220 kV AIS Switchyard

download 220 kV AIS Switchyard

of 26

Transcript of 220 kV AIS Switchyard

  • 7/29/2019 220 kV AIS Switchyard

    1/26

    Project By

    Mohammed Mahmooduddin

    Syed Abbas Noori

    Syed Obaidur Rahman

    Under guidance of

    Mrs. Ajaz Fatima(internal)

    Mr. M.A. Ahmed(external)

  • 7/29/2019 220 kV AIS Switchyard

    2/26

    PROJECT

    To design the switchyard is to evacuate the power from 375 MWCombined Cycle Power Plant.

    Purpose:

    The substations are very much essential to Evacuate power from generating stations.

    Transmit to the load centers.

    Distribute to the utilities & ultimate consumers

  • 7/29/2019 220 kV AIS Switchyard

    3/26

    WHY SUBSTATIONS ? The Electrical power generation from Hydel, Thermal,

    Nuclear and other generating stations has to beevacuated to load centers.

    The generation voltage is limited to 15/18 KV due to thelimitation of the rotating machinery.

    This bulk power has to be stepped up to higher voltages

    depending on quantum of power generated anddistance to the load centers.

    Again the power has to be stepped down to differentlower voltages for transmission and distribution

  • 7/29/2019 220 kV AIS Switchyard

    4/26

    TYPES OF SUBSTATIONS

    The substations are classified as

    a)Generating substations (Switchyard)

    b) Grid substations

    c) Switching stations

    d) Secondary substations.

  • 7/29/2019 220 kV AIS Switchyard

    5/26

    Generating substations (Switchyard)

    The generating substations are step up stations as thegeneration voltage needs to be stepped up to theprimary transmission voltage so that huge blocks ofpower can be transmitted over long distances to loadcenters

  • 7/29/2019 220 kV AIS Switchyard

    6/26

    grid substations The grid substations are created at suitable load

    centers along the primary transmission lines

  • 7/29/2019 220 kV AIS Switchyard

    7/26

    Switching stationsSwitching stations are provided in between lengthy primarytransmission lines

    To avoid switching surges.

    For easy segregation of faulty zones. For providing effective protection to the system in the A.C.network.

    The switching stations also required wherever the EHT lineare to be tapped and line to be extended to different load

    centers without any step down facility at the switchingstations. The number of outgoing lines will be more than the

    incoming lines, depending on the load points

  • 7/29/2019 220 kV AIS Switchyard

    8/26

    Secondary substations Secondary substations are located at actual load points

    along the secondary transmission lines where thevoltage is further stepped down to sub transmission &primary distribution voltage.

    Distribution substations are created where the sub-transmission voltage and primary distribution voltage

    are stepped down to supplyvoltage and feed the actual consumers through a

    network of distribution and service lines.

  • 7/29/2019 220 kV AIS Switchyard

    9/26

    TRANSMISSION SUBSTATION

    DISTRIBUTION SUBSTATION

    COLLECTOR SUBSTATION

    CONVERSION SUBSATION

    SWITCHING SUBSTATION

    ADJUST THE ABOVE HERE

  • 7/29/2019 220 kV AIS Switchyard

    10/26

  • 7/29/2019 220 kV AIS Switchyard

    11/26

    SELECTIONOFSITE

    Selection of site for construction of a Grid

    Sub Station is the first and important activity.

    This needs meticulous planning, fore-sight,skillful observation and handling so that the

    selected site is technically, environmentally,

    economically and socially optimal and is thebest suited to the requirements.

  • 7/29/2019 220 kV AIS Switchyard

    12/26

    SOCIALANDCOMMUNITY ENVIRONMENTAL

    What are the predicted futureenergy requirements of the

    community?

    What is the land zoning of the

    site and its proximity to

    residents? What is the likely visual impact,

    considering the direct line of

    sight, substation height and

    visual screening options?

    Can the substation be locatedas to not disturb surrounding

    residents and if not, can a

    design solution be determined?

    Are there any potential impactson declared rare flora or fauna,

    priority flora or threatened

    ecological communities?

    Is the site likely to impact anunderground water protection

    area or wetland system?

    Is a design option likely to

    impact on any knownIndigenous or European

    heritage sites?

  • 7/29/2019 220 kV AIS Switchyard

    13/26

    TECHNICALREQUIREMENTS

    Is the location close to the load area that it will service?

    Is the substation located as close as possible to existingtransmission lines, from which it will draw its power?

    Does the site allow for connection of in-coming transmission lines

    and out-going underground distribution lines?

    Is the site far enough away from underground copper cables (eg.telecommunications cables) and the steel pipelines used by gas and

    water companies, so that earthing and voltage induction issues can

    be avoided. Where this cannot be avoided, costs to mitigate are

    extreme.

