2013 Title 24 Standards - City of Chula Vista | Home
Transcript of 2013 Title 24 Standards - City of Chula Vista | Home
Title 24: Where We're Headed with the 2013 Standards
Featuring:
Martyn C. Dodd
EnergySoft, LLC
www.energysoft.com
2
Learning Objectives
Understand the major areas of change in the 2013 Title 24 Building Energy Efficiency Standards including:
Overall changes in scope and application
Envelope Requirements
Mechanical Requirements
Indoor Lighting Requirements
Outdoor Lighting Requirements
Wel
com
e
2013 Title 24 Standards
Overall Changes in Scope and Application
Welcome
Overall Changes in Scope and Application ● When and Why? ● Additional Scope of Coverage ● New Registration Procedures ● Performance Modeling
Low-rise Residential Envelope Nonresidential Envelope Low-rise Residential Mechanical Nonresidential Mechanical Residential Lighting Nonresidential Indoor Lighting Nonresidential Outdoor Lighting
Update Schedule
May 31, 2012 Business Meeting – Language Adoption
Jul 1, 2014 Implementation Date
Any projects that apply for permit on or after Jul 1, 2014 will be subject to the 2013 Standards.
Information and Documents available at:
http://www.energy.ca.gov/title24/2013standards/
2013 Title 24 Standards 4
Sco
pe &
App
licat
ion
Revised Standards
All Standards subchapters are now renumbered
Using a decimal system
Section 150 becomes 150.0
Section 151 becomes 150.1
All other conventions stay the same.
2013 Title 24 Standards 5
Computer Rooms
Section 140.9(a)
Prescriptive Requirements for Computer Rooms
(Exceeds 20 w/sqft of load)
Integrated economizers required for each cooling fan system, to meet 100% of expected load at OA temperature of 55F
Exception under 5 ton units assuming no other system has an economizer
Controls that prevent reheating, recooling or simultaneous heating and cooling
Non-adiabatic humidification (steam, infrared) is prohibited
2013 Title 24 Standards 6
Sco
pe &
App
licat
ion
Computer Rooms
Section 140.9(a) (cont)
The total fan power at design conditions of each fan system shall not exceed 27 W/kBtuh of net sensible cooling capacity
Two-speed or variable speed control on fans with motor demand limitations
Air barriers for containment –to prevent discharge air from recirculating
2013 Title 24 Standards 7
Sco
pe &
App
licat
ion
Commercial Kitchens
Section 140.9(b)
Prescriptive Requirements for Commercial Kitchens
Reduce short-circuiting of kitchen exhaust hoods –replacement air limited to 10% of hood exhaust airflow rate
Maximum exhaust flow rate requirements
2013 Title 24 Standards 8
Sco
pe &
App
licat
ion
Commercial Kitchens
Section 140.9(b) (cont)
Kitchens with Type I + Type II exhaust hoods > 5,000 cfm shall have one of the following:
At least 50% of replacement air is transfer air
Demand ventilation controls on >= 75% of exhaust air system
Energy recovery devices with recovery effectiveness >= 40% on at least 50% of total exhaust airflow
75% or more of makeup air volume is unheated or uncooled
Kitchen exhaust system acceptance testing
2013 Title 24 Standards 9
Sco
pe &
App
licat
ion
Laboratories
Section 140.9(c)
Prescriptive Requirements for Laboratory Exhaust Systems
For laboratory circulation rates <= 10 air changes per hour
Zone exhaust and makeup airflow rates shall be capable of reducing to regulated minimum circulation rates or rate necessary to maintain pressurization, whichever is larger
2013 Title 24 Standards 10
Sco
pe &
App
licat
ion
Refrigerated Warehouses
Section 120.6(a)
Some increases in insulation requirements
Some changes to mechanical requirements
Added Infiltration Barrier requirement
Air Curtain
Closing Door
2013 Title 24 Standards 11
Sco
pe &
App
licat
ion
Commercial Refrigeration
Section 120.6(b)
Retail food stores > 8,000 square feet of conditioned area
Have refrigerated display cases
or
Have walk-in coolers or freezers connected to remote compressor units or condensing units
Condenser requirements
Compressor requirements
Display case lighting control requirements
Refrigeration heat recovery requirements
2013 Title 24 Standards 12
Sco
pe &
App
licat
ion
Parking Garages
Section 120.6(c)
Mechanical ventilation systems for enclosed parking garages where the total design exhaust rate for the garage is > 10,000 cfm
Automatically detect contaminant levels and stage fans or modulate fan airflow rates to 50% or less of design capacity provided acceptable contaminant levels are maintained.
