BULLETIN 140U/UE Molded Case Circuit Breakers TECHNICAL DATA CATALOG NUMBERS 140U/UE

Transcript of 140u-td001_-en-p

Page 1: 140u-td001_-en-p

BULLETIN 140U/UEMolded Case Circuit Breakers

TECHNICAL DATA

CATALOG NUMBERS 140U/UE

Page 2: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

2

Electrical Specifications• Standards 4

• Interrupting Ratings 4

• Rated Insulation Voltage 4

• Rated Impulse Withstand Voltage 4

• Rated Operational Voltage 4

• Permissible Ambient Temperature 4

• DC-Rated Short Circuit Breaking Capacity 4

• Utilization Category 5

• Power Loss 5

Auxiliary Circuit Specifications• Internal Control Module Terminations 5

• Auxiliary and Alarm Contacts 5

• Undervoltage Release 6

• Shunt Trips 6

Mechanical Specifications• Weight 7

• Dimensions 7

• Mounting Hardware 7

• Terminals, Lugs, and End Caps 7

Termination Specifications• G- & H-Frames 8

• J- & K-Frames 10

• L- & M-Frames 12

• N-Frame 14

Dimension Drawings• G-Frame 18

• H-Frame 20

• J-Frame 23

• K-Frame 24

• L-Frame 25

• M-Frame 27

• N-Frame 28

Page 3: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

3

Time-Current Curves• G-Frame 100 A Thermal-Magnetic MCCBs 27

• H-Frame 125 A Thermal-Magnetic MCCBs 28

• J-Frame 250 A Thermal-Magnetic MCCBs 29

• J-Frame 250 A Electronic LS MCCBs 35

• J-Frame 250 A Electronic LSI MCCBs 36

• J-Frame 250 A Electronic LSG & LSIG MCCBs 37

• K-Frame 400 A Thermal-Magnetic MCCBs 40

—35, 65 kA (-K3, -K6) 40

—100 kA (-K0) 41

• K-Frame 400 A Electronic LS,LSG MCCBs 42

—35, 65 kA (-K3, -K6) 40

—100 kA (-K0) 41

• K-Frame 400 A Electronic LSI,LSIG MCCBs 40

—35, 65 kA (-K3, -K6) 40

—100 kA (-K0) 41

• K-Frame 400 A Electronic MCCBs with Ground Fault Protection 44

• L-Frame 600 UL (630 IEC) A Thermal-Magnetic MCCBs 48

• Q-Frame 600 A Thermal-Magnetic MCCBs 52

—35, 65 kA (-Q3, -Q6) 52

• M-Frame 800 A Thermal-Magnetic MCCBs (300…600 A) 52

—50, 65 A (-M5, -M6) 53

• M-Frame 800 A Thermal-Magnetic MCCBs (700 & 800 A) 52

—50, 65 A (-M5, -M6) 54

• M-Frame Electronic LS, LSG MCCBs 55

—50, 65 A (-M5, -M6) 55

• M-Frame Electronic LSI, LSIG MCCBs 55

—50, 65 A (-M5, -M6) 56

• M-Frame 800A Electronic MCCBs with Ground Fault Protection 57

• N-Frame Electronic LS MCCBs 58

• N-Frame Electronic LSI MCCBs 59

• N-Frame Electronic LSG, LSIG MCCBs with Ground Fault Protection 60

Page 4: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

4

Page 5: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

5

Page 6: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

6

Electrical Specifications

Frame Size

Interrupting Ratings G H H (UE) J K L L (UE) M N

Max RatedCurrent In

[A] 100 125 160 250 400 600 630 800 1200

FrameRatings [A] 100 125 160 250 400 600 630 800 800/1200

No. of Poles 2, 3 1, 2, 3 3, 4 3 3 3 3, 4 3 3

Rated Insulation Voltage (U) According to IEC 60947-2

Main Poles [V] 2-3P 415 750 750 750 750 750 750 750 750

AuxiliaryCircuit [V] 690 690 690 690 690 690 690 690 690

Rated Impulse Withstand Voltage (Uimp)

