15A
description
Transcript of 15A
Analysis of faults detected by DGA method
in GETCO
Mr.R.D.Naik
Chief Engineer (TR)
Ms. A S Shah
Deputy Engineer (TR)
Dissolve Gas Analysis (DGA)
• Most acceptable predictive maintenance tool for oil filled
transformer.
• The gases are formed due to breakdown of insulating material
under fault condition and dissolve in oil.
• The distribution of gases has been related to type of fault.
• The rate of gas generation has been related to severity of
fault.
Advantages of DGA
• Non intrusive means of condition monitoring
• Advance warning of developing faults
• Prevent unexpected outage
• Status checks on new and repaired units
• Convenient scheduling of repairs
• Reduce risk
Dissolve Gas Analysis (DGA)
• The principal cause of gas generation in transformer are
1.Thermal Energy Dissipation
Decomposition of insulation due to copper loss
Chemical Reaction
2.Electrical Disturbance
Discharge of energy in oil
Arcing
• The distribution of gases has been related to type of fault.
• The rate of gas generation has been related to severity of
fault.
Gases analyzed by DGA
5
• Methane CH4
• Ethane C2H6
• Ethylene C2H4
• Acetylene C2H2
• Hydrogen H2
• Carbon Monoxide CO
• Carbon Dioxide CO2
• Nitrogen N2 -Non fault gas
• Oxygen O2 –Non fault gas
• some of these gases will be formed in larger or smaller
quantities depending on the energy content of the fault.
•Key Gas Method
•Rogers Ratio Method
•Duval triangle
Methods for interpretation of DGA
DGA Diagnostic Tools
[1] Dissolved Gases acceptable limits as per IEEE C57.104
• >10% increase per month above typical levels = active fault
• >50% per week or evolving faults of higher energy = serious
Conditi
on H2 CH4 C2H2 C2H4 C2H6 C0 Co2 TDCG
Lower Upper Lower Upper Lower Upper Lower Upper Lower Upper Lower Upper Lower Upper Lower Upper
1 0 100 0 120 0 25 0 50 0 65 0 350 0 2500 0 720
2 101 700 121 400 36 50 51 100 66 100 351 570 2500 4000 721 1920
3 701 1800 401 1000 51 80 1010 200 101 150 571 1400 4001 10000 1921 4630
4 1800 inf 1000 inf 81 inf 201 inf 151 inf 1401 inf 10000 inf 4631 inf
1 Normal
2
Above normal value. Additional investigation needed to establish
trend. Fault(s) may be present.
3
High level of decomposition. Additional invetigation needed to stablish
trend. Fault(s) are probably present.
4
Excessive decomposition. Continued operation could result
to failure of the transformer.
DGA Diagnostic Tools
[2] Key Gases Method
Individual value of gases are taken in to consideration for evaluation.
DGA Diagnostic Tools
[3] Roger’s Ratio-based method Ratio method has to be employed in the incipient fault diagnosis. It has to be employed also
in conjunction with key gas method to check the severity of the fault.
Code for examining analysis of gas dissolved in Mineral oil
C2H2 CH4 C2H4
C2H4 H2 C2H6
Code
<0.1 0 1 0
0.1-1 1 0 0
1--3 1 2 1
>3 2 2 2
Analyses 0 0 0 NO FAULT
1 1 0 LOW ENERGY PD
2 1 0 HIGH ENERGY PD
1--2 0 1--2 LOW ENERGY SPARKING ARCING
1 0 2 HIGH ENERGY SPARKING ARCING
0 0 1 THIRMAL FAULT <150C
0 2 0 THIRMAL FAULT 150C-300C
0 2 1 THIRMAL FAULT 300C-700C
0 2 2 THIRMAL FAULT >700C
DGA Diagnostic Tools
[4] Duval Triangle
• The method is based on 3
gases (i.e.CH4, C2H4,
C2H2)
• The triangle plots the
relatively percentage of
three gases on each side.
• The figure depicts 6 main
zone of faults .
• Each DGA test report gives
one point in triangle , which
indicate the fault in the
respectively zone.
