15_NearMiss

download 15_NearMiss

of 14

Transcript of 15_NearMiss

  • 8/6/2019 15_NearMiss

    1/14

    Near Miss

    Could Have Been

    Serious!

  • 8/6/2019 15_NearMiss

    2/14

    High Pressure Gaseous

    Extinguishing SystemsMany of you have high pressure

    gaseous extinguishing systems

    such as FM 200 or Inergen

    protecting computer or otherelectronic/MCC rooms.

    We are confident you have the

    systems serviced semi-annually as

    required by insurers and/or codeauthorities.

    This inspection should include

    weighing of the gas cylinders.

  • 8/6/2019 15_NearMiss

    3/14

    Near Miss

    Recently one of our clients had a near misswhile this service was being

    performed.

    The incident could have proved devastating to both the physical plant and

    personnel in the area.

    While conducting the service, the technician disconnected the cylinder

    and removed the connection to the discharge piping.

    The service tech then removed the cylinder from the rack.

  • 8/6/2019 15_NearMiss

    4/14

    What Happened?

    A check valve malfunctioned, and allowed the main discharge valve to

    open. Could this incident have been prevented?

    YES!

    The manufacturers procedures call for the discharge line to be plugged or

    cappedPRIOR to removing the cylinder from its restraining brackets. In

    this case, this critical step was omitted.

    Had the cap been installed, a loud pop would have occurred, but the

    cylinder would not have been able to rocket violently throughout the

    room. This was a very small deviation from the manufacturers

    requirements, but one which could have been fatal to the technician or

    others in the area.

  • 8/6/2019 15_NearMiss

    5/14

    ConcreteH

    oles

    The force was so

    deadly that large

    chunks of concrete

    were knocked from

    the floor as it

    bounced around the

    room. It was all

    over in a matter of

    seconds, but the

    incident will neverbe forgotten by

    those in or near the

    area.

  • 8/6/2019 15_NearMiss

    6/14

    Cabinet Damage

    In this case, the service technician

    was the only person in the room.

    Although the cylinder damaged

    several cabinets, most wereglancing blows which did not

    penetrate the cover. The one

    cabinet where the cylinder ended

    up was a spare which was not

    energized.As it turned out the

    plant was able to continue

    production with little interruption.

  • 8/6/2019 15_NearMiss

    7/14

    MCCDamageThis is what can happen when a Halon tank has a problem and rockets

    through a room, damaging rather than protecting!

  • 8/6/2019 15_NearMiss

    8/14

    MCCM

    ess

  • 8/6/2019 15_NearMiss

    9/14

    Panel& PanelCover

    Damage

  • 8/6/2019 15_NearMiss

    10/14

    Tank&

    TankGuts

  • 8/6/2019 15_NearMiss

    11/14

    Tankin Bucket

  • 8/6/2019 15_NearMiss

    12/14

    Tray Damage

    Shortly after removal, the cylinder discharged and rocketed violently

    throughout the room, damaging cable trays and electrical panels.

  • 8/6/2019 15_NearMiss

    13/14

    MoreTray Damage

  • 8/6/2019 15_NearMiss

    14/14

    What does this point out?

    J Do not be bashful; ask your service technician if they are following themanufacturers service instructions in detail with regard all safety

    procedures.

    J Now is a good time to sit down with your provider and ask them to goover each service they are performing, insuring they are covering all

    needed inspections per appropriate NFPA standards. Make sure the

    frequencies are correct for each type of service.

    J As always, if you run into questions, your Matrix Risk Consultants

    Account Engineer is only a phone call or email away.

    Matrix wants to insure that all your systems are

    properly and SAFELYmaintained.