2208e/2204e Installation and Operating handbook issue 3

132
Installation and operation handbook 2208e 2204e TEMPERATURE CONTROLLERS ENG

Transcript of 2208e/2204e Installation and Operating handbook issue 3

Page 1: 2208e/2204e Installation and Operating handbook issue 3

Installation and operationhandbook

2208

e22

04e

TEMPERATURECONTROLLERS

ENG

Page 2: 2208e/2204e Installation and Operating handbook issue 3
Page 3: 2208e/2204e Installation and Operating handbook issue 3

Installation and Operation Handbook Contents

2208e and 2204e Controller Handbook Part No. HA026696 Issue 3.0 Nov-03 a-1

MODELS 2208e and 2204e TEMPERATURE CONTROLLERS

INSTALLATION AND OPERATION HANDBOOK

1 Chapter 1 OPERATION Page 1.1 FRONT PANEL LAYOUT................................................................1-2

1.2 GETTING STARTED .......................................................................1-4 1.2.1 Viewing The Process Value and Setpoint............................................1-4 1.2.2 To Adjust The Setpoint ........................................................................1-4 1.2.3 Viewing The Display Units ...................................................................1-5 1.2.4 Use Of The “SCROLL” Button .......................................................1-5 1.2.5 Use Of The ‘PAGE’ Button .............................................................1-6

PARAMETER LISTS .................................................................................1-7

1.4 MANUAL OR AUTOMATIC CONTROL..........................................1-8 1.4.1 Selecting Auto/Manual Operation ........................................................1-8 1.4.2 How To Manually Adjust Output Power ...............................................1-9

1.5 SUMMARY.......................................................................................1-9

1.6 Selecting SETPOINT 1 OR SETPOINT 2.....................................1-10

1.7 RAMP DWELL FUNCTION ...........................................................1-11 1.7.1 To Set up a Ramp/Time Program......................................................1-11 1.7.2 To Run the Program ..........................................................................1-12 1.7.3 Power Failure During Program Run...................................................1-12

1.8 LOCATION OF PARAMETERS - BLOCK DIAGRAM ..................1-13

1.9 NAVIGATION DIAGRAM (Part A) .................................................1-14

NAViGATION Diagram (Part B)..............................................................1-15 1.10 parameter tables ............................................................................1-16 1.10.2 Alarm List .......................................................................................1-17 1.10.3 Autotune List ..................................................................................1-17 1.10.4 PID List...........................................................................................1-18 1.10.5 Setpoint List ...................................................................................1-19 1.10.6 Input List ........................................................................................1-20 1.10.7 On/Off List ......................................................................................1-20 1.10.8 Output List......................................................................................1-21 1.10.9 Communications List......................................................................1-21 1.10.10 Access List .....................................................................................1-21

1.11 ALARMS.....................................................................................1-22 1.11.1 Types of Alarm Used in the 2200...................................................1-22

1.12 ALARM RELAY OUTPUT ..........................................................1-23 1.12.1 SETTING ALARM LEVELS............................................................1-24 1.12.2 ALARM INDICATION AND ACKNOWLEDGEMENT .....................1-25 1.12.3 DIAGNOSTIC ALARMS .................................................................1-26

Page 4: 2208e/2204e Installation and Operating handbook issue 3

Contents Installation and Operation Handbook

a-2 2208e and 2204e Controller Handbook Part No. HA026696 Issue 3.0 Nov-03

2 Chapter 2 INSTALLATION 2-1

2.2 INSTRUMENT LAYOUTS ...............................................................2-2 2.2.2 Outline Dimensions Model 2208e........................................................ 2-3 2.2.3 Outline Dimensions Model 2204e........................................................ 2-3

2.3 INTRODUCTION .............................................................................2-4 2.3.2 Controller labels .................................................................................. 2-4

2.4 MECHANICAL INSTALLATION......................................................2-4 2.4.2 Unplugging and plugging-in the controller........................................... 2-4

2.5 WIRING............................................................................................2-5 2.5.2 Wire Sizes ........................................................................................... 2-6 2.5.3 Wiring connections.............................................................................. 2-6 2.5.4 Sensor input connections .................................................................... 2-7 2.5.5 Outputs 1 and 2 connections............................................................... 2-7

2.6 PDS MODES....................................................................................2-8

2.7 SNUBBERS .....................................................................................2-8

Typical single loop wiring diagram........................................................2-9

2.9 RS 232/485/422 Communication connections...........................2-10 2.9.2 Wiring of EIA-485 serial communication links ................................... 2-11

2.10 DEVICENET WIRING TO SERIES 2200E CONTROLLERS.....2-12 2.10.2 DeviceNet Terminal Functions....................................................... 2-12 2.10.3 Wiring Interconnections for DeviceNet Communications............... 2-13

3 Chapter 3 ACCESS LEVELS 3-1

3.2 THE DIFFERENT ACCESS LEVELS..............................................3-2

3.3 SELECTING AN ACCESS LEVEL ..................................................3-3 3.3.2 Returning to Operator Level ................................................................ 3-5

3.4 EDIT LEVEL ....................................................................................3-5 3.4.2 Hiding or revealing a complete list ...................................................... 3-6 3.4.3 Promoting a parameter........................................................................ 3-6

Page 5: 2208e/2204e Installation and Operating handbook issue 3

Installation and Operation Handbook Contents

2208e and 2204e Controller Handbook Part No. HA026696 Issue 3.0 Nov-03 a-3

4. Chapter 4 TUNING ..............................................................................4-1

4.1. WHAT IS TUNING? .........................................................................4-2

4.2. AUTOMATIC TUNING.....................................................................4-3 4.2.1. Heating and Cooling Output Cycle Times............................................4-3

4.3. HOW TO TUNE................................................................................4-4 4.3.1. Typical automatic tuning cycle.............................................................4-5 4.3.2. Calculation of the cutback values ........................................................4-5

4.4. MANUAL TUNING...........................................................................4-6 4.4.1. Setting the cutback values...................................................................4-7 4.4.2. Integrating action and manual reset ....................................................4-8 4.4.3. Automatic droop compensation (Adc) .................................................4-8

5. Chapter 5 CONFIGURATION 5-1

5.1 SELECTING CONFIGURATION LEVEL 5-2

5.2 SELECTING A CONFIGURATION PARAMETER 5-3

5.3 LEAVING CONFIGURATION LEVEL 5-3

5.4 STEPS INVOLVED IN CONFIGURING A CONTROLLER 5-3

5.5 NAVIGATION DIAGRAM (PART A) 5-4

5.6NAVIGATION DIAGRAM (PART B) 5-5

5.7 CONFIGURATION PARAMETER TABLES 5-7

5.8 CONFIGURATION OF DIGITAL COMMUNICATIONS …………5-16

5.8.1. To Configure the Function and Baud Rate…………………………… 5-16 5.8.2. To Set Instrument Address…………………………………………… 5-17

5.9 DEVICENET…………………………………………………………… 5-17 5.9.1. The EDS File…………………………………………………………… 5-17 5.9.2. ODVA Compliance…………………………………………………… 5-17

6 Chapter 6 USER CALIBRATION..........................................................6-1

6.8 WHAT IS THE PURPOSE OF USER CALIBRATION? ..................6-2

6.9 USER CALIBRATION ENABLE......................................................6-3

6.10 SINGLE POINT CALIBRATION...................................................6-4

6.11 TWO POINT CALIBRATION........................................................6-5

6.12 CALIBRATION POINTS AND CALIBRATION OFFSETS...........6-6

Page 6: 2208e/2204e Installation and Operating handbook issue 3

Contents Installation and Operation Handbook

a-4 2208e and 2204e Controller Handbook Part No. HA026696 Issue 3.0 Nov-03

7 Chapter 7 ALARM CONFIGURATION.................................................7-1

7.1 DEFINITION OF ALARMS AND EVENTS ......................................7-2 7.1.1 Types Of Alarms.................................................................................. 7-2

7.2 DIGITAL OUTPUT FUNCTIONS.....................................................7-4

7.3 STEP1 - CONFIGURING THE FOUR ‘SOFT’ ALARMS ................7-5

7.4 STEP 2 - ATTACHING AN ALARM TO A PHYSICAL OUTPUT....7-6

7.5 STEP 3 - GROUPING ALARMS ON A SINGLE OUTPUT .............7-7

7.6 STEP 4 - REMOVING ALARMS FROM AN OUTPUT....................7-7

8. Chapter 8 MOTORISED VALVE CONTROL .....................................8-1

8.1. PARAMETERS FOR MOTORISED VALVE CONTROL.................8-2

8.2. COMMISSIONING THE MOTORISED VALVE CONTROLLER.....8-2 8.2.1. Adjusting the minimum on-time ‘Ont.H............................................ 8-2

8.3. MOTORISED VALVE APPLICATIONS...........................................8-3 8.3.1. Auto Tuning ......................................................................................... 8-3 8.3.2. 2200e Valve Positioner Set-up Table .................................................. 8-3

9 Chapter 9 LOAD CURRENT MONITORING AND DIAGNOSTICS 9-1

9.1 LOAD CURRENT MONITORING AND DIAGNOSTICS ...............9-2

9.2 EXAMPLE WIRING DIAGRAM (FOR MODE 1 & 2 OPERATION)9-3

Example Wiring Diagram (for mode 5 operation) ..............................9-4

9.4 OPERATION..................................................................................9-5 To Read Load Current (modes 2 and 5 only) ................................................. 9-5 9.1.2 To Display Load Current Continuously in the Lower Readout (modes 2

and 5 only) ....................................................................................... 9-5 9.1.3 Display Modes.................................................................................. 9-5 9.1.4 How Heater Alarms Are Displayed................................................... 9-6

9.5 TO SET THE ALARM TRIP LEVELS............................................9-7

9.6 Relay Outputs...............................................................................9-7

9.7 TO CONFIGURE PDS LOAD CURRENT DIAGNOSTICS ...........9-8 9.1.5 To configure the Logic Module for PDS modes 1 or 2 ..................... 9-8 9.1.6 To configure logic input a for pds (Mode 5 only) .............................. 9-9

To Configure Low and High Current Trip Alarms............................9-10

9.9 TO ATTACH SOFT ALARMS TO A RELAY OUTPUT ...............9-11

9.10 THE SCALING FACTOR.........................................................9-12 9.1.7 To adjust the scaling factor ............................................................ 9-12

Page 7: 2208e/2204e Installation and Operating handbook issue 3

Installation and Operation Handbook Contents

2208e and 2204e Controller Handbook Part No. HA026696 Issue 3.0 Nov-03 a-5

10 Chapter 10 RETRANSMISSION ...................................................10-1

10.1 WHAT IS RETRANSMISSION.................................................10-2

10.2 TO CONFIGURE RETRANSMISSION ....................................10-3

10.3 SCALING RETRANSMITTED OUTPUT SIGNALS.................10-4 10.1.1 To Range Retransmitted Output OP .........................................10-4 10.1.2 To Range Retransmitted Setpoint SP or Process Variable PV10-5 10.1.3 To Range Retransmitted Error Err ..........................................10-5

Appendix A UNDERSTANDING THE ORDERING CODE ........ A-1

Appendix B SAFETY & EMC INFORMATION ........................ B-1

TECHNICAL SPECIFICATION .......................... B-6

This product is covered by one or more of the following US Patents: 5,484,206 and 5,793,754; Additional patents pending.

PDSIO is a registered trademark of Eurotherm.

INSTANT ACCURACY™, SSRx Load Doctor™ and SSRx Enhanced Load Doctor ™ are trademarks of Eurotherm.”

Page 8: 2208e/2204e Installation and Operating handbook issue 3

Contents Installation and Operation Handbook

a-6 2208e and 2204e Controller Handbook Part No. HA026696 Issue 3.0 Nov-03

Symbols in Use In This Handbook

Useful information

Button Operation

Caution, (refer to theaccompanying documents)

Functional earth(ground) terminal!

i !

Page 9: 2208e/2204e Installation and Operating handbook issue 3

Installation and Operation Handbook Operation

2208e and 2204e Controller 1-1

Chapter 1 OPERATION

1.1 FRONT PANEL LAYOUT .................................................................2

1.2 GETTING STARTED.........................................................................4 1.2.1 Viewing The Process Value and Setpoint .............................................4 1.2.2 To Adjust The Setpoint..........................................................................4 1.2.3 Viewing The Display Units.....................................................................5 1.2.4 Use Of The “SCROLL” Button .........................................................5 1.2.5 Use Of The ‘PAGE’ Button ..............................................................6

PARAMETER LISTS ..................................................................................7

1.4 manual or automatic control ..........................................................8 1.4.1 Selecting Auto/Manual Operation .........................................................8 1.4.2 How To Manually Adjust Output Power.................................................9

1.5 SUMMARY ........................................................................................9

1.6 Selecting SETPOINT 1 OR SETPOINT 2 ......................................10

1.7 RAMP DWELL FUNCTION.............................................................11 1.7.1 To Set up a Ramp/Time Program .......................................................11 1.7.2 To Run the Program............................................................................12 1.7.3 Power Failure During Program Run ....................................................12

1.8 Location of Parameters - Block Diagram ....................................13

1.9 NAVIGATION DIAGRAM (Part A)...................................................14

NAViGATION Diagram (Part B) ...............................................................15

1.10 parameter tables.........................................................................16 1.10.1 HOME Display .................................................................................16 1.10.2 Alarm List.........................................................................................17 1.10.3 Autotune List....................................................................................18 1.10.4 PID List ............................................................................................18 1.10.5 Setpoint List.....................................................................................19 1.10.6 Input List ..........................................................................................20 1.10.7 On/Off List .......................................................................................20 1.10.8 Output List .......................................................................................21 1.10.9 Communications List .......................................................................21 1.10.10 Access List ......................................................................................21

1.11 alarms..........................................................................................22 1.11.1 Types of Alarm Used in the 2200 ....................................................22

1.12 Alarm relay output......................................................................23 1.12.1 SETTING ALARM LEVELS .............................................................24 1.12.2 ALARM INDICATION AND ACKNOWLEDGEMENT.......................25 1.12.3 DIAGNOSTIC ALARMS...................................................................26

Page 10: 2208e/2204e Installation and Operating handbook issue 3

Operation Installation and Operation Handbook

1-2 2208e and 2204e Controller

1.1 FRONT PANEL LAYOUT

Figure 1-1 Model 2208e front panel layout

Figure 1-2 Model 2204e front panel layout

Page Button

Scroll Button

Down Button

Up Button

Manual mode

Setpoint 2 active PDS Remote Setpoint

Setpoint rate limit active

20.0.0 20.0.0

OP1 OP2

SP2 REM

2208e

Output 1 Output 2

Upper readout

Lower readout

Down Button

Manual mode

Page Button

Scroll Button

Up Button

Remote Setpoint

Output 2

Upper readout

Lower readout

Output 1

Setpoint 2 active

Setpoint rate limit active

20.00 20.00

OP1 OP2

2204e

SP2 REM

Page 11: 2208e/2204e Installation and Operating handbook issue 3

Installation and Operation Handbook Operation

2208e and 2204e Controller 1-3

Button or indicator

Name Explanation

OP1 Output 1 When lit, it indicates that heating output is on.

OP2 Output 2 When lit, it indicates that cooling output is on.

SP2 Setpoint 2 When lit, this indicates that Setpoint 2 has been selected.

REM Remote Setpoint When lit, this indicates that the PDS remote Setpoint input has been selected. ‘REM’ is also used to indicate that user comms is active.

MAN Manual light When lit, it indicates that manual mode has been selected

RUN Run light When lit, it indicates that Setpoint rate limit is active.

Page button Press to select a new list of parameters.

Scroll button Press to select a new parameter in a list.

Down button Press to decrease a value in the lower readout.

Up button Press to increase a value in lower readout.

Figure 1.3 Controller buttons and indicators

For Valve Positioning, please refer to Appendix D ‘Motorised Valve Control i

Page 12: 2208e/2204e Installation and Operating handbook issue 3

Operation Installation and Operation Handbook

1-4 2208e and 2204e Controller

1.2 GETTING STARTED

Thank you for selecting the 2208e/2204e controller. This section shows the principle of operation.

1.2.1 Viewing The Process Value and Setpoint Install and wire up the controller in accordance with Chapter 2 and switch on. Following a 3 second self-test sequence, this is the display you will see,

Figure 1.4 The “Home Display”

The display may flash an alarm message. Refer to the Parameter Tables later in this chapter for a complete list and meaning of the messages.

1.2.2 To Adjust The Setpoint

Figure 1.5 The lower readout shows the setpoint

After 2 seconds the lower readout will ‘blink’ indicating that the new value has been accepted. For everyday use you may not need to do anymore than this.

Output 1

Actual Temperature (Process Value)

Output 2

Required Temperature (Setpoint)

20.023.0

OP1 OP2

! " Press and hold to increase temperature

Press and hold to decrease temperature

20.0140.0

OP1 OP2

Page 13: 2208e/2204e Installation and Operating handbook issue 3

Installation and Operation Handbook Operation

2208e and 2204e Controller 1-5

1.2.3 Viewing The Display Units

Figure 1.6 Pressing or will flash the display units for 0.5 secs

If you get lost, pressing and together will return you to the Home display

1.2.4 Use Of The “SCROLL” Button Pressing the scroll button will display the output power level. Continued pressing will display further parameters in the operator scroll list.

Figure 1.6 Upper readout is parameter name. Lower is value

Keep pressing to return to the Home display or select further parameters (if available)

2nd press

3rd press

Output

Actual output level % OPOPOPOP 100.0100.0100.0100.0

Manual/Auto

Actual state m m m m----AAAA AutoAutoAutoAuto

Display Units CCCC Degrees CentigradeFFFF Degrees Farenheit KKKK Degrees Kelvin

No units - Linear inputs

Momentarily press either button ! !

0.5 sec.

23.0 C

20.020.020.020.0

140.0140.0140.0140.0

i

Page 14: 2208e/2204e Installation and Operating handbook issue 3

Operation Installation and Operation Handbook

1-6 2208e and 2204e Controller

1.2.5 Use Of The ‘PAGE’ Button

The “PAGE” button accesses parameter LISTS. Parameters are settings in the instrument which, generally, can be changed by the user to suit the process. Examples are: Alarms, Self Tune, etc. They are found under headings called LISTS and a full set is given later in this chapter.

Figure 1.7 Press to choose a parameter list

The actual list headings may be longer or shorter than indicated above and you can customise this for the operator’s convenience in EDIT level, Chapter 3.

Keep pressing to select more list headings

1st press

0.2 sec.

23.023.023.023.0 CCCC 20.0 20.0 20.0 20.0

1400140014001400

3rd press 2nd press

ALALALAL

LiStLiStLiStLiSt atunatunatunatun LiStLiStLiStLiSt

22220.00.00.00.0

14.0014.0014.0014.00

i

Page 15: 2208e/2204e Installation and Operating handbook issue 3

Installation and Operation Handbook Operation

2208e and 2204e Controller 1-7

1.3 PARAMETER LISTS

Press to choose a LIST - “ALARMS” is a good one. This list allows you to set the alarm trip levels. The parameters which appear in the list will vary according to the configuration of your controller.

Figure 1.8 Choose a list. Press to select a parameter

If, at any time, no key is pressed within 45 seconds, the display will always return to the “HOME” display.

A complete description of the parameter lists is given on page 1-14.

or to change trip level

or to change trip level

1st press !

2nd press

0.2 sec.

23.023.023.023.0 CCCC

20.0

140.0

There are 4 alarms in the controller. The first character is the alarm number. The following three letters indicate alarm type as follows:

----FSLFSLFSLFSL Full Scale Low

----FSHFSHFSHFSH Full Scale High

----ddddHiHiHiHi Deviation High

----dLodLodLodLo Deviation Low

----dEvdEvdEvdEv Deviation Band

----LcrLcrLcrLcr Low current

----HcrHcrHcrHcr High current Disabled alarms will not be displayed. Chapter 7 gives a full description of alarms.

