M0.01 HVAC - SCHEDULES FILTER SCHEDULE SYSTEM 2 2 UNIT DESIGNATION TYPE FILTER POSITION CFM INITIAL RESISTANCE -H O FINAL RESISTANCE -H O MAX FACE VELOCITY DIMENSIONS EFF.-DUST SPOT (ATMOS. DUST) REMARKS: OTHER MOISTURE CONDENSATE DRAIN LINE HOT WATER SUPPLY HOT WATER RETURN CHILLED WATER SUPPLY CHILLED WATER RETURN MCD HWS HWR CHWS CHWR TEE LATERAL PIPE TURNING UP PIPE TURNING DOWN DIRECTION OF WATER FLOW GUIDE ANCHOR RECTANGULAR DUCT TURNING DOWN ROUND DUCT TURNING DOWN REGISTER TAPPING INTO BOTTOM OF DUCT ADJUSTABLE T’STAT CONCEALED T’STAT MANUAL VOLUME DAMPER SUPPLY DIFFUSER (4-WAY) MVD S T FD 1. 2. FILTERS TO MATCH UNIT CASING SIZE. RG/EG RF/EF RE/EE RD/ED RC/EC RB/EB RA/EA SYMBOL NECK 6" SQ 8" SQ 10" SQ 12" SQ 14" SQ 18" SQ 22" SQ FACE 8"x8" 75 300 1250 1700 CFM 200 540 700 SP .05 .05 .04 .06 .07 .07 .06 RUNOUT NC 2. 1. PERFORMANCE BASIS: EGG-CRATE RETURN & EXHAUST REGISTERS 28 28 27 28 28 27 25 10"x10" 12"x12" 14"x14" 18"x18" 20"x20" 24"x24" 10"x6" / 8"l 26"x12" / 18"l 24"x10" / 16"l PIPING LEGEND LOUVERED-FACE CEILING DIFFUSER SCHEDULE PERFORMANCE BASIS: 1. 2. 3. SYMBOL ADAPTOR/ NECK SIZE FACE SIZE MAX CFM MAX NC MAX SP THROW RUNOUT SIZE SA SB SC SD SE SJ SK 8" 10" 12"x12" 15"x15" 15"x15" 24"x24" 24"x24" 24"x24" 48"x24" 110 230 420 500 650 150 250 20 20 25 28 26 30 30 .07 .07 .08 .10 .09 .10 .09 4-WAY BLOW 4-WAY BLOW 4-WAY BLOW 4-WAY BLOW 4-WAY BLOW 8" 10" LAMINAR LAMINAR 6" / 6"x6" 8" / 9"x9" 10" / 12"x12" 12" / 12"x12" 12" / 15"x15" 6" / 8"x4" 8" / 10"x6" 10" / 12"x8" 12" / 16"x8" 12" / 18"x8" SMOKE DAMPER DUCT SMOKE DETECTOR VARIABLE VOLUME BOX MANUAL VOLUME DAMPER FULL RADIUS TURN DUCT TERMINATION 45” FULL RADIUS TURN MVD VAV SD SUPPLY FAN RETURN FAN MAX RPM E.S.P. MINIMUM H.P. ELECTRICAL POWER TYPE MAX OPERATING WEIGHT (LBS) DIMENSIONS (L"xW"xH") UNIT No. TOTAL CFM O.A. MINIMUM O.A. MAXIMUM INTERNAL S.P. EXTERNAL S.P. TOTAL S.P. MINIMUM HP ELECTRICAL COOLING COIL REMARKS: SERVICE CFM MAXIMUM FACE VELOCITY MAX WTR P.D. FT. IN H2O MAX AIR S.P. IN H2O CONTROL VALVE POWER TYPE MANUFACTURER G.P.M. GTH (BTU/HR) CHILLED WATER ROOFTOP UNIT SCHEDULE CFM MAX RPM INDICATES HIGH EFFICIENCY MOTOR REFER TO SPECIFICATIONS FOR ACCESSORIES 2. 1. 3. E.A.T. DB/WB (”F) DUCTWORK LEGEND INDICATES A SIZE "A" EXHAUST REGISTER SET FOR 50 CFM INDICATES A SIZE "A" SUPPLY REGISTER SET FOR 50 CFM INDICATES A SIZE "A" RETURN REGISTER SET FOR 50 CFM EA 50 RA 50 SA 50 EXHAUST GRILLE RETURN GRILLE SQUARE ELBOW W/ TURNING VANES DUCT TURNING DOWN TO SIDEWALL REGISTER AT FLOOR BRANCH TAP OFF MAIN W/45 DEG BOOT FITTING OR SPIN-IN FITTING W/DAMPER (LOW PRESSURE) TRANSITION