25 1800 450 20 31 A 32 20 450 1800 25 Change Room Hair Dryer D.C

D.C Change Room Hair Dryer 25 1800 450 20 33 B 34 15 450 450 100 Natatorium Receptacles GFCI

D.C Natatorium Strobe/Alarm 100 150 150 15 35 C 36 15 150 150 100 Pool Jet Controls D.C

REC Aquatic Corridor 100 300 300 15 37 A 38 15 150 150 100 Pool Jet Controls D.C

D.C Natatorium Strobe/Alarm 100 150 150 15 39 B 40 15 120 120 100 Pace clock D.C

D.C Universal Change Room Trap Primer 100 100 100 15 41 C 42 15 150 150 100 Motorized Blind Control Guard room D.C

REC Reception A101 Receptacle 100 450 450 15 43 A 44 15 200 200 100 G102 Elect/Comms REC

REC Reception A101 Receptacle Security Monitor 100 300 300 15 45 B 46 15 200 200 100 G102 Elect/Comms REC

REC Reception A101 Remote Paging 100 150 150 15 47 C 48 15 200 200 100 G102 Elect/Comms REC

REC Reception A101 Receptacle 100 450 450 15 49 A 50 15 200 200 100 G102 Elect/Comms REC

REC Reception A101 Receptacle 100 450 450 15 51 B 52 20 500 500 100 G102 Elect/Comms Cable Tray Mounted REC

REC Reception A101 Turnstile Power 100 150 150 15 53 C 54 2P 500 500 100

REC Reception A101 TV 100 150 150 15 55 A 56 20 500 500 100 G102 Elect/Comms Cable Tray Mounted REC

REC Reception A101 Printer 25 500 125 20 57 B 58 2P 500 500 100

REC Reception A101 REC 100 100 100 15 59 C 60 15 450 450 100 FC-01-01,02 D.C

D.C Reception A101 Sump pit Alarm 100 100 100 15 61 A 62 15 300 300 100 Entrance Vestibule G100 Receptacle REC

D.C FC-T-01 100 50 50 15 63 B 64 15 100

D.C Lobby Recessed Receptacles 100 450 450 15 65 C 66 20 300 300 100 Main Comm Room (P118) Receptacle D.C

Page 1 of 2

14 of 34

Page 15: 267-2017 Add Nr18 revFINAL - wx.toronto.ca · Michael Pacholok, Chief Purchasing Officer and Director Purchasing & Materials Management City Hall, 19th Floor, West 100 Queen Street

PANEL: RP-1EC LOCATION: G102 ELECT/COMMS

PROJECT NAME: BESSARION COMMUNITY CENTRE

PROJECT #: 14327.000.E.001 FED FROM: PP-P1EA

TYPE/ DESCRIPTION D.F CONN. DEMAND BKR CCT Φ CCT BKR DEMAND CONN. D.F DESCRIPTION TYPE/

INFO [%] LOAD [W] LOAD [W] [A] NO. NO. [A] LOAD [W] LOAD [W] [%] INFO

REC Charging Station Receptacle 100 150 150 15 67 A 68 2P 300 300 100

REC Lobbies G101 and A100 Receptacle 100 1000 1000 15 69 B 70 20 300 300 100 Main Comm Room (P118) Receptacle D.C

REC Counter displays 100 300 300 15 71 C 72 2P 300 300 100

100 15 73 A 74 20 300 300 100 Main Comm Room (P118) Receptacle D.C

100 15 75 B 76 2P 300 300 100

100 15 77 C 78 20 300 300 100 Main Comm Room (P118) Receptacle D.C

100 15 79 A 80 2P 300 300 100

100 20 81 B 82 15 300 300 100 Main Comm Room (P118) Receptacle REC

100 20 83 C 84 15 300 300 100 Main Comm Room (P118) Receptacle REC

PANEL OPTIONS: LOAD A [KW]: 7.58 PHASE VOLTAGE [V]: 120

2 :CSA ENCLOSURE RATING FLUSH LOAD B [KW]: 8.23 LINE VOLTAGE [V]: 208

FEED THROUGH X SURFACE LOAD C [KW]: 7.29 PHASE: 3Ф

SUB-FEED X TOTAL [KW]: 23.1 WIRE: 4

MAIN BREAKER SPD MAINS [A]: 125

200% RATED NEUTRAL BUS CURRENT A [A]: MAIN BREAKER [A]:

ISOLATED GROUND BUS CURRENT B [A]: 69 I.C. [kA]: 10

CURRENT C [A]: 61

LEGEND: NOTES:

BAS-Building Automation System R.C-Relay Controlled LTS-Lighting 1. Panel Enclosure To Be Sprinklerproof.

GFCI-Ground Fault Circuit Interrupter M-Motor 2. Panels greater than 66 circuits to be double tub.

AFCI-Arc Fault Circuit Interrupter D.F-Demand Factor 3. Surge Protection Device (SPD) to be in a separate barriered

SPD - Surge Protection Device REC-Receptacle D.C-Direct Connection enclosure with separate cover.

BLO-Breaker Lock-On Device 4. Terminate circuits for BAS in 4"x4" junction box 10' from panel.

BOLT-ON BREAKER

63

HID-High Intensity Discharge

Lighting Breaker

Page 2 of 2

15 of 34

Page 16: 267-2017 Add Nr18 revFINAL - wx.toronto.ca · Michael Pacholok, Chief Purchasing Officer and Director Purchasing & Materials Management City Hall, 19th Floor, West 100 Queen Street

PANEL: RP-2EC LOCATION: R202 ELECT/COMMS

PROJECT NAME: BESSARION COMMUNITY CENTRE

PROJECT #: 14327.000.E.001 FED FROM: PP-P1EA

TYPE/ DESCRIPTION D.F CONN. DEMAND BKR CCT Φ CCT BKR DEMAND CONN. D.F DESCRIPTION TYPE/

INFO [%] LOAD [W] LOAD [W] [A] NO. NO. [A] LOAD [W] LOAD [W] [%] INFO

REC G200, G202 HK Receptacle 100 600 600 15 1 A 2 15 450 450 100 G200, G202 Countertop Receptacle REC

100 300 300 15 3 B 4 15 900 900 100 R201 Receptacle REC

REC R201 Countertop Receptacle 100 150 150 20 5 C 6 15 500 500 100 R201 Fridge Receptacle REC

REC R201 Microwave Receptacle 25 1000 250 15 7 A 8 20 300 1200 25 Electrified Shades D.C

D.C R204, R205 ADO 75 600 450 15 9 B 10 20 300 1200 25 Electrified Shades D.C

REC Maintenance (R201) sump pit Alarm 100 150 150 15 11 C 12 15 300 300 100 R204, R205 Receptacle REC

