Copyright 2012 @LG Electronics / AC Company All Rights ReservedMULTI V III vs CHILLER 0
VS.
CHILLER SYSTEMCHILLER SYSTEM
-
Copyright 2012 @LG Electronics / AC Company All Rights ReservedMULTI V III vs CHILLER 1
1. Design Comparison
VRF is very simplified refrigerant piping system. More flexible VRF is very simplified refrigerant piping system. More flexible than water piping.than water piping.
Chiller
MULTI V III (VRF)Chiller system
Outdoor unit (air-cooled type) Indoor unit Refrigerant piping
Chiller FCU (Fan Coil Unit) AHU (Air Handling Unit)
Systemcomposition
Feature
Cooling tower Water piping, Duct working Water pumps
System concept
DesignDesign CommissioningOperation MaintenanceInstallation Reliability
-
Copyright 2012 @LG Electronics / AC Company All Rights ReservedMULTI V III vs CHILLER 2
Network
Feature Chiller system
Complicated wiring
MULTI V III (VRF)
Simple wiring
DesignDesign CommissioningOperation MaintenanceInstallation Reliability
Easy network wiringEasy network wiring
1. Design Comparison Network design
ACP
-
Copyright 2012 @LG Electronics / AC Company All Rights ReservedMULTI V III vs CHILLER 3
1. Design Comparison Total management
DesignDesign CommissioningOperation MaintenanceInstallation Reliability
[Manufacturer]
VAV boxes supplier
Controlsystem
Feature Chiller system MULTI V III (VRF)
(For VRF) M(For VRF) Manufactureranufacturer
provide all equipmentprovide all equipment
Simple control structureNo additional control provider
Central control and energy monitoring with low cost available
Complicated control structure, additional control manager in the system needed, increasing cost
Third part control provider needed, interconnectivity problems.
-
Copyright 2012 @LG Electronics / AC Company All Rights ReservedMULTI V III vs CHILLER 4
Design Commissioning
MULTI V III (VRF)Chiller system
The systems condition only the necessary rooms with regard to user demands.
The systems commonly condition the entire building at predetermined times, with no regard to user demands.(very hot midnight, weekend, holiday etc)
Capacitycontrol
Feature
After office hours operation, VRF could be operated for the userAfter office hours operation, VRF could be operated for the user
demands.demands.
Operating Area
< Limited operation>
Individual operation
OperationOperation MaintenanceInstallation Reliability
2. Operation Comparison
-
Copyright 2012 @LG Electronics / AC Company All Rights ReservedMULTI V III vs CHILLER 5
Temperaturecontrol
Feature Chiller system
Require1 or 2
MULTI V III (VRF)
Very precise 0.5
Precise temperature controlPrecise temperature control
3030
2525
2020
1515
1010 2020 3030 4040 5050 6060 7070
CoolingCooling
MIN.MIN.
Chiller system MULTI V system
R
o
o
m
t
e
m
p
.
R
o
o
m
t
e
m
p
. 0.5 0 C from set point
Design CommissioningOperationOperation MaintenanceInstallation Reliability
Temp. control2. Operation Comparison
-
Copyright 2012 @LG Electronics / AC Company All Rights ReservedMULTI V III vs CHILLER 6
VRF system doesnVRF system doesnt need a duct space.t need a duct space.
SpaceEfficiency
Feature MULTI V III (VRF)
Small refrigerant space
Chiller system
Large duct space
Design CommissioningOperation MaintenanceInstallationInstallation Reliability
Space (Duct working)3. Installation Comparison
-
Copyright 2012 @LG Electronics / AC Company All Rights ReservedMULTI V III vs CHILLER 7
Chiller
Pump
Boiler
Coolingtower
(On the rooftop)
(Machine room drawing)
OutdoorUnit
(On the rooftop)
(Rooftop drawing)
VRF system is no need for a machine room. VRF system is no need for a machine room.