Alarm List

Alarm 1

Now press the SCROLL button

2nd press

ALALALAL

LiStLiStLiStLiSt

1111------------

50.050.050.050.0

2222------------

2000200020002000

Keep pressing 1. to scroll through further parameters 2. to return to list header

Alarm 2

i

Page 16: 2208e/2204e Installation and Operating handbook issue 3

Operation Installation and Operation Handbook

1-8 2208e and 2204e Controller

1.4 MANUAL OR AUTOMATIC CONTROL

The controller can be used in two modes: Automatic mode - in which the output power is automatically adjusted to hold the temperature at the required value. The controller normally operates in this mode. Manual mode - in which the output is manually adjusted by the Operator. In this mode the ‘MAN’ light will be on.

One other mode is available: Remote setpoint - The setpoint is generated as an input signal from a master 2000 series controller. In this mode the REM light is on.

1.4.1 Selecting Auto/Manual Operation

Figure 1.9 Auto/Manual select

or to select

2 sec.

23.023.023.023.0 CCCC

20.020.020.020.0

1st press

Output

Actual output level %

Manual/Auto

AutoAutoAutoAuto automatic mode ManManManMan manual mode

2nd press

3rd press

OP OP OP OP

100.0100.0100.0100.0

mmmm----AAAA

mAnmAnmAnmAn

Keep pressing to return to “HOME” display

Page 17: 2208e/2204e Installation and Operating handbook issue 3

Installation and Operation Handbook Operation

2208e and 2204e Controller 1-9

1.4.2 How To Manually Adjust Output Power

Figure 1.10 The “Home Display” in manual mode

1.5 SUMMARY

To step through list headers press the Page button until the required header is obtained To step through parameters within a particular list press the Scroll button until the required parameter is obtained To change the value (or state) of a parameter press the Raise button or the Lower button The remainder of this chapter provides a complete list of all parameters available.

Actual Temperature (Process Value) 20.020.020.020.0 50.050.050.050.0

OP1 OP2

Output Power Demand

Manual Indicator on

! " Press and hold to increase power

Press and hold to decrease power

Manual mode is generally used for test and commissioning purposes, take care not to leave the controller in this mode since damage or personal injury could occur.

i

Page 18: 2208e/2204e Installation and Operating handbook issue 3

Operation Installation and Operation Handbook

1-10 2208e and 2204e Controller

1.6 SELECTING SETPOINT 1 OR SETPOINT 2

The instrument has the facility to select two setpoints. This may be useful, for example, where it is required to switch control between two different setpoints or to control in a standby condition, thus avoiding the necessity to change the setpoint manually each time.

To Select Setpoint 1 orSetpoint 2

This may be done in two ways:- 1. By an external switch or relay contact wired to a digital input 2. Through the front panel using the SP list

Figure 1-11 To Select Setpoint 1 or 2

Press to select SP list 20.0

140.0

Setpoint List

Press scroll button to SSEL

SPSPSPSP

LiStLiStLiStLiSt

SSELSSELSSELSSEL

SP 1SP 1SP 1SP 1 Press or to change between SP 1 and SP 2

When setpoint 2 is selected the SP2 beacon illuminates.

Page 19: 2208e/2204e Installation and Operating handbook issue 3

Installation and Operation Handbook Operation

2208e and 2204e Controller 1-11

1.7 RAMP DWELL FUNCTION

The ramp dwell function is selected by turning the setpoint rate limit parameter SPrr to a value. It can be set to RUN in two ways:-

1. Through the front panel using the SP list 2. By an external switch or relay contact wired to a digital input configured for reset

(rset). When closed the program will reset. When open the program will run. To run the program from the initial reset state, it is necessary to first close the switch then open it.

The controller will then ramp from setpoint 1 to setpoint 2 at a rate set by the SPrr parameter.

When the controller reaches setpoint 2 it can remain at this level for a timed period, using the dwel parameter.

At the end of the dwell period the action of the controller is determined by the End Type parameter End.t.

1.7.1 To Set up a Ramp/Time Program Set setpoint 1 to the value at which to start the ramp. Set setpoint 2 to the value which you wish to ramp to. This is described in the previous section.

Now press until SPrr is displayed

Figure 1-12 Ramp/Dwell Program

In Run mode the controller will ramp from SP 1 to SP 2 at 20.0 units per minute

Press scroll button to dwEl

SPrrSPrrSPrrSPrr 20.020.020.020.0

dweldweldweldwel 60.060.060.060.0

Press or to set the SP ramp rate in units per minute

Press or to set the dwell time in minutes

In Run mode the controller will dwell at SP 2 for 60 minutes

Press scroll button to End.t

End.tEnd.tEnd.tEnd.t rSEt rSEt rSEt rSEt Press or to choose

the action required at the end of the dwell time

In Run mode the controller will reset at the end of the dwell time. Other choices are:-

HoLd The program will go into Hold StbY The program will go into

standby dwel The program will dwell for an

unlimited period

Page 20: 2208e/2204e Installation and Operating handbook issue 3

Operation Installation and Operation Handbook

1-12 2208e and 2204e Controller

1.7.2 To Run the Program In Full access level the Status of the program can be read as follows:- A program may also be reset or run using an external switch contact if a digital input has been configured. See Configuration section.

Figure 1-13 To Run the Ramp/Dwell Program

1.7.3 Power Failure During Program Run 1. During Ramp. After return of power, the working setpoint will servo to the current PV

value, and the ramp continues to SP2 followed by the timed dwell.

2. During Dwell. After return of power the working setpoint will servo to PV, the ramp continues to SP2 followed by full programmed dwell. In effect this causes the program to restart.

Use the Hide, Reveal and Promote features to customise the display for a programmer. See Chapter 3.

From the previous view, press scroll button to ProG

ProgProgProgProg run run run run

Press or to choose run

To reset the controller to start conditions, select rSEt

i

From the previous view, press scroll button to StAt

StAtStAtStAtStAt rmp rmp rmp rmp

The status may be any one of the following:

rmp Ramping from SP1 to SP2

dwel Dwelling at SP2

End The program is complete.

If End.t = rSEt, End will flash briefly before changing to OFF

OFF The program is in the reset state

Page 21: 2208e/2204e Installation and Operating handbook issue 3

Installation and Operation Handbook Operation

2208e and 2204e Controller 1-13

1.8 LOCATION OF PARAMETERS - BLOCK DIAGRAM

The controller consists of a number of internal function blocks connected together to create a temperature controller. Each function block has a number of parameters found in lists to which the user has access. The block diagram shows location of these parameters within the controller.

Display Parameters

Figure 1-14 Controller Block Diagram

Input PID

OP1

OP2 Error

SP

PLANT INPUTS

PLANT OUTPUTS

Heat

Cool

Autotune Remote SP

TCs PRT Pyrometer mA. mV, Volts

Relay, Logic, triac, mA, Volts

SP1/SP2

Timer

PV

SPSPSPSP List

PiDPiDPiDPiD List

OPOPOPOP List

iPiPiPiP List

AtunAtunAtunAtun List

20.0 23.0

OP1 OP2

HOME List For example Output power Setpoint Auto/Manual

Control Parameters

Digital Comms

RS232 RS484 RS422

cmscmscmscms List Digital Comms

Retrans-mission

mA, Volts

OP PV Err SP

LA, LB, Module 2 Logic I/P

2 to 5 logic inputs

Functions listed in LA/LB conf lists

Relay output

Relay, Logic, triac

Alarm 1

Alarm 3

Other alarms

Normal/Invert

OR

ALALALAL List

These are available in configuration level only

Alarms

Logic Inputs Retrans-mission

Page 22: 2208e/2204e Installation and Operating handbook issue 3

Operation Installation and Operation Handbook

1-14 2208e and 2204e Controller

1.9 NAVIGATION DIAGRAM (PART A)

The navigation diagram shows a full list of possible parameters. However, some may not appear because they are dependent upon the particular controller variant.

Figure 1.15a Navigation diagram

20.020.020.020.0

20.0 20.0 20.0 20.0

Home List

AtunAtunAtunAtun

LiStLiStLiStLiSt

PidPidPidPid

LiStLiStLiStLiSt

PID(1) List

ALALALAL

LiStLiStLiStLiSt

Alarm List

Autotune List

SPSPSPSP

LiStLiStLiStLiSt

Setpoint List

OP

100.0

AmPS5

5

m-A

Auto

1---2

100.0

2--2

20.00

3--2

0.0

4--2

0.0

TunE

OFF

Lbt

OFF

Pb

50

Ti

300

td

50.0

rES

0.0

Lcb

Auto

Hcb

Auto

SSEL

SP 1

L-r8

Loc

SP 1

20.0

SP 2

0.0

rm.SP8

0.0

Loc.t8

0.0

rEL.C

1.00 SP1.L3

0.0

SP1.H3

100.0

Loc.L8

100.0

Loc.H8

0.0

SPrr

OFF

SP2.H3

100.0

SP2.L3

0.0

VPOS4

100.0

WSP9

20.0

SP

20.0

diSP

stnd

CID

1.0

HY

1.0

DwEl

0.0

End.t

rset

ProG

rset

StAt

OFF

Adc

OFF

Page 23: 2208e/2204e Installation and Operating handbook issue 3

Installation and Operation Handbook Operation

2208e and 2204e Controller 1-15

NAVIGATION DIAGRAM (PART B)

. .

Complete lists or individual parameters normally hidden in Operator level. To see all the available parameters you must select Full level. See Chapter 3, Access Levels Only displayed when option selected

Figure 1.15b Navigation diagram

iP LiSt

Input List

oP LiSt

Output List

CmS

LiSt

Comms List

ACCS

LiSt

Access List

OnOF LiSt

On Off List(1)

FiLt

1.0

CAL7

FACT

CAL.S7

Lo

OP.Lo

0.0

OP.Hi

100.0

Sb.OP

100.0

CYC.H

20.0

Notes: 1. Either the PID list or the On/Off list will be present

depending upon the type of control in use. 2. The last three characters depend upon the type of alarm

configured 3. Absolute setpoint limits are set in configuration, see Chapter

5. 4. VPOS only for VP. Refer to VP Ch8. 5. Amps is Mode 2 or Mode 5 PDSIO. 6. mtr used for VP version. Refer to VP Ch8. 7. Beware! Used for calibration. See chapter 6. 8. Is only available if using PDSIO® comms in the HA slot. 9. WSP is available if using ramp to setpoint.

ont.H

1.0

CYC.C

5.0

hYS.H

1.0

hYS.C

1.0

HC.db

0.0

Addr

1 coDE

PASS

Goto

OPEr

ont.C

1.0

ConF

0

Return to Home Display

OFST

0.0

Mtr6

20.0

AdJ7

0.0

CJC

21.0

mV

1.17

Page 24: 2208e/2204e Installation and Operating handbook issue 3

Operation Installation and Operation Handbook

1-16 2208e and 2204e Controller

1.10 PARAMETER TABLES

The tables which follow list all parameters that are available in Full operator level. Name Parameter

Description Default Value Min

Value Max Value

Units Customer Setting

UK USA

Display mnemonic

Brief description of parameter or function

Factory configured value

1.10.1 HOME Display

Name Parameter Description

Default Value Min Value

Max Value

Units Customer Setting

UK USA

Home List Home Measured Value

and Setpoint(SP) SP=25°C

SP=75°F

as display

vPoS Valve positioner output power

0.0 100.0 %of mtr

OP % Output Level -100.0 100.0 % wSP Working setpoint as

display

SP Setpoint -999 9999 as display

AmPS Heater current (PDS modes 2 and 5)

0 100 Amps

m-A Auto/manual select Auto Auto diSP Configure lower

readout of home display

StD StD None StD AmPS OP stat vPoS

Cid Customer ID 0 0 0 9999

Additional parameters may appear in the Home display if the ‘promote’ feature has been used (see Edit Level, Chapter 3).

Page 25: 2208e/2204e Installation and Operating handbook issue 3

Installation and Operation Handbook Operation

2208e and 2204e Controller 1-17

1.10.2 Alarm List

Name Parameter Description

Default Value Min Value

Max Value

Units Customer Setting

UK USA

ALALALAL Alarm List

1--- Alarm 1 set point value

0 0 as display

2--- Alarm 2 set point value

0 0 as display

3--- Alarm 3 set point value

0 0 as display

4--- Alarm 4 set point value

0 0 as display

In place of dashes, the last three characters indicate the alarm type, as follows:

-FSH Full Scale High alarm

-999 9999 as display

-FSL Full Scale Low alarm

-999 9999 as display

-DEv Deviation band alarm

0 9999 as display

-dHi Deviation High alarm

0 9999 as display

-dLo Deviation Low alarm

0 9999 as display

-Lcr Low current alarm 0 100 AMPS

-Hcr High current alarm 0 100 AMPS

Hy Hysteresis 0 9999 as display

Hy.EV Hysteresis for event alarms. See Note 1

0 9999 as display

Lbt Loop break time OFF OFF 0 9999 secs Note 1: This parameter has been added from software version 4. Event alarms are configured in the AL Conf List

Page 26: 2208e/2204e Installation and Operating handbook issue 3

Operation Installation and Operation Handbook

1-18 2208e and 2204e Controller

1.10.3 Autotune List

AtunAtunAtunAtun Autotune List

tunE Self tune enable OFF OFF OFF On

Adc Automatic droop compensation (Manual Reset) enable (only present if ti set to OFF)

MAn MAn MAn CALC

1.10.4 PID List

Name Parameter Description

Default Value Min Value

Max Value

Units Customer Setting

UK USA

PidPidPidPid PID List

Pb Proportional band

20.0 30 1

9999 as display

ti Integral time 360 360 OFF 9999 seconds

td Derivative time 60 60 OFF 9999 seconds

rES Manual reset (appears when ti set to OFF)

0.0 0.0 0.00 100.0 %

Lcb Cutback low Auto Auto 0 9999 as display

Hcb Cutback high Auto Auto 0 9999 as display

rEL.C Relative cool gain (set 1)

1.00 1.00 0.01 9.99

Page 27: 2208e/2204e Installation and Operating handbook issue 3

Installation and Operation Handbook Operation

2208e and 2204e Controller 1-19

1.10.5 Setpoint List

Name Parameter Description

Default Value Min Value

Max Value

Units Customer Setting

UK USA

SPSPSPSP Set Point List

SSEL Select SP1 or SP2 SP1 SP1 SP1 SP2

L-r Local or remote setpoint select

Loc Loc Loc rmt

SP1 Setpoint 1 value 25 70 As display range

SP2 Setpoint 2 value 25 70 As display range

rm.SP Remote setpoint 0 0 As display range

Loc.t Local trim 0 0 As display range

SP1.L Setpoint 1 low limit 0 32 As display range

SP1.H Setpoint 1 high limit

1000 2100 As display range

SP2.L Setpoint 2 low limit 0 32 As display range

SP2.H Setpoint 2 high limit

1000 2100 As display range

Loc.L Local setpoint trim low limit

-210 -346 As display range

Loc.H Local setpoint trim high limit

1200 2192 As display range

SPrr Setpoint rate limit OFF Off Units per minute

dwEl Dwell time OFF OFF 0.1 to 999.9 minutes

EnD.t End type rset rset rset

hoLd

Stby

dwel

ProG Program control rset rset run

rset

Stat Status of program Off OFF rmp

dwel

end

Off

Page 28: 2208e/2204e Installation and Operating handbook issue 3

Operation Installation and Operation Handbook

1-20 2208e and 2204e Controller

Input List

Name Parameter Description

Default Value Min Value

Max Value

Units Customer Setting

UK USA

iPiPiPiP Input list

*FiLt Input filter time constant

1.6 1.6 0.0 off

999.9 secs

OFSt PV Offset -999 9999 as display

The next 5 parameters will appear if User calibration has been enabled in configuration level. To perform a user calibration refer to Ch 6.

CAL FACt will re-instate factory settings and disable User Calibration. Default setting FACt USEr will re-instate any previously set User Calibration offsets and make available User Calibration parameters as follows:

CAL.S User calibration select

none none Hi Lo none

Adj~ Adjust calibrated

reference source

The following two parameters are always present in Full Access level but not in Operator level

CJCo Cold Junction compensation temperature

mV Millivolt input * A minimum filter time constant of one second is recommended to provide sufficient noise immunity.

~ Do not make adjustments to the AdJ parameter unless you wish to offset the controller calibration.

1.10.6 On/Off List

OnOfOnOfOnOfOnOf On/off list This set of parameters only appear if On/Off control has been configured

hYS.H Heat hysteresis

0 0 0 9999 as display

hYS.C Cool hysteresis 0 0 0 9999 as display

HC.db Heat/Cool dead band

1 1 0 9999 as display

Page 29: 2208e/2204e Installation and Operating handbook issue 3

Installation and Operation Handbook Operation

2208e and 2204e Controller 1-21

1.10.7 Output List

Name Parameter Description

Default Value Min Value

Max Value

Units Customer Setting

UK USA oPoPoPoP Output list Note; If On/Off control is configured only Sb.OP, ont.H

and ont.C will appear in the following list

OP.Lo Low (power) output limit

0.0 or -100.0 (cool)

-100.0 100.0 %

OP.Hi High (power) output limit

100.0 100.0 -100.0 100.0 %

Sb.OP Output setting when in sensor break

0.0 -100.0 100.0 %

1CYC.H Heat cycle time 1.0 (logic) 20 (relay)

0.2 999.9 secs

ont.H Heat output min. on time

0.1 0.1 Auto (50mS)

999.9

1CYC.C Cool cycle time 1.0 (logic) 20 (relay)

0.2 999.9 secs

1ont.C Cool output min. on time

0.1 0.1 Auto (50mS)

999.9 secs

mtr VP motor travel time

0.0 999.9 secs

1 Are not used for Valve Position Control.

1.10.8 Communications List

cmScmScmScmS Comms list

Addr Communications address

1 1 1 254

1.10.9 Access List

ACCSACCSACCSACCS Access list

codE Full and Edit level password

1 1 0 9999

Goto Goto level -OPErFuLL

Editor conF

OPEr OPEr OPEr conF

ConF Configuration level password

2 2 0 9999

Page 30: 2208e/2204e Installation and Operating handbook issue 3

Operation Installation and Operation Handbook

1-22 2208e and 2204e Controller

1.11 ALARMS

Alarms are used to alert an operator when a pre-set level has been exceeded. They are normally used to switch an output (see 1.12) – usually a relay – to provide external actions to the process.

Soft Alarms are indication only and do not operate an output.

Events are generally defined as conditions, which occur as part of the operation of the plant. They do not require operator intervention and, therefore, do not cause an alarm message to be displayed. They can be attached to operate an output (relay) in the same way as an alarm.

1.11.1 Types of Alarm Used in the 2200 This section shows graphically the operation of different types of alarm used in the controller. The graphs show changes in PV plotted against time.

Full scale low

On On

Deviation low

On On

Deviation high

On

Deviation band

On On On

Full scale high

On

Rate of change

On

Figure 1-17: Alarm Types

Time

Setpoint (SP)

Full Scale High

Full Scale Low

Deviation High

Deviation Low

Deviation Band

PV

Rate of Change

Process Variable (PV)

Alarm Type

Output State

Page 31: 2208e/2204e Installation and Operating handbook issue 3

Installation and Operation Handbook Operation

2208e and 2204e Controller 1-23

Hysteresis is the difference between the point at which the alarm switches ON and the point at which it switches OFF. It is used to prevent relay chatter.

Blocking Alarms only occur after the start up phase when the alarm has first entered a safe state. The alarm is only indicated the next time it is active. It is used, for example, to ignore start up conditions which are not representative of running conditions.

Latching Alarms see 7.1.1.

Loop Break Alarm. The control loop is considered to be open if the output demand signal increases to saturation level but the error does not reduce after a set period of time. The time period can be set manually, depending on the response time of the loop, using the parameter Lbt in the Alarm List (section 1.10.2). It is, also set automatically, following an autotune (see chapter 4), to 3 x Ti (integral time). The time period, Lbt, starts from the point at which the output demand reaches saturation. The loop break alarm L.br is displayed (as a diagnostic alarm, see section 1.12.3.) at the end of this period.

1.12 ALARM RELAY OUTPUT

Alarms can operate a specific output (usually a relay). Any individual alarm can operate an individual relay or any combination of alarms can operate an individual relay. They are either supplied pre-configured in accordance with the ordering code or set up in configuration level.

See Chapter 5 for further information.

