1SFC170001L0201
Transcript of 1SFC170001L0201
-
8/2/2019 1SFC170001L0201
1/2
Arc Guard SystemTM TVOC-2A protection device for reliable safety
Leaflet
A flexible and intelligentsolution for you and yourbusiness safety.
ABB is leader in arc guard technology since 35 years.
Experience from the highly appreciated TVOC is built into
the new TVOC-2, a product for protection of humans andproperty when having an electric arc.
HMI (Human Machine Interface)
Reliability
Certified according to functional safety (SIL 2) standard.
Over 35 years of experience in Arc Guard Systems.
Pre-calibrated optical sensors.
Flexibility
HMI can be mounted on the panel-door.
Expand with up to 30 optical sensors.
Configure the system according to various needs.
Simplicity
User-friendly start-up menu.
DIN-Rail or wall-mounted.
Easy to expand as the switchgear grows.
-
8/2/2019 1SFC170001L0201
2/2
Leafet1SFC170001L0201,
March2010.
ProdABB
AB,
Cewe-Control
Copyright 2010 ABB. All rights reserved.
Specications subject to changes without notice.
For more information please contact:
ABB AB
Cewe-Control
SE-72161 Vsters, Sweden
Phone: +46 21 32 07 00
Fax: +46 21 12 60 01
www.abb.com/lowvoltage
Technical dataReacting time (typical) Approx. 1 ms (depends on light intensity)
Optical detectors 10 inputs on Arc Monitor
10 inputs on Extension unit X2 (optional)
10 inputs on Extension unit X3 (optional)
Breaker trip contacts 3 NO solid state type IGBT
Signal relay outputs (K2, K3)
Manual or auto resetable 2 CO gold-plated contacts
Rated voltage 250 V AC/DC
Continous carry Ith
5 A
Make and carry for 0.2 s 30 A
Make and carry for 3 s 10% duty ratio 15 A
Breaking capacity 250V 30 A AC-15
250 V 0.3 A DC-13
110 V 0.6 A DC-13
48 V 2 A DC-13
Reinforced insulation betweenseparate contacts
Ith
= 5 AMin switching load:1 mA at 5 V DC with contacts not
used for switching current> 0.5 A if inductive/capacitive loadbefore
Congurat ion (DIP switches) Manual or auto reset of K1 and K3Use of CSU or not
Trip Conguration
HMI / User interface Full text display (55 x 26 mm)
Trip log with time stamp Yes
Power supplyRated supply voltage, U
s
100-240 V AC, 50-60 Hz100-250 V DC
Power consumption 5 W
Weight 0.95 kg
Environment
Altitude 2000 m above sea level
Permissible ambient temperature -25 C to +55 C
Degree of protection IP20 Arc MonitorIP54 HMI front side
Complies with CE, RoHS
Functional safety approval SIL2 (IEC61508)
Other system components
Current sensing unit (CSU) Option (same as for TVOC)
Optical detectors 1-60 m optical bre with lens
Arc Guard System components:
Arc moni tor (TVOC-2)
Extension unit (detector inputs)
HMI (display and menu)
Optical detectors
Current Sensing Unit, CSU (optional)
Dimension drawing
F11 A1
D
Q1
F11 Arc Monitor, Q1 Circuit breaker, A1 Switchgear, D Detector