IN DUCT (NOT DIRECTION OF AIRFLOW) FIRE DAMPER FSD FIRE/SMOKE DAMPER DSD MEDIUM PRESSURE TEE UNDERCUT DOOR 3/4" (UNLESS OTHERWISE NOTED) VARIABLE VOLUME TERMINAL BOX REFRIGERANT MACHINE SCHEDULE DESIGNATION TYPE CAPACITY TONS ( NOMINAL ) COND TEMP CONNECTED LOAD TONS GPM LOW AMBIENT TEMP COOLER EWT LWT SCALE FACTOR MAX PD FT CAPACITY TON @ SCHEDULED CONDITIONS No. OF COMPRESSORS MIN. STAGES UNIT ELECTRICAL MAX. FUSE WIRE SIZE AMPS POWER MANUFACTURER MODEL NO. REMARKS: 1 REFER TO SPECIFICATIONS AND DETAILS FOR ACCESSORIES AND PIPING CONNECTIONS. PROVIDE FREEZE PROTECTION CIRCUIT FOR EVAPORATOR. 1. 2. DESIGNATION SERVICE TYPE NPSH TEMPERATURE CASING WORKING PRESS MIN MOTOR HP VOLTAGE/PHASE RPM GPM MANUFACTURER POWER TYPE SIZE OTHERS REMARKS: HUMIDIFIER SCHEDULE COMPUTER ROOM AC UNIT PUMP SCHEDULE TOTAL BTUH SENSIBLE BTUH TOTAL CFM CAP #/HR EVAPORATOR UNIT COOLING CAPACITY MAX FUSE SIZE MIN. CIRCUIT AMPS HUMIDIFIER TYPE HEATING TYPE INDOOR UNIT NO. MANUFACTURER FAN HP UNIT ELECTRICAL FILTER EFFICIENCY STAGES CONDENSING UNIT MODEL ELECTRICAL MAX FUSE MCA POWER TYPE POWER TYPE CAPACITY (KW) APPROXIMATE SIZE (LxWxH) LIQ/SUCTION LINE SIZE NOTES NOTES EAWB-”F EADB-”F TYPE CAPACITY-LB/HR MANIFOLD LENGTH ACCESSORIES: DESIGNATION SERVICE ACCESSORIES MANUFACTURER CFM SERIES 80 INLINE 1 PROVIDE PROGRAMMABLE T’STAT PROVIDE STAINLESS STEEL DRAIN PAN FOR HUMIDIFER PROVIDE FRACTIONAL MOISTURE CONDENSATE PUMP. 2 1 1 REFER TO SPECIFICATIONS FOR ACCESSORIES. INDICATES HIGH EFFICIENCY MOTOR. REFER TO SPECIFICATIONS AND DETAILS FOR PIPING, VALVES AND ACCESSORIES. 2. 1. 100 100 INDICATES EXISTING AIR DISTRIBUTION DEVICE TO BE REBALANCED TO 100 CFM EACH. TITUS OMNI OR APPROVED EQUAL. PERFORATED PANELS (SJ, SK) BASED ON TITUS TLF-AA/KRUEGER SERIES 5000 O.R.D. CONTRACTOR TO USE DUCT SPIN-IN FITTINGS WITH MANUAL VOLUME DAMPER EQUAL TO FLEXMASTER CBD OR FLEXMASTER STOD (OR APPROVED EQUAL) FOR CIRCULAR DUCT AND STANDARD SIDE TAKE OFF WITH MANUAL VOLUME DAMPER FOR RECTANGULAR RUNOUT. SEE DETAIL. 4. FACE SIZE SHALL BE 24"X24" IN ALL LAY IN CEILING LOCATIONS TO FIT WITHIN GRIDS. 8"x4" / 6"l 14"x6" / 10"l 16"x8" / 12"l 18"x8" / 14"l SHUTOFF VALVE LTWS LTWR S-60 LOW TEMP CHILLED WATER WATER SUPPLY LOW TEMP CHILLED WATER WATER RETURN GC STEAM LINE-STEAM PRESSURE (60 PSI) GRAVITY CONDENSATE RETURN PCR PUMPED CONDENSATE RETURN TITUS MODEL 50-FS WITH 1/2"x1/2" EGG-CRATE CORE OR EQUAL (EXAMPLE RA). CONTRACTOR TO USE DUCT SPIN-IN FITTINGS WITH MANUAL VOLUME DAMPER EQUAL TO FLEXMASTER CBD OR FLEXMASTER STOD (OR APPROVED EQUAL) FOR CIRCULAR DUCT AND STANDARD SIDE TAKE OFF WITH MANUAL VOLUME DAMPER FOR RECTANGULAR RUNOUT. SEE DETAIL. 