Date : LS Reference : LS DS 031.a 1
11-Dec-09
Customer : CPGS 1
Project : Catalog 1
Moteurs Leroy Somer Tel. : +49 431 70 53 851 Author : P$ 1
ACEO Fax: +49 431 719 75 33
Barkauerstrasse 8 [email protected] LS DS 031.a 1
24145 Kiel GERMANY PS
Subject: V3.17 - 11/2009
Site : Prime mover : Diesel engine 1
Application : Base Rating Manufacturer : Caterpillar 1
Type : 16 CM 43 1
Main data: Quantity
Generator type: LSA 62 B 115 / 12p 1 1
Power: 17,550 kVA 14,040 kWe 14,400 kWm 1
Voltage: 11000V Star connection ± 5% Nominal curent: 932 A 1
Power factor: 0,8 1
Frequency: 50 Hz Speed: 500 rpm 1
Winding pitch : p5/6 Ambient: 40 °C 1
Insulation / Temperature rise : H / F Altitude: 1000 m 1
Electrical data:
Efficiency: 110% 100% 75% 50% 25%
Power factor 0,8: 97,5 % 97,5 % 97,4 % 97,0 % 95,2 % 1
Power factor 1,0: 98,1 % 98,1 % 97,9 % 97,4 % 95,5 % 1
Reactances Unsaturated, (rated KVA): (%) time constants:
SCR: Xd Xq X'd X'q X"d X"q X2 Xo T'do T'd T''d Ta
0,62 177 106 39,0 106 26,0 33,0 29,5 0,2 3,4 0,749 0,032 0,184 1
Saturated, (rated KVA): (%) Seconds
Ra (%) Xds Xqs X'ds X'qs X"ds X"qs X2s Xo T''do T'q T"q T''qo
0,5 161 97 33,2 97 22,1 28,1 25,1 0,2 0,048 NA 0,029 0,093 1
Mounting : IM1101 1
Mounting : Two bearing Axis : horizontal 1
Rotation : Clockwise (seen when facing the D-end) 1
Bearing type: Sleeve - self lubricated 1
Bearing insulation : 1 bearing insulated 1
Shaft end : Standard bare keywayed 1
Balancing : Half key / balancing class : G2,5 (std) 1Flange : None / without 1
Shaft height : 1400 mm / Width : 2800 mm 1
Axial clearance : Standard 1
Comments: 1
-
Cooling : IC01 1
Protection : IP23 1
Cooler : Coolant : Air / Temperature : 40 °C 1
Air quality : Clean 1
Ventilation (internal) : Self vent. 1
Filter : without filter 1
Ducting (I / O) : No 1
Comments: 1
LS DS 031.a rev. 1 Page 1 Comm - Ordo - Tech - Elec - Essa - Mont - Expe - Agen
![Page 2: 14MW DG(LS 11 kV ISO GD01-A0312-07-0300).pdf](https://reader036.fdocuments.in/reader036/viewer/2022082601/577cd8d41a28ab9e78a2171b/html5/thumbnails/2.jpg)
7/29/2019 14MW DG(LS 11 kV ISO GD01-A0312-07-0300).pdf
http://slidepdf.com/reader/full/14mw-dgls-11-kv-iso-gd01-a0312-07-0300pdf 2/7
Date : LS Reference : LS DS 031.a 1
11-Dec-09
Customer : CPGS 1
Project : Catalog 1
-
Connection & regulation: Radio int. suppression: C lass N 1
Parallel operation : With mains (3F) 1
Type of excitation: AREP + PMI Nota: CT&VT for regulation not supplied 1
Sustained three phase short circuit : greater than 3 x FLC for 10 seconds 1
AVR type: DECS200 (For panel mounting) AVR not supplied by LS 1
Voltage sensing : Terminal box mounted voltage sensing VTs / 1
Comments: 1
-
Protection and measurement accessories 1
With guide bearing sensor : = 1 X PT100 per bearing 1
With Winding sensors : = 6 x PT100 1
With Anti-condensation heater : Voltage : 230 V / 1Ph / Power : 3000 W 1
Comments:
1
LS Supply 1
Set of measuring or protection CTs: I Primary (A) I Secondary (A) Power (VA) Class
S1 1000 1 10 1FS5 1
Preliminary S2 1000 1 10 5P20 1
Neutral side S3 1S1 1
Preliminary S2 1
Line side S3 1
Comments:1
LS Supply 1
