GOGREENchillers · 2017-03-16 · EER net 3,16 3,32 3,15 3,28 3,24 3,13 ESEER 4,36 5,11 5,38 5,02...

12
GOGREENchillers the new HFO1234ze ecorange GOGREEN solutions rcgroupairconditioning Let’s treat well the earth on which we live: it was not donated by our fathers , but we borrowed it from our children ... (Masai Proverb)

Transcript of GOGREENchillers · 2017-03-16 · EER net 3,16 3,32 3,15 3,28 3,24 3,13 ESEER 4,36 5,11 5,38 5,02...

Page 1: GOGREENchillers · 2017-03-16 · EER net 3,16 3,32 3,15 3,28 3,24 3,13 ESEER 4,36 5,11 5,38 5,02 5,07 5,49 A (mm) 2410 3530 3530 4650 5770 6890 B (mm) 2260 2260 2260 2260 2260 2260

GOGREENchillersthe new HFO1234ze ecorange

GOGREENs o l u t i o n s

rcgroupairconditioning

Let’s treat well the earth on which we live:it was not donated by our fathers , but we borrowed it from our children ...

(Masai Proverb)

Page 2: GOGREENchillers · 2017-03-16 · EER net 3,16 3,32 3,15 3,28 3,24 3,13 ESEER 4,36 5,11 5,38 5,02 5,07 5,49 A (mm) 2410 3530 3530 4650 5770 6890 B (mm) 2260 2260 2260 2260 2260 2260

OUR PLANETToday, environmental respect is the core value and guideline to develop new technologies.The environmental sustainability makes its appearance in every sector through research techniques for the renewal of the resources of our planet Earth. Mankind has the duty to defend and preserve the delicate balance of the Earth.Sustainability for RC Group is the commitment of the present generations to leave to future generations the same quantity and quality of resources especially.Since 1997 (from the Kyoto Protocol) to today, the first aspect is the reduction of global warming, gradually limiting the use of HFC refrigerants and, later, of F gases as well.

OUR MISSIONThe high efficiency of the products together with the study and design of tailored solution, translate into energy savings, and consequently in cost reduction.RC Group solutions arise from synergies between RC Group hardware and software, through analysis and energy management.Calculating it in advance and carefully, drive us to system design compatible with requirements and environment. At the same time, we can also determine which will be the return of the initial investment in terms of economies of exercise.

Page 3: GOGREENchillers · 2017-03-16 · EER net 3,16 3,32 3,15 3,28 3,24 3,13 ESEER 4,36 5,11 5,38 5,02 5,07 5,49 A (mm) 2410 3530 3530 4650 5770 6890 B (mm) 2260 2260 2260 2260 2260 2260

GOReliableEcologicEvolvedNatural

rcgroupairconditioning

X TYPE

SPECIAL TURBO HFO SPECTRUM SEQUENCER COOLNET

RC-CLOUD PLATFORM

RCWORLD

Types y s t e m

OUR SOLUTION: X TYPE SYSTEMA new concept of CRAH unit designed around a revolutionary thermal exchange coil using the state of the art in terms of high efficiency components optimized for the new operating conditions for the lowest PUE (1,14).

• Supply air temperature: minimum 20°C• In/Out CHW temperature: 18 / 28°C

THE SYSTEM

Page 4: GOGREENchillers · 2017-03-16 · EER net 3,16 3,32 3,15 3,28 3,24 3,13 ESEER 4,36 5,11 5,38 5,02 5,07 5,49 A (mm) 2410 3530 3530 4650 5770 6890 B (mm) 2260 2260 2260 2260 2260 2260

HFO1234ze

GOGREEN

EnvironmentallyEnergy Saving

Ecosustainability

LIGHT WEIGHT SOLUTIONS FOR ENVIRONMENT

RC Group makes use of refrigerants innocuous to the atmosphere, first of all the HFO1234ze that, thanks to its high environmental compatibility joined to a high energy efficiency, results to be an excellent SOLUTION for replacement of R134a.Another point in its favor is the much higher critical temperature which allows to operate at much higher condensation temperatures retaining a good thermodynamic efficiency.

Page 5: GOGREENchillers · 2017-03-16 · EER net 3,16 3,32 3,15 3,28 3,24 3,13 ESEER 4,36 5,11 5,38 5,02 5,07 5,49 A (mm) 2410 3530 3530 4650 5770 6890 B (mm) 2260 2260 2260 2260 2260 2260

HFO1234ze

NOODP

LOWTEWI

LOWGWP

R134a HFO1234 ze

R134a

HFO1234 ze -37%

2018

-69%

2024 2030

-79%

CFCs1900s

HCFCs1990s

HFCsmid 1990s 2006

HFOs

CFC Phase-out

HCFC Phase-out F-Gas Regulation

rcgroupairconditioning

1900 1990 mid1990 2006

13 YEARS

18 DAYS

The GWP (Global Warming Potential) expresses the contribution to the greenhouse effect of a gas relatively to the effect of CO2, whose reference potential is equal to 1. Each GWP value is calculated for a specific time interval.

