2012 - Rack Level Modeling of Air Flow Through Perforated Tile in a Data Center
-
Upload
renika-baruah -
Category
Documents
-
view
224 -
download
0
Transcript of 2012 - Rack Level Modeling of Air Flow Through Perforated Tile in a Data Center
-
8/13/2019 2012 - Rack Level Modeling of Air Flow Through Perforated Tile in a Data Center
1/11
1 Copyright 2012 by ASME
Proceedings of the ASME 2012 International Mechanical Engineering Congress & ExpositionIMECE2012
November 9-15, 2012, Houston, Texas, USA
IMECE2012-85203
RACK LEVEL MODELING OF AIR FLOW THROUGH PERFORATED TILE IN A DATA
CENTER
Vaibhav K. ArghodeG.W. Woodruff School of Mechanical Engineering
Georgia Institute of TechnologyAtlanta, Georgia, USA
Pramod KumarDepartment of Mechanical Engineering
Indian Institute of ScienceBangalore, Karnataka, India
Yogendra JoshiG.W. Woodruff School of Mechanical Engineering
Georgia Institute of TechnologyAtlanta, Georgia, USA
Thomas S. WeissTriad Floors Inc.
Denver, Colorado, USA
Gary MeyerTriad Floors Inc.
Denver, Colorado, USA
ABSTRACTEffective air flow distribution through perforated
tiles is required to efficiently cool servers in a raised
floor data center. We present detailed computational
fluid dynamics (CFD) modeling of air flow through a
perforated tile and its entrance to the adjacent server
rack. The realistic geometrical details of the perforated
tile, as well as of the rack are included in the model.
Generally models for air flow through perforated tiles
specify a step pressure loss across the tile surface, or
porous jump model based on the tile porosity. Animprovement to this includes a momentum source
specification above the tile to simulate the acceleration
of the air flow through the pores, or body force model.In both of these models geometrical details of tile such
as pore locations and shapes are not included. More
details increase the grid size as well as the
computational time. However, the grid refinement can
be controlled to achieve balance between the accuracy
and computational time. We compared the results from
CFD using geometrical resolution with the porous
jump and body force model solution as well as with
the measured flow field using Particle Image
Velocimetry (PIV) experiments. We observe thatincluding tile geometrical details gives better results as
compared to elimination of tile geometrical details and
specifying physical models across and above the tile
surface. A modification to the body force model is also
suggested and improved results were achieved.
Key words: High density rack; Perforated tile;
Air flow distribution; Geometrical resolution; Porous
jump model;Body force model
INTRODUCTIONIn recent past, many investigations have been
reported on modeling of data center air flows [2-11].
Some of the investigations only focused on the under
floor region (plenum) modeling [3-5] and they
imposed a step pressure loss across the tile surface, or
porous jump model thereby eliminating any
geometrical details of the tile from the model. The
pressure loss factor (K=P/0.5Vin2) was calculated
based on the tile porosity (open area ratio) [1]. Thefocus of these works was to predict the air flow rate
emerging from the plenum. The suggested models
include a 0D model where a uniformly pressurized
plenum was considered [3] or 1D model where the
effects of under floor pressure variation as well as
frictional resistance in plenum was considered. These
simplified model results in manageable grid size and
reduced computational time for modeling large data
centers. Such investigations are helpful for
understanding the overall air supply pattern in the data
center with objective of supplying the air flow rate as
per the requirement of the adjacent rack. It was also
suggested that the air flow design problem is based onthe under floor flow features and supplying the
required amount of air is sufficient to effective cool
the adjacent server rack [2]. However experimental
investigation of air flow emerging from perforated tile
and entering the rack suggests that even though the
supplied air flow rate matches the rack requirement,
issues such as air bypass and room air entrainment
may be present [13-14]. Hence modeling of above
-
8/13/2019 2012 - Rack Level Modeling of Air Flow Through Perforated Tile in a Data Center
2/11
2 Copyright 2012 by ASME
floor system is deemed useful and has been considered
in investigation such as [8-11].
In a more comprehensive investigation, both
under floor and above floor regions have been
investigated together [6]. In this investigation the two
regions were connected by perforated tiles where a
step pressure loss is specified through the tile surface
(porous jump model). A review of the computational
investigations pertaining to data center air flows could
be found in [7].
