DRAWN BY: CHECKED BY: REVISIONS PROJECT NUMBER MEMBERS OF THE AMERICAN INSTITUTE OF ARCHITECTS THIS DOCUMENT IS THE PROPERTY OF STUDIO 3 REPRODUCTION, COPYING OR OTHERWISE USE OF THIS DOCUMENT IS STRICTLY PROHIBITED AND ANY STUDIO 3 DESIGN GROUP,P.C. d e s i g n 1617 WALTON WAY AUGUSTA, GA 30904 studio g r o u p 202002 PLOT DATE: ISSUE DATE: 3420 Julia Avenue Richmond County Public Schools RICHMOND HILL K-8 SCHOOL CLASSROOM ADDITIONS LEGAL ACTION. INFRINGEMENT THEREUPON MAY BE SUBJECT TO DESIGN GROUP, P.C. THE UNAUTHORIZED Augusta, Georgia Construction Documents COPYRIGHT 2007 FTE 1100 #B-17-010-3062.4 CIVIL DESIGN SOLUTIONS, L.L.C. CIVIL ENGINEER MECHANICAL ENGINEER PLUMBING ENGINEER ELECTRICAL ENGINEER ELECTRICAL DESIGN CONSULTANTS STRUCTURAL ENGINEER CRANSTON ENGINEERING ING CONSULTING, INC. ING CONSULTING, INC. MECHANICAL SCHEDULES M0.1 6/17/2020 6/17/2020 SAP JKF AIR DEVICE SCHEDULE TAG MANUFACTURER DESCRIPTION MODEL BORDER TYPE MODULE SIZE OPTIONS A TITUS SQUARE PLAQUE DIFFUSER OMNI LAY-IN 24 x 24 1, 2 B TITUS EGGCRATE RETURN GRILLE 50F LAY-IN 24 x 24 1, 3 C TITUS EGGCRATE RETURN GRILLE 50F LAY-IN 12 x 12 1, 3 OPTIONS: 1. BI-POLAR IONIZATION UNIT 2. 14" INSULATED ROOF CURB WITH CURB SEAL 3. FUSED DISCONNECT BY ELECTRICIAN. COORDINATE WITH ELECTRICAL 4. ECM MOTOR 5. LOUVERED HAIL GUARDS 6. THROUGH THE BASE CONNECTIONS 7. ACTIVE DEHUMIDIFICATION SYSTEM 8. STANDARD LEAK ENTHALPY ECONOMIZER WITH BAROMETRIC RELIEF 9. LOW GAS HEAT 10. TWO STAGE COOLING CAPACITY 11. PHASE MONITOR 12. VERTICAL DISCHARGE AND RETURN 13. 2-YEAR WARRANTY REQUIRED 14. PROVIDE UNITS CAPABLE OF STAGED AIR VOLUME CONTROL 15. INSTALL NEW FILTERS BEFORE TURNOVER AND ONE SET OF FILTERS AND BELTS FOR EACH UNIT FOR ATTIC STOCK 16. WALL MOUNTED, ADJUSTABLE SLIDE THERMOSTAT BY CONTROLS CONTRACTOR. ROOFTOP UNIT SCHEDULE TAG MANUFACTURER FAN PERFORMANCE COOLING PERFORMANCE HEATING PERFORMANCE ELECTRICAL WEIGHT (LBS) OPTIONS MODEL AIRFLOW (CFM) OUTSIDE AIR BHP ESP RPM ENT. AIR DB (°F) ENT. AIR WB (°F) LVG. AIR (°F) SENS. CAP. (BTUh) TOTAL CAP. (BTUh) INPUT CAP. (BTUh) OUTPUT CAP. (BTUh) EFF. (%) ENT. AIR (°F) LVG. AIR (°F) VOLTAGE PHASE MCA MOC P RTU-3-19 CARRIER 48LC*004 1,200 120 1.00 0.50 1,200 97 76 55 29,200 36,000 72,000 59,000 82 65 90 460 3 12 15 740 ALL RTU-3-20 CARRIER 48LC*004 1,200 120 1.00 0.50 1,200 97 76 55 29,200 36,000 72,000 59,000 82 65 90 460 3 12 15 740 ALL RTU-3-21 CARRIER 48LC*004 1,200 120 1.00 0.50 1,200 97 76 55 29,200 36,000 72,000 59,000 82 65 90 460 3 12 15 740 ALL RTU-3-22 CARRIER 48LC*004 1,200 120 1.00 0.50 1,200 97 76 55 29,200 36,000 72,000 59,000 82 65 90 460 3 12 15 740 ALL RTU-5-19 CARRIER 48LC*004 1,200 120 1.00 0.50 1,200 97 76 55 29,200 36,000 72,000 59,000 82 65 90 460 3 12 15 740 ALL RTU-5-20 CARRIER 48LC*004 1,200 120 1.00 0.50 1,200 97 76 55 29,200 36,000 72,000 59,000 82 65 90 460 3 12 15 740 ALL RTU-5-21 CARRIER 48LC*004 1,200 120 1.00 0.50 1,200 97 76 55 29,200 36,000 72,000 59,000 82 65 90 460 3 12 15 740 ALL RTU-5-22 CARRIER 48LC*004 1,200 120 1.00 0.50 1,200 97 76 55 29,200 36,000 72,000 59,000 82 65 90 460 3 12 15 740 ALL RTU-7-25 CARRIER 48LC*004 1,200 120 1.00 0.50 1,200 97 76 55 29,200 36,000 72,000 59,000 82 65 90 460 3 12 15 740 ALL RTU-7-26 CARRIER 48LC*004 1,200 120 1.00 0.50 1,200 97 76 55 29,200 36,000 72,000 59,000 82 65 90 460 3 12 15 740 ALL RTU-7-27 CARRIER 48LC*004 1,200 120 1.00 0.50 1,200 97 76 55 29,200 36,000 72,000 59,000 82 65 90 460 3 12 15 740 ALL RTU-7-28 CARRIER 48LC*004 1,200 120 1.00 0.50 1,200 97 76 55 29,200 36,000 72,000 59,000 82 65 90 460 3 12 15 740 ALL OPTIONS: 1. MANUFACTURER'S STANDARD WHITE FINISH 2. BACK PAN INSULATION OF MIN R-6 INSULATION VALUE 3. PROVIDE LINED GRILLE PLENUM. SEE DETAIL OPTIONS: 1. VARIABLE SPEED COMPRESSOR 2. FUSED DISCONNECT BY ELECTRICAL CONTRACTOR OPTIONS: 1. UNIT TO RECEIVE POWER FROM OUTDOOR UNIT 2. THERMOSTAT INTERFACE MODULE 3. MANUFACTURER'S SUPPLIED AIR FILTER. SUPPLY 1 EXTRA FILTER PER UNIT ATTIC STOCK 4. FIELD INSTALLED FUSED DISCONNECT 5. INTEGRAL CONDENSATE PUMP 6. PLASMA AIR CLEANER EQUAL TO GPS 7. RELAY CONTROL BOARD FOR INTERLOCKING WITH MOTORIZED OUTSIDE AIR DAMPER. 8. WALL-MOUNTED, ADJUSTABLE SLIDE THERMOSTAT BY CONTROLS CONTRACTOR GENERAL NOTES: 1. BRANCH DUCT SIZE IS EQUAL TO AIR DEVICE NECK SIZE UNLESS OTHERWISE NOTED. 2. COORDINATE ALL EQUIPMENT INSTALLATION FINAL LOCATIONS TO ALLOW FOR SUFFICIENT MAINTENANCE ACCESS. VRF INDOOR UNIT SCHEDULE TAG MANUFACTURER MODEL NOMINAL TONS MOUNT FAN CFM OUTSIDE AIR CFM ASSOCIATED HP COOLING CAPACITY (BTUh) HEATING CAPACITY (BTUh) ELECTRICAL WEIGHT (LBS) SEER EER OPTIONS VOLTAGE PHASE MCA IHP-3-1 MITSUBISHI NTXCKS12 1.0 CEILING CASSETTE 330 10 OHP-11 12,000 13,000 208 1 0.3 35 19.0 13.5 ALL IHP-3-2 MITSUBISHI NTXCKS12 1.0 CEILING CASSETTE 330 10 OHP-11 12,000 13,000 208 1 0.3 35 19.0 13.5 ALL VRF OUTDOOR UNIT SCHEDULE TAG MANUFACTURER MODEL NOMINAL TONS COOLING CAPACITY (BTUh) HEATING CAPACITY (BTUh) ELECTRICAL WEIGHT (LBS) SEER EER OPTIONS VOLTAGE PHASE MCA MOCP OHP-11 MITSUBISHI NTXMPH24 2.0 22,000 25,000 208 1 30.5 40 200 19.0 13.5 ALL 06/17/2020

