2016 LocalAuthorityBuildingStandardsScotland[LABSS]
LABSSProceduralGuidanceonverificationofcertifiedandnon-certifiedroutesforcompliancewiththebuildingregulations:February2016
1
LABSSProceduralguidanceonverificationofcertifiedandnon-certifiedroutesforcompliancewiththebuildingregulationsFebruary2016 FOREWORDbyLABSSCHAIRNICKMcLARENThebuildingstandardssysteminScotlandisoneofthemostrobustintheworld;itsetshighstandardsinconstruction,sustainabilityandenergyefficiencyrequirements,andlocalauthoritiesprovideanenviablerecordofmonitoringcompliance.BuildingStandardsCertificationisnowanestablishedalthoughoptionalpartofthesystem,butwhathappenswhenworkisnotcoveredbyaCertificateofDesignoraCertificateofConstruction?PromptedbytheScottishMinisters,aCertificationWorkshopinSeptember2014,attendedbyallinterestedparties,ledtotherecommendationthatwherenotcoveredbyaCertificateofDesignoraCertificateofConstruction“guidancebedevelopedtoencourageaconsistentapproachtotheverificationofcertifiablework”.Inacceptingthischallenge,theLABSSpositionhasalwaysbeenclear;localauthoritiesandtheschemeprovidersdonotprovideanequivalentservice.LABSSmembersundertakereasonableinquirywhilecertifiersassurecomplianceandaredirectlyresponsiblefortheworktheycertify.Thereisnoexpectationthatindividualbuildingstandardssurveyorsbecomeasexpertaspractitionersincertifiabletopics.Whatthisguidancedoesisprovideanapproachtoriskassessingcertifiableworkbasedongoodpractice,ittakestheopportunitytomakethisgoodpracticemorewidelyknown,anditprovidestheopportunityforamoreconsistentapproachtoriskassessingnationwide.TheresultisthissuiteofLABSSguidancenotesdraftedwithcontributionsfromtheScottishGovernment’sBuildingStandardsDivision,thevariouscertificationschemeprovidersand,ofcourse,theLABSSmembership.Inendorsingthiswork,theLABSSExecutivewishestorecognisethecontributionsfromTomAird,DaveAitken,RichardCairns,JohnDelamar,FrankFairgrieve,GordonLindsay,DonaldMacNeil,NeilMitchell,IainPatience,IainRockeandAndrewTurriff,allwhomhavediligentlyrepresentedLABSSthroughoutthisprocess,andtheassistanceofthosememberswhoparticipatedintheconsultationprocess.Thankyouall.
2016 LocalAuthorityBuildingStandardsScotland[LABSS]
LABSSProceduralGuidanceonverificationofcertifiedandnon-certifiedroutesforcompliancewiththebuildingregulations:February2016
2
CONTENT
Ref: Title Scope Page Foreword 1 Content 2 Introduction,aimsandbackground 3 LABSSPGNEQ001/2016
Riskmanagementintheverificationofbuildingwarrantsubmissions
Riskmanagement 4-10
LABSSPGNEQ002/2016
TheverificationofStructuresSection1.0oftheTechnicalHandbooks
Design 11-21
LABSSPGNEQ003/2016
TheverificationofEnergyUseSection6.0oftheTechnicalHandbooks
Design 22-32
LABSSPGNEQ004/2016
TheverificationofElectricalInstallationsSection4.5oftheTechnicalHandbooks
Construction 33-38
LABSSPGNEQ005/2016
TheverificationofPlumbingDrainageandHeatingInstallationsSection3.0oftheTechnicalHandbooks
Construction 39-44
2016 LocalAuthorityBuildingStandardsScotland[LABSS]
LABSSProceduralGuidanceonverificationofcertifiedandnon-certifiedroutesforcompliancewiththebuildingregulations:February2016
3
INTRODUCTIONInframingtheseguidancenotesitisimportanttoacknowledgeandrecognise,aspartofthe‘equivalence’process,thatverifiershavewellestablishedriskprotocolsinplacecoveringallaspectsofthebuildingwarrantprocessfromapplicationthroughtocompletion,allofwhichareimplementedbystaffwhoareprofessionallyqualifiedand/orsuitablyexperienced.AIMS Thesedocumentsprovideamethodologywhichseeksto:• promoteaconsistentapproachtotheverificationofcertifiablework,• examinewhatconstitutesproportionateauditing,and• offerguidanceonwhat,intermsofequivalence,mayconstitutereasonableinquiryfordesign
andconstructionworksthatarenotcoveredbyaCertificateofDesignoraCertificateofConstruction.
Thesedocumentsarenotdesignedorintendedtoprovidedesignerswithachoiceonhowtocomplywiththebuildingregulations.Asastartingpoint,itwasconsideredthattheguidanceshould:• bebasedonariskassessmentapproach,• considertechnicalandproceduralaspects,• considerthecompetenciesofverificationstafforotherresources,and• showthatauditingmeasuresarebasedonariskassessmentapproach.BACKGROUNDTheimportanceofcertificationwithinthebuildingstandardssysteminScotlandwashighlightedattheScottishGovernment’seventatEdinburghCastleinMarch2014andsubsequentlyattheBuildingStandardsCertificationWorkshop,heldinEdinburghon24thSeptember2014.TheworkshopresultedinthepublicationinMay2015ofadraftreportoncertifiedandnon-certifiedroutesforcompliancewiththebuildingregulations.TheissueofcertificationwasfurtherdiscussedatthemeetingbetweenLABSSandtheScottishGovernmentMinisterforLocalGovernment,earlyin2015.WorkingwithpartnersincludingtheBuildingStandardsDivisionandthevariouscertificationschemeproviders,LABSSacceptedthechallengetodevelopandpublishguidancetoencourageaconsistentapproachtotheverificationofcertifiablework.TheresultingsuiteoffiveindividualLABSSguidancenotes,coveringriskmanagementandverificationofstructures,energy,electricalinstallationsandplumbingdrainageandheatinginstallations,arecollatedandpresentedinthisdocument.
2016 LocalAuthorityBuildingStandardsScotland[LABSS]
LABSSProceduralGuidanceonverificationofcertifiedandnon-certifiedroutesforcompliancewiththebuildingregulations:February2016
4
LABSSPGNEQ001/2016Riskmanagementintheverification
ofbuildingwarrantsubmissions1.1PREAMBLEThisguidancenoteconsidershowtoprovideaconsistentapproachtoriskmanagementfortheverificationofbuildingwarrantsubmissions.Inparticular,thefocusisonriskmanagementassociatedwithSection1StructuresandSection6Energycomponentsofsubmissions,whicharosefromtheprojectonequivalencebetweencertified(underApprovedSchemes)andnon-certifiedsubmissions(seeBuildingStandardsCertificationWorkshopatBSD,Livingston,on24September2014).Ofnote,itisconsideredthattheproposedriskmanagementprocesscouldbereadilyappliedtotheother5sections(Fire,Environment,Safety,NoiseandSustainability)detailedintheTechnicalHandbooks.1.2AIMSAnyriskmatrixdevelopedasaresultofthe“Equivalenceinverification”projecthasthepotentialtoberolledoutacrossall32localauthoritiesinScotland.Duetodifferingmanagementandinformationsystemsused,itisproposedthatasimpleriskmodelbeutilised,thoughthegenericmodelcouldbefurtherextendedtomeetmoreadvancedlocalrequirements.Anauditingprocess,aimedatensuringenhancedtransparencyforevidencingconsistencyofriskapproachesappliedtobuildingwarrantsubmissionsthroughoutScotland,isalsopresented.2.APPROACHESTORISKTherearemanydifferentapproachestoriskmanagement,andthemostsuitableapproachisdependentonthefieldofapplication.Generally,riskisdefinedasthecombinationoftheprobabilityofahazardresultinginanadverseevent,timestheseverityoftheevent.Thisdefinitionformsthebasisofriskconsiderationsusedfortheassessmentofriskinrelationtobuildingwarrantapplications,fromtheperspectiveoftheverifier.2.1Selectinganapproachtorisk2.1.1RiskbasedonexistingDOM/NDOMcategoriesAttheoutset,anumberofapproachesbasedonexistingriskprocedureswereconsidered.Inparticular,useoftheexistingDOM/NDOMriskcategories,developedaspartofthePerformanceFrameworkandtheVerificationduringConstructionprocess,wereconsideredforeaseofimplementationacrossall32localauthorities.ThedomesticandnondomesticriskgroupingsarepresentedintheBSD/LABSSpublications:• VERIFICATIONDURINGCONSTRUCTION-GuidancetoSupporttheApplicationofReasonable
Inquiry• VERIFICATIONDURINGCONSTRUCTIONNON-DOMESTICBUILDINGS-GuidancetoSupportthe
ApplicationofReasonableInquiry
2016 LocalAuthorityBuildingStandardsScotland[LABSS]
LABSSProceduralGuidanceonverificationofcertifiedandnon-certifiedroutesforcompliancewiththebuildingregulations:February2016
5
Ingeneralterms,thedriversforincreasingriskarefireandstructuralorbuildingcomplexity.However,thereisawiderangeofbuildingtypesincertaincategories(forexample,NDOM7rangesfromcafesandsmallshopstolarge(notdefined)officebuildingsandshoppingcentres).Thiscangiverisetoconflictintheplacementwithintheoverallhierarchy.Accordingly,whilstthebenefitsofutilisingthecurrentDOMandNDOMriskcategoriesareconsideredtobeveryattractiveintermsofeaseofimplementationacrossall32localauthorities,itisevidentthatthisDOM/NDOMhierarchyistoodivergentforuseinagenericriskmatrix.2.1.2RiskbasedonSERapproachtostructuresAsanalternative,mirroringtheSER(StructuralEngineersRegistrationLtd.)approachtoriskforCertificationofStructureswasconsidered.TheSERapproachtoriskhasbeenguidedbytheclassificationwithinBSEN1990:2002Eurocode-Basisofstructuraldesign.InSERTechnicalBulletin2,thefourriskclassesusedforstructuraldesignaredetailedalongwithacheckingregime.Thefourriskclassificationshavebeenderivedfroma:• riskfactorwhichcomprisesaloadparameterandastructuralparameter,and• consequencefactor(takesaccountofthenumbersofpeopleatrisk,thelocationandasocietal
criteria)Ingeneralterms,thedriverforincreasingriskisstructuralcomplexity.However,therearedifficultiesindirectlymirroringtheSERriskprocesstobuildingwarrantapplications.Ofnote,80%ofbuildingwarrantapplicationsaredomesticinnaturewithavalueoflessthan£50,000.Inthiscontext,themajorityofbuildingwarrantapplicationswouldberiskedinthelowestSERRC1riskcategory.AstheSERriskhierarchydoesnotdifferentiateacrossthislargepercentageofbuildingwarrants,itisconsideredthattheSERriskmatrixaloneshouldnotformthebasisoftheriskassessmentmatrixusedtoaddressequivalence.2.1.3RiskbasedonapproachestypicallyusedbyverifiersAspartoflocalmanagementprocedures,overanumberofyears,verifiershavedevelopedindividualprocessestoensurethatriskisaddressedinrelationtobuildingwarrantsubmissions.Thelocalprocedurescurrentlyinplacehavetypicallybeendevelopedtolinkinwiththemanagementsystemsandconstraintswithinwhichtheverifiersmustoperate.3.RISKMANAGEMENTFORBUILDINGWARRANTAPPLICATIONS3.1Perceivedriskfromaverifier’sperspectiveFromaverifier’sperspective(andindeedfromthedesigner’s/architect’sperspective),riskisnotthesameforverifyingthe7individualtopicsdetailedintheTechnicalHandbooks.Eachparticulartopicwillhaveapotentialrangeofriskwhichdependsonthecomplexityoftheproposedworks.Fromtheverifiers’pointofviewofperceivedriskwhenassessingbuildingwarrantapplications,acomparativeexampleoftheperceivedrangeofrisksassociatedwiththe7topicspresentedintheTechnicalHandbooksispresentedinTable1.Eachofthe3maincategories(severity,verifyingandcomplaints)havebeendividedinto3sub-categories(high,mediumandlow)topermitdifferencesbetweenperceivedDOMandNDOMriskstobebetterhighlighted.
2016 LocalAuthorityBuildingStandardsScotland[LABSS]
LABSSProceduralGuidanceonverificationofcertifiedandnon-certifiedroutesforcompliancewiththebuildingregulations:February2016
6
Table1.Perceivedriskwhenassessingbuildingwarrantapplications
STRUCTURE FIRE ENVIRONMENT SAFETY NOISE ENERGY SUSTAINABILITY
DOM
NDO
M
DOM
NDO
M
DOM
NDO
M
DOM
NDO
M
DOM
NDO
M
DOM
NDO
M
DOM
NDO
M
Perceivedoverallriskfromverifierperspective
High High High High Med Med Med Med Med Low Med Low Low Low
Relativeseverityofanindividualadverseevent
High
Med
Low
RiskofnotverifyingfullcompliancewithBuildingRegulations
High
Med
Low
Relativelikelihoodofreceivingcomplaintspostcompletion
High
Med
Low
WhilstTable1issolelyintendedtobeindicative,thereasonsfortheindividualrisksdetailedarebasedongeneralriskapproachestypicallyusedbyverifiers:• Structures–Consequenceofstructuralfailure• Fire–Lifesafety• Environment–Impactonhealth(particularlycontamination,radon,drainageandventilation)• Safety–Riskofaccidentsandeaseofuse• Noise–Impactonwellbeing• Energy–Encouragingenergyefficiency• Sustainability–EncouragingsustainabilityTheperceivedoverallriskistheproductofthe‘Relativeseverityofanindividualadverseevent’multipliedby‘RiskofnotverifyingfullcompliancewithBuildingRegulations’multipliedby‘Relativelikelihoodofreceivingcomplaintspostcompletion’.Assuch,inthecontextofabuildingwarrantapplication,theperceivedoverallriskforsayEnergywillbeconsiderablylowerthanperceivedoverallriskforStructuresandFire.
