POWER SUPPLIES- DC Power Systems- Inverters- Converters- Static Switches

Page 2: 1UDC Catalogue

Power System 1UDC+

Basic shelf:

1U DC+ type I - includes a 19” 1U shelf (subrack) with up to 3 rectiers.

Electronic Basic shelf:

1U DC +type II - includes a 19” 3U shelf with up to 2 rectiers + SC 1UDC+

controller and an Electronic LVD device.

The Gamatronic 1U DC+ power system provides clean DC power to sensitive equipment while simultaneously charging the battery bank, and supplies backup power during mains failure.The 1U DC+ contains a 19” 1 U subrack that can house up to 3 hot-plugged rectiers, or 2 rectiers + controller and an ELVD device.Max system capacity: Up to 13 subrack (38 rectiers + controller), 1266 A with height of 13 U.

F e a t u r e sVery high eciency: 96%

100A for each 1U shelf

Intelligent power module, digitally controlled

One to three hot-swap rectiers in each shelf

Active current sharing among rectiers

Universal input voltage

A built-in dual 70 A Electronic Low Voltage Disconnect device (ELVD)

for battery protection

Option to connect 2 external LVD contactors of up to 1600 A

A high-performance, hot-swap system controller (SC 1UDC+) to measure,

monitor and control voltages, current, power, battery, temperature, etc.

USB (SC1U DC+) or TCP/IP+USB communication (SC 1UDC+ NET)

Advanced battery management

Up to two battery sets handled in one system

Automatic and pre-programmed battery test (for each battery set)

Automatic and pre-programmed equalize charging mode

Breaking alert by modem (option)

Up to 38 rectiers & a controller, 1266A

Power System 1UDC+

Basic shelf:

1U DC+ type I - includes a 19” 1U shelf (subrack) with up to 3 rectiers.

Electronic Basic shelf:

1U DC +type II - includes a 19” 3U shelf with up to 2 rectiers + SC 1UDC+

controller and an Electronic LVD device.

The Gamatronic 1U DC+ power system provides clean DC power to sensitive equipment while simultaneously charging the battery bank, and supplies backup power during mains failure.The 1U DC+ contains a 19” 1 U subrack that can house up to 3 hot-plugged rectiers, or 2 rectiers + controller and an ELVD device.Max system capacity: Up to 13 subrack (38 rectiers + controller), 1266 A with height of 13 U.

F e a t u r e sVery high eciency: 96%

100A for each 1U shelf

Intelligent power module, digitally controlled

One to three hot-swap rectiers in each shelf

Active current sharing among rectiers

Universal input voltage

A built-in dual 70 A Electronic Low Voltage Disconnect device (ELVD)

for battery protection

Option to connect 2 external LVD contactors of up to 1600 A

A high-performance, hot-swap system controller (SC 1UDC+) to measure,

monitor and control voltages, current, power, battery, temperature, etc.

USB (SC1U DC+) or TCP/IP+USB communication (SC 1UDC+ NET)

Advanced battery management

Up to two battery sets handled in one system

Automatic and pre-programmed battery test (for each battery set)

Automatic and pre-programmed equalize charging mode

Breaking alert by modem (option)

Up to 38 rectiers & a controller, 1266A

Power System 1UDC+

Basic shelf:

1U DC+ type I - includes a 19” 1U shelf (subrack) with up to 3 rectiers.

Electronic Basic shelf:

1U DC +type II - includes a 19” 3U shelf with up to 2 rectiers + SC 1UDC+

controller and an Electronic LVD device.

The Gamatronic 1U DC+ power system provides clean DC power to sensitive equipment while simultaneously charging the battery bank, and supplies backup power during mains failure.The 1U DC+ contains a 19” 1 U subrack that can house up to 3 hot-plugged rectiers, or 2 rectiers + controller and an ELVD device.Max system capacity: Up to 13 subrack (38 rectiers + controller), 1266 A with height of 13 U.

F e a t u r e sVery high eciency: 96%

100A for each 1U shelf

Intelligent power module, digitally controlled

One to three hot-swap rectiers in each shelf

Active current sharing among rectiers

Universal input voltage

A built-in dual 70 A Electronic Low Voltage Disconnect device (ELVD)

for battery protection

Option to connect 2 external LVD contactors of up to 1600 A

A high-performance, hot-swap system controller (SC 1UDC+) to measure,

monitor and control voltages, current, power, battery, temperature, etc.