Transcript of 1617 WALTON WAY AUGUSTA, GA 30904 - contractmgmtinc.com · 2020. 8. 19. · painted steel sched. 40...

  • DR

    AW

    N B

    Y:

    CH

    EC

    KED

    BY

    :

    REV

    ISIO

    NS

    PR

    OJE

    CT

    NU

    MB

    ER

    MEMBERS OF THE

    AMERICAN INSTITUTE OF ARCHITECTS

    THIS DOCUMENT IS THE PROPERTY OF STUDIO 3

    REPRODUCTION, COPYING OR OTHERWISE USE OFTHIS DOCUMENT IS STRICTLY PROHIBITED AND ANY

    STUDIO 3 DESIGN GROUP,P.C.

    d e s i g n

    1617 WALTON WAYAUGUSTA, GA 30904

    studio

    g r o u p

    202002

    PLO

    T D

    ATE:

    ISSU

    E D

    ATE:

    3420 J

    ulia

    Avenue

    Ric

    hm

    on

    d C

    ou

    nty

    Pu

    blic S

    ch

    oo

    lsR

    ICH

    MO

    ND

    HIL

    L K

    -8 S

    CH

    OO

    LC

    LA

    SS

    RO

    OM

    AD

    DIT

    ION

    S

    LEGAL ACTION.INFRINGEMENT THEREUPON MAY BE SUBJECT TO

    DESIGN GROUP, P.C. THE UNAUTHORIZED

    Augusta

    ,G

    eorg

    ia

    Constr

    uction D

    ocum

    ents

    COPYRIGHT 2007

    FT

    E 1

    100

    #B

    -17-0

    10-3

    062.4

    CIVIL DESIGN SOLUTIONS, L.L.C.

    CIVIL ENGINEER

    MECHANICAL ENGINEER

    PLUMBING ENGINEER

    ELECTRICAL ENGINEER

    ELECTRICAL DESIGN CONSULTANTS

    STRUCTURAL ENGINEER

    CRANSTON ENGINEERING

    ING CONSULTING, INC.

    ING CONSULTING, INC.

    ME

    CH

    AN

    ICA

    L S

    CH

    ED

    UL

    ES

    M0.16/17/20

    20

    6/1

    7/2

    020

    SA

    P

    JK

    F

    AIR DEVICE SCHEDULE

    TAG MANUFACTURER DESCRIPTION MODEL BORDER TYPE MODULE SIZE OPTIONS

    A TITUS SQUARE PLAQUE DIFFUSER OMNI LAY-IN 24 x 24 1, 2

    B TITUS EGGCRATE RETURN GRILLE 50F LAY-IN 24 x 24 1, 3

    C TITUS EGGCRATE RETURN GRILLE 50F LAY-IN 12 x 12 1, 3

    OPTIONS:1. BI-POLAR IONIZATION UNIT2. 14" INSULATED ROOF CURB WITH CURB SEAL3. FUSED DISCONNECT BY ELECTRICIAN. COORDINATE WITH ELECTRICAL4. ECM MOTOR5. LOUVERED HAIL GUARDS6. THROUGH THE BASE CONNECTIONS7. ACTIVE DEHUMIDIFICATION SYSTEM8. STANDARD LEAK ENTHALPY ECONOMIZER WITH BAROMETRIC RELIEF9. LOW GAS HEAT10. TWO STAGE COOLING CAPACITY11. PHASE MONITOR12. VERTICAL DISCHARGE AND RETURN13. 2-YEAR WARRANTY REQUIRED14. PROVIDE UNITS CAPABLE OF STAGED AIR VOLUME CONTROL15. INSTALL NEW FILTERS BEFORE TURNOVER AND ONE SET OF FILTERS AND BELTS FOR EACH UNIT FOR ATTIC STOCK16. WALL MOUNTED, ADJUSTABLE SLIDE THERMOSTAT BY CONTROLS CONTRACTOR.