D.C R204 Hand Dryer 25 1400 350 15 13 A 14 15 200 200 100 R204, R205, Trap Primer/Auto Flush/Sink D.C

D.C R205 Hand Dryer 25 1400 350 15 15 B 16 15 100

REC R206 Receptacle 100 900 900 15 17 C 18 15 450 450 100 R206 Projector and Screen REC

LTS L2 Lobby (G200), Corridor 100 194 194 20 19 A 20 15 100

LTS

Maintenance (R201), Custodial (R203), BF WC

(R204,R205) 100 292 292 20 21 B 22 15 100

LTS

Meeting (R206), Kitchen (R207), Pantry (R207A),

Storage (R208A) LIGHTS 100 438 438 20 23 C 24 15 100

D.C Air curtain (G200) 100 250 250 15 25 A 26 15 100

D.C Trap Primer Exterior 100 100 100 15 27 B 28 20 200 800 25 Motorized Blinds D.C

REC R201, R202, R203 Receptacle 100 450 450 15 29 C 30 20 200 800 25 Motorized Blinds D.C

REC G200 Reception 100 450 450 15 31 A 32 20 200 800 25 Motorized Blinds D.C

REC G200 Reception 100 300 300 15 33 B 34 20 200 800 25 Motorized Blinds D.C

REC G200 Reception Security Monitors 100 300 300 15 35 C 36 15 220 220 100 FC-02-01 D.C

REC G200 Reception Display Monitors 100 300 300 15 37 A 38 15 150 150 100 R204 BF EM Call Strip D.C

D.C L2 Lobby (G200) - F.P.B 100 187 187 15 39 B 40 15 150 150 100 R204 BF EM Call Strip D.C

100 187 187 15 41 C 42 15 100

15 43 A 44 15 373 373 100 Pantry (R207) - F.P.B, Meeting (R208) - F.P.B D.C

REC R208A Receptacle 100 450 450 15 45 B 46 2P 373 373 100

REC R207 Receptacle 100 300 300 15 47 C 48 15 450 450 100 R207A Receptacle REC

REC R207 Microwave Receptacle 25 1000 250 20 49 A 50 15 350 350 100 R207A Freezer REC

REC R207 Countertop Receptacle 100 150 150 20 51 B 52 15 500 500 100 R207A Fridge REC

REC R207 Countertop Receptacle 100 150 150 20 53 C 54 50 845 3380 25 C215 Dish Washer (Hobart LXEH) D.C

REC R207 Range 25 2400 600 50 55 A 56 2P 845 3380 25 120/208V

14-50R 25 2400 600 2P 57 B 58 20 150 150 100 R207 Countertop Receptacle REC

REC R207 Range Hood 25 500 125 20 59 C 60 20 150 150 100 R207 Countertop Receptacle REC

D.C R207 Warming Oven 25 1920 480 20 61 A 62 20 500 500 100 R207 Double Fridge REC

D.C R207 Warming Oven 25 1920 480 20 63 B 64 20 150 150 100 R207 Island Receptacle REC

100 20 65 C 66 15 200 200 100 Comms R202A REC

100 20 67 A 68 15 200 200 100 Comms R202A REC

100 20 69 B 70 15 200 200 100 Comms R202A REC

Page 1 of 2

16 of 34

Page 17: 267-2017 Add Nr18 revFINAL - wx.toronto.ca · Michael Pacholok, Chief Purchasing Officer and Director Purchasing & Materials Management City Hall, 19th Floor, West 100 Queen Street

PANEL: RP-2EC LOCATION: R202 ELECT/COMMS

PROJECT NAME: BESSARION COMMUNITY CENTRE

PROJECT #: 14327.000.E.001 FED FROM: PP-P1EA

TYPE/ DESCRIPTION D.F CONN. DEMAND BKR CCT Φ CCT BKR DEMAND CONN. D.F DESCRIPTION TYPE/

INFO [%] LOAD [W] LOAD [W] [A] NO. NO. [A] LOAD [W] LOAD [W] [%] INFO

100 20 71 C 72 15 300 300 100 Comms R202A REC

100 73 A 74 15 300 300 100

100 75 B 76 15 300 300 100 Comms R202A REC

100 77 C 78 15 300 300 100

100 79 A 80 15 100

100 81 B 82 15 100

100 83 C 84 15 100

PANEL OPTIONS: LOAD A [KW]: 7.59 PHASE VOLTAGE [V]: 120

2 :CSA ENCLOSURE RATING FLUSH LOAD B [KW]: 7.08 LINE VOLTAGE [V]: 208

FEED THROUGH X SURFACE LOAD C [KW]: 7.07 PHASE: 3Ф

SUB-FEED X TOTAL [KW]: 21.7 WIRE: 4

MAIN BREAKER SPD MAINS [A]: 125

200% RATED NEUTRAL BUS CURRENT A [A]: MAIN BREAKER [A]:

ISOLATED GROUND BUS CURRENT B [A]: 59 I.C. [kA]: 10

CURRENT C [A]: 59

LEGEND: NOTES:

BAS-Building Automation System R.C-Relay Controlled LTS-Lighting 1. Panel Enclosure To Be Sprinklerproof.

GFCI-Ground Fault Circuit Interrupter M-Motor 2. Panels greater than 66 circuits to be double tub.

AFCI-Arc Fault Circuit Interrupter D.F-Demand Factor 3. Surge Protection Device (SPD) to be in a separate barriered

SPD - Surge Protection Device REC-Receptacle D.C-Direct Connection enclosure with separate cover.

BLO-Breaker Lock-On Device 4. Terminate circuits for BAS in 4"x4" junction box 10' from panel.

BOLT-ON BREAKER

63

HID-High Intensity Discharge

Lighting Breaker

Page 2 of 2

17 of 34

Page 18: 267-2017 Add Nr18 revFINAL - wx.toronto.ca · Michael Pacholok, Chief Purchasing Officer and Director Purchasing & Materials Management City Hall, 19th Floor, West 100 Queen Street

PANEL: RP-2ED LOCATION: R211 ELECT CLS.

