25 October 2012 Gideon Evans LV Network Monitoring Demonstrating the Possibilities.

14
25 October 2012 Gideon Evans LV Network Monitoring Demonstrating the Possibilities

Transcript of 25 October 2012 Gideon Evans LV Network Monitoring Demonstrating the Possibilities.

Page 1: 25 October 2012 Gideon Evans LV Network Monitoring Demonstrating the Possibilities.

25 October 2012Gideon Evans

LV Network MonitoringDemonstrating thePossibilities

Page 2: 25 October 2012 Gideon Evans LV Network Monitoring Demonstrating the Possibilities.

Introduction

• SSE’s Low Carbon homes

• Can LV Network Monitoring equipment be retrofitted without taking customers off supply?

Page 3: 25 October 2012 Gideon Evans LV Network Monitoring Demonstrating the Possibilities.

Understanding the LV Network

• Capacity– Current– MDI Information– Demand and Generation– more informed decisions

• Performance– Voltage Limits– Power Factor– Power Quality / Harmonics– more informed decisions

Time

Capacity

Average Demand

XX:00 XX:30

Demand

Page 4: 25 October 2012 Gideon Evans LV Network Monitoring Demonstrating the Possibilities.

Monitoring Equipment

MDIs

Measuring Current

Measuring Voltage

Transmission of data

Installing Equipment

Storage of data

Calculated data

Rezap

Fault management

Page 5: 25 October 2012 Gideon Evans LV Network Monitoring Demonstrating the Possibilities.

Measuring Current

• Conventional CTs– Installation would require

disruptive substation works– Known choice

• Rogowski Sensors– Can be installed around

existing cable cores– Accuracy considerations

• Innovations– Sentec GRIDKEY current

transducer– Now on the market

Page 6: 25 October 2012 Gideon Evans LV Network Monitoring Demonstrating the Possibilities.

Measuring Voltage

• Terminal Block Connection– Possible on modern fuse cabinets

(eg Lucy Trifca)– Constrained cable routing– Need to drill holes in enclosures?

• Direct Busbar connection– Requires work on live busbars– Connection leads need to be

routed away from operational area

• Innovations– Drummond G clamp– Now on the market

Page 7: 25 October 2012 Gideon Evans LV Network Monitoring Demonstrating the Possibilities.

Data Aggregation

• Manufacturers offered integrated solutions– Current Group offered Open Grid product– GE offered a C650 Relay / RTU, designed to work with ENMAC– Selex Galileo offered their Sentec Gridkey product

• Early versions had limited functionality – They had difficulties with measurement of directional current and harmonics

• Communications– Aerial extensions were required

• Data Storage in the data aggregator– Issues with capacity and reliability

• Cabinets– Issues with size, weight, IP rating and mounting

Page 8: 25 October 2012 Gideon Evans LV Network Monitoring Demonstrating the Possibilities.

Equipment Connection

Page 9: 25 October 2012 Gideon Evans LV Network Monitoring Demonstrating the Possibilities.

Current Group Current Group Open Grid Open Grid

Harmonics

Real and Reactive Power

Chalvey Local s/s

Page 10: 25 October 2012 Gideon Evans LV Network Monitoring Demonstrating the Possibilities.

Selex Galileo / Sentec - GridKey

Page 11: 25 October 2012 Gideon Evans LV Network Monitoring Demonstrating the Possibilities.

Communications

• Modes of Operation– Streamed (Real Time measured data)– Half Hour (Calculated data)– Alarms (Un-solicited data)

• Protocol - DNP3– For use with existing SCADA based control systems– Standardised template was needed

• Storage– Pi Historian

Page 12: 25 October 2012 Gideon Evans LV Network Monitoring Demonstrating the Possibilities.

Further investigation

• Streamline installation process? (Thames Valley Vision Project)

• Equipment life-cycle – what should we expect from manufacturers? (Thames Valley Vision Project)

• Total monitoring system accuracy?

• Monitoring systems’ own energy usage?

Page 13: 25 October 2012 Gideon Evans LV Network Monitoring Demonstrating the Possibilities.

Key Learning Points

• Live retrofitting can be done

• Today’s equipment can monitor complex electrical parameters

• LV network is as unbalanced as we thought!

• Monitoring is a system. Comms and data storage are key features, not bolt on extras

• Manufacturers value access to DNO networks – help them to help you

Page 14: 25 October 2012 Gideon Evans LV Network Monitoring Demonstrating the Possibilities.

Any questions?