GOVERNMENT OF JAMMU AND KASHMIRLADAKH AUTONOMOUS HILL DEVELOPMENT COUNCIL,KARGIL
OFFICE OF THE PROJECT DIRECTOR /CEO, KREDA,KARGIL -LADAKH
NIT NO: 15
For and on behalf of the Governor of J&K, sealed tenders affixed with Rs.5/=
revenue stamps are invited from reputed Solar Photo Voltaic (SPV) Module
manufacturers for the supply and installation of SPV Power Plants of 42.5 Kwpcapacity. The firm must have ISO 9001 and ISO 14001 certification, manufacturing
facilities for SPV Module in India & should have a service centre at Kargil. The
tenders should be addressed to the Project Director/C.E.O,KREDA,Enviromental Awareness centre Baroo Tsog, Kargil, Ladakh J&K and
should reach the office of the same on or before 29.07.2010 (11.00 a.m. to 4:00p.m.) as per the following terms/conditions and specifications:
List of the 42.50KWp Proposed Power PlantsSI. No. Name of Village/Institution Proposed
Power Plant
Capacity
(kW)
Distance
from Kargil
(km)
Type of Road
1 Umba 42.5 55 motorable
2 Tacha 42.5 30 motorable
3 Ningos Hagnis 42.5 85 motorable
4 Khows 42.5 60 motorable
1. Minimum Criterion for BiddingThe bidder must have following minimum criterion for bidding:
a. The bidder must have ISO 9001 certification for quality management
systems.b. The bidder must have ISO 14001 certification for environmental
requirements.
c. The bidder must have annual turnover of Rs.1000 million in last financial
year and 40% of the turnover must be from Solar Photo-Voltaics.(i, e,Rs.400 million)
d. The bidder must have solar module manufacturing facility in India and
offered modules should be manufactured in accordance with IEC 61215Edition II for meeting quality standards of crystalline silicon solar cell
modules.
e. The bidder must qualify to IEC 61730 (Part I and Part II) for safetyqualification testing.
f. The bidder must have experience of supplying, installing and
commissioning Solar Photo-Voltaic Power Plants industry for more than 2
years in India.
1
-
8/7/2019 20100709-kreda-nit15
2/37
g. The bidder must have his service centre in Kargil with sufficient stock for
quick servicing.
h. The bidder must be a total integrated system designer which is inclusive ofsolar modules, solar charge controller, junction boxes, and mounting
structures.
i. The bidder must ensure that the battery manufacturer/supplier has ISO9001 certification.
j. Company authorized dealers or agencies shall not be allowed to participate
in the tender.k. Following components of the power plant must be made available during
the tender opening date for the inspection of the major components of the
power plant quoted by each supplier. For those bidders having tenders
submitted without the sample components, the price bid shall not beopened.
1. Sample of the solar panel quoted for each power plant
2. Sample of the battery quoted for each power plant
3. PCU Details Specification of each Power Plant to besubmittedNote: only one sample of each type need to besubmitted
Experience of the Bidder
A comprehensive list of past projects implemented, by the bidder in India or abroad,
indicating clients, dates, size of projects and any other relevant material should be
included in the offer. Companies having experience in execution and operation of solar
power plants in Indian states, especially in Ladakh will be given preference duringtechnical evaluation.
Documentation
One set of installation manual / user manual shall be supplied along with each system.
The manual shall include complete system details such as array lay-out, schematicdrawing of the system, inverter details, working principle etc. Step by step maintenance
and troubleshooting procedures shall be given in the manuals as well.
I .INSTRUCTIONS, TERMS AND CONDITIONS :
1. The tender should be in three parts viz. Part I, Part II and Part III as described in
Clause 2 below. These should be in separate envelopes duly super-scribed as Part I,
Part II and Part III, NIT No. and due date. Sealed envelopes containing all the threeparts should then be placed in a larger envelope, which should be sealed, and super-
scribed by the given NIT No., due date and name of the tenderer ,contact no
2
-
8/7/2019 20100709-kreda-nit15
3/37
Clause 2
2. PART I : - Part I of the tender should be super-scribed as Part I, TechnicalDetails for NIT No and should contain
Technical Details:
a. The bidder ISO 9001 certificate to be enclosed
b. The bidder ISO 14001 certificate to be enclosed
c. The bidder must ensure that the battery manufacturer/supplier has ISO 9001
certification; certificate to be enclosed.
d. The bidder must submit the undertaking/certificates for the materials to besupplied as per the Technical Specifications (Annexure 1).
e. The bidder must have solar modules manufacturing facility in India and offered
modules have been manufactured in accordance with IEC 61215 Edition II and
IEC 61730 (Part I and Part II); necessary certificates to be enclosed.
f. The bidder must use solar modules and other balance of system (BoS)
components that qualify to the latest edition of BIS or IEC standards; relevant test
reports and necessary certificates to be enclosed.
g. The bidder must have experience of supplying, installing and commissioning
solar photo voltaic power plants of 50 kWp and above in India. Preference will begiven to those companies who have successfully installed & commissioned such
power plants in the Ladakh Region. List & Purchase Order copy & performance
certificates must be enclosed.
h. The bidder must have PV modules tested at one of the IEC approved test centres.
Test certificates to be enclosed.
i. The bidder must have his service centre in kargil; details of the service centre
must be enclosed.
j. The bidder must be a total integrated system designer inclusive of solar modules,
solar charge controllers, junction boxes and mounting structures. Necessary
documentation must be enclosed.
3. PART II : Part II of the tender should be super scribed as Part II, Commercial
Bid for NIT No and should contain:
3
-
8/7/2019 20100709-kreda-nit15
4/37
a. Proof of Earnest Money.b. Income Tax Clearance Certificate.c. Proof of annual turnover of Rs. 1000 million in the last financialyear and 40% from solar photo voltaic turnover (i, e Rs 400
million)d PAN Noe. Tin Nof. VAT/ service Taxg. Audit balance sheet for the last three yearh.Latest bank solvency upto june,2010For items b to g shall be submitted by the firm duly signed withsealed & should be dully attested by gazetted officer.4. Demand Draft for the purchase of tender document, or for
downloaded tender documents worth Rs.2000.00 drawn in favourof project Director KREDA.
5. PART III: Part III of the tender should be super scribed as Part III, Price Bidfor NIT No and should contain the price bid for the product as per the bill of
material for each power plant, & strictly as per the price bid format given in theNIT. The price quoted should include the Maintenance contract for 5 years. The
supplier has to quote clearly the F.O.R at the site of installation, inclusive of all
taxes.6. The tender should be addressed to The Project Director/Chief Executive
Officer,KREDA, LAHDC Kargil. Both inner and outer covers duly sealed and
superscribed and sent either under registered cover or cast in the tender box kept inthe office of the Project Director/Chief Executive Officer,KREDA, LAHDC
Kargil.
7. The tenderer shall ensure timely receipt of tender in the office of the ProjectDirector/Chief Executive Officer, KREDA,LAHDC Kargil, the tenders receivedby hand or by post after due date of receipt of tenders shall not be entertained even if
the tender has been posted/ dispatched much before the due date of receipt.
8. The tenders will be opened on 31.07.2010 at 2 PM in the office of the Deputy
commissioner/Chief Executive Officer, LAHDC Kargil, on the date of opening of
the tenders only the technical and the commercial parts (part-I & part-II) shall be
opened in the presence of the tenderers who may be present, the price bid (part-III)shall be opened only in case of such tenderers who on scrutiny of part-I & part-II of
their offer are found to have qualified for opening of the price bid on the same day at
the D.Cs office or any other day at the discretion of the purchasing committee. In
case the due date of opening of the tenders falls on a holiday being declaredsubsequently, the tenders will be opened on the next working day.