USB (SC1U DC+) or TCP/IP+USB communication (SC 1UDC+ NET)

Advanced battery management

Up to two battery sets handled in one system

Automatic and pre-programmed battery test (for each battery set)

Automatic and pre-programmed equalize charging mode

Breaking alert by modem (option)

Up to 38 rectiers & a controller, 1266A

Page 3: 1UDC Catalogue

1UDC+ SpecicationsINPUTNominal Voltage Voltage RangeMaximum Current1 (@ full load)

FrequencyPower Factor (@ Full Load)Protection

OUTPUTVoltage (default)Adjustable RangeRegulation (line & load)Nominal Current1

Ripple & Noise @ BW=30MHzPsophometric NoiseEeciency (nominal load)

Short circuit current, Vo=0Over-voltage ProtectionProtectionWalk-in TimeHold-up TimeOutput Current IndicationActive Current SharingGENERALWithstand Voltage (1 min)2

Operating ambient TemperatureStorage TemperatureHumidityEMC

SafetyDimensions (1 module) Weight (1 module)

1UDC 24V 1UDC 48V 1UDC 48V EE230V

85Vac÷285Vac, with derating

Nx6A Nx10A

47Hz ÷ 63Hz≥ 0.99

Relay disconnects input Fused Relay disconnects input for >300V for >300V

27 ± 0.2Vdc 54 ± 0.2Vdc 23Vdc ÷ 30Vdc 47Vdc ÷ 58Vdc

±1%, ±0.25% with controller Nx40A (Vin>195V) Nx33.3A (Vin>195V) Nx20A (Vin=110V) Nx16A (Vin=110V) (max 38 modules) (max 38 modules)

200mVp/p, 20mVrms-52dbm over 600Ω (<2mV)

94% @ 230Vac 92% @ 230Vac 96% @ 230Vac 92% @ 115Vac 88% @ 115Vac 94% @ 115Vac Nx20A (Vin=230V) Nx14A (Vin=230V) Nx20A (Vin=230V) 31V 59.5V

Current limited, short circuit proof, output fuses10s

20ms (90% load, output decays to 46V)4 LEDs bar-graph on the front panel

10% accuracy @ full load

3000VacINPUT/OUTPUT, 1500vAC INPUT/GND-10o÷70oC, output de-rated above 50oC by 5%oC

-20o ÷ 80oC<95% non-condensing, equipped with standard 1U DC+ rackEN300 386-2 V1.1.1.3 (1997), EN55022, EN61000-4-2,3,4,5,6,11,

EN61000-3-2, EN61000-3-3 (certied)

IEC950, EN60950 (certied)146mm (W) x 44mm (H) x 260mm (D)

1.4Kg 1.2Kg 1.4Kg

Notes:1. “N” denotes the number of power modules2. Equivalent DC test voltage is applied to overcome Y-capacitors leakage current to ground. Output is oating (not grounded during test).

1UDC+ Eciency (%) Vs. Output Current (A)

Load Output (A)

0 5 10 15 20 25 30 35

100

95

90

85

80

75

70

Effic

ienc

y (%

)

Model IPU 1000

F e a t u r e sUp to 30 units in parallel, 30kVAEmploys high frequency PWM technology A microprocessor controls all diagnostics and operationPower density (2kVA in 1U 19” shelf; 1kVA in 1U 9.5” cabinet)LightweightStandalone or parallel operation Parallel capability for N+1 redundancy High eciency Continuous input DC curentOptional: bypass (for standalone operation)

10 units of IPU1000 installed in parallel

1UDC+ SpecicationsINPUTNominal Voltage Voltage RangeMaximum Current1 (@ full load)

FrequencyPower Factor (@ Full Load)Protection

OUTPUTVoltage (default)Adjustable RangeRegulation (line & load)Nominal Current1

Ripple & Noise @ BW=30MHzPsophometric NoiseEeciency (nominal load)

Short circuit current, Vo=0Over-voltage ProtectionProtectionWalk-in TimeHold-up TimeOutput Current IndicationActive Current SharingGENERALWithstand Voltage (1 min)2

Operating ambient TemperatureStorage TemperatureHumidityEMC

SafetyDimensions (1 module) Weight (1 module)