Have controls and/or devices that will result in fan motor demand of no more than 30 percent of design wattage at 50% of design airflow.
One CO sensor per 5,000 sq ft.
2013 Title 24 Standards 13
Sco
pe &
App
licat
ion
Parking Garages
Parking Garage Controls (cont)
CO concentration at all sensors is maintained ≤ 25 parts per million (ppm) at all times.
The ventilation rate shall be at least 0.15 cfm/sq ft when the garage is scheduled to be occupied.
The system shall maintain the garage at negative or neutral pressure relative to other occupiable spaces when the garage is scheduled to be occupied.
EXCEPTION to Section 120.6(c): Any garage, or portion of a garage, where more than 20% of the vehicles expected to be stored have non gasoline combustion engines.
2013 Title 24 Standards 14
Sco
pe &
App
licat
ion
Process Boilers
Section 120.6(d)
Boiler, or group of boilers served by a common exhaust stack with a combined heat input capacity of > 2,500,000 Btu/h
Equipped with a combustion air positive shut-off. (flue damper or a vent damper)
Boiler with combustion air fan motors rated at 10+ horsepower
Variable speed drive or equivalent
Boiler with input capacity > 5,000,000 Btu/h
Maintain excess (stack-gas) oxygen concentrations <= 5%
Boiler with input capacity > 10,000,000 Btu/h
Maintain excess (stack gas) oxygen concentrations <= 3% 2013 Title 24 Standards 15
Sco
pe &
App
licat
ion
Compressed Air
New compressed air systems, and all additions or alterations of compressed air systems where the total combined compressor power is > 25 hp
The compressed air system shall be equipped with an appropriate sized trim compressor and primary storage to provide acceptable performance across the range of a system and to avoid control gaps.
Compressed air systems with more than one compressor, having a combined horsepower rating > 100 hp, must operate with an approved controller that is able to choose the most energy efficient combination of compressors within the system based on the current air demand as measured by a sensor.
2013 Title 24 Standards 16
Sco
pe &
App
licat
ion
Design Review
All nonresidential, hotel/motel & highrise residential
Requires a Design Review Kickoff Certificate(s) of Compliance and
Construction Document Design Review Checklist Certificate(s) of Compliance
Completed and signed by a licensed professional engineer (PE) or contractor performing work
2013 Title 24 Standards 17
Sco
pe &
App
licat
ion
Design Review
Buildings less than 10,000 sq ft may be the engineer of record.
Buildings greater than 10,000 sq ft but less than 50,000 sq ft, shall be a qualified in-house engineer with no other project involvement or a third party engineer
Buildings greater than 50,000 sq ft and all buildings with complex mechanical systems, the licensed professional engineer shall be a third party.
2013 Title 24 Standards 18
Sco
pe &
App
licat
ion
Design Review
2013 Title 24 Standards 19
Sco
pe &
App
licat
ion
Commissioning
2013 Title 24 Standards 20
Sco
pe &
App
licat
ion Section 120.8 (moved from Green Building Standard)
All nonresidential buildings > 10,000 sq ft
Owner’s or owner representative’s project requirements
Basis of design
Design phase design review
Commissioning measures shown in the construction documents
Commissioning plan
Functional performance testing
Documentation and training
Commissioning report
Electrical Power Distribution
Section 130.5(a)
Minimum requirement for metering of electrical load
2013 Title 24 Standards 21
Sco
pe &
App
licat
ion
Metering Requirements
Meter Type Services
<= 50kVA
50 kVA <
Services
<= 250kVa
250 kVA <
Services
<= 1000 kVa
Services
> 1000 kVa
Instantaneous (at the time) kW demand Req Req Req Req