9. Tenders must be complete in all respects; all the terms and conditions of tender
including the technical specifications should be carefully studied for the sake ofsubmitting complete and comprehensive tender documents. Failure to comply with
any of terms and conditions or instructions of the offer with insufficient particulars
which are likely to render fair comparison of tender as a whole impossible may leadto rejection even if otherwise it is a competitive offer/tender.
4
-
8/7/2019 20100709-kreda-nit15
5/37
10. Telegraphic tenders or the tenders of such tenderers who have not purchased
tender document shall not be entertained. Any request by post or by hand or
telegraphically for any modification addition or deletion etc. in the tenders shall notbe considered.
11. The tenders shall be prepared in a formal manner with all quotations written both
in figures & words. The tenders shall be typed or written in ink, any tender writtenby pencil shall be rejected. There shall be no erasures or overwriting and if
corrections are made the same shall be neatly done and attested. A systematic form
of totalling shall be adopted to avoid any ambiguity. The detailed description of theequipment offered shall be given Rank charge, if any shall be debited to the account
of the tenderer.
12. The tenderer shall furnish an affidavit duly attested by notary that design of their
equipment is free from legal encumbrances and that no legal case of any kind oflitigation regarding the patent design is pending in any court of law.
13. No tenderer unless otherwise specified in these specifications, terms and
conditions shall be exempted from depositing earnest money.
14. The tenderer must have full-fledged service centre with all repairing facilitiesin kargil.
15. No claim shall be laid against the department either in respect of interest ordepreciation in value for the amount of security deposit and or earnest money. In the
case of bank deposits the department shall not be responsible for any loss on account
of failure of the bank.
II. SPECIAL INSTRUCTIONS:
a. Tenders not submitted on the lines indicated above are liable to be rejected
without any correspondence.
b. Request for extension in last date of receipts of tenders shall be ignored.c. The purchaser reserves the right to order additional quantity or reduce the
quantity of the material advertised at the time of placement of
order for which the quoted rate shall be valid.d. All legal proceedings in connection with the order, tender will be subject to the
jurisdiction of local court of Jammu and Kashmir State alone.
e. The purchaser reserves the right to divide the order between two or more
tenders for 100% achievement.f. In case of any doubt, dispute or differences arising out of the contract, the same
shall be referred to the Finance Commissioner (Planning) and
Ladakh Affairs Department, J&K Government for the decisionunder J&K State Arbitration Act.
g. The purchaser shall not be bound to accept the lowest or any tender and reserves
to itself the right of accepting the whole or a portion of any of thetender, as it may deem fit, without assigning any reason thereof.
h. Any form of canvassing by the tenderers to influence the consideration of their
tender shall liable to summery rejection.
5
-
8/7/2019 20100709-kreda-nit15
6/37
i. In order to avoid delay caused by postal correspondence and to expedite the
process, the purchaser may require the successful tenderer to hold
technical & commercial negotiations and convey thedecision/acceptance on behalf of the tenderer, with the Purchase
Committee.
j. The condition hereafter deal with systems details and supplementary conditionsof the contract in addition to those stipulated in foregoing clauses
which along with schedules and annexure, shall be deemed to
form part of detail specification for equipment. The tenderer areadvised to study and familiarize themselves with the terms &
conditions of the tender.
k. All material shall be best quality in the market and be capable of satisfactory
operation when exposed to the local atmospheric conditions atsite.
l. The tenderer is required to submit a statement of facts in details as to their
previous experience in performing a similar or comparable work
and business and technical similar or comparable work andbusiness & technical organization. Financial resources and
manufacturing facilities available to be used in performing thecontract.
m. Force majeure clause shall apply.
n. No other conditions except those mentioned above will be acceptable.
o. Offers not complying with the delivery schedule shall be considered nonresponsive and shall not be evaluated
p. Offers not providing clause by clause compliance shall be considered non
responsive and shall not be evaluatedq. Offers not providing minimum array capacity of designated rating (Wp) shall be
considered non responsive and shall not be evaluated
r. Offers not submitted as per price bid format shall be considered non-responsiveand shall not be evaluated.
III. EARNEST MONEY:
1. Tenders shall be accompanied with the earnest money Rs11,00000.00(Rupees
Eleven lacs only) in the form of CDR/FDR/DD/BG pledged to the Project
Director, KREDA-LAHDC, kargil.2. Tenders not accompanied with the required amount of earnest money will be
rejected and their price bid shall not be opened.
3. The earnest money of the tenderers shall be forfeited if they withdraw their tenderor raise the prices of their offer within the validity period. The earnest money
shall also be forfeited in case of the tenderers who do not comply with the
purchase order placed on them within the validity period of the offer or violateany terms and conditions contained herein for this, purchase order shall be
deemed to have been placed from the due date of letter of intent.
4. Earnest money deposit shall be released in favour of the unsuccessful tender(s)
within one month after the final acceptance of the tender.
6
-
8/7/2019 20100709-kreda-nit15
7/37
IV. SECURITY DEPOSIT:
The successful tenderer(s) shall be required to furnish security deposit
equivalent to 10% of the value of the contract in the
CDR/FDR/bank guarantee from nationalized/scheduled bankpledged to the Project Director, KREDA-LAHDC, Kargil. This
shall be released after testing and commissioning of the SPV
Solar Power Plants.
Security deposit shall be furnished within one month from the date of detailed
purchase order. Failure to do so within the stipulated period will
make the contract liable for cancellation together with forfeiture
of EMD at the discretion of chairman purchase committee. TheEMD of the successful tenderer(s) equivalent to Rs11,00000.00
shall be released after the submission of the security deposit.
V. WARRANTY:
The mechanical structures, electrical works including inverters/charge
controllers/power conditioning unit/ maximum power point
tracker, distribution board/digital meters/, storage batteries
and overall workmanship of the solar power plants must be
warranted for a minimum of 5 years.
PV modules used in solar power plants must be warranted for output wattage,
which should not be less than 90% at the end of 10 years and 80%
at the end of 25 years.
Necessary maintenance spares for five years trouble free operation shall also be
supplied with the system. The supplier shall be responsible to replace free of cost (including
transportation and insurance expenses) to the purchaser whole or
any part of supply which under normal and proper use become
dysfunctional within one month of issue of any such complaint bythe purchaser.
In case the supplier fails to rectify/replace the defective/damaged equipment
including transit damage, shortages within one month from thedate of intimation of such shortage/damage, they shall have to pay
interest to Project Director,KREDA-LAHDC, Kargil @3% per
month on the value of such materials.
VI. OPERATION AND MAINTENANCE:
The supplier shall be responsible for the operation & maintenance of the systemsfor a period of 5 years (that is during the warranty period) from the date of
commissioning of the systems. The price quoted by the supplier should include
the Operation & Maintenance for 5 years. The manufacturer will submit aquarterly report about the maintenance of the system.
7
-
8/7/2019 20100709-kreda-nit15
8/37
The bidder shall give the details of their service centers in kargil district or nearest
places and ensure that all the essential men and materials are placed to ensurequick and efficient operation and after sales service.
During the Operation and Maintenance period, the supplier shall train local
personnel for operation and maintenance. An explanation of preventative
maintenance schedule, plan of operation, scope and implementation of the aftersales service is to be defined and properly documented.
VII. SALES TAX ETC:
The rates offered by the tenderer for design, manufacturing, supply, installation,
commissioning, construction of civil works and operation andmaintenance should be inclusive of all taxes, F.O.R. at the site.