2016 LocalAuthorityBuildingStandardsScotland[LABSS]
LABSSProceduralGuidanceonverificationofcertifiedandnon-certifiedroutesforcompliancewiththebuildingregulations:February2016
7
Ofnote,theoverallperceivedriskassociatedwithabuildingwarrantapplicationwillbethehighesttopicrisk,oncetheindividualtopicrisksarenormalisedasinTable1.3.2ProposedbuildingwarrantapplicationriskprocessItisconsideredthatthemosteffectiveapproachisforagenericriskdependingonbuildingtype/usetobeappliedtoeachbuildingwarrantapplication.Thisriskcouldthenbemodifieddependingonadditionalrisks,suchas:• Buildingcomplexity• Trainingandcompetenceofchecker• QualityofsubmissionTheriskmanagementprocessforbuildingwarrantsoutlinedinthefollowingsectionisbasedongoodpractisecurrentlyused.Itisnotedthatthedetailspresentedareintendedtoformabase-linetoenableaconsistentapproachofriskmanagementinrelationtobuildingwarrantsthroughoutScotland.Theproposedriskmatrixbasedonbuildingtype/useispresentedinFigure1andTable2.Ingeneralterms,thedriversforincreasingriskarefiresafetyandstructuralcomplexity.InTable2,fornondomesticbuildings,CategoriesA,BandCfocusonpropertyprotection,lifesafety,andlifesafetycoupledwithhighoccupancyandlimitedfamiliarityissuesrespectively.Fromtheoutset,itwasdeemedthatmulti-storeybuildingswouldattractahigherriskthantheequivalentsinglestorybuildings.3.3PeercheckingandauditThepurposeofpeercheckingistoensurethatallverificationissueswithinthesampleofbuildingwarrantapplicationsaresuitablyaddressed.Assuch,itistheresponsibilityoftheverifiertoensurethatstaffundertakingpeercheckingaresuitablytrained,experienced,andunderstandatwhatpointtheirknowledgeandexpertiseisinsufficienttofullycheckthecontentofanapplication.ThepeercheckingregimepresentedinTable3isbasedontheratesspecifiedbyeachverifier.Theserateswillreflectlocalresourcesavailableforpeerchecking.Thepeercheckingcanbeusedtomaintainalevelofqualityofoutput,andtoidentifyanyissuesthatmayrequireremedialactions,suchasadditionaltrainingforcasesurveyors.Wheretheriskrequirestobeincreasedtotakeintoaccountcasespecificissues,peercheckingshouldbeappliedtotheapplicationbydefault.
2016 LocalAuthorityBuildingStandardsScotland[LABSS]
LABSSProceduralGuidanceonverificationofcertifiedandnon-certifiedroutesforcompliancewiththebuildingregulations:February2016
8
Figure1.Proposedriskmanagementflowchartforbuildingwarrantapplications
Buildingwarrantapplicationreceived
Management:Applicationgivenbuildingriskcategory(Table2):
DOM:DL1toDH5NDOM:NL2toNH6
Management:Applicationallocatedto
casesurveyorandallocatedpeercheckingrequirement
(Table3)
Anychangestoprojectresultinreappraisalofrisk
Management:Whereriskismodifiedtotakeaccountofcase
specificissues,defaulttopeercheckingforthecase.
Management:Applicationreviewedtoflagifsufficientinternal(in-
house)expertiseavailableforpeercheckingorifexternalpeercheckingisrequired.
Applicationassessed
Applicationapprovedorrejected
Applicationpassedtosuitablycomptentcasesurveyor
Whererequired,applicationinternallypeerchecked
Whererequired,applicationexternallypeerchecked
2016 LocalAuthorityBuildingStandardsScotland[LABSS]
LABSSProceduralGuidanceonverificationofcertifiedandnon-certifiedroutesforcompliancewiththebuildingregulations:February2016 9
Table2.RiskmatrixforbuildingwarrantapplicationsRisk Domestic(PrefixD;Risk:L=Low,M=Medium,H=High;finalnumberisrelativeranking) Non-domestic(PrefixN;Risk:L=Low,M=Medium,H=High;finalnumberisrelativeranking) Checking
High
DH6
NH6 • Assessmentofproposedbuilding(s)requiringexternalfireengineeringexpertisetoresolve.• Complexdevelopment,alterationsandextensions(includingnon-standardconstruction).
High
DH5• Assessmentofproposedbuilding(s)requiringexternalfireengineeringexpertisetoresolve.• Complexdevelopment,alterationsandextensions(includingnon-standardconstruction). NH5
• Development,alterations,extensionsinvolvingmulti-storeyCatBorCbuildings.• Conversionsfromanondomesticbuildingtypetoadomestictype,forexamplehouse-office,house-shop,etc.;involvingmulti-storeyCatA,BorCbuildings.
Med
ium
DM4
• Multi-plotdevelopmentencompassingflats(allorinpart).• Conversionsfromanondomesticbuildingtypetoadomestictype,forexampleoffice-house,shop-house,etc.
• Multi-plotdevelopmentsencompassinghouseswithmorethan2storeys.
NM4
• Development,alterations,extensionsinvolvingmulti-storeyCatAbuildings.• Development,alterationsandextensionsinvolvingsingle-storeyCatBorCbuildings.• Conversionsfromanondomesticbuildingtypeadomestictype,forexamplehouse-office,house-shop,etc.;involvingsingle-storeyCatA,BorCbuildings.
Interm
ediate
DM3
• Multi-plotdevelopmentsencompassinghousesupto2storeysonly.• Developmentencompassingasinglehouse.• Alterationsandextensionsinvolvingorcreatingmorethan2storeys.• Roomintheroofconversionscreatingmorethan2storeys.• Demolition/removals(adjpublicaccessinvolved).
NM3
• Development,alterations,extensionsinvolvingsingle-storeyCatAbuildings.• Demolition/removals(adjpublicaccessinvolved).
Low
DL2
• Alterationsandextensionsinvolvingorcreating2storeys.• Roomintheroofconversionscreating2storeys.• Conversionofintegral,attachedanddetacheddomesticgaragestoformapartment(s).• Interioralterationstoflats.• Anylowrisk(DL1)workinvolvingseparatingwallsrelatingtonoise.• Demolitions/removals(noadjpublicaccessinvolved).• Single-storeyextensionsandalterations(conservatories,sunrooms,garages,etc.)withboundaryfireissues.
• Interioralterationsto2storeydwellings.• Neworreplacementfuelstoragetank(s).
NL2
• Minorinternalandexternalalterations,whichdonotaffectmeansofescape.• Demolitions/removals(noadjpublicaccessinvolved).
Low
DL1
• Single-storeyextensionsandalterations(conservatories,sunrooms,garages,etc.)withoutboundaryfireissues.
• Interioralterationstosinglestoreydwellings.• Erectingoralteringretainingwalls.• Alterexistingexternalopenings(windows,doors,patiodoors,Frenchdoors,etc.).• Infillstoexternalwallsandroofs.• Formopeningstoexternalwallsandroofs.• Erectingoralteringwalls,fencinganddecking.
NL1
CategoryA–focusonpropertyprotection
CategoryB–focusonlifesafety;relativelyhighoccupancy,publicaccess,etc. CategoryC–focusonlifesafety;relativelyveryhighoccupancy,publicaccess,etc.ANDlimitedmobilityofoccupants,limitedfamiliaritywithbuilding,non-compliance,etc.
a) Storagebuildingsb) Factorybuildingsc) Industrialunitsd) Agriculturalbuildings
a) Entertainment,includinglicensedbettingoffices,clubs,publichouses,restaurants,cafes,etc.
b) Residentialbuildingsc) Offices
d) Shopse) Assembly,includingswimmingpoolbuildings,
churches/placesofworship,educationalestablishments,librariesopentothepublic,daycentres,healthcentresandsurgeries,etc.
a) Entertainment,includinghalls,conference,exhibitionandleisurecentres,etc.
b) Shops(multi-storeyorseparationissues)c) Residentialcare/hospicesd) Hospitals
e) Shoppingmallsf) Anynondomesticworkinvolvingnon
compliancewithguidance.
2016 LocalAuthorityBuildingStandardsScotland[LABSS]
LABSSProceduralGuidanceonverificationofcertifiedandnon-certifiedroutesforcompliancewiththebuilding
regulations:February201610
Table3.Templateforinternalpeercheckingrates(tobecompletedbyeachverifierbasedonresourcesavailable)
Competencyofchecker Totalprojectrisk Minimuminternalpeerchecking*
Seniorsurveyor Low
Competency:Tobecompletedbyverifier.Forexample,holdsmembershipofprofessionalbody,orcompletedrelevantin-housetraining,andexperiencedatassessingcomplexapplications.
Med
High
Surveyor Low
Competency:Tobecompletedbyverifier.Forexample,holdsmembershipofprofessionalbody,orcompletedrelevantin-housetraining.
Med
High
AssistantorTraineesurveyor Low
Competency:Tobecompletedbyverifier.Forexample,completedrelevantin-housetraining.
Med
High
*Forexample,insertratiosof1:1,1:2,1:5,1:10,1:25,1:50or1:100.
4.ProposedauditingofbuildingwarrantapplicationriskmanagementprocessTopermittransparencyofthebuildingwarrantapplicationriskprocessacrossall32verifiers,itissuggestedthattheresultsbecollatedbyeachverifierintheformatdetailedinTable4.Whereaverifierwishestomakeuseofamoreadvancedriskmanagementprocess,thisoptionwouldbepursuableanditwouldbetheresponsibilityoftheverifiertoevidencesuitableauditingoftheirriskmanagementprocess.Table4.Internalauditreportforriskmanagement
Completedby SystemAdmin SystemAdmin Management Casesurveyor Casesurveyor Management BWreference Riskcategory Riskassessed
followingLABSSPGNEQ001/2016
StructurescheckedfollowingLABSSPGNEQ002/2016
EnergycheckedfollowingLABSSPGNEQ003/2016
Peerchecked(internalorexternal)
15/00001 DL1 ü ü ü ü
15/00002 DL2 ü ü - -
15/00003 DM3 ü ü ü -
15/00004 DM4 ü ü ü ü
15/00005 NL2 ü ü - -
15/00006 NM4 ü ü ü -
15/00007 DH5 ü ü ü ü
15/00008 NH5 ü ü ü ü
15/00009 DL2 ü ü ü ü
15/00010 DL1 ü ü - -
Totals 10 10 100% 100% 70% 50%
2016 LocalAuthorityBuildingStandardsScotland[LABSS]
LABSSProceduralGuidanceonverificationofcertifiedandnon-certifiedroutesforcompliancewiththebuilding
regulations:February201611
LABSSPGNEQ002/2016TheverificationofStructures-Design
Section1.0oftheTechnicalHandbooks1.1PREAMBLEThisguidancenoteisintendedtohighlightthebestpracticeoflocalauthoritiesandtoprovideaframeworkonwhichauthoritiescanaddressequivalenceintheverificationofbuildingstructuredesigns.1.2AIMSTooutlineaconsistentapproachtotheverificationofbuildingstructuredesigns,andtoprovideguidanceforverifiersontheassessmentofnon-certifiedbuildingstructuredesigns.1.3BACKGROUNDItisconsideredthatguidanceonequivalenceinthecheckingofstructuraldesignshouldbebasedonthefindingscontainedintheBREresearchreport“Astudyintothelevelofcheckingofstructuraldesign”,covering:• Theriskclassificationsforprojectsandhowtoassessrisk• Thecompetencerequiredforindividualsassessingcomplianceatdifferentrisklevels• Projectchecklistsforcompliancecheckingofstructuraldesign• Technicalguidancetobereferredtobythoseundertakingcompliancechecking• Flowchartandproceduralguidanceinordertomeettheneedsoftheservicelevelagreements
offeredtothepublicbyBuildingStandards• Proportionatecheckingofnon-certifiedworkonanannualbasis• Examplesoftheuseoftheprocedureincompliancecheckingfordifferentcomplexitiesof
buildingAttheBSD/LABSS/SERstructuralliaisongroupmeetingon19thJuly2013(andalsoatanumberofpreviousmeetingsofthatgroup),SERrepresentativesraisedanissueregardingcommentsfromsomeoftheirCertifiersthata“twotier”systemhasdevelopedforcheckingthestructuraldesignofbuildingwarrantapplicationsinScotland.LABSSrepresentativesatthemeetingwereoftheviewthatasthecertificationprocessisnotmandatory,analternativeassessmentprocessisrequired,andthatthisdoesnotcreatea“twotier”systembutinsteadindicatedanecessaryalternative.Subsequently,theBSDcommissionedresearchfromtheBuildingResearchEstablishment(BRE),askingthemtoinvestigatethelevelofcheckingofstructuraldesign.Aftercirculatingaquestionnairetoall32ScottishVerifiers,andconductinginterviewswith6selectedverifiers,BREissuedtheirreportinApril2014.BREincludedcommentsintheirreportthat:
• “there was a lack of consistency and indeed transparency amongst verifiers to structural
checking”• “there is no evidence that the end products of certified and non-certified approaches were
different”
2016 LocalAuthorityBuildingStandardsScotland[LABSS]
LABSSProceduralGuidanceonverificationofcertifiedandnon-certifiedroutesforcompliancewiththebuilding
regulations:February201612
• “thereisscopetoimprovetheconsistencyofthenon-certifiedapproach”2.SERCERTIFICATION
StructuralEngineersRegistrationLtd(SERLtd.)wasappointedbytheBSDtoadministeraschemeforCertificationofDesign(BuildingStructure).TheSchemewasestablishedasaresultofajointinitiativebytheInstitutionofStructuralEngineersandtheInstitutionofCivilEngineers,andwasdrivenbynewlegislationintroducedinScotland,namelytheBuilding(Scotland)Act2003.