MainConductors [kV] 2-3P 6 6 6 8 8 8 8 8 8

AuxiliaryCircuits [kV] 4 4 4 4 4 4 4 4 4

Rated Operational Voltage (Ue) - AC

IEC (50 Hz) [V] 440 690 690 690 690 690 690 690 690

UL/NEMA (60Hz) [V] 480 600/347 600/347 600 600 600 600 600 600

Standards Compliance

UL 489 — ‡ — ‡ ‡

CSA 22.2 No. 5 — ‡ — ‡ ‡

IEC 60947-2 — —

Ambient Operating Temperature Range

+16…140°F (–8.9…60°C)

Permissible Ambient Temperature, Low Setting/High Setting Derating Factor (%)

Molded Case Circuit Breaker

At 40° C 100 100 /100 100 /100 100/100 100/100 100/100 100/100 100/100 100

At 50° C 96 96/92 96/92 96/94 96/92 96/91 96/91 96/91 91

At 55° C 93 93/87 93/87 94/90 93/87 93/86 93/86 93/86 85

At 60° C 91 91/83 91/83 92/87 90/84 90/82 90/82 90/82 81

At 70° C 86 86/73 86/73 88/80 85/75 84/70 84/70 84/70 —

Isolation Switch

At 40° C — 100 100 100 100 100 100 100 100

At 50° C — 100 100 100 100 100 100 100 91

At 55° C — 96 96 96 96 95 95 95 85

At 60° C — 81 81 88 90 90 90 90 81

At 70° C — 86 86 82 85 84 84 84 —

DC - Rated Short Circuit Breaking Capacity (kA)

Time Constant < 8ms, non-inductive loads

1 Pole 250V 10 (2p) 10 10 10 10 10 10 10 —

2 Poles inSeries 440V 20 20 20 20 20 20 — —

3 Poles inSeries 660V 20 20 20 20 20 30 — —

Thermal set at max. on Fixed Thermal.‡ Bulletin 140UE versions of the H-, J-, L-, M-, and N-Frame only comply with IEC 60947-2.

Page 7: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

7

Auxiliary Circuit Specifications

Frame Size

G H H (UE) J K L L (UE) M N

Internal Control Module Terminations

with TerminalConnections - CableSize

Wire sizerange

AWG — — — — — — — — —

mm2 — — — — — — — — —

with Supplied Leads

LeadLength in. (cm) 48 (122) 48 (122) 48 (122) 48 (122) 48 (122) 48 (122) 48 (122) 48 (122) 48 (122)

Wire sizerange

AWG #18 #18 #18 #18 #18 #18 #18 #18 #18

mm2 0.82 0.82 0.82 0.82 0.82 0.82 0.82 0.82 0.82

TighteningTorque

Lb-in 7..12.4 7..12.4 7..12.4 7..12.4 7..12.4 7..12.4 7..12.4 7..12.4 7..12.4

N•m 0.8..1.4 0.8..1.4 0.8..1.4 0.8..1.4 0.8..1.4 0.8..1.4 0.8..1.4 0.8..1.4 0.8..1.4

Auxiliary & Alarm Contacts

RatedThermalCurrent - Ith

[A] 6 6 6 6 6 6 6 6 6

RatedMakingCapacities

[A] 10 20 20 20 20 20 20 20 20

Rated OperationalCurrent (AC15)

230V [A] 6 (240V) 6 6 6 6 6 6 6 6

400V [A] — 3 3 3 3 3 3 3 3

480V [A] —

690V [A] — 0.25 (600V) 0.25 (600V) 0.25 0.25 0.25 0.25 0.25 0.25

Rated OperationalCurrent (DC13)

24V [A] 5 6 6 6 6 6 6 6 6

125V [A] — 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5

240V [A] — 0.15 0.15 0.15 0.15 0.15 0.15 0.15 0.15

Back-up Protection (maxrating)

Fuses [A] 6 6/4/4 6/4/4 6/4/4 6/4/4 6/4/4 6/4/4 6/4/4 6/4/4

MiniatureCircuit

Breakers[A] 6 6/4 6/4/4 6/4 6/4 6/4 6/4 6/4 6/4

Electrical Specifications, Continued

Frame Size

G H H (UE) J K L L (UE) M N

Utlization Category A A A A A A A A

MaximumSwitchingFrequency

Ops/hour 300 300 300 240 240 240 240 60 60

Power Loss

At maximum ratedcurrent (In), 3-PhaseSymmetrical Load

MoldedCaseCircuitBreaker

[W] 50 50 — 75 175 250 — 87 87/210

MoldedCase Switch [W] 40 40 — 75 107 160 — 87 87/210

Page 8: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

8

Auxiliary Circuit Specifications, Continued

Frame Size

G H H (UE) J K L L (UE) M N

Undervoltage Releases

Response Voltage

Drop-out(CB trip)