In case of failure to deliver in full the required supplies on order, the purchaser
shall have the right to make a risk purchase at the cost of supplier
and/or cancel the contract and claim reasonable
compensation/damages. The contract of supply shall berepudiated if the supplies are not made within the prescribed
period and to the satisfaction of the purchasing officer.
The price bid should include CST, income tax, surcharge on income tax, service
tax, local taxes etc. Income tax, service tax and other deductible
taxes shall be deducted at the source.
VIII. DELIVERY OF THE POWER PLANT:
The bidder shall indicate delivery time along with the offer and shall be
mutually agreed at the time of order finalization.
IX. VALIDITY:
The tender should be unconditionally valid for a period of sixmonths from the date of opening of the tenders. The quoted price
per system as such shall be firm and not variable with the market
price. The rates approved as per the NIT year would be valid for
further purchase of the systems during the validity period. Anytenderer revising the offer within the validity period, without
prejudice to other remedies available with the department is likely
to be blacklisted.
X. PAYMENT SCHEDULE:
25% shall be made as advanced payment to the successful, subject
to the submission of a bank guarantee for an equal amount valid
for a period of one year at least. Another 25% shall be released on
receipt of the material at the site, 45% after the installation andcommissioning. 5% shall be released in five equal instalments at
8
-
8/7/2019 20100709-kreda-nit15
9/37
the end of each year on submission of documentary evidence
confirming successful O&M during that year.
XI. PENALTY:
In case of failure on the part of the tenderer to make supplies andexecute the work in full, part thereof within the delivery schedule
stipulated in the purchase order, penalty @ 0.5% per week of
undelivered portion subject to a maximum of 15% of the cost ofundelivered portion shall be levied.
XII. CHANGES:
No variation or modification or waiver of any of the terms and
provisions of these specifications shall be deemed valid unless
mutually agreed upon in writing by both the purchaser and the
supplier.
XIII. PACKING:
The bidder shall be responsible for assuring that all commodities
shipped are properly packed and protected to prevent damage or
deterioration during shipment. Packaging and shipping costs shallbe borne by the supplier. Customs clearance and all costs and
actions associated with import duties, taxes and processing of
documents are to be borne by the bidder. The supplier shall beresponsible for all the damages/losses if any. All crates shall be
marked with proper signs indicating UP and DOWN sides of the
packing and also unpacking instructions considered necessary bythe supplier.
XIV. INSURANCE:
The bidder shall provide insurance coverage ex-factory untilcommissioning, and acceptance for replacement or repair of any part of
the consignment due to damage or loss.
XV. HEALTH, SAFETY AND ENVIROMENT:
The bidder shall submit the following before starting the installation of thepower plant.
Safety and Environment policy of the Company
HSE Manuals for Installation
Emergency Management Plan
9
-
8/7/2019 20100709-kreda-nit15
10/37
XVI. CLEAN DEVELOPMENT MECHANISM (CDM) BENEFITS:
All CDM/Carbon Trading benefits from the installation, commissioning
and operation of SPV Power Plants shall be the property of KREDA.
XVII. MATERIAL INSPECTION:
The material inspection shall be done at the factory location before shipment ofthe material from factory location. The material inspection
charges (boarding /lodging) for two representatives from KREDA
have to be borne by the successful tenderer.
XVIII. AGREEMENT:
The successful tenderer(s) shall be required to execute an
agreement on a valid stamped paper for strict compliance of theterms and conditions of the contract, vis--vis the NIT and the
supply order within seven days of placement of the order
XIX. TECHNICAL SPECIFICATION (refer to Annexure I for 42.5 kWp
SPV Plant):
Project Director /Chief Executive Officer,
KREDA,LAHDC, Kargil
10
-
8/7/2019 20100709-kreda-nit15
11/37
ANNEXURE I TECHNICAL SPECIFICATIONS FOR 42.5 kWpSOLAR POWER PLANTS
PREPARED BY
Kargil Renewable Energy Development AgencyLAHDC, Kargil, LADAKH
11
-
8/7/2019 20100709-kreda-nit15
12/37
1. Bill of Material
1.1 List ofComponents of a Typical Solar Power Plant
Sl. Description Total UOM
No Qty
1 Solar module - 160Wp (minimum),crystalline 42.5 Kwp
2 Module mounting structureSuitable for
aboveSet
3 Array Junction Box - ABS PlasticSuitable for
aboveNos
4 Main Junction Box - ABS PlasticSuitable for
aboveNo
5 PCU (240 VDC, 45kWp, 415V AC, 25kVA)Suitable for
aboveNo
6 1C X 4 Sq.mm. Poly Ethylene Cu.cable 375 M
7 2C X 10 Sq.mm. Poly Ethylene Cu.cable 60 M
8 1C X 50 Sq.mm. Poly Ethylene Cu.cable 80 M
9 3.5C X 10 Sq.mm. Poly Ethylene Cu.cable 30 M
10AC Distribution Board with MCB, voltmeter, ammeter and energy meter forPCU output
1 No
11 Battery protection panel 1 No
12 Solar Water Distillation plant (3-4 litres per day) 3 Set
13Battery bank - 240V, 2400 Ah Lead Acid @ C10, 27 deg C with rack andaccessories
1 Set
14 Earthing kit 1 Set
15 Lightning and overvoltage protection 1 Set
16 Installation kit 1 Se
17 CFL,15watt , 230V, 50Hz 2000 No
17 Spares: PCU (240 VDC, 45kWp, 415V AC, 25kVA) 1 no
All the cables listed above are indicative only. It may vary during thetime of installation.
1.2 The bidder is responsible for arranging all the hardware,
accessories, measuring instruments or any other item needed forsuccessful installation/ commissioning/ operation andmaintenance of the power plant.A complete Bill of Materials inclusive of Solar PV Modules,array Junction box, main junction box, cables, Batterybank, PCU, Array mounting structures etc. shall beprovided along with the offer. The numbers of eachcomponent proposed for supply shall be clearly specified.
12
-
8/7/2019 20100709-kreda-nit15
13/37
2. Scope of Work
This job involves by means of the enclosed specification, design,manufacture, supply, installation, commissioning of the Solar PV Power
Systems with 5 years warranty period including 5 years of operationand maintenance.
The Scope of Work shall include the following,
a. Design, manufacture and supply of Solar PV Power Plantb. Detailed planning for smooth execution of the projectc. Performance testing of the complete system & warranty of the
system for 5 years faultless operationd. Construction of Battery Room, Control Room and Power Plant
Fencing
e. Risk liability of all personnel associated with the implementationrealization of the project
f. Operation & Maintenance of the Power Plant for 5 Years including5 years of warranty period.
3. Technical Specifications of Major Components of Solar PVPower Plant
1 Solar PV modules and array2 Module mounting structures for Solar PV Modules3 Junction Boxes
4 Power Conditioning Unit5 Battery Bank with Accessories6 Solar Distillation Plant7 DC & AC Distribution Boards8 Cables and installation accessories9 Earthing and lightning protection10 Battery and Control Room
a. SOLAR PV MODULES & ARRAY
Crystalline high power cells shall be used in the Solar Photovoltaicmodule. Each solar module shall consist of redundantly interconnectedphotovoltaic cells and peak power rating shall not be less than 160W.However, higher wattage modules shall be preferred.
To connect the solar modules interconnection cables shall be provided.Photoelectric conversion efficiency of SPV module shall be greater than
13
-
8/7/2019 20100709-kreda-nit15
14/37
13%. Modules shall be made of high transmissivity glass front surfacegiving high encapsulation gain and silicon rubber edge sealant formodule protection and mechanical support.