    ROOFTOP UNIT SCHEDULE

    TAG MANUFACTURER

    FAN PERFORMANCE COOLING PERFORMANCE HEATING PERFORMANCE ELECTRICALWEIGHT

    (LBS)OPTIONS

    MODELAIRFLOW

    (CFM)OUTSIDE

    AIRBHP ESP RPM

    ENT. AIRDB (°F)

    ENT. AIRWB (°F)

    LVG. AIR(°F)

    SENS. CAP.(BTUh)

    TOTAL CAP.(BTUh)

    INPUT CAP.(BTUh)

    OUTPUT CAP.(BTUh)

    EFF. (%)ENT. AIR

    (°F)LVG. AIR

    (°F)VOLTAGE PHASE MCA

    MOCP

    RTU-3-19 CARRIER 48LC*004 1,200 120 1.00 0.50 1,200 97 76 55 29,200 36,000 72,000 59,000 82 65 90 460 3 12 15 740 ALL

    RTU-3-20 CARRIER 48LC*004 1,200 120 1.00 0.50 1,200 97 76 55 29,200 36,000 72,000 59,000 82 65 90 460 3 12 15 740 ALL

    RTU-3-21 CARRIER 48LC*004 1,200 120 1.00 0.50 1,200 97 76 55 29,200 36,000 72,000 59,000 82 65 90 460 3 12 15 740 ALL

    RTU-3-22 CARRIER 48LC*004 1,200 120 1.00 0.50 1,200 97 76 55 29,200 36,000 72,000 59,000 82 65 90 460 3 12 15 740 ALL

    RTU-5-19 CARRIER 48LC*004 1,200 120 1.00 0.50 1,200 97 76 55 29,200 36,000 72,000 59,000 82 65 90 460 3 12 15 740 ALL

    RTU-5-20 CARRIER 48LC*004 1,200 120 1.00 0.50 1,200 97 76 55 29,200 36,000 72,000 59,000 82 65 90 460 3 12 15 740 ALL

    RTU-5-21 CARRIER 48LC*004 1,200 120 1.00 0.50 1,200 97 76 55 29,200 36,000 72,000 59,000 82 65 90 460 3 12 15 740 ALL

    RTU-5-22 CARRIER 48LC*004 1,200 120 1.00 0.50 1,200 97 76 55 29,200 36,000 72,000 59,000 82 65 90 460 3 12 15 740 ALL

    RTU-7-25 CARRIER 48LC*004 1,200 120 1.00 0.50 1,200 97 76 55 29,200 36,000 72,000 59,000 82 65 90 460 3 12 15 740 ALL

    RTU-7-26 CARRIER 48LC*004 1,200 120 1.00 0.50 1,200 97 76 55 29,200 36,000 72,000 59,000 82 65 90 460 3 12 15 740 ALL

    RTU-7-27 CARRIER 48LC*004 1,200 120 1.00 0.50 1,200 97 76 55 29,200 36,000 72,000 59,000 82 65 90 460 3 12 15 740 ALL

    RTU-7-28 CARRIER 48LC*004 1,200 120 1.00 0.50 1,200 97 76 55 29,200 36,000 72,000 59,000 82 65 90 460 3 12 15 740 ALL

    OPTIONS:1. MANUFACTURER'S STANDARD WHITE FINISH2. BACK PAN INSULATION OF MIN R-6 INSULATION VALUE3. PROVIDE LINED GRILLE PLENUM. SEE DETAIL

    OPTIONS:1. VARIABLE SPEED COMPRESSOR2. FUSED DISCONNECT BY ELECTRICAL CONTRACTOR

    OPTIONS:1. UNIT TO RECEIVE POWER FROM OUTDOOR UNIT2. THERMOSTAT INTERFACE MODULE3. MANUFACTURER'S SUPPLIED AIR FILTER. SUPPLY 1 EXTRA FILTER PER UNIT ATTIC STOCK4. FIELD INSTALLED FUSED DISCONNECT5. INTEGRAL CONDENSATE PUMP6. PLASMA AIR CLEANER EQUAL TO GPS7. RELAY CONTROL BOARD FOR INTERLOCKING WITH MOTORIZED OUTSIDE AIR DAMPER.8. WALL-MOUNTED, ADJUSTABLE SLIDE THERMOSTAT BY CONTROLS CONTRACTOR

    GENERAL NOTES:1. BRANCH DUCT SIZE IS EQUAL TO AIR DEVICE NECK SIZE UNLESS OTHERWISE NOTED.2. COORDINATE ALL EQUIPMENT INSTALLATION FINAL LOCATIONS TO ALLOW FOR SUFFICIENT MAINTENANCE ACCESS.

