1. THE CONTRACTOR SHALL EXAMINE ALL CONTRACT DOCUMENTS,
CHECK DIMENSIONS AND REPORT ANY DISCREPANCIES TO THE
ENGINEER FOR CLARIFICATION PRIOR TO COMMENCING
CONSTRUCTION. DISCREPANCIES NOT REPORTED ARE THE
RESPONSIBILITY OF THE CONTRACTOR. CHECK AND VERIFY ALL
DIMENSIONS WITH THE ARCHITECTURAL DRAWINGS BEFORE
COMMENCING WITH ANY WORK. NOTIFY THE ARCHITECT OF ANY
ERRORS OR OMISSIONS.
2. READ STRUCTURAL DRAWINGS IN CONJUNCTION WITH THE
ARCHITECTURAL DRAWINGS
3. TEMPORARY SUPPORT AND TEMPORARY AND PERMANENT
BRACING OF LOAD BEARING AND NON-LOAD BEARING ELEMENTS
DURING CONSTRUCTION TO RESIST DEAD, LIVE AND
CONSTRUCTION LOADS IS THE RESPONSIBILITY OF THE
CONTRACTOR. DESIGN OF THE TEMPORARY SUPPORTS IS THE
RESPONSIBILITY OF THE CONTRACTOR.
4. DO NOT CONSTRUCT FROM THESE DRAWINGS UNLESS MARKED
"ISSUED FOR CONSTRUCTION".
5. THE GENERAL CONTRACTOR SHALL PROVIDE SHOP DRAWINGS
FOR REVIEW BY THE ENGINEER OF RECORD. ALLOW ADEQUATE
TIME FOR REVIEW BY THE ENGINEER OF RECORD PRIOR TO
FABRICATION OR ERECTION. SHOP DRAWINGS SHALL BE
REVIEWED BY THE GENERAL CONTRACTOR PRIOR TO
SUBMISSION FOR REVIEW BY THE ENGINEER OF RECORD. SHOP
DRAWINGS SHALL BE SEALED BY A PROFESSIONAL ENGINEER
REGISTERED IN THE PROJECT PROVINCE OR STATE OF
JURISDICTION. THE SHOP DRAWING ENGINEER SHALL ENSURE
THAT THE FABRICATION AND ERECTION OF THESE ELEMENTS ARE
IN ACCORDANCE WITH THEIR DESIGN AND THAT THE DESIGN IS IN
ACCORDANCE WITH ALL RELEVANT CODES AND REGULATIONS.
SHOP DRAWINGS SHALL BE SUPPLIED FOR REVIEW FOR THE
FOLLOWING BUT NOT LIMITED TO:
* REINFORCING STEEL FOR CONCRETE
* STRUCTURAL STEEL SHAPES AND PLATES
* TIMBER
* ENGINEERED WOOD PRODUCTS
6. ALL DESIGN TO CONFORM TO THE ABC 2006, AND ALL
OTHER APPLICABLE CODES AND PRACTICES AND BEST PRACTICES.
7. FIELD REVIEWS:
NOTIFY THE ENGINEER 48 HOURS IN ADVANCE FOR FIELD
REVIEWS AND APPROVAL OF THE FOLLOWING:
* CONCRETE REINFORCEMENT BEFORE EACH CONCRETE POUR
* STRUCTURAL STEEL BEFORE COVERING UP
* WOOD FRAMING BEFORE COVERING UP
8. DO NOT SCALE FROM THESE DRAWINGS.
9. THE DESIGN HAS BEEN PREPARED BASED ON THE ASSUMPTION
THAT THE OWNER AND/OR OPERATOR HAS A SITE SAFETY PLAN
IN PLACE TO ADDRESS AND MITIGATE SAFETY HAZARDS, BOTH
COMMON AND SPECIFIC TO THIS PROJECT
GENERAL
ABBREVIATIONS
AIFB ASPHALT IMPREGNATED
FIBRE BOARD
ALT. ALTERNATE
ARCH. ARCHITECTURAL
B.C.E. BOTTOM CHORD
EXTENSION
BLL BOTTOM LOWER LAYER
BUL BOTTOM UPPER LAYER
BM. BEAM
BOT. BOTTOM
BPO BAR PLACING ORDER
BTWN BETWEEN
BRG. BEARING
CANT. CANTILEVER
C.J. CONTROL JOINT
CL. CENTER LINE
CLR. CLEAR
COL. COLUMN
CONC. CONCRETE
CONT. CONTINUOUS
C.P. COMPLETE
PENETRATION
C/W COMPLETE WITH
DET DETAIL
D.L. DEAD LOAD
D.O. DO OVER (DITTO)
DP. DEEP
DWG. DRAWING
DWLS DOWELS
E.E. EACH END
E.F. EACH FACE
ELEC. ELECTRICAL
EL. ELEVATION
ELEV. ELEVATION
E.S. EACH SIDE
E.W. EACH WAY
EXIST. EXISTING
EX EXTRA
EXT. EXTERIOR
F.D. FLOOR DRAIN
F.S. FAR SIDE
FTG FOOTING
GALV. GALVANIZED
G.L. GRID LINE
H.1.E. HOOK ONE END
H.2.E. HOOK 2 ENDS
H.D.G. HOT DIPPED GALVANIZED
HOR. HORIZONTAL
HORIZ. HORIZONTAL
I.F. INSIDE FACE
INT. INTERIOR
JT. JOINT
LG. LONG
L.L. LIVE LOAD
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LSH LONG SIDE HORIZONTAL
LSV LONG SIDE VERTICAL
L.V. LENGTH VARIES
L.W. LONG WAY
MAX. MAXIMUM
MECH. MECHANICAL
MIN. MINIMUM
N.I.C. NOT IN CONTRACT
N.S. NEAR SIDE
N.T.S. NOT TO SCALE
O/C ON CENTRE
O.F. OUTSIDE FACE
OPP. OPPOSITE
OWSJ OPEN WEB STEEL JOIST
PLA POINT LOAD ABOVE
P/T PRESSURE TREATED
R.D. ROOF DRAIN
REINF. REINFORCING
R/W REINFORCED WITH
S.D.L. SUPERIMPOSED DEAD
LOAD
SIM. SIMILAR
S.O.G. SLAB ON GRADE
STAG. STAGGERED
STIR. STIRRUP
S.W. SHORT WAY
TEMP. TEMPERATURE
REINFORCING
THK. THICK
THRU THROUGH
T.J. TIE JOIST
TLL TOP LOWER LAYER
T.O. TOP OF
T.O.C. TOP OF CONCRETE
T.O.S. TOP OF STEEL/SLAB
TUL TOP UPPER LAYER
TYP. TYPICAL
T & B TOP AND BOTTOM
T & G TONGUE AND GROOVE
U.N.O. UNLESS NOTED
OTHERWISE
U/S UNDERSIDE
VERT. VERTICAL
WT. WALL THICKNESS
W.P. WORK POINT
DESIGN CODE : (ABC 2006)
IMPORTANCE FACTOR (Is) = 1
ROOF
DEAD LOADS:
ROOFING , FRAMING & INSULATION --------------------------- 0.47 kPa
CEILING, MECHANICAL & ELECTRICAL ------------------------ 0.25 kPa
TOTAL DEAD LOADS ------------------------------------------------- 0.72 kPa
ENVIRONMENTAL LOADS:
DESIGN SNOW LOAD (Ss) ------------------------------------------ 2.00 kPa
RAIN LOAD (Sr) --------------------------------------------------------- 0.10 kPa
SEISMIC DATA:
Sa(0.2) = 0.095
Sa(0.5) = 0.057
Sa(1.0) = 0.026
Sa(2.0) = 0.014
PGA = 0.05
DESIGN DATA
STEEL
1. PROVIDE STRUCTURAL STEEL TO CSA/CAN-G40.20/G40.21 OR ASTM
STANDARD A 992/ A992M. THE FOLLOWING SHOULD HAVE GRADES
MINIMUM OF:
* STRUCTURAL SHAPES GRADE 350W
* HOLLOW STRUCTURAL SECTIONS GRADE 350W CLASS 'C'
* COLUMN BASE PLATES GRADE 300W
* MISCELLANEOUS PLATES GRADE 260W
* PIPE SECTIONS ASTM A53, 241 MPa
WELDING
1. WELDING TO BE METAL ARC WELDING TO CSA W59 BY WELDERS
APPROVED BY THE CANADIAN WELDING BUREAU TO REQUIREMENTS
OF CSA W47.1. CERTIFICATE TO BE MADE AVAILABLE UPON REQUEST
2. WELD REINFORCEMENT STEEL TO CSA W186.
HARDWARE
* BOLTS: ASTM A307, A325, A325M, A490, A490M OR
F182.