All materials used shall have a proven history of reliable and stable
operation in external applications. It shall perform satisfactorily inrelative humidity up to 100% with temperatures between -30 Deg Cand +85 Deg C and with stand gust up to 200km/h from the back sideof the panel.
Solar module shall be crystalline type, employing laminationtechnology using established polymer (EVA) and tedlar laminate.
Sample modules, representative of the production processes employedin the manufacture of the offered module shall be in accordance withthe requirements of IEC 61215-Edition II for quality of crystalline silicon
solar cell modules, IEC 61730 (Part I and Part II). The bidder shallsubmit appropriate certificates.
Other General Requirements of PV module
The rated output power of any supplied module shall not vary morethan 3-5% from the average power rating of all modules.
The module frame shall be made of corrosion resistant materials,which are electrolytically compatible with the structural materialused for mounting the module.
Protective devices against surges at the PV module shall beprovided, if required. Low voltage drop bypass and / or blockingdiode(s) may also be provided, if required.
Module Junction box (weather resistant) shall be designed for longlife outdoor operation in harsh environment.
PV modules used in solar power plants must be warranted foroutput wattage, which should not be less than 90% at the end of 10years and 80% at the end of 25 years.
The solar modules shall have suitable encapsulation and sealingarrangements to protect the silicon cells from the environment. Thearrangement and the material of encapsulation shall be compatiblewith the thermal expansion properties of the silicon cells and themodule framing arrangement/material. The encapsulationarrangement shall ensure complete moisture proofing for the entirelife of the solar modules.
Each module shall have low iron tempered glass front for strengthand superior light transmission. It shall also have tough multi
14
-
8/7/2019 20100709-kreda-nit15
15/37
layered polymer back sheet for environment protection againstmoisture and provide high voltage electrical insulation.
The fill factor of modules shall not be less than 0.70.
Other balance of systems components (BoS) must qualify to thelatest edition of BIS or IEC standards issued in this regard.
Array capacity shall not be less than the designed capacity andnumber of modules required shall be worked out accordingly.
Each PV module must use a RF identification tag. The followinginformation must be mentioned in the RFID used on each module(This can be inside or outside the laminate, but must be able towithstand harsh environmental conditions.)
i. Name of the manufacturer of PV Moduleii. Name of the Manufacturer of Solar cellsiii. Month and year of the manufacture (separately for solar cells
and module)
iv. Country of origin (separately for solar cells and module)v. I-V curve for the modulevi. Wattage, Im, Vm and FF for the modulevii. Unique Serial No and Model No of the moduleviii. Date and year of obtaining IEC PV module qualification
certificateix. Name of the test lab issuing IEC certificatex. Other relevant information on traceability of solar cells and
module as per ISO 9000 series.
Data sheet shall be furnished duly filled as follows:
1) Mounting arrangement for Solar module :
2) Solar module frame material :
3) Module type :
4) Module dimensions :
5) No. of solar cells per module :
6) Solar cell manufacturer type :
7) Make of Solar module :
8) Peak power voltage (Vmp) at 25 Deg C :
9) Peak Power current (Imp) at 25 Deg C :
10) Open circuit voltage (Voc) at 25 Deg C :
11) Short circuit current (Isc) at 25 Deg C :
12) Weight of each module :
Orientation and Tilt of PV Module
Modules alignment and tilt angle shall be calculated to provide the maximum annualenergy output at site.
15
-
8/7/2019 20100709-kreda-nit15
16/37
b. MODULE MOUNTING STRUCTURE The array structure shall be made of hot dip galvanized MS angles of size not
less than 50 mm x 50 mm x 6 mm size. The minimum thickness ofgalvanization shall be at least 70 microns. All nuts & bolts shall be made ofvery good quality stainless steel. The minimum clearance of the lowest part ofthe module structure and the developed ground level shall not be less than
500 mm. Leg assembly of module mounting structure made of different diameter
galvanized tubes may be accepted. The work should be completed withsupply, fitting fixing of clamps, saddles, nut & bolts etc. While quoting therate, the bidder may mention the design & type of structure offered. All nuts &bolts shall be made of high quality stainless steel.
The structure shall be designed to allow easy replacement of any module andshall be in line with site requirements.
The structure shall be designed for simple mechanical and electricalinstallation. It shall support SPV modules at a given orientation, absorb andtransfer the mechanical loads to the ground properly. There shall be norequirement of welding or complex machinery at site.
The array structure shall be so designed that it will occupy minimum spacewithout sacrificing the output from SPV panels. At the same time it shouldwithstand wind speed up to maximum 200 km/h.
The drawings along with detailed design shall be submitted to KREDA forapproval before starting the execution work. The supplier/manufacturer shallspecify installation details of the PV modules and the support structures withappropriate diagrams and drawings. The work will be carried out as perdesigns approved by KREDA.
PCC ARRAY FOUNDATION BASE: The legs of the structures made with GIangles will be fixed and grouted in the PCC foundation columns made with1:2:4 mix of cement concrete. The minimum clearance of the lowest part ofany module structure shall not be less 500 mm from ground level. While
making the foundation design, due consideration shall be given to weight ofmodule assembly, maximum wind speed of 200 km/hr and seismic factors forthe site.
The bidder can visit the site before quoting rate for civil works. After taking into consideration all aspects of the site, condition of soil etc., the bidder shallquote for civil works. No extra claim shall be entertained at post project stage.The foundation design of module structure design shall be submitted toKREDA for approval. The work will be carried out as per designs approved byKREDA.
c. JUNCTION BOXES
The junction boxes shall be dust, vermin and waterproof and made of FRP / ABS /Thermo Plastic. The terminals shall be connected to copper bus bar arrangementof proper sizes. The junction boxes shall have suitable cable entry points fittedwith cable glands of appropriate sizes for both incoming and outgoing cables.Suitable markings shall be provided on the bus bar for easy identification andcable ferrules shall be fitted at the cable termination points for identification. Thejunction boxes shall have suitable arrangement for the following:
Combine groups of modules into independent charging sub-arrays that shallbe wired to the controller.
16
-
8/7/2019 20100709-kreda-nit15
17/37
Provide arrangement for disconnection for each of the groups.
Provide a test point for each sub-group for quick fault location.
To provide group array isolation.
The rating of the JBs shall be suitable with adequate safety factor to interconnect the Solar PV array.
Metal oxide variastors shall be provided inside the Array JunctionBoxes.
d. POWER CONDITIONING UNIT
As SPV array produces direct current, it is necessary to convert thisdirect current into alternating current and adjust the voltage levelsbefore powering equipment designed for nominal mains AC supply.Conversion shall be achieved using an electronic inverter and theassociated control and protection devices. All these components ofthe system are termed the Power Conditioning Unit or simply thePCU. In addition, the PCU shall also house MPPT (Maximum PowerPoint Tracker), to maximize Solar PV array energy input into theSystem.
PCU refers to combination of charge controller and inverter and shall besupplied as integrated unit or different units of charge controller andinverter depending on rating and size of the power plant.
Maximum Power Point Tracker (MPPT)
Maximum Power Point Tracker (Tracker) shall be integrated into thePCU to maximize energy drawn from the Solar PV array. The MPPT
should be microprocessor / micro-controller based to minimizepower losses. The details of working mechanism of MPPT shall bementioned.
The efficiency of the MPPT shall not be less than 94% and shall besuitably designed to meet array capacity.