An improvement in the tile flow model was
suggested in [10-11]. However, in these investigations
the focus was limited to the above floor surface only
where designated air flow rates were specified at the
tile inlet. It was mentioned that in the porous jump
model (which considers uniform velocity based on
total open area of tile), the momentum rise of air due
to pressure loss across the tile surface is not captured
and hence in these investigations additional body force
(momentum source) was specified above the tile
surface to simulate higher momentum of the air flowabove the tile surface (body force model). This model
showed improved results as compared to the porous
jump model [10-11]. Other strategies such as modeling
the tile with an equivalent reduced single open area to
simulate higher momentum or multiple openings were
also suggested [10]. Multiple openings with some tile
geometrical details (much larger pore length scales as
compared to the actual pore size) was also investigated
and fair agreement with measurements was obtained
[10]. In this case higher air entrainment and faster
mixing was observed as compared to the body force
model which eliminated pore geometrical details.
This suggests that further inclusion of finergeometrical details can be helpful to closely capture
the flow pattern above the floor and at rack entry.
Hence, in the present work we report the effect of
including more resolved tile geometrical details on the
solution accuracy at the expense of increased
computational effort. Note that a balance between the
solution accuracy and computational effort needs to be
considered while investigating data center air flows.
We also present a modification to the body force
model which could be useful to simulate the flow field
with much reduced computational efforts and it also
shows promise for further improvements to develop
simplified models which will reduce thecomputational time while still maintaining acceptable
accuracy.
COMPUTATIONAL SETUPFigure 1 shows the server simulators, rack and the
perforated tile used in the experimental investigation
[13-14]. The 42U (1U = 4.45 cm) rack houses four
server simulators each having height of 10U (see
Figure 1(a)). There is a gap of about 2.54 cm (1 inch)
between the bottom of the rack and the solid tile
surface below the rack (see Figure 1(b)). Server
simulators have a front plastic grill with porosity of
about 37% [12]. Each server simulator has four fans
mounted on a plate. The fan-plate is located at a
distance of 25.4 cm (10 inch) from the front of server
simulator. The fans are centered and spaced 5.08 cm (2
inch) apart from fan outer edge. Each fan has an outer
diameter of 16.83 cm (6.625 inch) and 8.26 cm (3.25
inch) hub diameter. Each server simulator has fan
speed dial settings to set desired flow rates through the
rack. Further details of the server simulator could be
found in [12].
The tile used for the investigation has dampers on
the bottom and a perforated plate on the tile top
surface. The dampers have multiple rectangular
openings (see Figure 1(d)) and the tile top has
openings of different shapes with length scales of
about 1.27 cm (0.5 inch) (see Figure 1(c)). The
distance between the dampers and the tile top is about
3.81 cm (1.5 inch).Figure 2 shows the computational domain and
modeled geometrical tile details. The computational
domain considers only one tile and one rack as shown
in the Figure 2(a). All the geometrical features are
modeled as orthogonal shapes. Circular fans with hub
are modeled as square openings with square hub. The
rack geometry after the fan plate is not included in the
model and the fans are considered as exhaust fans with
target mass flow boundary condition. In this case the
pressure at the fan surface is adjusted so as to reach a
pre-assigned mass flow rate through the fan surface.
The swirl generated by the fans is not included in the
model.Figure 3 shows the dimensional details of the
computational domain. The grill at the rack inlet is
modeled as thin rectangular openings of about 1.27 cm
(0.5 inch) height. The impermeable strips adjacent to
the openings have height of 2.54 cm (1 inch) hence
giving an overall porosity of 33% (see Figure 3(d)).
All four server simulators are separated by
impermeable walls as shown in Figure 3(a). The gap
of 2.54 cm (1 inch) between the bottom of the rack and
solid tile below it is also considered in the model and
pressure inlet boundary condition is specified at the
inlet of the gap (see Figure 3(a)).