    Could a standard design be accommodated on the site, or are therespecial design considerations?

    Physical constraints such as slope, geology, water table and

    flooding.

    Engineering features such as vehicle access, earthworks and

    services.

  • 7/29/2019 220 kV AIS Switchyard

    14/26

    ECONOMICREQUIREMENTS

    As a regulated body, can we satisfy the

    Economic Regulation Authority that the most

    cost effective solution has been identified? What alternative solutions are available?

    Can cost effective improvements to the design

    reduce the visual impacts on the community?

  • 7/29/2019 220 kV AIS Switchyard

    15/26

    REQUIREMENT OF LAND/AREA

    The site should have sufficient area to properly accommodate the Sub

    Station buildings ,structures ,equipments, etc. and should have the

    sufficient area for future extension of the buildings and / or switchyard.

    The requirement of land for construction of Sub SUBSTATION1. 400 kV 20.0 Hectare

    2. 220 kV 6.0 Hectare

    3. 132 kV 3.5 Hectare

    While preparing proposals for acquisition of private land and allotment

    of Government.

  • 7/29/2019 220 kV AIS Switchyard

    16/26

    SYSTEMBUSES

    The main criterias to be considered during selection of

    one particular Bus Bar Arrangement Scheme among

    others

    i. Simplicity of system

    (ii) Easy maintenance of different equipments.

    (iii) Minimizing the outage during maintenance.(iv) Future provision of extension with growth of demand

    (v) Optimizing the selection of bus bar arrangement

    scheme so that it gives maximum return from the system.

  • 7/29/2019 220 kV AIS Switchyard

    17/26

    Types of system

  • 7/29/2019 220 kV AIS Switchyard

    18/26

  • 7/29/2019 220 kV AIS Switchyard

    19/26

    DOUBLE BUS SYSTEMWITH BYPASS

    ISOLATORS This is combination of the double bus

    system and main and transfer bussystem.

    In Double Bus System with Bypass

    Isolators either bus can act as main bus

    and second bus as transfer bus.

    It permits breaker maintenance withoutinterruption of power which is not

    possible in double bus system but it

    provides all the advantages of double

    bus system.

    It however requires one additionalisolator (bypass isolator) for each feeder

    circuit and introduces slight complication

    in system layout. Still this scheme is best

    for optimum economy of system and it is

    best optimum choice for 220KV system.

  • 7/29/2019 220 kV AIS Switchyard

    20/26

    EQUIPMENTSCOMMONLYFOUNDIN

    SWITCHYARD Lightening arrestor

    Current transformer

    Voltage transformer Power transformers / I.C.T.

    Bus bar and clamp fittings

    Support structure Isolators

    Circuit Breaker

    Wave traps

  • 7/29/2019 220 kV AIS Switchyard

    21/26

    EQUIPMENTSINASUB-STATION

    Transformers :

    - Transforms the voltage levels from higher to lower level

    or vice versa, keeping the power constant.

    Instrument transformers :

    - For stepping-down the electrical parameter (Voltage or Current) to

    a lower and safe value for Metering and Protection logics.

  • 7/29/2019 220 kV AIS Switchyard

    22/26

    Earth switch :

    - Used to connect the charged body to ground to discharge thetrapped charge to have a safe maintenance zone

    Lightning arrestors :- Safe guards the equipment by discharging the high currents

    due to Lightning.

  • 7/29/2019 220 kV AIS Switchyard

    23/26

    EQUIPEMENTSOverhead earth wire :

    - Protects the O/H transmission line from Lightning strokes.

    Wave Traps/Line traps :

    - Used in PLCC circuits for Communication and Protection of

    Transmission lines

  • 7/29/2019 220 kV AIS Switchyard

    24/26

    Reactive Power control devices :

    - Controls the reactive power imbalance in the grid byswitching ON/OFF the Shunt Reactors, Shunt Capacitors etc.,

    Current Limiting Reactors :

    - Limits the Short circuit currents in case of faulty conditions

  • 7/29/2019 220 kV AIS Switchyard

    25/26

    EQUIPMENTINBUSCOUPLERBAY

    Circuit breakers Makes or automatically breaks

    the electrical circuits underLoaded condition

    Interrupting short-circuit current

    Reliable protection of motors

    Protection of leads and itsoptimum utilisation

    Protection of installations

    Integration in the control circuit Switching under normal service

    conditions

    Disconnecting function

  • 7/29/2019 220 kV AIS Switchyard

    26/26

    Operates under off-load

    conditions

    Physically isolates the electric

    circuit

    Does not have any current

    making & breaking capacity

    Used in addition to C.B.

    isolators