1UDC 24V 1UDC 48V 1UDC 48V EE230V

85Vac÷285Vac, with derating

Nx6A Nx10A

47Hz ÷ 63Hz≥ 0.99

Relay disconnects input Fused Relay disconnects input for >300V for >300V

27 ± 0.2Vdc 54 ± 0.2Vdc 23Vdc ÷ 30Vdc 47Vdc ÷ 58Vdc

±1%, ±0.25% with controller Nx40A (Vin>195V) Nx33.3A (Vin>195V) Nx20A (Vin=110V) Nx16A (Vin=110V) (max 38 modules) (max 38 modules)

200mVp/p, 20mVrms-52dbm over 600Ω (<2mV)

94% @ 230Vac 92% @ 230Vac 96% @ 230Vac 92% @ 115Vac 88% @ 115Vac 94% @ 115Vac Nx20A (Vin=230V) Nx14A (Vin=230V) Nx20A (Vin=230V) 31V 59.5V

Current limited, short circuit proof, output fuses10s

20ms (90% load, output decays to 46V)4 LEDs bar-graph on the front panel

10% accuracy @ full load

3000VacINPUT/OUTPUT, 1500vAC INPUT/GND-10o÷70oC, output de-rated above 50oC by 5%oC

-20o ÷ 80oC<95% non-condensing, equipped with standard 1U DC+ rackEN300 386-2 V1.1.1.3 (1997), EN55022, EN61000-4-2,3,4,5,6,11,

EN61000-3-2, EN61000-3-3 (certied)

IEC950, EN60950 (certied)146mm (W) x 44mm (H) x 260mm (D)

1.4Kg 1.2Kg 1.4Kg

Notes:1. “N” denotes the number of power modules2. Equivalent DC test voltage is applied to overcome Y-capacitors leakage current to ground. Output is oating (not grounded during test).

1UDC+ Eciency (%) Vs. Output Current (A)

Load Output (A)

0 5 10 15 20 25 30 35

100

95

90

85

80

75

70

Effic

ienc

y (%

)

The Gamatronic 1U DC+ power system provides clean DC power to sensitive equipment while simultaneously charging the battery bank, and supplies backup power during mains failure.The 1U DC+ contains a 19” 1 U subrack that can house up to 3 hot-plugged rectiers, or 2 rectiers + controller and an ELVD device.Max system capacity: Up to 13 subrack (38 rectiers + controller), 1266 A with height of 13 U.

Up to 38 rectiers & a controller, 1266A

1UDC+ SpecicationsINPUTNominal Voltage Voltage RangeMaximum Current1 (@ full load)

FrequencyPower Factor (@ Full Load)Protection

OUTPUTVoltage (default)Adjustable RangeRegulation (line & load)Nominal Current1

Ripple & Noise @ BW=30MHzPsophometric NoiseEeciency (nominal load)

Short circuit current, Vo=0Over-voltage ProtectionProtectionWalk-in TimeHold-up TimeOutput Current IndicationActive Current SharingGENERALWithstand Voltage (1 min)2

Operating ambient TemperatureStorage TemperatureHumidityEMC

SafetyDimensions (1 module) Weight (1 module)

1UDC 24V 1UDC 48V 1UDC 48V EE230V

85Vac÷285Vac, with derating

Nx6A Nx10A

47Hz ÷ 63Hz≥ 0.99

Relay disconnects input Fused Relay disconnects input for >300V for >300V

27 ± 0.2Vdc 54 ± 0.2Vdc 23Vdc ÷ 30Vdc 47Vdc ÷ 58Vdc

±1%, ±0.25% with controller Nx40A (Vin>195V) Nx33.3A (Vin>195V) Nx20A (Vin=110V) Nx16A (Vin=110V) (max 38 modules) (max 38 modules)

200mVp/p, 20mVrms-52dbm over 600Ω (<2mV)

94% @ 230Vac 92% @ 230Vac 96% @ 230Vac 92% @ 115Vac 88% @ 115Vac 94% @ 115Vac Nx20A (Vin=230V) Nx14A (Vin=230V) Nx20A (Vin=230V) 31V 59.5V

Current limited, short circuit proof, output fuses10s

20ms (90% load, output decays to 46V)4 LEDs bar-graph on the front panel

10% accuracy @ full load

3000VacINPUT/OUTPUT, 1500vAC INPUT/GND-10o÷70oC, output de-rated above 50oC by 5%oC

-20o ÷ 80oC<95% non-condensing, equipped with standard 1U DC+ rackEN300 386-2 V1.1.1.3 (1997), EN55022, EN61000-4-2,3,4,5,6,11,

EN61000-3-2, EN61000-3-3 (certied)

IEC950, EN60950 (certied)146mm (W) x 44mm (H) x 260mm (D)

1.4Kg 1.2Kg 1.4Kg

Notes:1. “N” denotes the number of power modules2. Equivalent DC test voltage is applied to overcome Y-capacitors leakage current to ground. Output is oating (not grounded during test).