3. FACE SIZE TO BE 24"X24" IN ALL LAY IN CEILING LOCATIONS TO FIT WITHIN THE GRID. PF-OR AHU-OR 1 PRE 8,980 0.25" 0.85" 500 60% NOTE #1 FILTERS TO MATCH UNIT CASING SIZE UTILIZING ALL 24"x24" FILTERS. FF-OR RTU-OR 2 FINAL 8,980 0.60" 1.2" 280 90% 4’W x 8’H 2 90% EFFICIENT, 12" THICK CARTRIDGE 1 60% EFFICIENT, 4" THICK CARTRIDGE VFD VFD COIL L.A.T. DB/WB (”F) 4. PROVIDE UNIT WITH INTERNAL LIGHTS ON SINGLE CIRCUIT IN THE SUPPLY FAN AND ACCESS SECTIONS. 5. AHU SHALL BE PROVIDED WITH STEAM GRID HUMIDIFIER. SEE SEPARATE HUMIDIFIER SCHEDULE. PROVIDE ULTRA-SORB DISPERSION TUBES. ROWS / FINS PER INCH CFM MAXIMUM FACE VELOCITY MAX WTR P.D. FT. IN H2O MAX AIR S.P. IN H2O CONTROL VALVE G.P.M. GTH (BTU/HR) E.A.T. DB/WB (”F) COIL L.A.T. DB/WB (”F) ROWS / FINS PER INCH GLYCOL COOLING COIL CFM MAXIMUM FACE VELOCITY MAX WTR P.D. FT. IN H2O MAX AIR S.P. IN H2O CONTROL VALVE G.P.M. GTH (BTU/HR) E.A.T. DB/WB (”F) COIL L.A.T. DB/WB (”F) ROWS / FINS PER INCH REHEAT COIL FILTERS SEE SCHEDULE AIR BLENDER SUPPLY AIR TURNDOWN (CFM) RETURN AIR TEMPERATURE (”F) FREEZE STAT SET POINT (”F) WINTER DESIGN TEMP. ”F) REQUIRED MIXING EFFECTIVENESS MODEL UP DISTANCE DOWN DISTANCE MAX. AIR P.D. IN H20 CONFIDENCE RATING STARTER TYPE ROTARY SCROLL 3. PROVIDE BACNET CHILLER CONTROLS GATEWAY TO INTERFACE WITH EXISTING SIEMENS BUILDING EMS. 6. E.W.T. (”F) / L.W.T. (”F) 8,890 450 78.5” / 65.7” 52.0” / 51.8” 391,000 65.2 44”F/56”F 6/10 15 0.75" 2-WAY E.W.T. (”F) / L.W.T. (”F) 8,980 450 52.0” / 51.8” 42.0” / 41.8” 210,250 35 34”F/46”F 8/10 15 0.75" 3-WAY E.W.T. (”F) / L.W.T. (”F) 7,455 70”F 36”F 22”F 64% AB30 (x2) 9" 30" 0.1" 95% 6. 7. PROVIDE ONE VFD TO CONTROL A SINGLE FAN ARRAY. (EX. AHU-OR SHALL HAVE ONE VFD FOR SUPPLY FAN ARRAY & ONE VFD FOR RETURN FAN ARRAY.) TDH FT H2O STEAM PRESSURE H-OR AHU-OR STEAM 8,980 200 1 AS REQ’D 25 DRISTEAM SOUND ATTENUATOR SCHEDULE IDENTIFICATION SYSTEM DIMENSIONS MAX. S.P. DROP DYNAMIC INERTION LOSS MANUFACTURER MODEL QUANTITY 28"x18"x36"L OR BOXES 0.15" 7-8-11-13-18-24-17-10 VIBRO-ACOUSTICS RFMB-LV-F2 REFER TO FLOOR PLANS SA-H 16"x12"x36"L OR BOXES 0.15" 7-8-11-13-18-24-17-10 VIBRO-ACOUSTICS RFMB-LV-F2 REFER TO FLOOR PLANS SA-CV FAN SCHEDULE FAN NUMBER SERVICE TYPE CFM MAX FAN RPM MAX OUTLET VEL/TS SIZE MIN MOTOR HP ELECTRICAL INLET SCREEN OUTLET SCREEN INLET DAMPER-TYPE OUTLET DAMPER-TYPE OTHER POWER TYPE MANUFACTURER REMARKS: SP-IN H2O DOWNBLAST CENTRIFUGAL 1 CHWP-OR-1 RM-OR 1 1 1 / 2 x 1 1 / 2 50 55’ -- 42”F 150 2 460/3/60 1750 NORMAL B&G --- CHWP-OR-2 RM-OR 1 1 1 / 2 x 1 1 / 2 50 55’ -- 42”F 150 2 460/3/60 1750 NORMAL B&G --- AHU-1 TRANE 8,100 LBS. 218"L x 57"W x 88"H C.V.O.R./HYBRID O.R. 8,980 1,750 8,980 2x1 PLENUM ARRAY 1,750 4.25" 3.0" 7.25" 10 EACH 460/3/60 EMERGENCY YES 2x1 PLENUM ARRAY 7,230 1,600 0.75" 3 EACH 460/3/60 EMERGENCY YES RAF-OR IS DETACHED FROM AHU-OR. RAF-OR WEIGHT OF 3,600 LBS IS NOT INCLUDED IN OVERALL UNIT WEIGHT SHOWN. 