Plenum is included in the model by specifyingmass flow rate boundary condition below the tile
surface with symmetry boundary condition on the
plenum walls (see Figure 2(a), 3(a), 3(b)). For the
present investigation the plenum is fairly deep (~ 0.9
m or 3 ft) and hence the effect of directional flow
under the tile surface is expected to be less in the
present case [2]. Moreover, two down flow CRAC
units were used which were located on either sides of
the cold aisle (along the length). This would further
-
8/13/2019 2012 - Rack Level Modeling of Air Flow Through Perforated Tile in a Data Center
3/11
3 Copyright 2012 by ASME
suppress the directional flow characteristics in the
plenum, see [13-14] for data center layout. Hence,
mass flow condition is specified below the tile surface
and not on the sides of the modeled plenum. The aisle
top is specified as pressure outlet and the aisle
center is specified as pressure inlet. The aisle
center is the aisle surface facing the rack inlet. The
sides of the aisle are specified as pressure inlet with
some resistance to the air flow (pressure loss
coefficient, K = 10). This condition was used due to
the anticipated resistance to the flow entering the
computational domain because of the presence of
adjacent tiles. Refer [13-14] for further details on tile
layout for the experimental investigation. The value of
K was appropriately adjusted to simulate the flow field
features obtained by experiments. However, further
investigation is required to arrive at an appropriate
value for K based on the physical set-up and operating
conditions.
The modeled tile geometry is shown in Figure
2(b-f). The tile top surface is modeled as 900 squarepores of 1.27 cm (0.5 inch) side. Note that the tile top
surface has pore shapes which have curved edges,
however in our investigation we observe that the
curved pores could be modeled as orthogonal shapes
with same hydraulic diameter [15]. The spacing
between two square pores on the tile top is about 0.64
cm (0.25 inch). The porosity of the modeled tile top
surface is about 39%. The damper openings are
modeled as 36 rectangular openings, each with size of
3.18 cm (1.25 inch) 13.34 cm (5.25 inch). The
distance between two damper openings is 0.64 cm
(0.25 inch) along the longitudinal direction and 3.18
cm (1.25 inch) in the transverse direction. The porosityof damper openings is 41%. The tile top and the
dampers are spaced 3.81 cm (1.5 inch) apart (see
Figure 3(a)).
The computational domain is meshed with full
rectilinear grid. The region near the perforated tile is
appropriately refined such that each square pore on the
tile top has 8 8 cells. In this case grid refinement was
performed using hanging-node approach. Simulations
suggest that having 8 8 cells in each pore gives
reasonably close result with a grid independent
solution [15]. Note that appropriate balance between
grid refinement and solution accuracy is sought here.
For the case using geometrical details the grid size isabout 4.2 million cells. Without grid refinement, for
the cases using simplified models such as porous jump
or body force models the grid size is about 1 million
cells.
The isothermal flow field was solved using a
steady state, finite volume based method and SIMPLE
algorithm was used for pressure velocity coupling
[16]. Symmetry with only one-half the geometry was
used to reduce the computational time. k- realizable
turbulence model was used with inlet turbulence
intensity of 5%. For convective term discretization,
second order upwind scheme was used. Convergence
was assumed when the normalized residuals for all the
variables were less than 1E-04 and the selected
velocity monitors have stabilized within variation of
1%. Commercial CFD software FLUENT was used for
the simulations.
The results are compared with the experiments
[13-14], and with the simplified models specifying
porous jump boundary condition as well as body force
source above the tile surface.
Porous jump model:
Porous jump model specifies step pressure loss
across the tile surface [2-9]. Generally, the magnitude
of pressure loss factor is calculated based on the
porosity of the tile. The pressure loss specification has
a form similar to that given below in Equation (1-2)
[1].
= (1) = +1 (2)
= , = , = = It may be noted that use of this model results in no
alteration in the velocity field across the tile surface.
However, there is acceleration of air though the pores
resulting in increased momentum flux, attempted to be
captured by the body force model. It may be noted that
the tile has two surfaces in series in the path of airflow. The bottom surface has tile dampers and top
surface has the perforations as shown in Figure 2(b-f).
The pressure drop across theses surfaces, as obtained
by correlation (equation 1-2), is added to arrive at the
final pressure drop. Note that in actual case the flow is
not uniform after passing through the dampers and this
may affect the overall pressure drop from the tile. For
the present case the equivalent K across the two tile
surfaces is 16.5. The equivalent porosity of the two
layers is calculated as 31%. The value of K across the
rack inlet (front grill of server simulators) is 14.3
corresponding to the grill porosity of 33%.