PROJECT NAME: BESSARION COMMUNITY CENTRE

PROJECT #: 14327.000.E.001 FED FROM: DP-P2EB

TYPE/ DESCRIPTION D.F CONN. DEMAND BKR CCT Φ CCT BKR DEMAND CONN. D.F DESCRIPTION TYPE/

INFO [%] LOAD [W] LOAD [W] [A] NO. NO. [A] LOAD [W] LOAD [W] [%] INFO

D.C Pool Area Motorized Blinds 25 800 200 20 1 A 2 15 450 450 100 G202 HK Receptacle REC

D.C Pool Area Motorized Blinds 25 800 200 20 3 B 4 20 225 900 25 Electrified Shades D.C

D.C Pool Area Motorized Blinds 25 800 200 20 5 C 6 20 225 900 25 Electrified Shades D.C

D.C Pool Area Motorized Blinds 25 800 200 20 7 A 8 20 225 900 25 Electrified Shades D.C

D.C Pool Area Motorized Blinds 25 800 200 20 9 B 10 20 113 450 25 Electrified Shades D.C

D.C Pool Area Motorized Blinds 25 800 200 20 11 C 12 15 150 150 100 Exterior Recep REC

D.C Meeting (R210) - F.P.B, Meeting (R209) - F.P.B 100 373 373 15 13 A 14 15 150 150 100 R208 Motorized AV Screen + Projector REC

100 373 373 2P 15 B 16 20 250 1000 25 R208, R209 Curtain Divider D.C

100 15 17 C 18 20 150 600 25 R208, R209 Motorized Blinds/Black out Shades D.C

100 15 19 A 20 15 150 600 25 R208, R209 Motorized Blinds/Black out Shades D.C

D.C Electronic Trap Primer 75 100 75 15 21 B 22 15 150 600 25 R208, R209 Motorized Blinds/Black out Shades D.C

REC R208, R209 Receptacle 100 750 750 15 23 C 24 15 150 150 100 R209 Countertop Receptacle REC

REC R209 Receptacle 100 900 900 15 25 A 26 15 120 120 100 R209 Motorized AV Screen + Projector D.C

D.C R208A AV RACK 50 1440 720 15 27 B 28 15 100

REC R210 Receptacle 100 600 600 15 29 C 30 15 150 600 25 G202 ADO D.C

REC Digital Screen 100 150 150 15 31 A 32 15 25 Air Curtain

LTS Natatorium (A123) Lights 75 1120 840 20 33 B 34 20 528 528 100

Meeting (R208,R209,R210), Corridor (G202)

Lights LTS

LTS Natatorium (A123) Lights 100 1120 1120 20 35 C 36 20 37 37 100 Elec. Closet R211 FFH-02-04 D.C

LTS Natatorium (A123) Lights 100 1120 1120 20 37 A 38 20 300 300 100 FC-02-02 D.C

LTS Natatorium (A123) Lights 100 1280 1280 20 39 B 40 20 100

LTS Natatorium (A123) Lights 100 384 384 20 41 C 42 20 100

PANEL OPTIONS: LOAD A [KW]: 4.34 PHASE VOLTAGE [V]: 120

2 :CSA ENCLOSURE RATING FLUSH LOAD B [KW]: 4.95 LINE VOLTAGE [V]: 208

FEED THROUGH X SURFACE LOAD C [KW]: 4.12 PHASE: 3Ф

SUB-FEED X TOTAL [KW]: 13.4 WIRE: 4

MAIN BREAKER SPD MAINS [A]: 125

200% RATED NEUTRAL BUS CURRENT A [A]: MAIN BREAKER [A]:

ISOLATED GROUND BUS CURRENT B [A]: 41 I.C. [kA]: 10

CURRENT C [A]: 34

LEGEND: NOTES:

BAS-Building Automation System R.C-Relay Controlled LTS-Lighting 1. Panel Enclosure To Be Sprinklerproof.

GFCI-Ground Fault Circuit Interrupter M-Motor 2. Panels greater than 66 circuits to be double tub.

AFCI-Arc Fault Circuit Interrupter D.F-Demand Factor 3. Surge Protection Device (SPD) to be in a separate barriered

SPD - Surge Protection Device REC-Receptacle D.C-Direct Connection enclosure with separate cover.

BOLT-ON BREAKER

36

HID-High Intensity Discharge

Lighting Breaker

Page 1 of 2

18 of 34

Page 19: 267-2017 Add Nr18 revFINAL - wx.toronto.ca · Michael Pacholok, Chief Purchasing Officer and Director Purchasing & Materials Management City Hall, 19th Floor, West 100 Queen Street

PANEL: RP-2ED LOCATION: R211 ELECT CLS.

PROJECT NAME: BESSARION COMMUNITY CENTRE

PROJECT #: 14327.000.E.001 FED FROM: DP-P2EB

TYPE/ DESCRIPTION D.F CONN. DEMAND BKR CCT Φ CCT BKR DEMAND CONN. D.F DESCRIPTION TYPE/

INFO [%] LOAD [W] LOAD [W] [A] NO. NO. [A] LOAD [W] LOAD [W] [%] INFO

BLO-Breaker Lock-On Device 4. Terminate circuits for BAS in 4"x4" junction box 10' from panel.

Page 2 of 2

19 of 34

Page 20: 267-2017 Add Nr18 revFINAL - wx.toronto.ca · Michael Pacholok, Chief Purchasing Officer and Director Purchasing & Materials Management City Hall, 19th Floor, West 100 Queen Street

PANEL: RP-4EA LOCATION: 405 ELECT

PROJECT NAME: BESSARION COMMUNITY CENTRE

PROJECT #: 14327.000.E.001 FED FROM: TX-4EA

TYPE/ DESCRIPTION D.F CONN. DEMAND BKR CCT Φ CCT BKR DEMAND CONN. D.F DESCRIPTION TYPE/

INFO [%] LOAD [W] LOAD [W] [A] NO. NO. [A] LOAD [W] LOAD [W] [%] INFO

REC Vestibule General Receptacles 100 1050 1050 15 1 A 2 20 750 750 100 Roof top receptacles REC

REC General Receptacle Track area 100 450 450 15 3 B 4 20 900 900 100 Roof top receptacles REC

D.C Net Winch 25 1370 343 15 5 C 6 15 960 960 100 ScoreBoard and Time keeper REC

D.C Net Winch 25 1370 343 15 7 A 8 15 960 960 100 ScoreBoard and Time keeper REC

D.C Net Winch 25 1370 343 15 9 B 10 15 480 480 100 Shot Clocks D.C

D.C Net Winch 25 1370 343 15 11 C 12 15 100

D.C Net Winch 25 1370 343 15 13 A 14 15 100 400 25 Motorized curtain D.C

D.C Net Winch 25 1370 343 15 15 B 16 15 100 100 100 Trap Primers D.C

REC Drinking Fountain 100 500 500 15 17 C 18 20 150 150 100

Storage (R407), Vestibule (R404), L3 Mezzanine

(R401) LTS

LTS Stretching (R402A), Gym (R318) 100 1440 1440 20 19 A 20 20 168 168 100 Gym (R318) LTS