    VRF INDOOR UNIT SCHEDULE

    TAG MANUFACTURER MODELNOMINAL

    TONSMOUNT

    FANCFM

    OUTSIDEAIR CFM

    ASSOCIATEDHP

    COOLINGCAPACITY (BTUh)

    HEATINGCAPACITY (BTUh)

    ELECTRICAL WEIGHT(LBS)

    SEER EER OPTIONSVOLTAGE PHASE MCA

    IHP-3-1 MITSUBISHI NTXCKS12 1.0 CEILING CASSETTE 330 10 OHP-11 12,000 13,000 208 1 0.3 35 19.0 13.5 ALL

    IHP-3-2 MITSUBISHI NTXCKS12 1.0 CEILING CASSETTE 330 10 OHP-11 12,000 13,000 208 1 0.3 35 19.0 13.5 ALL

    VRF OUTDOOR UNIT SCHEDULE

    TAG MANUFACTURER MODEL NOMINAL TONS COOLING CAPACITY (BTUh) HEATING CAPACITY (BTUh)ELECTRICAL

    WEIGHT (LBS) SEER EER OPTIONSVOLTAGE PHASE MCA MOCP

    OHP-11 MITSUBISHI NTXMPH24 2.0 22,000 25,000 208 1 30.5 40 200 19.0 13.5 ALL

    06/17/2020

  • END PLUGCLEANOUT

    BARB ADAPTOR WITHSTEEL BANDINGCLAMPS

    TYPE "M" COPPER PIPE WITH DWV FITTINGS

    TO NEAREST DRAIN

    CLEAR VINYL TUBING(3'-0" MAXIMUM)

    CONDENSATE PUMP CONNECTION

    FAN COIL

    NOTE: CONTRACTOR SHALL REFERENCEFINAL EQUIPMENT MANUFACTURERINSTALLATION INSTRUCTIONS FORFINAL DIMENSIONS AND PLACEMENTREQUIREMENTS.

    HAND TIGHT PLUG

    WATER SEAL

    LINE SIZE OF CONDENSATE CONNECTION ON UNIT

    SLOPE TO DRAINH

    H = FAN INLET PRESSURE (IN. W.C.) + 1 INCH

    H/2 MIN.

    FROM COIL PAN

    EGG CRATE RETURN GRILLE WITH BORDER, FRAME & 22"x22" NECK

    LAY-IN CEILING

    ACCOUSTICALLY LINED PLENUM

    RETURN/EXHAUST PLENUM

    LEGEND

    W = WIDTHH = HEIGHTD = DIAMETERV.D. = MANUAL VOLUME DAMPER WITH STANDOFF

    VERTICAL SUPPLY DUCT

    WxH

    VDVD

    VD

    VD

    VDVD

    WxH

    CROWN 3300-DSOR EQUAL

    90° ELBOW WITH DOUBLE THICKNESS TURNING VANES

    4'-0"

    MA

    XIM

    UM

    FLEXIBLE DUCT. PROVIDE SHEET METAL FITTINGS FOR ALL CHANGES OF DIRECTION.

    CROWN 314-DSOOR EQUAL

    BULLHEAD TEE WITH TURNING VANES PER SMACNA

    ADJUSTABLE PIPING ROLLER SUPPORT W/ HDPE BASE. SPACE SUPPORTS NO GREATER THAN 7'-0" ON CENTER.

    PAINTED STEEL SCHED. 40 GAS PIPING.

    SCHEDULE 40 PVC CONDENSATE DRAIN PIPE. PRIMED AND PAINTED.

    ROOFTOP UNIT

    UNION

    GAS COCK

    SUPPORT EQUAL TO B-LINE MODEL C610 WITH B-LINE ARMAFIX CLAMP.

    ROOF

    ROOF CURB

    GAS PRESSURE REGULATOR & OPD (OVER PRESSUREIZATION DEVICE) W/ VENT PROTECTION

    3" LONG SEDIMENT TRAP W/ REMOVABLE SCREW CAP

    Y-STRAINER

    T/P TESTING PORTS

    UNION

    DR

    AW

    N B

    Y:

    CH

    EC

    KED

    BY

    :

    REV

    ISIO

    NS

    PR

    OJE

    CT

    NU

    MB

    ER

    MEMBERS OF THE

    AMERICAN INSTITUTE OF ARCHITECTS

    THIS DOCUMENT IS THE PROPERTY OF STUDIO 3

    REPRODUCTION, COPYING OR OTHERWISE USE OFTHIS DOCUMENT IS STRICTLY PROHIBITED AND ANY

    STUDIO 3 DESIGN GROUP,P.C.

    d e s i g n

    1617 WALTON WAYAUGUSTA, GA 30904

    studio

    g r o u p

    202002

    PLO

    T D

    ATE:

    ISSU

    E D

    ATE:

    3420 J

    ulia

    Avenue

    Ric

    hm

    on

    d C

    ou

    nty

    Pu

    blic S

    ch

    oo

    lsR

    ICH

    MO

    ND

    HIL

    L K

    -8 S

    CH

    OO

    LC

    LA

    SS

    RO

    OM

    AD

    DIT

    ION

    S

    LEGAL ACTION.INFRINGEMENT THEREUPON MAY BE SUBJECT TO

    DESIGN GROUP, P.C. THE UNAUTHORIZED

    Augusta

    ,G

    eorg

    ia

    Constr

    uction D

    ocum

    ents

    COPYRIGHT 2007

    FT

    E 1

    100

    #B

    -17-0

    10-3

    062.4

    CIVIL DESIGN SOLUTIONS, L.L.C.

    CIVIL ENGINEER

    MECHANICAL ENGINEER

    PLUMBING ENGINEER

    ELECTRICAL ENGINEER

    ELECTRICAL DESIGN CONSULTANTS

    STRUCTURAL ENGINEER

    CRANSTON ENGINEERING

    ING CONSULTING, INC.

    ING CONSULTING, INC.