Body force model:
In this model a momentum source is specified
above the tile surface to simulate the acceleration of
air passing through the pores in the tile (see equation
(3-5)) [10-11]. The magnitude of the momentum
source was calculated based on the difference of
momentum through the tile pores as compared to the
momentum of air flow in case of uniform velocity as
in the case in porous jump model (see Equation (3)).
-
8/13/2019 2012 - Rack Level Modeling of Air Flow Through Perforated Tile in a Data Center
4/11
4 Copyright 2012 by ASME
The momentum of air flow through the pores was
calculated assuming top-hat velocity profile through
the pores (see Equation (4)).
= (3) =
(4)
= (5), "" = =
Modified Body force model:
The body force model suggested previously
considers a top hat velocity profile at the tile pores
while calculating the excess momentum of air above
the tile surface. However, even higher momentum of
the jets is expected as in reality there will be a velocity
profile present at the tile pores instead of a top-hat
profile. Hence, we suggest a modification to the bodyforce model. In the modified body force model the
momentum rise across the tile surface is calculated
based on the pressure loss as obtained from the
correlations (see Equation (6)).
= = = + 1 (6), Once the momentum averaged velocity (Vpore)
through the tile surface is calculated the momentum
source term can be calculated as suggested by the
body force model (see Equation (5)). Note that the
modified body force model will have higher
magnitude of momentum source as compared to the
body force model.
RESULTS AND DISCUSSIONTable 1 summarizes the cases studied. The air
flow rate across the rack corresponds to a high power
density rack with 15 kW of heat dissipation and bulk
air temperature rise of 10 C across the rack. The tile
flow rate is varied from 0% upto 100% of the rack air
flow rate and the values are listed in Table 1. Further
details of the experimental conditions could be found
in [13-14].
Table 1. Different cases investigated.
Case
#
Rack flow
rate (m3/s,
CFM)
Tile flow
rate (m3/s,
CFM)
Tile flow /
Rack flow
1 1.224, 2594 0, 0 0%
2 1.224, 2594 0.234, 496 20%
3 1.224, 2594 0.754, 1598 60%
4 1.224, 2594 1.224, 2594 100%
Figure 4 shows the pressure loss obtained across
the tile surface from CFD simulations. In this case the
tile geometrical details are included in the model as
shown in Figure 2(b-f). The correlation used forcomparison is given in Equation (2) corresponding to
equivalent tile porosity of 31%. Figure 4 suggests a
good comparison between the correlation and CFD
simulations. However, note that we assume addition of
pressure loss across the two tile surfaces based on the
correlations and in actual case this may not represent
the actual pressure loss. Value of K across the tile for
cases 2, 3 and 4 are also very close to each other
suggesting that the pressure loss factor does not vary
significantly with respect to flow rates investigated
here. Note that case 1 is not included, as there is no
flow through the tile in this case.
Figure 5-8 shows the comparison between
experimental (PIV) and computational (CFD) results
for cases 1-4 (see Table 1). Pathline plots are used for
visualization of the flow field. In the CFD simulations,
massless particles released from the lines at
boundaries (tile, aisle center and aisle top, see
Figure 5-8) and are tracked and plotted. The plots
correspond to the symmetry plane positioned along the
height of the rack. Note that in the CFD model
considering geometrical resolution, the modeled
geometry of the grill at the rack inlet is included. In
the porous jump model pressure loss is specified
across the grill surface.
Figure 5 shows the results for case 1 (see Table 1).
In this case there is no flow through the tile. From thefigure we observe that the flow field measured by PIV
and calculated using CFD are similar and entrainment
of air from aisle top as well as the aisle center is
present in both the experimental and computational
results. The top region of the rack inlet shows air
entrainment from the aisle top (see figure 5(a)). Figure
5(b-e) suggests that the resolution of grill geometry
(rack inlet) does not significantly influence the
computational solution, as compared to using the
porous jump model across the grill for the present
case. This also suggests that it may be beneficial to use
porous jump boundary condition across the rack inlet
to save computational effort for this case.Figure 6 shows the flow field for case 2 (see Table
1). In this case the flow rate through the tile is about
20% of the air flow rate through the rack. Due to
insufficient supply of air from the perforated tile, the
rack also entrains the air from aisle top as well as aisle
center as shown in Figure 6(a). The air supplied from
the tile reaches only the lower portion of the rack,
while near the top the rack entrains air from aisle top.