TheActencouragesaholisticoverviewfromdesigntocompletionofanybuildingproject,byenablinganengineerwhoisamemberoftheSchemeasanApprovedCertifierofDesign(BuildingStructures)tocertifythestructuraldesignofbuildingsinScotlandandtoincludeacertificatewiththeapplicationtolocalauthoritiesforbuildingwarrant.
ThecertifyingengineerisresponsibleforensuringthatallaspectsofdesignofthestructureofaprojectsatisfytherequirementsoftheBuilding(Scotland)Regulations2004.Thelegislationalsomakesengineerswhoareresponsibleforbuildingstructuresspecificallyawareoftheirresponsibilitiesanddutiesinthedesign,thusimprovingassuranceofstructuralsafety.
SERhasissuedaSchemeGuideandnumberofGuidanceNotesandTechnicalBulletins.Theseareavailableattheirwebsiteatwww.ser-ltd.com.Ofparticularrelevancetothismatterare:
• SERGuidanceNote2-CertificationofCompliancewiththeBuildingRegulations• SERGuidanceNote4-UseofCertificatesofDesign(BuildingStructures)• SERTechnicalBulletin1-Certificationofcontractordesignedelements• SERTechnicalBulletin2-Guidelinesforcheckingthestructuraldesignofbuildings
TheBSDdocumentProceduralGuidanceonCertificationincludinginformationtobesubmittedwithabuildingwarrantapplicationgivesadviceonthepracticalapplicationofthebuildingstandardssystemwhenanApprovedCertifierisusedonaprojecttopromoteaconsistentapproach.GuidanceonthelevelofinformationonthestructuraldesigntobeprovidedtotheverifierwhentheseaspectsarecoveredbyaCertificateofDesignisincluded.
Section1.9.2oftheBSDpublicationProceduralHandbook(ThirdEdition,Version1.1)statesthatApprovedCertifiersofDesignareresponsibleforspecifiedaspectsofthedesignofbuildingssuchasthestructure.Ifsatisfiedthattheproposeddesignmeetstherequirementsofthebuildingregulations,anApprovedCertifierofDesignmayissueacertificateforsubmissionwiththeapplicationforbuildingwarrant.Certifiersmusthavedueregardforcompliancewiththefullrangeofrelevantbuildingstandardsrequirements,notjustthoseofimmediaterelevancetotheparticularaspect.AstheCertificateofDesignistakenasproofofwhatitpurportstocover,theverifierdoesnotcheckthosematters,althoughsufficientstructuraldetailsandspecificationmustbeprovidedtomeettherequirementsoftheaboveproceduralguidancedocument.Averifiermust,however,checkthatthepersonsigning(theApprovedCertifier)issuitablyqualifiedtoissuetheCertificateofDesigninrelationtothematterscertifiedandthatthecounter-signingfirm(theApprovedBody)isapprovedtoco-ordinatethecertificationoftheseaspects.Thesechecksaremadeusingtheon-linecertificationregisterontheBSDwebsiteatwww.scotland.gov.uk/Topics/Built-Environment/Building/Building-standards.
2016 LocalAuthorityBuildingStandardsScotland[LABSS]
LABSSProceduralGuidanceonverificationofcertifiedandnon-certifiedroutesforcompliancewiththebuilding
regulations:February201613
Theverifierchecksthevalidityofacertificateandmayonlyacceptitif:• thepersonisregisteredasanApprovedCertifieronthedateofsignature;and• thefirmisregisteredasanApprovedBodyonthedateofsignaturebythecertification
coordinator;and• bothareregisteredunderthesameschemewhichisrelevanttotheworkbeingcertified.
Theverifieralsochecksthatthecertificaterelatestothewarrantapplicationorcompletioncertificatesubmissionforexample,buildingaddress,descriptionofworksanddescriptionofstagesareconsistent.Acertificatemayalsobelimitedbythescopeoftheschemeandparticulardesignations.
ACertificateofDesignmustcertifyalltheworkcoveredbythewarrantapplicationoramendmenttowarrantapplication.
ThischeckingalsoappliestotheFormQ(Noticeoffinalisationofdesigndetails)onthefinalisationofstructuraldesign.
3.CHECKINGOFSTRUCTURALDESIGNBYVERIFIERS
Alternatively,structuraldesigncalculationsmaybesubmittedinsupportofabuildingwarrantapplication.Theverifiermustthenreviewthestructuralcalculationsanddesigndrawingssubmitted,andsatisfythemselvesthattheworkforwhichthebuildingwarrantistobegrantedwillcomplywiththeBuildingRegulations(inparticularSchedule5,Regulation9,Sections1.1and1.2),alongwiththerelevantBritishStandardsandStructuralEurocodes.Thiswouldnormallyinvolvecheckingtheinputtocalculations,runningchecksonthedesign(althoughitisacknowledgedthatitmaynotbepractical,intimeorfinancialterms,forverifierstoruntheirowndesignchecks),andacheckofthesubmitteddrawings,toensurethatsufficientstructuralinformationhasbeenprovidedandthattheengineeringdrawingsmatchupwiththe(oftenearlier)architect’sdrawings.AsuggestedsetofguidancenotesforverifiersisattachedasAppendix1.AlistofcriteriafortheassessmentofprojectsisgiveninAppendix2.Thequestionofanonymoussetsofcalculationisworthyoffurtherconsideration.TheProceduralHandbookdoesnotinsistthatdrawingsaresignedbytheirproducer,thereforeitisdifficulttoarguethattheauthorofasetofstructuralcalculationswouldhavetosignhisorherwork.Iftheproducerisnotknown,orifthedesignissubmittedanonymously,thentheverifiershouldgivethesecalculationsmoredetailedscrutiny.Asthecertificationprocessisnotmandatory,certificationcannotbeinsisteduponandtheoptionofacceptingeitheravalidCertificateofStructuralDesignorstructuralcalculationsshouldalwaysbeofferedbyverifiers.Ineithercase,sufficientdetailforreasonableinquirypurposesisrequired,assetoutintheBSDCertificationdocument.The32localauthoritiesinScotlandactasverifiers,butitisunderstoodthatverifiersutilisearangeofstaffinthecheckingstructuralcalculations,forexampletheuseof:• lessexperiencedBuildingStandardsSurveyors(withnoformalcivil/structuralqualifications)• experiencedBuildingStandardsSurveyors(withnoformalcivil/structuralqualifications)• Civil/StructuralEngineersdirectlyemployedbythatCouncil’sBuildingStandardsservice• Civil/StructuralEngineersfromothertechnicalserviceswithinthesameCouncil
2016 LocalAuthorityBuildingStandardsScotland[LABSS]
LABSSProceduralGuidanceonverificationofcertifiedandnon-certifiedroutesforcompliancewiththebuilding
regulations:February201614
• Civil/StructuralEngineersfromaBuildingStandardsserviceatanotherCouncil(withtheprovisothattheyshouldhaveadequateknowledgeandexperienceintherelevantbuildingstructure,notjustdrainageortransportation,forexample)
• Civil/StructuralEngineersfromanexternalfirm(outsourcing)
Thecompetenceofanystaffusedshouldbechecked,forexamplewhetherexperiencedinthetypeofwork,whethermembersofarelevantprofessionalInstitutionandtheirlevelofmembership,includingwhetherCharteredetc.VerifiersmaywishtoconsidertheuseofApprovedBodiesorApprovedCertifiersforexternalchecking.
Ifstructuralcheckingisbeingoutsourcedbywhatevermeans,clearguidanceshouldbegivenastowhatlevelofcheckingisrequired,forexamplecheckingofinputs,calculations,andcompliancewithSections1.1&1.2oftheTechnicalStandardsetc.(seeAppendices1&2).GuidanceisalreadygivenintheSmallBuildingsStructuralGuidance(SBSG).Thisisnolongerbeingupdated,butcontainsusefulinformationofspantablesforfloorjoist,rackingresistanceetc.Inasimilarvein,thevariouspartsofBS8103StructuralDesignofLowRiseBuildingsalsocontainsusefulguidance.BS8103isEurocodecompatible,butdoesnotcovertimberkitconstruction.Itisimportanttonotethatverifiersshouldnot“cherrypick”betweenthevariouspiecesofguidance.TheSBSGwaswrittenforthosewithexpertiseinbuildingdesignandconstruction,butnotnecessarilystructuralengineeringdesign.WheretheconditionsorparametersfalloutsidethescopeoftheSBSG,thenspecialistadviceshouldbesoughtfromapprovedCertifiersofDesign,CharteredEngineersorotherappropriatelyqualifiedpersons.Whenworkingwithcontractordesignedelementswhicharestilltobedesignedatbuildingwarrantstage,itshouldbenotedthatverifiersshouldnotrelyonthirdpartydesigncertificates,forexampleManufacturer’sCertificatesfortrussedrafters,unlesstheyhavesatisfiedthemselvesastothecompetenceofthedesignerandchecker,andtheadequacyofthecheck.Eventhen,theverifierwillhavetosatisfythemselvesthatthedesigncalculationsanddrawingsarecomplete,thatthedesignassumptionsandloadingsareappropriate,andthattheresultsappearreasonable.OnmorecomplexprojectswithContractordesignedelements,stagingmaybeconsidered.4.RISK-BASEDAPPROACHItissuggestedthatarisk-basedapproachwouldbethebestwayforwardforprovidingconsistencyforverifierscheckingstructuralcalculations.Thisassessmentwouldnotnecessarilybebestmirroredbyvalue,butcouldbemetbyconsideringthecomplexityofthewholeof,orpartof,theproject.Examplesofriskinclude:• Buildingtype/complexity/value• Consequencesoffailure(forexamplepublicsafety,financiallossetc.)• Likelihoodoffailure• Roleandcompetencyofdesigner/installer-experiencedinthetypeofwork?Companyknown
toverifier?Goodtrackrecord?• Qualityofdesigndetails/installation• Verificationcheckingactivities• Verificationcheckingcompetency(inhouse/external)• Verificationqualityassurance
2016 LocalAuthorityBuildingStandardsScotland[LABSS]
LABSSProceduralGuidanceonverificationofcertifiedandnon-certifiedroutesforcompliancewiththebuilding
regulations:February201615
SERTechnicalBulletinNo.2Guidelinesforcheckingthestructuraldesignofbuildingsputsforwardguidanceforstructuralchecking.Someofitscontentsmaybeusefulincompilingguidanceforverifiers.SERintroducedtheconceptofaRiskClass,basedontheconsequencesoffailure(RC1=low;RC2=medium;RC3=high).BuildingsarethenallocatedtotheseRiskclasses,forexampleRC1=houses,smallbuildings,minoralterationstofactories&officesetc.,RC2AandRC2BthroughtoRC3=multi-storeybuildings,placesofspecialfirerisk,grandstandsetc.AmodifiedversionoftheSERguidanceispresentedinTable1.ItisconsideredthatRC1shouldbebrokenintotwosubsets(RC1AandRC1B),wherethelowestlevel(RC1A)wouldnotrequireCharteredEngineerinputandcouldthereforebecheckedbyasuitablyqualifiedBuildingStandardsSurveyor,whoisexperiencedinthistypeofwork.Ifrequired,specialistadviceshouldbesoughtfromApprovedCertifiersofDesign,CharteredEngineersorotherappropriatelyqualifiedpersons.Normally,warrantsareallocatedtoSurveyorsbyManagersorTeamLeadersorequivalentseniorstaff.Asectioncouldbeaddedtotheallocationsheettoallowseniorstafftostatethelevelofstructuralcheckingthatisconsideredtoberequired.Theimportanceofhavingtoconsidertheexistingbuildingwhendealingwithextensionsandalterationsshouldbenoted.RiskClassDescription(seeNote1toTable1)RC1 Lowconsequenceforlossofhumanlifeandeconomic,socialorenvironmental
consequences smallornegligibleRC2 Mediumconsequenceforlossofhumanlife,economic,socialorenvironmental
consequences considerableRC3 Highconsequenceforlossofhumanlifeoreconomic,socialorenvironmental
consequences verygreatSimplifiedsummaryforcheckingRC1A BuildingStandardsSurveyor,suitablyqualifiedandexperiencedRC1B EngineerRC2A EngineerRC2B EngineerRC3 Engineer
2016 LocalAuthorityBuildingStandardsScotland[LABSS]
LABSSProceduralGuidanceonverificationofcertifiedandnon-certifiedroutesforcompliancewiththebuilding
regulations:February201616
Table1.Riskclassificationbybuildingtypeandoccupancy
RiskClassification
BuildingTypeandOccupancy
RC1A Houseswithmasonryortimber-framewallsnotmorethantwostoreyswithoutbasementstoreys.Extensions,withmasonryortimber-framewalls,notmorethantwostoreys,tohousesincludinggaragesandoutbuildings.Singlestorey,singleleafbuildingsformingagarageoroutbuildingwithinthecurtilageofadwelling.Houses(seenote2)includingalterationsandextensionstohouses.SmallbuildingsofTypes5to8and13to20describedinSchedule1toRegulation3oftheBuilding(Scotland)Regulations2004(seenote3).Minoralterationstofactories,storagebuildingsorofficeswhichfallswithinthedescriptionoftheRC1riskclassification(seenotes4and5).