Installationspace
Feature MULTI V III (VRF)
No need a machine room
Chiller system
Need a machine room
Design CommissioningOperation MaintenanceInstallationInstallation Reliability
Installation space3. Installation Comparison
-
Copyright 2012 @LG Electronics / AC Company All Rights ReservedMULTI V III vs CHILLER 8
Efficient use of space is possible for VRF systemEfficient use of space is possible for VRF system
Chiller system
SpaceEfficiency
Feature
P P
1/3
CHILLER SYSTEMCHILLER SYSTEM
Large pipe shaft is needed for water piping
MULTI V III (VRF)
VRF SystemVRF System
Small pipe shaft is needed
Design CommissioningOperation MaintenanceInstallationInstallation Reliability
Space (Pipe shaft)3. Installation Comparison
-
Copyright 2012 @LG Electronics / AC Company All Rights ReservedMULTI V III vs CHILLER 9
VRF system expansion is very easy with extra outdoor & indoor unVRF system expansion is very easy with extra outdoor & indoor unit.it.
Chiller system
SystemExpansion
Feature
Capacity addition is difficult as additional mechanical room, pump, cooling tower,panel and piping is required.
MULTI V III (VRF)
System Expansion is Easy
+
Design CommissioningOperation MaintenanceInstallationInstallation Reliability
System expansion3. Installation Comparison
-
Copyright 2012 @LG Electronics / AC Company All Rights ReservedMULTI V III vs CHILLER 10
1 step Commissioning6 steps Commissioning
MULTI V Plus
(VRF)Chiller system
Commissioning
Feature
There are a lot of commissioning points for the chiller systemThere are a lot of commissioning points for the chiller system
6 Steps Commissioning 1 Step Commissioning
Water cooled chiller (3)
(4)
Design CommissioningCommissioningOperation MaintenanceInstallation Reliability
NO. of commissioning point4. Commissioning Comparison
-
Copyright 2012 @LG Electronics / AC Company All Rights ReservedMULTI V III vs CHILLER 11
Maintenance
Feature
Maintenance costs for a Multi V is lower than chilled water systMaintenance costs for a Multi V is lower than chilled water systems.ems.
Water cooled chiller (3)
(4)
MULTI V III (VRF)
Filter cleaning Heat exchanger cleaning Cycle check by notebook (LG MV)
Chiller system Filter cleaning Duct cleaning Water pipe maintenance Periodical oil change, overhaul
Pump Water treatment Cooling tower cleaning
Design CommissioningOperation MaintenanceMaintenanceInstallation Reliability
Maintenance list5. Maintenance Comparison
-
Copyright 2012 @LG Electronics / AC Company All Rights ReservedMULTI V III vs CHILLER 12
(For Chiller Water treatment is required for clean water)(For Chiller Water treatment is required for clean water)
Watertreatment
Feature Chiller system
Water treatment is required(deficient service can cause legionary disease in the system)
MULTI V III (VRF)
No water treatment is needed
Design CommissioningOperation MaintenanceMaintenanceInstallation Reliability
Water treatment5. Maintenance Comparison
-
Copyright 2012 @LG Electronics / AC Company All Rights ReservedMULTI V III vs CHILLER 13
Scalecleaning
Feature Chiller system MULTI V III (VRF)
< The system is consist of refrigerant pipes >
No water pipes : No scale (use refrigerant) Need to clean the water pipesSystem efficiency drop & origin of germs
After 2~3year After 5~6year After 7~8year10% 25~30% 35~40%
thickness of scale
Energy Loss
Unit : mm
Unit : %
(For Chiller) Maintenance & cleaning periodically by exclusive c(For Chiller) Maintenance & cleaning periodically by exclusive companyompany
Design CommissioningOperation MaintenanceMaintenanceInstallation Reliability
Scale cleaning5. Maintenance Comparison
-
Copyright 2012 @LG Electronics / AC Company All Rights ReservedMULTI V III vs CHILLER 14
Maintenance Staff5. Maintenance Comparison
Design CommissioningOperation MaintenanceMaintenanceInstallation Reliability
MaintenanceStaff
Feature Chiller system MULTI V III (VRF)
(For Chiller) Certified maintenance staff is needed(For Chiller) Certified maintenance staff is needed
No need special maintenance staff. Economic and easy maintenance
The system requires certified maintenance staff not only for chillers but also pumps, boilers, cooling towers etc.