The middle portion of the rack mostly entrains air
-
8/13/2019 2012 - Rack Level Modeling of Air Flow Through Perforated Tile in a Data Center
5/11
5 Copyright 2012 by ASME
from the aisle center. These flow field features are also
captured by all the computational models (see Figure
6(b-e)). The body force model and modified body
force model show that the tile air flow reaches higher
along the rack height, as compared to the porous jump
model (see Figure 6(b) and 6(c)). Inclusion of body
force source above the tile surface increases the
momentum of bulk air in the region above the tile
surface, and hence results in higher reach of air to the
rack inlet. The momentum source region is between
the yellow line and tile surface (see Figure 6(c-d)).
The result obtained with geometrical resolution is very
similar to the result obtained by the body force and
modified body force models.
The flow field for case 3 (60% of rack air flow
through tile, see Table 1) is shown in Figure 7. From
Figure 7(a) we note that even though the air flow rate
through the tile is lower than the rack air requirement,
a portion of the supplied air escapes from the aisle top.
We can also observe delayed entry of the tile air at the
lower portion of rack inlet (see bottom right corner ofFigure 7(a)). This was attributed to the higher
momentum of air emerging from the tile [13-14]. Air
entrainment from the aisle center could also be noticed
for this case (see bottom left corner of Figure 7(a)).
The porous jump model is not able to capture these
phenomena and the air flow from the tile reaches only
up to a certain height of rack (see Figure 7(b)). Porous
jump model also suggests entrainment of air from aisle
top which is not observed experimentally. The porous
jump model is also not able to capture the air
entrainment from aisle center near the tile surface
(bottom left corner) and delayed entry of air in the
lower portion of rack inlet (bottom right corner).When momentum source is included above the
tile surface (body force model) the tile air flow reaches
higher as compared to the porous jump model (see
Figure 7(c)). However air entrainment from the aisle
top could be observed for the body force model too,
which is not present in the experimental results. Body
force model shows minor improvement in the
computed flow field. In this case, small entrainment of
air from the aisle center near tile (bottom left corner)
and slight delay of entry of air in lower portion of rack
could be observed (bottom right corner).
The modified body force model shows further
improvement in the results possibly due to highermagnitude of momentum source specification above
the tile surface (see Figure 7(d)) as compared to the
body force model. It may be noted that even with the
modified body force model, the flow field is
significantly different from the experimental results.
The flow field with the model that included the
geometrical details of the tile is shown in Figure 7(e).
From the figure we observe that the flow field features
are closer to the experimental results. A portion of air
flow is observed to escape from the aisle top. This
model also captures the delayed entry of air to the
lower portion of the rack inlet. The air entrainment
from aisle center could also be observed from Figure
7(e).
Figure 8 shows the flow field features for case 4
(see Table 1). In this case, the air flow rate through the
tile is equal to the air flow rate through the rack. Due
to higher momentum of air jet, significant portion of
the tile air is observed to bypass the rack through the
aisle top (see Figure 8(a), refer to [14] for the
discussion). The air entrainment through the aisle
center and delayed entry of tile air to the rack could be
prominently observed. The porous jump model (see
Figure 8(b)) shows the tile air reaching near the aisle
top, however, the prominent flow field features
measured experimentally, could not be captured by
this model. The body force model, as well as modified
body force model while showing improved prediction,
could not compare closely with the experimental
results (see Figure 8(c-d).Figure 8(e) shows the flow field obtained by
resolving the tile geometry, which is closer to the
experimental results. This model is able to capture
significant bypass of the tile air through the aisle top,
as well as entrainment of air though aisle center near
the tile (bottom left corner). The delayed entry of the
air near the bottom portion of the rack could be clearly
seen from bottom right corner of Figure 8(e). This
suggests that simplified geometrical resolution shows
promise for better solution accuracy and further
improvements in the body force, or development of
other simplified models is required to capture the flow
field closely.