Historical peak demand (kW) Req Req
Resettable kWh Req Req Req Req
kWh per rate period Req
Electrical Power Distribution
Section 130.5(b)
Minimum requirement for separation of electrical load
2013 Title 24 Standards 22
Sco
pe &
App
licat
ion
Load Type Services <=
50kVA
50 kVA <
Services
<= 250kVa
250 kVA <
Services
<= 1000 kVa
Services
> 1000 kVa
Lighting A D D
HVAC Systems A D D
Domestic Hot Water A A A Plug Loads A A D Elevators & Escalators A A A Appliances 25 kVa or higher A D D
Load Centers 25 kVa or higher A D D
Renewable Power Source Each Group Each Group Each Group Each Group
Renewable Loads A A A
Charging Stations A A A A
A: Aggregated load D: All loads disaggregated (see standard for details)
Section 130.5(d)
In all buildings, both controlled and uncontrolled 120 volt receptacles shall be provided in:
Private offices
Open office areas
Reception lobbies
Conference rooms
Kitchenette in office spaces
Copy rooms
Circuit Controls for 120-Volt Receptacles
2013 Title 24 Standards 23
Sco
pe &
App
licat
ion
Updated Weather
New weather data used in performance
Uses NREL dataset from 2009
Data based upon historical average
New “reference cities”
Zone 6 - Torrance
Zone 8 – Fullerton
Zone 14 – Palmdale
Zone 15 – Palm Springs
Zone 16 – Blue Canyon
Climate zone boundaries have changed
2013 Title 24 Standards 24
Sco
pe &
App
licat
ion
Solar Zones
Nonresidential Buildings 3 stories or less
High-rise Res & Hotel/Motel buildings 10 stories or less
Minimum 15% of roof area
Exceptions are given in Section 110.10 for locating solar zone
elsewhere
2013 Title 24 Standards 25
Non
resi
dent
ial E
nvel
ope
Solar Zone
Roof oriented between 110 degrees and 270 degrees or flat roof
No roof obstructions
Designed for weight of solar panels
The area may be divided into 80 sqft or more sections, no dimension < 5 feet
Nonresidential Mechanical
Welcome Overall Changes in Scope and Application Low-rise Residential Envelope Nonresidential Envelope Low-rise Residential Mechanical
Nonresidential Mechanical ● Equipment ● Economizers ● Fans ● Controls
Residential Lighting Nonresidential Indoor Lighting Nonresidential Outdoor Lighting
HVAC
New efficiencies for DX equipment
Implementation on Jan 1, 2015
Equipment < 65,000 Btuh 14 SEER
Equipment >= 65,000 Btuh < 240,000 Btuh 11.7 EER
2013 Title 24 Standards 27
Non
resi
dent
ial M
echa
nica
l
Chillers
Chilled water plants shall not have more than 300 tons provided by air cooled chillers
Slight modification to original rule
Prescriptive limitation
2013 Title 24 Standards 28
Non
resi
dent
ial M
echa
nica
l
Economizers
Mandatory Fault Detection and Diagnostics (FDD)
All air-cooled unitary direct-expansion units with an economizer and
Mechanical cooling capacity >= 54,000 Btuh
Must include a Fault Detection and Diagnostics (FDD) system
Includes
Packaged DX rooftops
Split-systems
Heat pumps
Variable refrigerant flow systems
2013 Title 24 Standards 29
Non
resi
dent
ial M
echa
nica
l
Economizers
Prescriptive threshold for economizers lowered
Moved from 75,000 Btuh down to 54,000 Btuh (4.5 tons)
Removed exemptions related to computer equipment and telecommunications
2013 Title 24 Standards 30
Non
resi
dent
ial M
echa
nica
l
Economizers
DX systems with economizers must be able to stage or modulate cooling capacity as follows:
2013 Title 24 Standards 31
Non
resi
dent
ial M
echa
nica
l
Cooling Capacity Staging or Modulation
Fan Type Stages Required Cooling Capacity Effective Date
Constant Volume 2 >= 75,000 Btuh Jan 1, 2014
Constant Volume 2 > =65,000 Btuh Jan 1, 2016
Variable Volume 3 or 4 > =65,000 Btuh Jan 1, 2014
Fans
Each system listed in Table 140.4-B shall be designed to vary the airflow rate as a function of actual load.