[Us] 35…70% 35…70% 35…70% 35…70% 35…70% 35…70% 35…70% 35…70% 35…70%

Pick-up(CB switchon)

[Us] 85…110% 85…110% 85…110% 85…110% 85…110% 85…110% 85…110% 85…110% 85…110%

Power Consumption

AC (50/60 Hz)

12V [VA] — 0.95 0.95 1.9 1.9 1.9 1.9 1.9 1.9

24V [VA] 5.3 0.72 0.72 3.9 3.9 3.9 3.9 3.9 2.4

48…60V [VA] 1.5 1.15 …1.78 1.15 …1.78 2.5…3.8 2.5…3.8 2.5…3.8 2.5…3.8 2.5…3.8 2.3…4.1

110…127V [VA] 1.8 0..96…1.25 0..96…1.25 1.8…2.4 1.8…2.4 1.8…2.4 1.8…2.4 1.8…2.4 3.4…4.2

208…240V [VA] 1.4 1.28…1.68 1.28…1.68 2.7…3.8 2.7…3.8 2.7…3.8 2.7…3.8 2.7…3.8 4.8…6.5

380…500V [VA] 4.8 2.2…3.9 2.2…3.9 3.4…5.8 3.4…5.8 3.4…5.8 3.4…5.8 3.4…5.8 6.8…12.0

525…600V [VA] 3.4…4.3 3.4…4.3 3.4…5.4

DC

12V [W] — 0.88 0.88 1.6 1.6 1.6 1.6 1.6 2.6

24V [W] — 0.7 0.7 3.1 3.1 3.1 3.1 3.1 3.6

48…60V [W] — 1.12…1.76 1.12…1.76 2.0…3.1 2.0…3.1 2.0…3.1 2.0…3.1 2.0…3.1 3.5…5.5

110…125V [W] — 0.94…1.21 0.94…1.21 1.6…2.2 1.6…2.2 1.6…2.2 1.6…2.2 1.6…2.2 2.9…3.6

220…250V [W] — 1.45…1.86 1.45…1.86 3.1…4 3.1…4 3.1…4 3.1…4 3.1…4 4.8…6.3

Max.Operating

Time[ms] 50 50 50 50 50 50 50 50 80

Shunt Trips

Response Voltage

Pick-up(CB Trip)

[Us] 70…110% 70…110% 70…110% 70…110% 70…110% 70…110% 70…110% 70…110% 70…110%

Power Consumption

AC (50/60 Hz)

24V [VA] — 10 10 87…405 87…405 87…405 87…405 200 86…631

48…60V [VA] — 139…210 139…210 710…1105 710…1105 710…1105 710…1105 830…1280 48…71

110…240V [VA] 135…500 83…360 83…360 66…432 66…432 66…432 66…432 100…550 81…505

380…440V [VA] — — — 127…188 127…188 127…188 127…188 95…136 43…68

480…600V [VA] — 418…1080 418…1080 34…60 34…60 34…60 34…60 40…70 41…69

DC

12V [W] — 29 29 164 164 79 79 35 46

24V [W] — 120 120 631 631 1000 1000 170 405

48…60V [W] — 475…720 475…720 830…1580 830…1580 18…31 18…31 710…1105 58…94

110…125V [W] — 99…121 99…121 112…150 112…150 112…150 112…150 110…140 74…98

220…250V [W] — — — — 40…58 — — 41…54 38…49

Max.Operating

Time[ms] 50 50 50 50 50 50 50 50 62

Page 9: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

9

Frame Size

G H H (UE) J K L L (UE) M N

Weight (approx.)