Inverter
Inverters shall be of very high quality, having high efficiency and shall becapable of running in isolated mode. The inverter should be completelycompatible with the charge controller and distribution panel.
The inverter shall be designed for continuous, reliable power supply as per
specifications. The inverter shall have high conversion efficiency from 25percent load to the full rated load. The efficiency of the inverter shall be morethan 90% at full load and more than 80% at partial load (50%-75%). Thesupplier shall specify the conversion efficiency in the offer.
The inverter shall be designed for high altitude and extreme temperatures ofthe district of Leh.
The inverter shall have internal protection arrangement against any sustained
fault in the feeder.
17
-
8/7/2019 20100709-kreda-nit15
18/37
The dimension, weight, foundation details etc. of the inverter shall be clearlyindicated in the detailed technical specification.
The inverter shall have provision for input & output isolation.
Each solid-state electronic device shall have to be protected to ensure longlife of the inverter as well as smooth functioning of the inverter.
Supplier shall indicate tripping voltage & start up voltage for the inverters &this should be perfectly matched with the recommendation of batterymanufacturers.
The PCU shall be mounted on a suitable reinforced concrete pad inside controlroom not susceptible to inundation by water. All cable entry to and from thePCU shall be fully sheathed to prevent access of rodents, termites or otherinsects into the PCU from bottom/top of the PCU in the form of a detachablegland plate.
Under conditions with the battery in a Full State of Charge theavailable solar power shall supply the site load via the inverterwith the excess solar power (if any) being exported to the grid.
The contractor shall furnish details of proper operation, maintenance and
troubleshooting details to KREDA.
The contractor shall intimate KREDA prior to dispatch of the inverter forinspection. Shop tests on the inverter shall be conducted in the presence ofthe authorized representative of KREDA in order to verify the capacity andproper working of all control and protection arrangement.
TRANSMISSION AND DISTRIBUTION
The output voltage shall be 415 V, 3-ph, 50 Hz output with a single unit. T&D networkfor
these power plants shall be accordingly designed and installed by KREDA.
f. BATTERYBANK
The batteries shall be solar photo voltaic batteries of floodedelectrolyte, low maintenance, lead Acid and made of hardrubber/PP container.
The batteries shall use 2V/12V cells and battery capacity is to bedesigned at C10 rate with end cell cut off voltage of 1.80V / cell.
Battery terminals shall be provided with covers.
Batteries shall be provided with micro porous vent plugs withfloats.
Charging instructions shall be provided along with the batteries.
Suitable carrying handle shall be provided.
18
-
8/7/2019 20100709-kreda-nit15
19/37
A suitable battery rack with interconnections & end connectorshall be provided to suitably house the batteries in the bank. Thefeatures and dimensions of the battery rack shall be providedalong with the bid document.
The batteries shall be suitable for recharging by means of solarmodules via solar charge regulators.
Bidder shall mention the design cycle life of batteries at 80%,50% and 10% depth of discharge at 25 deg. C. .
The batteries shall be designed for operating in ambienttemperature of site in the district of Kargil.
The self discharge of batteries shall be less than 3 % per monthat 27 deg. C and less than 6% per month at 30 deg. C
The charge efficiency shall be more than 90% up to 70% state ofcharge.
The topping up frequency shall be > 6months.
The batteries shall consist of individual cells, which can becarried separately with ease while transporting.
Offered batteries shall comply to the following:
10 % of DOD: 7200 cycles50 % of DOD: 3000 cycles80 % of DOD: 1200 cycles
The Battery Bank shall be designed to provide 2 No Sun days autonomy. The minimum rating of the battery bank foreach type of power plant shall not be less than the ratingshown in system design details and BOM.Battery Rack & AccessoriesBattery interconnecting links shall be provided for interconnecting the
cells in series and in parallel as needed. Connectors for inter cellconnection (series / parallel) shall be maintenance free screws.Insulated terminal covers shall be provided.
g. DC & AC Distribution Boards
DC Distribution Board (DCDB)
19
-
8/7/2019 20100709-kreda-nit15
20/37
The DC DB shall be provided in between PCU and Solar Array.This can be integrated in the PCU also, to save space.
It shall have MCCB of suitable rating for connection anddisconnection of array input.
AC Distribution Board (ACDB) An ACDB shall be provided in between PCU and Loads. It shall have MCB/MCCB of suitable rating for connection and disconnection of
PCU from load.
It shall have MCBs to supply power to control room loads such asexhaust fans, lighting loads and power plug sockets.
It shall have energy meter to record energy supplied to loads
h. Cables and Accessories
All the cables shall be supplied conforming to IS 1554 / 694 Part 1 of1988 & shall be of 650 V/ 1.1 kV grade as per requirement. OnlyPVC/polyethylene copper cables shall be used.The size of the cables between array interconnections, array tojunction boxes, junction boxes to PCU etc shall be so selected to keepthe voltage drop and losses to the minimum.The bidder shall supply, installation accessories, which are required toinstall and successfully commission the power plant.
i. Earthing and Lightning Protection
Earthing: The array structure of the PV yard shall be groundedproperly using adequate number of earthing kits. All metal casing /shielding of the plant shall be thoroughly grounded to ensure safety ofthe power plant..Lightning: The SPV Power Plant shall be provided with lightning &over voltage protection. The main aim in this protection shall be toreduce the over voltage to a tolerable value before it reaches the PV or
other sub system components. The source of over voltage can belightning, atmosphere disturbances etc.
j. Battery Room, Control Room and Maintenance StaffQuarter
The building shall comprise at least the following room sizes:a) Battery Bank Room: 16- 0 X 58-0b) Control Room: 7-0 X 58-0
20
-
8/7/2019 20100709-kreda-nit15
21/37
c) Operator Room: 12-6 X 13-0d) Kitchen: 80X 10-6
Plinth and Underground: The building shall have a plinth height of 2-6 restingona mud mate of 4 thick cement concrete 1:4:8 mix. The plinth shall be 2 below theground level in 1:3:6 mix cement concrete blocks
Under Floors: There shall be a sand filling lining below a thermocol lining with alayer of polythene sheet (water barrier)
Flooring: 1.5 thick cement concrete flooring of 1:2:4 mix shall be laid with a neatfloating coat of neat cement
Super-Structure: The outer walls (except front south side wall) shall be doublewalled having 50 mm thick thermocol insulation for the resistance of heat flow.The outer wall shall be raised in stone masonry in cement mortar 1:6 mix and shallbe 1 thick. The inner layer of the wall shall be raised with precast hollow blocks of1:2:4 mix in 1:6 cement mortar. The front wall shall be a trombe wall, painted blackfor heating purposes. All the partitions and room walls shall be of solid blocks of1:3:6 mix raised in 1:6 cement mortar including the front south side wall.
Opening: The door shall be fully panelled and the windows fully glazed of firstclass kail wood resting in wooden frames
Roofing: 150 mm R.C.C slab shall be laid over ground floor as roofing. 350 mmthick layer of mud pushka shall be laid over the R.C.C. slab for insulationpurposes. The roof shall be local type with a slight slope to run the rain water withall side parapets.
Finishing: The walls shall be finished with cement plaster from inside and roughcast cement plaster from outside, with distempering from inside and cementplaster from outside. All exposed woodwork shall be polished with French Spiritpolish
Ceiling: The R.C.C slab shall be finished with cement lining and the whole ceilingshall be white washed with lime
Fencing: The fencing should be chain link fencing (type A) of size 50 X 50 mmmesh fixed in a frame 60 X 60 X 6 mm of equal angles; this should be embed inconcrete blocks with R-R (random rubble) masonry wall 2-0 above ground level
with 50 mm thick DPC. 1 no. steel gate should be provided and installed with thefencing. The fencing shall be constructed such that the SPV array is not in itsshadow area.