2013 Title 24 Standards 32
Non
resi
dent
ial M
echa
nica
l
Variable Airflow Control of Fans
Cooling System Type Fan Motor Size Cooling Capacity Effective Date
Direct Expansion any >= 75,000 Btuh Jan 1, 2014
Direct Expansion any > =65,000 Btuh Jan 1, 2016
Chilled Water & Evap > 1 hp any Jan 1, 2014
Chilled Water & Evap > ¼ hp any Jan 1, 2016
Fans
Single zone systems shall have controls and/or devices that will result in fan motor demand of no more than 40 percent of design wattage at 66 percent of design fan speed
Two-speed fan or variable speed drive
Multiple zone systems shall include controls that limit the fan motor demand to no more than 30 percent of the total design wattage at 50 percent of design air volume when static pressure set point equals 1/3 of the total design static pressure
Variable speed drive 2013 Title 24 Standards 33
Non
resi
dent
ial M
echa
nica
l
Controls
Occupancy sensors allowed as a control option for demand control ventilation
May reduce the ventilation rate to zero
One sensor per room
Must do one hour pre-purge prior to normal occupancy
Requires fan cycle control sequence to maintain the average outdoor air rate over a 2 hr. period
Must shut off outside air within 30 minutes of vacancy
If single zone system, must also cycle off the fan
2013 Title 24 Standards 34
Non
resi
dent
ial M
echa
nica
l
Controls
Mandatory Occupancy sensor based HVAC control in:
Multipurpose rooms less than 1000 sqft
Classrooms greater than 750 sqft
Conference rooms greater than 750 sqft
Must automatically setup the cooling set point by 2°F or more and setback the heating temperature set point by 2˚F or more
AND
Automatically reset the minimum required ventilation rate to zero or turn the supply fan off when the zone is unoccupied
2013 Title 24 Standards 35
Non
resi
dent
ial M
echa
nica
l
Hotel/Motel Guest Rooms
Hotel and motel guest rooms shall have captive card key controls, occupancy sensing controls, or automatic controls.
Activated no longer than 30 minutes after the guest room has been vacated
Setpoints are:
Set-up at least 5°F in cooling mode
Set-down at least 5°F in heating mode
Lighting is switched off
At least one-half of the 120-volt switched
EXCEPTION: One high efficacy luminaire as defined in TABLE 150.0-A or 150.0-B that is switched separately and where the switch is located within 6 feet of the entry door.
2013 Title 24 Standards 36
Non
resi
dent
ial M
echa
nica
l
Nonresidential Indoor Lighting
Welcome Overall Changes in Scope and Application Low-rise Residential Envelope Nonresidential Envelope Low-rise Residential Mechanical Nonresidential Mechanical Residential Lighting Nonresidential Indoor Lighting
● Mandatory Measures ● Power Adjustment Factors ● Complete Building Method ● Area Category Method ● Tailored Method
Nonresidential Outdoor Lighting
Multi-level Controls
Section 130.1(b)
Multi-level controls required in areas > 0.5 w/sqft and >= 100 sqft
Each luminaire shall be controlled by at least of one of the following methods:
Manual dimming
Lumen maintenance
Tuning
Automatic daylighting controls
Demand responsive lighting controls
2013 Title 24 Standards 38
Non
resi
dent
ial I
ndoo
r Lig
htin
g
Multi-level Controls
Exceptions to Section 130.1(b)
Classrooms, with a connected general lighting load of 0.7 watts per square feet and less
Can have at one control step between 30-70 percent of full rated power.
An area enclosed by ceiling height partitions that has only one luminaire with no more than two lamps.
2013 Title 24 Standards 39
Non
resi
dent
ial I
ndoo
r Lig
htin
g
Lumen Maintenance will maintain constant light output as lamp ages. Tuning is the ability to set maximum light levels at a lower level than full power.
Occupant Sensors
Occupant sensors to reduce power by 50%
Aisles and open areas in warehouses
Must control that particular aisle
40% power reduction if LPD is less than 80% of Area Category allowance
Library book stack aisles
10 feet or longer that are accessible from only one end
20 feet or longer that are accessible from both ends
Lighting installed in corridors and stairwells
2013 Title 24 Standards 40
Non
resi
dent
ial I
ndoo
r Lig
htin
g
Occupant Sensors
Section 130.1(c)7B
Stairwells and common area corridors which provide access to guestrooms and dwelling units of high-rise residential buildings and hotel/motels
Parking garages, parking areas and loading and unloading areas.
At least one control step between 20 percent and 50 percent
No more than 500 watts together.