1-Pole[lb.] — 1.0 1.0 — — — — — —

[kg] — 0.45 0.45 — — — — — —

2-Pole[lb.] 1.5 2.0 2.0 11.4 — — — — —

[kg] 0.7 0.91 0.91 5.2 — — — — —

3-Pole[lb.] 2.2 3.0 3.0 11.4 13.4 13.4 13.4 43.9 46.9

[kg] 1 1.36 1.36 5.2 6.1 6.1 6.1 19.9 21.3

4-Pole[lb.] — 4.0 0.0 15.4 16.1 16.1 16.1 — 62.3

[kg] — 1.81 — 7 7.3 7.3 7.3 — 28.3

Dimensions in Inches (mm)

1-Pole

Height — 5.5 (139.7) 5.5 (139.7) 7 (177.8) — — — — —

Width — 1 (25.4) 1 (25.4) 4.13 (105) — — — — —

Depth — 3 (76.2) 3 (76.2) 4.05 (103) — — — — —

2-Pole

Height 4.88 (124.0) 5.5 (139.7) 5.5 (139.7) 7 (177.8) — — — — —

Width 2 (50.8) 2 (50.8) 2 (50.8) 4.13 (105) — — — — —

Depth 2.81 (71.4) 3 (76.2) 3 (76.2) 4.05 (103) — — — — —

3-Pole

Height 4.88 (124.0) 5.5 (139.7) 5.5 (139.7) 7 (177.8) 10.16 (258) 10.16 (258) 10.16 (258) 16 (406) 15.98 (406)

Width 3 (76.2) 3 (76.2) 3 (76.2) 4.13 (105) 5.51 (140) 5.51 (140) 5.51 (140) 8.25 (210) 8.27 (210)

Depth 2.81 (71.4) 3 (76.2) 3 (76.2) 4.05 (103) 4.09 (104) 4.09 (104) 4.09 (104) 4.05 (103) 4.09 (104)

4-Pole

Height — 5.5 (139.7) 5.5 (139.7) 7 (177.8) 10.16 (258) 10.16 (258) 10.16 (258) — 15.98 (406)

Width — 4 (101.6) 4 (101.6) 5.51 (140) 7.2 (183) 7.2 (183) 7.2 (183) — 11.02 (280)

Depth — 3 (76.2) 3 (76.2) 4.05 (103) 4.09 (104) 4.09 (104) 4.09 (104) — 4.09 (104)

Endurance OperatingCycles 10000 10000 10000 10000 10000 8000 8000 3000 3000

Mounting Hardware

Imperial (in.) 0.138-32 x2.63

0.138-32 x3.00 — — 0.250-20 x

1.750.3125-18 x

3.90.3125-18 x

3.90.3125-18 x

1.250.3125-18 x

1.25

Cat. No. 140U-G-MHS 140U-H-MHS — — 140U-K-MHS 140U-L-MHS 140U-L-MHS 140U-M-MHS 140U-N-MHS

Metric M4 x 0.7 x 75mm

M4 0.7 x 75mm

M4 x 0.7 x 75mm

M4 x 0.7 x 90mm

M6 x 1.0 x 45mm

M5 x 0.8 x100 mm

M5 x 0.8 x100 mm

M8 x 1.0 x 35mm

M8 x 1.0 x 35mm

Cat. No. 140U-G-MHM

140U-H-MHM

140U-H-MHM 140U-J-MHM 140U-K-

MHM 140U-L-MHM 140U-L-MHM 140U-M-MHM

140U-N-MHM

Quantity 4 4 4 4 4 4 4 4 4

Style Pan Head Pan Head Pan Head Pan Head Pan Head Pan Head Pan Head Pan Head Pan Head

TighteningTorque

Lb-in 15 15 15 10 20…25 25 25 28 28

N•m 1.69 1.69 1.69 1.13 2…3 3 3 3 3

Mechanical Specifications

Page 10: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

10

Terminal and Lugs Specifications

Dimensions are in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.

FrameSize

Terminals Lugs EndCapSpecification Specification Box Lugs Multitap

G

Material Std/Optional Standard — — — — — — —

Dim.

A 1/2(12.7) Cat. No. — — — — — — — —

B 3/8(9.53) Material Steel — — — — — — —

C 1/8(3.175)

TerminalFastenerHardware

Flathead — — — — — — —

Fastener Slip onbox lug

TerminalFastener Torque

Lb-in 10 — — — — — — —

TorqueLb-in — N•m 0.2 — — — — — — —

N•m — Cable Type Cu Only — — — — — — —

A

B

C

CableTemperature

Rating60°/75°C — — — — — — —

Cable Quantity 1 — — — — — — —

WireStrip

Length

in. 1/2 — — — — — — —

mm 12.7 — — — — — — —

WireRange

AWG #14…3 — — — — — — —

mm2 2.5…26 — — — — — — —

Terminal Type Slotted — — — — — — —

WireTorque

Lb-in #14…10 36 lb-in. #8 40lb-in.