LTS Stretching (R402A), Gym (R318) 100 1440 1440 20 21 B 22 15 300 300 100 Elev 3 and Elev 4 Receptacles REC

LTS Stretching (R402A), Gym (R318) 100 1440 1440 20 23 C 24 15 374 374 100 Roof top H-RTU-02 D.C

D.C Roof top H-RTU-01 100 374 374 15 25 A 26 15 374 374 100 Roof top H-RTU-03 D.C

D.C Roof top H-RTU-04 100 374 374 15 27 B 28 15 264 264 100 EF-L4-04 M

D.C L4 Elec. Room FFH-04-01 75 30 23 15 29 C 30 15 100

D.C L4 Stair D FFH-04-02 75 30 23 15 31 A 32 15 100

M EF-L4-02 75 100 75 20 33 B 34 15 100

D.C EF-L4-03 75 372 279 20 35 C 36 15 100

100 20 37 A 38 15 100

100 39 B 40 100

100 41 C 42 100

PANEL OPTIONS: LOAD A [KW]: 5.92 PHASE VOLTAGE [V]: 120

2 :CSA ENCLOSURE RATING FLUSH LOAD B [KW]: 5.07 LINE VOLTAGE [V]: 208

FEED THROUGH X SURFACE LOAD C [KW]: 4.41 PHASE: 3Ф

SUB-FEED X TOTAL [KW]: 15.4 WIRE: 4

MAIN BREAKER SPD MAINS [A]: 225

200% RATED NEUTRAL BUS CURRENT A [A]: MAIN BREAKER [A]:

ISOLATED GROUND BUS CURRENT B [A]: 42 I.C. [kA]: 10

CURRENT C [A]: 37

LEGEND: NOTES:

BAS-Building Automation System R.C-Relay Controlled LTS-Lighting 1. Panel Enclosure To Be Sprinklerproof.

GFCI-Ground Fault Circuit Interrupter M-Motor 2. Panels greater than 66 circuits to be double tub.

AFCI-Arc Fault Circuit Interrupter D.F-Demand Factor 3. Surge Protection Device (SPD) to be in a separate barriered

SPD - Surge Protection Device REC-Receptacle D.C-Direct Connection enclosure with separate cover.

BOLT-ON BREAKER

49

HID-High Intensity Discharge

Lighting Breaker

Page 1 of 2

20 of 34

Page 21: 267-2017 Add Nr18 revFINAL - wx.toronto.ca · Michael Pacholok, Chief Purchasing Officer and Director Purchasing & Materials Management City Hall, 19th Floor, West 100 Queen Street

PANEL: RP-4EA LOCATION: 405 ELECT

PROJECT NAME: BESSARION COMMUNITY CENTRE

PROJECT #: 14327.000.E.001 FED FROM: TX-4EA

TYPE/ DESCRIPTION D.F CONN. DEMAND BKR CCT Φ CCT BKR DEMAND CONN. D.F DESCRIPTION TYPE/

INFO [%] LOAD [W] LOAD [W] [A] NO. NO. [A] LOAD [W] LOAD [W] [%] INFO

BLO-Breaker Lock-On Device 4. Terminate circuits for BAS in 4"x4" junction box 10' from panel.

Page 2 of 2

21 of 34

Page 22: 267-2017 Add Nr18 revFINAL - wx.toronto.ca · Michael Pacholok, Chief Purchasing Officer and Director Purchasing & Materials Management City Hall, 19th Floor, West 100 Queen Street

PANEL: RP-P1EB LOCATION: P115 ELECT ROOM

PROJECT NAME: BESSARION COMMUNITY CENTRE

PROJECT #: 14327.000.E.001 FED FROM: TX-P1EB

TYPE/ DESCRIPTION D.F CONN. DEMAND BKR CCT Φ CCT BKR DEMAND CONN. D.F DESCRIPTION TYPE/

INFO [%] LOAD [W] LOAD [W] [A] NO. NO. [A] LOAD [W] LOAD [W] [%] INFO

LTS

BCC Elev Machine (P304), BCC Elev Vest

(P302) 100 59 59 20 1 A 2 20 1070 1070 100

Irrigation Room (P114), Bcc Elev Vest (P102),

Boilr Room (P119) Pool Mechanical (P207), Pool

Filtration (P206) LTS

LTS

BCC Elev Vest (P202), Sprinkler Water Meter

(P210) 100 78 78 20 3 B 4 20 100

100 20 5 C 6 20 100

LTS

Entrance Vestibule G100, Aquatic Lobby A100,

Men's WC G103, Women's WC G105, Universal

WC G104, EXIT, Recycling G114, Receiving

G110, Admin Mechanical G111, Custodial G112 100 932 932 20 7 A 8 15 500 500 100 Public Display Art D.C

REC House Keeping Receptacle 100 750 750 15 9 B 10 15 75 300 25 Main Entrance ADO D.C

REC Charging Station Receptacle 100 150 150 15 11 C 12 15 188 250 75 Fire Alarm Annunciator Panel D.C

15 13 A 14 40 2100 3000 70 TPS Custodial DHWR-P1-03 D.C

REC Aquatics Lobby Receptacle 100 150 150 15 15 B 16 2P 2100 3000 70

REC Mens WC G103 Receptacle 100 300 300 15 17 C 18 15 150 600 25 Universal Washroom G104 ADO, Corridor ADO D.C

REC Mens WC G103 Receptacle 100 150 150 15 19 A 20 15 450 600 75 Washroom G103, 104, 105 Trap Primer , Auto FlushD.C

REC Universal Washroom G104 Receptacle 100 300 300 15 21 B 22 15 72 96 75 BCC Elev Vest (P102) FC-P1-02 D.C

REC Womens Washroom G105 Receptacle 100 300 300 15 23 C 24 15 72 96 75 BCC Elev Vest (P302) FC-P3-02 D.C

REC Admin Mech G111 Receptacle 100 450 450 15 25 A 26 15 56 75 75 Garbage Room G114 FFH D.C

REC Admin Mech G111 Receptacle 100 150 150 15 27 B 28 15 375 500 75 Universal Washroom G104 Change Lift REC

REC Receiving Room G110 Receptacle 100 150 150 15 29 C 30 15 350 1400 25 Hand Dryer (G105) D.C

REC Receiving Room G110 Receptacle 100 450 450 15 31 A 32 15 350 1400 25 Hand dryer(G105) D.C

REC Garbage Room G114 Receptacle 100 600 600 15 33 B 34 15 350 1400 25 Hand Dryer (G104) D.C

REC Vending Machine 1 100 300 300 15 35 C 36 15 350 1400 25 Hand dryer (G103) D.C

REC Vending Machine 2 100 300 300 15 37 A 38 15 350 1400 25 Hand dryer (G103) D.C