* THREADED ROD: ASTM A307
* LAG BOLTS: ASTM A307
* DRIFT PINS: ASTM A307 OR CSA/CAN-G40.21 300W
* SCREWS: GRK RSS, SFS INTEC BLUE MAX OR SPAX
* WASHERS: MALLEABLE CAST IRON
* SPLIT RINGS: 2 1/2"Ø OR 4"Ø AS SPECIFIED
* SHEAR PLATES: ASTM A47 GRADE 32510
* STEEL ROD: ASTM A449 OR ASTM A307
CUSTOM HARDWARE
1. FABRICATE TO CAN/CSA S16.01
2. PROVIDE STEEL TO CSA/CAN-G40.20/G40.21 OR ASTM STANDARD A 992/
A992M. THE FOLLOWING SHOULD HAVE GRADES MINIMUM OF;
STRUCTURAL SHAPES: 350W
HOLLOW STRUCTURAL SECTIONS 350W
COLUMN BASE PLATES 300W
MISCELLANEOUS PLATE 260W
PIPE SECTIONS ASTM A53, 241W
3. HOT DIP GALVANIZE ALL HARDWARE PERMANENTLY EXPOSED TO
WEATHER OR WHERE STAINING OF THE TIMBER IS A CONCERN. ALL
FINISHES TO CLIENT OR ARCHITECTS SPECIFICATIONS.
MATERIAL SPECIFICATIONS
1. FABRICATE AND ERECT STRUCTURAL STEEL TO CSA S16.1.
2. DESIGN OF CONNECTIONS BY STEEL FABRICATOR UNLESS DETAILED ON
THE DRAWINGS. USE MIN. 2 BOLTS PER CONNECTION AND DESIGN FOR
BEARING CONNECTIONS WITH THREADS INCLUDED IN THE SHEAR
PLANE.
3. ANCHOR BOLTS TO ASTM A36 OR A307 UNLESS NOTED. OTHERWISE
STRUCTURAL BOLTS AND NUTS TO ASTM A325 OR A325M-89. TIGHTEN
ALL BOLTS WITH AN IMPACT WRENCH.
4. PROVIDE A CONTINUOUS 35 MPa GROUT BED BENEATH BASE PLATES
AND OTHER CONNECTIONS BEARING ONTO CONCRETE.
5. FRAME OPENINGS IN STEEL DECK GREATER THEN 450mm WITH L90x90x6
MINIMUM.
6. SHOP COAT STEEL SURFACES INTENDED FOR HEATED INTERIOR AREAS
WITH ONE COAT OF PRIMER TO CISC/CPMA 1-73A. USE ONE COAT OF
CGSB 1-GP-40 PRIMER FOR ALL STEEL SURFACES EXPOSED DIRECTLY
TO THE WEATHER AND FOR STEEL IN UNHEATED BUT COVERED AREAS
SUCH AS CANOPIES. PRIMERS MAY BE EXCLUDED ONLY WHERE
SPRAYED FIREPROOFING IS SPECIFIED OR SPECIFICALLY APPROVED BY
THE OWNER AND THE ENGINEER.
7. SUBMIT SHOP DRAWINGS TO THE ENGINEER AND RECEIVE
APPROVAL PRIOR TO FABRICATION. SHOW ALL DETAILS, INCLUDING
FIELD WELDS, AND MATERIAL SPECIFICATIONS. SHOP DRAWINGS TO BE
SEALED BY A PROFESSIONAL ENGINEER FOR DESIGN OF
CONNECTIONS.
8. PROVIDE 10mm THICK BEARING STIFFENERS EACH SIDE OF WEB OR TO
ONE SIDE OF CHANNEL WEB CENTERED OVER THE SUPPORT WHERE
BEAM OR CHANNEL PASSES OVER THE SUPPORT.
9. OPEN WEB STEEL JOIST SEATS TO BE 65mm DEEP WITH 100mm
MINIMUM BEARING UNLESS OTHERWISE NOTED.
10. MISCELLANEOUS STEEL NOT DETAILED ON THE DRAWINGS SUCH AS
STAIRS, RAILINGS, AWNINGS, AND NON-STRUCTURAL ARCHITECTURAL
STEEL SHALL BE DETAILED TO RESIST LOADS AND OTHER EFFECTS TO
THE REQUIREMENTS OFTHE GOVERNING BUILDING CODE.
11. WELDING TO BE METAL ARC WELDING TO CSA W59-03 BY WELDERS
APPROVED BY THE CANADIAN WELDING BUREAU TO THE
REQUIREMENTS OF CSA W47.1.
12. WELD REINFORCEMENT STEEL TO CSA W185. USE WELDABLE
REINFORCEMENT TO CSA G30.18 GRADE 400.
13. MINIMUM SIZE OF FIELD WELD, 2mm LESS THAN THE THICKNESS OF
THE MATERIAL BUT NOT LESS THAN 6mm.
14. TOUCH UP ALL FIELD WELDS WITH PRIMER AFTER SLAG HAS BEEN
REMOVED.