#6…345 lb-in. — — — — — — —

N•m 2.5…6 mm 3.9N•m

10 mm4.5

N•m

16…26mm 5.1

N•m— — — — — — —

H

Material Std/Optional Standard Optional Optional Optional

Dim.

A 1/2(12.7) Cat. No. — 140U-H-MTL3A 140U-H-MTL6A 140U-

H-ECM

B 7/16(10.99) Material Steel Aluminum Aluminum Molded

Housing

C 1/4(6.35)

TerminalFastenerHardware

Flathead #10-32 Slotted Screw #10-32 Slotted Screw —D 1/5 (5.0)

Fastener Flathead

TerminalFastener Torque

Lb-in 10 45 lb-in 45 lb-in —

TorqueLb-in 35…50 N•m 0.2 5 N•m 5 N•m —

N•m 4.0…5.6 Cable Type Cu Only Cu/Al Cu/Al —

A

B

C

D

CableTemperature

Rating60°/75°C 60/75°C 60/75°C —

Cable Quantity (1) (3) (6) —

WireStrip

Lengthin. 1/2

(A)3/8…1/

2 in.

(B)3/4…7/

8 in.

(C) 1-1/4…1-3/8 in.

(A)3/8…1/

2 in.

(B)3/4…7/

8 in.

(C) 1-1/4…1-3/8 in.

mm 12.7(A)

9…13mm

(B)19…22

mm

(C)32…35

mm

(A)9…13mm

(B)19…22

mm

(C)32…35

mm—

WireRange

AWG #14…10 #8 #6…4 #3 3/0 #14…#2 #14…#6 —

mm2 2.5…6 10 16…25 35…95 2.5…35 2.5…10 —

Terminal Type Slotted Allen - 5/32 in. (4 mm) Allen - 3/32 in. (3 mm) Allen - 4mm

WireTorque

Lb-in 35 40 45 50 70 lb-in 25 lb-in 34…38Lb-in

N•m 4.0 4.5 5.1 5.6 7.9 N•m 2.8 N•m 3.8…4.3N•m

Page 11: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

11

Terminal and Lugs Specifications, Continued

Dimensions are in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.

FrameSize

Terminals Lugs

Specification SpecificationBoxLugs Mechanical Lugs

J

Material Std/Optional Optional Optional — — — — — — —

Dim.

A 3/4(19.05) Cat. No. 140U-J-TLS1

140U-J-TLA1 — — — — — — —

B 5/8(15.88) Material Steel Alumium — — — — — — —

C 5/16(7.94) Terminal FastenerHardware

PhillipsHead

Phillipshead — — — — — — —

D 5/16(8.0)

Fastener Hex TerminalFastenerTorque

Lb-in 10 10 — — — — — — —

TorqueLb-in 180/250 N•m 0.2 0.2 — — — — — — —

N•m 20/28 Cable Type Cu Only Cu/Al — — — — — — —

A

B

C

D

CableTemperature

Rating60/75°C 60/75°C — — — — — — —

Cable Quantity (1) (1) — — — — — — —

WireStrip

Length

in. 0.75 0.75 — — — — — — —

mm 19.05 19.05 — — — — — — —

WireRange

AWG 4…350MCM

4…350MCM — — — — — — —

mm2 25…185 25…185 — — — — — — —

Terminal Type Allen Allen — — — — — — —

WireTorque

Lb-in 180 250 — — — — — — —

N•m 20 28 — — — — — — —

K

Material Std/Optional Optional Optional Optional Optional Optional Optional Optional Optional Optional

Dim.