1UDC+ Eciency (%) Vs. Output Current (A)

0 5 10 15 20 25 30 35

100

95

90

85

80

75

70

Effic

ienc

y (%

)

Page 4: 1UDC Catalogue

0.5kVA 24V 1kVA 48VDual high frequency conversion Dual 8-bit RISC Microcontroller

24Vdc (nominal) 21÷ 30Vdc 48Vdc (nominal) 42 ÷ 60Vdc21A (max.) 20A (max.)

< 2mV at full load, over 600 Ω21Vdc ± 0.5 42Vdc ± 0.5

220/230Vac500VA / 300W 1000VA / 700W88% @ 24VDC 90% @ 48VDC

50/60Hz ± 0.1% (free-mode)Active current sharing

Pure sinewave1.5% max. for linear load

4% max. for non-linear load3:1 max. for non-linear load

± 1% (static)recovery within 500mS

Up to 30 units in parallel1500VAC input-output

1500VAC output-chassis500VDC input-chassis

Output over-voltage, output overload & short circuit (inherent by pulse-by-pulse), LVD

(low input voltage disconnection), over-temperature5 LEDs and load bar graph

IEC 950 (EN 60950)EN300-386-2, EN 50082-1, EN 55022

< 50dBA @ 1.5m-10o ÷ +50oC -10o ÷ +45oC

1 dry contact (fault indication)202 x 44 x 243

1.5Kg

All specications are typical and subject to change without prior notice

Model IPU 1000

F e a t u r e sUp to 30 units in parallel, 30kVAEmploys high frequency PWM technology A microprocessor controls all diagnostics and operationPower density (2kVA in 1U 19” shelf; 1kVA in 1U 9.5” cabinet)LightweightStandalone or parallel operation Parallel capability for N+1 redundancy High eciency Continuous input DC curentOptional: bypass (for standalone operation)

0.5kVA 24V 1kVA 48VDual high frequency conversion Dual 8-bit RISC Microcontroller

24Vdc (nominal) 21÷ 30Vdc 48Vdc (nominal) 42 ÷ 60Vdc21A (max.) 20A (max.)

< 2mV at full load, over 600 Ω21Vdc ± 0.5 42Vdc ± 0.5

220/230Vac500VA / 300W 1000VA / 700W88% @ 24VDC 90% @ 48VDC

50/60Hz ± 0.1% (free-mode)Active current sharing

Pure sinewave1.5% max. for linear load

4% max. for non-linear load3:1 max. for non-linear load

± 1% (static)recovery within 500mS

Up to 30 units in parallel1500VAC input-output

1500VAC output-chassis500VDC input-chassis

Output over-voltage, output overload & short circuit (inherent by pulse-by-pulse), LVD

(low input voltage disconnection), over-temperature5 LEDs and load bar graph

IEC 950 (EN 60950)EN300-386-2, EN 50082-1, EN 55022

< 50dBA @ 1.5m-10o ÷ +50oC -10o ÷ +45oC

1 dry contact (fault indication)202 x 44 x 243

1.5Kg

POWER TopologyControlINPUTVoltage Current Psophometric noise Low voltage shutdown OUTPUTVoltage Power Eciency (dc-ac) Frequency Synchronization systemWaveformTHD

Crest factorVoltage regulation (line & load)GENERALParallel CongurationIsolation voltage

Protection

DisplaySafetyEMC (including the shelf)Audible noiseTemperature SignalizationDimensions WxHxD (mm)Weight (without shelf)

All specications are typical and subject to change without prior notice

Model IPU 1000

F e a t u r e sUp to 30 units in parallel, 30kVAEmploys high frequency PWM technology A microprocessor controls all diagnostics and operationPower density (2kVA in 1U 19” shelf; 1kVA in 1U 9.5” cabinet)LightweightStandalone or parallel operation Parallel capability for N+1 redundancy High eciency Continuous input DC curentOptional: bypass (for standalone operation)

0.5kVA 24V 1kVA 48VDual high frequency conversion Dual 8-bit RISC Microcontroller

24Vdc (nominal) 21÷ 30Vdc 48Vdc (nominal) 42 ÷ 60Vdc21A (max.) 20A (max.)