    ME

    CH

    AN

    ICA

    L D

    ET

    AIL

    S

    M0.26/17/20

    20

    6/1

    7/2

    020

    SA

    P

    JK

    F

    NOT TO SCALEM0.2

    1 CASSETTE COIL CONDENSATE PIPENOT TO SCALEM0.2

    2 NEGATIVE PRESSURE CONDENSATE DRAIN TRAPNOT TO SCALEM0.2

    3 RETURN/EXHAUST GRILLE

    NOT TO SCALEM0.2

    4 TYPICAL SUPPLY OR RETURN DUCTNOT TO SCALEM0.2

    5 TYPICAL GAS ROOFTOP PIPING

    06/17/2020

  • 2ND GRADE317

    2ND GRADE3162ND GRADE

    315

    2ND GRADE318

    GIRL'S315.2

    BOY'S315.3

    VEST.315.1

    GIRL'S316.3 VESTIBULE

    316.1BOY'S316.2

    NEW CLASSROOM319

    NEW CLASSROOM320

    ASSIST. PRINCIPAL321

    BOOK STORAGE322

    NEW CLASSROOM323 NEW CLASSROOM

    324

    VE

    ST

    IBU

    LE

    319.1

    BOY'S TLT.319.2

    GIRL'S TLT.319.3 V

    ES

    TIB

    UL

    E320.1

    BOY'S TLT.320.2

    GIRL'S TLT.320.3

    CORRIDOR300

    8"øA

    300

    8"øA

    300

    8"øA

    300

    8"øA

    300

    12"x

    10"

    SA

    20"x

    9"

    SA

    12"x

    10"

    SA

    20"x

    9"

    SA

    8"øA

    300

    8"øA

    300

    8"øA

    300

    8"øA

    300

    22"x22"B

    1,200ø16"

    22"x22"B

    1,200

    ø16"

    8"x

    8"

    EA

    8"x6" EA

    6"x

    4"

    EA

    11"x11"C

    75

    11"x11"C

    75

    8"x6" EA

    6"x

    4"

    EA

    11"x11"C

    75

    11"x11"C

    75

    (E) ECH-1

    20"x

    9"

    SA

    20"x

    9"

    SA

    12"x

    10"

    SA

    12"x

    10"

    SA

    8"øA

    300

    8"øA

    300

    8"øA

    300

    8"øA

    300

    22"x22"B

    1,200

    ø16" ø16"

    22"x22"B

    1,200

    8"øA

    300

    8"øA

    300

    8"øA

    300

    8"øA

    300

    8"øA

    240

    (E) 8"ø

    240

    (E) ECH-1

    IHP-3-1 IHP-3-2

    1 14"ø OA4"ø OA

    8"x

    8"

    EA

    10"x

    8"

    SA

    10"x

    8"

    SA

    6

    6

    2

    3/4" C

    3/4" C33

    4 T

    T

    77

    77

    (E)8

    "x6"

    EA

    11

    T T

    TT

    S

    S

    12

    12

    EXISTING BUILDING

    K-2ND ADDITION

    KEY PLAN

    N

    RTU-3-17

    RTU-3-18

    RTU-3-15

    RTU-3-16

    (E) EF-3

    3/4

    " N

    G

    5

    3/4

    " N

    G3/4

    " N

    G

    1/2" NG

    1/2" NG

    1/2" NG

    1/2" NG

    RTU-3-22

    RTU-3-20

    RTU-3-19

    RTU-3-21

    OHP-11

    (E)

    (E)

    (E)

    (E)

    9

    9

    9

    9

    10

    8

    DR

    AW

    N B

    Y:

    CH

    EC

    KED

    BY

    :

    REV

    ISIO

    NS

    PR

    OJE

    CT

    NU

    MB

    ER

    MEMBERS OF THE

    AMERICAN INSTITUTE OF ARCHITECTS

    THIS DOCUMENT IS THE PROPERTY OF STUDIO 3

    REPRODUCTION, COPYING OR OTHERWISE USE OFTHIS DOCUMENT IS STRICTLY PROHIBITED AND ANY

    STUDIO 3 DESIGN GROUP,P.C.

    d e s i g n

    1617 WALTON WAYAUGUSTA, GA 30904

    studio

    g r o u p

    202002

    PLO

    T D

    ATE:

    ISSU

    E D

    ATE:

    3420 J

    ulia

    Avenue

    Ric

    hm

    on

    d C

    ou

    nty

    Pu

    blic S

    ch

    oo

    lsR

    ICH

    MO

    ND

    HIL

    L K

    -8 S

    CH

    OO

    LC

    LA

    SS

    RO

    OM

    AD

    DIT

    ION

    S

    LEGAL ACTION.INFRINGEMENT THEREUPON MAY BE SUBJECT TO

    DESIGN GROUP, P.C. THE UNAUTHORIZED

    Augusta

    ,G

    eorg

    ia

    Constr

    uction D

    ocum

    ents

    COPYRIGHT 2007

    FT

    E 1

    100

    #B

    -17-0

    10-3

    062.4

    CIVIL DESIGN SOLUTIONS, L.L.C.

    CIVIL ENGINEER

    MECHANICAL ENGINEER

    PLUMBING ENGINEER

    ELECTRICAL ENGINEER

    ELECTRICAL DESIGN CONSULTANTS

    STRUCTURAL ENGINEER

    CRANSTON ENGINEERING

    ING CONSULTING, INC.

    ING CONSULTING, INC.

    ME

    CH

    AN

    ICA

    L -

    K-2

    ND

    GR

    AD

    E A

    DD

    ITIO

    N

    M1.16/17/20

    20

    6/1

    7/2

    020

    SA

    P

    JK

    F

    NO

    RT

    H

    1/8" = 1'-0"M1.1

    1 MECHANICAL - K-2ND GRADE CLASSROOM ADDITION

    GENERAL NOTES:

    KEYNOTES

    (THIS SHEET ONLY)

    (THIS SHEET ONLY)

    NO

    RT

    H

    1/8" = 1'-0"M1.1

    2 MECHANICAL ROOF PLAN - K-2ND GRADE CLASSROOM ADDITION

    1. BRANCH DUCT SIZE IS EQUAL TO AIR DEVICE NECK SIZE UNLESS OTHERWISE NOTED.

    2. COORDINATE ALL EQUIPMENT INSTALLATION FINAL LOCATIONS TO ALLOW FOR SUFFICIENT MAINTENANCE ACCESS.

    3. REFRIGERANT AND CONDENSATE DRAIN PIPING SHALL BE INSULATED WITH ½" ARMFLEX FOAM

    TERMINATE OUTSIDE AIR INTAKE DUCT TO WALL BRICK VENT WITH INSECT SCREEN. COMPARABLE TO GREENHECK MODEL BVE-808.