70"L x 57"W x 88"H NOT INCLUDED IN OVERALL DIMENSIONS OF UNIT. FINAL FILTER SECTIONS ARE EXTERNAL TO THE UNIT AND ARE CALCULATED AS INTERNAL PRESSURE DROPS. FF-OR WEIGHT OF 1,600 LBS IS NOT INCLUDED IN OVERALL WEIGHT SHOWN. 48"L x 58"W x 103"H IS NOT INCLUDED IN OVERALL DIMENSIONS OF UNIT. 3 FUEL OIL SYSTEM TYPE FUEL CAPACITY-GPH MAX DISCHARGE VOLTAGE REMARKS: MOTOR HP POWER TYPE 1. OTHER PRESSURE (PSI) FOPS-1 NO. 2 FUEL OIL 400 50 3/4 480/3/60 EMERGENCY NOTE 2 2. 3. PUMP PUMP SET FOPS-1 TO SERVE BOILERS AND GENERATORS. CONTRACTOR SHALL FURNISH ONE TANK FULL OF FUEL OIL AND REFILL TO REPLACE FUEL OIL USED FOR TESTING EQUIPMENT AT END OF PROJECT. UNIT NO. E.S.P. IN H O MANUFACTURER MODEL NO. TOTAL CFM TOTAL BTUH O.A. CFM 2 MINIMUM H.P. ELECTRICAL MAX FUSE CONDENSING UNIT MODEL COOLING CAPACITY O.A.D.B. ^F COND. UNIT ELECTRICAL M.C.A. MAX FUSE FILTER ACCESSORIES REMARKS HEAT PUMP A/C SYSTEMS LINE SIZES (HOT GAS - LIQUID) AUX. KW HEATER @ 208 SENSIBLE BTUH 1. 2. 3. PROVIDE UNIT WITH PROGRAMMABLE T’STAT. INDOOR UNIT TO HAVE SINGLE POINT POWER CONNECTION. HEAT PUMP HEATING CAP. @ 47^F MCA AC-1 TRANE 1,200 0 0.5" 1/2 18,500 N/A 208/1/60 5 15 CU-1 4TWB3036 35,300 26,600 95 208/1/60 18 30 1" THROWAWAY 7/8" - 3/8" UNITS TO BE EQUIPPED WITH DUCT FIRESTATS IN SUPPLY DUCTWORK. FIRESTATS TO SHUT DOWN UNITS WHEN ACTIVATED. AC-CATH LIEBERT MMD-36 48"Lx24"Wx18"H 33,200 26,900 72” 60” 1,250 1/2 460/3/60 20 16.5 EMERGENCY STEAM GENERATNG 4.3 ELECTRIC 5.6 1 30% CU-CATH PFH037 460/3/60 15 7.8 EMERGENCY 3/8" - 7/8" 1,2 & 3 AC-OR LIEBERT MMD-36 48"Lx24"Wx18"H 33,200 26,900 72” 60” 1,250 1/2 460/3/60 20 16.5 EMERGENCY STEAM GENERATNG 4.3 ELECTRIC 5.6 1 30% CU-OR PFH037 460/3/60 15 7.8 EMERGENCY 3/8" - 7/8" 1,2 & 3 EF-OR GENERAL 1 1750 0.5" 730 3,441 180 ACEB 1/3 120/1/60 NO YES BACKDRAFT NONE CURB EMERGENCY COOK EF2-1 GENERAL 1 1775 0.5" 741 3,491 180 ACEB 1/3 120/1/60 NO YES BACKDRAFT NONE CURB EMERGENCY COOK RM-OR 1 30 95”F 32”F 17.5 GLYCOL 35 46”F 34”F 17.5 0.0001 15 2 2 460/3/60 90 69.9 REDUCE VOLTAGE NORMAL TRANE CGAM-30 8,980 450 42.0” 52.0” 97,500 9.8 150”F/130”F 1/10 5 0.75" 2-WAY PUMP SETS FOPS-1 TO BE DUPLEX PUMP SET FOR INDOOR INSTALLATION. REFER TO DETAILS FOR PIPING ARRANGEMENT. 1 1 1