RC1B Houses,includingalterationsandextensions.HouseswhicharenotincludedinRC1(seetheTechnicalStandards).
RC2A Hotelsnotexceeding4storeys.Flats,apartmentsandotherresidentialbuildingsnotexceeding4storeys.Officesnotexceeding4storeys.Factories(Class2)notexceeding3storeys.Shopsandenclosedshoppingcentresnotexceeding3storeysoflessthan2000sq.m.floorareaineachstorey.Singlestoreyeducationalbuildings.Assemblybuildings(otherthaneducationalbuildings),entertainmentbuildingsandotherbuildingsaccessibletothegeneralpublicallnotmorethan2storeysandwitheachstoreyareaofnotmorethan2000sq.m.
RC2B Hotels,flats,apartmentsandotherresidentialbuildingsgreaterthan4storeysbutnotexceeding15storeys.Educationalbuildingsgreaterthan1storeybutnotexceeding15storeys.Shopsandenclosedshoppingcentresgreaterthan3storeysbutnotexceeding15storeys.Hospitalsnotexceeding3storeys.Officesgreaterthan4storeysbutnotexceeding15storeys.Assemblybuildings(otherthaneducationalbuildings),entertainmentbuildingsandotherbuildingsaccessibletothegeneralpublicandwitheachstoreyareaofmorethan2000sq.m.butnotmorethan5000sq.m.Opensidedcarparksandstoragebuildings(Class1)morethan6storeys.Grandstandsaccommodatingupto5000spectators.
RC3 Highoccupancymulti-storeybuildings>15storeys.Buildingshavingunconventionalconstructionorinnovativedesignandbuildingconstructionspronetodynamicinstability.AllbuildingsdefinedaboveasRC2AandRC2Bthatexceedthelimitsonareaand/ornumberofstoreys.Grandstandsandsportsarenasaccommodatingmorethan5000spectators.Storagebuildings(Class1),Factories(Class1)andplacesofspecialfirerisk.
Note1:ForbuildingsintendedformorethanonetypeofusetheClassshouldbethatpertainingtothemostoneroustype.
Note2:AhouseisdefinedbyRegulation2oftheBuilding(Scotland)Regulations2004(whicharereproducedinthelistofdefinedtermswhichformAppendixAtotheTechnicalHandbook)asadwellingononeormorestories,eitherdetachedorformingpartofabuildingfromallotherpartsofwhichitisdividedonlyvertically.
Note3:Schedule1listsanumberofbuildingtypeswhichareexemptedfromtherequirementsoftheregulationsotherthanexceptionsalsolistedintheschedule.TheRC1classificationthereforeappliestocertificatesissuedinsupportofbuildingwarrantapplicationsforworksthatfallwithintheexceptioncategory.
Note4:DefinitionsofbuildingtypesandoccupancyaregivenwithintherelevantpartsoftheBuilding(Scotland)Regulations2004.
Note5:RC1Aexcludeshouseswhichareconstructedofskeletalframesoftimber,steeletc.(i.e.“non-traditional”houses),andthosewhosestabilityisachievedbysystemsotherthantimberrackingormasonryshearwalls.Itshouldalsoexcludeunusualorinnovativebuildingsthatfitintothiscategorybutrequirespecialistengineeringinput,forexamplelarge2storeyglazedwalls,largeopenplanlayoutswithstructuralbeams/columnsetc.
2016 LocalAuthorityBuildingStandardsScotland[LABSS]
LABSSProceduralGuidanceonverificationofcertifiedandnon-certifiedroutesforcompliancewiththebuilding
regulations:February201617
5.PROPORTIONATEAUDITINGItisconsideredthatproportionatecheckingshouldbeatooltoaidconsistentreasonableinquiry.Peerreviewwithinconsortiumgroupsmaywellbeperfectlyadequate,similartotheinterconsortiaauditingcarriedoutforlocalauthoritywarrantapplications.EachlocalauthorityshouldconsiderhavingQAproceduresinplacetoensurethatthecheckingdescribedinthisguidanceisbeingundertakenandprocessesfollowed.
2016 LocalAuthorityBuildingStandardsScotland[LABSS]
LABSSProceduralGuidanceonverificationofcertifiedandnon-certifiedroutesforcompliancewiththebuilding
regulations:February201618
APPENDIX1XXXXXXXXXXXBuildingStandardsServiceBuilding(Scotland)Act2003Guidelinesonminimumrequirementswhensubmittingstructuralcalculationsforbuildingwarrantapplications.Structuralcalculations,whicharebeingsubmittedforthepurposeofobtainingabuildingwarrant,shouldbeinaformofareportandbepreparedbyaCivilorStructuralEngineerexperiencedinthetypeofdesignproposed.Thismaybesubmittedintypedorhandwrittenformandmust:- beclear,legibleandaccurate;- haveallpagestitledandnumbered;- providein-textclausestotherelevantBritishStandards/StructuralEurocodesandortext
references;and- containsketchesanddrawings,asrelevant.• Thecalculationsshouldcontainadetaileddescriptionofthebuilding.Thisshouldhighlightthe
followingaspects:(a) Existingstructuralcondition(b) Functionalrequirements(c) Siterequirements(d) Architecturalrequirements
• Thecalculationsshouldprovidealistofcomponentsandshouldhighlightanyspecificdesign
requirementsofthevariousstructuralelements.• AdetailedMethodologyastohowthebuildings/structuralelementshavebeenanalysedand
designedshouldbeprovided.Anaccountofhowthebuildingwillfunctionstructurallytowithstandverticalandhorizontalloadsshouldalsobeprovided.
• ThedesignshouldconformtocurrentandrelevantBritishStandards/StructuralEurocodesand
showcompliancewithTechnicalStandards1.1(DesignLoadings)and1.2(PreventionofDisproportionateCollapse).Referencetospecificstandardsmustbeincludedwithinthetextwheneverrelevant.Thespecificationofmaterialsmustbedetailedinthedocumentandindrawings.
• Abreakdownofallpermanentandimposedhorizontalandlateralloadingmustbeprovided.
ReferencestotherelevantBritishStandards/StructuralEurocodesandotherrelevantdocumentswherecharacteristicloadswereobtainedmustbelistedandreferredtowhereused.Thesitewindloadcalculationsmustbeprovidedwhereapplicable.
• Thestructuralanalysismaybedonemanuallyorbytheuseofcomputersoftware.Analysisby
softwaremustbecheckedandvalidatedbythedesigner.• DesigncalculationsshouldbedoneinaccordancewiththerelevantBritishStandards/
StructuralEurocodes.Thelocationofeachstructuralcomponentsbeingdesignedmustbeshowninadrawingandsketchesoftherelevantdetailsmustbeprovided.Thedesignmusttakeintoaccountthepracticalissuesrelatingtoconstructionandhealthandsafetyissues.
2016 LocalAuthorityBuildingStandardsScotland[LABSS]
LABSSProceduralGuidanceonverificationofcertifiedandnon-certifiedroutesforcompliancewiththebuilding
regulations:February201619
• Detaileddrawingsofthedesignedstructuralcomponentsmustbeprovidedillustratingall
relevantdesigncomponents.Alldrawingsmustbesuitablytitledandallrelevantsupportinginformationandmustbesigned.
• Thedocumentmustcontainallinformationusedinthestructuraldesign.Thiscouldincludea
GeotechnicalInvestigationreport,sitesurveyinformationetc.(EnvironmentalorGeotechnicalSiteInvestigationReportsshouldbesubmittedasahardpapercopyandelectronicformati.e.MicrosoftWordor.PDF).
2016 LocalAuthorityBuildingStandardsScotland[LABSS]
LABSSProceduralGuidanceonverificationofcertifiedandnon-certifiedroutesforcompliancewiththebuilding
regulations:February201620
APPENDIX2CriteriafortheAssessmentofProjects1.WarrantSubmissionScopeofsubmission2.GeneralDesignOverviewandParametersLoadingassessmentOverallstabilityDisproportionatecollapseConversionsStructuralmovementjoints3.ReportsandInvestigationsGroundInvestigationreportsExistingbuildingconditionassessment4Design(PrincipalStructure)MineralconsolidationSub-structure(excludingpiling)PilingEarthretainingstructuresGroundimprovementSuperstructureTies,fixingsandconnections5.Design(BuildingEnvelope)Claddingsystem(includingglazing)Cladding,fixingsandsupports(includingpurlins,sheetingrailsetc.)Claddingmovementjoints6.Design(SecondaryStructure)InternalpartitionsProtectivebarriers7.SpecificationStructuralmaterials/components/fixings8StructuralFireProtectionElementsofstructure(asdefinedbyRegulation2)
2016 LocalAuthorityBuildingStandardsScotland[LABSS]
LABSSProceduralGuidanceonverificationofcertifiedandnon-certifiedroutesforcompliancewiththebuilding
regulations:February201621
2016 LocalAuthorityBuildingStandardsScotland[LABSS]
LABSSProceduralGuidanceonverificationofcertifiedandnon-certifiedroutesforcompliancewiththebuilding
regulations:February201622
LABSSPGNEQ003/2016TheverificationofEnergy-Design
Section6.0oftheTechnicalHandbooks1.1PREAMBLEIntermsofenergy,limitingunnecessaryenergyuseandassociatedcarbondioxideemissionsisahighpriority,andisakeycomponentofgovernmentpolicyonclimatechange,andislikelytocontinuetobesofortheforeseeablefuture.1.2AIMSThisguidancenoteconsidershowbesttoprovideaconsistentapproachtotheverificationofSection6energysubmissions.1.3BACKGROUNDIngeneralterms,foralterations,extensionsorconversionsofbuildings,itisconsideredreasonabletoproposethattheriskassociatedwithabuildingwarrantenergysubmissionisproportionaltothecurrentandtheproposedenergyuseandcarbondioxideemissionsofthebuildingorbuildingsinquestion.Likewise,fornewbuilds,theriskisproportionaltotheproposedenergyuseandcarbondioxideemissionsofthebuildingorbuildings.Additionalconsiderations,suchastheimpactoftheproposeddesignonthehealthandwellbeingofthosewhouseandinteractwithabuildingwillalsorequireconsideration.Assuch,anyriskbasedapproachforverifierscheckingenergysubmissionsrequirestobeunderpinnedmainlybythecategoryofbuildinginvolved,andotherrelevantmodifiersmaythencomeintoplay.2.VERIFICATIONOFENERGYSUBMISSIONS2.1Goodpracticeforcheckingofbuildingwarrantapplications–energyApplicationsforbuildingwarrantscovernewbuild,alterations,extensionsandconversions.IntermsofEnergysubmissions,thereistheoptionofthecertifiedroute(submittingaCertificateofDesignforEnergyundertheApprovedSchemeprocess),orthenon-certifiedroute(submittingsuitableenergy-relatedinformationinsupportoftheapplication).Ofnote,certificationisnotmandatoryandthecurrentsituationislikelytoremainfortheforeseeablefuture.IntermsofSection6Energy,thefollowingapproachesareusedtoshowcompliance:1) Newbuild–DomesticandNon-domestic
InaccordancewithStandard6.1,everybuildingmustbedesignedandconstructedinsuchawaythat:
2016 LocalAuthorityBuildingStandardsScotland[LABSS]
LABSSProceduralGuidanceonverificationofcertifiedandnon-certifiedroutesforcompliancewiththebuilding
regulations:February201623
a) theenergyperformanceisestimatedinaccordancewithamethodologyofcalculationapprovedunderregulation7(a)oftheEnergyPerformanceofBuildings(Scotland)Regulations2008and
b) theenergyperformanceofthebuildingiscapableofreducingcarbondioxideemissions.
Forthemajorityofnewbuildings,Standard6.1hasthegreatestinfluenceondesignforenergyperformance.However,Standards6.2to6.6alsorecommendbenchmarkandbackstoplevelstobeachievedforindividualelementsorsystems.Standard6.6impactsonthecompliancecalculationinStandard6.1byincludinganelementofdesignassessmentinrespectofsolargain/overheating.
DomesticTheStandardAssessmentProcedureforEnergyRatingofDwellings(SAP)isthecalculationtoolused.Theobjectiveisthatthecalculatedcarbondioxideemissions(measuredinkg/m2/year)fortheproposeddwelling(thedwellingemissionsrate,DER),shouldbelessthanorequaltothetargetcarbondioxideemissionsfora‘notionaldwelling’(thetargetemissionsrate,TER).AnalternativewayofmeetingStandard6.1whichavoidstheuseofthecalculationmethodologyistodesigntothesetofvaluesusedforthe‘notionaldwelling’.
Non-domesticTheSimplifiedBuildingEnergyModel(SBEM)isacalculationtoolwhichmaybeused.Theobjectiveisthatthecalculatedcarbondioxideemissions(measuredinkg/m2/year)fortheproposedbuilding(thebuildingemissionrate,BER)shouldnotexceedthosewhicharecalculatedfora‘notionalbuilding’(thetargetemissionsrate,TER),whichhasthesamesizeandshape.Alternativecalculationtoolsmaybeused(suchasdynamicsimulationmodelling,DSM),particularlywherethebuildingisconsideredtobeacomplexdesign.