Figure 1-18: Attaching Alarms to an Output

dIG

SEnS

nor

inv

Relay output

Any combination of alarms can operate the relay. Typical alarms are shown

OR

Alarm 1

Alarm 2

Sensor break

Input fail

Alarm 3

i

Page 32: 2208e/2204e Installation and Operating handbook issue 3

Operation Installation and Operation Handbook

1-24 2208e and 2204e Controller

1.12.1 SETTING ALARM LEVELS Up to 4 Alarms may be configured. Each alarm is given a name to describe its function - see table below: If an alarm is not configured it does not appear in the list below.

Figure 1-19 To Set Alarm Trip Levels

2222------------

1111------------100100100100

3333------------

4444------------

ALALALAL

LiStLiStLiStLiSt

LbLbLbLb tttt

In place of dashes, letters indicate alarm type as follows:

-FSL Full Scale Low

-FSH Full Scale High

-dEv Deviation Band

-dHi Deviation High

-dLo Deviation Low

-Lcr Low current

-Hcr High current

Alarm List

Alarm 1

2nd press

or to change

3rd press

4th press

5th press

Alarm 2

Alarm 3

Alarm 4

Loop break time

or to change

or to change

or to change

or to change

Press to return to list header

Page 33: 2208e/2204e Installation and Operating handbook issue 3

Installation and Operation Handbook Operation

2208e and 2204e Controller 1-25

1.12.2 ALARM INDICATION AND ACKNOWLEDGEMENT When an alarm occurs, the alarm mnemonic (e.g. 1FSH) will be indicated by a double flash in the HOME display. Similarly, if more than one alarm occurs the relevant mnemonics are flashed in the HOME display. The double flash will continue whilst the alarm condition is present and is not acknowledged. Press and together to acknowledge the alarm. If the alarm condition is still present when the alarm is acknowledged, it will be indicated by a single flash of the alarm mnemonic and this single flash will be repeated for as long as the alarm condition remains. When the alarm condition disappears the indication will also disappear.. If the alarm condition is no longer present when the alarm is acknowledged, the flashing message will disappear immediately on acknowledgement. If a relay has been attached to the alarm output (see Chapter 7 ‘Alarm Operation’), it will operate when the alarm condition occurs and remain in the operated condition until the alarm is acknowledged AND it is no longer present

Page 34: 2208e/2204e Installation and Operating handbook issue 3

Operation Installation and Operation Handbook

1-26 2208e and 2204e Controller

1.12.3 DIAGNOSTIC ALARMS These indicate that a fault exists in either the controller or the connected devices.

Display shows

What it means What to do about it

EE.Er Electrically Erasable Memory Error: The value of an operator or configuration parameter has been corrupted

This fault will automatically take you into configuration level. Check all of the configuration parameters before returning to operator level. Once in operator level, check all of the operator parameters before resuming normal operation. If the fault persists or occurs frequently, contact your supplier

S.br Sensor Break: Input sensor is unreliable or the input signal is out of range

Check that the sensor is correctly connected

L.br Loop Break: The feedback loop is open circuit

Check that the heating and cooling circuits are working properly

Ld.F Load failure Indication that there is a fault in the heating circuit or the solid state relay

This is an alarm generated by feedback from a TE10S solid state relay (SSR) operating in PDS SSRx mode. It indicates either an open or short circuit SSR, blown fuse, missing supply or open circuit heater

SSr.F Solid state relay failure Indication that there is a fault in the solid state relay

This is an alarm generated by feedback from a TE10S solid state relay (SSR) operating in PDS SSRx mode. It indicates either an open or short circuit condition in the SSR

Htr.F Heater failure Indication that there is a fault in heating circuit

This is an alarm generated by feedback from a TE10S solid state relay (SSR) operating in PDS SSRx mode. It indicates either a blown fuse, missing supply or open circuit heater

HW.Er

Hardware error Indication that a module is the wrong type

Check that the correct modules are fitted

no. io No I/O module Modules are configured but not fitted

This error message normally occurs when pre-configuring a controller without installing any of the required I/O modules

Figure 1.20a Diagnostic alarms - continued on the next page

Page 35: 2208e/2204e Installation and Operating handbook issue 3

Installation and Operation Handbook Operation

2208e and 2204e Controller 1-27

Diagnostic alarms continued

These indicate that a fault exists in either the controller or the connected devices.

Display shows

What it means What to do about it

rmt.F Remote input failure. The PDS input is open circuit. (PDS Also known as SST – Smart Setpoint Transmission)

Check for open or short circuit wiring on the PDS input

LLLL Out of Display range, low reading

Check the value of the display range

HHHH Out of Display range, high reading

Check the value of the display range

Err1 Error 1: ROM self-test fail Return the controller for repair

Err2 Error 2: RAM self-test fail Return the controller for repair

Err3 Error 3: Watchdog fail Return the controller for repair

Err4 Error 4: Keyboard failure Stuck button, or a button was pressed during power up.

Switch the power off and then on without touching any of the controller buttons.

Err5 Error 5: Input circuit failure Return the controller for repair*

Pwr.F Power failure. The line voltage is too low

Check that the supply to the controller is within the rated limits

TU.Er Tune error. If any one stage of the tuning process exceeds 2 hours the tune error alarm occurs

Check response time of process: check that the sensor has not failed: check that the loop is not broken. Acknowledge by pressing ‘page’ button and ‘scroll’ button together.

Figure 1.20b Diagnostic alarms

*If the user has disassembled and reassembled the instrument, this error can occur if any connectors are not seated properly.

Page 36: 2208e/2204e Installation and Operating handbook issue 3

Operation Installation and Operation Handbook

1-28 2208e and 2204e Controller

Page 37: 2208e/2204e Installation and Operating handbook issue 3

Installation and Operation Handbook Installation

2208e and 2204e Controller 2-1

2 Chapter 2 INSTALLATION

2 Chapter 2 INSTALLATION ..............................................1

2.1 INSTRUMENT LAYOUTS.................................................................2 2.1.2 Outline Dimensions Model 2208e .........................................................3 2.1.3 Outline Dimensions Model 2204e .........................................................3

2.2 INTRODUCTION...............................................................................4 2.2.2 Controller labels ....................................................................................4

2.3 MECHANICAL INSTALLATION .......................................................4 2.3.2 Unplugging and plugging-in the controller.............................................4

2.4 WIRING .............................................................................................5 2.4.2 Wire Sizes.............................................................................................6 2.4.3 Wiring connections................................................................................6 2.4.4 Sensor input connections......................................................................7 2.4.5 Outputs 1 and 2 connections ................................................................7

2.5 PDS MODES .....................................................................................8

2.6 SNUBBERS.......................................................................................8

2.7 TYPICAL SINGLE LOOP WIRING DIAGRAM.................................9

2.8 RS 232/485/422 COMMUNICATION CONNECTIONS ..................10 2.8.2 Wiring of EIA-485 serial communication links.....................................11

2.9 DEVICENET WIRING TO SERIES 2200E CONTROLLERS .........12 2.9.2 DeviceNet Terminal Functions ............................................................12 2.9.3 Wiring Interconnections for DeviceNet Communications....................13

Page 38: 2208e/2204e Installation and Operating handbook issue 3

Installation Installation and Operation Handbook

2-2 2208e and 2204e Controller

2.1 INSTRUMENT LAYOUTS

Figure 2-1: 2208e 1/8 DIN controller

Figure 2-2: 2204e 1/4 DIN controller

3

4

5

6

7

8

KEY

1. Display screen

2. Latching ears

3. Panel sealing gasket

4. Panel retaining clips

5. Label

6. Sleeve

7. Connection Terminals

8. Keypad

2

2

1

1

2

2

3

4

4

5

6

7

8

Page 39: 2208e/2204e Installation and Operating handbook issue 3

Installation and Operation Handbook Installation

2208e and 2204e Controller 2-3

2.1.2 Outline Dimensions Model 2208e

Figure 2-3: Outline dimensions Model 2208e controller

2.1.3 Outline Dimensions Model 2204e

Figure 2-4: Outline dimensions Model 2204e controller

The controller plugs into a plastic sleeve, which in turn fits into the panel cut-out shown in Figures 2-3 and 2-4.

2208

OP1 OP2

SP2 REM

Panel cutout

92 x 45mm

3.62x1.77in

-0 +0.8

-0 +0.6

-0 +0.03

-0 +0.02

103mm (4.01in) 48mm (1.89in)

96mm (3.78in)

38mm (1.5in)

10mm (0.4in)

(Not to scale)

Recommended minimum spacing of controllers

20.0.0

20.0.020.0.020.0.020.0.0

2204

OP1 OP2

SP2 REM

Panel cutout

92 x 92 -0 +0.8mm

3.62 x 3.62 -0 +0.03in

103mm (4.01in) 96mm (3.78in)

96mm 3.78in

Recommended minimum spacing of controllers

38mm (1.5in)

10mm (0.4in)

(Not to

scale)

20.0.0

20.0.0 20.0.0 20.0.0 20.0.0

Page 40: 2208e/2204e Installation and Operating handbook issue 3

Installation Installation and Operation Handbook

2-4 2208e and 2204e Controller

2.2 INTRODUCTION

The Models 2208e and 2204e are precision temperature controllers with self tuning. They have a modular hardware construction which provides two control outputs, two alarm relays and one communications port. Two logic inputs are provided as standard. In addition the Model 2204e has an optional plug-in 10A relay heating output.

2.2.2 Controller labels The labels on the sides of the controller identify the ordering code, the serial number, and the wiring connections. Appendix A, Understanding the Ordering Code explains the hardware and software configuration of your particular controller.

2.3 MECHANICAL INSTALLATION

To install the controller

1. Cut the panel to the relevant hole size shown in Figure 2-3 and 2.4.

2. Insert the controller through the front of this cutout.

3. Spring the upper and lower panel retaining clips into place. Secure the controller in position by holding it level and pushing both retaining clips forward.

Note: If the panel retaining clips subsequently need removing, they can be unhooked from the side with either your fingers or a screwdriver.

2.3.2 Unplugging and plugging-in the controller The controller can be unplugged from its sleeve by easing the latching ears outwards and pulling it forward out of the sleeve. When plugging the controller back into its sleeve, ensure that the latching ears click into place to maintain moisture sealing protection.

Page 41: 2208e/2204e Installation and Operating handbook issue 3

Installation and Operation Handbook Installation

2208e and 2204e Controller 2-5

2.4 WIRING

Please read Appendix B, Safety and EMC information before proceeding.

WARNING Please ensure that the controller is correctly configured for your application. Incorrect configuration could result in damage to the process being controlled, and/or personal injury. The controller may either have been configured when ordered, or may need configuring now. See Chapter 5, Configuration.

The wiring connections are shown in figure 2-5. Outputs 1 and 2 are factory fitted modules which can be any one of the types shown in figure 2-8. Check the ordering code on the controller side label to determine which have been fitted.

Model 2208e connections

Figure 2-5: Model 2208e wiring connections

*The ground connection is not required for electrical safety but must be connected to ensure EMC performance is optimised.

*Do not use unused terminals as wire holders.

Pt100

N

L

V+

VI

V-

Line

Neutral

Ground

+

-

+ PV -

2B

2A

1B

1A

HF

HD

HE

Common

Input 1

Input 2

85 to 264Vac

LC

LA

LB

AC

AB

Output 1

3B

3A

3C

Output 2

Output 4

Output 3

AA

HB

HC

HA

Comms

!

!

Page 42: 2208e/2204e Installation and Operating handbook issue 3

Installation Installation and Operation Handbook

2-6 2208e and 2204e Controller

2.4.2 Wire Sizes All electrical connections are made to the screw terminals at the rear of the controller. They accept wire sizes from 0.5 to 1.5 mm2 (16 to 22 AWG), and are protected by a hinged cover to prevent hands or metal making accidental contact with live wires. Rear terminals should be tightened to a torque of 0.4Nm (3.5 lb in).

2.4.3 Wiring connections The wiring connections are shown in figure 2-6. Outputs 1 and 2 are factory fitted modules which can be any one of the types shown in figure 2-8. Check the ordering code on the controller side label to determine which have been fitted.

Model 2204e Connections

Figure 2-6: Model 2204e Wiring connections

*The ground connection is not required for safety purposes but must be connected to ensure EMC performance is optimised.

*Do not use unused terminals as wire holders.

!

Input 1

Neutral

*Ground*

+

-

+ PV -

85-264Vac H I G H C U R R E N T O U T P U T

Pt100

Output 1

Output 2

4B

4C

4D

5A

5B

5D

6A

6B

6C

6D

5C

1B

2A

2B

1A

3A

3B

3C

N

LA

LB

LC

L

AB

AC

VI

V+

V-

AA

HB

HC

HD

HE

HF

HA

Line

Line

BUS BAR

Output 4

Output 3

Input 2

Common

Dig

ital

Com

mun

icat

ions

Line 4A

NO

NO

NC

NC

BUS BAR

Page 43: 2208e/2204e Installation and Operating handbook issue 3

Installation and Operation Handbook Installation

2208e and 2204e Controller 2-7

2.4.4 Sensor input connections The connections for the various types of input are as follows:

Figure 2-7: Sensor input connections

Sensor inputs should not be paralleled

2.4.5 Outputs 1 and 2 connections Outputs 1 and 2 can be any one of the types shown in the table below, configured to perform any one of the functions shown.

To check which outputs are installed, and their configuration, refer to the ordering code and the wiring information on the controller side labels.

Connections

Output 1 Output 2 Possible functions

Module type 1A 1B 2A 2B

Relay: 2-pin (2A, 264 Vac max.)

Heating Cooling Alarms

Logic: non-isolated* (18Vdc at 24mA)

+ -

+ -

+PDS modes 1 or 2 (SSRx) Heating Cooling Alarms

Triac (1A, 30 to 264Vac) Heating or cooling

DC control: isolated (18Vdc, 20mA max)

+ - DC not available in output 2

PID Heating or cooling

*Logic output can also be configured as logic input on module 2A. +PDS Mode 1 & 2 are only supported in Module 1A.

Figure 2-8: Outputs 1 and 2 connections

VI

V+

V-

VI

V+

V-

VI

V+

V-

VI

V+

V-

Thermocouple Resistance thermometer mA input Volts or mV

inputs

+

- PV

2.49Ω current sense resistor

Line Load Line Load

!

Page 44: 2208e/2204e Installation and Operating handbook issue 3

Installation Installation and Operation Handbook

2-8 2208e and 2204e Controller

2.5 PDS MODES

PDS is a proprietary technique developed for bi-directional communication over a single pair of wires. There are several operating modes. In SSRx Load Doctor™ a logic output delivers a power demand signal to a TE10 solid state (SSR) relay and the SSR responds with a single load circuit failure message. In SSRx Enhanced Load Doctor™ a logic output delivers a power demand signal to an SSR and the SSR responds with the ON state rms load current, and two fault messages - SSR failure or heater circuit failure.

2.6 SNUBBERS

The controller is supplied with ‘snubbers’ (15nF +100Ω) which should be wired across the relay or triac outputs when switching inductive loads such as mechanical contactors and solenoid valves. The snubbers are used to prolong contact life and to suppress interference when switching such loads. Snubbers pass 0.6mA at 110Vac and 1.2mA at 240Vac, which may be sufficient to hold in high impedance relay coils. They should not, therefore, be used in such installations.

WARNING When a relay contact is used in an alarm circuit ensure that the current passing through the snubber when the relay contact is open does not hold in low power electrical loads and thereby interfere with the failsafe operation of the alarm circuit.

!

Page 45: 2208e/2204e Installation and Operating handbook issue 3

Installation and Operation Handbook Installation

2208e and 2204e Controller 2-9

2.7 TYPICAL SINGLE LOOP WIRING DIAGRAM

Figure 2-9: Typical wiring diagram, Model 2208e Controller

Neutral

N

L

V+

VI

V-

+

-

+

PV

-

2B

2A

3B

3A

3C

1B

1A

HF

HD

HE

LC

LA

LB

AC

AA

AB

Cooling Power Fuse 1A(T)

Heating power fuse (load dependent)

Cooling Solenoid Valve

Heater

Thermocouple

-

Controller Fuse 2A(T)

Solid State Relay

* +

-

Snubber

Output 1 logic heating

Line

Output 2 Triac cooling

HC

HA

HB

Page 46: 2208e/2204e Installation and Operating handbook issue 3

Installation Installation and Operation Handbook

2-10 2208e and 2204e Controller

2.8 LOGIC DRIVE FAN OUT

The logic outputs from the 2200 series controllers are capable of driving more than one solid state relay (SSR) in series or parallel. The following table shows the number of SSRs which can be driven depending on type of SSR. S = Series; P = Parallel.

Drive mA

SVDA RVDA TE10S 425S

Logic DC Logic DC Logic DC Logic 10V

Logic 24V

Logic 20mA

Logic 18V@24 4S 6P 4S 4P 3S 3/2P 3S 3P 1S 2P 6S 1P

450 TC1027

CE TE200S TC2000

CE RS3DA

Standard TTL Multi-drive

Logic V Logic DC Logic DC Logic DC

Logic 2S 3P 1S 2P 6S 1P 3S 4/3P 3S 4P 3S 2/1P 4S 2P

2.9 RS 232/485/422 COMMUNICATION CONNECTIONS

The communication option can be either of four types shown in the table below

Connection

Communications type HB HC HD HE HF

4-wire EIA-422 serial communications

A’ (RX +)

B’ (RX -)

Common A (TX +)

B (TX -)

2-wire EIA-485 serial communications

Do not use

Do not use

Common A (+)

B (-)

EIA-232 serial communications

Not used Not used Common A B

PDS Setpoint input Not used Not used Not used Signal Common

Figure 2-10: Communication connections

Page 47: 2208e/2204e Installation and Operating handbook issue 3

Installation and Operation Handbook Installation

2208e and 2204e Controller 2-11

2.9.2 Wiring of EIA-485 serial communication links

Local

LocalEarth

HF +Series 2000™Controller

Com

Note:All termination resistors are 220 ohm 1/4W carbon composition.Local grounds are at equipotential. Where equipotential is not available wire intoseparate zones using a galvanic isolator.

A

B

PC

Universal Convertor

RXTXCom

Com TXRX

Up to 32controllers orInterface Units maybe included on thenetwork

232

Com B A

Com

A

B

GalvanicIsolationBarrier

Com

A

B

Com

AB

Local Earth

Com

AB

Earth

UniversalConverter

MMI

Series 2000™Controller

Series 2000™Controller

For safety reasons,do not connect tolocal earth here.

HD

HF+

HE

HD

HF+

HE

HE

HD

Figure 2-11: 2-wire EIA-485 wiring

Standard EIA-485 is a 2-wire connection which allows up to 32 controllers to be multi-dropped from a single communications link over a distance of up to 1.2Km. To ensure reliable operation of the communications link, (without data corruption due to noise or line reflections) the connections between the controller should be made using a twisted pair of wires inside a shielded cable with the connections terminated with resistors in the manner shown in this diagram. This diagram also shows the use of a Comms converter to connect the 2-wire EIA-485 link into a standard EIA-232 computer port.

Common and Local Earth cannot be connected together.

Page 48: 2208e/2204e Installation and Operating handbook issue 3

Installation Installation and Operation Handbook

2-12 2208e and 2204e Controller

2.10 DEVICENET WIRING TO SERIES 2200E CONTROLLERS

This section covers the DeviceNet digital communications option for the model 2208e and 2204e PID controllers. To configure DeviceNet communications refer to pages 5-16 and 5-17.

2.10.2 DeviceNet Terminal Functions

Series 2200e Terminal

CAN

Label

Color

Chip

Description

HA V+ Red DeviceNet network power positive terminal. Connect the red wire of the DeviceNet cable here. If the DeviceNet network does not supply the power, connect to the positive terminal of an external 11-25 Vdc power supply.

HB CAN_H White DeviceNet CAN_H data bus terminal. Connect the white wire of the DeviceNet cable here.

HC SHIELD None Shield/Drain wire connection. Connect the DeviceNet cable shield here. To prevent ground loops, the DeviceNet network should be grounded in only one location.

HD CAN_L Blue DeviceNet CAN_L data bus terminal. Connect the blue wire of the DeviceNet cable here.

HE V- Black DeviceNet network power negative terminal. Connect the black wire of the DeviceNet cable here. If the DeviceNet network does not supply the power, connect to the negative terminal of an external 11-25 Vdc power supply.