100 15 39 B 40 15 1050 1050 100

Irrigation Room (P114), Mech Vest (P112), BCC

Elev Vest (P102), Serice Vest (P117) Recepatcle REC

REC Boiler Room (P119) Receptacle 100 750 750 15 41 C 42 15 600 600 100 Boiler Room (P119) Receptacle, Trap Primers REC

REC Boiler Room (P119) Receptacle 100 750 750 15 43 A 44 15 300 1199 25

REC Boiler Room (P119) Receptacle 100 600 600 15 45 B 46 ↓ 300 1199 25 O/H Door D.C

D.C Boiler Room (P119) UH-P1-01/02 75 74 56 15 47 C 48 3P 300 1199 25

SPARE 15 49 A 50 15 140 186 75 Admin mech. (G111) EF-01-01

D.C Boiler Room (P119) JUNCTION BOX 75 100 75 15 51 B 52 2P 140 186 75

REC Exit Stair D 100 150 150 15 53 C 54 15 140 186 75 EF-L1-02 D.C

D.C Elect room (P115) BU Unit 100 100 100 15 55 A 56 15 100 100 100 Boiler controls D.C.

D.C BCC Elev Vest (P202) FC-P2-02 100 100 100 15 57 B 58 15

Page 1 of 4

22 of 34

Page 23: 267-2017 Add Nr18 revFINAL - wx.toronto.ca · Michael Pacholok, Chief Purchasing Officer and Director Purchasing & Materials Management City Hall, 19th Floor, West 100 Queen Street

PANEL: RP-P1EB LOCATION: P115 ELECT ROOM

PROJECT NAME: BESSARION COMMUNITY CENTRE

PROJECT #: 14327.000.E.001 FED FROM: TX-P1EB

TYPE/ DESCRIPTION D.F CONN. DEMAND BKR CCT Φ CCT BKR DEMAND CONN. D.F DESCRIPTION TYPE/

INFO [%] LOAD [W] LOAD [W] [A] NO. NO. [A] LOAD [W] LOAD [W] [%] INFO

REC BCC Elev Vest (P202) Receptacles 100 150 150 15 59 C 60 15

LTS Exterior lighting South 100 781 781 20 61 A 62 15

100 20 63 B 64 15

100 20 65 C 66 15

REC BCC Elev Machine (P304) Receptacle 75 300 225 20 67 A 68 15

LTS Exterior lighting East 100 936 936 20 69 B 70 15 450 450 100 Exit Stair L REC

LTS Exterior lighting East 100 1178 1178 20 71 C 72 15 200 200 100 Exterior signage D.C

LTS Main entrance wall Sheppard avenue 100 350 350 20 73 A 74 15 750 750 100 Sump Pit room (P307) Receptacle REC

D.C Boiler Room (P119) DHWH-P1-01 100 373 373 15 75 B 76 15 750 750 100 Sump Pit room (P307) Receptacle REC

D.C. Boiler Room (P119) DHWH-P1-02 100 373 373 15 77 C 78 15 50 50 100 Sump Pit room (P307) Trap Primer D.C

D.C Sump Pit room (P307) UH-P3-01 75 60 45 15 79 A 80 20 300 300 100 CC Elev 3, CC Elev 4 Receptacle REC

REC Water Treatment (P306) Receptacles 100 750 750 15 81 B 82 15 150 150 100 Sump Pit room (P307) Bas Control D.C

REC Water Treatment (P306) Receptacles 100 450 450 15 83 C 84 20 126 126 100 Exterior Lighting West LTS

D.C Water Treatment (P306) UH-P3-02 75 37 28 15 85 A 86 20 1221 1221 100 Exterior lighting North LTS

REC BCC Elev Vest (P302) Receptacle 100 150 150 15 87 B 88 15 150 150 100 P106 BAS Control D.C

REC BCC Elev Machine (P304) Receptacle 100 450 450 20 89 C 90 15 500 500 100 Main Fire Alarm Control Panel

D.C TPA Custodial (P107) DHWH-P1-03 Control 70 100 70 15 91 A 92 15 750 750 100 P115 GFCI Receptacles, P116 REC

D.C Water Softner L1 100 150 150 15 93 B 94 15 150 150 100 Remote Paging REC

D.C. Boiler Controller 100 150 150 15 95 C 96 15

D.C FFH-01-04 75 288 216 15 97 A 98 15

15 99 B 100 15

15 101 C 102 15

15 103 A 104 15

15 105 B 106 15

15 107 C 108 15 100 100 100 Glycol Feed Package D.C

D.C Boiler Room (P119) Emergency Gas Shutoff 100 100 100 15 109 A 110 15 28 37 75 Irrigation Room UH-P1-04 D.C

D.C Irrigation room (P114) Irrigation Pumps 100 280 280 15 111 B 112 15 196 280 70 Irrigation room (P114) Irrigation Pumps D.C

100 280 280 2P 113 C 114 2P 196 280 70

15 115 A 116 15

15 117 B 118 15

15 119 C 120 15

Page 2 of 4

23 of 34

Page 24: 267-2017 Add Nr18 revFINAL - wx.toronto.ca · Michael Pacholok, Chief Purchasing Officer and Director Purchasing & Materials Management City Hall, 19th Floor, West 100 Queen Street

PANEL: RP-P1EB LOCATION: P115 ELECT ROOM

PROJECT NAME: BESSARION COMMUNITY CENTRE

PROJECT #: 14327.000.E.001 FED FROM: TX-P1EB

TYPE/ DESCRIPTION D.F CONN. DEMAND BKR CCT Φ CCT BKR DEMAND CONN. D.F DESCRIPTION TYPE/

INFO [%] LOAD [W] LOAD [W] [A] NO. NO. [A] LOAD [W] LOAD [W] [%] INFO

15 121 A 122 15

15 123 B 124 15

15 125 C 126 15

D.C P1 Heat Tracing 25 1440 360 20 127 A 128 15

25 1440 360 2P 129 B 130 15

D.C P1 Heat Tracing 25 1440 360 20 131 C 132 15

25 1440 360 2P 133 A 134 15

D.C P1 Heat Tracing 25 1440 360 20 135 B 136 15

25 1440 360 2P 137 C 138 15

D.C P1 Heat Tracing 25 1440 360 20 139 A 140 15

25 1440 360 2P 141 B 142 15

D.C Exterior Heat Tracing 25 1440 360 20 143 C 144 15

25 1440 360 2P 145 A 146 15

147 B 148 15

149 C 150 15

151 A 152 15

153 B 154 15

155 C 156 15

157 A 158 60 100

159 B 160 ↓ 100 RP-2EB

161 C 162 3P 100

163 A 164 15 37 37 100 G114 UH-01-01 D.C

165 B 166 15 37 37 100 G114 UH-01-02 D.C

167 C 168 15 360 1440 25 Main Entrance O/H Door

PANEL OPTIONS: LOAD A [KW]: 14.9 PHASE VOLTAGE [V]: 120

2 :CSA ENCLOSURE RATING FLUSH LOAD B [KW]: 12.9 LINE VOLTAGE [V]: 208

X FEED THROUGH X SURFACE LOAD C [KW]: 9.95 PHASE: 3Ф

SUB-FEED X TOTAL [KW]: 37.8 WIRE: 4

MAIN BREAKER SPD MAINS [A]: 400

200% RATED NEUTRAL BUS CURRENT A [A]: MAIN BREAKER [A]:

ISOLATED GROUND BUS CURRENT B [A]: 107 I.C. [kA]: 10

CURRENT C [A]: 83

LEGEND: NOTES:

BAS-Building Automation System R.C-Relay Controlled LTS-Lighting 1. Panel Enclosure To Be Sprinklerproof.

GFCI-Ground Fault Circuit Interrupter M-Motor 2. Panels greater than 84 circuits to be double tub.

BOLT-ON BREAKER

125

HID-High Intensity Discharge

Lighting Breaker

Page 3 of 4

24 of 34

Page 25: 267-2017 Add Nr18 revFINAL - wx.toronto.ca · Michael Pacholok, Chief Purchasing Officer and Director Purchasing & Materials Management City Hall, 19th Floor, West 100 Queen Street

PANEL: RP-P1EB LOCATION: P115 ELECT ROOM

PROJECT NAME: BESSARION COMMUNITY CENTRE

PROJECT #: 14327.000.E.001 FED FROM: TX-P1EB

TYPE/ DESCRIPTION D.F CONN. DEMAND BKR CCT Φ CCT BKR DEMAND CONN. D.F DESCRIPTION TYPE/

INFO [%] LOAD [W] LOAD [W] [A] NO. NO. [A] LOAD [W] LOAD [W] [%] INFO

AFCI-Arc Fault Circuit Interrupter D.F-Demand Factor 3. Surge Protection Device (SPD) to be in a separate barriered

SPD - Surge Protection Device REC-Receptacle D.C-Direct Connection enclosure with separate cover.

BLO-Breaker Lock-On Device 4. Terminate circuits for BAS in 4"x4" junction box 10' from panel.

Lighting Breaker

Page 4 of 4

25 of 34

Page 26: 267-2017 Add Nr18 revFINAL - wx.toronto.ca · Michael Pacholok, Chief Purchasing Officer and Director Purchasing & Materials Management City Hall, 19th Floor, West 100 Queen Street

1

1

2

2

3

3

4

4

5

5

7

7

12

12

13

13

14

14

B B

FF

E E

8

8

Bx Bx

2x

2x

Ax Ax

11

11

15

15

17

17

16

16

9

9

Wsite

Wsite

Ssite

Ssite

E siteE site

18

18

19

19

E southE south

TTC

TTC

20

20

FxFx

6

6

By By

A A

D D

Cx Cx

HH

15x

15x

11x

11x

1x

1x

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SP

SPSPSPSP

SPSPSP

SP

SP

SP

SP SP

SP SP

SP SP

SP

SP

SP

SPSPSPSP

SP

SPSP

SPSP

SPSPSPSP

SPSP

SP SP

SPSP

SPSP

60.4M2(56.0m2 required for 10 toddlers)

58.5M2(56.0m2 required for 10 infants)

181.6M2(179.2m2 required for 32 preschool)

PINK = SU - SINGLE UNIT TRUCK , ZERO CORRECTION

RED = CITY OF TORONTO (FRONT LOADING REFUSE)

EX.MH 23A

Contractor must check and verify all dimensions on the job, and report anydiscrepancies to the Architect before proceeding with the work.

Do not scale this drawing.

CIVIL ENGINEERS

STRUCTURAL ENGINEERS

MECHANICAL ENGINEERS

ELECTRICAL ENGINEERSHYDROGEOLOGICAL ENGINEERS

GEOTECHNICAL ENGINEERS

REV DESCRIPTION DATE

26 of 34

Page 27: 267-2017 Add Nr18 revFINAL - wx.toronto.ca · Michael Pacholok, Chief Purchasing Officer and Director Purchasing & Materials Management City Hall, 19th Floor, West 100 Queen Street

Contractor must check and verify all dimensions on the job, and report anydiscrepancies to the Architect before proceeding with the work.

Do not scale this drawing.

CIVIL ENGINEERS

STRUCTURAL ENGINEERS

MECHANICAL ENGINEERS

ELECTRICAL ENGINEERSHYDROGEOLOGICAL ENGINEERS

GEOTECHNICAL ENGINEERS

REV DESCRIPTION DATE

27 of 34

Page 28: 267-2017 Add Nr18 revFINAL - wx.toronto.ca · Michael Pacholok, Chief Purchasing Officer and Director Purchasing & Materials Management City Hall, 19th Floor, West 100 Queen Street

AD

C

10

10

12

12

13

13

14

14

B

F

E

G

8

8

Bx

Ax

IRRIGATION ROOMP114

11

11

15

15

17

17

16

16

BOILER ROOMP119

9

9

Wsite

E site

18

18

19

19

E south

TTC

TTC

20

20

MECH. VESTP112

TPA SCRUBBERP110

SERVICE VESTIBULEP117

ELECT ROOMP115

Fx

POOL

SER

VICE

TUN

NELS

P120

By

A

D

Cx

POOL MECHANICAL FILTRATIONP206

H

MECHANICAL EXHAUST SHAFTP121 15x

15x

11x

11x

BCC ELEV VEST. P1P102

TPA MAIN ELECTP116

EXIT STAIR CSTR C

EXIT STAIR DSTR D

STAIR KSTR K

BCC ELEV 3ELEV 3

BCC ELEV 4ELEV 4

min 6x3.6m

STAIR C VEST L1P10C

EXIT STAIR CSTR C

P1 PARKINGP100 MAIN COMMS

P118

Ex

PARK

ING

INTA

KE A

IRP3

08

PARKING INTAKE AIRP308

STAIR JSTR J

EXIT STAIR CSTR C

POOL SERVICE TUNNELSP120

POOL

REE

L TUN

NEL

P120

A

MECH INTAKE AIRP207

C

12

12

13

13

14

14

B

F

E

G

8

8

Bx

Ax

11

11

15

15

17

17

16

16

Wsite

E site

18

18

19

19

E south

TTC

TTC

20

20

Fx

By

A

D

Cx

H

15x

15x

11x

11x

Contractor must check and verify all dimensions on the job, and report anydiscrepancies to the Architect before proceeding with the work.