2) Alterations,extensionsandconversions
Alterations,extensionsorconversionsofbuildingsdonotattractStandard6.1(carbondioxideemissions),insteadfollowingtheelementalroutesetoutinStandards6.2to6.6and6.10,fortheperformanceofthebuildinginsulationenvelopeandfixedbuildingservices.However,useofthecarboncompliancemethodologymaybeanoptioninsomesuchprojectswheregreaterflexibilityisneededandthereissufficientinformationontheexistingbuilding.Forconversions,Standards6.2to6.6canbemetasfarasisreasonablypracticable.
2.1.1CertifiedEnergydesignTheBSDdocument‘ProceduralGuidanceonCertificationincludinginformationtobesubmittedwithaBuildingWarrantApplication’providesguidancetothosemakingapplicationstolocalauthoritiesforabuildingwarrantundereithertheBREorRIAS-EnergyDesignCertificationSchemes.Inparticular,AnnexB(producedjointlybyBREandRIAS)aimstoencourageacommonapproachtothesupplyofinformationacrossallofthe32verifiers,andissummarisedasfollows:1) Ofnote,aCertificateofDesignforEnergymustaddressallpartsofSection6relevanttothe
applicationitaccompanies.Thiswillincludeanycalculationsundertakentodemonstratetheperformanceofthebuildinginsulationenvelopeandfixedbuildingservices.Inallrespects,theinformationthatshouldbeprovidedaspartofthebuildingwarrantapplicationwillbeidenticalwhetheraSection6(Energy)Certificateisbeingusedornot.
2016 LocalAuthorityBuildingStandardsScotland[LABSS]
LABSSProceduralGuidanceonverificationofcertifiedandnon-certifiedroutesforcompliancewiththebuilding
regulations:February201624
2) Anyapplicationmustcontainsufficientinformationtoallowtheverifiertoundertakemeaningfulsiteinspections.Allapplicationsshouldbeaccompaniedbygeneralarrangementdrawings,including:• aplanofthefoundation,eachfloorandanyroof• sectionsthroughthebuilding• anelevationofeachfaceofthebuilding
Togetherwithsuchinformationasmayberequiredtoidentifyandconfirmtheinputstoenergycalculationssuchas:• theconstructionandthermalperformanceofthebuildingenvelope;• thespecificationandperformanceofallfixedbuildingservicesinstallations(heating/cooling,
hotwater,lightingandventilation),includingequipmentefficienciesandsystemcontrols;• detailsofanylowcarbonequipment,suchasrenewableenergyandmicro-generation
systems;and• detailsofanymethodsemployedtocontrolorbenefitfromsolargain.
3) Notalloftheinformationaccompanyinganapplicationneedbesubmittedintheformofplans.
Theproceduralregulationsallowforinformationalsotobeprovidedintheformofreportsorschedules.
4) WhenaSection6(Energy)Certificateissupplied,theverifierisnotrequiredtoreviewtheenergycalculations,reportsandothersupportinginformationsuppliedinsupportofthebuildingwarrantapplication.Theverifierwill,however,checktoensurethatsufficientinformationisprovidedtoallowverificationofworkduringtheconstructionphaseandonsubmissionofaCompletionCertificate.Accordingly,aswithanyotherapplication,theverifierretainstheopportunitytoaskforfurther,relevantinformationinthisrespect.
WherecontradictionsareidentifiedwithinasubmissioncoveredbyaSection6(Energy)Certificate,theverifierwillreferthesubmissiontotheSchemeProviderforinvestigation.
2.1.2Non-certifieddesignFornon-certifiedEnergysubmissions,ratherthanhaveastandalonechecklist,verifierstendtorelyonthegeneralguidanceapplicabletobuildingwarrantapplications,asdetailedintheProceduralandTechnicalHandbooks.Forconsistencyandastandardisingofrequirements,itissuggestedthattheInformationChecklistusedbyCertifiersofDesignforEnergybeadoptedbyverifiersfornon-certifieddesign.Theinformationrequiredispresentedin‘ProceduralGuidanceonCertificationincludinginformationtobesubmittedwithaBuildingWarrantApplication’intheformofachecklistandisreproducedinTable1.ThechecklisthasbeenadaptedtoclarifythesuggestedcheckingfordifferentEnergysubmissions.TherecommendedcompetencyofBuildingStandardsSurveyors,andsamplingrates,forcheckingnon-certifiedSection6Energysubmissions,encompassingnew-buildSAPandSBEM,andexistingsituations(alterations,extensionsandconversions),ispresentedinSection2.2.
2016 LocalAuthorityBuildingStandardsScotland[LABSS]
LABSSProceduralGuidanceonverificationofcertifiedandnon-certifiedroutesforcompliancewiththebuildingregulations:February2016 25
Table1.ChecklistforverifyingSection6Energysubmissions
Element InformationtobecheckedNewbuild Existing
LABSSSAPChecklist
LABSSSBEMChecklist Extensions Alterations Conversions
Constructionincludingexternalenvelope
• Adescriptionofthebuildupoftheconstruction. ü ü ü ü ü• Repeatingthermalbridgingcalculationsforallareasofdifferingconstruction:U-values(W/m²K) ü ü ü ü ü• Non-repeatingthermalbridgingatjunctions:ψ-values(psi)(W/mK)ordefaulty-values(W/m2K) ü ü - - -• Thermalcapacityoftheconstructionelements:κmvalues(kappa-m)(kJ/m²K) ü ü - - -• Formanufacturedelements,suchasdoors,windowsandglazing,confirmationofU-values,framefactorsandanyotherrelevantperformanceinformation. ü ü ü ü ü
• Whereapplicable,acompensatoryheatlosscalculation. - - * - *• Intendedinfiltrationrateforenvelope,asusedintheenergycalculations. ü ü - - -
Heatingandhotwater
• Generaldescriptionofheatingsystem,includingdistributionsystem,heatemittingdevicesandcontroldevicesandancillarycomponents(suchaspumps,valvesandinsulation).Specificationofcomponentsandperformance.Requirementsforlabelling,commissioningandoperation.Providemanufacturersinformationwhereproductsspecified.
ü ü * * *
Ventilation • Generaldescriptionofventilationsystem,includingdetailsoffanunits,distributionductwork,controlsandancillarycomponents(suchasterminalsandinsulation).Specificationofcomponentsandperformance.Requirementsforlabelling,commissioningandoperation.Providemanufacturersinformationwhereproductsspecified.
ü ü * * *
Cooling • Generaldescriptionofcoolingsystemincludingdetailsofchillerunits,pipe/ductwork,controlsandancillarycomponents(suchasterminals,valves,pumpsandinsulation).Specificationofcomponentsandperformance.Requirementsforlabelling,commissioningandoperation.Providemanufacturersinformationwhereproductsspecified.
ü ü * * *
Fueltype • Confirmationoffuel(s)used,togetherwithmeteringprovisions,whereapplicable. ü ü * * *Renewableandmicrogeneration
• Beforeconstructionstarts,thetechnical,environmentalandeconomicfeasibilityofhigh-efficiencyalternativesystems,ifavailable,isconsideredandtakenintoaccount(seeGuidanceleafletConsiderationofhigh-efficiencyalternativesystemsinnewbuildings).
ü ü - - -
• Detailsofanylowcarbonequipment,suchasrenewableenergyandmicro-generationsystems.Generaldescriptionofsystem,specificationofcomponentsandperformance,requirementsforlabelling,commissioningandoperation.Wherespecificsystemsspecified,providemanufacturer’sinformationtoconfirmperformancetogetherwithanyreportsnecessarytosubstantiateassertedperformance(forexample,groundconditions/boreholereportswhereagroundsourceheatpumphasbeenspecified).
ü ü * * *
Lighting • Detailoflightingsystem–luminaires,lampsandcontrolsystems,includingtype,dispositionandefficacyoflamps/luminaires. ü ü * * *
Shading • Detailsoforientationandanyobstructions(whereknown)andanymethodsemployedtocontrolorbenefitfromsolargain,usedwithinassessmentofbuildingenergyperformance. ü ü * * *
Performancetesting
• Noteanypost-completionperformancetestingexpected(e.g.airtightness)tosubstantiateassertionsmadewithintheEnergyCalculations.Provideabriefmethodstatementforsuchtests(informationandsourcesareprovidedinguidancewithinHandbooks).
ü ü - - -
Finalising/handover
• Detailsofanyrelevantcommissioningofbuildingservices(asper6.7ofHandbooks),writtenInformation(asper6.8),Energyperformancecertificates(asper6.9)andmetering(asper6.10). ü ü * * *
*=ifapplicable.LABSSSAPandSBEMChecklistsareavailablefordownloadfromtheLABSSwebsiteathttp://www.labss.org/
2016 LocalAuthorityBuildingStandardsScotland[LABSS]
LABSSProceduralGuidanceonverificationofcertifiedandnon-certifiedroutesforcompliancewiththebuildingregulations:February2016
26
2.2Checkingnon-certifiedSection6Energysubmissions
2.2.1Competency
Inthefollowingdiscussionregardingcompetency,thetitleBuildingStandardsSurveyorisusedgenericallytorefertothefirstprofessionalgradeforBuildingStandardsstaff.However,dependingonthegradingsystemsusedbyindividualverifiers,itmaybeappropriatetoencompassAssistantorTraineeBuildingStandardsSurveyorswithinthiscategory.Ingeneralterms,thecheckingSection6Energysubmissionsmaybesummarisedas:• SAP-giventherelativelystraight-forwardSAPcalculation,andthefamiliaritygainedbyBuilding
StandardsSurveyorsfrequentlydealingwithdomesticnewbuilds,thecheckingofSAPcalculationsisnotconsideredtobetooonerous.
• SBEM-forrelativelystraight-forwardnondomesticbuildings,withrelativelysimplezoning,
heatingandventilationsystems,andlightingsystems,thecheckingofnewbuildSBEMsubmissionscanbereadilyachievedbyBuildingStandardsSurveyorsachievingLevel1competencydetailedinTable2.Issuesmayarisewhenthecomplexityofthenondomesticbuildingincreases,suchascomplexzoning,oramultitudeofheating,ventilationandlightingsystemsandassociatedcontrols(see2.2.3).
• Alterations,extensionsandconversionsofexistingbuildings-giventheextensiveexperienceof
processingbuildingwarrantsrelatingtoalterations,extensionsandconversions,thecheckingtheSection6Energy-relatedelementsofthesesubmissionsbyBuildingStandardsSurveyorsisnotconsideredtobetooonerous.
However,toensureaconsistentapproachnationwide,itisrecommendedthatBuildingStandardsSurveyorscheckingSection6EnergysubmissionsmeettheminimumLevel1competencyinTable2.
Table2.SuggestedcompetencyforEnergysubmissions
Competency
Domestic-Newbuild
SAP
NonDomestic-NewbuildSBEM/DSM
DomesticandNonDomestic-Alterations,extensionsand
conversions
Increasingcomplexityè
1) BuildingStandardsSurveyor/Energycheckerforverifier
1) SAPtraining2) Familiaritywithand
useofLABSSSAPDataVerificationandCompletionChecklist
1) SBEMtraining2) Familiaritywithanduseof
LABSSSBEMDataVerificationandCompletionChecklist
1) TrainingonTechnicalHandbook–Energy
2) Forextensions,familiaritywithanduseofCompensatoryHeatLosscalculations
2) BuildingStandardsSurveyor/Energymentorforverifierorconsortium
1) SAPtraining2) Familiaritywithand
useofLABSSSAPDataVerificationandCompletionChecklist
3) Advancedtraining
1) SBEMtraining2) Familiaritywithanduseof
LABSSSBEMDataVerificationandCompletionChecklist
3) Advancedtraining
1) TrainingonTechnicalHandbook–Energy
2) Forextensions,familiaritywithanduseofCompensatoryHeatLosscalculations
3) Expert–externalpeerreview
1) AccreditedCertifierofDesignforEnergy
1) AccreditedCertifierofDesignforEnergy
2) Expertiseatdynamicsimulationmodelling(DSM)whenapplicabletobuildingwarrantapplication
1) AccreditedCertifierofDesignforEnergy
2016 LocalAuthorityBuildingStandardsScotland[LABSS]
LABSSProceduralGuidanceonverificationofcertifiedandnon-certifiedroutesforcompliancewiththebuildingregulations:February2016
27
2.2.2Checkingprocess
TherecommendedcheckingprocessforSection6EnergysubmissionsispresentedinTables3and4.
Table3.Checkingprocessfornon-certifiedSection6Energysubmissions
Section6Energysubmissions
Checkingprocess Recommendedcheckingrateswithinanindividualbuildingwarrantapplication
NewbuildSAP AsperTable1andtheLABSSSAPDataVerificationandCompletionChecklist,whichcanbedownloadedfromtheLABSSwebsite.
• AllsingleplotSAPorSBEMsubmissionsreceivefullchecksandasamplingregimebeusedformulti-plotsites.
• SuggestedsamplecheckingratesarepresentedinTable4.
• Intermsofmulti-plotsites,astheexperienceandcompetencyoftheSection6Energyassessorincreases,therateofcheckingbytheverifierdecreases.
NewbuildSBEM AsperTable1andtheLABSSSBEMDataVerificationandCompletionChecklist,whichcanbedownloadedfromtheLABSSwebsite.
Existingalterations,extensionsandconversions
AsperTable1.