Notes: Power taps are recommended to connect the DC power supply to the DeviceNet trunk line. Power taps include:

A Schottky Diode to connect the power supply V+ and allows for multiple power supplies to be connected. 2 fuses or circuit breakers to protect the bus from excessive current which could damage the cable and connectors.

!

Page 49: 2208e/2204e Installation and Operating handbook issue 3

Installation and Operation Handbook Installation

2208e and 2204e Controller 2-13

2.10.3 Wiring Interconnections for DeviceNet Communications

Figure 2-12: 2-Wiring Connections for 2200e Series DeviceNet Controllers

HA

HB

HC

HD

HE

HF

2200e Controller

(SLAVE) Address 11

V+

CAN-H

CAN-L

Drain

V-

HA

HB

HC

HD

HE

HF

2200e Controller

(SLAVE) Address 12

V+

CAN-H

CAN-L

Drain

V-

HA

HB

HC

HD

HE

HF

2200e Controller

(SLAVE) Address N+1

V+ 5

CAN-H 4

CAN-L 2

Drain 3

V- 1

5-Position COMBICOM

Diag DB-9M

RDY RUN

NET MON

Card Top

Red

Wht

Blu

Blk

121! *

* Fit to last instrument in the chain

Network Supply 24Vdc ( +1%)

250mV p-p Ripple

V+

V-

V-

V+

Typical Interface Card (MASTER)

Daisy chain to further instruments

Page 50: 2208e/2204e Installation and Operating handbook issue 3

Installation Installation and Operation Handbook

2-14 2208e and 2204e Controller

Page 51: 2208e/2204e Installation and Operating handbook issue 3

Installation and Operation Handbook Access Levels

2208e and 2204e Controller 3-1

3 Chapter 3 ACCESS LEVELS

3 Chapter 3 ACCESS LEVELS............................................1

3.2 THE DIFFERENT ACCESS LEVELS ...............................................2

3.3 SELECTING AN ACCESS LEVEL ...................................................3 3.3.2 Returning to Operator Level ..................................................................5

3.4 Edit level...........................................................................................5 3.4.2 Hiding or revealing a complete list ........................................................6 3.4.3 Promoting a parameter .........................................................................6

Page 52: 2208e/2204e Installation and Operating handbook issue 3

Access Levels Installation and Operation Handbook

3-2 2208e and 2204e Controller

3.2 THE DIFFERENT ACCESS LEVELS

Access level

Display shows

What you can do

Password Protection

Operator OPEr In this level operators can view and adjust the value of parameters defined in Edit level (see below).

No

Full FuLL In this level all the parameters relevant to a particular configuration are visible. All alterable parameters may be adjusted.

Yes

Edit Edit In this level you can set which parameters an operator in Operator level is able to view and adjust. You can hide or reveal complete lists and individual parameters within each list, and you can make parameters read-only or alterable. You can also promote parameters to the home list. (See Edit level at the end of the chapter).

Yes

Configuration ConF This special level allows access to set up the fundamental characteristics of the controller.

Yes

Figure 3-1 Access levels

Page 53: 2208e/2204e Installation and Operating handbook issue 3

Installation and Operation Handbook Access Levels

2208e and 2204e Controller 3-3

3.3 SELECTING AN ACCESS LEVEL

Access to Full, Edit or Configuration levels is protected by a password to prevent unauthorised access. If you need to change the password, see Chapter 5, Configuration

3.2.2 Access list header

Press until you reach the access list header ‘ACCS’. Press the Scroll button

3.2.3 Password entry

The password is entered from the ‘CodE display.

Enter the password using the or buttons.

Once the correct password has been entered, there is a two second

delay after which the lower readout will change to show ‘PASS

indicating that access is now unlocked.

The pass number is set to ‘1’ when the controller is shipped from the factory. Note; A special case exists if the password has been set to ‘0’. In this case access will be permanently unlocked and the lower readout will always show ‘PASS’ Press the Scroll button to proceed to the ‘goto’ display. (If an incorrect password has been entered and the controller is still ‘locked’ then pressing Scroll at this point will simply return you to the aCCs list header.) Note: From this code display, you can access “read only”

configuration level by pressing and together.

To escape, press and together

AccS

LiSt

CodE

0

Page 54: 2208e/2204e Installation and Operating handbook issue 3

Access Levels Installation and Operation Handbook

3-4 2208e and 2204e Controller

AccS LiSt

ConF PASS

inSt ConF

GotO

FuLL

3.2.4 Level selection

The Goto display allows you to select the required access level.

Use and to select from the following display codes: OPEr: Operator level FuLL: Full level Edit: Edit level conF: Configuration level

Press the Scroll button

If you selected either ‘OPEr, FuLL or Edit level you will be returned to the ‘ACCS list header in the level that you chose. If you selected ‘conF’, you will get an alternative display showing ‘ConF’ in the upper readout (see below).

3.2.5 Configuration password

When the ‘ConF’ display appears, you must enter the Configuration password in order to gain access to Configuration level. Do this by repeating the password entry procedure described in the previous section The configuration password is set to ‘2’ when the controller is shipped from the factory. If you need to change the configuration password, see Chapter 5, Configuration Press the Scroll button

3.2.6 Configuration level The first display of configuration is shown. See chapter 5, Configuration for details of the configuration parameters. For instructions on leaving configuration level see Chapter 5, Configuration.

Page 55: 2208e/2204e Installation and Operating handbook issue 3

Installation and Operation Handbook Access Levels

2208e and 2204e Controller 3-5

3.3.2 Returning to Operator Level

To return to operator level from either ‘FuLL’ or ‘Edit’ level, select ‘OPEr’ on the ’Goto’ display, or turn the controller of and on. In ‘Edit’ level the controller will automatically return to operator level if no button is pressed for 45 seconds.

3.4 EDIT LEVEL

Edit level is used to set which parameters you can see and adjust in Operator level. It also gives access to the ‘Promote’ feature which allows you to select and add (‘Promote’) up to twelve parameters into the Home display list, thereby giving simple access to commonly used parameters.

Setting operator access to a parameter

First you must select Edit level, as shown on the previous page. Once in Edit level you select a list or a parameter within a list in the same way as you would in Operator or Full level. Τhat is, you move from list header to list header by pressing the Page button, and from parameter to parameter within each list using the Scroll button. However, in Edit level what is displayed is not the value of a selected parameter but a code representing the parameter’s availability in Operator level.

When you have selected the required parameter, use the and buttons to set its availability in operator level. There are four codes: ALtrALtrALtrALtr Makes a parameter alterable in Operator level ProProProPro Promotes a parameter into the Home display list rEAdrEAdrEAdrEAd Makes a parameter or list header read-only (it can be viewed but not altered) HidEHidEHidEHidE Hides a parameter or list header. For example:

The parameter selected is the set point for Alarm 2 - Full Scale Low It will be alterable in Operator level

2FSL

ALtr

Page 56: 2208e/2204e Installation and Operating handbook issue 3

Access Levels Installation and Operation Handbook

3-6 2208e and 2204e Controller

3.4.2 Hiding or revealing a complete list To hide a complete list of parameters, all you have to do is hide the list header. If a list header is selected only two selections are available: rEAd and HidE. (It is not possible to hide the ‘ACCS’ list which will always display the code: ‘LiSt’.)

3.4.3 Promoting a parameter

Scroll through the lists to the required parameter and choose the ‘Pro’ code. The parameter is then automatically added (promoted) into the Home display list (the parameter will also be accessible as normal from the standard lists. a maximum of 12 parameters can be promoted. Promoted parameters are automatically ‘alterable’.

Page 57: 2208e/2204e Installation and Operating handbook issue 3

Installation and Operation Handbook Tuning

2208e and 2204e Controller 4-1

4. Chapter 4 TUNING

4. Chapter 4 TUNING...........................................................1

4.1. WHAT IS TUNING? ..........................................................................2

4.2. AUTOMATIC TUNING ......................................................................3 4.2.1. Heating and Cooling Output Cycle Times .............................................3

4.3. How to Tune.....................................................................................4 4.3.1. Typical automatic tuning cycle ..............................................................5 4.3.2. Calculation of the cutback values..........................................................5

4.4. MANUAL TUNING ............................................................................6 4.4.1. Setting the cutback values ....................................................................7 4.4.2. Integrating action and manual reset......................................................8 4.4.3. Automatic droop compensation (Adc) ...................................................8

Page 58: 2208e/2204e Installation and Operating handbook issue 3

Tuning Installation and Operation Handbook

4-2 2208e and 2204e Controller

Before tuning please read Chapter 1, Operation, to learn how to select and change a parameter.

This chapter has three main topics:

• WHAT IS TUNING?

• AUTOMATIC TUNING

• MANUAL TUNING

4.1. WHAT IS TUNING?

In tuning you match the characteristics of the controller to that of the process being controlled in order to obtain good control. Good control means:

Stable ‘straight-line’ control of the temperature at setpoint without fluctuation

Acceptable overshoot or undershoot of the temperature setpoint

Quick response to deviations from the setpoint caused by external disturbances, thereby restoring the temperature rapidly to the setpoint value.

Tuning involves calculating and setting the value of the parameters listed in Table 4-1. These parameters appear in the PiD list.

Parameter

Code

Meaning or Function

Proportional band

Pb The bandwidth in display units over which the output power is proportioned between minimum and maximum.

Integral time ti Determines the time taken by the controller to remove steady-state error signals.

Derivative time

td Determines how strongly the controller will react to the rate-of-change of the measured value.

Low cutback Lcb The number of display units below setpoint at which the controller will cutback the output power in order to prevent overshoot on heat up.

High Cutback Hcb The number of display units above setpoint at which the controller will increase the output power in order to prevent undershoot on cool down.

Relative cool gain

rEL.C Only present if cooling has been configured. Sets the cooling proportional band by dividing the Pb value by the rEL.C value.

Table 4-1 Tuning parameters

Page 59: 2208e/2204e Installation and Operating handbook issue 3

Installation and Operation Handbook Tuning

2208e and 2204e Controller 4-3

4.2. AUTOMATIC TUNING

This method automatically determines the value of the parameters listed in table 4-1 on the previous page.

The 2208e and 2204e use a ‘one-shot’ tuner which works by switching the output on and off to induce an oscillation in the measured value. From the amplitude and period of the oscillation, it calculates the tuning parameter values.

If the process cannot tolerate full heating or cooling being applied during tuning, then the level of heating or cooling can be restricted by setting the heating and cooling power limits in the Output list. However, the measured value must oscillate to some degree for the tuner to be able to calculate values

A One-shot Tune can be performed at any time but normally it is performed only once during the initial commissioning of the process. However, if the process under control subsequently becomes unstable (because its characteristics have changed), you can re-tune again for the new conditions.

It is best to start tuning with the process at ambient temperature. This allows the tuner to calculate more accurately the low cutback and high cutback values that restrict the amount of overshoot or undershoot.

4.2.1. Heating and Cooling Output Cycle Times

Before commencing a tuning cycle, set the values of CYC.H (heat cycle time) and CYC.C (cool cycle time) in the op (output list). These values apply if you are using a logic, relay or triac output. They have no effect on a DC output.

A logic output switching a solid state relay can be set to values such as 1 sec.

A relay or triac output should be set to 20 sec.

Page 60: 2208e/2204e Installation and Operating handbook issue 3

Tuning Installation and Operation Handbook

4-4 2208e and 2204e Controller

4.3. HOW TO TUNE

1. Set the setpoint to the value at which you will normally operate the process.

2. In the ‘Atun’ list, select ‘tunE’ and set it to ‘on’

3. Press the Page and Scroll buttons together to return to the Home display. The display will flash ‘tunE’ to indicate that tuning is in progress.

4. The controller will induce an oscillation in the temperature by turning the heating on and then off. The first cycle will not complete until the measured value has reached the required setpoint.

5. After two cycles of oscillation the tuning will be completed and the tuner will switch itself off.

6. The controller will then calculate the tuning parameters listed in Table 4-1 and will resume normal control action.

If you want ‘Proportional only’ or ‘PD’ or ‘PI’ control, you should set the ‘ti’ or ‘td’ parameters to OFF before commencing the tuning cycle. The tuner will leave them off and will not calculate a value for them.

For valve position tuning and set-up, please refer to Appendix D.

Page 61: 2208e/2204e Installation and Operating handbook issue 3

Installation and Operation Handbook Tuning

2208e and 2204e Controller 4-5

4.3.1. Typical automatic tuning cycle

4.3.2. Calculation of the cutback values Low cutback and High cutback are values that restrict the amount of overshoot or undershoot that occur during large step changes in temperature (for example, under startup conditions).

If either low cutback or high cutback is set to ‘Auto’ the values will be fixed at three times the proportional band, and will not be changed during automatic tuning.

Time

Setpoint

Temperature

Page 62: 2208e/2204e Installation and Operating handbook issue 3

Tuning Installation and Operation Handbook

4-6 2208e and 2204e Controller

4.4. MANUAL TUNING

If for any reason automatic tuning gives unsatisfactory results, you can tune the controller manually. There are a number of standard methods for manual tuning. The one described here is the Ziegler-Nichols method.

With the process at its normal running temperature:

1. Set the Integral Time ‘ti and the Derivative Time ‘td’ to OFF.

2. Set High Cutback and Low Cutback, ‘Hcb’ and ‘Lcb’, to ‘Auto’

3. Ignore the fact that the temperature may not settle precisely at the setpoint

4. If the temperature is stable, reduce the proportional band ‘Pb’ so that the temperature just starts to oscillate. If the temperature is already oscillating, increase the proportional band until it just stops oscillating. Allow enough time between each adjustment for the loop to stabilise. Make a note of the proportional band value ‘B’ and the period of oscillation ‘T’.

5. Set the Pb, ti, td parameter values according to the calculations given in Table 4-2.

Type of control

Proportional

band ‘Pb’

Integral time ‘ti’

Derivative time

‘td’

Proportional only

2xB

OFF

OFF

P + I control

2.2xB

0.8xT

OFF

P + I + D control

1.7xB

0.5xT

0.12xT

Table 4-2 Tuning values

Page 63: 2208e/2204e Installation and Operating handbook issue 3

Installation and Operation Handbook Tuning

2208e and 2204e Controller 4-7

4.4.1. Setting the cutback values The above procedure sets up the parameters for optimum steady state control. If unacceptable levels of overshoot or undershoot occur during start-up or for large step changes in temperature, then manually set the cutback parameters Lcb and Hcb.

Proceed as follows:

1. Set the low and high cutback values to three proportional bandwidths (that is to say, Lcb = Hcb = 3 x Pb).

2. Note the level of overshoot or undershoot that occurs for large temperature changes (see the diagrams below).

In example (a) increase Lcb by the overshoot value. In example (b) reduce Lcb by the undershoot value.

Example (a)

Temperature

Example (b)

Temperature

Where the temperature approaches setpoint from above, you can set Hcb in a similar manner.

Time

Undershoot

Setpoint Overshoot

Page 64: 2208e/2204e Installation and Operating handbook issue 3

Tuning Installation and Operation Handbook

4-8 2208e and 2204e Controller

4.4.2. Integrating action and manual reset In a full three-term controller (that is, a PID controller), the integral term ‘ti’ automatically removes steady state errors from the setpoint. If the controller is set up to work in two-term mode (that is, PD mode), the integral term will be set to OFF. Under these conditions the measured value may not settle precisely at setpoint. When the integral term is set to OFF the parameter manual reset (code rES) appears in the PiD LisT in ‘FuLL’ Access level. This parameter represents the value of the power output that will be delivered when the error is zero. You may set this value manually in order to remove the steady state error.

4.4.3. Automatic droop compensation (Adc) The steady state error from the setpoint, which occurs when the integral term is set to OFF, is sometimes referred to as ‘droop’. Adc automatically calculates the manual reset value in order to remove this droop. To use this facility, you must first allow the temperature to stabilise. Then, in the autotune parameter list, you must set Adc to ‘CALC’. The controller will then calculate a new value for manual reset, and switch Adc to ‘mAn’.

Adc can be repeated as often as you require but between each adjustment you must allow time for the temperature to stabilise.

Page 65: 2208e/2204e Installation and Operating handbook issue 3

2208e and 2204e Controller 5-1

Installation and Operation Handbook Configuration

5 Chapter 5 CONFIGURATION

5 Chapter 5 CONFIGURATION.................................................1

5.8 SELECTING CONFIGURATION LEVEL ..........................................2

5.9 SELECTING A CONFIGURATION PARAMETER............................3

5.10 LEAVING CONFIGURATION LEVEL...........................................3

5.11 STEPS INVOLVED IN CONFIGURING A CONTROLLER...........3

5.12 NAVIGATION DIAGRAM (PART A)..............................................4

5.13 CONFIGURATION PARAMETER TABLES .................................7

5.14 CONFIGURATION OF DIGITAL COMMUNICATIONS ..............16 5.14.1 To Configure the Function, and Baud Rate .........................16 5.14.2 To Set Instrument Address ..................................................17

5.15 DEVICENET ................................................................................17 5.15.1 The EDS File........................................................................17 5.15.2 ODVA Compliance...............................................................17

WARNING Configuration is protected and should only be carried out by an authorised person. Incorrect configuration could result in damage to the process being controlled and/or personal injury. It is the responsibility of the person commissioning the instrument to ensure that the configuration is correct.

Whenever the configuration menus are displayed or accessed all controller outputs are held at the power off state and control operation is suspended until exiting from configuration.

!

!

Page 66: 2208e/2204e Installation and Operating handbook issue 3

5-2 2208e and 2204e Controller

nstallation and Operation Handbook Configuration

5.8 SELECTING CONFIGURATION LEVEL

Figure 5.1

PASSPASSPASSPASS

“HOME” display

Press Page button

repeatedly until Access List appears

GotoGotoGotoGoto

conF conF conF conF

20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0

ACCSACCSACCSACCS

LiStLiStLiStLiSt

or to enter password

(factory default = 1)

If incorrect password entered

Note: Selecting OPErFuLLor Edit

will allow direct entry to these levels at this point

1st press

2nd press

3rd press

If the password has been set to ‘0’ - access

is permanently unlocked & the lower readout always shows

PASS

2 secs

or to select ConF.

CodECodECodECodE

1 1 1 1

PASSPASSPASSPASS

At this point the controller is in

configuration level

or to enter password

(factory default = 2)

Repeated pressing of “Page” button selects configuration list headings in a

continuous loop

ConFConFConFConF 2 2 2 2

4th press

InstInstInstInst ConF ConF ConF ConF

IPIPIPIP ConFConFConFConF

Page 67: 2208e/2204e Installation and Operating handbook issue 3

2208e and 2204e Controller 5-3

Installation and Operation Handbook Configuration

5.9 SELECTING A CONFIGURATION PARAMETER

Figure 5.2

5.10 LEAVING CONFIGURATION LEVEL

Figure 5.3

5.11 STEPS INVOLVED IN CONFIGURING A CONTROLLER

The navigation diagram which follows shows the general location of parameters which define the way in which the controller works. They are grouped under headings. The actual parameters shown in your controller may differ slightly since some appear only as a result of selecting others. A full list of possibilities is included in the PARAMETER TABLES which follow the navigation diagram.

ExitExitExitExit

no no no no

Keep pressing until Exit display appears

Press or to select YES After a 2 second delay the screen will blank, the instrument will reset,

and revert to the Home display

PASSPASSPASSPASS

Select the desired configuration list using See Navigation diagram for the full list of headings

or to select oC oF or oK

Continue to press to access all parameters in the list before returning to list header

ConFConFConFConF 2 2 2 2

1st press

InstInstInstInst ConF ConF ConF ConF

UnitUnitUnitUnit

oCCCC

2nd

Page 68: 2208e/2204e Installation and Operating handbook issue 3

5-4 2208e and 2204e Controller

nstallation and Operation Handbook Configuration

5.12 NAVIGATION DIAGRAM (PART A)

Instrument Input User cal. Alarms Logic input 1 Logic input 2 Output 3 Config Config Config Config Config Config Config

Ltch

no

Unit

°C

inSt

ConF

See table B

iP

ConF

CAL

ConF

AL

ConF

Lb

ConF AA

ConF

DEc.P

0000

CtrL

Pid

Act

rEv

CooL

Lin

InPt

K.tc

rng.L

0.0

AdJ

no

Pnt.L

0.0

Pnt.H

100.0

OFS.L

0.0

AL1

FSH

OFS.H

0.0

id

LoG.i

Func

mAn

id

Log.I

Func

SP.2

iD

rELy

Sens

nor

PwrF

on

Pd.tr

no

FoP

no

InP.L

4.0

InP.H

20.0

VAL.L

0.0

VAL.H

100.0

CJC

Auto

BLoc

no

AL 2

FSL

Ltch

no

BLoc

no

AL 3

OFF

Ltch

no

BLoc

no

AL 4

OFF

Ltch

no

BLoc

no

Summary Step through List Headers

using the ‘Page’ button Choose a parameter from a list

using the ‘Scroll’ button Change value

using the ‘Raise/Lower’ buttons or

The first four headings set up the controller functions, as follows:

Instrument Config. - Groups those parameters associated with the display and control action.