Set of Voltage measuring VTs: U Primary (V) U Secondary (V) Power (VA) Class
S1 1
Preliminary S2 1
Line side S3 1
Comments:1
-
Terminal box :Power connection : 3 connectors (internal neutral) 1
Line side outlet : Right hand side (viewed from drive end) 1
Gland plate : Non magnetic 1
Comments: Standard CPGS Terminal box 1
-
Various items :mounting of half couping supplied by the client ref 1
Overspeed : 600 rpm / Duration (min.) : 2 1
Requested noise level : 1
Vibration level : 1
Comments: 1
Paint : OtherOther - Cat Yellow 1Documentation : PDF manual Language : anglais 1
Comments: 1
LS DS 031.a rev. 1 Page 2 Comm - Ordo - Tech - Elec - Essa - Mont - Expe - Agen
![Page 3: 14MW DG(LS 11 kV ISO GD01-A0312-07-0300).pdf](https://reader036.fdocuments.in/reader036/viewer/2022082601/577cd8d41a28ab9e78a2171b/html5/thumbnails/3.jpg)
7/29/2019 14MW DG(LS 11 kV ISO GD01-A0312-07-0300).pdf
http://slidepdf.com/reader/full/14mw-dgls-11-kv-iso-gd01-a0312-07-0300pdf 3/7
Date : LS Reference : LS DS 031.a 1
11-Dec-09
Customer : CPGS 1
Project : Catalog 1
-
Controls :Rules : CEI 1
QUAL/INES/006 001 Measurement of winding resistance 1
QUAL/INES/006 021 Insulation check on sensors (when fitted) 1
QUAL/INES/006 002 Voltage balance and phase order check 1
QUAL/INES/006 003 No load characteristics, no load losses 1
QUAL/INES/006 004 Three phase short circuit characteristic 1QUAL/INES/006 005 On load test (subject to test bench capacity) 1
QUAL/INES/006 007 Overspeed test 1
QUAL/INES/006 008 Calculation of efficiency by summation of losses 1
QUAL/INES/006 009 High potential test 1
QUAL/INES/006 010 Insulation resistance measurement 1
1
-
Sleeve Bearing data:Bearing cooling : self lubricated 1
With Lube oil pump : Supply voltage : ? V (AC) 16 1
oil type (viscosity) : mineral oil (Std) / / 1
Comments: 1
guide bearing sensor : 1 X PT100 per bearing 1
Comments: 1
-
Performances :Voltage accuracy : 0,5%
Maximum inrush current for a voltage dip of 15% : 8924 kVA
when starting an AC motor having a starting power factor between 0 and 0.4
LS DS 031.a rev. 1 Page 3 Comm - Ordo - Tech - Elec - Essa - Mont - Expe - Agen
![Page 4: 14MW DG(LS 11 kV ISO GD01-A0312-07-0300).pdf](https://reader036.fdocuments.in/reader036/viewer/2022082601/577cd8d41a28ab9e78a2171b/html5/thumbnails/4.jpg)
7/29/2019 14MW DG(LS 11 kV ISO GD01-A0312-07-0300).pdf
http://slidepdf.com/reader/full/14mw-dgls-11-kv-iso-gd01-a0312-07-0300pdf 4/7
Date : LS Reference : LS DS 031.a 1
11-Dec-09
Customer : CPGS
Project : Catalog
Moteurs Leroy Somer V3.17 - 11/2009 Author : P$
ACEO
Barkauerstrasse 8 LS DS 031.a
24145 Kiel GERMANY Main curves
LSA 62 B 115 / 12p - 17550 - 11000V - 500 rpm
Efficiency curves.
93,5
94
94,5
95
95,5
96
96,5
97
97,5
98
98,5
25% 50% 75% 100%
Load - Charge - % of rated electrical kW
E f f i c i e n c y -
R e n d e m e n t e n %
PF 1
PF 0,8
0
0,1
0,2
0,3
0,4
0,5
0,6
0,7
0,8
0,9
1
-1 -0,8 -0,6 -0,4 -0,2 0 0,2 0,4 0,6 0,8 1
kWe / rated kVA
kVAr / rated kVA
0,9 p.f. 0,8 p.f.
0,4 p.f.
0,7 p.f.
0,6 p.f.
0,5 p.f.
0,3 p.f.
0,2 p.f.
0,1 p.f.
0,9 p.f.0,8 p.f.0,7 p.f.
0,6 p.f.
0,5 p.f.
0,4 p.f.
0,3 p.f.