Type of Faults
•IEC 60599 has defined 6 basic types of faults detectable by DGA.
1. Partial discharges of the corona-type (PD).
-Typical examples: Discharges in gas bubbles or voids trapped in paper, as a
result of poor drying or poor oil-impregnation.
2. Discharges of low energy (D1)
-Typical examples: Partial discharges of the sparking-type, inducing carbonized
punctures in paper.
-or low-energy arcing, inducing surface tracking of paper and
carbon particles in oil.
3. Discharges of high energy (D2)
-Typical examples: High energy arcing, flashovers and short circuits with power
follow through, resulting in extensive damage to paper, large
formation of carbon particles in oil, metal fusion.
4. Thermal faults of temperatures < 300 C (T1).
Typical examples: Overloading, blocked oil ducts paper turning brown.
5. Thermal faults of temperatures between 300 and 700 C (T2)
Typical examples: Defective contacts, defective welds, circulating
currents.
Carbonization of paper or formation of carbon
particles in oil.
6. Thermal faults of temperatures > 700 C (T3).
Typical examples: Large circulating currents in tank and core, short
circuits in laminations. Sparking/burning of joints
formation of carbon particles in oil
Type of Faults
Population of Power Transformers in GETCO
> 30 Yrs
16%
21 - 30 Yrs
17%
0 - 10 Yrs
32%
11 - 20 Yrs
35%
Sr. No. Voltage
Class
Total
Nos.
Aging of Power X’mers in Years
0 - 10 11 - 20 21 - 30 > 30
1 400 KV 20 08 08 04 00
2 220 KV 195 60 85 31 19
3 132 KV 162 14 68 27 53
4 66 KV 1885 641 635 329 280
Total 2262 723 796 391 352
Practices Adopted by GETCO
• DGA for 132KV & above class transformers once in a year.
However, frequency depends on rate of rise of individual
gas.
• Table top assessment for normal & abnormal unit.
• For abnormal unit, analysis of DGA done by Key gas,
Rogers ratio & Duval triangle through our own software
• For abnormal unit, further low voltage testing & rectification
has been planned.
Summary of results of typical cases of DGA
(found in GETCO)
Sr.
NoS/S MVA
Key Gas
Method
Ratio Method
Analyses
Duval
Triangl
e
Fault observed
1 Asoj 167
Thermal
Fault
>500C
Not defined T3
Magnetic shunt on inner
tank body found shorted
with multiple earthing
2 Chorania 167
Thermal
Fault
>500C
Not defined T3
Tertiary winding connections
loose. Other loose points
observed at HV
3 Vadavi 315
Thermal
Fault
>500C
Core and Tank
circulating
current,
Overloaded
Joints
T3No abnormality observed
during internal inspection
•Voltage Ratio 400/220 KV
Summary of results of typical cases of DGA
(found in GETCO)
Sr.
No.S/S MVA
Key Gas
Method
Ratio Method
Analyses
Duval
TriangleFault observed
1 Shivlakha 100Thermal
Fault >500C
Core and tank
circulating
current,over
loaded joints
T3
In Y phase switch many
contacts found eroded. In
R phase and B phase
also contacts of pre-
selector found eroded.
2 Kim1 100Thermal
Fault >500CNot defined T3
OLTC lead connection to
winding loose, sparked
and bolt thread damaged
3 Khanpur 100Thermal
Fault >500C
Core and Tank
circulating
current,
Overloaded
Joints
T3
Nut found at the bottom
touching the core and
also water found at
bottom.Multiple earthing
of core
•Voltage Ratio 220/66 KV
Summary of results of typical cases of DGA
(found in GETCO)
Sr.N
o.S/S MVA
Key Gas
Method
Ratio Method
Analyses
Duval
Triangl
e
Fault observed
4 Viramgam 50 High arcing Not defined T3OLTC selector and
diverter damaged
5 Sachin 100
Thermal
Fault
>500C
Circulating
currents in
winding
T3
OLTC Tap contacts
and terminals found
overheated
6 Kim2 100
Thermal
Fault<>500
C
Not defined T2
OLTC Y phase lead
connection to winding
loose with missing cap
nut found at bottom.