2013 Title 24 Standards 41
Non
resi
dent
ial I
ndoo
r Lig
htin
g
Skylit Zone Definition
0.7 times ceiling height in each direction from the edge of the rough opening of the skylight
2013 Title 24 Standards 42
Non
resi
dent
ial I
ndoo
r Lig
htin
g
Primary Sidelit Zone Definition
One window head height deep into the area
Includes window width plus 0.5 times window head height wide on each side of the rough opening of the window
2013 Title 24 Standards 43
Non
resi
dent
ial I
ndoo
r Lig
htin
g
Automatic Daylighting Controls
Section 130.1(d)2
Required in skylit zones
Required in primary sidelit zones
Zones documented on plans
Luminaires in each type of zone must be controlled separately
Photosensors are not readily accessible to unauthorized personnel
Must be a Multi-Level control
2013 Title 24 Standards 44
Non
resi
dent
ial I
ndoo
r Lig
htin
g
Exceptions:
Less than 120 watts of lighting
Less than 24 sqft of glazing
Automatic Daylighting Controls
2013 Title 24 Standards 45
Non
resi
dent
ial I
ndoo
r Lig
htin
g
Parking Garage Daylighting
Section 130.1(d)3
Automatic daylighting controls required
Parking garage area with combined total of 36 square feet or more of glazing or opening
Daylit zones shall be shown on the plans.
Photosensors are not readily accessible to unauthorized personnel
Controls shall be multi-level, continuous dimming or ON/OFF.
Shut lights off when illuminance levels greater than 150 percent of the lighting illuminance level. 2013 Title 24 Standards 46
Non
resi
dent
ial I
ndoo
r Lig
htin
g
Exception: Less than 60 watts of lighting in the perimeter zone
Demand Responsive Lighting Controls
Section 130.1(e)
Applies to all buildings larger than 10,000 sqft.
Demand responsive controls and equipment shall be capable of receiving and automatically responding to at least one standards based messaging protocol which enables demand response after receiving a demand response signal.
2013 Title 24 Standards 47
Non
resi
dent
ial I
ndoo
r Lig
htin
g
Demand Responsive Lighting Controls
Must automatically provide either:
A 15% reduction in lighting power via dimming; or
A reduction in lighting by one level below full ON in accordance with Table 130.1-A via stepped dimming or stepped switching
Spaces that are non-habitable shall not be used to comply with this requirement.
Spaces with a lighting power density of less than 0.5 watts per square foot shall not be counted toward the building’s total lighting power.
Table 130.1-A shown on next slide
2013 Title 24 Standards 48
Non
resi
dent
ial I
ndoo
r Lig
htin
g
Demand Responsive Lighting Controls
2013 Title 24 Standards 49
Non
resi
dent
ial I
ndoo
r Lig
htin
g
Control Credits – Called PAFs
Table 140.6-A Lighting Power Adjustment Factors (PAFs)
Non
resi
dent
ial L
ight
ing
Sta
ndar
ds
Secondary Daylight Zones
Prescriptive compliance
Secondary daylight zone
120 watts or more of lighting in secondary area
Automatic daylighting controls required
2013 Title 24 Standards 51
Non
resi
dent
ial I
ndoo
r Lig
htin
g
Complete Building Method
Reduction in LPDs for Offices and Parking Garages
2013 Title 24 Standards 52
Non
resi
dent
ial I
ndoo
r Lig
htin
g
Area Category Method
Reduced LPDs for Offices, Grocery, Retail & Parking
New category for Videoconferencing
2013 Title 24 Standards 53
Non
resi
dent
ial I
ndoo
r Lig
htin
g
Area Category Method
New footnotes for additional allowances
Applies to Tasks, Ornamental, etc
2013 Title 24 Standards 54
Non
resi
dent
ial I
ndoo
r Lig
htin
g
Alterations
Screw base adapters are not recognized, even if permanent
Luminaires and luminaire housings manufactured with incandescent screw base sockets shall be classified only as incandescent. Field modifications, including hard wiring of an LED module, shall not be recognized
Replacement of lamps in a luminaire manufactured or rated for use with linear fluorescent lamps, with linear lamps of a different technology such as linear LED lamps, shall not be recognized.
2013 Title 24 Standards 55
Non
resi
dent
ial I
ndoo
r Lig
htin
g
Alterations
Lighting System Alterations shall include alterations where an existing lighting system is modified, luminaires are replaced, or luminaires are disconnected from the circuit, removed and reinstalled, whether in the same location or installed elsewhere.