    ROUTE CONDENSATE PIPING WITH ½" ARMAFLEX INSULATION DOWN EXTERIOR WALL, CONCEALED IN WALL CAVITY OR AIR SPACE, AND TERMINATE TO THE EXTERIOR WITH 90° ELBOW, ABOVE CONCRETE SPLASH BLOCK INSTALLED OVER FINISHED GRADE. PAINT ANY EXPOSED PVC TO MATCH WALL

    REFER TO CONDENSATE DRAIN CONNECTION DETAIL #1 / M0.2

    CLEANOUT

    RECALIBRATING (E) EF-3 TO 1,000 CFM SO AS TO ACCOMMODATE NEW EXHAUST TERMINALS. TEST AND BALANCE 4 NEW DIFFUSERS WITH 8 EXISTING DIFFUSERS AT 75 CFM EACH.

    REMOVE AND RELOCATE EXISTING ELECTRIC CEILING HEATER AND ASSOCIATED TEMPERATURE SENSOR (S) TO NEW LOCATION. REPAIR VOID FROM EXISTING LOCATION WITH LIKE MATERIALS AND METHODS. CONTRACTOR SHALL COORDINATE WITH ELECTRICAL.

    DUCT UP TO UNIT ON ROOF. SUPPLY DUCT IN CLASSROOMS SHALL RUN PARALLEL TO CORRIDOR WALLS AND INSTALLED WITH NO GREATER THAN 2 FEET BETWEEN FACE OF DUCT AND CORRIDOR WALL (TO ALLOW ROOM FOR ELECTRICAL INSTALLATION). TOP OF INSULATION SHALL BE BUTTED UP AGAINST THE BOTTOM OF JOIST. COORDINATE ROOF CURB INSTALLATION LOCATION SO THAT THE CLOSEST EDGE OF THE CURB IS NO FURTHER THAN 2' AWAY FROM THE JOIST BEARING LOCATION (CORRIDOR WALL). CONTROL BOX FOR UNIT CONTROLS SHALL BE LOCATED ABOVE THE CEILING IN THE CORRIDOR. COORDINATE WITH ELECTRICAL AND CONTROLS CONTRACTOR. COORDINATE LOCATION OF CONTROL BOX WITH DUCTWORK AND PIPING LOCATED ABOVE THE CEILING.

    NEW GAS LINE TAP INTO EXISTING MAIN AT 1½"ø APPROXIMATELY 180' PLAN NORTH (NOT SHOWN) WITH GAS COCK. CONTRACTOR TO FIELD VERIFY.

    CONNECT NEW ROOF TOP UNIT INTO EXISTING GAS PIPING. REFER TO DETAIL #5 / M0.2 FOR TYPICAL GAS ROOFTOP PIPING ARRANGEMENT

    COORDINATE WITH ROOFING CONTRACTOR TO PROVIDE CURB TO SUPPORT DUCTLESS AIR CONDITIONER. CURB SHALL BE FLASHED INTO ROOFING SYSTEM. PROVIDE FLASHED PITCH POCKET FOR REFRIGERANT PIPING PENETRATION THROUGH ROOF.

    BALANCE NEW AND 4 EXISTING AIR DIFFUSERS SERVING CORRIDOR TO 240 CFM EACH.

    INSTALL MOTORIZED, NORMALLY SPRING CLOSED, INTAKE DAMPER INTERLOCKED WITH IHP RELAY. PROVIDE TRANSFORMER AS REQUIRED.

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    06/17/2020

  • EXISTING BUILDING

    3RD-5TH ADDITION

    KEY PLAN

    N

    BOYS514

    5TH GRADE516

    GIRLS512

    5TH GRADE518

    5TH GRADE517

    NEW CLASSROOM519

    NEW CLASSROOM520

    NEW CLASSROOM521

    NEW CLASSROOM522

    CORRIDOR500

    (E) ECH-1

    (E) ECH-1

    8"øA

    240

    (E) 8"ø

    240

    T

    T

    T

    T

    20"x9" SA

    12"x10" SA8"øA

    300

    8"øA

    300 8"øA

    300

    8"øA

    300

    8"øA

    300

    22"x22"B

    1,200

    8"øA

    300

    8"øA

    300

    8"øA

    300

    20"x9" SA

    12"x10" SA

    ø16

    "

    ø16

    "22"x22"B

    1,200

    10"x8" SA

    20"x9" SA

    12"x10" SA

    ø16

    "

    22"x22"B

    1,200 8"øA

    300

    8"øA

    300

    8"øA

    300

    8"øA

    300

    22"x22"B

    1,200

    ø16

    "

    8"øA

    300

    8"øA

    300

    8"øA

    300

    8"øA

    300

    20"x9" SA

    12"x10" SA

    2

    1

    1

    2

    2

    2

    5

    S

    S

    RTU-5-17

    RTU-5-18

    RTU-5-16

    1" NG

    3/4" NG

    3/4" NG

    1/2"

    NG

    1/2"

    NG

    1/2"

    NG

    1/2"

    NG

    RTU-5-22

    RTU-5-19

    RTU-5-20

    RTU-5-21

    (E)

    (E)

    (E)

    3

    4

    4

    4

    4

    DR

    AW

    N B

    Y:

    CH

    EC

    KED

    BY

    :

    REV

    ISIO

    NS

    PR

    OJE

    CT

    NU

    MB

    ER

    MEMBERS OF THE

    AMERICAN INSTITUTE OF ARCHITECTS

    THIS DOCUMENT IS THE PROPERTY OF STUDIO 3

    REPRODUCTION, COPYING OR OTHERWISE USE OFTHIS DOCUMENT IS STRICTLY PROHIBITED AND ANY

    STUDIO 3 DESIGN GROUP,P.C.

    d e s i g n

    1617 WALTON WAYAUGUSTA, GA 30904

    studio

    g r o u p

    202002

    PLO

    T D

    ATE:

    ISSU

    E D

    ATE:

    3420 J

    ulia

    Avenue

    Ric

    hm

    on

    d C

    ou

    nty

    Pu

    blic S

    ch

    oo

    lsR

    ICH

    MO

    ND

    HIL

    L K

    -8 S

    CH

    OO

    LC

    LA

    SS

    RO

    OM

    AD

    DIT

    ION

    S

    LEGAL ACTION.INFRINGEMENT THEREUPON MAY BE SUBJECT TO

    DESIGN GROUP, P.C. THE UNAUTHORIZED

    Augusta

    ,G

    eorg

    ia

    Constr

    uction D

    ocum

    ents

    COPYRIGHT 2007

    FT

    E 1

    100

    #B

    -17-0

    10-3

    062.4

    CIVIL DESIGN SOLUTIONS, L.L.C.