Copper wire also
found at bottom
•Voltage Ratio 220/66 KV
Summary of results of typical cases of DGA
(found in GETCO)
Sr.N
o.S/S MVA
Key Gas
Method
Ratio Method
Analyses
Duval
Triangl
e
Fault observed
7 Ranavav 50All within
limit
Partial
Discharge -
corona with
tracking
PD
OLTC diverter switch B
phase main lead bolt
at the common ring
loose, sparked with
insulation damaged
8 Ichchhapur 100
High
energy
discharge
Arc-- with
power flow
through
D1
66 KV Y ph.lead found
opened.2 bolts of
lower portion of jumper
found melted.
•Voltage Ratio 220/66 KV
Summary of results of typical cases of DGA
(found in GETCO)
Sr.N
o.S/S MVA
Key Gas
Method
Ratio Method
Analyses
Duval
Triangl
e
Fault observed
1 Jambuva 50
Thermal
Fault
>500C
Not defined T3
Yoke and Core near
HV R phase found
overheated and
damaged
2 Idar 50
Thermal
Fault
>500C
Not defined T3OLTC polarity switch
damaged
3 Bhestan1 50
Thermal
Fault
>500C
Core and Tank
circulating
current,
Overloaded
Joints
T3
OLTC diverter switch
lead to drum loose at
drum end
4 Bhestan2 50Overheatin
g ,oilNot defined T2
Oil leakage from OLTC
to main tank due to O
ring damaged and
loose contact.
•Voltage Ratio 132/66 KV
Summary of results of typical cases of DGA
(found in GETCO)
Sr.
No.S/S MVA
Key Gas
Method
Ratio Method
Analyses
Duval
Triangl
e
Fault observed
1 Gotri 12.5Partial
Discharge
Partial
Discharge -
corona with
tracking
PD
LV B phase winding
insulation at lead
insulation failed at
joint
•Voltage Ratio 132/11 KV
Analysis & classification of faults based on
inspection
• 4 main type faults are found (i.e. T2,T3, PD, D1)
Key gas method Identify the general faults
Ratio & Triangle
method
Further qualitatively analyzed the fault which
enabled us taking decision regarding continuation
in service or immediate repair
T3Hot spots in oil with overheated joint in oil or circulating
current in core & winding
T1 & T2Thermal faults in oil & paper with heating and browning of
paper.
D1 & D2
Electrical discharge with power follow through with lesser
or higher degree & may lead to failure of paper insulation
& winding
Case Study-1 : 220/66KV, 100 MVA (220 KV Sardargadh)
[1] Year of Mfg. :- 1997
(2) Year of Comm. :- 1997
[2] Problem observed :- In April 2009, during annual routine monitoring of DGA,
the higher concentration of key gases were detected.
DGA Test Results
Date H2 CH4 C2H4 C2H6 C2H2 CO2 CO
17.04.08 10 8 4 3 0 2505 431
17.04.09 28 19 23 4 39 3625 330
25.06.09 32 21 23 4 37 3983 477
21.07.09 35 20 21 4 24 3629 410
28.08.09 19 16 20 4 19 3386 333
30.09.09 38 22 23 5 11 3937 446
16.11.09 0 0 0 0 0 79 13
17.03.10 1 0 0 0 0 430 40
03.08.10 6 3 2 1 0 1328 121
23
1.By Key Gas :-High energy fault
2.By Ratio method :-Arc with power follow through
3.By Duval Triangle :-D2- Discharge of high energy. High energy arcing, flashovers
and short circuits with power follow through, metal fusion are
some of the example of D2.
DGA Analyses
Case Study-1 : 220/66KV, 100 MVA (220 KV Sardargadh)
•The Trend of gas concentration and further testing:-
• The test was repeated after one month, there was no increase in
concentration of dissolved gasses.
• The low voltage test including winding resistance indicates no fault.
• The trend as per triangle indicates there was either one time arc
between joint, which has subsequently stopped or there may be mixing
of Tap changer oil.
