    ------ Original Message --------

    Subject:TR::029 Submission of Revised VFD Reactor & Transformer SizingCalculations Rev.02-Korba STPP

    Date:Tue, 05 Feb 2008 08:52:27 +0530

    From:RAMA MOHAN.G

    To:[email protected], 'N K Gupta' ,[email protected]

    CC:[email protected]

    Bharat Heavy Electricals Limited Fax : 080-26741953( A Government of India Undertaking ) 26740137

    ELECTRONICS DIVISION : 080-26998259PB No. 2606, Mysore Road, Bangalore - 560 026 26745150

    REF:CE:PMC:KORBA-III:GRMTo, 05.02.08

    Shri TAPAS DEYDGM (I/C- Kh Korba & Farakka Task Force)NTPC/EOC Complex Fax: 0120-2410217Plot No. A8A , Sector 24NOIDA : 201 301 (UP)

    ATTN: Shri KS RAMASWAMY / CDE (TF Korba/Farakka)Dear sir,

    Sub.: Submission of Revised VFD Reactor & Transformer Sizing Calculations Rev.02-

    for KORBA III 1X500MW

    Please find enclosed the VFD REACTOR & TRANSFORMER SIZINGCALCULATIONS Rev.02 dtd.21.01.2008(2140-108-27EN-PVE-U-001-02 Descal.pdf)

    for NTPC KORBA III 1x500MW.

    The following are the changes in Rev.02

    a.Calculations have been done with 12 Pulse Motor rating changed to 3900KW as given

    by BHEL Bhopal. b.VFD Transformer rating has been revised to

    3250KVA,6.6kV/2.3kV against earlier rating of 3000KVA,6.6kV/2.3kV to match the

    rating of VFD Transformer for Farakka St-III 1x500MW.

    Rev.01 of the above document has been given Cat-IV approval by NTPC vide transmittalRef.:CC:PEK:2140:108102:27:561 dtd.27.02.07 enclosed herewith.

    With the above, we request NTPC to kindly approve the above document at the earliest.

    Thanking You,

    Yours faithfully,

    mailto:[email protected]%3emailto:[email protected]:[email protected]:[email protected]%3emailto:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]:[email protected]%3emailto:[email protected]:[email protected]%3e
  • 7/27/2019 2140-108-27-EN-PVE-U-001-02

    2/4

    For BHARAT HEAVY ELECTRICALS

    LTD.

    G.RAMAMOHAN

    Dy. Manager PMC/CE

    Copy to::

    L.SubbalakshmiDy.Mgr(CE-D&PS)

  • 7/27/2019 2140-108-27-EN-PVE-U-001-02

    3/4

    PROJECT : VFD FOR NTPC-KORBA STPP ST-III (1X500MW)

    DOCUMENT NO: D&PS/NTPCKORBA/DESCAL/REV.02 Date : 21.01.2008

    DC LINK REACTOR & TRANSFORMER RATING CALCULATIONS (NTPC-KORBA VFD)

    PAGE 1 :DC REACTOR SIZING ( RATING) CALCULATIONS:NTPC Drg . No: 2140-108-27EN-PVE-U-001 REV02

    BHEL Drg No : EN-DG-2410-145-4052

    FROM MOTOR SPEC/DATA SHEET:

    TEST BLOCK PT: DESIGN POINT 1: ( 3900KW , 545 RPM) : 12 PULSE RATING

    IAC1 = 3900 = 566 Amps

    2* 3 * 2.3 * 0.96 * 0.90 (Taking 0.96 eff. & 0.9 lead p.f)

    IDC1 = 1.2825 * IAC1 = 1.2825 * 566= 726 Amps

    BMCR-DC RATING: (1475 KW, 390 RPM) : 6 PULSE RATING

    IAC2 = 1475 = 558 Amps

    3 * 1.804 * 0.94 * 0.90 (Taking 0.94 eff. & 0.90 lead p.f)Motor Terminal Voltage at BMCR Pt = 1.804KV

    IDC2 = 1.2825 * IAC2 = 1.2825 * 558= 716 Amps

    IDC MIN = 0.2 * IDC2 = 0.2 * 716= 143 Amps

    DC Reactor is required to absorb : ( * 2 * 2300) * 1/600 volt-sec= 1.355 volt-sec

    Inductance value = 1.355/143 = 9.48 mH

    Take 10 mH

    Current rating = 726 * 1.2 = 871 amps (20% for ripple)

    Take 1000 amps

    Reactor Rating = 10 mH , 1000 amp s

    KVAR Rating of Reactor = (2fLI) * I * 10 3

    = (314 * 10 * 103 * 1000) * 1000 * 10 3= 3140 KVAR

    Assume 0.7 % losses in reactor: 0.7 * 10 2 * 3140 = 22 kW

    Voltage drop across reactor = 22 * 10 3 = 22 volts

    1000

    Digitally signed byN.K. GUPTADN: cn=N.K.GUPTA, c=IN,o=NTPCLTD,ou=TASKFORCE,email=nkgupta@nt

    pceoc.co.inReason: CAT-IVDate: 2008.02.1511:27:49 +05'30'

  • 7/27/2019 2140-108-27-EN-PVE-U-001-02

    4/4

    PAGE 2 :TRANSFORMER SIZING (RATING) CALCULATIONS:

    NTPC Drg . No: 2140-108-27EN-PVE-U-001 REV02BHEL Drg No : EN-DG-2410-145-4052

    Keeping a margin angle of 25% for Inverter operation:

    (+) = 155 = 180 - ( - ) ( - ) = 25

    = 39 , = 14 (XT = 12%, XS = 0.5%)

    DC Voltage on motor side of reactor :

    = Cell drop + 1.35 * ELL (cos + Xc/2 + Rm)

    [ Reactance = 0.10 (Xc) ; Rm = Ra = 0.012 ]

    = 9 + 1.35 * 2300 ( 0.78 + 0.05 + 0.012)= 2623 volts

    Voltage on converter side of DC Link Reactor := 2623 + 22 = 2645 volts [Drop across reactor = 22 volts]

    Assuming a 5% dip on mains :

    0.95 EDO = 2645 + [(XT + XS)/2 + RT] * EDO + 9= 2645 + [(0.12 + 0.005)/2 +0.01] * EDO + 9

    0.8775 EDO = 2654 EDO = 3025 volts

    Transformer Secondary voltage = 3025 /1.35 = 2240 voltsTake 2300 volts

    Transformer Rating = 1.05 * EDO * IDC= 1.05 * ( 1.35 * 2300) * 726 * 10-3

    = 2367 KVA ( XT = 12%)

    Taking into consideration transformer losses, add 20% to KVA 1.2 * 2367 =2840 KVA

    Take 3250 KVA

    Transf orm er Rating = 6.6 KV / 2.3 KV, 3250 KVA

    Flexible Couplin g : Type PM 270 (Renold Hi-Tec Coupling)

    Prepared By Checked By Approved By

    (L.Subbalakshmi) (Prachi Rao.V) (S.K.Iyengar)