0,2 p.f.
0,1 p.f.
Capability Curve.
LS DS 031.a rev. 1 Page 1
![Page 5: 14MW DG(LS 11 kV ISO GD01-A0312-07-0300).pdf](https://reader036.fdocuments.in/reader036/viewer/2022082601/577cd8d41a28ab9e78a2171b/html5/thumbnails/5.jpg)
7/29/2019 14MW DG(LS 11 kV ISO GD01-A0312-07-0300).pdf
http://slidepdf.com/reader/full/14mw-dgls-11-kv-iso-gd01-a0312-07-0300pdf 5/7
Date : LS Reference : LS DS 031.a 1
11-Dec-09
Customer : CPGS
Project : Catalog
Moteurs Leroy Somer V3.17 - 11/2009 Author : P$
ACEO
Barkauerstrasse 8 LS DS 031.a
24145 Kiel GERMANY Main curves
LSA 62 B 115 / 12p - 17550 - 11000V - 500 rpm
0
1
2
3
4
5
6
7
0,001 0,01 0,1 1 10 100
s h o r t c i r c u
i t a t g e n e r a t o r t e r m i n a l s
Isc (Per unit - rms)
Time (sec)
Symmetrical phase to neutral short circuit
Symmetrical two phase short circuit
Symmetrical three phase short circuit
Heat damage curve
Stator current decrement curves.
Thermal Damage Curve
1
1,5
2
2,5
3
10 100 1000 10000
Maximum duration (seconds)
Stator current (per rated current)
LS DS 031.a rev. 1 Page 2
![Page 6: 14MW DG(LS 11 kV ISO GD01-A0312-07-0300).pdf](https://reader036.fdocuments.in/reader036/viewer/2022082601/577cd8d41a28ab9e78a2171b/html5/thumbnails/6.jpg)
7/29/2019 14MW DG(LS 11 kV ISO GD01-A0312-07-0300).pdf
http://slidepdf.com/reader/full/14mw-dgls-11-kv-iso-gd01-a0312-07-0300pdf 6/7
Date : LS Reference : LS DS 031.a 1
11-Dec-09
Customer : CPGS
Project : Catalog
Moteurs Leroy Somer V3.17 - 11/2009 Author : P$
ACEO
Barkauerstrasse 8 LS DS 031.a
24145 Kiel GERMANY Main curves
LSA 62 B 115 / 12p - 17550 - 11000V - 500 rpm
0%
5%
10%
15%
20%
25%
30%
35%
40%
45%
0,0 0,4 0,8 1,2 1,6 2,0
PF = 0
PF = 0,8
Transient voltage dip curve versus load impact
V o l t a g e d i p
- ( %
o f r a t e d v o l t a g e )
Inrush - Appel de charge - % of rated kVA
0%
5%
10%
15%
20%
25%
30%
35%
0,00 0,25 0,50 0,75 1,00 1,25 1,50
PF = 0,8
Transient voltage rise curve versus load rejection
kVA shedding at P.F. - % of rated kVA
V o l t a g e r i s e -
( % o
f r a t e d v o l t a g e )
LS DS 031.a rev. 1 Page 3
![Page 7: 14MW DG(LS 11 kV ISO GD01-A0312-07-0300).pdf](https://reader036.fdocuments.in/reader036/viewer/2022082601/577cd8d41a28ab9e78a2171b/html5/thumbnails/7.jpg)
7/29/2019 14MW DG(LS 11 kV ISO GD01-A0312-07-0300).pdf
http://slidepdf.com/reader/full/14mw-dgls-11-kv-iso-gd01-a0312-07-0300pdf 7/7
Date : LS Reference : LS DS 031.a 1
11-Dec-09
Customer : CPGS
Project : Catalog
Moteurs Leroy Somer V3.17 - 11/2009 Author : P$
ACEO
Barkauerstrasse 8 LS DS 031.a
24145 Kiel GERMANY Main curves
LSA 62 B 115 / 12p - 17550 - 11000V - 500 rpm
Unbalanced Load Curve
0
1
2
3
1 10 100 1000 10000
Maximum duration of fault (seconds)
Negative phase sequence current (per rated current)
Phase to Earth Fault Current
0
25
50
75
0 1 2 3 4 5 6 7 8 9 10 11 12
Maximum duration of fault (seconds)
Fault Current (A)
C : Extensive damageB : Considerable damage
A : Acceptable damage
A
B
C
LS DS 031.a rev. 1 Page 4