• In September 2009 --- increasing trend of Hydrogen.
• The internal inspection of transformer through inspection windows was
arranged.
Case Study-1 : 220/66KV, 100 MVA (220 KV Sardargadh)
• 80 % of Lead wire of B phase bushing found burnt at the top joint
• The rectification done at site and transformer put in service
• Catastrophic failure averted
Case Study-2 : 220/66KV, 100 MVA (220 KV Chhatral)
[1] Year of Mfg. :- 1996
(2) Year of Comm. :-1996
[2] Problem observed :- In August-2009, during annual routine monitoring of
DGA, the higher concentration of key gases were
detected.
Date H2 CH4 C2H4 C2H6 C2H2 CO2 CO
06.08.06 8 6 9 1 0 922 123
20.06.07 0 3 0 0 0 814 91
14.07.08 5 4 3 1 0 2556 266
12.08.09 44 207 186 50 0 1399 99
24.09.09 85 732 642 211 0 6619 586
16.10.09 1 1 1 0 0 123 24
17.11.09 13 7 5 1 0 442 36
10.03.10 13 7 3 1 0 1175 78
25.06.10 13 13 5 3 0 1507 92
27
1. By Key Gas Method :-Thermal fault -Oil
2. By Ratio : Not defined
3. By Triangle Method : Thermal faults of temperatures between 300 and 700 C
(T2).
Carbonization of paper, formation of carbon particles in oil.
Typical examples: lead / paper involvement problem.
Case Study-2 : 220/66KV, 100 MVA (220 KV Chhatral)
•The Trend of gas concentration and further testing:-
• Periodical test results indicates rise in concentration of H2, CH4,C2H4 , C2H6 and
CO gases.
• Low voltage test including winding resistance indicates no fault.
• SFRA testing was carried out, no abnormality observed.
• The increasing trend of key gases became faster over a period of time and DGA
trend indicates persistence thermal fault.
• Due to increasing trend of key gases, it was planned to carry out internal
inspection at site.
Case Study-2 : 220/66KV, 100 MVA (220 KV Chhatral)
•Internal Inspection
Internal inspection of transformer was done on dtd.26.09.09.
During internal inspection, equipotential link between two top frames were found burnt.
Also frame earthing link found burnt.
The rectification done at site and transformer put in service.
Catastrophic failure averted
Case Study-3 : 220/66KV, 100 MVA (220 KV Kim)
[1] Year of Mfg. :- 2001
(2) Year of Comm. :- 2001
[2] Problem observed :- In July 2008, the high concentration of key gases were
observed during annual testing.
DGA Test Results
Date H2 CH4 C2H4 C2H6 C2H2 CO2 CO
18.07.08 10 92 125 15 0 2888 201
25.11.08 18 107 146 20 0 2928 143
09.01.09 19 115 151 23 0 3226 153
19.02.09 14 131 181 25 0 3452 153
12.03.09 22 144 190 28 0 3826 172
18.03.09 0 10 21 4 0 452 14
15.06.09 1 5 20 3 0 476 15
06.10.09 4 6 16 3 0 1023 28
07.11.09 4 7 19 3 0 1290 57
32
1. By Key Gas Method :-Thermal fault -Oil
2. By Ratio : Thermal Fault >700 C
3. By Triangle Method : Thermal faults of temperatures > 700 C (T3).
T3 Typical examples: large circulating currents in tank and core, short circuits in
laminations. Sparking/burning of joints
Case Study-3 : 220/66KV, 100 MVA (220 KV Kim)
1
2
DUVAL TRIANGLE
0 100
0
100 0
C2H2
CH4 C2H4
100
D1
D2
DT
T1
T2
T3
•The Trend of gas concentration and further testing:-
Case Study-3 : 220/66KV, 100 MVA (220 KV Kim)
• Periodical test results indicates rise in concentration of CH4,C2H4 and
C2H6 gases.
•Routine test of above transformer (Magnetic balance test, magnetic
current test, voltage ratio test, Short ckt. test, measurement of winding
resistance) was carried out on 20.1.09.