Lighting: 12 lighting points shall be provided in the control room/ battery bankbuilding and 8 security lighting shall be placed evenly around the SPV powerplant fencing. The security lighting should include a 3.5 metre pole, luminaryfixtures, lamp (CFL 15 W), cables, switch box and all items necessary forfunctionality. Erection of the security lighting poles shall be undertaken by thesuccessful bidder. All lighting shall be powered by the SPV power plant installed.3 nos. three-pin socket points shall also be installed in the operator room and thekitchen (2 in operator room, 1 in kitchen).
The bidder shall include cost of construction of the battery room, control room,maintenance staff quarter, local toilet facility, lighting and fencing of the SPV
power plant in the offer. The bidder can visit the site before quoting rate for civil works. After taking in toconsideration all aspects of the site, condition of soil etc., the bidder shall quote forall civil works. No extra claim will be entertained at post project stage. The workwill be carried out as per designs given by KREDA.
Refer to Annexure II for the details and drawings of above
4. Documentation
21
-
8/7/2019 20100709-kreda-nit15
22/37
Two sets of installation manual / user manual shall be supplied alongwith the each power plant. The manual shall include complete systemdetails such as array lay out, schematic of the system, inverter details,working principle etc. Step by step maintenance and troubleshooting
procedures shall be given in the manuals.
Detailed Estimate for SPV Building (42.5Kwp) under KREDA-Kargil
SI No. Particular of Work Rate Amount (R
1 Earth work in excavation over areas (exceeding 30 cm in depth, 1.5 m in
width as well as 10 sqm in plan) including disposal of excavated earth, and
lift upto 1.5 m, disposed earth to be levelled and neatly dressed.
Qty: Total = 346.00 m
3
Rs. 82.35/ m3 28,499/-
2 Earthwork in excavation in foundation trenches or drains (not exceeding
1.50m) in width as well as 10 sq. m on plan) including dressing of sides
and ramming of bottoms, lift up to 1.50 m, including taking out the
excavated soil and disposal of surplus excavated soil as directed
Qty: Total = 84.68 m3
Rs. 69.35/ m3 5,873/-
3 Providing and laying in position cement concrete of specified grade
excluding the cost of centering and shuttering - all work up to plinth level.
1:4:8 (1 cement: 4 fine sand: 8 graded stone aggregate 40mm nom. size
crushed)
Qty: Total = 25.88 m3
Rs. 1243.50/
m332,191/-
4 Providing and laying in position cement concrete of specified grade
excluding the cost of centering and shuttering - all work up to plinth level.
1:3:6 (1 cement: 3 fine sand: 6 graded stone aggregate 40mm nom. size
crushed)
Qty: Total = 76.87 m3
Rs. 1471.50/
m31,13,119/-
5 Random rubble masonry with hard stone from quarry in foundation and
plinth including levelling up with cement concrete 1:6:12 (1 cement: 6
coarse sand: 12 graded stone aggregate 20 mm nominal size) at plinth level
with cement mortar 1:6 (1 cement : 6 coarse sand)
Qty: Total = 66.60 m3
Rs. 1471.50/
m373,153/-
6 Providing and fixing upto floor five level precast cement concrete hollow
block including hoisting and setting in position with cement mortar 1:6 (1
cement: 6 coarse sand), cost of centering, shuttering and finishing smooth
with 6 mm thick cement plaster 1:3 (1 cement: 3 fine sand) on exposed
surfaces complete.
Qty: Total = 20.30 m3
Rs. 3160.00/
m364,160/-
22
-
8/7/2019 20100709-kreda-nit15
23/37
7 Providing and fixing upto floor five level precast cement concrete solid
block including hoisting and setting in position with cement mortar 1:6 (1
cement: 6 coarse sand), cost of centering, shuttering and finishing smooth
with 6 mm thick cement plaster 1:3 (1 cement: 3 fine sand) on exposed
surfaces complete.
1:3:6 (1 cement: 3 coarse sand:6 graded stone aggregate 20 mm nominal
size - crushed)
Qty: Total = 58.54 m3
Rs. 3065.20/
m31,79,447/-
8 Reinforced cement concrete work in roof upto floor five level excluding
the cost of centering, shuttering, finishing and reinforcement with 1:2:4 (1
cement: 2 coarse sand: 4 graded stone aggregate 20mm nominal size)
Qty: Total = 41.34 m3
Rs. 2444.40/
m31,01,054/-
9 Mud pushka roofing of damped brick earth on roofs laid to slope
consolidated and plastered with 25 mm thick mud mortar mixed with local
yakzes.
Qty: Total = 160.28 m2
Rs. 182.20/ m2 29,205/-
10 Reinforcement for R.C.C work including straightening, cutting, bending,
placing in position and binding all complete thermo-mechanically treated
bars (TMTB).
Qty: Total = 4339.98 kg
Rs. 26.30/ kg 1,14,141/-
11 Extra for every additional 1 cm thickness of mud pushka, 155 mm thick,
i.e. 6 extra layers. Area vide item 9.
Qty: Total = 961.73 m2
Rs. 4.50/ m2 4,328/-
12 Centering and shuttering including strutting, propping, etc. and removal of
form for:
a) Foundation, footings, bases of columns etc. for mass concrete
Qty: Total = 32.27 m2
b) Walls (any thickness) including attached pilasters, buttresses,
plinth, and string courses etc. vide item 4
Qty: Total = 225.17 m2
c) Lintels, beams, plinth beams, girders, bressumers and cantilevers
Qty: Total = 59.67 m2
d) Suspended floors, roofs, landings, balconies, and access platform
Qty: Total = 132.37 m2
e) Edge of slabs and breaks in floors and walls : edge length, under
Rs. 59.70/ m2
Rs. 109.15/ m2
Rs. 90.55/ m2
Rs. 105.75/ m2
Rs. 34.35/ m
1926/-
24,578/-
9,403/-
13,998/-
23
-
8/7/2019 20100709-kreda-nit15
24/37
20 cm wide
Qty: Total = 99.82 Rm 3,429/-
13 Sand filling in rooms under flooring with watering and ramming
Qty: Total = 36.15 m3Rs. 126.00/ m3 4,555/-
14 Cement concrete flooring 1:2:4 (1 cement: 2 coarse sand: 4 graded stone
aggregate) finished with a floating coat of neat cement including cement
slurry, but excluding the cost of nosing of steps. etc. complete - 50 mm
thick cement concrete flooring with 20 mm nominal size stone
Qty: Total = 165.84 m2
Rs. 142.00/ m2 23,550/-
15 Providing and fixing glass strips in joints of terrazzo/cement concrete floor
40 mm wide X 6 mm thick
Qty: Total = 590.73 m
Rs. 17.40/ m 10,279/-
16 Providing woodwork in frames of doors, window, clerestory windows andother frames, wrought framed and fixed in position - first class kail wood
Qty: Total = 1.21 m3
Rs. 21451/ m3 26,011/-
17 Providing and fixing panelled or panelled and glazed shutters for doors,
windows, and clerestory windows including ISI marked black enamelled
M.S. butt hinges with necessary screws, excluding panelling which will bepaid for separately - 35 mm thick 1st class kail wood
Qty: Total = 33.67 m2
Rs. 696.05/ m2 23,437/-
18 Providing and fixing panelling or panelling and glazing in panelled orpanelled and glazed shutters for door, windows, and clerestory windows
(area of opening for panel inserts excluding portion inside grooves orrebates to be measured). Panelling for panelled or panelled glazed shutters,
35 mm 1st class kail wood
Qty: Total = 24.33 m2
Rs. 559.90/ m2 13,626/-
19 Pebble dash plaster up to 10 mtr. height above ground level with a mixture
of washed pebbles or crushed stones 6mm to 12.5 mm nominal size dashedover and including fresh plaster in two layers, under layer 12 mm cement
plaster 1:4 (1 cement: 4 coarse sand) and top layer 10 mm cement plaster
with cement mortar 1:3 (1 cement: 3 fine sand) mixed with 10% finely
grounded hydrated lime by volume of cement.