Table4.SuggestedsamplingcheckingratesforEnergysubmissions
Competencyofsubmitter
Domestic–Newbuild
SAP
NonDomestic–NewbuildSBEM
DomesticandNonDomestic-Alterations,extensionsand
conversionsSingleplot Multi-plot Singleplot Multi-plot Singleplot Multi-plot
1) Firsttime/notrackrecord Fullcheck
Eachhousetypeandminimum1in5
Fullcheck
Eachuniquebuildingandminimum1in5
Fullcheck
Eachuniquebuildingandminimum1in5
2) Experienced/acceptabletrackrecord
Fullcheck
Eachhousetypeandminimum1in10
Fullcheck
Eachuniquebuildingandminimum1in10
Fullcheck
Eachuniquebuildingandminimum1in10
3) Highlyexperienced/noissueseveridentified
Fullcheck
Eachhousetypeandminimum1in25
Fullcheck
Eachuniquebuildingandminimum1in25
Fullcheck
Eachuniquebuildingandminimum1in25
2.2.3Peerreviewing
Section6Energysubmissionswillrequiretobepeerreviewedifapeerreviewisallocatedtothebuildingwarrantapplicationviariskmanagementprocess.WhereabuildingwarrantapplicationwithaSection6Energysubmissionhasbeenallocatedapeerreviewaspartoftheriskmanagementprocess,itisrecommendedthattheBuildingStandardsSurveyorundertakingthepeerreviewofthesubmissionalsomeetstheminimumLevel1competencysetoutinTable2.
2016 LocalAuthorityBuildingStandardsScotland[LABSS]
LABSSProceduralGuidanceonverificationofcertifiedandnon-certifiedroutesforcompliancewiththebuildingregulations:February2016
28
Verifiersareencouragedtoidentifyatleastonein-housesurveyortoactasanEnergymentor,toguideandadviseothersurveyorsonthemorecomplexSection6Energyissues.TherecommendedLevel2competencyofanEnergymentorisdetailedinTable2.Whereaverifierisunabletoidentifyasuitablein-houseEnergymentor,arrangingaccesstoEnergymentorswithinthelocalconsortiumcouldformasuitablealternative.TherecommendedapproachtoexternalpeerreviewingofSection6EnergysubmissionsisdetailedinTable5.
Table5.Externalpeerreviewing
Section6Energysubmissions
Externalpeerreviewingcomments
NewbuildSAP ItisconsideredunlikelythataSAPsubmissionwouldrequiretobesubmittedforexternalpeerreview,though,ifrequired,therecommendedcompetencyforanexternalpeerreviewisdetailedinTable3.Asamatterofcourse,itisrecommendedthattechnicalissuesarisingfrommorecomplexSAPsubmissionsaresharedatlocalconsortiumandLABSSlevels,toensureconsistencyofapproachatanationallevel.
NewbuildSBEM Issueswithverifierexpertisemayarisewhenthecomplexityofthenondomesticbuildingincreases,suchascomplexzoning,oramultitudeofheating,ventilationandlightingsystemsandassociatedcontrols.ItisconsideredgoodpractiseforeachverifiertoidentifythelevelofSBEMsubmissionwhichisbeyondtheleveloflocalexpertise.Insuchinstances,theverifierwouldensureaccesstosuitableexternalSBEMexpertise,forexamplewithintheirlocalconsortiumorviaanexternalaccreditedexpert.
Alterations,extensionsandconversionsofexistingbuildings
ItisconsideredunlikelythataSection6Energysubmissionforalterations,extensionsandconversionswouldrequiretobesubmittedforexternalpeerreview,though,ifrequired,therecommendedcompetencyforanexternalpeerreviewisdetailedinTable3.Asamatterofcourse,itisrecommendedthattechnicalissuesarisingfrommorecomplexEnergysubmissionforalterations,extensionsandconversionssubmissionsaresharedatlocalconsortiumandLABSSlevels,toensureconsistencyofapproachatanationallevel.
2.2.4Recommendationsforfutureimprovements
Whilstthecheckingprocessfornon-certifiedSection6EnergysubmissionsintermsofSAPandexistingalterations,extensionsandconversionsisrelativelystraightforward,forSBEMsubmissions,thecheckingprocesscanbeproblematicduetoalackoftransparencywithinasubmissionandalackofconsistencyofdatapresentationbetweenthedifferentSBEMpackages.AsanadditionaloutcomefromtheEnergyEquivalenceGroup,itisrecommendedthatdiscussionbeheldwithprovidersofSBEMpackages,toencouragestandardisationoftheformatoftheSBEMoutputsandtobetterhighlightfeaturesthatrequiretobeinspectedbytheverifiers.2.3SummaryfortheverificationofSection6energysubmissions
AnoverviewsummarisingtherecommendedequivalenceprocessforSection6energysubmissionsispresentedintheflowchartinFigure1.
2016 LocalAuthorityBuildingStandardsScotland[LABSS]
LABSSProceduralGuidanceonverificationofcertifiedandnon-certifiedroutesforcompliancewiththebuildingregulations:February2016
29
Figure1.FlowchartforverificationofSection6Energysubmissions
Section6Energysubmission
Non-certified
Buildingwarrantapplicationriskassessedwhenreceived–peercheckingallocated,ifrequired.
Section6EnergyCertificate
CheckcertificateonBSDwebsite,applydiscountandrecord
inUNI-form
Checksubmissioncontainssufficientinformationtoallowreasonableinquirysiteinspections.
Reportanycontradictionsinsubmissionto
schemeprovider.
Buildingwarrantapplication
approvedorrejected.
Whererequiredbyriskmanagement,applicationispeerchecked(see2.2.3).
SAP–Newbuild
SBEM-Newbuild
Alterations,extensionsandconversions
1)SubmissionassessedasperTable1andtheLABSSSAPDataVerificationandCompletionChecklist.
2)SamplingratesasperTable4.
3)Checksubmissioncontainssufficientinformationtoallowsiteinspections.
1)SubmissionassessedasperTable1andtheLABSSSBEMDataVerificationandCompletionChecklist.
2)SamplingratesasperTable4.
3)Checksubmissioncontainssufficientinformationtoallowsiteinspections.
1)SubmissionassessedasperTable1.
2)SamplingratesasperTable4.
3)Checksubmissioncontainssufficientinformationtoallowsiteinspections.
Ifanyerrorsoromissionsareidentified,raiseinreporttoapplicantoragent.
Uponreceipt,checkrevisions.Repeatprocessuntilsubmissioncomplies.
Noerrorsoromissionsidentified.
2016 LocalAuthorityBuildingStandardsScotland[LABSS]
LABSSProceduralGuidanceonverificationofcertifiedandnon-certifiedroutesforcompliancewiththebuildingregulations:February2016
30
2.4Casestudies
ExamplesofapplyingtheriskmanagementandenergyequivalenceprocesstoDomesticandNonDomesticbuildingwarrantsubmissionsarepresentedinAppendixA.
2.5PromotingCertificationforEnergy
Onthebasisoftheinformationpresentedinthisdocument,theopportunitiesforandfocusonpromoting/encouragingcertificationofdesignforenergycanbesummarisedaspresentedinTable6.
Table6.Encouragingcertificationofdesign–Energy
Submission Domestic Non-domestic
NewbuildSAP
Comments:Consideredtoberelativelystraightforward,withahighlevelofSAPexpertiseavailablewithinLAs.Externalexpertise:Considerednoneedtouseexternalcheckingexpertise.Focus:
PromoteEnergyCertificationforfirsttime
SAPsubmissions,toreducefaultsandspeed
upprocessing.
Na
NewbuildSBEM Na
Comments:Consideredberelativelydifficulttocheckforcomplexbuildings(e.g.Nondomestichighrisk,NH1toNH4inTable3),duetowidevarietyofbuildingservicesandnon-standardpresentationsofcalculation.Externalexpertise:LevelofSBEMexpertisevariablewithinLAs,assurveyorsnotexposedtoSBEMcalculationsasfrequentlyasSAP.WhereexpertiseisnotavailableinternallytoaLA,certificationistypicallysought.Focus:
PromoteEnergyCertificationforcomplex
buildings(complexbuildingdesign,and
complexheatingandventilationsystems).
Alterations,extensionsandconversions
Comments:Consideredtoberelativelystraightforward,duetoahighlevelofexperienceandexpertiseavailablewithinLAs.Focus:
Nochangefromcurrent
Comments:Checkingismoreonerousthanthatfordomestic,butisfullyachievable,duetoahighlevelofexperienceandexpertiseavailablewithinLAs.Focus:
Nochangefromcurrent
2016 LocalAuthorityBuildingStandardsScotland[LABSS]
LABSSProceduralGuidanceonverificationofcertifiedandnon-certifiedroutesforcompliancewiththebuildingregulations:February2016
31
APPENDIXA–CASESTUDYEXAMPLES
Example1-Newbuilddomestic
Proposal Erecta5apartmentsinglestoreyhouse.Building/userisk DM3(DomesticMedium3,Developmentencompassingasinglehouseupto2
storeys(seeLABSSPGNEQ001/2016-Riskmanagementintheverificationofbuildingwarrantsubmissions).
Additionalrisk(s)verifyingdesign
None.
Casesurveyor Juniorsurveyor-Level1Energycompetency(seeTable2)PeercheckingrateforDomesticMediumRisksetat1:2byverifier(seeLABSSPGNEQ001/2016-Riskmanagementintheverificationofbuildingwarrantsubmissions).
Experienceofenergyassessor/submitter
Experienced/acceptabletrackrecord(seeTable4).
Riskmodifier None.Energysubmissioncheckbycasesurveyor
AsperTable1andLABSSSAPDataVerificationandCompletionChecklist(seeTable3).Fullcheck,assingleplot(seeTable4).
Peercheck No–unlesspeercheckallocatedbyverifierforthecasesurveyor(inorderforcasesurveyortoachieveapeercheckrateof1:2forDomesticMediumRisk).
Example2-Newbuilddomestic
Proposal 100plotdevelopmentof5housetypesand3flattypesBuilding/userisk DM4(DomesticMedium4,Multi-plotdevelopmentencompassingflatsmore
than2storeys(allorinpart)(seeLABSSPGNEQ001/2016-Riskmanagementintheverificationofbuildingwarrantsubmissions).
Additionalrisk(s)verifyingdesign
None.
Casesurveyor Experiencedsurveyor–Level1Energycompetency(seeTable2)PeercheckingrateforDomesticMediumRisksetat1:5byverifier(seeLABSSPGNEQ001/2016-Riskmanagementintheverificationofbuildingwarrantsubmissions).
Experienceofenergyassessor/submitter
Nopreviousexperience/trackrecord(seeTable4)
Riskmodifier None.Energysubmissioncheckbycasesurveyor
AsperTable1andLABSSSAPDataVerificationandCompletionChecklist(seeTable3).Multi-plotsamplingcheckingrateduetoexperienceofassessor/submitter–checkeachhousetypeandminimumof1in5(seeTable4).
Peercheck No–unlesspeercheckallocatedbyverifierforthecasesurveyor(inorderforcasesurveyortoachieveapeercheckrateof1:5forDomesticMediumRisk).
2016 LocalAuthorityBuildingStandardsScotland[LABSS]
LABSSProceduralGuidanceonverificationofcertifiedandnon-certifiedroutesforcompliancewiththebuildingregulations:February2016
32
APPENDIXA–CASESTUDYEXAMPLES(continued)
Example3–Existingsituation-extension
Proposal Erectasinglestoryextensiontoahousetoformasunroom.Building/userisk DL2(DomesticLow2,Single-storeyextensionsandalterations(conservatories,
sunrooms,garages,etc.)withboundaryfireissues(seeLABSSPGNEQ001/2016-Riskmanagementintheverificationofbuildingwarrantsubmissions).
Additionalrisk(s)verifyingdesign
None.
Casesurveyor Experiencedsurveyor–Level1Energycompetency(seeTable2)PeercheckingrateforDomesticHighRisksetat1:25byverifier(seeLABSSPGNEQ001/2016-Riskmanagementintheverificationofbuildingwarrantsubmissions).
Experienceofenergyassessor/submitter
Experienced/acceptabletrackrecord(seeTable4).
Riskmodifier None.Energysubmissioncheckbycasesurveyor
AsperTable1(seeTable3).Fullcheck,assingleplot(seeTable4).
Peercheck No–unlesspeercheckallocatedbyverifierforthecasesurveyor(inorderforcasesurveyortoachieveapeercheckrateof1:25forDomesticLowRisk).
Example4-Newbuildnondomestic
Proposal Erect2storeyresidentialcarehome.Building/userisk NH5(NonDomesticHigh5,Development,alterations,extensionsinvolving
multi-storeyCatBorCbuildings(seeLABSSPGNEQ001/2016-Riskmanagementintheverificationofbuildingwarrantsubmissions).
Additionalrisk(s)verifyingdesign
Complexheatingsystemsandcontrols.
Casesurveyor Experiencedsurveyor–Level1Energycompetency(seeTable2)PeercheckingrateforDomesticHighRisksetat1:1byverifier(seeLABSSPGNEQ001/2016-Riskmanagementintheverificationofbuildingwarrantsubmissions).
Experienceofenergyassessor/submitter
Highlyexperienced(AccreditedCertifierofDesignforEnergy)(seeTable4).
Riskmodifier Yes-duetocomplexheatingsystemsandcontrols.Energysubmissioncheckbycasesurveyor
AsperTable1andLABSSSBEMDataVerificationandCompletionChecklist(seeTable3).Fullcheck,assingleplot(seeTable4).
Peercheck Yes–dueto1:1checkingratiosetbyverifier.Alsopeercheckingrequiredasriskmodified.Ifinsufficientpeercheckingexpertiseavailableinternallytoverifier,accesstoexternalSBEMexpertisetobearranged,forexamplewithinlocalconsortiumorviaanexternalaccreditedexpert(seeTable5).