Transcript of M0bidroom.net/donahuefav/acadianahc/Amendment 2...mcd hws hwr chws chwr tee lateral pipe turning up...

Page 1: M0bidroom.net/donahuefav/acadianahc/Amendment 2...mcd hws hwr chws chwr tee lateral pipe turning up pipe turning down direction of water flow guide anchor rectangular duct turning

M0.01

HVAC - SCHEDULES

FILTER SCHEDULE

SYSTEM

2

2

UNIT DESIGNATION

TYPE

FILTER POSITION

CFM

INITIAL RESISTANCE -H O

FINAL RESISTANCE -H O

MAX FACE VELOCITY

DIMENSIONS

EFF.-DUST SPOT (ATMOS. DUST)

REMARKS:

OTHER

MOISTURE CONDENSATE DRAIN LINE

HOT WATER SUPPLY

HOT WATER RETURN

CHILLED WATER SUPPLY

CHILLED WATER RETURN

MCD

HWS

HWR

CHWS

CHWR

TEE

LATERAL

PIPE TURNING UP

PIPE TURNING DOWN

DIRECTION OF WATER FLOW

GUIDE

ANCHOR

RECTANGULAR DUCT TURNING DOWN

ROUND DUCT TURNING DOWN

REGISTER TAPPING INTO

BOTTOM OF DUCT

ADJUSTABLE T’STAT

CONCEALED T’STAT

MANUAL VOLUME DAMPER

SUPPLY DIFFUSER (4-WAY)

MVD

S

T

FD

1.

2.

FILTERS TO MATCH UNIT CASING SIZE.

RG/EG

RF/EF

RE/EE

RD/ED

RC/EC

RB/EB

RA/EA

SYMBOL NECK

6" SQ

8" SQ

10" SQ

12" SQ

14" SQ

18" SQ

22" SQ

FACE

8"x8" 75

300

1250

1700

CFM

200

540

700

SP

.05

.05

.04

.06

.07

.07

.06

RUNOUTNC

2.

1.

PERFORMANCE BASIS:

EGG-CRATE RETURN & EXHAUST REGISTERS

28

28

27

28

28

27

25

10"x10"

12"x12"

14"x14"

18"x18"

20"x20"

24"x24"

10"x6" / 8"ł

26"x12" / 18"ł

24"x10" / 16"ł

PIPING LEGEND

LOUVERED-FACE CEILING DIFFUSER SCHEDULE

PERFORMANCE BASIS:

1.

2.

3.

SYMBOLADAPTOR/

NECK SIZE

FACE

SIZE

MAX

CFM

MAX

NC

MAX

SPTHROW RUNOUT SIZE

SA

SB

SC

SD

SE

SJ

SK

8"

10"

12"x12"

15"x15"

15"x15"

24"x24"

24"x24"

24"x24"

48"x24"

110

230

420

500

650

150

250

20

20

25

28

26

30

30

.07

.07

.08

.10

.09

.10

.09

4-WAY BLOW

4-WAY BLOW

4-WAY BLOW

4-WAY BLOW

4-WAY BLOW

8"

10"

LAMINAR

LAMINAR

6" / 6"x6"

8" / 9"x9"

10" / 12"x12"

12" / 12"x12"

12" / 15"x15"

6" / 8"x4"

8" / 10"x6"

10" / 12"x8"

12" / 16"x8"

12" / 18"x8"

SMOKE DAMPER

DUCT SMOKE DETECTOR

VARIABLE VOLUME BOX

MANUAL VOLUME DAMPER

FULL RADIUS TURN

DUCT TERMINATION

45” FULL RADIUS TURN

MVD

VAV

SD

SUPPLY FAN

RETURN FAN

MAX RPM

E.S.P.

MINIMUM H.P.

ELECTRICAL

POWER TYPE

MAX OPERATING WEIGHT (LBS)

DIMENSIONS (L"xW"xH")

UNIT No.

TOTAL CFM

O.A. MINIMUM

O.A. MAXIMUM

INTERNAL S.P.

EXTERNAL S.P.

TOTAL S.P.

MINIMUM HP

ELECTRICAL

COOLING COIL

REMARKS:

SERVICE

CFM

MAXIMUM FACE VELOCITY

MAX WTR P.D. FT. IN H2O

MAX AIR S.P. IN H2O

CONTROL VALVE

POWER TYPE

MANUFACTURER

G.P.M.

GTH (BTU/HR)

CHILLED WATER ROOFTOP UNIT SCHEDULE

CFM

MAX RPM

INDICATES HIGH EFFICIENCY MOTOR

REFER TO SPECIFICATIONS FOR ACCESSORIES2.

1.

3.

E.A.T. DB/WB (”F)

DUCTWORK LEGEND

INDICATES A SIZE "A" EXHAUSTREGISTER SET FOR 50 CFM

INDICATES A SIZE "A" SUPPLYREGISTER SET FOR 50 CFM

INDICATES A SIZE "A" RETURNREGISTER SET FOR 50 CFM

EA50

RA50

SA50

EXHAUST GRILLE

RETURN GRILLE

SQUARE ELBOW

W/ TURNING VANESDUCT TURNING DOWN TO SIDEWALLREGISTER AT FLOOR

BRANCH TAP OFF MAIN W/45 DEG

BOOT FITTING OR SPIN-IN FITTING

W/DAMPER (LOW PRESSURE)

TRANSITION IN DUCT (NOTDIRECTION OF AIRFLOW)

FIRE DAMPER

FSD

FIRE/SMOKE DAMPER

DSD

MEDIUM PRESSURE TEE

UNDERCUT DOOR 3/4"

(UNLESS OTHERWISE NOTED)

VARIABLE VOLUME TERMINAL BOX

REFRIGERANT MACHINE SCHEDULE

DESIGNATION

TYPE

CAPACITY TONS ( NOMINAL )

COND TEMP

CONNECTED LOAD TONS

GPM

LOW AMBIENT TEMP

COOLER

EWT

LWT

SCALE FACTOR

MAX PD FT

CAPACITY TON @ SCHEDULED CONDITIONS

No. OF COMPRESSORS

MIN. STAGES

UNIT ELECTRICAL

MAX. FUSE

WIRE SIZE AMPS

POWER

MANUFACTURER

MODEL NO.