    CIVIL ENGINEER

    MECHANICAL ENGINEER

    PLUMBING ENGINEER

    ELECTRICAL ENGINEER

    ELECTRICAL DESIGN CONSULTANTS

    STRUCTURAL ENGINEER

    CRANSTON ENGINEERING

    ING CONSULTING, INC.

    ING CONSULTING, INC.

    ME

    CH

    AN

    ICA

    L -

    3R

    D-5

    TH

    GR

    AD

    E A

    DD

    ITIO

    N

    M1.26/17/20

    20

    6/1

    7/2

    020

    SA

    P

    JK

    F

    NO

    RT

    H

    1/8" = 1'-0"M1.2

    1 MECHANICAL - 3RD-5TH GRADE CLASSROOM ADDITION

    NO

    RT

    H

    1/8" = 1'-0"M1.2

    2 MECHANICAL ROOF PLAN - 3RD-5TH GRADE CLASSROOM ADDITION

    GENERAL NOTES:

    KEYNOTES

    (THIS SHEET ONLY)

    (THIS SHEET ONLY)

    1. BRANCH DUCT SIZE IS EQUAL TO AIR DEVICE NECK SIZE UNLESS OTHERWISE NOTED.

    2. COORDINATE ALL EQUIPMENT INSTALLATION FINAL LOCATIONS TO ALLOW FOR SUFFICIENT MAINTENANCE ACCESS.

    3. REFRIGERANT AND CONDENSATE DRAIN PIPING SHALL BE INSULATED WITH ½" ARMFLEX FOAM

    REMOVE AND RELOCATE EXISTING ELECTRIC CEILING HEATER AND ASSOCIATED TEMPERATURE SENSOR (S) TO NEW LOCATION. REPAIR VOID FROM EXISTING LOCATION WITH LIKE MATERIALS AND METHODS. CONTRACTOR SHALL COORDINATE WITH ELECTRICAL.

    DUCT UP TO UNIT ON ROOF. SUPPLY DUCT IN CLASSROOMS SHALL RUN PARALLEL TO CORRIDOR WALLS AND INSTALLED WITH NO GREATER THAN 2 FEET BETWEEN FACE OF DUCT AND CORRIDOR WALL (TO ALLOW ROOM FOR ELECTRICAL INSTALLATION). TOP OF INSULATION SHALL BE BUTTED UP AGAINST THE BOTTOM OF JOIST. COORDINATE ROOF CURB INSTALLATION LOCATION SO THAT THE CLOSEST EDGE OF THE CURB IS NO FURTHER THAN 2' AWAY FROM THE JOIST BEARING LOCATION (CORRIDOR WALL). CONTROL BOX FOR UNIT CONTROLS SHALL BE LOCATED ABOVE THE CEILING IN THE CORRIDOR. COORDINATE WITH ELECTRICAL AND CONTROLS CONTRACTOR. COORDINATE LOCATION OF CONTROL BOX WITH DUCTWORK AND PIPING LOCATED ABOVE THE CEILING.

    NEW GAS LINE TAP INTO EXISTING MAIN AT 1½"ø APPROXIMATELY 100' PLAN NORTHWEST (NOT SHOWN) WITH GAS COCK. CONTRACTOR TO FIELD VERIFY.

    CONNECT NEW ROOF TOP UNIT INTO EXISTING GAS PIPING. REFER TO DETAIL #5 / M0.2 FOR TYPICAL GAS ROOFTOP PIPING ARRANGEMENT

    BALANCE NEW AND EXISTING 4 AIR DIFFUSERS SERVING CORRIDOR TO 240 CFM EACH.

    1

    2

    3

    4

    5

    06/17/2020

  • EXISTING BUILDING

    5TH-8TH ADDITION

    KEY PLAN

    N

    6TH-8TH CLASSROOM724

    6TH-8TH CLASSROOM720

    6TH-8TH CLASSROOM722

    6TH-8TH CLASSROOM719

    6TH-8TH CLASSROOM723

    6TH-8TH CLASSROOM721

    NEW CLASSROOM725

    NEW CLASSROOM726

    NEW CLASSROOM727

    NEW CLASSROOM728

    CORRIDOR700

    (E) ECH-1

    (E) ECH-18"øA

    240

    20"x9" SA

    12"x10" SA

    8"øA

    3008"øA

    300

    8"øA

    300

    8"øA

    300

    22"x22"B

    1,200ø16"

    12"x10" SA20"x9" SA

    8"øA

    300

    8"øA

    3008"øA

    300

    8"øA

    300

    22"x22"B

    1,200

    ø16"

    12"x10" SAT

    20"x9" SA

    22"x22"B

    1,200

    8"øA

    300

    8"øA

    300

    8"øA

    300

    8"øA

    300

    20"x9" SA

    12"x10" SAT

    ø16"

    22"x22"B

    1,200

    ø16"