Input Config. - selects the input sensor type

User cal. Config. - to calibrate to external reference sources

Alarms Config. - sets up the alarm types

Imp

Auto

Func

diG

Sbr.t

Sb.OP

La

ConF

rng.H

100.0

LC.Hi

100

Page 69: 2208e/2204e Installation and Operating handbook issue 3

2208e and 2204e Controller 5-5

Installation and Operation Handbook Configuration

NAVIGATION DIAGRAM (PART B)

Comms Output 1 Output 2 Output 3 10A output Password Config Config Config Config Config Config

Figure 5.4

id

cmS

HA

ConF

See Table B parameter

table, page 5-14

See Table B parameter

table, page 5-14

1A

ConF 2A

ConF

3A

ConF

Exit

no

4A

ConF

PASS

ConF

id

dC.OP

id

rELy

id

rELy

id

rELy

ACC.P

1

Func

cms

Func

diG

SEnS

nor

Func

HEAT

Func

COOL

Baud

9600

SEnS

inv

SEnS

nor

Func

HEAt

cnF.P

2

SEnS

nor

PrtY

nonE

Out.L

0.0

RESn

Ful

Out.H

100.0

VaL.L

0.0

VaL.H

100.0

Page 70: 2208e/2204e Installation and Operating handbook issue 3

5-6 2208e and 2204e Controller

nstallation and Operation Handbook Configuration

Heading Input/Output Functions Wiring Terminals

The first four headings set up the controller functions as follows:

InSt ConF Sets up display and control parameters Not applicable

IP ConF Selects the input sensor type Not applicable

CAL ConF To calibrate to external reference sources Not applicable

AL ConF Sets up the alarm types Not applicable The remaining headings configure the controller input/output functions.

The upper readout corresponds to rear terminal numbers associated with a particular i/o.

LA LB Conf Sets up the action of the two digital inputs LA & LB

AA Conf Sets up the action of the fixed relay on output AA AA to AC

HA Conf Sets up digital comms type HB to HF

1A 2A Conf Sets up the output modules 1A and 2A 1A & 1B / 2A & 2B

3A Conf Sets up the action of the fixed relay on output 3A 3A to 3C

4A Conf Sets the action of the 10A output relay in 2204 4A to 6D

Pass Conf To choose new passwords

Exit no/Yes To leave configuration level and return to operator level

Page 71: 2208e/2204e Installation and Operating handbook issue 3

2208e and 2204e Controller 5-7

Installation and Operation Handbook Configuration

5.13 CONFIGURATION PARAMETER TABLES

Name Parameter description Values Meaning

inStinStinStinSt Instrument configuration

unit Instrument C Centigrade (default UK)

units F Fahrenheit (default USA)

k Kelvin

nonE Units are not displayed

dEc.P Decimal places in the nnnn None

displayed value nnn.n One

nn.nn Two

CtrL Control type on.OF On/off control

Pid PID control

vp Boundless VP Control (no feedback pot required)

Act Control action rEv Reverse acting (required for temperature control) - output decreases on approach to SP

dir Direct acting

cooL Type of cooling Lin Linear

oiL Oil (50mS min on time)

H2O Water(non-linear)

FAn Fan (0.5S min on time)

PwrF Power feedback on Power feedback is on (compensates for changes in supply voltage)

OFF Power feedback is off

Pd.tr Bumpless manual/auto no Non-bumpless transfer

transfer when using PD control YES Bumpless transfer (auto to manual and manual to auto)

FoP Forced manual output no Bumpless manual/auto transfer

Yes Returns to the manual value last set in manual mode.

Sbr.t Sensor break output Sb.OP Go to pre-set value (maintains output at a known, safe level)

HoLd Freeze output (maintains output at value immediately before break)

LC.Hi Load Current Scaling Factor 100 See Chapter 9

Factory default parameter values and states are included where applicable and are indicated by the shaded areas in the following tables.

i

Page 72: 2208e/2204e Installation and Operating handbook issue 3

5-8 2208e and 2204e Controller

nstallation and Operation Handbook Configuration

Name Parameter description Value Meaning

iPiPiPiP Input configuration

inPt Input type J.tc J thermocouple (default USA)

K.tc K thermocouple (default UK)

L.tc L thermocouple

r.tc R thermocouple (Pt/Pt13%Rh)

b.tc B thermocouple (Pt30%Rh/Pt6%Rh)

n.tc N thermocouple

t.tc T thermocouple

S.tc S thermocouple (Pt/Pt10%Rh)

PL.2 PL 2 thermocouple

NOTE: rtd 100Ω platinum resistance thermometer.

After selecting an input type, do not forget to adjust the setpoint limits in Full Access level

C.tc Custom downloaded input type. The default is C thermocouple, or the name of the downloaded custom input will be displayed.

mV Linear millivolt (Also mA input via an external 2.49Ω current sense resistor)

voLt Linear voltage

rng.L Input range low Display low range for input

rng.H Input range high Display high range for input

CJC CJC ref. temperature Auto Automatic cold junction compensation

(CJC does not appear for 0C 0°C external reference

linear inputs) 45C 45°C external reference

50C 50°C external reference

Linear Input Scaling - The next 4 parameters only appear if a linear input is chosen

inPL

Input value low

inPH

Input value high

VALL

Displayed reading low

VALH

Displayed reading high

ImP Sensor break input impedance trip level

OFF Sensor break detection is disabled Appears for mV or V inputs only

Auto Trip level set by the sensor input table

Hi Trip level set at 7.5KΩ

HiHi Trip level set at 15KΩ (must be selected when voLt input is enabled)

VAL.L

VAL.H

InP.L InP.H

Displayed Value

Electrical Input

Page 73: 2208e/2204e Installation and Operating handbook issue 3

2208e and 2204e Controller 5-9

Installation and Operation Handbook Configuration

Name Parameter description Value Meaning

CALCALCALCAL User calibration config. See Chapter 6 - User calibration

AdJ User cal enable no User calibration is disabled

YES User calibration is enabled

Pnt.L User calibration point low

0 This is the value (in display units) at which a User last performed a low point calibration

Pnt.H User calibration point high

100 This is the value (in display units) at which a User last performed a high point calibration

OFS.L Low point calibration offset

0 Offset, in display units, at the user low calibration point ‘Pnt.L’. This value is automatically calculated when performing low point calibration.

OFS.H High point calibration offset

0 Offset, in display units, at the user high calibration point ‘Pnt.H’. This value is automatically calculated when performing a high point calibration.

* If User calibration is enabled, then the User calibration parameters will appear in the Input list of Operator Full access level. See Chapter 6, User calibration.

Page 74: 2208e/2204e Installation and Operating handbook issue 3

5-10 2208e and 2204e Controller

nstallation and Operation Handbook Configuration

Name Parameter description Values

ALALALAL Alarm configuration Values Defaults if not specified

AL1 Alarm 1 Type As table A OFF

bLoc Alarm 1 Blocking(1) no/YES no

Ltch Alarm 1 Latching no/Auto/man/Evt

no

AL2 Alarm 2 Type As table A OFF

bLoc Alarm 2 Blocking(1) no/YES no

Ltch Alarm 2 Latching no/Auto/man/Evt

no

AL3 Alarm 3 Type As table A OFF

bLoc Alarm 3 Blocking(1) no/YES no

Ltch Alarm 3 Latching no/Auto/man/Evt

no

AL4 Alarm 4 Type As table A OFF

bLoc Alarm 4 Blocking(1) no/YES no

Ltch Alarm 4 Latching no/Auto/man/Evt

no

Table A: Alarm types

OFF No alarm

FSL Full scale low

FSH Full scale high

dEv Deviation band

dHi Deviation high

dLo Deviation low

Lcr Low current

Hcr High current

(1) Blocking allows the alarm to become active only after it has first entered a safe state.

These are ‘soft’ alarms, i.e. Indication only. They would normally be attached to an output. See Chapter 7 for a step by step guide. i

Page 75: 2208e/2204e Installation and Operating handbook issue 3

2208e and 2204e Controller 5-11

Installation and Operation Handbook Configuration

Name Parameter description Values

LALALALA Logic input 1 configuration Functions Action on contact closure

id Identity of input LoG.i Logic input

Func Function nonE None mAn Manual mode select rmt Remote setpoint select SP.2 Setpoint 2 select ti H Integral hold Ac.AL Acknowledge alarms Loc.b Lock Key pad rset Reset StbY Standby - ALL outputs = OFF AmPS PDS load current input

LbLbLbLb Logic input 2 configuration Functions Action on contact closure

As per Logic input 1 except ‘AmPS’ not available

Page 76: 2208e/2204e Installation and Operating handbook issue 3

5-12 2208e and 2204e Controller

nstallation and Operation Handbook Configuration

Name Parameter description Functions Meaning

AAAAAAAA Alarm relay configuration Functions Meaning

id Identity of output rELy Relay

Func Function nonE None

diG Function set by diG.F (as in Table B)

HEAt Heating

COOL Cooling

For function = diG go to table B on the next page

SEnS Sense of output (always appears)

nor

inv

Normal (heat & cool outputs) Inverted (alarms de-energised in the alarm state)

HAHAHAHA Comms module config Functions Meaning

id Identity of the option installed PDS.i PDS setpoint input cmS 2- or 4-wire EIA-485 (422) or

EIA-232 comms module

Func Function

Some of the following parameters may appear if one of the comms options is installed

cms DIGITAL Communication protocol ordered (ModBus, EIBisynch or DeviceNet)

nonE None

The following parameters will appear if the PDSIO setpoint input option is installed.

nonE No PDS function SP.iP PDS setpoint input

VAL.L PDS low input value Range = -999 to 9999

VAL.H PDS high input value Range = -999 to 9999

The following parameters will appear if id = cms

BAud Baud Rate - ModBus 1200 (1), 2400, 4800, 9600, 19.20, 1920 (19200)

BAud Baud Rate - DeviceNet

125(K), 250(K), 500(K)

Prty (2) Comms Parity nonE No parity

EvEn Even parity

Odd Odd parity

RESn (2) Comms Resolution FuLL Full resolution

Int Integer resolution

Note 1: 1200 baud rate not supported by EIBisynch Note 2: Not used with some communication protocols. Please consult factory.

Page 77: 2208e/2204e Installation and Operating handbook issue 3

2208e and 2204e Controller 5-13

Installation and Operation Handbook Configuration

Name Parameter description Function Meaning

1A Output 1 configuration Function Meaning

id Identity of module installed nonE No module fitted

RELy Relay output

dC.OP DC output (isolated)

LoG Logic or PDS output

SSr Triac output

Func Function NonE Module does not operate

DIG Function set by diG.F

HEAt Heating output

COOL Cooling output

Only appear for id = dC.OP OP Retransmission of output demand

Only appear for id = dC.OP PV Retransmission of Process Value

Only appear for id = dC.OP Err Retransmission of error

Only appear for id = dC.OP wSP Retransmission of setpoint

Only appear for id = LoG SSr.1 PDS mode 1 heating

Only appear for id = LoG SSr.2 PDS mode 2 heating

For function = diG (refer to table B on page 5-14)

SEnS Sense of output nor

inv

Normal (e.g.heating and cooling) Inverted (alarms - de-energise in alarm)

DC output scaling For id = dC.OP the following parameters appear

Out.L DC output minimum 0mA to 20mA

Out.H DC output maximum 0mA to 20mA

Page 78: 2208e/2204e Installation and Operating handbook issue 3

5-14 2208e and 2204e Controller

nstallation and Operation Handbook Configuration

Table B The following parameters appear if ‘diG’ is chosen as the function.

diG.F Digital output functions noch No change

Any number of the functions listed can be combined on to

the output. Use the and

buttons to select a desired digital function. After two seconds the display will blink and return to the ‘noch’ display. Use the arrows again to scroll through the function list. The previously selected function display will show two decimal points indicating that it has been added to the output.

cLr 1 - - - * 2 - - - *

3 - - - *

4 - - - *

MAn Sbr Lbr Htrf Ld.F ENd SPAn SSrF NwaL RmtF Ct.OP Ct.Sh

Clear all existing functions Alarm 1 * Alarm 2 * Alarm 3 * Alarm 4 * Manual/Auto Sensor Break Loop Break Heater Fail Load Fail END Program PV Out of Range PDSIO® SSR Failure New Alarm Remote Sp Fail CTx open circuit CTx short circuit

* From previous page. In place of the dashes, the last three characters indicate the alarm type as per table A in the AL list: eg 1FSL = Full Scale Low If an alarm is not configured the displayed name will differ: e.g. ‘AL 1 will be shown, for the first alarm.

Page 79: 2208e/2204e Installation and Operating handbook issue 3

2208e and 2204e Controller 5-15

Installation and Operation Handbook Configuration

Name Parameter description Function Meaning

2A2A2A2A Output 2 configuration Function Meaning

id Identity of module installed nonE No module fitted

rELy Relay output

LoG Logic

SSr Triac output

Func Function nonE none

Outputs diG Function set by diG.F HEAt Heating output COOL Cooling output

Logic Inputs mAn Manual mode select rmt Remote setpoint select SP.2 Setpoint 2 select ti H Integral hold Ac.AL Acknowledge alarms Loc.b Lock Key pad rset Reset StbY Standby - ALL outputs = OFF AmPS PDS load current input

For Func = diG (Refer to table B).

SEnS Sense of output nor

inv

Normal (heat and cool outputs) Inverted (alarms - de-energise in alarm)

3A3A3A3A Output 3 configuration As per output 2A configuration

4A4A4A4A 10Amp heating output Available on 2204e only.

As per Output 3A configuration

PASSPASSPASSPASS Password list

ACC.P FuLL or Edit level password

cnF.P Configuration level Password

Note:- When passwords are changed please make a note of the new numbers

ExitExitExitExit Exit Configuration nononono/YESYESYESYES

Page 80: 2208e/2204e Installation and Operating handbook issue 3

5-16 2208e and 2204e Controller

nstallation and Operation Handbook Configuration

5.14 CONFIGURATION OF DIGITAL COMMUNICATIONS

The 2208e and 2204e controllers can be fitted with the following digital communications modules:-

Protocol Module Fitted Order Code ModBus 2-wire RS485

4-wire RS422 RS232

2YM 2FM 2AM

EI-Bisynch 2-wire RS485 4-wire RS422 RS232

2YE 2FE 2AE

DeviceNet 2DN

5.14.1 To Configure the Function, and Baud Rate All devices on a network must have the same Baud Rate, Parity and Resolution. Parity and Resolution can be set by the same procedure. These will normally be set to None and Full respectively

Comms configuration list - HA

Identity of module

This is a read-only parameter displaying the identity of the module fitted

Function

Set Func = CmS to select the protocol. Ensure that the correct Comms module has been fitted. To disable comms set Func to nonE.

HA ConF

id

CmS

Func

CmS

bAud

500

Baud Rate

Press or to set the Baud Rate. The choices are:- 1200. 2400, 4800, 9600, 19,200 for Modbus and EI-Bisynch 125(K), 250(K), or 500(K) for DeviceNet

Page 81: 2208e/2204e Installation and Operating handbook issue 3

2208e and 2204e Controller 5-17

Installation and Operation Handbook Configuration

5.14.2 To Set Instrument Address All devices on a network must have a different node address. Instrument address is set in Full operator level. Exit configuration level. This is described on page 5-3.

5.15 DEVICENET

The following is applicable to DeviceNet only.

5.15.1 The EDS File The EDS (Electronic Data Sheet) file for the Series 2200e is named 2K2DN.EDS and is available from your supplier, or electronically by going to Web site (www.eurotherm.com). The EDS file is designed to automate the DeviceNet network configuration process by precisely defining vendor-specific and required device parameter information. Following a data sheet metaphor, the EDS file describes a device’s configurable parameters, including its legal and default values and the public interfaces to those parameters. Software configuration tools utilize the EDS files to configure a DeviceNet network.

5.15.2 ODVA Compliance This interface has been tested to comply with the full requirements of the ODVA (Open DeviceNet Vendors Association) conformity tests.

Comms list

From the HOME display, press the Page button until you reach the cmS list

Address

Press the raise or lower buttons until the desired address is set. The choices are:- 0 to 99 for Modbus and EI-Bisynch 0 to 64 for DeviceNet.

id Cms

Addr

7

Page 82: 2208e/2204e Installation and Operating handbook issue 3

5-18 2208e and 2204e Controller

nstallation and Operation Handbook Configuration

Page 83: 2208e/2204e Installation and Operating handbook issue 3

Installation and Operation Handbook User Calibration

2208e and 2204e Controller 6-1

6 Chapter 6 USER CALIBRATION

6 Chapter 6 User calibration ..............................................1

6.8 What is the Purpose of User Calibration? ....................................2

6.9 User Calibration Enable ..................................................................3

6.10 Single point calibration................................................................4

6.11 Two point calibration ...................................................................5

6.12 Calibration points and Calibration offsets.................................6

Page 84: 2208e/2204e Installation and Operating handbook issue 3

User Calibration Installation and Operation Handbook

6-2 2208e and 2204e Controller

This chapter has five topics:

• WHAT IS THE PURPOSE OF USER CALIBRATION?

• USER CALIBRATION ENABLE

• SINGLE POINT CALIBRATION

• TWO POINT CALIBRATION

• CALIBRATION POINTS AND CALIBRATION OFFSETS To understand how to select and change parameters in this chapter you will need to have read Chapter 2 - Operation, Chapter 3- Access Levels and Chapter 5 - Configuration.

6.8 WHAT IS THE PURPOSE OF USER CALIBRATION?

The basic calibration of the controller is highly stable and set for life. User calibration allows you to offset the ‘permanent’ factory calibration to either:

1. Calibrate the controller to your reference standards

2. Match the calibration of the controller to that of a particular transducer or sensor input

3. Calibrate the controller to suit the characteristics of a particular installation.

User calibration works by introducing zero and span offsets onto the factory set calibration. The factory set calibration can always be retrieved.

Page 85: 2208e/2204e Installation and Operating handbook issue 3

Installation and Operation Handbook User Calibration

2208e and 2204e Controller 6-3

6.9 USER CALIBRATION ENABLE

The User calibration facility must first be enabled in configuration level by setting the parameter ‘AdJ' in the CAL conf list to 'YES' This will make the User calibration parameters appear in Operator ‘FuLL’ level. Select configuration level as shown in Chapter 5, Configuration

CAL Conf

AdjYES

Exitno

The User calibration configuration List Press until you reach the ‘CAL conf list ress the Scroll button until you reach

User calibration enable

Use or to select: YES: Calibration enable no: Calibration disabled Press and together to go to the Exit display

Exit configuration

Use or to select ‘YES’ and return to Operator level.

Page 86: 2208e/2204e Installation and Operating handbook issue 3

User Calibration Installation and Operation Handbook

6-4 2208e and 2204e Controller

6.10 SINGLE POINT CALIBRATION

Your controller is calibrated for life against known reference sources during manufacture. A calibration offset is often used to allow the controller to compensate for sensor and other system errors. The normal procedure is to set up the system under test against a known independent reference, as follows: Set up the process to be calibrated such that the known reference displays the required value (temperature). Observe the reading on the controller. If it is different, proceed as follows: Select ‘FuLL Access level as described in Chapter 3

iP List

CAL USEr

CAL.S Lo

Input list header

Press until you reach the input list header. Press Scroll until you reach the ‘CAL’ display

Calibration type

Use or to select either ‘FACt’ or ‘USEr’. Selecting ‘FACt’ will reinstate the factory calibration and hide the following User calibration parameters. Selecting ‘USEr’ will reinstate any previously set User calibration and make available the User parameters, as follows: Press the Scroll button Calibrate low point? Use or to select ‘YES’ Selecting ‘no’ will hide the next parameter

Press the Scroll button continued on the next page

Page 87: 2208e/2204e Installation and Operating handbook issue 3

Installation and Operation Handbook User Calibration

2208e and 2204e Controller 6-5

To protect the calibration against unauthorised adjustment return to Operator level and make sure that the calibration parameters are hidden. Parameters are hidden using the ‘Edit’ facility describe in Chapter 3.

