Pipe SizingPIPE SIZING CALCULATIONSl. No.Line DescriptionFlowFlowPressurePressureVelocityVelocityTemp.FlowCalculated Pipe SizeSelected Pipe NBPipe ODThicknessStandardPipe IDActual Velocity(Nm3/hr)(Nm3/min)Kg/cm2 (g)Kg/cm2 (a)(m/sec)(m/min)deg. C(m3/min)mmmmmmmmmm(m/sec)INSTRUMENT AIR PIPE SIZING ( Refer to Equipment Selection Calculation)1IA line from Air Drier to IA Receiver1202.008.09.031590050.00.27119.572533.44.5524.39.732IA line to Thermax Package (Thermax Data)350.588.09.031590050.00.07910.572533.44.5524.32.843IA line to Siemens Package300.508.09.031590050.00.0689.782533.44.5524.32.434IA to Others50.088.09.031590050.00.0113.992533.44.5524.30.411IA line from Both Unit #1 & #22404.008.09.031590050.00.54127.674048.265.0838.17.91PLANT AIR PIPE SIZING1Compressor Outlet Line3005.008.09.031590050.00.67730.944048.265.0838.19.892SA Line to Thermax Boiler Area-1.308.09.031590050.00.17615.782533.44.5524.36.323SA Line to Air Drier1202.008.09.031590050.00.27119.572533.44.5524.39.734SA Line CW Pump House1001.678.09.031590050.00.22617.862533.44.5524.38.105SA Line to Turbine Building1001.678.09.031590050.00.22617.862533.44.5524.38.10scfmSm3/hrNm3/hrIA to Boiler By Thermax2033.9802231.131060152935(say)