    8"øA

    300

    8"øA

    300

    8"øA

    300

    8"øA

    300

    TT

    1

    1

    2 2

    22

    5

    10"x8" SA

    (E) 8"ø

    240

    SS

    RTU-7-23RTU-7-21

    RTU-7-20 RTU-7-22 RTU-7-24

    RTU-7-19

    3/4" NG3/4" NG3/4" NG1" NG

    3/4" NG 1/2" NG

    1/2

    " N

    G

    1/2

    " N

    G

    1/2

    " N

    G

    1/2

    " N

    G

    RTU-7-25 RTU-7-27

    RTU-7-26 RTU-7-28

    (E)(E)

    (E)

    3

    4 4

    4 4

    (E)(E)

    (E)

    DR

    AW

    N B

    Y:

    CH

    EC

    KED

    BY

    :

    REV

    ISIO

    NS

    PR

    OJE

    CT

    NU

    MB

    ER

    MEMBERS OF THE

    AMERICAN INSTITUTE OF ARCHITECTS

    THIS DOCUMENT IS THE PROPERTY OF STUDIO 3

    REPRODUCTION, COPYING OR OTHERWISE USE OFTHIS DOCUMENT IS STRICTLY PROHIBITED AND ANY

    STUDIO 3 DESIGN GROUP,P.C.

    d e s i g n

    1617 WALTON WAYAUGUSTA, GA 30904

    studio

    g r o u p

    202002

    PLO

    T D

    ATE:

    ISSU

    E D

    ATE:

    3420 J

    ulia

    Avenue

    Ric

    hm

    on

    d C

    ou

    nty

    Pu

    blic S

    ch

    oo

    lsR

    ICH

    MO

    ND

    HIL

    L K

    -8 S

    CH

    OO

    LC

    LA

    SS

    RO

    OM

    AD

    DIT

    ION

    S

    LEGAL ACTION.INFRINGEMENT THEREUPON MAY BE SUBJECT TO

    DESIGN GROUP, P.C. THE UNAUTHORIZED

    Augusta

    ,G

    eorg

    ia

    Constr

    uction D

    ocum

    ents

    COPYRIGHT 2007

    FT

    E 1

    100

    #B

    -17-0

    10-3

    062.4

    CIVIL DESIGN SOLUTIONS, L.L.C.

    CIVIL ENGINEER

    MECHANICAL ENGINEER

    PLUMBING ENGINEER

    ELECTRICAL ENGINEER

    ELECTRICAL DESIGN CONSULTANTS

    STRUCTURAL ENGINEER

    CRANSTON ENGINEERING

    ING CONSULTING, INC.

    ING CONSULTING, INC.

    ME

    CH

    AN

    ICA

    L -

    6T

    H-8

    TH

    GR

    AD

    E A

    DD

    ITIO

    N

    M1.36/17/20

    20

    6/1

    7/2

    020

    SA

    P

    JK

    F

    NO

    RT

    H

    1/8" = 1'-0"M1.3

    1 MECHANICAL - 6TH-8TH GRADE CLASSROOM ADDITION

    NO

    RT

    H

    1/8" = 1'-0"M1.3

    2 MECHANICAL ROOF PLAN - 6TH-8TH GRADE CLASSROOM ADDITION

    GENERAL NOTES:

    KEYNOTES

    (THIS SHEET ONLY)

    (THIS SHEET ONLY)

    1. BRANCH DUCT SIZE IS EQUAL TO AIR DEVICE NECK SIZE UNLESS OTHERWISE NOTED.

    2. COORDINATE ALL EQUIPMENT INSTALLATION FINAL LOCATIONS TO ALLOW FOR SUFFICIENT MAINTENANCE ACCESS.

    3. REFRIGERANT AND CONDENSATE DRAIN PIPING SHALL BE INSULATED WITH ½" ARMFLEX FOAM

    REMOVE AND RELOCATE EXISTING ELECTRIC CEILING HEATER AND ASSOCIATED TEMPERATURE SENSOR (S) TO NEW LOCATION. REPAIR VOID FROM EXISTING LOCATION WITH LIKE MATERIALS AND METHODS. CONTRACTOR SHALL COORDINATE WITH ELECTRICAL.

    DUCT UP TO UNIT ON ROOF. SUPPLY DUCT IN CLASSROOMS SHALL RUN PARALLEL TO CORRIDOR WALLS AND INSTALLED WITH NO GREATER THAN 2 FEET BETWEEN FACE OF DUCT AND CORRIDOR WALL (TO ALLOW ROOM FOR ELECTRICAL INSTALLATION). TOP OF INSULATION SHALL BE BUTTED UP AGAINST THE BOTTOM OF JOIST. COORDINATE ROOF CURB INSTALLATION LOCATION SO THAT THE CLOSEST EDGE OF THE CURB IS NO FURTHER THAN 2' AWAY FROM THE JOIST BEARING LOCATION (CORRIDOR WALL). CONTROL BOX FOR UNIT CONTROLS SHALL BE LOCATED ABOVE THE CEILING IN THE CORRIDOR. COORDINATE WITH ELECTRICAL AND CONTROLS CONTRACTOR. COORDINATE LOCATION OF CONTROL BOX WITH DUCTWORK AND PIPING LOCATED ABOVE THE CEILING.

    NEW GAS LINE TAP INTO EXISTING MAIN AT 1½"ø APPROXIMATELY 200' PLAN WEST (NOT SHOWN) WITH GAS COCK. CONTRACTOR TO FIELD VERIFY.

    CONNECT NEW ROOF TOP UNIT INTO EXISTING GAS PIPING. REFER TO DETAIL #5 / M0.2 FOR TYPICAL GAS ROOFTOP PIPING ARRANGEMENT

    BALANCE NEW AND EXISTING 4 AIR DIFFUSERS SERVING CORRIDOR TO 240 CFM EACH.

    1

    2

    3

    4

    5

    06/17/2020

    SheetsM0.1 - MECHANICAL SCHEDULESM0.2 - MECHANICAL DETAILSM1.1 - MECHANICAL - K-2ND GRADE ADDITIONM1.2 - MECHANICAL - 3RD-5TH GRADE ADDITIONM1.3 - MECHANICAL - 6TH-8TH GRADE ADDITION