< 2mV at full load, over 600 Ω21Vdc ± 0.5 42Vdc ± 0.5

220/230Vac500VA / 300W 1000VA / 700W88% @ 24VDC 90% @ 48VDC

50/60Hz ± 0.1% (free-mode)Active current sharing

Pure sinewave1.5% max. for linear load

4% max. for non-linear load3:1 max. for non-linear load

± 1% (static)recovery within 500mS

Up to 30 units in parallel1500VAC input-output

1500VAC output-chassis500VDC input-chassis

Output over-voltage, output overload & short circuit (inherent by pulse-by-pulse), LVD

(low input voltage disconnection), over-temperature5 LEDs and load bar graph

IEC 950 (EN 60950)EN300-386-2, EN 50082-1, EN 55022

< 50dBA @ 1.5m-10o ÷ +50oC -10o ÷ +45oC

1 dry contact (fault indication)202 x 44 x 243

1.5Kg

POWER TopologyControlINPUTVoltage Current Psophometric noise Low voltage shutdown OUTPUTVoltage Power Eciency (dc-ac) Frequency Synchronization systemWaveformTHD

Crest factorVoltage regulation (line & load)GENERALParallel CongurationIsolation voltage

Protection

DisplaySafetyEMC (including the shelf)Audible noiseTemperature SignalizationDimensions WxHxD (mm)Weight (without shelf)

All specications are typical and subject to change without prior notice

10 units of IPU1000 installed in parallel

Page 5: 1UDC Catalogue

SINGLE PHASE STATIC SWITCH 3U3 – 30 kVA

AC input and output Nominal power Input voltage rangeInput frequency range Signals and indicators 6Eciency Size in mm (H × W × D) Weight Regulations

Single phase with common neutral3 to 30 kVA

187–253 Vac, other ranges also available46 Hz–64 Hz, other ranges also available

6 LEDs, 3 keys, audible alarm, RS232 interface99.9%

132 × 483 × 250 (3U)<10 kVA: ~10 kg ; 10–30 kVA: ~15kg

Complies with IEC950 standards

F e a t u r e sAutomatic static switch to increase reliability and overload capabilityZero time load transfer from inverters to bypass and vice-versaClear, user-friendly colored LED indicators on the static switch panelAudible alarm if failure detected or load on bypassProtect load against illegal bypass voltages

STATIC SWITCH

SINGLE PHASE STATIC SWITCH 1U3 kVA / 6 kVA

Ac inputs and outputNominal power Input voltage range Input frequency range Maximum currentSignals and indicators EciencySize in mm (W × D× H)WeightSafety

Single phase with common neutral3kVA 6kVA

196 V~253V (Phase to Neutral), other values are available

50 ±3Hz13A 30A

6 LEDs, 3 keys, audible alarm, RS232 interface99.9%

485 × 280 × 44 (1U)3.7kg

Complies with IEC60950

THREE PHASE STATIC SWITCH (Wall Mounted)10 -250 kVA

Ac input and output Nominal power Input voltage range Input frequency range Transition time in synchronized mode1 Transition time in non-synchronized modeSignals and indicatorsEciency Regulations

Three phase with a common neutral is available10 ~ 250 kVA

196 V ~ 253 V (Phase to Neutral), other values are available46 Hz ~ 64 Hz, other values are available

< 3 msec< 200 msec

5 LEDs, 3 keys, audible alarm99.9 %

Complies with the IEC950 standard

SINGLE PHASE STATIC SWITCH 3U3 – 30 kVA

AC input and output Nominal power Input voltage rangeInput frequency range Signals and indicators 6Eciency Size in mm (H × W × D) Weight Regulations

Single phase with common neutral3 to 30 kVA

187–253 Vac, other ranges also available46 Hz–64 Hz, other ranges also available

6 LEDs, 3 keys, audible alarm, RS232 interface99.9%

132 × 483 × 250 (3U)<10 kVA: ~10 kg ; 10–30 kVA: ~15kg

Complies with IEC950 standards

F e a t u r e sAutomatic static switch to increase reliability and overload capabilityZero time load transfer from inverters to bypass and vice-versaClear, user-friendly colored LED indicators on the static switch panelAudible alarm if failure detected or load on bypassProtect load against illegal bypass voltages