REMARKS:

1

REFER TO SPECIFICATIONS AND DETAILS FOR ACCESSORIES ANDPIPING CONNECTIONS.

PROVIDE FREEZE PROTECTION CIRCUIT FOR EVAPORATOR.

1.

2.

DESIGNATION

SERVICE

TYPE

NPSH

TEMPERATURE

CASING WORKING PRESS

MIN MOTOR HP

VOLTAGE/PHASE

RPM

GPM

MANUFACTURER

POWER TYPE

SIZE

OTHERS

REMARKS:

HUMIDIFIER SCHEDULE

COMPUTER ROOM AC UNIT

PUMP SCHEDULE

TOTAL BTUH

SENSIBLE BTUH

TOTAL CFM

CAP #/HR

EVAPORATOR UNIT

COOLING CAPACITY

MAX FUSE SIZE

MIN. CIRCUIT AMPS

HUMIDIFIER

TYPE

HEATING

TYPE

INDOOR UNIT NO.

MANUFACTURER

FAN HP

UNIT ELECTRICAL

FILTER EFFICIENCY

STAGES

CONDENSING UNIT

MODEL

ELECTRICAL

MAX FUSE

MCA

POWER TYPE

POWER TYPE

CAPACITY (KW)

APPROXIMATE SIZE (LxWxH)

LIQ/SUCTION LINE SIZE

NOTES

NOTES

EAWB-”F

EADB-”F

TYPE

CAPACITY-LB/HR

MANIFOLD LENGTH

ACCESSORIES:

DESIGNATION

SERVICE

ACCESSORIES

MANUFACTURER

CFM

SERIES 80 INLINE1

PROVIDE PROGRAMMABLE T’STAT

PROVIDE STAINLESS STEEL DRAIN PAN FOR HUMIDIFER

PROVIDE FRACTIONAL MOISTURE CONDENSATE PUMP.

2

1

1 REFER TO SPECIFICATIONS FOR ACCESSORIES.

INDICATES HIGH EFFICIENCY MOTOR.

REFER TO SPECIFICATIONS AND DETAILS FOR PIPING, VALVES

AND ACCESSORIES.

2.

1.

100

100INDICATES EXISTING AIR DISTRIBUTION DEVICE TO BE REBALANCED TO 100 CFM EACH.

TITUS OMNI OR APPROVED EQUAL.

PERFORATED PANELS (SJ, SK) BASED ON TITUS TLF-AA/KRUEGER SERIES 5000 O.R.D.

CONTRACTOR TO USE DUCT SPIN-IN FITTINGS WITH MANUAL VOLUME DAMPER EQUAL

TO FLEXMASTER CBD OR FLEXMASTER STOD (OR APPROVED EQUAL) FOR CIRCULAR DUCT

AND STANDARD SIDE TAKE OFF WITH MANUAL VOLUME DAMPER FOR RECTANGULAR

RUNOUT. SEE DETAIL.

4. FACE SIZE SHALL BE 24"X24" IN ALL LAY IN CEILING LOCATIONS TO FIT WITHIN GRIDS.

8"x4" / 6"ł

14"x6" / 10"ł

16"x8" / 12"ł

18"x8" / 14"ł

SHUTOFF VALVE

LTWS

LTWR

S-60

LOW TEMP CHILLED WATER WATER SUPPLY

LOW TEMP CHILLED WATER WATER RETURN

GC

STEAM LINE-STEAM PRESSURE (60 PSI)

GRAVITY CONDENSATE RETURN

PCR PUMPED CONDENSATE RETURN

TITUS MODEL 50-FS WITH 1/2"x1/2" EGG-CRATE CORE OR EQUAL (EXAMPLE RA).

CONTRACTOR TO USE DUCT SPIN-IN FITTINGS WITH MANUAL VOLUME DAMPER EQUAL TO

FLEXMASTER CBD OR FLEXMASTER STOD (OR APPROVED EQUAL) FOR CIRCULAR DUCT

AND STANDARD SIDE TAKE OFF WITH MANUAL VOLUME DAMPER FOR RECTANGULAR

RUNOUT. SEE DETAIL.