More expensive maintenance cost.
< Maintenance Staff>
-
Copyright 2012 @LG Electronics / AC Company All Rights ReservedMULTI V III vs CHILLER 15
Pipe Erosion6. Reliability Comparison
Design CommissioningOperation MaintenanceInstallation ReliabilityReliability
PipeErosion
Feature Chiller system MULTI V III (VRF)
(For Chiller) Certified maintenance staff is needed(For Chiller) Certified maintenance staff is needed
Refrigerant does not cause corrosion thereforeno pipe damage occurred
Pipe erosion can cause leakage. System capacity reduction. Brines use increase corrosion, anti corrosion
additives needed
< Water pipe leakage >
-
Copyright 2012 @LG Electronics / AC Company All Rights ReservedMULTI V III vs CHILLER 16
Category Product Initial Cost(USD)Initial Cost(USD)Total
Water Cooled C
hiller
Chiller Price 355,484
877,097AHU / Cooling T ower / Pump, Pr
ice148,065
Installation 383,871
VRVMulti V 874,498
1,109,660Installation 235,161
April 2008Cooling OnlyAir Duct Included
Initial CostInitial Cost Running Cost Maintenance Cost Total cost
Type of Building: Shopping Mall Total area 9,000 m2 : 6 storey Building :1,500 m2/floor Actual cooling area : 1,500 m2 * 80 % * 6 Floor = 7,200 m2 Cooling Load (Tr) / m2 : 700 Tr *12000 Btu/Hr = 1,166 Btu/m2
Equipment : Water cooled chiller /Multi V unit- Water Cooled Chiller :Trane Water cooled chiller
350 Tr x 2 set =700 Tr + 300 Back upPumps =400 Tr x 2 setAHU = 8000 CFM x 36 setCooling Tower =1200 Gpm x 3 +3 Back up
- VRF System :LG Multi V Plus II48 Hp x 19 set=912 Hp 726 Tr
Air conditioning time : Operation- 13 hour a day (09:00 ~ 22:00)- 30 days a month- average load by month
Equipments & Installation costEquipments & Installation cost
MULTI V vs Chiller7. Economic analysis
-
Copyright 2012 @LG Electronics / AC Company All Rights ReservedMULTI V III vs CHILLER 17
Multi V running cost is 65 % compare to chiller
Category Product
RunningCost
(USD)Tota l
Water Cooled C
hiller
Chiller Price
308,697AHU / Coolin g Tower / Pu
mp, Price
Multi V Price 200,158
Based on KW data chiller/Multi VBased on, Thailand electrical standardARI-Air conditioning & Refrigeration Institute
$0k
$100k
$200k
$300k
$400k
year 2n
d 4th 6th 8th 10th
12th
14th
Chiller
Multi V
Running costSavings up to15th yr : 35%
Chiller
Multi V
Electrical costElectrical cost
MULTI V vs Chiller7. Economic analysis
Initial Cost Running CostRunning Cost Maintenance Cost Total cost
-
Copyright 2012 @LG Electronics / AC Company All Rights ReservedMULTI V III vs CHILLER 18
Category PriceMaintenance
Cost(USD)Total
Water Cooled C
hiller
Chiller Price
32,177AHU / Cooling Tower / Pump,
Price
Multi V Price 11,468
$0k
$100k
$200k
$300k
$400k
year 2nd 4th 6th 8th 10th
12th
14th
Chiller
Multi V
Chiller
Multi V
MaintenanceCost savings Up to 15th yr: 66%
Maintenance breakdownChiller system -31 USD / Rt / yr.- 6 times/yrMulti V- 48 USD / Indoor / yr.- 6 times/yr
- 145 USD / Outdoor / yr.- 6 times/yr
Multi V maintenance cost is 24 % compare to chiller
Maintenance costMaintenance cost
MULTI V vs Chiller7. Economic analysis