The ODP (Ozone Depletion Potential) index refers to a chemical compound and it is the relative value of degradation of the ozone layer that this compound may cause.

The TEWI (Total Equivalent Warming Impact) index allows to quantify the impact that the equipment have on global warming considering both the emission of greenhouse gases during operation and disposal of the fluids operating at the end of the l ife cycle.

UE GOALS

GREENHOUSE GASES REDUCTION

MONTREAL PROTOCOLEU LEGISLATIONKYOTO PROTOCOL

Ozone depletingVery high GWP

No-Ozone depletingHigh GWP

No-Ozone depletingVery low GWP

GWP 1430 6

ODP 0 0

NON-Toxicity level A Class A Class

Inflammability NO NO

Efficiency + ++

Critical Temperature (°C) 101 110

-20%CO2

+20%Renewable

Energy-20%

PrimaryEnergy

ConsumptionEmission

LIFE TIME IN ATMOSPHERE

Page 6: GOGREENchillers · 2017-03-16 · EER net 3,16 3,32 3,15 3,28 3,24 3,13 ESEER 4,36 5,11 5,38 5,02 5,07 5,49 A (mm) 2410 3530 3530 4650 5770 6890 B (mm) 2260 2260 2260 2260 2260 2260

±0,3°C

310 kW

+ 3%

NEWPRODUCT

3 new High Efficiency series36 models for a wide selection opportunity

Design excellence by RC GroupGren refrigerant HFO1234ze

Microchannel condensing coilsHigh EER and ESEER

Wide range of accessories

OUR ECO-RANGE SELECTION

UNICO TURBO FLGAir cooled liquid chillers in A class energy efficiency equipped with oil-free centrifugal compressors with magnetic levitation bearings, flooded evaporator and microchannel condensing coils.

UNICO TURBO FLG FREE Air cooled liquid chillers with Free-Cooling system in A class energy efficiency equipped with oil-free centrifugal compressors with magnetic levitation bearings, flooded evaporator and microchannel condensing coils.

FRIGO TURBO FLGWater cooled liquid chillers in A class energy efficiency equipped with oil-free centrifugal compressors with magnetic levitation bearings, flooded evaporator and shall and tube condenser.

Cooling Capacity, Range 310-65 kW

Accurate Cooling

Energy Efficiency increase compared to R134a

COMPRESSOR TG310

Page 7: GOGREENchillers · 2017-03-16 · EER net 3,16 3,32 3,15 3,28 3,24 3,13 ESEER 4,36 5,11 5,38 5,02 5,07 5,49 A (mm) 2410 3530 3530 4650 5770 6890 B (mm) 2260 2260 2260 2260 2260 2260

INVERTER

HIGHEFFICIENCY

AB

C

LOWNOISE HFO1234ze

UNICO TURBO FLG

rcgroupairconditioning

OUR ECO-RANGE SELECTION

Model 200 T1 VT2 260 T1 VT2 310 T1E VT3 400 T2 VT4 520 T2E VT5 620 T2E VT6Cooling Capacity (kW) 200 260 310 400 520 620

EER net 3,16 3,32 3,15 3,28 3,24 3,13ESEER 4,36 5,11 5,38 5,02 5,07 5,49A (mm) 2410 3530 3530 4650 5770 6890B (mm) 2260 2260 2260 2260 2260 2260C (mm) 2370 2370 2370 2370 2370 2370

Net weight (Kg) 2429 2680 3433 3720 4285 5141

Model 700 T3 VT7 780 T3E VT7 900 T3E VT8 1040 T4E VT10 1200 T4E VT11 1300 T4E VT12Cooling Capacity (kW) 700 780 900 1040 1200 1260

EER net 3,28 3,16 3,15 3,20 3,15 3,17ESEER 5,15 5,09 5,59 5,07 5,46 5,71A (mm) 8010 8010 9130 10250 12490 13610B (mm) 2260 2260 2260 2260 2260 2260C (mm) 2370 2370 2370 2370 2370 2370

Net weight (Kg) 5518 5647 5296 5913 6945 8196

Model Sound Pressure Level (Lp1m)[dB(A)]

Sound Power Level(Lw)[dB(A)]