3. FACE SIZE TO BE 24"X24" IN ALL LAY IN CEILING LOCATIONS TO FIT WITHIN THE GRID.

PF-OR

AHU-OR

1

PRE

8,980

0.25"

0.85"

500

60%

NOTE #1

FILTERS TO MATCH UNIT CASING SIZE UTILIZING ALL 24"x24" FILTERS.

FF-OR

RTU-OR

2

FINAL

8,980

0.60"

1.2"

280

90%

4’W x 8’H

2 90% EFFICIENT, 12" THICK CARTRIDGE

1 60% EFFICIENT, 4" THICK CARTRIDGE

VFD

VFD

COIL L.A.T. DB/WB (”F)

4. PROVIDE UNIT WITH INTERNAL LIGHTS ON SINGLE CIRCUIT

IN THE SUPPLY FAN AND ACCESS SECTIONS.

5. AHU SHALL BE PROVIDED WITH STEAM GRID HUMIDIFIER. SEE SEPARATE

HUMIDIFIER SCHEDULE. PROVIDE ULTRA-SORB DISPERSION TUBES.

ROWS / FINS PER INCH

CFM

MAXIMUM FACE VELOCITY

MAX WTR P.D. FT. IN H2O

MAX AIR S.P. IN H2O

CONTROL VALVE

G.P.M.

GTH (BTU/HR)

E.A.T. DB/WB (”F)

COIL L.A.T. DB/WB (”F)

ROWS / FINS PER INCH

GLYCOL COOLING COIL

CFM

MAXIMUM FACE VELOCITY

MAX WTR P.D. FT. IN H2O

MAX AIR S.P. IN H2O

CONTROL VALVE

G.P.M.

GTH (BTU/HR)

E.A.T. DB/WB (”F)

COIL L.A.T. DB/WB (”F)

ROWS / FINS PER INCH

REHEAT COIL

FILTERS SEE SCHEDULE

AIR BLENDER

SUPPLY AIR TURNDOWN (CFM)

RETURN AIR TEMPERATURE (”F)

FREEZE STAT SET POINT (”F)

WINTER DESIGN TEMP. ”F)

REQUIRED MIXING EFFECTIVENESS

MODEL

UP DISTANCE

DOWN DISTANCE

MAX. AIR P.D. IN H20

CONFIDENCE RATING

STARTER TYPE

ROTARY SCROLL

3. PROVIDE BACNET CHILLER CONTROLS GATEWAY TO INTERFACE

WITH EXISTING SIEMENS BUILDING EMS.

6.

E.W.T. (”F) / L.W.T. (”F)

8,890

450

78.5” / 65.7”

52.0” / 51.8”

391,000

65.2

44”F/56”F

6/10

15

0.75"

2-WAY

E.W.T. (”F) / L.W.T. (”F)

8,980

450

52.0” / 51.8”

42.0” / 41.8”

210,250

35

34”F/46”F

8/10

15

0.75"

3-WAY

E.W.T. (”F) / L.W.T. (”F)

7,455

70”F

36”F

22”F

64%

AB30 (x2)

9"

30"

0.1"

95%

6.

7. PROVIDE ONE VFD TO CONTROL A SINGLE FAN ARRAY. (EX. AHU-OR SHALL HAVE

ONE VFD FOR SUPPLY FAN ARRAY & ONE VFD FOR RETURN FAN ARRAY.)

TDH FT H2O

STEAM PRESSURE

H-OR

AHU-OR

STEAM

8,980

200

1

AS REQ’D

25

DRISTEAM

SOUND ATTENUATOR SCHEDULE

IDENTIFICATION

SYSTEM

DIMENSIONS

MAX. S.P. DROP

DYNAMIC INERTION LOSS

MANUFACTURER

MODEL

QUANTITY

28"x18"x36"L

OR BOXES

0.15"

7-8-11-13-18-24-17-10

VIBRO-ACOUSTICS

RFMB-LV-F2

REFER TO FLOOR PLANS

SA-H

16"x12"x36"L

OR BOXES

0.15"

7-8-11-13-18-24-17-10

VIBRO-ACOUSTICS

RFMB-LV-F2

REFER TO FLOOR PLANS

SA-CV

FAN SCHEDULE

FAN NUMBER

SERVICE

TYPE

CFM

MAX FAN RPM

MAX OUTLET VEL/TS

SIZE

MIN MOTOR HP

ELECTRICAL

INLET SCREEN

OUTLET SCREEN

INLET DAMPER-TYPE

OUTLET DAMPER-TYPE

OTHER

POWER TYPE

MANUFACTURER

REMARKS:

SP-IN H2O

DOWNBLAST CENTRIFUGAL1

CHWP-OR-1

RM-OR

1

1 1 / 2 x 1 1 / 2

50

55’

--

42”F

150

2

460/3/60

1750

NORMAL

B&G

---

CHWP-OR-2

RM-OR

1

1 1 / 2 x 1 1 / 2

50

55’

--

42”F

150

2

460/3/60

1750

NORMAL

B&G

---

AHU-1

TRANE

8,100 LBS.