CONCLUSIONSExperimentally measured flow field in data center
cold aisles were compared with various computational
modeling approaches. The simplified flow models
through floor tiles, such as porous jump and body
force models suggests fair comparison with the
experimental results at lower tile air flow rates.
However, at higher air flow rates, required for high
power density racks, these simplified models do not
capture the flow field features accurately. A modified
body force model is suggested, which calculates the
momentum rise based on the prescribed pressure lossacross the tile surface. While this model shows
improvement in the results, it still does not compare
well with the experimental results at higher tile air
flow rates. Including the geometrical details of the tile
provides better comparison with the experimental
results. This model is able to capture the prominent
flow features, such as bypass of tile air though the
aisle top, as well as entrainment of air from aisle
center and delayed entry of air to the rack inlet. The
-
8/13/2019 2012 - Rack Level Modeling of Air Flow Through Perforated Tile in a Data Center
6/11
6 Copyright 2012 by ASME
present investigation suggests that a fairly coarse grid
could be used, with more geometrical details to
achieve better solution accuracy as compared to
specifying simplified models across the tile surface.
Improvements in the simplified models show scope for
future exploration to achieve a better balance between
the desired solution accuracy and reduced
computational time.
ACKNOWLEDGMENTSThis research is supported by Triad Floors, Inc. and
the Consortium for Energy Efficient Thermal
Management (CEETHERM). The support is gratefully
acknowledged.
REFERENCES[1] Freid, E., Idelchik, I. E., Flow Resistance, A
Design Guide for Engineers, Hemisphere, New York,
1989.
[2] Patankar, S. V., Airflow and Cooling in a Data
Center, Journal of Heat Transfer, 2010, Vol. 132, pp.073001-1-17.
[3] Kang, S., Schmidt, R., Kelkar, K. M.,
Radmehr, A., Patankar, S. V., A Methodology for the
Design of Perforated Tiles in Raised Floor data
Centers using Computational Flow Analysis, IEEE
Transactions on Components and Packaging
Technologies, 2001, Vol. 24, pp. 177-183.
[4] Karki, K. C., Patankar, S. V., Airflow
Distribution Through Perforated Tiles in Raised-Floor
Data Centers, Building and Environment, 2006, Vol.
41, pp. 734-744.
[5] Schmidt, R. R., Karki, K. C., Kelkar, K. M.,
Radmehr, A., Patankar, S. V., Measurements andPredictions of the Flow Distribution through
Perforated Tiles in Raised-Floor Data Centers,
International Electronic Packaging Technical
Conference and Exhibition, July 8-13, 2001, Kauai,
Hawaii, USA.
[6] Rambo, J., Joshi, Y., Convective Transport
Process in Data Centers, Numerical Heat Transfer
Part A, 2006, Vol. 49, pp. 923-945.
[7] Rambo, J., Joshi, Y., Modeling of Data Center
Airflow and Heat Transfer: State of the Art and Future
Trends, Distributed Parallel Databases, 2007, Vol. 21,
pp. 193-225.
[8] Cruz, E., Joshi, Y., Iyengar, M., Schmidt, R.,Comparison of Numerical Modeling to Experimental
Data in a Small Data center Test Cell, International
Electronic Packaging Technical Conference and
Exhibition, July 19-23, 2009, San Francisco,
California, USA.
[9] Iyengar, M., Schmidt, R. R., Hamann, H.,
VanGilder, J., Comparision between Numerical and
Experimental Temperature Distributions in a Small
Data Center Test Cell, International Electronic
Packaging Technical Conference and Exhibition, July
8-12, 2007, Vancouver, British Columbia, Canada.
[10] Abdelmaksoud, W. A., Khalifa, H. E., Dang,
T. Q., Elhadidi, B., Schmidt, R. R., Iyengar, M.,
Experimental and Computational Study of Perforated
Floor Tile in Data Centers, Intersociety Conference on
Thermal Phenomena, Jun 2-5, 2010, Las Vegas, USA.
