18_Aizam_HV IT in TNB Substations.pdf

download 18_Aizam_HV IT in TNB Substations.pdf

of 22

Transcript of 18_Aizam_HV IT in TNB Substations.pdf

  • Copyright 2013 TNB Research

    Diagnostic And Condition Assessment Of High Voltage Instrument Transformer in

    TNB Transmission Substation

    Slide No. 1

    Mohd Aizam Talib

  • Copyright 2013 TNB Research Slide No. 2

    1.0 Background High voltage instrument transformers form an integral part

    of the power utility control circuits to monitor load currents and voltages for protection and measurement purpose

    Inexpensive components and require minimal maintenance

    Failure and explosion of instrument transformer - loss of assets, revenue and safety issue

  • Copyright 2013 TNB Research Slide No. 3

    01234567

    No.

    of F

    ailu

    res

    Year

    Failure Cases of High Voltage Instrument Transformer

    Over 36 failures and explosion of instrument transformers has been recorded at TNB Transmission substations from year 2001 until 2010.

    There is a need to assess the condition of in service high voltage instrument transformers

  • Copyright 2013 TNB Research Slide No. 4

    visual inspection cleaning of the porcelain Thermography hot spot

    detection

    Routine maintenance practices Limitations

    Provide partial information on the condition of instrument transformers

    Unable to detect abnormal degradation

    Off-line and on-line diagnostic techniques

    Verify the condition of in-service instrument transformer

    Guarantee the reliability of instrument transformer

  • Copyright 2013 TNB Research Slide No. 5

    2.0 Diagnostic of In-Service Instrument Transformer

    Degradation of insulation system will increases the probability of instrument transformer failures

    Important to assess the condition of in-service instrument transformer

    Used of nonintrusive diagnostic tools to improve the maintenance practices for instrument transformers

    Diagnostic techniques; dielectric dissipation factor, dielectric response analysis & on-line partial discharge measurement

  • Copyright 2013 TNB Research Slide No. 6

    Dielectric Dissipation Factor / Power Factor

    Ratio of the resistive current to the capacitive current under an applied AC voltage

    Good insulation usually has a very low loss and increases in dielectric loss may indicate problems in the insulation structure.

    IR

  • Copyright 2013 TNB Research Slide No. 7

    Dielectric dissipation factor of new instrument transformer should not exceeded 0.5% and for in-service age units the measurement should less than 1.0%

    Periodic measurement during the service life can indicate either the insulation is aging normally or deteriorating rapidly

  • Copyright 2013 TNB Research Slide No. 8

    Dielectric Response Analysis

    Used to estimate moisture and ageing state of oil-paper insulation from dielectric properties like polarization currents and dissipation factor.

    Dielectric response techniques o Frequency domain ; Frequency Dielectric

    Spectroscopy (FDS) o Time domain ; Polarization Depolarization Current

    (PDC) & Recovery Voltage Measurement (RVM)

  • Copyright 2013 TNB Research Slide No. 9

    Frequency Dielectric Spectroscopy

    Measures the tangent delta over wide frequency range

    An applied alternating voltage polarizes the molecules in the dielectric

    As the frequency is increased, some of the molecule cannot follow the imposed fast change of polarity and stop their participation in polarization process

    Display as dissipation factor or complex permittivity; which decrease with frequency

  • Copyright 2013 TNB Research Slide No. 10

  • Copyright 2013 TNB Research Slide No. 11

    Polarization Depolarization Current

    A dc voltage is applied to the insulation for a time. The current arising from the activation of the polarization process measured.

    Then, the voltage is removed and the object is short-circuited. Thus, the discharging current jumps to a negative value, which goes gradually towards zero.

    Both kinds of currents called polarization and depolarization current

  • Copyright 2013 TNB Research Slide No. 12

    On-line Partial Discharge Measurement All dielectric defects are accompanied by the presence

    of partial discharges

    PDs are in general are always generate electromagnetic signals and often accompanied by emission of sound, light, heat, and chemical reactions

    Thus PD measurements (chemical, electrical and acoustic) are technically able to detect dielectric defects, even identify the presence of a specific defect.

    When a PD occurs inside instrument transformer, an electromagnetic wave is radiated and can be detected using HF sensors.

  • Copyright 2013 TNB Research Slide No. 13

    HFCT

    fibre optical cable

    BNC Cable Analysis software

    Instrument Transformer under test

    USB 2.0

    Batt

    ery

    Test circuit for on-line partial discharge detection on current transformer

  • Copyright 2013 TNB Research Slide No. 14

    3.0 Field Measurements

    132kV current transformer was tested during routine maintenance testing

    Tan delta test results

    Power Factor and Dielectric Response Measurement

    No Phase % tan delta

    1 Red 0.5913 2 Yellow 0.5704 3 Blue 6.5288

    Further analysis using dielectric response measurement

  • Copyright 2013 TNB Research Slide No. 15

    FDS response of current transformer

    * higher response at B phase

  • Copyright 2013 TNB Research Slide No. 16

    The increasing of the responses at low frequency ranges indicated higher moisture content in blue phase of the instrument transformer

    Moisture estimated in cellulose insulation

    The instrument transformer was decided to replace

    No Phase % moisture

    1 Red 2.4 2 Yellow 2.6 3 Blue 4.3

  • Copyright 2013 TNB Research Slide No. 17

    Newly diagnostic techniques adopted by TNB for condition assessment of in-service instrument transformers

    Preliminary work in the laboratory using the technique showed encouraging results

    Partial discharge measurement was carried out on in-service 132kV oil-filled high voltage current transformer.

    On-line PD Measurement

  • Copyright 2013 TNB Research Slide No. 18

    PD laboratory experimental set-up

    HV Source

    Test Vessel HFCT

    MPD600

    Phase resolved PD pattern of void inside the pressboard sample

  • Copyright 2013 TNB Research Slide No. 19

    HFCT MPD600

    External hardware gating

    On-line PD measurement at site

  • Copyright 2013 TNB Research Slide No. 20

    PD pattern for instrument transformer with high PD activity, 800pC

    PD pattern for instrument transformer with low PD activity, 100pC

  • Copyright 2013 TNB Research Slide No. 21

    4.0 Conclusions The condition of the instrument transformer can be

    accurately assessed by various off-line and on-line diagnostic measurements

    TNB has employed advanced diagnostic dielectric response measurement and on-line partial discharge testing as parts of their condition based maintenance strategies

    Condition assessment of in-service instrument transformers - assess the reliability of aged units, and planning for the replacement to avoid any catastrophic failures occurs.

  • Copyright 2013 TNB Research

    Thank You

    Mohd Aizam Talib Contact:- [email protected] TNB Research Sdn. Bhd. No. 1, Lorong Ayer Itam, Kawasan Institusi Penyelidikan, 43000 Kajang, Selangor, MALAYSIA Tel: +603-89225000 Fax: +603-89268828 / 29

    Slide No. 22

    Slide Number 11.0 BackgroundSlide Number 3Slide Number 42.0 Diagnostic of In-Service Instrument TransformerDielectric Dissipation Factor / Power FactorSlide Number 7Dielectric Response AnalysisFrequency Dielectric SpectroscopySlide Number 10Polarization Depolarization CurrentOn-line Partial Discharge MeasurementSlide Number 133.0 Field MeasurementsSlide Number 15Slide Number 16Slide Number 17Slide Number 18Slide Number 19Slide Number 204.0 ConclusionsThank You