Qty: Total = 248.01 m2
Rs. 129.90/ m2 32,044/-
20 12 mm thick cement plaster finished with a floating coat of neat cement of
mix 1:4 (1 cement: 4 fine sand)
Qty: Total = 521.70 m2
Rs. 71.50/ m2 37,301/-
21 6 mm thick cement plaster to ceiling of mix 1:3 (1 cement: 3 fine sand) Rs. 44.55/ m2 6,563/-
24
-
8/7/2019 20100709-kreda-nit15
25/37
Qty: Total = 147.72 m2
22 Distempering with oil bound washable distemper of approved brand andmanufacture to give an even shade. New work (2 or more coats) over and
including priming coat with cement primer. Quantity as per item 20 and 21
Qty: Total = 669.01 m2
Rs. 30.40/ m2 20,338/-
23 Finishing walls with water proofing cement paint of approved brand andmanufacture to give an even shade. New work (2 or more coats applied @
3.84 kg/10 sqm).
Qty: Total = 248.01 m2
Rs. 45.25/ m2 11,223/-
24 French Spirit polishing on wood work: two or more coats on new works
including a coat of wood filler
Qty: Total = 113.92 m2
Rs. 69.70/ m2 7,941/-
25 Painting with aluminium paint of approved brand and manufacture to give
an even shade, two or more coats on new work
Qty: Total = 30.65 m2
Rs. 22.20/ m2 681/-
26 Providing 40 X 5 mm flat iron hold fast 40 cm long including fixing to
frame with 10 mm diameter bolts, nuts and wooden plugs and embedding
in cement concrete blocks 13 X 10 X 15 cm, 1:3:6 mix (1 cement: 2 coarse
sand: 6 graded stone aggregate 20 mm nominal size)
Qty: Total = 135 Nos.
Rs. 37.25/ no. 5,042/-
27 Providing and fixing bright finished brass tower bolts (barrel type) with
necessary screws etc. complete for wooden door and windows
250 X 10 mm
a) 17 nos.
100 X 10 mm
b) 17 nos.
Rs. 109.20/no.
Rs. 48.55/ no.
1856/-
825/-
28 Providing and fixing aluminium tower bolts, ISI marked (anodized anodiccoating not less than grade AC 10 as per IS:1868) transparent or dyed to
required colour or shade with necessary screws etc. complete: in
aluminium frames/shutters 100 X 10 mm
Qty: Total = 56 Nos.
Rs. 22.05/no. 1235/-
29 Providing and fixing bright finished brass 100 mm mortice latch and lockwith 6 levers and a pair of lever handles with necessary screws etc.
complete (best make of approved quality)
Qty: Total = 6 nos.
Rs. 253.20/ no. 1519/-
30 Providing and fixing ISI marked oxidized M.S sliding door bolts with nut Rs. 51.95/no. 571/-
25
-
8/7/2019 20100709-kreda-nit15
26/37
and screws etc. complete 250X16 mm
Qty: Total = 11 nos.
31 Providing and fixing ISI marked oxidized M.S handles conforming to
IS:4992 with necessary screws etc. complete 125 mm/100mm
a) Inner Doors (125 mm)Qty: Total = 8 nos.
b) Windows (100 mm)
Qty: Total = 4 nos.
Rs. 9.20/ no.
Rs. 7.00/ no.
74/-
28/-
32 Providing and fixing aluminium handles ISI marked anodized (anodic
coating not less than grade AC 10 as per IS: 1868) transparent or dyed to
required colour and shade with necessary screws etc. complete 125 mm
Qty: Total = 10 nos.
Rs. 33.65/no. 337/-
33 Providing and fixing aluminium hanging floor door stopper ISI markedanodized (anodic coating not less than grade AC 10 as per IS: 1868)
transparent or dyed to required colour and shade with necessary screws
etc., twin rubber stopper
Qty: Total = 8 nos.
Rs. 46.15/no. 369/-
34 Providing and fixing bright finished brass casement window
stopper/fastener with necessary screws etc. complete
Qty: Total = 14 nos.
Rs. 30.35/no. 425/-
35 Providing and fixing nickel plated M.S pipe curtain rods with nickel plated
brackets - 25 mm diameter (heavy type)
Qty: Total = 17.47 m
Rs. 49.60/ m 867/-
TOTAL 10,29,201/-
36 Add 145% above on all items as tender appreciation
25,21,542/-
NON SCHEDULED ITEMS
37 Providing and laying thermocol lining of 50 mm thickness in between
double walls
Qty: Total = 261.92 m2
Rs. 500/ m2 1,30,961/-
38 Providing and laying of polythene sheet (water barrier)
Qty: Total = 118.66 m2
Rs. 50/ m2 5,933/-
GRAND
TOTAL 26,58,436/-
Construction of Chain Link Fencing around SPV Solar Power Plant
26
-
8/7/2019 20100709-kreda-nit15
27/37
S No. Particulars Specification
1 Earthworks in excavation over areas (exceeding 30cm in depth, 1.5 mtr. in width as well as 10 sqm on
plan) including disposal of excavated earth lead upto1.5 mtr and lift upto 1.5 mtr disposed earth to be level
Size of Trench =.50 m X .60 m X length
2 Providing and laying in position cement concrete of
specified grade excluding the cost of centering and
shuttering all work upto plinth level in 1:4:8 (1cement: 4 coarse sand: 8 graded stone aggregate 40
mm nominal size)
Bed Concrete =
.50 m X .10 m X length
3 Providing and laying in position cement concrete of
specified grade excluding the cost of centering and
shuttering, all work upto plinth level in 1:3:6 (1cement: 3 coarse sand: 6 graded stone aggregate 20
mm nominal size)
Concrete Blocks =
.50 m X .50 m X 1.0 m
each
4 Random rubble masonry with hard stone from quarry
in foundation and plinth including levelling up with
cement concrete 1:6:12 (1 cement: 4 coarse sand: 12
graded stone aggregate 20 mm nominal size) at plinthlevel with cement mortar 1:6 (1 cement : 6 coarse
sand)
Masonry Wall Size =
.50 m X 1.0 m X length
5 Centering and shuttering including strutting, propping,
etc. and removal of form retaining wall/other wall of
any thickness upto plinth level
6 Providing and laying DPC 1:2:4 mix 40 mm thick, 20
mm nominal size aggregate7 Pointing on stone work with 1:3 mix (flush pointing)
8 Steel work in built up section (riveted and bolted)framed including cutting, hoisting, and fixing in
position and applying primer coat using steel primer
and nuts and bolts, complete job.