Subject to Table 141.0-E
Exception: Alterations that qualify as a Luminaire Modification-in-Place (definition to follow)
2013 Title 24 Standards 56
Non
resi
dent
ial I
ndoo
r Lig
htin
g
Alterations
2013 Title 24 Standards 57
Non
resi
dent
ial I
ndoo
r Lig
htin
g
130.1(a) = Area Control 130.1(d) = Daylighting Control 130.1(b) = Multi-level Control 130.1(e) = Demand Response Control 130.1(c) = Automatic Shut Off Control 130.0(d) = Mfg. Instructions
Alterations
To qualify as a Luminaire Modification-in-Place, lighting systems shall be modified in only one or more of the following methods:
Replacing lamps and/or ballasts.
Changing the number or type of light source in a luminaire including socket renewal, removal or relocation of sockets.
Changing the optical system of a luminaire.
Installing lighting control systems devices.
Replacement of whole luminaires one for one in which the only electrical modification involves disconnecting the existing luminaire and reconnecting the replacement luminaire.
2013 Title 24 Standards 58
Non
resi
dent
ial I
ndoo
r Lig
htin
g
Alterations
2013 Title 24 Standards 59
Non
resi
dent
ial I
ndoo
r Lig
htin
g
130.1(a) = Area Control 130.1(d) = Daylighting Control 130.1(b) = Multi-level Control 130.1(e) = Demand Response Control 130.1(c) = Automatic Shut Off Control 130.0(d) = Mfg. Instructions
Nonresidential Outdoor Lighting
Welcome Overall Changes in Scope and Application Low-rise Residential Envelope Nonresidential Envelope Low-rise Residential Mechanical Nonresidential Mechanical Residential Lighting Nonresidential Indoor Lighting Nonresidential Outdoor Lighting
● General ● Hardscape Lighting Power ● Specific Applications Lighting Power ● Ordinance Tables ● Signs
Motion Sensors
All luminaires with mounting heights less than 24’ above the ground
Motion sensor required
Reduce lighting power of each luminaire by at least 40 percent but not exceeding 80 percent
OR
Provide continuous dimming
Shall employ auto-on functionality
Maximum of 1,500 watts of lighting power shall be controlled together
2013 Title 24 Standards 61
Non
resi
dent
ial O
utdo
or L
ight
ing
Motion Sensors
Exceptions to motion sensors
Sales Frontage
Sales Lots
Sales Canopies
Building Facades
Ornamental Hardscape
Dining
Pole-mounted luminaires <= 75 watts
Non-pole mounted luminaires <= 30 watts
Linear lighting <= 4 watts per linear foot of luminaire
2013 Title 24 Standards 62
Non
resi
dent
ial O
utdo
or L
ight
ing
Hardscape Lighting Power
Table 140.7-A
Hardscape Allowances
Reductions in Lighting Allowances (shown in red)
2013 Title 24 Standards 63
Non
resi
dent
ial O
utdo
or L
ight
ing
Type of Power Allowance Lighting
Zone 1
Lighting
Zone 2
Lighting
Zone 3
Lighting
Zone 4
Area Wattage Allowance (AWA) 0.035 W/ft² 0.045 W/ft² 0.090 W/ft² 0.115 W/ft²
Linear Wattage Allowance (LWA) 0.25 W/lf 0.45 W/lf 0.60 W/lf 0.85 W/lf
Initial Wattage Allowance (IWA) 340 W 510 W 770 W 1030 W
Specific Applications Lighting Power
Reductions in Lighting Allowances (shown in red)
2013 Title 24 Standards 64
Non
resi
dent
ial O
utdo
or L
ight
ing
Lighting Application Lighting Zone 1 Lighting Zone 2 Lighting Zone 3 Lighting Zone 4
Building Entrances or Exits. Allowance per door. Luminaires qualifying for this allowance shall be within 20 ft of the door.
30 W 60 W 90 W 90 W
Vehicle Service Station Canopies
Allowance for the total area within the drip line of the canopy. Luminaires qualifying for this allowance shall be located under the canopy.
0.514 W/ft² 1.005 W/ft² 1.300 W/ft² 2.200 W/ft²
Outdoor Dining. Allowance for the total illuminated hardscape of outdoor dining. Outdoor dining areas are hardscape areas used to serve and consume food and beverages. Qualifying luminaires shall be within 2 mounting heights of the hardscape area of outdoor dining.
0.014 W/ft² 0.135 W/ft² 0.240 W/ft² 0.400 W/ft²
Questions?
This concludes the Title 24 Standards Training.
Please be sure to complete your evaluation sheets so we can plan future events.