2016 LocalAuthorityBuildingStandardsScotland[LABSS]
LABSSProceduralGuidanceonverificationofcertifiedandnon-certifiedroutesforcompliancewiththebuildingregulations:February2016
33
LABSSPGNEQ004/2016
TheverificationofElectricalInstallationsSection4.5oftheTechnicalHandbooks
1.1PREAMBLE
Inrelationtoelectricalsafety,itsimportanceinthebuildingstandardssystemisrecognisedthroughtheBuilding(Scotland)Act2003.Insodoing,theaimisthattheowner(relevantperson)shouldappointanApprovedCertifierofConstruction(ACC)toundertakeallelectricalinstallationstoBS7671andissueaCertificateofConstructionconfirmingcompliancewithbuildingregulations.However,giventhenon-mandatorystatusofthecertificationschemes,inpractice,notallelectricalinstallationsareundertakenorsupervisedbyanACC.1.2AIMS
ThisguidanceseekstoensuretheaimsoftheBuilding(Scotland)Act2003andtheaimsoftheCertifierofConstructionprocessarebeingfulfilled.1.3BACKGROUND
AtBSD/LABSS/CertificationSchemeProvidersliaisonmeetings,concernswereraisedregardingaperceivedlackofconsistencyintheapproachofverifiers,bothintermsofwhatconstitutes‘reasonableinquiry’andwhatconstitutes‘equivalency’inrelationtothelevelofcheckbeingundertakenwithregardstoelectricalinstallations.
2.RECOMMENDEDOPTIONSFORACHIEVINGEQUIVALENCE
Thisguidancenoterecommendsadoptingariskbasedapproachtodeterminingtheextentofreasonableinquirybyaverifier,basedonwhoisundertakingtheinstallation.Thedocumentsuggeststherearefourrisklevelsasoutlinedbelow.Risklevel1-installationsundertakenbyanACCwhoiscertifyingtheelectricalinstallation.AsexplainedinSection1.3,itisrecommendedthatverifiersshouldbeactivelypromotingthisoptiononthebasisoftheaddedvaluethisbringstothecomplianceagenda.ItisrecognisedthatanACCwillconsidertheimpactthattheconstructionoftheelectricalinstallationhasonallrelatedfunctionalbuildingstandards.SuggestedreasonableinquiryinsuchcaseswillbelimitedtocheckingthevalidityoftheCertificateofConstruction.Risklevel2-installationsundertakenbyanelectricianwhoisregisteredwithNICEIC,amemberofSELECToranequivalentorganisationaccreditedbyUKAStoconductinspectionsorprovidecertificationservices(ISO/IEC17065orISO/IEC17020:2012).Suggestedreasonableinquiryinsuchcasesmayinvolvesomelevelofinspection,primarilyinrelationtotheimpactoftheelectricalinstallationonrelatedstandardsandassessingtheBS7671information.Risklevel3-installationsundertakenbyotherelectricianwhofallsoutwith1and2above,whodemonstratecompetencethroughsubmissionofacompletedchecklist(seeAppendixA).SuggestedreasonableinquiryinsuchcasesmayinvolvesomelevelofinspectionoftheelectricalinstallationandassessingtheBS7671information,inadditiontothesatisfactorycompletionofthechecklist.
2016 LocalAuthorityBuildingStandardsScotland[LABSS]
LABSSProceduralGuidanceonverificationofcertifiedandnon-certifiedroutesforcompliancewiththebuildingregulations:February2016
34
Risklevel4-installationsundertakenbysomeoneotherthanasdescribedin1,2or3above.SuggestedreasonableinquiryinsuchcasesshouldinvolvesomelevelofinspectionoftheelectricalinstallationandrequirestheinstallationtobeinspectedandsignedoffbyanACCoranelectricalcontractorcertifiedbyaUKASISO/IEC17065accreditedcertificationbody.ThefourrisklevelsoutlinedabovearefurtherclarifiedintabularforminAppendixBandbytheprovisionofaflowchartinAppendixC.Indetermining‘reasonableinquiry’ingeneral,itisemphasisedthatitisnottheverifiers’roletoinspectallmaterialsandworkoneverybuildingsite.Tothisend,owners/clientsshouldbereminded/advisedthattheyultimatelycarryresponsibilityforcompliancewiththemandatoryfunctionalstandards.Notes:a) Whereaverifieristoinspectanelectricalinstallation,theinspectionmustbeundertakenby
suitablyqualifiedandexperiencedstaff.TrainingistobeasprovidedonanongoingbasisbySELECT/NICEIC.
b) Forauditingpurposes,theverifiershouldhaveinplaceariskprotocollinkedtotraining/competencies.
3.IDENTIFIEDNONCOMPLIANCE
RiskLevel1-asinthecaseofallworkcoveredbyanyofthecertificationschemes,theverifierhasnoremittoquestiontheinstallationwiththeACC.Where,however,faultsarefound,reportedorevensuspected,theverifiershouldreportthesetotheSchemeProvider.RiskLevel2-fordefectsintheelectricalinstallationfoundorsuspectedpre-completion,acceptanceshouldberaisedwiththeagent/client,asisthecasewithotherdefects.Fordefectsintheelectricalinstallationreportedfollowingacceptanceofacompletioncertificate,theverifiermaysuggesttotheagent/applicantthattheyreportthemattertotherelevantcertificationortradebody,astheyhaveinvestigativeandremedialpowersundertheirschemes.RiskLevel3&4-fordefectsintheelectricalinstallationfoundorsuspectedpre-completion,acceptanceshouldberaisedwiththeagent/client,asisthecasewithotherdefects.Fordefectswithanelectricalinstallationreportedfollowingacceptanceofacompletioncertificate,thereisnorecoursetoacertification/tradebodytoaddresstheconcerns.
2016 LocalAuthorityBuildingStandardsScotland[LABSS]
LABSSProceduralGuidanceonverificationofcertifiedandnon-certifiedroutesforcompliancewiththebuildingregulations:February2016
35
APPENDIXA
Assessmentofcompetenciesfornon-certifiedbuildingwarrantelectricalwork
TheaimofthisformistodemonstratethecompetencyofthepersonwhocarriedouttheinstallationasrequiredinStandard4.5-ElectricalSafetyintheDomesticHandbook.Notes:• ThisformneednotbecompletediftheelectricianisregisteredwithNICEIC,amemberofSELECT
oranequivalentorganisationaccreditedbyUKAStoconductinspectionsorprovidecertificationservices(ISO/IEC17065orISO/IEC17020:2012)
• Tobecompletedbythepersonwhocarriedouttheelectricalinstallation
InstallationAddress:
Pleaseentertheaddressofthepropertywheretheinstallationhastakenplace.
InstallersName:
Pleaseprovideyournameandaddress.
InstallersBusiness:
Ifyouareabusiness,pleaseprovideyourbusinessname.
Insurance:Ihaveemployers’liabilityinsurance(£2millionminimumisrecommended),unlessthebusinesshasnoemployees.
Ticktoconfirm
Ifyouareamemberofatradebody,pleaseprovidenameoforganisation.
Yearofcompletionofapprenticeship:
Differentcriteriamaybeapplieddependinguponwhenyourapprenticeshipwascompleted.
Pre1995 Post
1995
DoyouholdacurrentSJIB/JIBGradeCard? Yes No IfyoudonotholdacurrentSJIBGradeCard-pleaseindicateifyouhaveeverheldsuchacardandwhenitexpired.
Haveheld Neverheld Dateexpired
DoyouholdacurrentECSHealth&Safety
Certificate?
PleaseprovideevidenceofsuccessfulcompletionoftheECSHealthandSafetyassessmentwithinthepast3years.
Yes No
Dateexpired
IfyoudonothaveacurrentESCCertificate,pleaseindicatehereifyouhaveeverheldsuchacertificateandwhenitexpired.
Haveheld Neverheld
Dateexpired
2016 LocalAuthorityBuildingStandardsScotland[LABSS]
LABSSProceduralGuidanceonverificationofcertifiedandnon-certifiedroutesforcompliancewiththebuildingregulations:February2016
36
Apprenticeship
Haveyousatisfactorilycompletedaregisteredapprenticeshipandhadapracticaltraininginelectricalinstallationwork?
Yes No
Experience Yes No
Haveyouhadatleasttwoyears’journeymanexperience?
QualificationsDoyouholdanyofthefollowingqualifications?
Yes No
SVQLevelIIIinElectricalInstallation
SuccessfullypassedtheACA(AdvancedCompetenceAssessment)(1995apprenticetrainingscheme),ANDsuccessfulcompletionoftheDistanceLearningCourse,theEnhancedCollegeWeekwheretheapprenticeshipwascompletedafterSeptember1995;or
Successfulcompletionofanapproved,assessedElectricalInstallationDesignandVerificationorInspectionandTestingTrainingCoursewithinthepreviousfiveyears,wheretheapprenticeshipwascompletedbefore1995,or
GainedtheSQACertificateinElectricalInstallationParts1and2orapprovedequivalent,ANDgainedanassessedcertificateforBS7671(asamended)Inspection&Testingofelectricalinstallationswithinthelast5years,or
Ifnoneofthese,confirmwhatqualificationsyouholdandwhenyougainedthem*
*useaseparatesheettoconfirmyourqualifications.
TestingEquipment
Pleaseconfirmthatyoupossessandhaveacurrentcalibrationcertificateforthefollowingtestingequipmentinordertocarryoutbasicelectricaltestandinspectionofaninstallation,either:
Amultifunctioninstallationtestmeter(whichwillcancarryoutalltestprocedures),or
Oneeachof:• Alow/highInsulationResistancetestmeter,and • AnEarthFaultLoopImpedanceTester(EFLI)/ProspectiveFaultCurrent(PFC)
Tester,and
• AResidualCurrentDevice(RCD)Tester.
Declaration
Pleasesignthisformtoconfirmthatthestatementscontainedthereinareatrueaccountofyourcurrentqualifications,experienceandcompetencies.
Signed:
Dated:
Whenarequestismadeinthisformforconfirmationofdocumentsheld,includingqualifications,SJIBCardyoushouldprovidecopieswhereverpossible.
2016 LocalAuthorityBuildingStandardsScotland[LABSS]
LABSSProceduralGuidanceonverificationofcertifiedandnon-certifiedroutesforcompliancewiththebuildingregulations:February2016 37
APPENDIXB
Risk Installer ImpactonorBenefittoverifier/serviceuser SuggestedReasonableInquiryby(dependentonsizeandscaleofproject)ElectricalInstallation RelatedStandards
RiskLevel1 ApprovedCertifierofConstruction(ACC)–declaredonwarrantapplicationform
CoveredbyCoCscheme
Recoursetoschemeprovider
CoveredbyCoCscheme
Recoursetoschemeprovider
CheckvalidityofCertificateofConstruction.
RiskLevel2 AnelectricianregisteredwithNICEIC,memberofSELECToranequivalentorganisationaccreditedbyUKAStoconductinspectionsorprovidecertificationservices(ISO/IEC17065orISO/IEC17020:2012)
Coveredbyscheme/registration/tradebody
Recoursetotradebody
Notcoveredbyscheme/registration/tradebody
SubjecttoRIbyverifier
CCNP Intermediatestage-whereappropriatecheck notching/firestoppingetc. Completionstage-carryoutcursorycheckof theelectricalinstallation.CheckmembershipofTradeBody.CheckdetailsinBS7671certificate.
RiskLevel3 Electricianwhodemonstratescompetency(AppendixA)
Notcoveredbyscheme/registration/tradebody
SubjecttoRIbyverifier
Notcoveredbyscheme/registration/tradebody
SubjecttoRIbyverifier
CCNP Intermediatestage-whereappropriatecheck notching/firestoppingetc. Completionstage-carryoutcursorycheckof theelectricalinstallation.Receivecompletedself-certificationform(AppendixA).CheckdetailsinBS7671certificate.
RiskLevel4 ANOther Notcoveredbyschemeorcertification/tradebody
SubjecttoRIbyverifier
Notcoveredbyscheme
SubjecttoRIbyverifier
CCNP Intermediatestage–whereappropriatecheck notching/firestoppingetc. Completionstage-carryoutcursorycheckof theelectricalinstallation.RequestasatisfactoryEICReportfromanelectricianwhoisregisteredwithNICEIC,amemberofSELECToranequivalentorganisationaccreditedbyUKAStoconductinspectionsorprovidecertificationservices(ISO/IEC17065orISO/IEC17020:2012).CheckdetailsinBS7671certificate.
2016 LocalAuthorityBuildingStandardsScotland[LABSS]
LABSSProceduralGuidanceonverificationofcertifiedandnon-certifiedroutesforcompliancewiththebuildingregulations:February201638
APPENDIXC
ACCtobeused?
Yes
CertofConstructionreceived?
Yes
RICheckvalidityofCert
No Paymentofdiscountgivenatapplication
stagetoberequested.