Size of fencing =40 m X 40 m X 6 mm
equal angles for
horizontal and verticalposts and flat iron 20
mm X 6 mm
9 Providing and fixing chain link fencing of size
(2X2) mesh galvanized steel wire (complete job)
10 Carriage of materials from source/stores to the site of
work by mechanical transport and by head load likecement, chain link fencing, stone aggregate and sand
etc. (complete job)
11 Provision of 1 No. Steel Gate of size 8-0 X 14-0
using 60 X 60 X 5 mm equal angle frames with 6 mmthick M.S. Sheet including red oxide primer coating
and painting (complete job)
Total Estimated Cost (4500 Rs./Rm for Fencing +
27
-
8/7/2019 20100709-kreda-nit15
28/37
35,000 Rs. For 1 No. Steel Gate)
Total length of the 42.5Kwp SPV power palnt to be
quoted=Rs 150Mtrs
PRICE BID FORMAT(42.5Kwp)
COST ESTIMATE FOR LIGHTING WORKS IN SPV PLANT (42.5 kWp)
Si No. Description Rate Amount (Rs.)
1 Providing and fixing lighting points, completejob
Qty: Total = 12
Rs. 400/ each 4,800.00
2 Providing and fixing 3 pin socket points,complete job
Qty: Total = 3
Rs. 500/ each 1500.00
3 Providing security lighting, 3.5 metre poleabove ground level, mild steel,
with weather proof paint finishing, mounting
hardware, luminary fixtures,
15 W lamp, cables and accessories, complete
job
Qty: Total = 8
Rs. 9000/ each 72,000.00
GRAND
TOTAL78,300.00
Detailed Estimate for Local Toilet Facility for SPV Power PlantParticular of work
Earth work in excavation over areas (exceeding 30
Si No. Description Price Bid(Rs.)
1 Total Cost of Systems as per the Bill of Materials
inclusive of all taxes applicable (F.O.R. at site)2 Installation and Commissioning including
construction of control room, battery bankroom, maintenance staff room, fencing, localtoilet and any other civil/electrical works forcompletion of the Job sticky as per the design& schedule given in the NIT
3 Operation and Maintenance for 5 years
GRAND TOTAL
28
-
8/7/2019 20100709-kreda-nit15
29/37
cm in depth,1.5 m in width as
well as 10 sqm in plan )
including disposal of excavated
earth, and lift up to 1.5 m
disposed earth to be levelled and
neatly dressed.
Qty ;total =44.57m3
Earth work in excavation in foundation trenches or
drains ( not exceeding 1.50m) in
width as well as 10 sq.m on plan
) including dressing of sides and
ramming of bottoms, left up to
1.50m, including taking out the
excavated soil and disposal of
surplus excavated soil as
directedQty;
total =6.19m3Providing and laying in position cement concrete of
specified grade excluding the
cost of centring and shuttering
all work up to plinth level.1:4:8( 1 cement : 4 fine sand : 8
graded stone aggregate 40mm
nom. Size crushed)
Qtytotal=1.23m3
Random rubble masonry with hard stone fromquarry in foundation and plinth
including levelling up withcement concrete 1:6:12( 1
cement:6 coarse sand : 12graded stone aggregate 20 mm
nominal size ) at plinth level
with cement mortar 1:6 ( 1
cement: 6 coarse sand )
Qty
total= 33.18m3
Providing and fixing up to floor five level precast
cement concrete solid block
including hoisting and setting in
position with cement mortar 1:6( 1 cement :6 coarse sand) , cost
of centring , shuttering and
finishing smooth with 6 mm
thick cement plaster 1:3 ( 1
cement : 3 fine sand) on exposed
surface complete .
1:3:6 ( 1 cement : 3 coarse sand :6 graded stone
29
-
8/7/2019 20100709-kreda-nit15
30/37
aggregate 20mm nominal size
crushed )
Qty total =
3.05m3
Reinforced cement concrete work in roof up to
floor five level excluding the
cost of centring , shuttering ,finishing ,and reinforce cement
with 1:2:4 ( 1cement :2 coarse
sand :4 graded stone aggregate
20 mm nominal size )
Qty total
= 3.42m3
Reinforce cement for R.C.C work including
straightening , cutting ,bending,
placing in position and binding
all complete , thermo ,
mechanically treated bars
( TMTB),QTY
Total=342.5kg
Cantering and shuttering including strutting ,
propping etc. And removal of
form for;
a) Foundation , footings ,bases of columns etc. For
mass concert
Qty total =1.62m2
b) Suspended floors ,roofs, landing, balconies and
access platformQty total=9.73 m2
c) Edge of slabs and breaks in floors and walls andedge length under 20cm wide
Qty total =121.64Rm
Rs 59.70/m2
Providing wood work in frames of doors ,window , clerestory, windows
and other frames , wrought
framed and fixed in position ,
first class kail woodQty
total= 0.10m3Providing and fixing panelled or panelled and
glazed shutters for doors ,
windows , and clerestorywindows including ISI
marked black enamelled M.S.
butt hinges with necessaryscrews , excluding panelling
30
-
8/7/2019 20100709-kreda-nit15
31/37
which will be paid for
separately -35mm thick 1st
class kail wood
Qty
total= 1.21m2
Providing and fixing panelling or panelling and
glazed in panelled or panel and
glazed shutters for door ,
windows , and clerestory
windows ( area of opening for
panel inserts excluding portion
inside grooves or rebates to bemeasured ) panelling for
panelled or panelled glazed
shutters , 35mm 1st class kail
wood
Qty total 2.27m2
Pebble dash plaster up to 10mtr .height above
ground level with a mixture of
washed pebbles or crushed stone
6mm to 12.5 mm nominal size
dashed over and including fresh
plaster into layers , under layer
12mm cement plaster 1:4 ( 1
cement : 4 coarse sand ) and top
layer 10mm cement plaster with
cement mortar 1:3 ( 1 cement :3
fine sand ) mix with 10 %finally grounded hydrated lime
by volume e of cement
Qty
total= 37.16m2
12 mm thick cement plaster finished with a floating
coat of heat cement of mix 1:4
( 1 cement :4 fine sand)
Qty
total=29.86m2
Distempering with oil bound washable distemper of
approval band and manufacture
to give an shade. new work ( 2or more coats)over and
including priming coat with
cement primer. Quantity as per
item 20 & 21.
Qty.
Total=29.86 m2
Finishing walls with water proofing cement paint of
approved brand and manufacture
31
-
8/7/2019 20100709-kreda-nit15
32/37
to give an even shade. New
work (2 or more coats applied @
3.84 kg/ 10sqm.
Qty.
Total=37.16m2
French spirit polishing on wood work: two or more
coats on new work including acoat of wood filler
Qty.
Total=4.85m2
Painting with synthetic enamel paint of approved
brand and manufacture to give
an even shade, two or more
coats on new word (on wood
work)
Qty.
Total=4.85m2
Providing 40 X 5 mm flat iron hold fast 40 cm. longincluding fixing to frame with
10mm. diameter bolts, nuts and
wooden plugs and embedding in
cement concrete blocks 13 X 10
X 15cm, 1: 3:6 mix (1
cement:2coarse sand:6 graded
stone aggregate 20mm nominal
size)
Qty.
Total=6Nos
Providing and fixing bright finished brass towerbolts (barrel type) with
necessary screws etc. Complete
for wooden door and windows
250 X 10 mm
a) 6X1=2Nos.
Providing and fixing aluminium tower bolts, ISI
marked (anodized anodic
coating not less than grade AC
10 as per ISI:1868) transparentor dyed to required colour or
shade with necessary screws etc.
Complete: in aluminium
frames/shutters 100X10 mm
Qty.
Total=2Nos.
32
-
8/7/2019 20100709-kreda-nit15
33/37
Add 145% above on all items as tender appreciation
ANNEXURE IIDetails drawing of control room ,site plan of SPV Power plant
42.5 kWp & local lantern