Initial Cost Running Cost Maintenance CostMaintenance Cost Total cost
-
Copyright 2012 @LG Electronics / AC Company All Rights ReservedMULTI V III vs CHILLER 19
Category Chiller system VRF system Remarks
Economic Analysis
Initial cost (USD) 877,097 927,057
Running cost (USD) 308,698 200,158
Shopping mall 6F,
9,000
Maintenace cost (USD) 32,177 11,468
Total cost (USD) 1,217,972 1,138,683
BEP - 1.7 years
7. Economic analysis
Initial Cost Running Cost Maintenance Cost Total costTotal cost
-
Copyright 2012 @LG Electronics / AC Company All Rights ReservedMULTI V III vs CHILLER 20
LCC (Life Cycle Cost for 15 years) : Chiller 5.99 M$ > Multi V 4.27 M$ (71%)BEP (Break Even Point) : 1.7 Years
LCC (15 years) BEP
1st year 2nd year 3rd year 4th year- 20K$
+10K$
+40K$
+70K$
BEP :1.7 Years
$0k
$1000k
$2000k
$3000k
$4000k
$5000k
$6000k
$7000k
y
e
a
r
1
s
t
2
n
d
3
r
d
4
t
h
5
t
h
6
t
h
7
t
h
8
t
h
9
t
h
1
0
t
h
1
1
t
h
1
2
t
h
1
3
t
h
1
4
t
h
1
5
t
h
Chiller
Multi V
Cost savings : 29%
BEP :1.7 Years
8. LCC
-
Copyright 2012 @LG Electronics / AC Company All Rights ReservedMULTI V III vs CHILLER 21
Chiller Multi V
1,228
1,109877
32
308 200
11
1,3217%
Product &Installation
Maintenance
Electrical Fee
Chiller Multi V
5,992
23%15%
8%
77% 73%
4%
4,27435%
Product &Installation
Maintenance
Electrical Fee
Initial Cost (1st year) ( K US$ )
LCC (15 years)
8. LCC
-
Copyright 2012 @LG Electronics / AC Company All Rights ReservedMULTI V III vs CHILLER 22
Type of building : Shopping mallWater cooled Chiller :350 TR x 2 set=700 Tr + 300Tr (back up)VRF system:48 Hp x 19 set = 912 Hp (726TR)Commercial Building : (Shopping Mall - 9,000 Total Area) - 6 storey building:1500 per floorActual cooling area : 1,500 * 80% * 6F = 7,200Cooling load(TR) / : 700TR * 12,000Btu/h/TR 7,200 = 1167 Btu/
Capacity Price EA Sub total (THB) % Sub total (USD)350 RT 3,960,000 2 7,920,000 255,484 300 RT 3,100,000 1 3,100,000 100,000 400 RT 500,000 2 1,000,000 32,258 400 RT 500,000 1 500,000 16,129
1200 GPM 100,000 3 300,000 9,677 840 GPM 90,000 3 270,000 8,710
8,000 CFM 70,000 36 2,520,000 81,290 15,610,000 57% 503,548
9,000,000 33% 290,323 2,900,000 11% 93,548
11,900,000 43% 383,871 27,510,000 100% 887,419
48 Hp 957,000 19 18,183,000 586,548 Indoor unit ceiling duct 10 Hp 91,355 90 8,221,950 265,224
2,915 90 262,350 8,463 81,125 1 81,125 2,617
141,570 1 141,570 4,567 1,650 57 94,050 3,034 3,300 38 125,400 4,045
27,109,445 79% 874,498
Indoor unit ceiling duct
36,000 90 3,240,000 104,516 7,290,000 21% 235,161
34,399,445 100% 1,109,660
I lot
back up cooling tower (open type)
Duct working
45,000
back up chiller (screw type)
Wired remote controllerCentrol controller (ACP)
Centrol control software (AC Manager)
Sub totalTotal (Product + Installation)
Pump (Evaporator) + 1 back upAHU
Outdoor unit
Sub total
130,645
Y branchODU joint
90 4,050,000
VRF Sub total
Sub total
Outdoor unit
Total (Product + Installation)
Product
Installationduct work
piping & electrical work
Water Cooled Chiller(Screwtype)
Classification
Pipe & InsulationValve & Acc.