•All test results were found in order except winding resistance test.
Winding resistance of LV Y ph for tap no.14 was found high compared to R
&B phase.
•OLTC inspection by draining oil was carried out in presence of OEM on
dtd.24.2.09, No abnormality has been observed. Again winding resistance
measured on all tap, but on tap no.14 winding resistance found higher.
•For investigation of fault, transformer detailed inspection after draining of
oil and opening of all inspection covers was carried out from dtd . 12.3.09
to 15.3.09.
During detailed inspection, BV6 connectionon OLTC switch ( i.e. BV6 No. connectionused for Y-Ph tap no 14 connection 2-6 ) issparked and melted due to looseconnection.
The bolt thread found damaged up to 3threads. Same was replaced by new onewith two washers.
Minor pitting was also noticed onconnection bush and Lug. Same wascleaned and smoothen by the emery paper.
Also all other connection checked fortightness. No other abnormally was foundinside the transformer.
After refilling of oil and necessary testingtransformer was put in service.
Case Study-3 : 220/66KV, 100 MVA (220 KV Kim)
Case Study-4 : 132/66KV, 50 MVA (220 KV Jambuva)
[1] Year of Mfg. :- 2008
(2) Year of Comm. :- 2008
[2] Problem observed :- In Nov’10, during annual routine monitoring of DGA,
the higher concentration of key gases were detected.
DGA Test Results
Date H2 CH4 C2H4 C2H6 C2H2 CO2 CO
02.06.08 4 0 0 0 0 187 28
23.06.08 5 0 0 0 0 168 21
25.06.09 13 1 2 0 0 1714 110
23.11.10 29 63 151 17 0 1918 115
36
1.By Key Gas :-High energy fault
2.By Ratio method :-Core & tank circulating current, over loaded joints
3.By Duval Triangle :-Thermal faults of temperatures > 700 C (T3).
T3 Typical examples: large circulating currents in tank and
core, short circuits in laminations. Sparking/burning of joints
DGA Analyses
Case Study-4 : 132/66KV, 50 MVA (220 KV Jambuva)
•The Trend of gas concentration and further testing:-
• The low voltage test including winding resistance carried out, under
which
• In turn ratio test,%Deviation not available at Tap Nos 1,5,13 for B
Ph.
• Winding resistance not available for Tap No.1,3,5,7 & 13 for LV b
Ph.
• For further investigation, the internal inspection of transformer through
inspection window was arranged.
Case Study-4 : 132/66KV, 50 MVA (220 KV Jambuva)
• Fixed & moving contacts of B phase OLTC was found damaged.
• The contacts replaced at site and transformer put in service
• Catastrophic failure averted
Benefits realized
• Total 28 nos of transformers are observed problematic in
DGA in last three years and all are attended at site
before catastrophic failure.
• By attending the transformer at site, huge amount of
procurement cost or its repairing cost saved.
• Reduction in failure
Transformer failure
0
1
2
3
4
5
6
7
8
9
failu
res in
No
s
0
0.5
1
1.5
2
2.5
3
3.5
4
4.5
Failu
re in
%
400 KV 220 KV 132 KV % failure
400 KV 0 0 1 0
220 KV 6 7 2 0
132 KV 8 2 3 5
% failure 3.93 2.51 1.63 1.33
2006-07 2007-08 2008-09 2009-10
Popul
ation354 358 369 377
Conclusion
• From DGA test , according to key gases value , Criticaltransformers are identified & further rectification actions taken.
• Four main types of faults namely T2,T3,PD and D1 wereidentified .By co relating three methods of DGA ,we were able totake corrective actions before the faults become severe i.e. D2.While the Key Gas method helped to identify general fault, Ratioand Triangle methods further qualitatively analyzed the faultwhich enabled us taking decision regarding continuation inservice or immediate repair.
• We have diagnosed the fault at site and attended it timelybefore permanent failure.
• By SFRA , Accoustic Emission, tan delta & capacitancemeasurement also provide information to locate fault once thegassing in transformer starts.