A 1(25.4) Cat. No. 140U-K-TLC1

140U-K-TLA1

140U-K-TLA1A

140U-K-TLC2

140U-K-TLA2

140U-K-TLC1A

140U-K-TLA2A

140U-K-TLA1B

140U-K-TLC1B

B 3/4(19.05) Material Copper Alumium Alumium Copper Alumium Copper Alumium Alumium Copper

C 3/8(9.53) Terminal FastenerHardware Hex 7/32 Hex 7/32 Hex 7/32 Hex 7/32 Hex 7/32 Hex 7/32 Hex 7/32 Hex 7/32 Hex 7/32

D 11/32(8.9)

Fastener Hex TerminalFastenerTorque

Lb-in 96 96 96 96 96 96 96 96 96

TorqueLb-in 275/375 N•m 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8 10.8

N•m 3/42 Cable Type Cu Only Cu/Al Cu/Al Cu Only Cu/Al Cu Only Cu/Al Cu/Al Cu Only

A

B

C

D

CableTemperature

Rating60/75°C 60/75°C 60/75°C 60/75°C 60/75°C 60/75°C 60/75°C 60/75°C 60/75°C

Cable Quantity (1) (1) (1) (2) (2) (1) (2) (1) (1)

WireStrip

Length

in. 1 1 1 1 1 1 1 1 1

mm 25.4 25.4 25.4 25.4 25.4 25.4 25.4 25.4 25.4

WireRange

AWG 250…500

250…500 #3…350 3/0…250 3/0…250 3…350

2/0…250MCM (2)

or2/0…500

(1)

500…750

500…750

mm2 120…240

120…240 30…185 95…120 95…120 30…185

70…120(2)or

70…240(1)

300…400 (1) —

Terminal Type Allen 3/8 Allen 3/8 Allen 3/8 Allen 3/8 Allen 3/8 Allen 3/8 Allen 3/8 Allen 3/8 Allen 3/8

WireTorque

Lb-in 375 375 275 275 275 275 275…375 550 550

N•m 42 42 31 31 31 31 31 or 42 62 62

Page 12: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

12

Frame Size

Lugs

End CapSpecification Multitap

J

Std/Optional Optional Optional Optional

Cat. No. 140U-J-MTL3A 140U-J-MTL6A 140U-J-ECM

Material Aluminum Aluminum MoldedHousing

Terminal Fastener Hardware 1/4…20 screw 1/4…20 screw —

TerminalFastenerTorque

Lb-in 50 lb-in 50 lb-in —

N•m 5.6 N•m 5.6 N•m —

Cable Type Cu/Al Cu/Al —

Cable Temperature Rating 60/75°C 60/75°C —

Cable Quantity (3) (6) —

Wire StripLength in. (A) 3/8…1/2

in.(B) 3/4…7/8

in.(C) 1-1/4…1-

3/8 in.(A) 3/8…1/2

in.(B) 3/4…7/8

in.(C) 1-1/4…1-

3/8 in. —

mm (A) 9…13 mm (B) 19…22mm

(C) 32…35mm (A) 9…13 mm (B) 19…22

mm(C) 32…35

mm —

Wire RangeAWG #14…#2 #14…#6 —

mm2 2.5…25 2.5…10 —

Terminal Type Allen - 5/32 in. (4 mm) Allen - 3/32 in. Allen - 4 mm

Wire TorqueLb-in 70 lb-in 25 lb-in 120…144 Lb-

in

N•m 7.9 N•m 2.8 N•m 14…16 N•m

K

Std/Optional Optional Optional Optional

Cat. No. 140U-K-MTL3A 140U-K-MTL6A 140U-K-ECM

Material Aluminum Aluminum MoldedHousing

Terminal Fastener Hardware .375 x 25 screw .375 x 25 screw —

TerminalFastenerTorque

Lb-in 72 -96 lb-in 72 -96 lb-in —

N•m 8.6…10.8 N•m 8.6…10.8 N•m —

Cable Type Cu/Al Cu/Al —

Cable Temperature Rating 60/75°C 60/75°C —

Cable Quantity (3) (6) —

Wire StripLength

in. (A) 9/16.…3/4in.

(B) 1-3/16.…1-1/2 in.

(C) 1-7/8…2-1/4 in.

(A) 9/16.…3/4in.

(B) 1-3/16.…1-1/2 in.