Power & Control
Product
Installation
Chiller (screw type)
Cooling tower (open type)
Pump (Condenser) + 1 back up
App. Cost estimation
-
Copyright 2012 @LG Electronics / AC Company All Rights ReservedMULTI V III vs CHILLER 23
Energy consumption
/ unit
Totalenergy
consumption(kW) (kW)271 2 542
14.9 2 29.84 Load 100% 75% 50% 25%55.2 6 331.2 Chillier 542 179 84 472.35 48 112.8 Others 474 474 474 474
1015.84 Total 1016 653 558 521Outdoor Unit 48 HP-R410a 42 19 798Indoor Unit 10 HP CCD 0.8 90 72 Load 100% 75% 50% 25%
870.0 VRF 870 609 287 165
1330
100% kW portion1% 100% 542 100% Used by Schedule 4.2.2 condition
42% 75% 179.2 33% electrical charge in Thailand45% 50% 83.9 15% THB / month USD12% 25% 47.2 9% VRF 517,076 16,680
Chiller 797,469 25,725 Gap 280,393 9,045
Operationhours kWh / day kWh / month
Operationhours kWh / day kWh / month
0.1 113.1 3,393.0 0.1 132.06 3,961.78 5.5 3,325.1 99,754.2 5.5 3,565.60 106,967.95 VRF 200,158 5.9 1,679.5 50,386.1 5.9 3,262.78 97,883.37 Chiller 308,698 1.6 257.9 7,736.0 1.6 812.82 24,384.67
13.0 5,375.6 161,269.3 13.0 7,773.3 233,197.8
VRF system
Cooling load portion IPLV100% cooling load
VRF (MULTI V system) Chiller system
75% cooling load50% cooling load25% cooling load
VRF
AHU-10 tr
Total
operating time / day (hours)operating day / month
ChillerPower consumptionLoad
operating cost 1 year
Chiller system
Category EA
Total
Power consumption under partial loadWater Cooled Chiller(Screwtype)
Chiller-350 TrCooling tower-1260 GPM
Pump-50 Hp
App. Actual running cost
-
Copyright 2012 @LG Electronics / AC Company All Rights ReservedMULTI V III vs CHILLER 24
Cost Unit350 RT 105,000 Baht/unit 2 210,000 400 RT 60,000 Baht/unit 2 120,000
1200 GPM 15,600 Baht/unit 6 93,600 15 RT 2,000 Baht/unit 70 140,000
2 persons 20,000 Baht/unit 12 240,000 803,600
840 Hp 3,000 Baht/unit 90 270,000 Outdoor unit 4,500 19 85,500
355,500
THB USD RemarksChiller 997,500 32,177 6 times / year
270,000 6 times / year85,500 6 times / year
355,500 11,468
Pump
TotalVRF
1500 THB / indoor unit, year4500 THB / ODU module, yea
950 THB / RT, year
Control engineer
Chiller(Screwtype)
Chiller (Screw type)Cooling tower
AHU
Total
TotalVRF
Indoor unit
A noteCategory CapacityMaintenance cost
EA Maintenancecost / year
App. Maintenance cost
-
Copyright 2012 @LG Electronics / AC Company All Rights ReservedMULTI V III vs CHILLER 25
ARI Released The New Standard in 2003
Available through the ARI web site:WWW.ARI.ORG
Portion by cooling load (%)Portion by cooling load (%)
IPLVIPLVOROR
APLVAPLV==
0.010.01 + + 0.420.42 + + 0.450.45 + + 0.120.12A B C DA B C D
11
kW / kW (ARI Part load weighting factors)
1% 1% 42% 45% 42% 45% 12%12%
100% 75% 50% 25%100% 75% 50% 25%
WEIGHTED (%)WEIGHTED (%)
ARI550/590ARI550/590--20032003
Cooling LoadCooling Load
App. Energy efficiency (IPLV)
Slide Number 1Slide Number 2Slide Number 3Slide Number 4Slide Number 5Slide Number 6Slide Number 7Slide Number 8Slide Number 9Slide Number 10Slide Number 11Slide Number 12Slide Number 13Slide Number 14Slide Number 15Slide Number 16Slide Number 17Slide Number 18Slide Number 19Slide Number 20Slide Number 21Slide Number 22Slide Number 23Slide Number 24Slide Number 25ARI Released The New Standard in 2003