200 T1 VT2 73,4 92,3260 T1 VT2 73,9 93,4

310 T1E VT3 73,9 93,4400 T2 VT4 74,8 94,8

520 T2E VT5 75,1 95,6620 T2E VT6 75,4 96,4700 T3 VT7 75,7 97,1

780 T3E VT7 75,7 97,1900 T3E VT8 76,1 97,8

1040 T4E VT10 76,1 98,21200 T4E VT11 76,4 99,11300 T4E VT12 76,5 99,5

Cooling Capacity: 200 ÷ 1260 kW

Referred to water temperature 12/7°C and 35°C ambient air temperature according to Eurovent standard

EER up to 3,28ESEER up to 5,71

Sound pressure ISO3744Sound power ISO9614-2

Page 8: GOGREENchillers · 2017-03-16 · EER net 3,16 3,32 3,15 3,28 3,24 3,13 ESEER 4,36 5,11 5,38 5,02 5,07 5,49 A (mm) 2410 3530 3530 4650 5770 6890 B (mm) 2260 2260 2260 2260 2260 2260

FREECOOLING

INVERTERHIGHEFFICIENCY

LOWNOISEHFO1234ze

AB

C

UNICO TURBO FLG FREE

Model 200 T1 VT2 260 T1 VT3 310 T1E VT3 400 T2 VT4 520 T2E VT5 620 T2E VT6Cooling Capacity (kW) 200 260 310 400 520 620

Free-Cooling (kW) 243 364 364 485 607 728EER net 3,09 3,33 3,46 3,22 3,51 3,46ESEER 3,92 4,60 4,84 4,52 4,56 4,94A (mm) 2410 3530 3530 4650 5770 6890B (mm) 2260 2260 2260 2260 2260 2260C (mm) 2370 2370 2370 2370 2370 2370

Net weight (Kg) 2706 3091 3844 4280 4983 6000

Model 700 T3 VT7 780 T3E VT7 900 T3E VT8 1040 T4E VT10 1200 T4E VT11 1300 T4E VT12Cooling Capacity (kW) 700 780 900 1040 1200 1260

Free-Cooling (kW) 849 849 970 1092 1334 1456EER net 3,29 3,48 3,46 3,47 3,48 3,43ESEER 4,64 4,58 5,03 4,56 4,91 5,14A (mm) 8010 8010 9130 10250 12490 13610B (mm) 2260 2260 2260 2260 2260 2260C (mm) 2370 2370 2370 2370 2370 2370

Net weight (Kg) 6519 6648 6438 7197 8512 9904

Model Sound Pressure Level (Lp1m)[dB(A)]

Sound Power Level(Lw)[dB(A)]

200 T1 VT2 73,4 92,3260 T1 VT2 73,9 93,4

310 T1E VT3 73,9 93,4400 T2 VT4 74,8 94,8

520 T2E VT5 75,1 95,6620 T2E VT6 75,4 96,4700 T3 VT7 75,7 97,1

780 T3E VT7 75,7 97,1900 T3E VT8 76,1 97,8

1040 T4E VT10 76,1 98,21200 T4E VT11 76,4 99,11300 T4E VT12 76,5 99,5

Cooling Capacity: 200 ÷ 1260 kWFree-Cooling Capacity: 243 ÷ 1456 kW

Referred to water temperature 12/7°C and 35°C ambient air temperature according to Eurovent standard

EER up to 3,51ESEER up to 5,03EER up to 3,51ESEER up to 5,03

Sound pressure ISO3744Sound power ISO9614-2

Page 9: GOGREENchillers · 2017-03-16 · EER net 3,16 3,32 3,15 3,28 3,24 3,13 ESEER 4,36 5,11 5,38 5,02 5,07 5,49 A (mm) 2410 3530 3530 4650 5770 6890 B (mm) 2260 2260 2260 2260 2260 2260

INVERTER

HIGHEFFICIENCY

LOWNOISEHFO1234ze

AB

C

FRIGO TURBO FLG

rcgroupairconditioning

Model K 270 T1 250 T1 P4 280 T1 310 T1E 400 T2 400 T2 P4 500 T2 P4Cooling Capacity (kW) 270 250 280 310 400 400 500

EER net 4,55 5,23 5,05 5,24 5,21 5,23 5,24ESEER 7,45 8,09 8,24 8,27 8,33 8,37 8,63A (mm) 1000 3620 3620 3620 3620 3620 3805B (mm) 1300 1360 1360 1360 1360 1360 1360C (mm) 1850 1770 1770 1770 1770 1770 1929

Net weight (Kg) 1200 1921 1918 2031 2108 2208 2704

Model 560 T2 620 T2E 750 T3 P4 840 T3 930 T3E 1000 T4 P4 1120 T4 1240 T4ECooling Capacity (kW) 560 620 750 840 930 1000 1120 1240

