    Arc Guard SystemTM TVOC-2A protection device for reliable safety

    Leaflet

    A flexible and intelligentsolution for you and yourbusiness safety.

    ABB is leader in arc guard technology since 35 years.

    Experience from the highly appreciated TVOC is built into

    the new TVOC-2, a product for protection of humans andproperty when having an electric arc.

    HMI (Human Machine Interface)

    Reliability

    Certified according to functional safety (SIL 2) standard.

    Over 35 years of experience in Arc Guard Systems.

    Pre-calibrated optical sensors.

    Flexibility

    HMI can be mounted on the panel-door.

    Expand with up to 30 optical sensors.

    Configure the system according to various needs.

    Simplicity

    User-friendly start-up menu.

    DIN-Rail or wall-mounted.

    Easy to expand as the switchgear grows.

  • 8/2/2019 1SFC170001L0201

    2/2

    Leafet1SFC170001L0201,

    March2010.

    ProdABB

    AB,

    Cewe-Control

    Copyright 2010 ABB. All rights reserved.

    Specications subject to changes without notice.

    For more information please contact:

    ABB AB

    Cewe-Control

    SE-72161 Vsters, Sweden

    Phone: +46 21 32 07 00

    Fax: +46 21 12 60 01

    www.abb.com/lowvoltage

    Technical dataReacting time (typical) Approx. 1 ms (depends on light intensity)

    Optical detectors 10 inputs on Arc Monitor

    10 inputs on Extension unit X2 (optional)

    10 inputs on Extension unit X3 (optional)

    Breaker trip contacts 3 NO solid state type IGBT

    Signal relay outputs (K2, K3)

    Manual or auto resetable 2 CO gold-plated contacts

    Rated voltage 250 V AC/DC

    Continous carry Ith

    5 A

    Make and carry for 0.2 s 30 A

    Make and carry for 3 s 10% duty ratio 15 A

    Breaking capacity 250V 30 A AC-15

    250 V 0.3 A DC-13

    110 V 0.6 A DC-13

    48 V 2 A DC-13

    Reinforced insulation betweenseparate contacts

    Ith

    = 5 AMin switching load:1 mA at 5 V DC with contacts not

    used for switching current> 0.5 A if inductive/capacitive loadbefore

    Congurat ion (DIP switches) Manual or auto reset of K1 and K3Use of CSU or not

    Trip Conguration

    HMI / User interface Full text display (55 x 26 mm)

    Trip log with time stamp Yes

    Power supplyRated supply voltage, U

    s

    100-240 V AC, 50-60 Hz100-250 V DC

    Power consumption 5 W

    Weight 0.95 kg

    Environment

    Altitude 2000 m above sea level

    Permissible ambient temperature -25 C to +55 C

    Degree of protection IP20 Arc MonitorIP54 HMI front side

    Complies with CE, RoHS

    Functional safety approval SIL2 (IEC61508)

    Other system components

    Current sensing unit (CSU) Option (same as for TVOC)

    Optical detectors 1-60 m optical bre with lens

    Arc Guard System components:

    Arc moni tor (TVOC-2)

    Extension unit (detector inputs)

    HMI (display and menu)

    Optical detectors

    Current Sensing Unit, CSU (optional)

    Dimension drawing

    F11 A1

    D

    Q1

    F11 Arc Monitor, Q1 Circuit breaker, A1 Switchgear, D Detector