1MRK511113-HEN D en Phasor Measurement Terminal RES 521

3
Phasor Measurement T erminal RES 521 Opening a new perspective The Phasor Measurement Terminal RES 521 enables increasing the transmission capacity without the need to invest in additional transmission lines. At the same time, it improves the operational security of the power system. The superior measurement performance of RES 521, in combination with software tools for monitoring and presentation of power system dynamics, provide the operator with real-time phasor information for remedial actions. The RES 521 terminal is more than a first-class product. It is supplied with a value-adding information package about the product and its use in your application. Information such as technical data, user documentation and connection diagrams is essential to ensure the smooth and efficient use of the terminal throughout its lifetime. Y ou can access this information easily via the operator’s workplace or from your PC with Inform IT  Aspect Object Viewer software. Optimize your asset utilization The GPS (Global Positioning System) synchronization of the RES 521 phasor measurements allows for a direct comparison of the phase angles between corresponding phasors from  various locations in the power system. Operators receive the measurements time-tagged with an accuracy of one micro- second. This high measurement accuracy is used to estimate, or in fact, calculate the power system state. In the case of evolving power oscillations, RES 521 provides information, for example, about voltages and currents to retain system stability. These measurements, based on system-wide data, allow, for instance, fast and reliable emergency actions as well as load shedding. Additionally, RES 521 facilitates the transfer of data to a centrally located data concentrator or evaluation station for off-line studies and analyses. As a result, the stability limit can be moved closer to the thermal limits of power lines, enabling efficient utilizati on of the entire transmission system. Reliable and proven technology RES 521 is based on the same proven technology as ABB’s 500 series protection and control terminals, ensuring a reliable foundation for accurate phasor measurement. Developed to meet the stringent EMC requirements imposed on protective relays, it can be connected directly to CTs and VTs without the need for any additional equipment.

Transcript of 1MRK511113-HEN D en Phasor Measurement Terminal RES 521

Page 1: 1MRK511113-HEN D en Phasor Measurement Terminal RES 521

8/3/2019 1MRK511113-HEN D en Phasor Measurement Terminal RES 521

http://slidepdf.com/reader/full/1mrk511113-hen-d-en-phasor-measurement-terminal-res-521 1/2

Phasor Measurement Terminal

RES 521

Opening a new perspectiveThe Phasor Measurement Terminal RES 521 enables increasingthe transmission capacity without the need to invest in additionaltransmission lines. At the same time, it improves the operationalsecurity of the power system. The superior measurementperformance of RES 521, in combination with software toolsfor monitoring and presentation of power system dynamics,provide the operator with real-time phasor information forremedial actions.

The RES 521 terminal is more than a first-class product. It is

supplied with a value-adding information package about theproduct and its use in your application. Information such astechnical data, user documentation and connection diagramsis essential to ensure the smooth and efficient use of theterminal throughout its lifetime. You can access this informationeasily via the operator’s workplace or from your PC with InformIT

 Aspect Object Viewer software.

Optimize your asset utilization

The GPS (Global Positioning System) synchronization of theRES 521 phasor measurements allows for a direct comparisonof the phase angles between corresponding phasors from

 various locations in the power system. Operators receivethe measurements time-tagged with an accuracy of one micro-

second. This high measurement accuracy is used to estimate,or in fact, calculate the power system state.

In the case of evolving power oscillations, RES 521 providesinformation, for example, about voltages and currents to retainsystem stability. These measurements, based on system-widedata, allow, for instance, fast and reliable emergency actionsas well as load shedding. Additionally, RES 521 facilitates thetransfer of data to a centrally located data concentrator orevaluation station for off-line studies and analyses. As a result,the stability limit can be moved closer to the thermal limits of power lines, enabling efficient utilization of the entire transmissionsystem.

Reliable and proven technologyRES 521 is based on the same proven technology as ABB’s 500series protection and control terminals, ensuring a reliablefoundation for accurate phasor measurement. Developed tomeet the stringent EMC requirements imposed on protectiverelays, it can be connected directly to CTs and VTs without theneed for any additional equipment.

Page 2: 1MRK511113-HEN D en Phasor Measurement Terminal RES 521

8/3/2019 1MRK511113-HEN D en Phasor Measurement Terminal RES 521

http://slidepdf.com/reader/full/1mrk511113-hen-d-en-phasor-measurement-terminal-res-521 2/2

Take a major step toincrease transmissioncapacity

RES 521 *1.0

Technology summary:

   I  m  a  g  e  n  e  e  r   i  n  g   /   P  r   i  n   t  e   d   i  n   F   i  n   l  a  n   d

   b  y   W  a  a  s  a   G  r  a  p   h   i  c  s   /   1   0   /   2   0   0   4   1   M   R   K   5   1   1   1   1   3  -   H   E   N

 ABB Power Technologies ABSubstation Automation ProductsSE-721 59 Västerås, SwedenPhone: +46 21 342 000, Fax: +46 21 32 42 23www.abb.com/substationautomation

Open communicationRES 521 features communication capabilities for standard protocols in TCP/IP

and UDP/IP:IEEE 1344 streaming data or PC37.118 synchrophasor format. Thisensures openness and enables the use of standard communication components,as well as easy integration into any system or PC compliant with the phasordata format.

Integrated in ABB’s PSGuard system When synchronized phasor measurements from RES 521 are combined withadvanced communication technology, you can access a wide range of applications to improving the efficiency of your power system. As a key component in ABB’s PSGuard Wide Area Monitoring, Control and ProtectionSystem RES 521 provides you with the means to, for instance, monitor andrecord power system dynamics, improve state estimation and system-widepower oscillation mitigation.

Features and functions

•Protective relay technology and EMC noise

suppression

•Time-tagged AC phasors, positive sequence

 voltages and currents as real and imaginary 

quantities, for local or remote applications

•Frequency, 3-phase based, and rate-of-change

of frequency 

•Selectable transfer rate to 1 per cycle,

1 per 2 cycles, or 1 per 4 cycles

•Built-in GPS clock module for synchronized

sampling of terminals in different substations

•Time-tagged accuracy of one microsecond

•Continuous self-supervision and diagnostics

•Highly accurate voltage and current

measurements

•Extensive calibration possibilities to compen-

sate for external CT and VT non-linearity 

•Highly accurate phase angle calculation

•6 analogue current inputs, 3 analogue voltage

inputs; additional 6 analogue current inputs,3 analogue voltage inputs as option

•8 binary inputs can be freely connected

to the IEEE 1344 protocol

•2 settable trigger levels for frequency and

∆f/∆t measurement

•2 settable undervoltage and 4 settable

overcurrent triggers

•Normally open output contacts for trigger

pickup for f, rate of change of frequency 

∆f/∆t, U and I

•Change over output contact for loss of 

power supply and internal failure

•Front HSI panel•Ready-made configuration

Communication

•Remote communication port 10/100 Base Tx

for TCP/IP, UDP/IP and streaming data in

IEEE 1344 or PC37.118 synchrophasor formats

•Option for additional optical remote commu-

nication ports 100 Base FX for TCP/IP, UDP/IP

and streaming data in IEEE 1344 or PC37.118

synchrophasor formats

Technical details are available in the RES 521 Buyer’sGuide at www.abb.com/substationautomation.