6.11 TWO POINT CALIBRATION

The previous section described how to perform a single point calibration which applies a fixed offset over the full display range of the controller. A two-point calibration is used to calibrate the controller at two points and apply a straight line between them. Any readings above or below the two calibration points will be an extension of this straight line. For this reason it is best to calibrate with the two points as far apart as possible.

Proceed as follows:

1. Decide upon the low and high points at which you wish to calibrate.

2. Perform a single point calibration at the low calibration point in the manner described above

3. Set the process under calibration such that the known reference exhibits the required higher Process Value (temperature) and allow to stabilize.

4. Press the Scroll button to obtain the high calibration point as shown in the following diagrams.

Adj50.0

Adjust the low point calibration

The controller will display the current measured input value in the lower readout. Use or to adjust the reading to the reference source value, if different. After a two second delay the display will blink and the reading will change to the new, calibrated value. You can calibrate at any point over the entire display range This is a single point calibration which applies a fixed offset over the full display range of the controller. The calibration is now complete. You can return to the factory calibration at any time by select ‘FACt’ in the CAL display shown earlier. Press and together to return to the Home display

Page 88: 2208e/2204e Installation and Operating handbook issue 3

User Calibration Installation and Operation Handbook

6-6 2208e and 2204e Controller

To protect the calibration against unauthorised adjustment return to Operator level and make sure that the calibration parameters are hidden. Parameters are hidden using the ‘Edit’ facility described in Chapter 3.

6.12 CALIBRATION POINTS AND CALIBRATION OFFSETS

If you wish to see the points at which the User calibration was performed and the value of the offsets introduced these are shown in Configuration, under CAL ConF. The parameters are:

Name Parameter description Meaning

Pnt.L User low calibration point This is the value (in display units) at which a User last performed an ‘AdJ.L’ (adjust low calibration).

Pnt.H User high calibration point This is the value (in display units) at which a User last performed an ‘AdJ.H’ (adjust high calibration).

OFS.L Low point calibration offset Offset, in display units, at the user low calibration point ‘Pnt.L

OFS.H High point calibration offset Offset, in display units, at the user high calibration point ‘Pnt.H.

CAL.S Hi

Adj 800.0

Calibrate high point? Use or to select ‘Hi’

Press the Scroll button

Adjust the high point calibration

The controller will display the current measured input value in the lower readout. Use or to adjust the reading to the reference source value, if different. After a two second delay the display will blink and the reading will change to the new, calibrated value. The calibration is now complete. You can return to the factory calibration at any time by select ‘FACt’ in the CAL display shown earlier.

Press and together to return to the Home display

Page 89: 2208e/2204e Installation and Operating handbook issue 3

Installation and Operation Handbook Alarm Operation

2208e and 2204e Controller 7-1

7 Chapter 7 ALARM CONFIGURATION

7 Chapter 7 ALARM CONFIGURATION..............................1

7.1 DEFINITION OF ALARMS AND EVENTS........................................2 7.1.1 TYPES OF ALARMS.............................................................................2

7.2 DIGITAL OUTPUT FUNCTIONS ......................................................4

7.3 STEP1 - CONFIGURING THE FOUR ‘SOFT’ ALARMS..................5

7.4 STEP 2 - ATTACHING AN ALARM TO A PHYSICAL OUTPUT .....6

7.5 STEP 3 - GROUPING ALARMS ON A SINGLE OUTPUT...............7

7.6 STEP 4 - REMOVING ALARMS FROM AN OUTPUT .....................7 The 2200e series controllers are capable of very sophisticated alarm strategies and, although setting up of alarms has already been covered in previous chapters, this section has been included to enable operators and commissioning engineers to design their own strategies for optimum plant operation.

Page 90: 2208e/2204e Installation and Operating handbook issue 3

Alarm Operation Installation and Operation Handbook

7-2 2208e and 2204e Controller

7.1 DEFINITION OF ALARMS AND EVENTS

See also section 1.11 for further information on Alarms.

Alarms are used to alert an operator when a pre-set level or condition has been exceeded. They are normally used to switch an output - usually a relay - to provide interlocking of the machine or plant or external audio or visual indication of the condition.

Soft Alarms are indication only within the controller and are not attached to an output (relay).

Events - can also be alarms - but are generally defined as conditions which occur as part of the normal operation of the process. They do not generally require operator intervention.

Events are referred to as Digital Output Functions in the manual (see Table B, page 5-14).

For the purposes of the operation of this instrument alarms and events can be considered the same.

7.1.1 TYPES OF ALARMS The use of alarms in the 2208e and 2204e controllers is extremely versatile. Up to 4 alarms can be configured. Any combination of these 4 alarms can be attached to any one or more outputs, or any number of the available “soft” alarms can be combined to operate a single output.

Note: In a three term controller at least one of these outputs is used to maintain the required temperature of the process.

Outputs 1A and 2A Are plug in modules.

Normally used for control outputs, eg. Heat and Cool, but can be used for alarm outputs.

Outputs AA and 3A Are fixed relays. Normally used for alarms or events, but can be used as control outputs.

10A Output 4A (2204e 0nly) Is a plug in 10 Amp relay output. Normally used to switch heaters directly in control mode, but can be used as an alarm output.

!

Page 91: 2208e/2204e Installation and Operating handbook issue 3

Installation and Operation Handbook Alarm Operation

2208e and 2204e Controller 7-3

There are seven process alarm types listed below. Alarm Types are found in configuration mode under the Alarm Config. List.

ALARMS

Full Scale High The PV exceeds a set high level

Full Scale Low The PV exceeds a set low level

Deviation Band The difference between PV & SP is outside a set band

Deviation High The difference between PV & SP is higher than a set level

Deviation Low The difference between PV & SP is lower than a set level

High Current The measured current returned from a PDS slave is higher than a set level. See also Chapter 9.

Low Current The measured current returned from a PDS slave is lower than a set level. See also Chapter 9.

Each alarm can be set to:

Latching Alarm is indicated until acknowledged (Off, Auto, MAN)

Auto Acknowledge: ( Ltch Ltch Ltch Ltch AutoAutoAutoAuto) If the alarm is acknowledged while the alarm condition is still present, it will cause the alarm to reset as soon as the alarm condition is removed.

Manual Acknowledge: ( Ltch Ltch Ltch Ltch mAnmAnmAnmAn) If the alarm is acknowledged while the alarm condition is still present, it will be ignored. A further acknowledgement is required when the alarm condition has been removed to cause the alarm to reset.

Blocking Alarm occurs after it has been through a start up phase not in alarm condition.

Sense Of Output Relay energised or de-energised in alarm condition. See also sections 1-12 and 7.4.

Soft Alarms Indication only and do not operate an output.

See also Section 1.11 for further information on alarm types.

Page 92: 2208e/2204e Installation and Operating handbook issue 3

Alarm Operation Installation and Operation Handbook

7-4 2208e and 2204e Controller

7.2 DIGITAL OUTPUT FUNCTIONS

In addition there are nine “digital output functions” used as events or alarms depending upon the requirements of the process under control:

Sensor Break The input is open circuit

Loop Break The controller does not measure a response to an output change

Load Failure Used with PDS Mode 1 load failure. See also Chapter 9.

Manual Controller in manual mode

PV Out Of Range Process Variable too high or too low

Remote SP Fail No signal measured at the remote set point input terminals

Heater Fail Used with PDS Mode 2 heater open circuit. See also Chapter 9 .

SSR Fail Used with PDS Mode 2 solid state relay open or short circuit. See also Chapter 9

Program END Signals the end of a program

New Alarm Signals a new alarm

The Sense of the Output can be set to relay energised or de-energised in the alarm condition for any of the above functions.

!

Page 93: 2208e/2204e Installation and Operating handbook issue 3

Installation and Operation Handbook Alarm Operation

2208e and 2204e Controller 7-5

7.3 STEP1 - CONFIGURING THE FOUR ‘SOFT’ ALARMS

Soft alarms are indication only and do not operate a relay

Go To Configuration Level Refer to Chapter 5

ConFConFConFConFPASSPASSPASSPASS

AAAALLLL ConfConfConfConf

AAAALLLL 1 1 1 1DevDevDevDev

LtchLtchLtchLtchnononono

Press “PAGE” key as many times as necessary to find Alarm Configuration

Press “SCROLL” key to the alarm which needs to be configured

Alarm Type choices are

OFF OFF

FSL Full Scale Low

FSH Full Scale High

dEv deviation Band

dHi deviation High

dLo deviation low

Lcr Low current

Hcr High current

Press “SCROLL” key to choose alarm 1 latching or non-latching

Choices No/Auto/Man

Press

bLocbLocbLocbLoc nononono

Press “SCROLL” key to choose alarm 1 blocking

Choices Yes/No

Press

Press “SCROLL” key to repeat for alarms 2 - 4 to return to list header

Figure 7.1

Page 94: 2208e/2204e Installation and Operating handbook issue 3

Alarm Operation Installation and Operation Handbook

7-6 2208e and 2204e Controller

7.4 STEP 2 - ATTACHING AN ALARM TO A PHYSICAL OUTPUT

This may be necessary if: 1. The instrument has been supplied un-configured or it is required to re-configure 2. Alarm relays are added

GF GF GF GF 3FSH 3FSH 3FSH 3FSH

IdIdIdId rELy rELy rELy rELy

FuncFuncFuncFunc diG diG diG diG

Press “PAGE” key as many times as necessary to find AA Configuration

Press “SCROLL” key to identification of output type (this is read only)

Press “SCROLL” key to output Function

ConFConFConFConF PASS PASS PASS PASS

AAAAAAAA Conf Conf Conf Conf

Use or to select diG Other choices are:

1. Heat

2. COOL

3. None

Use or buttons to select a desired digital function, e.g., 3FSH. Other choices are shown in the table on the next page. After two seconds, the display will blink and return to the ‘noch’ (no change) display. Use the arrows again to scroll through the function list. The previously selected function will show 2 decimal points indicating that it has been added to the output, i.e., 3F.S.H.

Use or to select: 1. inverted (relay de-energised

in alarm) 2. direct (relay energised in

alarm)

Press “SCROLL” key to digital output function

Keep pressing “SCROLL” button to return to list header

SEnSSEnSSEnSSEnS inv inv inv inv

DiGFDiGFDiGFDiGF noch noch noch noch

Figure 7.2

Page 95: 2208e/2204e Installation and Operating handbook issue 3

Installation and Operation Handbook Alarm Operation

2208e and 2204e Controller 7-7

7.5 STEP 3 - GROUPING ALARMS ON A SINGLE OUTPUT

In the previous example one alarm condition is allocated to one output relay. The 2208e and 2204e controllers allow alarms and events to be grouped on to a single output. These events are shown in the table below. noch No change CLr 1 - - -2 - - -3 - - -4 - - -

Clear all existing functions Alarm 1* Alarm 2* Alarm 3* Alarm 4*

* See Table B page 5-14 See also section 1.12 for further information on alarm grouping.

Figure 7.3

7.6 STEP 4 - REMOVING ALARMS FROM AN OUTPUT

Figure 7.4

GF GF GF GF SbrSbrSbrSbr

GF GF GF GF 3FS3FS3FS3FS

DiGFDiGFDiGFDiGF nochnochnochnoch

DiGFDiGFDiGFDiGF nochnochnochnoch

Press until you reach the 1stsoft alarm you wish to attach to an output, e.g., 3FSH. The display returns to no change after 2 sec. accepting the condition.

Press until you reach the 2nd soft alarm you wish to attach to the output, e.g., Sbr. The display returns to no change after 2 sec. accepting the condition.

Repeat for all alarms to be attached to the chosen output

Press once to show clear After 2 sec. the lower readout reverts to no change clearing all events from the chosen output.

Each time you scroll through the table of alarms, note that 2 decimal points appear confirming acceptance that the particular alarm has been attached to the output, i.e., 3FSH, Sbr, etc.

GF GF GF GF CLrCLrCLrCLr

DiGFDiGFDiGFDiGF nochnochnochnoch

Page 96: 2208e/2204e Installation and Operating handbook issue 3

Alarm Operation Installation and Operation Handbook

7-8 2208e and 2204e Controller

Page 97: 2208e/2204e Installation and Operating handbook issue 3

Installation and Operation Handbook Valve Position

2208e and 2204e Controller 8-1

8. Chapter 8 MOTORISED VALVE CONTROL

8. Chapter 8 MOTORISED VALVE CONTROL ..................1

8.1. Parameters For Motorised Valve Control......................................2

8.2. Commissioning the Motorised Valve Controller ..........................2 8.2.1. Adjusting the minimum on-time ‘Ont.H .............................................2

8.3. MOTORISED VALVE APPLICATIONS ............................................3 8.3.1. Auto Tuning...........................................................................................3 8.3.2. 2200e Valve Positioner Set-up Table....................................................3

Page 98: 2208e/2204e Installation and Operating handbook issue 3

Valve Position Installation and Operation Handbook

8-2 2208e and 2204e Controller

8.1. PARAMETERS FOR MOTORISED VALVE CONTROL

The 2208e and 2204e can be configured for motorised valve control as an alternative to the standard PID control algorithm. This algorithm is designed specifically for positioning motorised valves. The motorised valve algorithm operates in the boundless mode, which does not require a position feedback potentiometer for control purposes.

The following parameter list will appear in the navigation diagram shown in Chapter 1 if your controller is configured for motorised valve control.

Name Description Values

oPoPoPoP Output list Min Max Default

mtr Valve travel time in seconds.

This is the time taken for the valve to travel from its fully closed position to its fully open position.

0.0 999.9 30.0

OP.Lo OP.Lo is the low output power limit. -100.0 100.0 -100.0

OP.Hi OP.Hi is the High output power limit -100.0 100.0 100.0

Ont.H Output pulse minimum on time, in seconds. Auto 999.9 0.2

Table 8-1 Motorised valve parameter list

8.2. COMMISSIONING THE MOTORISED VALVE CONTROLLER

Proceed as follows:

1. Measure the time taken for the valve to be raised from its fully closed to its fully open position and enter this as the value in seconds into the ‘mtr’ parameter.

2. Set all the other parameters to the default values shown in Table 8-1.

The controller can then be tuned using the automatic or manual tuning techniques.

8.2.1. Adjusting the minimum on-time ‘Ont.HOnt.HOnt.HOnt.H The default value of 0.2 seconds is satisfactory for most processes. The minimum on time determines how accurately the valve can be positioned. The shorter the time, the more precise the control. However, if the time is set too short, process noise will cause an excessively busy valve.

Page 99: 2208e/2204e Installation and Operating handbook issue 3

Installation and Operation Handbook Valve Position

2208e and 2204e Controller 8-3

8.3. MOTORISED VALVE APPLICATIONS

8.3.1. Auto Tuning

Before the auto tune is activated, the TD parameter must be set to a numeric value. The TD parameter cannot be set to OFF when an auto tune is activated. When the auto tune is complete, the auto tune will set the TD parameter back to the OFF position.

8.3.2. 2200e Valve Positioner Set-up Table

Name Description Value

ConFConFConFConF Configuration Mode Ctr In the Inst configuration list set the CtrL to vP. vP

1A Module 1A id needs to be a rELy or a SSR.

The Func for 1A should be configured for Heat. (Open Valve)

HEAt

2A Module 2A id needs to be a rELy or a SSR.

The Func for 2A should be configured for COOL. ( Close Valve)

COOL

OPEROPEROPEROPER Operating Mode (OP List)

mtr Valve travel time in seconds.

This is the time taken for the valve to travel from its fully closed position to its fully open position.

30.0

OP.Lo Low output power limit. -100.0

OP.Hi High output power limit 100.0

Ont.H Output pulse minimum on-time, in seconds. 0.2

OPEROPEROPEROPER Home List

VPOS Calculated position of valve % of motor travel time

Table 8-2 Valve Positioner Set-up Table

The following operating parameters do not effect the 2200e when the valve positioner option has been configured:

CYC.H Heat Cycle Time

CYC.C Cool Cycle Time

ont.C Minimum on time for cooling

!

Page 100: 2208e/2204e Installation and Operating handbook issue 3

Valve Position Installation and Operation Handbook

8-4 2208e and 2204e Controller

Page 101: 2208e/2204e Installation and Operating handbook issue 3

Installation and Operation Handbook Load Current Monitoring and Diagnostics

2208e and 2204e Controller 9-1

9 Chapter 9 LOAD CURRENT MONITORING AND DIAGNOSTICS

9 Chapter 9 LOAD CURRENT MONITORING AND DIAGNOSTICS ....................................................................... 1

9.1 LOAD CURRENT MONITORING AND DIAGNOSTICS ..................2

9.2 EXAMPLE WIRING DIAGRAM (FOR MODE 1 & 2 OPERATION)..3

EXAMPLE WIRING DIAGRAM (FOR MODE 5 OPERATION) ................4

9.4 OPERATION .....................................................................................5 To Read Load Current (modes 2 and 5 only) ................................................... 5 9.4.2 To Display Load Current Continuously in the Lower Readout (modes 2 and 5 only)........................................................................................................ 5 9.4.3 Display Modes..................................................................................... 5 9.4.4 How Heater Alarms Are Displayed...................................................... 6

9.5 TO SET THE ALARM TRIP LEVELS...............................................7

9.6 RELAY OUTPUTS............................................................................7

9.7 TO CONFIGURE PDS LOAD CURRENT DIAGNOSTICS ..............8 9.7.1 To configure the Logic Module for PDS modes 1 or 2 ........................ 8 9.7.2 To configure logic input a for pds (Mode 5 only) ................................. 9

TO CONFIGURE LOW AND HIGH CURRENT TRIP ALARMS ............10

9.9 TO ATTACH SOFT ALARMS TO A RELAY OUTPUT ..................11

9.10 THE SCALING FACTOR ............................................................12 9.10.1 To adjust the scaling factor ........................................................... 12

Page 102: 2208e/2204e Installation and Operating handbook issue 3

Load Current Monitoring and Diagnostics Installation and Operation Handbook

9-2 2208e and 2204e Controller

9.1 LOAD CURRENT MONITORING AND DIAGNOSTICS

Current flowing in a system of electrical heating elements (the ‘Load’) can be displayed on the controller by using a TE10 SSR fitted with intelligent current transformer, PDCTX, or an SSR or contactor with an external PDCTX. Load current monitoring and diagnostics may be used with any time proportioned output, fitted in module position 1A, and uses the logic output wires which drive the SSR to return signals back to the controller These signals represent the RMS value of the load current during the ON period, or load related alarm conditions. It is not designed for analogue outputs i.e. phase angle control. It is also designed for single phase operation only. There are three modes of operation:-

1. Mode 1 This is used with TE10 SSR only. It detects if there is a break in the heater circuit. This includes heater or SSR open circuit. A single Load Failure alarm message is displayed on the lower readout of the controller.

2. Mode 2 This is used with TE10 SSR plus PD/CTX intelligent current transformer, and provides:-

Display of true RMS load current On the lower readout of the controller

Displays the true RMS current in the ON state to the load.

Low current alarm Analogous to Partial Load Failure (PLF) supplied in some SSRs

Provides advanced warning of failure of one or more heaters in parallel

High current alarm Activated when the heater exceeds a set limit

Typically used where element bunching may occur

SSR short circuit This will apply full power to the heaters which could result in an over temperature condition. This alarm provides early warning.

Heater failure Indicates open circuit load conditions

3. Mode 5 This mode is for use with contactors or other devices which do not use the PDS logic output from the controller as the drive signal. For example, a time proportioning logic,relay or triac output. Mode 5, therefore, requires an additional input to the controller to display the load conditions. It uses the digital input terminals for this, as shown in Figure 9-2. Mode 5 provides the same features as mode 2 with two additional alarms:-

Current Transformer Open Circuit An alarm is shown if the PDS connection to PDCTX or SSR become disconnected

Current Transformer Short Circuit An alarm is shown if the PDS connection from PDCTX or SSR are short circuited

Page 103: 2208e/2204e Installation and Operating handbook issue 3

Installation and Operation Handbook Load Current Monitoring and Diagnostics

2208e and 2204e Controller 9-3

1.