218"L x 57"W x 88"H

C.V.O.R./HYBRID O.R.

8,980

1,750

8,980

2x1 PLENUM ARRAY

1,750

4.25"

3.0"

7.25"

10 EACH

460/3/60

EMERGENCY

YES

2x1 PLENUM ARRAY

7,230

1,600

0.75"

3 EACH

460/3/60

EMERGENCY

YES

RAF-OR IS DETACHED FROM AHU-OR. RAF-OR WEIGHT OF 3,600 LBS IS NOT

INCLUDED IN OVERALL UNIT WEIGHT SHOWN. 70"L x 57"W x 88"H NOT INCLUDED

IN OVERALL DIMENSIONS OF UNIT.

FINAL FILTER SECTIONS ARE EXTERNAL TO THE UNIT AND ARE CALCULATED AS

INTERNAL PRESSURE DROPS. FF-OR WEIGHT OF 1,600 LBS IS NOT INCLUDED IN

OVERALL WEIGHT SHOWN. 48"L x 58"W x 103"H IS NOT INCLUDED IN OVERALL

DIMENSIONS OF UNIT.

3

FUEL OIL SYSTEM

TYPE FUEL

CAPACITY-GPH

MAX DISCHARGE

VOLTAGE

REMARKS:

MOTOR HP

POWER TYPE

1.

OTHER

PRESSURE (PSI)

FOPS-1

NO. 2 FUEL OIL

400

50

3/4

480/3/60

EMERGENCY

NOTE 2

2.

3.

PUMP

PUMP SET FOPS-1 TO SERVE BOILERS AND GENERATORS.

CONTRACTOR SHALL FURNISH ONE TANK FULL OF FUEL OIL

AND REFILL TO REPLACE FUEL OIL USED FOR TESTING

EQUIPMENT AT END OF PROJECT.

UNIT NO.

E.S.P. IN H O

MANUFACTURER

MODEL NO.

TOTAL CFM

TOTAL BTUH

O.A. CFM

2

MINIMUM H.P.

ELECTRICAL

MAX FUSE

CONDENSING UNIT

MODEL

COOLING CAPACITY

O.A.D.B. ^F

COND. UNIT ELECTRICAL

M.C.A.

MAX FUSE

FILTER

ACCESSORIES

REMARKS

HEAT PUMP A/C SYSTEMS

LINE SIZES (HOT GAS - LIQUID)

AUX. KW HEATER @ 208

SENSIBLE BTUH

1.

2.

3.

PROVIDE UNIT WITH PROGRAMMABLE T’STAT.

INDOOR UNIT TO HAVE SINGLE POINT POWER CONNECTION.

HEAT PUMP HEATING CAP. @ 47^F

MCA

AC-1

TRANE

1,200

0

0.5"

1/2

18,500

N/A

208/1/60

5

15

CU-1

4TWB3036

35,300

26,600

95

208/1/60

18

30

1" THROWAWAY

7/8" - 3/8"

UNITS TO BE EQUIPPED WITH DUCT FIRESTATS IN SUPPLY

DUCTWORK. FIRESTATS TO SHUT DOWN UNITS WHEN ACTIVATED.

AC-CATH

LIEBERT

MMD-36

48"Lx24"Wx18"H

33,200

26,900

72”

60”

1,250

1/2

460/3/60

20

16.5

EMERGENCY

STEAM GENERATNG

4.3

ELECTRIC

5.6

1

30%

CU-CATH

PFH037

460/3/60

15

7.8

EMERGENCY

3/8" - 7/8"

1,2 & 3

AC-OR

LIEBERT

MMD-36

48"Lx24"Wx18"H

33,200

26,900

72”

60”

1,250

1/2

460/3/60

20

16.5

EMERGENCY

STEAM GENERATNG

4.3

ELECTRIC

5.6

1

30%

CU-OR

PFH037

460/3/60

15

7.8

EMERGENCY

3/8" - 7/8"

1,2 & 3

EF-OR

GENERAL

1

1750

0.5"

730

3,441

180 ACEB

1/3

120/1/60

NO

YES

BACKDRAFT

NONE

CURB

EMERGENCY

COOK

EF2-1

GENERAL

1

1775

0.5"

741

3,491

180 ACEB

1/3

120/1/60

NO

YES

BACKDRAFT

NONE

CURB

EMERGENCY

COOK

RM-OR

1

30

95”F

32”F

17.5

GLYCOL

35

46”F

34”F

17.5

0.0001

15

2

2

460/3/60

90

69.9

REDUCE VOLTAGE

NORMAL

TRANE

CGAM-30

8,980

450

42.0”

52.0”

97,500

9.8

150”F/130”F

1/10

5

0.75"

2-WAY

PUMP SETS FOPS-1 TO BE DUPLEX PUMP SET FOR INDOOR INSTALLATION.

REFER TO DETAILS FOR PIPING ARRANGEMENT.

1

1

1