STATIC SWITCH

SINGLE PHASE STATIC SWITCH 1U3 kVA / 6 kVA

Ac inputs and outputNominal power Input voltage range Input frequency range Maximum currentSignals and indicators EciencySize in mm (W × D× H)WeightSafety

Single phase with common neutral3kVA 6kVA

196 V~253V (Phase to Neutral), other values are available

50 ±3Hz13A 30A

6 LEDs, 3 keys, audible alarm, RS232 interface99.9%

485 × 280 × 44 (1U)3.7kg

Complies with IEC60950

THREE PHASE STATIC SWITCH (Wall Mounted)10 -250 kVA

Ac input and output Nominal power Input voltage range Input frequency range Transition time in synchronized mode1 Transition time in non-synchronized modeSignals and indicatorsEciency Regulations

Three phase with a common neutral is available10 ~ 250 kVA

196 V ~ 253 V (Phase to Neutral), other values are available46 Hz ~ 64 Hz, other values are available

< 3 msec< 200 msec

5 LEDs, 3 keys, audible alarm99.9 %

Complies with the IEC950 standard

Page 6: 1UDC Catalogue

Dc-Dc Converter 48/24 600W ModulesThis dc-dc converter module simply converts a nominal 48 V (42 V-61.5 V) into 24 V(25 A maximum) accurate voltage at the output.The unit comes with the option to parallel several similar modules in order to gain morepower and redundant operation (N+1).

InputVoltage range Current Eciency Protection Low Voltage Protection Restart operation OutputVoltage Current limit Voltage adjustment Voltage regulation Ripple Protection Display Parallel operation GeneralAmbient temperature Humidity Dimensions (mm) Weight (Kg) Withstand voltage

Cooling SafetyEMC

Single Dc-Dc 48-24 Module42÷ 61.5VDC

17A (max)>88%

Against reserve polarity connectionStops at Vin < 42VDC

Automatic at Vin > 46VDC

24VDC25A (folds back to 9A at shortcircuit)

±5%±1%

50mVrmsOver load, output OVP, Over-temperature

4 LED bar-graph display the load levelActive current-sharing

-10÷50°C0-95 %

146 (W); 44 (H); 260 (D)0.8

Input – Output: 1500VDCInput – chassis: 1500VDC

Output – chassis: 1500VDCForced, fan speed control

IEC950, EN60950EN55022, EN6100-4-2

2,3,4,5,6,11 ,EN61000-3-2EN6100-3-2, EN61000-3-3

May 2011

Headquarters and Factory 14 Hartom St. POB 45029, Jerusalem 97774, Israel Tel: +972-2-5888222 Fax: +972-2-5828875 [email protected] www.gamatronic.com

GAMATRONIC ELECTRONIC INDUSTRIES LTD.

- All specications are subject to change without prior notice- All images are for illustration only

Dc-Dc Converter 48/24 600W ModulesThis dc-dc converter module simply converts a nominal 48 V (42 V-61.5 V) into 24 V(25 A maximum) accurate voltage at the output.The unit comes with the option to parallel several similar modules in order to gain morepower and redundant operation (N+1).

InputVoltage range Current Eciency Protection Low Voltage Protection Restart operation OutputVoltage Current limit Voltage adjustment Voltage regulation Ripple Protection Display Parallel operation GeneralAmbient temperature Humidity Dimensions (mm) Weight (Kg) Withstand voltage

Cooling SafetyEMC

Single Dc-Dc 48-24 Module42÷ 61.5VDC

17A (max)>88%

Against reserve polarity connectionStops at Vin < 42VDC

Automatic at Vin > 46VDC

24VDC25A (folds back to 9A at shortcircuit)

±5%±1%

50mVrmsOver load, output OVP, Over-temperature

4 LED bar-graph display the load levelActive current-sharing

-10÷50°C0-95 %

146 (W); 44 (H); 260 (D)0.8

Input – Output: 1500VDCInput – chassis: 1500VDC

Output – chassis: 1500VDCForced, fan speed control

IEC950, EN60950EN55022, EN6100-4-2

2,3,4,5,6,11 ,EN61000-3-2EN6100-3-2, EN61000-3-3

Headquarters and Factory 14 Hartom St. POB 45029, Jerusalem 97774, Israel Tel: +972-2-5888222 Fax: +972-2-5828875 [email protected] www.gamatronic.com

GAMATRONIC ELECTRONIC INDUSTRIES LTD.

- All specications are subject to change without prior notice- All images are for illustration only