9.2 EXAMPLE WIRING DIAGRAM (FOR MODE 1 & 2 OPERATION)

Hardware Required

1. SSR type TE10/PDS2 OR 2. Intelligent current transformer type PD/CTX + contactor or zero voltage switching SSR 2208e or 2204e controller configured for PDS mode 2 option using logic output. This module must be fitted in module position 1. (order code M2).

Figure 9.1 Connections for Mode 1 & 2

Warning

Take care that the controller is correctly wired for the mode of operation which is configured. Failure to do so may be hazardous in some situations.

Heater

Heater power fuse

(load dependent)

L N Controller Fuse 2A(T)

N

L

V+

V-

1B

1A M O D U L E 1

C O M M S 1

+ -

+ PV -

C O M M S 2

Alternative current regulator arrangements:-

The TE10/PDS2 contains integral power

regulator and intelligent PDCTX The PDCTX can be supplied separately for use with any SSR or logic thyristor unit as

shown in the diagram below. The output drive capability of the PDCTX is

5V at 7mA maximum

PDCTX Intelligent Current Transformer

Logic input SSR

+

+ -

-

To Heater

To L To logic output 1A & 1B

TE10 Solid State Relay

T/C

+ -

L N

This represents a single turn through the CT

!

Page 104: 2208e/2204e Installation and Operating handbook issue 3

Load Current Monitoring and Diagnostics Installation and Operation Handbook

9-4 2208e and 2204e Controller

9.3 EXAMPLE WIRING DIAGRAM (FOR MODE 5 OPERATION)

Hardware Required 1. Eurotherm intelligent current transformer type PD/CTX + contactor 2. 2208e or 2204e controller configured for PDS mode 5 option using logic, relay or triac

output. This module must be fitted in module position 1. Digital input LA (order code M5) must be configured to accept PDCTX input as described in the configuration section of this appendix.

The controller will have the order code M5 in the Logic Input position.

Figure 9.2 Example Wiring Connections For Contactor Operation (mode 5)

Warning!

Take care that the controller is correctly wired for the mode of operation which is configured. Failure to do so may be hazardous in some situations.

Contactor + PDCTX mode 5

+ -

Contactor

Heater power fuse (load dependent)

L N

Controller Fuse 2A(T)

N

V+

V-

1B

1A M O D U L E 1

C O M M S 1

+ PV -

C O M M S 2

Heater

T/C

LA

LC

!

Page 105: 2208e/2204e Installation and Operating handbook issue 3

Installation and Operation Handbook Load Current Monitoring and Diagnostics

2208e and 2204e Controller 9-5

9.4 OPERATION

9.4.1 To Read Load Current (modes 2 and 5 only)

Do This This Is The Display You Should See Additional Notes

From the ‘HOME’ display, Figure 1.4,

Press until AmPS is shown in the upper display

It will revert to the HOME display after 45 seconds or 10 seconds if an alarm is present

9.4.2 To Display Load Current Continuously in the Lower Readout (modes 2 and 5 only)

Do This This Is The Display You Should See Additional Notes From the ‘HOME’ display, Figure 1.4,

Press until diSP is shown in the upper display

Press or until AmPS is displayed in the lower display

Current will be displayed in the lower readout continuously when the controller reverts to the HOME display, see also ‘Display Modes’ below.

9.4.3 Display Modes

SSR RMS On State Current This is the default state when high or low current alarms are configured. The load current displayed is the steady state true rms current measured during the ON period. The minimum on times are:- Mode 2 0.1second Mode 5 3 seconds

Meter Mode Meter mode applies to mode 5 only. If low current alarms are not configured the current displayed is a filtered instantaneous RMS value. This behaves like a damped analogue meter. It may be used in applications where the current sensor is not linked to control, for example, telemetry, indication.

AmPSAmPSAmPSAmPS 555 5

AmPSAmPSAmPSAmPS

----------------

diSPdiSPdiSPdiSP AmPSAmPSAmPSAmPS

This display will be shown if: I. The controller is unable to resolve the reading II. The controller is not obtaining a reading III. The measurement has timed out i.e. current has

not flowed for 15 seconds, in mode 2.

Current will be displayed in the lower readout. See also ‘Display Modes’ below.

Page 106: 2208e/2204e Installation and Operating handbook issue 3

Load Current Monitoring and Diagnostics Installation and Operation Handbook

9-6 2208e and 2204e Controller

9.4.4 How Heater Alarms Are Displayed

Do This This Is The Display You Should See Additional Notes

If an alarm is present it will flash a four character mnemonic in the lower display

If more than one alarm is active, the display will alternate between the alarm messages and the default parameter in the lower display

The Alarm Messages are:-

Mnemonic Meaning Description

The following two messages are alarms which are produced as a result of failure within the process. In place of dashes the alarm number will appear i.e 1, 2, 3, or 4

-LCr Alarm number - Low Current

Used for partial load failure detection. To avoid nuisance tripping due to supply voltage variations set to a value at least 15% below the minimum normal operating current

-HCr Alarm number - High Current

Used for load overcurrent protection. To avoid nuisance tripping due to supply voltage variations set to a value at least 15% above the maximum normal operating current.

Note: This alarm is not intended to provide instantaneous safety protection from short circuit fault conditions

The following message is a diagnostic alarm which appears for mode 1 operation only.

LdF Load Fail This includes failure of the heater circuit or the SSR

The following four messages are diagnostic alarms produced as a result of failure within the equipment or wiring connections. They appear for modes 2 and 5 operation only.

Htr.F Heater Fail No current is being drawn while the controller output demand signal is on

SSr.F SSR Fail The load is continuously on while the controller output demand signal is off

Ct.OP Current Transformer Open Circuit

Indicates that the PDS input is open circuit.

Mode 5 only.

Ct.Sh Current Transformer Short Circuit

Indicates that the PDS input is short circuit.

Mode 5 only.

Actual Temperature (PV)

HOME Display

20.0 1LCr

OP1 OP2

Page 107: 2208e/2204e Installation and Operating handbook issue 3

Installation and Operation Handbook Load Current Monitoring and Diagnostics

2208e and 2204e Controller 9-7

9.5 TO SET THE ALARM TRIP LEVELS

Do This This Is The Display You Should See Additional Notes

From the HOME display

press until the AL LiStAL LiStAL LiStAL LiSt is displayed

Press button

until the desired alarm number is displayed

Press or

to adjust the alarm trip level

To select the Alarm List header

To select the diagnostic alarm parameter found under the Alarm List header

The alarm trip level is set to 123

9.6 RELAY OUTPUTS

The fixed relay output connected to terminals AA to AC in a 1/8 or 1/4 DIN controller is normally used for alarm purposes. In addition, any plug in module can be used for alarms provided they are not already being used for another purpose , such as control. Any one or more alarms can be attached to an output, which will operate when an alarm occurs. Contacts are rated at 2A 264Vac for operating external beacons or audible devices.

AL AL AL AL LiStLiStLiStLiSt

1111------------ 123123123123

1 2 3 or 4 indicates the alarm number; --- indicates the alarm type:- e.g. LCr or HCr

Page 108: 2208e/2204e Installation and Operating handbook issue 3

Load Current Monitoring and Diagnostics Installation and Operation Handbook

9-8 2208e and 2204e Controller

9.7 TO CONFIGURE PDS LOAD CURRENT DIAGNOSTICS

Configuration of PDS load current diagnostics is in four parts:-

1. Configure the Logic Module for PDS Mode 1 or 2 operation. If the control device is a contactor or standard SSR, configure the LA digital input for mode 5 operation.

2. Configure the Low and High Current trip alarms. 3. Attach the alarms to operate an output relay. 4. Set up the Scaling Factor. First enter Configuration Level. See Chapter 5

9.7.1 To configure the Logic Module for PDS modes 1 or 2

Do This This Is The Display You Should See Additional Notes

Press until the 1A Conf is displayed

Press to show id

Press to show Func

Press or to show SSr1 or SSr 2 as required.

Press to show SEnS

Press or to show nor

This opens the configuration list associated with module position 1A

This shows the identity of the module

The module identity is logic output

This shows the function of module

The module function is set to PDS mode 1

This sets the output signal to normal for heating control

1A 1A 1A 1A ConfConfConfConf

id id id id LogLogLogLog

FuncFuncFuncFunc SSr1SSr1SSr1SSr1

SEnSSEnSSEnSSEnS nornornornor

Page 109: 2208e/2204e Installation and Operating handbook issue 3

Installation and Operation Handbook Load Current Monitoring and Diagnostics

2208e and 2204e Controller 9-9

9.7.2 To configure logic input a for pds (Mode 5 only)

Do This This Is The Display You Should See Additional Notes

Press button

until the La Conf

is displayed

Press to show id

Press to show Func

Press or to select AmPs

This identifies the LA input as logic and is read only To configure the input for the PDCTX.

The system is designed to operate in either mode 2 or mode 5 configuration only. Selecting both simultaneously will disable the output. However, mode 1 and mode 5 may be used together.

La La La La ConfConfConfConf

id id id id LoG.iLoG.iLoG.iLoG.i

FuncFuncFuncFunc AmPsAmPsAmPsAmPs

!

Page 110: 2208e/2204e Installation and Operating handbook issue 3

Load Current Monitoring and Diagnostics Installation and Operation Handbook

9-10 2208e and 2204e Controller

9.8 TO CONFIGURE LOW AND HIGH CURRENT TRIP ALARMS

Alarm 1 will be configured as Load Current Low (Lcr) Alarm 2 will be configured as Load Current High (Hcr)

Do This This Is The Display You Should See Additional Notes

Press button

until the AL Conf

is displayed

This opens the configuration list which contains the Alarms

Press to show AL1 (alarm 1)

Press or to show LCr

Press until AL2 (alarm 2) appears

Press or to show HCr

To select alarm 1 To make alarm 1 = Low Current To select alarm 2. To make alarm 2 = High Current

Note:- The above alarms are known as SOFT ALARMS because they are indication only.

AL AL AL AL ConfConfConfConf

AL1 AL1 AL1 AL1 LCrLCrLCrLCr

After 0.5 sec the display will blink to show the alarm type has been accepted

AL2 AL2 AL2 AL2 HCrHCrHCrHCr

After 0.5 sec the display will blink to show the alarm type has been accepted

!

Page 111: 2208e/2204e Installation and Operating handbook issue 3

Installation and Operation Handbook Load Current Monitoring and Diagnostics

2208e and 2204e Controller 9-11

9.9 TO ATTACH SOFT ALARMS TO A RELAY OUTPUT

Any one alarm indicated above may be attached to an output (normally a relay). Alternatively any combination of alarms may be attached to operate a relay using the procedure below:-

Do This This Is The Display You Should See Additional Notes

Press “PAGE” key

as many times as necessary to aA ConF

Press until dig.f appears

Press or until the first alarm you wish to attach to the AA output is displayed e.g. Htrf Repeat the above step for every alarm to be attached to the output

Any output module can be configured for an alarm output provided it is not used for any other purpose, eg as a control output. In place of AA you should select the module required, i.e. 1A, 2A, 3A (or 4A 2204 only) DiGF = digital functions noch = no change After 0.5 second the display will revert to noch to attach the alarm Each time you scroll through the table of alarms note that two decimal points appear. This confirms that the particular alarm has been attached to the output, i.e. Ht.r.F SS.r.F etc

To remove alarms from an output press or until CLr appears in the lower display. This will clear all alarms attached to this output.

Dig.fDig.fDig.fDig.f no.chno.chno.chno.ch

aA aAaAaA ConfConfConfConf

Dig.fDig.fDig.fDig.f HtrfHtrfHtrfHtrf

Dig.fDig.fDig.fDig.f no.CHno.CHno.CHno.CH

0.5 sec

Alarms Connected to a Relay Output

dIG SEnS

nor

inv Output Module

Soft Alarms OR

AA

AB

Page 112: 2208e/2204e Installation and Operating handbook issue 3

Load Current Monitoring and Diagnostics Installation and Operation Handbook

9-12 2208e and 2204e Controller

9.10 THE SCALING FACTOR

The value of the current displayed on the controller is scaled using the scaling factor. This is found in the inSt ConF list. It is set, by default, to 100 and assumes a single turn through the current transformer. If two turns are made through the current transformer it will be necessary to adjust the scaling factor to 50 to obtain the same reading. Under normal conditions you should not need to change the scaling factor. If, however, you wish to change the sensitivity of the current reading, for example, to read very low currents you may need to change the number of turns through the PDCTX and/or adjust the scaling factor to compensate. See also note 1 below.

9.10.1 To adjust the scaling factor

Do This This Is The Display You Should See Additional Notes

Press button

until inSt Conf is

displayed

Press until LC.Hi is displayed

Press or to change the scaling factor

Minimum Resolvable Current TE10 4A RMS. It is not possible to read currents lower than 4A when using a TE10. PDCTX 4A RMS for a single turn through the PDCTX Should you wish to read currents lower than 4A using a PDCTX it is necessary to increase the number of turns through the PDCTX and adjust the scaling factor to compensate. For example: To read 1.0A wind 4 turns through the PDCTX and adjust the scaling factor to 25 as shown in the table below.

Scalar = 100/N Where N = Turns through PDCTX N Scalar 1 100 2 50 4 25 5 20 10 10

Maximum Resolvable Current TE10 Determined by the maximum range of the SSR PDCTX 100A (or 100 ampere turns)

Finally Exit configuration level. See Chapter 5.

inStinStinStinSt ConfConfConfConf

LC.HiLC.HiLC.HiLC.Hi 100100100100

Page 113: 2208e/2204e Installation and Operating handbook issue 3

Installation and Operation Handbook Retransmission

2208e and 2204e Controller 10-1

10 Chapter 10 RETRANSMISSION

10 Chapter 10 RETRANSMISSION.................................... 1

10.1 What is retransmission...............................................................2

10.2 To configure retransmission......................................................3

10.3 scaling retransmitted output signals ........................................4

10.1.1 To Range Retransmitted Output OP .............................................. 4

10.1.2 To Range Retransmitted Setpoint SP or Process Variable PV..... 5

10.1.3 To Range Retransmitted Error Err ............................................... 5

Page 114: 2208e/2204e Installation and Operating handbook issue 3

Retransmission Installation and Operation Handbook

10-2 2208e and 2204e Controller

10.1 WHAT IS RETRANSMISSION

The controller can be configured to generate an analogue output signal which represents a selected parameter. The parameters which can be configured for retransmission are:- 1. Process Variable 2. Setpoint 3. Error 4. Control Output The retransmission signal is available as 0-20mA, 4-20mA, 0-5V, 1-5V or 0-10V and is connected to terminals 1A and 1B when module 1A is fitted as a DC module.

Page 115: 2208e/2204e Installation and Operating handbook issue 3

Installation and Operation Handbook Retransmission

2208e and 2204e Controller 10-3

10.2 TO CONFIGURE RETRANSMISSION

A DC module must be fitted in module position 1A. First enter configuration level. See Chapter 5. Then:-

Do This This Is The Display You Should See Additional Notes

Press button

until the 1A Conf

is displayed

This opens the configuration list for module 1A.

Press to show id

Press to show Func

Press or to select the parameter for retransmission

Press to show SEns

This is the identity of the module fitted in this position The module must be a DC output dC.OP If Func is a retransmission parameter the value of Sens has no effect.

1A 1A 1A 1A ConfConfConfConf

id id id id dC.OPdC.OPdC.OPdC.OP

FuncFuncFuncFunc PV PV PV PV

SEnSSEnSSEnSSEnS nor nor nor nor

The choices are:-

nonE Output turned off

Control Outputs

HEAT Heat control output

COOL Cool control output

Retransmission

OP Output demand

PV Process Variable

Err Error

wSP Setpoint (working)

Page 116: 2208e/2204e Installation and Operating handbook issue 3

Retransmission Installation and Operation Handbook

10-4 2208e and 2204e Controller

Press to show Out.L

Press to show

Out.H

The retransmitted output signal can be limited by adjusting these parameters.

To reverse the output, set Out.L to 20.0 and Out.H to 0.0.

10.3 SCALING RETRANSMITTED OUTPUT SIGNALS

The analogue output signal may be set between 0 and 20mA. A 4-20mA output is achieved by applying an offset as described below. A 0 to 10Vdc output may be achieved by fitting a 500 ohm resistor across the output terminals 1A and 1B. A 0 to 5Vdc output may be achieved by fitting a 250 ohm resistor across the output terminals 1A and 1B. Suitable resistors are supplied with the controller.

10.1.1 To Range Retransmitted Output OPOPOPOP

Out.LOut.LOut.LOut.L 0.0 0.0 0.0 0.0

Out.HOut.HOut.HOut.H 20.0 20.0 20.0 20.0

OUT.HOUT.L

% Output

For output of 0-100% = 0-20mA

set Out.H to 20.0 and Out.L to 0.0 For output of 0-100% = 4-20mA

set Out.H to 20.0 and Out.L to 4.0

Page 117: 2208e/2204e Installation and Operating handbook issue 3

Installation and Operation Handbook Retransmission

2208e and 2204e Controller 10-5

10.1.2 To Range Retransmitted Setpoint SP SP SP SP or Process Variable PVPVPVPV

10.1.3 To Range Retransmitted Error Err Err Err Err

For output of 0 - 1000oC = 0-20mA

set Out.L to 0.0 and Out.H to 20.0

and rnG.L to 0.0 and rnG.H to 1000

rnG.L is the low limit of the input range

rnG.H is the high limit of the input range

These are found in the iP ConF list as described in Chapter 5. If the range limits are not set the retransmitted output is the maximum input range as stated in the order code, Appendix A.

OUT.HOUT.L

rng.L

rng.H

The retransmitted output value is dependent upon the range limits rnG.H and rnG.L set in the iP ConF list of the controller. The following examples are given to illustrate the retransmitted error values:

Example 1: Type K thermocouple, rnG.L = -200 rnG.H = +200 Retransmitted Value 0mA for an error of -200 10mA for an error of 0 20mA for an error of +200 Example 2:

As above but rnG.L = -10 and rnG.H = 400 Retransmitted Value 0mA for an error of -10 0.0487mA for an error of 0 20mA for an error of +400 Note:

To read a negative error it is necessary to set rnG.L to a negative limit

OUT.HOUT.L

rng.L

rng.H

0

Page 118: 2208e/2204e Installation and Operating handbook issue 3

Retransmission Installation and Operation Handbook

10-6 2208e and 2204e Controller

Page 119: 2208e/2204e Installation and Operating handbook issue 3

Installation and Operation Handbook Understanding the Ordering Code

2208e and 2204e Controller A-1

A Appendix A UNDERSTANDING THE ORDERING CODE

The 2208e and 2204e controllers have a modular hardware construction with the option of four outputs and one communications port. Two logic inputs are provided as standard. In addition the Model 2204e has an optional plug-in 10A heating output. The ordering code is in two parts: the hardware code followed by the software code. The hardware code specifies the hardware build of the controller, and the software code the software configuration. The software code is optional.