EER net 5,05 5,25 5,26 5,08 5,28 5,26 5,08 5,30ESEER 8,61 8,68 8,99 8,87 8,76 8,55 8,67 8,80A (mm) 3805 3097 3870 3870 3870 4640 4640 4640B (mm) 1360 1360 1400 1400 1400 1400 1400 1400C (mm) 1929 1929 2059 2059 2059 2090 2090 2090

Net weight (Kg) 2703 2763 3912 3912 4094 5289 5291 5468

Model Sound Pressure Level (Lp1m)[dB(A)]

Sound Power Level(Lw)[dB(A)]

K 270 T1 69,4 86,0250 T1 P4 69,5 87,5

280 T1 69,5 87,5310 T1E 69,9 87,9400 T2 71,7 89,7

400 T2 P4 71,7 89,7500 T2 P4 71,5 89,7

560 T2 71,5 89,7620 T2E 71,7 89,9

750 T3 P4 71,6 90,7840 T3 71,6 90,7

930 T3E 72,1 91,21000 T4 P4 72,7 92,1

1120 T4 72,7 92,11240 T4E 72,9 92,3

Cooling Capacity: 270 ÷ 1240 kW

Referred to water temperature 12/7°C and condenser water temperature 30/35°C according to Eurovent standard

EER up to 5,30ESEER up to 8,99EER up to 5,30ESEER up to 8,99

Sound pressure ISO3744Sound power ISO9614-2

Page 10: GOGREENchillers · 2017-03-16 · EER net 3,16 3,32 3,15 3,28 3,24 3,13 ESEER 4,36 5,11 5,38 5,02 5,07 5,49 A (mm) 2410 3530 3530 4650 5770 6890 B (mm) 2260 2260 2260 2260 2260 2260

X TYPE AIR CONDITIONERS

GOGREEN

CHILLEDWATER

NEWPRODUCT

ECFAN

XCOILS

BAGFILTERS

The new chil led water air conditioners range designed for a perfect synergy with TURBO FLG liquid chil lers.3 models: from 100 to 190 kW EER up to 52,63 cabinets2 stage CHW coil and 2-way CHW valveEC plug fansReturn air bag filterIn/Out CHW connections from the bottom

UNDER PATENT

Page 11: GOGREENchillers · 2017-03-16 · EER net 3,16 3,32 3,15 3,28 3,24 3,13 ESEER 4,36 5,11 5,38 5,02 5,07 5,49 A (mm) 2410 3530 3530 4650 5770 6890 B (mm) 2260 2260 2260 2260 2260 2260

rcgroupairconditioning

TIER II TIER IVPotenza Frigorifera (kW) 140 101Portata Aria (m3/h) 31000 22000Potenza Assorbita Ventilatori (kW) 4,5 1,92EER (kW / kW) 31,1 52,6

FILTER SECTIONwith low pressure drop G4 efficiency bag type return air filters for once a year replacement

INNOVATIVE X COIL SECTIONLower pressure drop on air sideLower turbulenceCorrect water side pressure dropPossibility to have two independent separate CHW coils complying with TIER IV without modifications

FANS SECTIONwith nr. 2, 3 or 4 x Plug Fan EC “radical” type with:large diameter, 630 mm very high energy efficiency (wing profile).

TWO OPERATING COOLING LOGICS FOR A PERFECT REDUNDANCY

COOLING LOGIC 1

Single CHW source with:nr. 1 x TWO STAGE COOLING PROCESS FOR FULL CAPACITY

COOLING LOGIC 2

Double CHW source with:nr. 2 x SINGLE STAGE COOLING PROCESS FOR HALF CAPACITY EACH TO MEET THE TIER IV REQUIREMENTS

More uniform air/CHW temperature

Correct air path crossing the unit

Fans in symmetrical position on the vertical axes

Lower power input and noise

Page 12: GOGREENchillers · 2017-03-16 · EER net 3,16 3,32 3,15 3,28 3,24 3,13 ESEER 4,36 5,11 5,38 5,02 5,07 5,49 A (mm) 2410 3530 3530 4650 5770 6890 B (mm) 2260 2260 2260 2260 2260 2260

GOReliableEcologicEvolvedNatural

RC GROUP S.p.A Via Roma 5, 27010 Valle Salimbene (PV) Italy +39 0382 433811 www.rcgroup.it [email protected]

RC Group isa company of

Technicaldataanddimensionsarepreliminaryandnotbinding.RCGROUPS.p.A.reservestherightforchangesand/ormodificationswithoutnotice