Do not scale this drawing.

CIVIL ENGINEERS

STRUCTURAL ENGINEERS

MECHANICAL ENGINEERS

ELECTRICAL ENGINEERSHYDROGEOLOGICAL ENGINEERS

GEOTECHNICAL ENGINEERS

REV DESCRIPTION DATE

FO

R C

ON

TIN

UA

TIO

N R

EF

ER

T

O D

RA

WIN

G E

302A

28 of 34

Page 29: 267-2017 Add Nr18 revFINAL - wx.toronto.ca · Michael Pacholok, Chief Purchasing Officer and Director Purchasing & Materials Management City Hall, 19th Floor, West 100 Queen Street

1

1

2

2

3

3

4

4

5

5

C

7

7

10

10

B

F

E

G

8

8

Bx

2x

2x

Ax

9

9

Wsite

Ssite

Ssite

E site

E south

OFFICEA104

POOL STORAGEA110

LOBBYG101

10 m²

ELECT/COMMSG102

RECEPTIONA101

Fx

EXIT/SERVICEG107

6

6

RECEPTION ROOMA101ABy

A

D

Cx

H

GARBAGE ROOMG114

STAFF ROOML112

BF WASHROOML114

MIDDLE AGE CHILDRENL110

MEDIA ROOM AL106

PROG

RAM

ROOM

STO

RAGE

L108

OFFICE / PROGRAM PLANNINGL109

LIBRARY CUSTODIALL116

LOUNGEL101

TPA ELEV 1ELEV 1

TPA ELEV 2ELEV 2

ENTRANCE VESTIBULEG100

RECEPTIONL100

WORK ROOML103

1x

1x

PROGRAM ROOML102

6 m²

ELECTRICALL117

STAFF WCL113

6 m²

COMML118 WOMENS WC

G105

MENS WCG103

AQUATICS LOBBYA100

EXIT VESTG109

19 m²

ELECT SWITCH VAULTG113

EXIT STAIR BSTR B

CUSTODIALG112

BCC ELEV 3ELEV 3

BCC ELEV 4ELEV 4

STAIR B EXIT VESTG108

ADULT AREAL104

QUIET STUDYL119

STAIR HSTR H

ADMIN MECH.G111

RECEIVINGG110

TEEN AREAL105

Ex

SERV

ICE

VEST

L115

MEDIA ROOM BL107

EXIT STAIR ASTR A

FD

E.W.

PARKING INTAKE AIRP308

TPA VESTIBULEG100A

Contractor must check and verify all dimensions on the job, and report anydiscrepancies to the Architect before proceeding with the work.

Do not scale this drawing.

CIVIL ENGINEERS

STRUCTURAL ENGINEERS

MECHANICAL ENGINEERS

ELECTRICAL ENGINEERSHYDROGEOLOGICAL ENGINEERS

GEOTECHNICAL ENGINEERS

REV DESCRIPTION DATE

FO

R C

ON

TIN

UA

TIO

N R

EF

ER

T

O D

RA

WIN

G E

303B

29 of 34

Page 30: 267-2017 Add Nr18 revFINAL - wx.toronto.ca · Michael Pacholok, Chief Purchasing Officer and Director Purchasing & Materials Management City Hall, 19th Floor, West 100 Queen Street

DN

DN

1

1

2

2

3

3

4

4

5

5

C

7

7

10

10

B

F

E

G

8

8

Bx

2x

2x

Ax

9

9

Wsite

Ssite

Ssite

E site

E south

PRESCHOOL PLAYROOM 2C208B

LAUN

DRY/

TOY

WAS

HC2

11

TEACHING KITCHENC213

MAINTENANCER201

SOUTH CORRIDORC209

STORAGEC205D

FAMILY STROLLERSC202

L2 LOBBYG200

OFFICEC220

GROSS MOTORC218

LOBBY/WAITINGC217

ELECC210

TODDLER CUBBIESC206A

PRESCHOOL WCC208C

PRESCHOOL CUBBIES 2C208A

KITCHENC215

CC CORRIDORC201

KITCHEN / LOCKERSC224

COMMSR202A

Fx

6

6

CC STROLLERSC203

EXIT VESTC212A

By

SUPERVISORC219

MTGC221

LOUNGEC223

CC WCC222

A

D

ELECTR202

Cx

H

EXIT STAIR A VEST L2C225

SECURITY/COMMC204

1x

1x

CUSTODIALC214

PRESCHOOL PLAYROOM 1C207B

EXIT STAIR LSTR L

TPA ELEV 2ELEV 2

TPA ELEV 1ELEV 1

BCC ELEV 4ELEV 4

BCC ELEV 3ELEV 3

PRESCHOOL CUBBIES 1C207A

INFANT PLAYROOMC205B

INFANT SLEEP ROOMC205C

INFANT / TODDLER WCC206C

INFANT CUBBIESC205A

TODDLER PLAYROOMC206B

18 m²CHILDCARE STORAGE SHED 1

18 m²CHILDCARE STORAGE SHED 2

Ex

EXIT STAIR ASTR A

CUSTODIALR203

MAINT. VESTR201A

Contractor must check and verify all dimensions on the job, and report anydiscrepancies to the Architect before proceeding with the work.

Do not scale this drawing.

CIVIL ENGINEERS

STRUCTURAL ENGINEERS

MECHANICAL ENGINEERS

ELECTRICAL ENGINEERSHYDROGEOLOGICAL ENGINEERS

GEOTECHNICAL ENGINEERS

REV DESCRIPTION DATE

FO

R C

ON

TIN

UA

TIO

N R

EF

ER

T

O D

RA

WIN

G E

304B

30 of 34

Page 31: 267-2017 Add Nr18 revFINAL - wx.toronto.ca · Michael Pacholok, Chief Purchasing Officer and Director Purchasing & Materials Management City Hall, 19th Floor, West 100 Queen Street

DN

DN

DN

DN

C

10

10

12

12

13

13

14

14

B

F

E

G

8

8

Bx

Ax

11

11

15

15

17

17

16

16

9

9

Wsite

E site

18

18

19

19

E south

TTC

TTC

20

20

EXIT STAIR ESTR E

AMENITY / MEETINGR210

MAINTENANCER201

L2 LOBBYG200

VESTIBULEG201

BF WCR205

BF WCR204

MEETING ROOM / OFFICER206

KITCHENR207COMMS

R202A

Fx

By

A

D

STORAGER208A

ELECTR202

Cx

H

ELECT CLS.R211

MEETINGR208

PANTRYR207A

15x

15x

11x

11x

L2 CORRIDORG202

EXIT STAIR DSTR D

BCC ELEV 4ELEV 4

BCC ELEV 3ELEV 3

Ex

CUSTODIALR203

MAINT. VESTR201A

Contractor must check and verify all dimensions on the job, and report anydiscrepancies to the Architect before proceeding with the work.