15. OPEN WEB STEEL JOIST (OWSJ) NOTES:
* PROVIDE 65mm DEEP JOIST SEAT U.N.O.
* PROVIDE A MINIMUM OF 65mm BEARING U.N.O.
* SELF WEIGHT OF OWSJ IS INCLUDED IN THE DEAD LOADS
SPECIFIED.
* T.J. INDICATES A BOTTOM CHORD EXTENSION REQUIRED TO
CONNECT TO AN ADJACENT COLUMN.
16. METAL DECK TO BE 38mm PROFILE x 0.762 THK. GALVANISED BUTTON
CLINCH SIDE LAPS @400 O.C.
17. FLAME APPLIED GALVANIZING TO BE USED WHERE SHOP GALVANIZING
HAS BEEN COMPROMISED.
18. STEEL COLUMNS MAY ONLY BE CALLED UP AT THE BASE OF THE COLUMN
AND REFERRED TO AS 'SC' ON PLANS ABOVE.
19. CONTINUOUS COLUMNS TO BE BLOCKED AT ALL FLOOR PENETRATIONS.
STRUCTURAL STEEL
WIND LOADS: HOURLY WIND PRESSURE (1/50) ---------------------- 0.40 kPa
DRAWING LIST
S1.0
GENERAL NOTES
S2.0
MAIN FLOOR PLAN
S2.1
CEILING PLAN
S3.0
SECTIONS AND DETAILS
Site Class : C (ASSUME)
PRODUCT GEOMETRIES MUST MET OR EXCEED THE MINIMUM PROPOSED BY THE
STEEL STUD MANUFACTURES ASSOCIATION FOR INDUSTRY STANDARDIZATION.
FOR SSMA DESIGNATIONS SEE TABLE BELOW.
COLD-FORMED METAL PRODUCT IDENTIFICATION
MEMBER SECTION TABLE
SSMA
IDENTIFICATION
FLANGE
WIDTH
SECTION
S-SECTION
(STUDS)
S137
S162
S200
S250
1
3
8
"
1
5
8
"
2"
2
1
2
"
T-SECTION
(TRACKS)
T125
T200
2
1
4
"
2"
MEMBER THICKNESS TABLE
MIN.
DELIVERED
THICKNESS
MILS
0.0329"
0.0428"
0.0538"
0.0677"
0.0966"
0.1180"
GAUGE
33
43
54
68
97
118
20
18
16
14
12
10
DESIGN
THICKNESS
0.0346"
0.0451"
0.0566"
0.0713"
0.1017"
0.1242"
S1252
1
4
"
MEMBER
DEPTH
SSMA
IDENTIFICATION
3
5
8
"
MEMBER DEPTH
(WEB SIZE) TABLE
6"
8"
10"
362
600
800
1000
SSMA
PRODUCT IDENTIFICATION
800S162-43 (50ksi)
MEMBER
DEPTH
SHAPE
FLANGE WIDTH
MIL THICKNESS
YIELD STRENGTH
(IF GREATER
THAN 33ksi)
USED STEEL STUDS "SCAFCO" OR APPROVED EQUIVALENT
2
1
2
"
250
3
1
2
"
350
S : STUD OR JOIST
T : TRACK
U : CHANNEL
F : FURRING
S2.2
ROOF FRAMING PLAN
S3.1
SECTIONS AND DETAILS
S3.2
SECTIONS AND DETAILS
S3.3
SECTIONS AND DETAILS
S1.0
#1, 6325 - 12 St SE, Calgary, AB T2H 2K1
Calgary Office 403 254 0544
GENERAL NOTES
9
S3.1
#1, 6325 - 12 St SE, Calgary, AB T2H 2K1
Calgary Office 403 254 0544
9
B1
S
C
2
S
C
2
S
C
2
B
1
B
1
B
1
B
1
#1, 6325 - 12 St SE, Calgary, AB T2H 2K1
Calgary Office 403 254 0544
9
T
Y
P
.
B2 B2
#1, 6325 - 12 St SE, Calgary, AB T2H 2K1
Calgary Office 403 254 0544
#1, 6325 - 12 St SE, Calgary, AB T2H 2K1
Calgary Office 403 254 0544
#1, 6325 - 12 St SE, Calgary, AB T2H 2K1
Calgary Office 403 254 0544
SE
E A
RC
H.
#1, 6325 - 12 St SE, Calgary, AB T2H 2K1
Calgary Office 403 254 0544
#1, 6325 - 12 St SE, Calgary, AB T2H 2K1
Calgary Office 403 254 0544