(C) 1-7/8…2-1/4 in. —

mm (A) 14…19 mm (B) 30…38mm

(C) 48…57mm (A) 14…19 mm (B) 30…38

mm(C) 48…57

mm —

Wire RangeAWG #12…2/0 #14…2 AWG —

mm2 4…70 2.5…70 —

Terminal Type Allen - 3/16 in. (5 mm) Allen - 1/8 in. (3 mm) Allen - 8 mm

Wire TorqueLb-in 120 lb-in 25 lb-in 275 Lb-in

N•m 13.5 N•m 2.8 N•m 31 -m

Page 13: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

13

FrameSize

Terminals Lugs

Specification Specification Box Lugs Mechanical Lugs

L

Material Std/Optional —

Dim.

A 1.0 (25.4) Cat. No. — 140U-L-TL6A1

140U-L-TL6C1

140U-L-TL6A2

140U-L-TL6C2

140U-L-TL4A1

140U-L-TL4C1

B 15/16(23.81) Material — Aluminum Copper Aluminum Copper Aluminum Copper

C 1/2 (12.7)Terminal Fastener

Hardware — Hex (8 mm) Hex (8 mm) Hex (8 mm) Hex (8 mm) Hex (8 mm) Hex (8 mm)D 33/64

(13.0)

Fastener Slotted TerminalFastenerTorque

Lb-in — 200 200 200 200 200 200

TorqueLb-in 42 N•m — 22 22 22 22 22 22

N•m 3 Cable Type — Cu/Al Cu only Cu/Al Cu only Cu/Al Cu only

Cable TemperatureRating — 60/75°C 60/75°C 60/75°C 60/75°C 60/75°C 60/75°C

Cable Quantity — (1) (1) (2) (2) (1) (1)

Wire StripLength

in. — 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8

mm — 29 29 29 29 29 29

WireRange

AWG — 500…750 500…750 2…500 2…500 2…500 2…500

mm2 — 240…380 240…380 35…240 35…240 35…240 35…240

Terminal Type — Hex (8 mm) Hex (8 mm) Hex (8 mm) Hex (8 mm) Hex (8 mm) Hex (8 mm)

WireTorque

Lb-in — 550 500 375 375 375 375

N•m — 62 57 42 42 42 42

M

Material Std/Optional — Optional Optional Optional Optional Optional Optional

Dim.

A 1-1/16(26.99) Cat. No. — 140U-M-

TLC3140U-M-

TLA2140U-M-

TLC2140U-M-

TLA3140U-M-TLA2A —

B 17/8 (45) Material — Copper Aluminum Copper Aluminum Aluminum —

C 1/2 (12.7) Terminal FastenerHardware — Bolt (19

mm)Bolt (19

mm)Bolt (19

mm)Bolt (19

mm)Bolt (19

mm) —D 1/2 (12.7)

Fastener Socket TerminalFastenerTorque

ft-lb — 30…35 30…35 30…35 30…35 30…35 —

TorqueLb-in 275/400 N•m — 40.5…47.5 40.5…47.5 40.5…47.5 40.5…47.5 40.5…47.5 —

N•m 31.1/45.2 Cable Type — Cu only Cu/Al Cu only Cu/Al Cu/Al —

Cable TemperatureRating — 60/75°C 60/75°C 60/75°C 60/75°C 60/75°C —

Cable Quantity — (3) (2) (2) (3) (2) —

Wire StripLength in. — 1-1/16 1-1/16 1-1/16 1-1/16 1-1/16 —

mm — 27 27 27 27 27 —

WireRange

AWG — 3/0…300 1…500 2/0…500 3/0…400 500…750 —

mm2 — 95…185 50…240 70…240 95…185 95…185 —

Terminal Type — Hex (8 mm) Hex (8 mm) Hex (8 mm) Hex (8 mm) Hex (8 mm) —

WireTorque

Lb-in — 275 375 300 375 500 —

N•m — 31 42 34 42 56 —

A

B

C

D

A

B

C

D

Terminal and Lugs Specifications, Continued

Dimensions are in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.

Page 14: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

14

Frame Size

Lugs

End CapSpecification Multitap

L

Std/Optional Optional Optional Optional

Cat. No. — — 140U-L-ECM

Material — — MoldedHousing

Terminal Fastener Hardware — — —

TerminalFastenerTorque

Lb-in — — —

N•m — — —

Cable Type — — —

Cable Temperature Rating — — —

Cable Quantity — (6) —

Wire StripLength

in. — — (C) 1-7/8…2-1/4 in.