UK Default USA Default

Type K thermocouple 0 to 1000°C Type J thermocouple 32 to 2192°F

Hardware code

Software code

Model I/O 1 Comms Display Number Language units

Supply I/O 2 Manual Voltage Sensor

Output 3 input Range

min Range

Max Options

Function

Figure A.1

Page 120: 2208e/2204e Installation and Operating handbook issue 3

Understanding the Ordering Code Installation and Operation Handbook

A-2 2208e and 2204e Controller

Hardware code

Model

number Function Supply

voltage I/O 1

I/O 2 Output 3

Output 4

10A output

Comms Manual Default Settings

2208e 2204e

CC

VH

LH

RC

FL

FH

XX

2YM

ENG

AO-American EO-European

Supply voltage VH 85-264Vac

Function CC Controller VC Valve

Positioner NF On/Off AL Alarm unit

10A output 2204e only XX None R5 fitted unconfiig. RH PID heating

Manual XXX No manual ENG English FRA French GER German ITA Italian

I/O 1 XX None Relay: 2-pin R1 Unconfigured RU VP raise O/P RH PID heating FH High alarm 1 FL Low alarm 1 DB Deviation band 1 DL Low dev. alarm 1 DH High dev alarm 1 Logic: non-isolated L1 Unconfigured LH PID heating M1 PDS mode 1 note 1 M2 PDS mode 2 note 2 Triac T1 Unconfigured TH PID heating TU VP raise O/P DC control -isolated D3 Unconfigured H6 0-20mA PID heating H7 4-20mA PID heating C6 0-20mA PID cooling C7 4-20mA PID cooling DC Retrans. (isolated) Select from table A

Table A D6 Fitted unconfigured V- PV retrans P- Setpoint retrans O- Output retrans Z- Error retrans -1 0-20mA -2 4-20mA -3 0-5V -4 1-5V -5 0-10V

I/O 2 XX None Relay: 2-pin R1 Unconfigured RC PID cooling RW VP lower O/P FH High alarm 2 FL Low alarm 2 DB Deviation band 2 DL Low deviation alarm 2 DH High deviation alarm 2 AL Hi & Lo alarms 1 & 2 Logic Input AM Auto manual select S2 Setpoint 2 select AC Alarm ack/reset EH Integral hold SB Standby mode SR PDS remote SP select M5 CTX mode 5 current input Logic output L1 Unconfigured LC PID cooling LH Heating output Triac T1 Unconfigured TC PID cooling TW VP lower O/P TH Heating output

Outputs 3 and 4 XX None RF Unconfigured RH PID heating RC PID cooling FH High alarm 3 FL Low alarm 3 DB Deviation band 3 DL Low deviation. alarm 3 DH High deviation alarm 3 AL High and Low alarms PDS Alarms LF Heater break HF Current monitoring

heater break SF Current monitoring

SSR failure

Comms 2XX None Modbus protocol 2YM 2-wire RS485 2FM 4-wire RS422 2AM RS232 EI-Bisynch 2YE 2-wire RS485 2FE 4-wire RS422 2AE RS232 DeviceNet 2DN DeviceNet PDS Input 2RS Setpoint

Page 121: 2208e/2204e Installation and Operating handbook issue 3

Installation and Operation Handbook Understanding the Ordering Code

2208e and 2204e Controller A-3

Software code

Sensor input Range min Range max Units Digital

input 1 Digital input 2

Options

K

0

(note 2)

1000

(note 2)

C

XX

XX

CF

Sensor input Range Min Range Min Standard sensors Min °C max Min °F max J J thermocouple -210 1200 -340 2192 K K thermocouple -200 1372 -325 2500 T T thermocouple -200 400 -325 750 L L thermocouple -200 900 -325 1650 N N thermocouple -200 1300 -325 2370 R R thermocouple -50 1768 -58 3200 S S thermocouple -50 1768 -58 3200 B B thermocouple 0 1820 32 3310 P Platinel II therm’ple 0 1369 32 2496 Z RTD/PT100 -200 850 -325 1562 Custom sensors (*replaces C thermocouple) C *C thermocouple

W5%Re/W26%Re (Hoskins)

0 2319 32 4200

D W3%Re/W25%Re 0 2399 32 4350 E E thermocouple -200 1000 -325 1830 1 Ni/Ni18%Mo 0 1399 32 2550 2 Pt20%Rh/Pt40%Rh 0 1870 32 3398 3 W/W26%Re

(Englehard) 0 2000 32 3632

4 W/W26%Re (Hoskins)

0 2010 32 3650

5 W5%Re/W26%Re (Englehard)

10 2300 50 4172

6 W5%Re/W26%Re (Bucose)

0 2000 32 3632

7 Pt10%Rh/Pt40%Rh -200 1800 392 3272 8 Exergen K80 IR

pyrometer -45 650

Process inputs Min Max M -9.99 to +80.00mV -999 9999 Y 0 to 20mA -999 9999 A 4 to 20ma -999 9999 W 0 to 5Vdc -999 9999 G 1 to 5Vdc -999 9999 V 0 to 10Vdc -999 9999

Options Control action XX Reverse acting

(standard) DP Direct acting PID Power feedback XX Enabled on logic,

relay & triac heating outputs

PD Power feedback disabled

Cooling options XX Linear cooling CF Fan cooling CW Water cooling CL Oil cooling

Digital inputs 1 & 2 XX No function AM Manual select SR Remote setpoint select S2 Second setpoint EH Integral hold AC Alarm acknowledge SB Standby mode M5 CTX mode 5 current

input (input 1 only)

Units C Centigrade F Fahrenheit K Kelvin X Linear input

Page 122: 2208e/2204e Installation and Operating handbook issue 3

Understanding the Ordering Code Installation and Operation Handbook

A-4 2208e and 2204e Controller

Notes:

1. PDS heater break detect will transmit the power demand to a TE10 solid state relay and read back a heater break alarm.

2. PDS current monitoring will transmit the power demand to a TE10 solid state relay and read back load current and open and short circuit alarms.

3. Setpoint limits: Include the decimal position required in the displayed value – up to one for temperature inputs, up to two for process inputs

4. An external 1% current sense resistor is supplied as standard. If greater accuracy is required, a 0.1% 2.49Ω can be ordered as part number SUB2K/249R.1.

Page 123: 2208e/2204e Installation and Operating handbook issue 3

Installation and Operation Handbook Safety Information

2208e and 2204e Controller B-1

B Appendix B SAFETY and EMC INFORMATION This controller is intended for industrial temperature and process control applications when it will meet the requirements of the European Directives on Safety and EMC. Use in other applications, or failure to observe the installation instructions of this handbook may impair safety or EMC. The installer must ensure the safety and EMC of any particular installation.

Safety

This controller complies with the European Low Voltage Directive 73/23/EEC, amended by 93/68/EEC, by the application of the safety standard EN 61010.

Electromagnetic compatibility

This controller conforms with the essential protection requirements of the EMC Directive 89/336/EEC, amended by 93/68/EEC, by the application of a Technical Construction File. This instrument satisfies the general requirements of the industrial environment defined in EN 50081-2 and EN 50082-2. For more information on product compliance refer to the Technical Construction File. GENERAL The information contained in this manual is subject to change without notice. While every effort has been made to ensure the accuracy of the information, your supplier shall not be held liable for errors contained herein.

Unpacking and storage

The packaging should contain an instrument mounted in its sleeve, two mounting brackets for panel installation and this operating book. Certain ranges are supplied with an input adapter. If on receipt, the packaging or the instrument are damaged, do not install the product but contact your supplier. If the instrument is to be stored before use, protect from humidity and dust in an ambient temperature range of -30oC to +75oC. SERVICE AND REPAIR This controller has no user serviceable parts. Contact your supplier for repair.

Caution: Charged capacitors

Before removing an instrument from its sleeve, disconnect the supply and wait at least two minutes to allow capacitors to discharge. It may be convenient to partially withdraw the instrument from the sleeve, then pause before completing the removal. In any case, avoid touching the exposed electronics of an instrument when withdrawing it from the sleeve. Failure to observe these precautions may cause damage to components of the instrument or some discomfort to the user.

Page 124: 2208e/2204e Installation and Operating handbook issue 3

Safety Information Installation and Operation Handbook

B-2 2208e and 2204e Controller

Electrostatic discharge precautions

When the controller is removed from its sleeve, some of the exposed electronic components are vulnerable to damage by electrostatic discharge from someone handling the controller. To avoid this, before handling the unplugged controller discharge yourself to ground.

Cleaning

Do not use water or water based products to clean labels or they will become illegible. Isopropyl alcohol may be used to clean labels. A mild soap solution may be used to clean other exterior surfaces of the product. INSTALLATION SAFETY REQUIREMENTS

Safety Symbols

Various symbols are used on the instrument, they have the following meaning:

Caution, (refer to theaccompanying documents)

Functional earth(ground) terminal!

The functional earth connection is not required for safety purposes but is used to ground RFI filters.

Personnel

Installation must only be carried out by qualified personnel.

Enclosure of live parts

To prevent hands or metal tools touching parts that may be electrically live, the controller must be installed in an enclosure.

Caution: Live sensors

The logic and PDS outputs are electrically connected to the main PV input, (thermocouple etc.). If the temperature sensor is connected directly to an electrical heating element then these non-isolated inputs and outputs will also be live. The controller is designed to operate under these conditions. However you must ensure that this will not damage other equipment connected to these inputs and outputs and that service personnel do not touch connections to these I/O while they are live. With a live sensor, all cables, connectors and switches for connecting the sensor and non-isolated inputs and outputs must be mains rated.

Page 125: 2208e/2204e Installation and Operating handbook issue 3

Installation and Operation Handbook Safety Information

2208e and 2204e Controller B-3

Wiring

It is important to connect the controller in accordance with the wiring data given in this handbook. Take particular care not to connect AC supplies to the low voltage sensor input or other low level inputs and outputs. Only use copper conductors for connections, (except thermocouple). Ensure that the wiring of installations comply with all local wiring regulations. For example in the UK, use the latest version of the IEE wiring regulations, (BS7671). In the USA, use NEC Class 1 wiring methods.

Power Isolation

The installation must include a power isolating switch or circuit breaker that disconnects all current carrying conductors. The device should be mounted in close proximity to the controller, within easy reach of the operator and marked as the disconnecting device for the instrument.

Earth leakage current

Due to RFI Filtering there is an earth leakage current of less than 0.5mA. This may affect the design of an installation of multiple controllers protected by Residual Current Device, (RCD) or Ground Fault Detector, (GFD) type circuit breakers.

Overcurrent protection

To protect the internal PCB tracking within the controller against excess currents, the AC power supply to the controller and power outputs must be wired through the fuse or circuit breaker specified in the technical specification.

Voltage rating

The maximum continuous voltage applied between any connection to ground must not exceed 264Vac.

The controller should not be wired to a three phase supply with an unearthed star connection. Under fault conditions such a supply could rise above 264Vac with respect to ground and the product would not be safe.

Voltage transients across the power supply connections, and between the power supply and ground, must not exceed 2.5kV. Where occasional voltage transients over 2.5kV are expected or measured, the power installation to both the instrument supply and load circuits should include a transient limiting device.

These units will typically include gas discharge tubes and metal oxide varistors that limit and control voltage transients on the supply line due to lightning strikes or inductive load switching. Devices are available in a range of energy ratings and should be selected to suit conditions at the installation.

Page 126: 2208e/2204e Installation and Operating handbook issue 3

Safety Information Installation and Operation Handbook

B-4 2208e and 2204e Controller

Conductive pollution

Electrically conductive pollution must be excluded from the cabinet in which the controller is mounted. For example, carbon dust is a form of electrically conductive pollution. To secure a suitable atmosphere, install an air filter to the air intake of the cabinet. Where condensation is likely, for example at low temperatures, include a thermostatically controlled heater in the cabinet.

Grounding of the temperature sensor shield

In some installations it is common practice to replace the temperature sensor while the controller is still powered up. Under these conditions, as additional protection against electric shock, we recommend that the shield of the temperature sensor is grounded. Do not rely on grounding through the framework of the machine.

Over-temperature protection

When designing any control system it is essential to consider what will happen if any part of the system should fail. In temperature control applications the primary danger is that the heating will remain constantly on. Apart from spoiling the product, this could damage any process machinery being controlled, or even cause a fire.

Reasons why the heating might remain constantly on include:

• the temperature sensor becoming detached from the process

• thermocouple wiring becoming short circuit;

• the controller failing with its heating output constantly on

• an external valve or contactor sticking in the heating condition

• the controller setpoint set too high.

Where damage or injury is possible, we recommend fitting a separate over-temperature protection unit, with an independent temperature sensor, which will isolate the heating circuit.

Please note that the alarm relays within the controller will not give protection under all failure conditions.

Page 127: 2208e/2204e Installation and Operating handbook issue 3

Installation and Operation Handbook Safety Information

2208e and 2204e Controller B-5

INSTALLATION REQUIREMENTS FOR EMC To ensure compliance with the European EMC directive certain installation precautions are necessary as follows:

• For general guidance refer to EMC Installation Guide, HA025464.

• When using relay or triac outputs it may be necessary to fit a filter suitable for suppressing the conducted emissions. The filter requirements will depend on the type of load. For typical applications we recommend Schaffner FN321 or FN612.

• If the unit is used in table top equipment which is plugged into a standard power socket, then it is likely that compliance to the commercial and light industrial emissions standard is required. In this case to meet the conducted emissions requirement, a suitable mains filter should be installed. We recommend Schaffner types FN321 and FN612.

Routing of wires

To minimise the pick-up of electrical noise, the low voltage DC connections and the sensor input wiring should be routed away from high-current power cables. Where it is impractical to do this, use shielded cables with the shield grounded at both ends. In general keep cable lengths to a minimum.

Page 128: 2208e/2204e Installation and Operating handbook issue 3

Safety Information Installation and Operation Handbook

B-6 2208e and 2204e Controller

TECHNICAL SPECIFICATION

Inputs General Range +100mV and 0 to 10Vdc (auto ranging) Sample rate 9Hz (110mS) Calibration accuracy 0.25% of reading, ±1 LSD or ±1°C/F Resolution <1µV for ± 100mV range, <0.2mV for 10Vdc

range Linearisation accuracy <0.1% of reading Input filter 1.0 to 999.9secs Zero offset User adjustable over the fully display range Thermocouple Types Refer to Sensor inputs and display ranges table Cold junction compensation Automatic compensation typically >30 to 1

rejection of ambient temperature change (incorporates INSTANT ACCURACY™ cold junction sensing technology).

External references 32, 113 and 122°F (0, 45 and 50°C)

RTD/PT100 Type 3-wire, Pt100 DIN43760 Bulb current 0.2mA Lead compensation No error for 22 ohms in all 3 leads Process Linear -9.99 to 80.00mV, 0 to 20mA or 0 to 10Vdc

(All configurable between limits) Digital Type Contact closure Application Manual select, 2nd setpoint, keylock, setpoint

rate limit enable

Outputs Relay Rating: 2-pin relay Min: 12V, 100mA dc Max: 2A, 264Vac

resistive Rating: change-over, alarm relay Min: 6V, 1mA dc Max: 2A, 264Vac resistive Application Heating, cooling or alarms Logic Rating 18Vdc at 20mA (non-isolated) Application Heating, cooling or alarms PDS mode 1: SSRx Load Doctor™ logic

heating with load failure alarm PDS mode 2: SSRx Enhanced Load Doctor™

logic heating with load/SSC failure alarm and load current display

Triac Rating 1A, 30 to 264Vac resistive Application Heating or cooling High current Rating 10A, 264Vac resistive Application Heating Analog Range Isolated 0 to 20mA or 0 to 10Vdc (configurable

between limits) Application Heating or cooling

Page 129: 2208e/2204e Installation and Operating handbook issue 3

Installation and Operation Handbook Safety Information

2208e and 2204e Controller B-7

Communications Digital Transmission standard EIA-485 2wire, EIA-422 4 wire or EIA-232 at

1200, 2400, 4800, 9600, 19,200 baud 125K, 250K, 500K for DeviceNet Protocols Modbus®, EI-Bisynch, DeviceNet PDS Setpoint input Setpoint input from master PDS controller

Control functions Control Modes PID or PI with overshoot inhibition, PD, P only

or On/Off Application Heating and cooling Auto/manual Bumpless transfer Setpoint rate limit 0.01 to 99.99 degrees or display units per

minute. Cooling algorithms Linear; Water (non-linear); Fan (minimum on

time), Oil, proportional only Tuning One-shot tune Automatic calculation of PID and overshoot

inhibition parameters Automatic droop compensation Automatic calculation of manual reset value

when using PD control Alarms Types Full scale high or low. Deviation high, low, or

band Modes Latching or non-latching. Normal or blocking

action Up to four process alarms can be combined

onto a single output

Page 130: 2208e/2204e Installation and Operating handbook issue 3

Safety Information Installation and Operation Handbook

B-8 2208e and 2204e Controller

General Display Dual, 4 digit x 7 segment high intensity LED Dimensions and weight 2404e:- 96W x 96H x 103Dmm (3.78W x

3.78H x 4.06D inches) 600g (21oz) 2408e:- 48W x 96H x 103Dmm (1.89W x

3.78H x 4.06D inches) 320g (11oz) Supply 85 to 264Vac -15%, +10%. 48 to 62Hz.

10watts max Temperature and RH Operating: 32 to 131°F (0 to 55°C), RH: 5 to

90% non-condensing. Storage: 14 to 158°F (-10 to 70°C)

Panel sealing IP 65 Electromagnetic compatibility Meets generic emissions standard EN50081-2

for industrial environments. Meets general immunity requirements of EN50082-2(95) for industrial environments

Safety standards EN61010, installation category 2 (voltage transients must not exceed 2.5kV)

Atmospheres Electrically conductive pollution must be excluded from the cabinet in which this controller is mounted. This product is not suitable for use above 6,562ft (2000m) or in corrosive or explosive atmospheres without further protection.

Page 131: 2208e/2204e Installation and Operating handbook issue 3
Page 132: 2208e/2204e Installation and Operating handbook issue 3

INTERNATIONAL SALES AND SERVICE

HA026696

© Copyright Eurotherm Limited 2003

All rights are strictly reserved. No part of this document may be reproduced, modified, or transmitted in any form by any means, nor may it be stored in a retrieval system other than for thepurpose to act as an aid in operating the equipment to which the document relates, without theprior written permission of Eurotherm limited.

Eurotherm Limited pursues a policy of continuous development and product improvement. Thespecifications in this document may therefore be changed without notice. The information in thisdocument is given in good faith, but is intended for guidance only. Eurotherm Limited will acceptno responsibility for any losses arising from errors in this document.

http://www.eurotherm.co.uk

ENG

AUSTRALIA SydneyEurotherm Pty. Ltd.Telephone (+61 2) 9838 0099Fax (+61 2) 98389288

AUSTRIA ViennaEurotherm GmbHTelephone (+43 1) 7987601Fax (+43 1) 7987605

BELGIUM Moha &LUXEMBURG HuyEurotherm S.A./N.V.Telephone (+32 ) 85 274080Fax (+32 ) 85 274081

BRAZIL Campinas-SPEurotherm Ltda.Telephone (+55 19) 3237 3413Fax (+55 19) 3234 7050

DENMARK CopenhagenEurotherm Danmark A/STelephone (+45 70) 234670Fax (+45 70) 234660

FINLAND ABOEurotherm FinlandTelephone (+358) 22506030Fax (+358) 22503201

FRANCE LyonEurotherm Automation SATelephone (+33 478) 664500Fax (+33 478) 352490

GERMANY LimburgEurotherm Deutschland GmbHTelephone (+49 6431) 2980Fax (+49 6431) 298119Also regional offices

HONG KONG AberdeenEurotherm LimitedTelephone (+852) 28733826Fax (+852) 28700148

INDIA ChennaiEurotherm India LimitedTelephone (+9144) 4961129Fax (+9144) 4961831

IRELAND DublinEurotherm Ireland LimitedTelephone (+353 01) 4691800Fax (+353 01) 4691300

ITALY ComoEurotherm S.r.lTelephone (+39 031) 975111Fax (+39 031) 977512

KOREA SeoulEurotherm Korea LimitedTelephone (+82 31) 2868507Fax (+82 31) 2878508

NETHERLANDS Alphen a/d RynEurotherm B.V.Telephone (+31 172) 411752Fax (+31 172) 417260

NORWAY OsloEurotherm A/STelephone (+47 67) 592170Fax (+47 67) 118301

SPAIN MadridEurotherm España SATelephone (+34 91) 6616001Fax (+34 91) 6619093

SWEDEN MalmoEurotherm ABTelephone (+46 40) 384500Fax (+46 40) 384545

SWITZERLAND FreienbachEurotherm Produkte (Schweiz) AGTelephone (+41 55) 4154400Fax (+41 55) 4154415

UNITED KINGDOM WorthingEurotherm LimitedCONTROLS & DATA MANAGEMENTTelephone (+44 1903) 695888Fax (+44 1903) 695666PROCESS AUTOMATIONTelephone (+44 1903) 205277Fax (+44 1903) 236465

U.S.A LeesburgEurotherm Inc.Telephone (+1 703) 443 0000Fax (+1 703) 669 1300Web www.eurotherm.com

ED 36