RIcarriedoutbasedonoptionsinrisklevel2to
4
No
NICEIC/SELECTregistered/memberorotherUKASaccreditedelectrician
Risklevel2
Check
registration/membershipiscurrent
RIcarriedoutbasedon
RiskLevel2
Electrician(AppendixA)
Risklevel3
Checkcompetencyself-
certificate
RIcarriedoutbasedon
RiskLevel3
ANOther
Risklevel4
ElectricalInstallationConditionreportfromACCorelectricianoronewhoisregisteredwithNICEIC,amemberofSELECToranequivalentorganisationaccreditedbyUKAStoconductinspectionsorprovidecertificationservices(ISO/IEC17065orISO/IEC17020:2012)
2016 LocalAuthorityBuildingStandardsScotland[LABSS]
LABSSProceduralGuidanceonverificationofcertifiedandnon-certifiedroutesforcompliancewiththebuildingregulations:February2016
39
LABSSPGNEQ005/2016TheverificationofDrainageHeatingandPlumbingInstallations
Section3.0oftheTechnicalHandbooks
1.1PREAMBLE Thepurposeofthisguidancenoteisto:• outlineaconsistentapproachtotheverificationofcertifiablework;• examinewhatconstitutesproportionateauditing;and• provideguidanceforverifiersonwhatisdeemedequivalenceinreasonableinquiryinrelation
todrainage,heatingandplumbinginstallationsnotcoveredbyaCertificateofConstruction.1.2AIMSAsastartingpoint,itisconsideredthatguidanceinthisrespectshould:• bebasedonariskassessmentapproach,• considertechnicalandproceduralaspects,• considerthecompetenciesofverificationstafforotherresources,• introduceauditingmeasurestocoverthescopeofthedesignworkthatcanbecertified,and• showthatauditingmeasuresarebasedonariskassessmentapproach.
1.3BACKGROUNDTheimportanceofdrainage,heatingandplumbinginstallationswithintheBuildingStandardssysteminScotlandisrecognised.Consequently,theaimisthattheowner(relevantperson)shouldappointanApprovedCertifierofConstruction[ACC]toundertakealldrainage,heatingandplumbinginstallationsandissueaCertificateofConstruction,confirmingcompliancewithbuildingregulations.However,giventhenon-mandatorystatusoftheApprovedCertifierofConstructionschemes,practicehasrevealedthatfewdrainage,heatingandplumbinginstallationsareundertakenorsupervisedbyACCs.AtBSD/LABSS/CertificationSchemeProvidersmeetings,concernswereraisedregardinglackofconsistencyinapproachofverifierstoreasonableinquiryandlackofequivalencyinrelationtolevelofcheckbeingundertakeninrelationtodrainage,heatingandplumbinginstallations.Consequently,thisguidance,drawnupinpartnershipwiththeBSDandSNIPEF,isissuedwiththeaimofensuringcompliancewiththeaimsoftheBuilding(Scotland)Act2003andbuildingontheaimsoftheACCprocess.2.OPTIONSFORCOMPLIANCEAsverifiers,theemphasisshouldbeplacedonencouragingtheuptakeoftheApprovedCertifierofConstructionandtheaddedvaluethisbringstothecomplianceagendainthatthecertifierconsidersallrelatedfunctionalbuildingstandardsaspartofthedrainage,heatingandplumbingcertificationprocess.
2016 LocalAuthorityBuildingStandardsScotland[LABSS]
LABSSProceduralGuidanceonverificationofcertifiedandnon-certifiedroutesforcompliancewiththebuildingregulations:February2016
40
ToachieveequivalenceintermsofreasonableinquirywhenanACCisnotinvolvedintheproject,inspectionoftheworksorsamplingofinstallationsinmulti-plotsiteswillbemaderelativetothelevelofrisk.Thedrainage,heatingandplumbinginstallationisembeddedintheConstructionComplianceandNotificationPlanasreferencedinthepublicationVerificationduringConstruction-GuidancetoSupporttheApplicationofReasonableInquiry.Itisnottheverifier’sroletoinspectallmaterialsandworkoneverybuildingsiteand,tothisend,owners/clientsmustalwaysbemindfulthattheyultimatelycarryresponsibilityforcompliancewiththemandatoryfunctionalstandards.RiskAssessmentThedegreetowhichaninstallationmaybeinspectedortestedwillbedependentonanassessmentofrisk,relatedtoboth‘InstallationRisk’and‘InstallerRisk’.InstallationRiskrelatestothelevelofriskposedbythenatureoftheinstallation.Again,thesehavebeenconsideredtobebrokendownintothreecategories:
LowRisk:Alterationsandextensiontoexistingdrainage/sanitaryfacilities,installationofradiators,convectorheaters,thermostaticcontrolsandinstallationofsolarthermalpanels.MediumRisk:Newdrainage,privatewastewatertreatmentsystems,air/groundsourceheatpumps,thermostatictapsandneworreplacementhearths.HighRisk:Installationofcombustionappliances,chimneysandfluepipes,unventedhotwatersystemsandoilandgasstorage.
Installerriskrelatestotherecognisedcompetencyoftheinstallerandmaybeoneofthreecategories(RiskLevels1-3describedinTables1and2andFigure1below).
2016 LocalAuthorityBuildingStandardsScotland[LABSS]
LABSSProceduralGuidanceonverificationofcertifiedandnon-certifiedroutesforcompliancewiththebuildingregulations:February2016
41
Table1.InstallerRiskLevelandexpectedaction
Risklevel Installer Expectedactionbyverifier
RiskLevel1 InstallationbyanApprovedCertifierofConstruction(ACC)–declaredonwarrantapplicationform
Theverifierwillatthebuildingwarrantapplicationvettingstagehaveobtainedconfirmationthatinstallationcontractor(s)tobeanACC.
IncludetheneedforsubmissionoftheCertificateofConstruction(CoC)intheCCNP.
TheACCwilloncompletionsubmitaCertificateofConstruction.
CarryoutchecksinordertoensurethevalidityoftheCoCandthatitrelatestotheprojectandbuildingwarrant.RecorddetailsoftheCoCintheBuildingStandardsRegister.
RiskLevel2 InstallationbyaRecognisedCompetentInstaller(seeAppendixA)
Atbuildingwarrantapplications/vettingstagepromotethebenefitsofanACC.
Atthebuildingwarrantapplicationstageensurethespecificationincludesastatementtotheeffectthattheinstallationcontractor(s)tobeanACCoraRecognisedCompetentInstaller.
IncludewhereitisdeemednecessarytheneedforinspectionofrelatedworkintheCCNP.
Thecontractorwilloncompletionsubmitanyrelevanttestcertification.
UndertakereasonableinquiryinspectionasoutlinedinTable2.
RiskLevel3 InstallationbyaninstallernotbeingaRecognisedCompetentInstaller
AtbuildingwarrantapplicationsstagepromotethebenefitsofanACC.
Atthebuildingwarrantapplicationvettingstageconfirmationobtainedthatinstallationcontractor(s)nottobeanACCoraRecognisedCompetentInstaller.
IncludewhereitisdeemednecessarytheneedforinspectionofworkintheCCNP.
UndertakeReasonableInquiryofthedrainage,heatingandplumbinginstallationasoutlinedinTable2.
Theverifierwillreservetherighttorequestthattheapplicantprovide,attheirexpense,thirdpartytestcertificationfromanACCorRecognisedCompetentInstallerwheredeemednecessary(refertoTable2).
Notes:1) Whereaverifieristoinspecttheinstallation,theinspectionmustbeundertakenbysuitablyqualifiedand
experiencedstaff(supplementarytrainingonkeyissuesistobemadeavailablebyarecognisedTradeScheme).
2) Forauditingpurposes,theverifiermusthaveinplaceariskprotocollinkedtotraining/competencies.
2016 LocalAuthorityBuildingStandardsScotland[LABSS]
LABSSProceduralGuidanceonverificationofcertifiedandnon-certifiedroutesforcompliancewiththebuildingregulations:February2016
42
Figure1.Flowchartforexpectedaction
ACCtobe
used?
NO
YESCertificateofConstructionreceived
NO
YES
RIcarriedoutbasedonInstallerRiskLevel
2inTable2
CheckvalidityofCertificateandrecordinBuildingStandards
Register
NotaRecognisedCompetentInstaller
RecognisedCompetentInstaller
RIcarriedoutbasedonInstallerRiskLevel
2inTable2
Gasinstallation
Notacceptable–Installationtobebya
RecognisedCompetentInstaller
Otherinstallation
RIbasedonInstallerRiskLevel3in
Table2
2016 LocalAuthorityBuildingStandardsScotland[LABSS]
LABSSProceduralGuidanceonverificationofcertifiedandnon-certifiedroutesforcompliancewiththebuildingregulations:February2016 43
Table2.ReasonableInquiry
InstallerRiskLevel
Installer ScopeofReasonableInquiry SuggestedReasonableInquirybyverifier(dependentonsizeandscaleofproject)EquipmentInstallation RelatedStandards
RiskLevel1 InstallationbyanApprovedCertifierofConstruction(ACC)
–declaredonwarrantapplicationform
Coveredbyscheme*1 Coveredbyscheme*1 CheckvalidityofCertificateofConstruction.
RiskLevel2 InstallationbyaRecognisedCompetentInstaller(see
AppendixA)
Coveredbycompetenceofinstallerandanyrelevanttest
certification*2preparedbythem*1
Verifierwillneedtoundertakereasonable
inquiry
CheckinstallermeetstherequirementsofaRecognisedCompetentInstaller.
Requestandrecordanyrelevanttestcertificationrelatedtoinstallationrisklevel*2.
CheckcompliancewithTechnicalStandardsandGuidance,aspartofCCNP*3.
RiskLevel3 InstallationbyanInstallernotbeingaRecognisedCompetentInstaller
NotacceptableforGasCombustioninstallations-InstallationtobebyaRecognisedCompetentInstallerOtherwise,verifierwillneedtoundertakereasonableinquiry
Verifierwillneedtoundertakereasonable
inquiry
Undertakeanyrelevanttesting,relatedtoinstallationrisklevel*2.OR
RequestthirdpartycertificationfromACCorRecognisedCompetentInstaller.
CheckcomplianceoffullinstallationwithTechnicalStandardsandGuidance,aspartofCCNP*3.
NotestoTable21) Theverifiermayqueryanyaspectoftheequipmentinstallationwhichisnotedbythemduringanyinspectionasnotbeingincompliancewiththestandards.ForRiskLevel2orfor
RiskLevel3wherethirdpartycertificationfromACCorRecognisedCompetentInstallerissubmitted,anoverviewcheckoftheequipmentinstallationshouldbecarriedoutbytheverifier.
2) Whethertestingorspecialist’sreportsbyaRecognisedCompetentInstallerortheverifierisrequiredinadditiontovisualinspectionisdependentontheInstallationRiskcategory.Thefollowingisageneralindicationofwhatwouldbeexpected: LowRisk:Visualinspectiononly MediumRisk:Visualinspectionandpotentiallytestingorspecialist’sreports. HighRisk:Visualinspectionandtestingorspecialist’sreports.FurtherguidanceonthisiscontainedintheannexestothetwoguidancedocumentsVerificationduringConstruction-GuidancetoSupporttheApplicationofReasonableInquiry-DomesticBuildings,orNonDomesticBuildings.
3) GuidanceoncomplianceiscontainedintheappropriateDomesticandNonDomesticTechnicalHandbooks.ThefollowingrelevantguidanceisalsoavailableontheBSDwebsite:Lowcarbonequipmentandbuildingregulations-Aguidetosafeandsustainableconstructions:BiomassInstallationsLowCarbonEquipmentGuides-AirSourceHeatPumps LowCarbonEquipmentGuides-GroundsourceandwatersourceheatpumpsLowCarbonEquipmentGuides-Solarthermalsystemsorsolarhotwater(SHW)
2016 LocalAuthorityBuildingStandardsScotland[LABSS]
LABSSProceduralGuidanceonverificationofcertifiedandnon-certifiedroutesforcompliancewiththebuilding
regulations:February2016
44
APPENDIXARecognisedCompetentInstallerrequirementsGasInstallations:InstallermustberegisteredwiththeGasSafeRegister
http://www.gassaferegister.co.uk/
BiomassBoilers:InstallermustholdanappropriateregistrationwithHETAS,
http://www.hetas.co.uk/orholdacurrentAdvancedorTechnicianPlumberorHeatingEngineeror
HeatingTechnicianSNIJIBRegistrationcard,andholdacurrentWaterByelaws/Regulations
qualification.InstallermustalsoeitherholdanindustryapprovedSVQLevel3Certificatein
RenewableTechnologyintherelevanttechnologyorholdacompetencebasedqualificationsuchas
aBPECcoursehttp://bpec.org.uk/
SolidFuelcombustionappliancesandorheatingorhotwatersystems:Installersmustholda
currentAdvancedorTechnicianPlumberorHeatingEngineerorHeatingTechnicianSNIJIB
RegistrationcardorbeeligibletoqualifyforsuchacardandholdacurrentWater
Byelaws/Regulationsqualification.Certifiersmustalsoholdthefollowingqualification:HETASWet
systeminstallercourse.HETAS,http://www.hetas.co.uk/
OilFiredInstallations:InstallermustholdacurrentAdvancedorTechnicianPlumberorHeating
EngineerorHeatingTechnicianSNIJIBRegistrationcardorbeeligibletoqualifyforsuchacardand
holdacurrentWaterByelaws/Regulationsqualification.Installermustalsoholdthefollowing
qualifications:OFTEC105E,OFTEC600Aandeither:OFTEC101and/orOFTEC102.OFTEC-(OilFiring
technicalAssociation)http://oftec.org/
Unventedhotwatersystems:InstallermustholdacurrentAdvancedorTechnicianPlumberor
HeatingEngineerorHeatingTechnicianSNIJIBRegistrationcardandholdacurrentWater
Byelaws/Regulationsqualification.Installermustalsoholdanappropriateunventedqualification.
AboveandBelowGroundDrainage:InstallermustholdacurrentAdvancedorTechnicianPlumber
SNIJIBRegistrationcard.