[11] Abdelmaksoud, W. A., Khalifa, H. E., Dang,
T. Q., Schmidt, R. R., Iyengar, M., Improved CFD
Modeling of a Small Data Center Test Cell,
Intersociety Conference on Thermal Phenomena, Jun
2-5, 2010, Las Vegas, USA.
[12] Nelson, G., Development of an
Experimentally-Validated Compact Model of a Server
Rack. MS Thesis - 2007, Georgia Institute of
Technology, GA, USA.
[13] Kumar, P., Joshi, Y., Experimental
Investigations on the Effect of Perforated Tile Air Jet
Velocity on Server Air Distribution in a High Density
Data Center, Intersociety Conference on Thermal
Phenomena), Jun 2-5, 2010, Las Vegas, USA.[14] Kumar, P., Sundaralingam, V., Joshi, Y.,
Dynamics of Cold Aisle Air Distribution in a Raised
Floor Data Center, Thermal Issues in Emerging
Technologies, Dec 19-22, 2010, Cairo, Egypt.
[15] Arghode, V. K., Joshi, Y., Modeling
Strategies for Air flow Through Perforated Tile in a
Data Center, IEEE Transactions on Components,
Packaging and Manufacturing Technology, In
Preparation 2012
[16] Patankar, S. V., Numerical Heat Transfer and
Fluid Flow, Hemisphere, New York, 1980.
-
8/13/2019 2012 - Rack Level Modeling of Air Flow Through Perforated Tile in a Data Center
7/11
7 Copyright 2012 by ASME
(c) Tile top
(a) Server simulators (b) Rack (d) Dampers
Figure 1. (a-b) Rack and (c-d) tile details under investigation.
-
8/13/2019 2012 - Rack Level Modeling of Air Flow Through Perforated Tile in a Data Center
8/11
8 Copyright 2012 by ASME
(b) Tile top (c) Mesh for each square
pore in tile top
(d) Dampers (e) Mesh for eachopening in dampers
(a) Computational domain (f) Perforated tile with dampers
Figure 2. (a) Computational domain and (b-f) the modeled tile.
-
8/13/2019 2012 - Rack Level Modeling of Air Flow Through Perforated Tile in a Data Center
9/11
9 Copyright 2012 by ASME
Figure 3. Details of the computational domain and set-up.
Figure 4. Pressure drop across the tile obtained by CFD with tile geometrical resolution.
. . . .
(.
)
(a) Side view (b) Front view (c) Fans (rack exit) (d) Grill (rack inlet)
.
()
.
.
-
8/13/2019 2012 - Rack Level Modeling of Air Flow Through Perforated Tile in a Data Center
10/11
10 Copyright 2012 by ASME
Velocity
(m/s)
(a) PIV (b) Porous jump (c) Body force (d) Modified
body force
(e) Geometrical
resolution
Figure 5. Comparison of PIV and CFD results for case 1 (rack flow = 1.224 m3/s, 2594 CFM, tile flow = 0 m3/s,0 CFM, 0% of rack flow).
Velocity
(m/s)
(a) PIV (b) Porous jump (c) Body force (d) Modified body
force
(e) Geometrical
resolution
Figure 6. Comparison of PIV and CFD results for case 2 (rack flow = 1.224 m3/s, 2594 CFM, tile flow = 0.234
m3/s, 496 CFM, 60% of rack flow).
-
8/13/2019 2012 - Rack Level Modeling of Air Flow Through Perforated Tile in a Data Center
11/11
11 Copyright 2012 by ASME
Velocity
(m/s)
(a) PIV (b) Porous jump
model
(c) Body force
model
(d) Modified body
force
(d) Geometrical
resolution
Figure 7. Comparison of PIV and CFD results for case 3 (rack flow = 1.224 m3/s, 2594 CFM, tile flow = 0.754m
3/s, 1598 CFM, 60% of rack flow).
Velocity
(m/s)
(a) PIV (b) Porous jump (c) Body force (d) Modified body
force
(e) Geometrical
resolution
Figure 8. Comparison of PIV and CFD results for case 4 (rack flow = 1.224 m3/s, 2594 CFM, tile flow = 1.224
m3/s, 2594 CFM, 100% of rack flow).