Do not scale this drawing.

CIVIL ENGINEERS

STRUCTURAL ENGINEERS

MECHANICAL ENGINEERS

ELECTRICAL ENGINEERSHYDROGEOLOGICAL ENGINEERS

GEOTECHNICAL ENGINEERS

REV DESCRIPTION DATE

FO

R C

ON

TIN

UA

TIO

N R

EF

ER

T

O D

RA

WIN

G E

304A

31 of 34

Page 32: 267-2017 Add Nr18 revFINAL - wx.toronto.ca · Michael Pacholok, Chief Purchasing Officer and Director Purchasing & Materials Management City Hall, 19th Floor, West 100 Queen Street

1

1

2

2

3

3

4

4

5

5

C

7

7

10

10

B

F

E

G

8

8

Bx

2x

2x

Ax

9

9

Wsite

Ssite

Ssite

E site

E south

FEMALE WASHROOMR339

DANCE STUDIOR330

FITNESS STUDIOR329

GAMES/LOUNGER300F

CROS

S BR

ACE

BAY

MALE WASHROOMR337

ARTS&CRAFTSR334

MULTI-PURPOSE/MEETINGR326

MULTI-PURPOSE/ARTR323

ROOF TERRACER322

CLASSROOMR335

STORAGER324

STORAGER325

STORAGER328

STORAGER327

Fx

6

6

STORAGER333

CU-1

PUBL

IC C

ORRI

DOR/

SEAT

ING

R300

E

By

EXIT STAIR LSTR L

A

D

ELECTR301A

Cx

H

CLASSROOM STORAGER335A

CLASSROOM WCR336

MEETING ROOMR301

REC CORRIDORR300B

DANC

E FI

TNES

S CO

RRID

ORR3

00C

PUBLIC CORRIDORR300G

REC CORRIDOR/SEATINGR300D

L3 CORRIDORR300

COMMSR301B

1x

1x

ELECTRICALR332

CUSTODIALR331

BCC ELEV 4ELEV 4

BCC ELEV 3ELEV 3

Ex

CROS

S BR

ACE

BAY

L3 CORRIDORR300

Contractor must check and verify all dimensions on the job, and report anydiscrepancies to the Architect before proceeding with the work.

Do not scale this drawing.

CIVIL ENGINEERS

STRUCTURAL ENGINEERS

MECHANICAL ENGINEERS

ELECTRICAL ENGINEERSHYDROGEOLOGICAL ENGINEERS

GEOTECHNICAL ENGINEERS

REV DESCRIPTION DATE

FO

R C

ON

TIN

UA

TIO

N R

EF

ER

T

O D

RA

WIN

G E

305B

32 of 34

Page 33: 267-2017 Add Nr18 revFINAL - wx.toronto.ca · Michael Pacholok, Chief Purchasing Officer and Director Purchasing & Materials Management City Hall, 19th Floor, West 100 Queen Street

C

10

10

12

12

13

13

14

14

B

F

E

G

8

8

Bx

Ax

11

11

15

15

17

17

16

16

9

9

Wsite

E site

POOL HALLA123

18

18

19

19

E south

OFFICEA104

TTC

TTC

20

20

CHEM.A121

VIEWING AREAA123A

DECK SHOWER AA117A

WC CORRIDORA114B

UNIVERSAL CHANGEROOM BA113B

GUARDSA111

CUSTODIALA106

POOL STORAGEA110

STAFF ROOMA105

FIRST AIDA109

FILES/STORAGEA107

STROLLER PARKINGA103A

LOBBYG101

10 m²

ELECT/COMMSG102

AQUATIC CORRIDORA103

WOMEN CHANGEA108

MEN CHANGEA112

POOL STORAGEA122

WCA116A

WCA116B

WCA116C

WCA116D

WCA116E

WCA116F

RECEPTIONA101

DECK SHOWER BA117B

POOL HALLA123

Fx

RECEPTION ROOMA101A By

A

D

Cx

H

10 m²

MECHANICAL EXHAUST SHAFTP121

15x

15x

116 m²

GENERATOR ROOMG115

MECH VESTA118

11x

11x

UNIVERSAL CHANGE BA115B

UNIVERSAL CHANGE AA115A

WC CORRIDORA114A

ELECTA120

AQUATICS LOBBY

AQUATIC CORRIDORA103

EXIT STAIR CSTR C

EXIT STAIR DSTR D

STAIR FSTR F

BCC ELEV 3ELEV 3

BCC ELEV 4ELEV 4

STAIR HSTR H

UNIVERSAL CHANGEROOM AA113A

Ex

MECH INTAKE AIRP207

PARKING INTAKE AIRP308

Contractor must check and verify all dimensions on the job, and report anydiscrepancies to the Architect before proceeding with the work.

Do not scale this drawing.

CIVIL ENGINEERS

STRUCTURAL ENGINEERS

MECHANICAL ENGINEERS

ELECTRICAL ENGINEERSHYDROGEOLOGICAL ENGINEERS

GEOTECHNICAL ENGINEERS

REV DESCRIPTION DATE

FO

R C

ON

TIN

UA

TIO

N R

EF

ER

T

O D

RA

WIN

G E

403A

33 of 34

Page 34: 267-2017 Add Nr18 revFINAL - wx.toronto.ca · Michael Pacholok, Chief Purchasing Officer and Director Purchasing & Materials Management City Hall, 19th Floor, West 100 Queen Street

TPA MAIN ELECTP116

ELECT ROOMP115

6 m²

ELECTRICALL117

6 m²

COMML118

10 m²

ELECT/COMMSG102

OR

ELECC210

SECURITY/COMMC204

BIES

R301A R301B

T

ELECTR406

CUSTODIALR405 ELECTRICAL

R332

C

Cx

Cx

COMMSR202A

ELECTR202

9

C

15

Cx

15x

C

Cx

6

109

C

C

109

B

C

109

MAIN COMMSP118

11 11x

Contractor must check and verify all dimensions on the job, and report anydiscrepancies to the Architect before proceeding with the work.

Do not scale this drawing.

CIVIL ENGINEERS

STRUCTURAL ENGINEERS

MECHANICAL ENGINEERS

ELECTRICAL ENGINEERSHYDROGEOLOGICAL ENGINEERS

GEOTECHNICAL ENGINEERS

REV DESCRIPTION DATE

34 of 34