(A) 9/16.…3/4in.

(B) 1-3/16.…1-1/2 in.

(C) 1-7/8…2-1/4 in. —

mm — (B) 30…38mm

(C) 48…57mm (A) 14…19 mm (B) 30…38

mm(C) 48…57

mm —

Wire RangeAWG #12…2/0 — —

mm2 4…70 — —

Terminal Type — — Allen - 8 mm

Wire TorqueLb-in — — 200 Lb-in

N•m — — 22 N•m

M

Std/Optional — — —

Cat. No. — — —

Material — — —

Terminal Fastener Hardware — — —

TerminalFastenerTorque

Lb-in — — —

N•m — — —

Cable Type — — —

Cable Temperature Rating — — —

Cable Quantity — — —

Wire StripLength in. — — —

mm — — —

Wire RangeAWG — — —

mm2 — — —

Terminal Type — — —

Wire TorqueLb-in — — —

N•m — — —

Page 15: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

15

Terminal and Lugs Specifications, Continued

Dimensions are in inches (millimeters). Dimensions are not intended to be used for manufacturing purposes.

Frame Size

Terminals Lugs

Specification Specification Mechanical Lugs

N

Material Std/Optional Optional Optional Optional Optional Optional Optional

Dim.

A 1-3/8 in. (35mm) Cat. No. 140U-N-

TLA3140U-N-

TLA2140U-N-

TLC2140U-N-

TLA4140U-N-

TLC3140U-N-

TLC4

B 1-1/2 in. (38mm) Material Aluminum Aluminum Copper Aluminum Copper Copper

C 1/2 in. (12.7mm) Terminal Fastener

HardwareBolt

(19 mm)Bolt

(19 mm)Bolt

(19 mm)Bolt

(19 mm)Bolt

(19 mm)Bolt

(19 mm)D (2) 0.5x13

(12.7x1.75)

Fastener TerminalFastenerTorque

ft-lb 35…45 35…45 35…45 35…45 35…45 35…45

TorqueLb-in — N•m 40.5…47.5 40.5…47.5 40.5…47.5 40.5…47.5 40.5…47.5 40.5…47.5

N•m — Cable Type Cu/Al Cu/Al Cu Only Cu/Al Cu Only Cu Only

Cable TemperatureRating 60/75°C 60/75°C 60/75°C 60/75°C 60/75°C 60/75°C

Cable Quantity (3) (2) (2) (4) (3) (4)

Wire StripLength

in. 1 1 1 1 1 1

mm 25.4 25.4 25.4 25.4 25.4 25.4

Wire RangeAWG 3/0…400

MCM#1…500

MCM2/0…500

MCM4/0…500

MCM3/0…500

MCM3/0…400

MCM

mm2 95…185 50…240 70…240 120…240 95…240 95…185

Terminal Type Hex (8 mm) Hex (8 mm) Hex (8 mm) Hex (8 mm) Hex (8 mm) Hex (8 mm)

Wire TorqueLb-in 375 375 300 375 300 275

N•m 42 42 34 34 34 31

A

B

C D

D

Page 16: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

16

Dimensions

G Frame

2.0050,8[ ]

3.2281,8[ ]

Ø.143,6[ ]

.8421,4[ ]

1.2230,9[ ]

2.4261,5[ ]1.00

25,4[ ]

3.2181,5[ ]

.4912,5[ ]

.4912,4[ ]

1.0025,4[ ]

1.2230,9[ ]

.164[ ]

.8421,4[ ]

.164,1[ ]

.9724,6[ ]

15-20 AMP, CLAMP ANDBINDING SCREW TERMINALS

25-100 AMP, PRESSURE COLLAR TERMINALS

Page 17: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

17

Dimensions, Continued

1.0025,4[ ]

3.2281,7[ ]

3.0076,2[ ]

4.88123,8[ ]

3.2181,4[ ]

1.2231[ ]

2.4161,2[ ]

.8421,3[ ]

Ø.164,1[ ]

2.8371,8[ ]

.369,1[ ]

.4511,4[ ]

1.0025,4[ ]

1.0025,4[ ]

.369,1[ ]

.4511,4[ ]

140UG FRAME

140U G-FRAME

Page 18: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

18

Dimensions, Continued

H Frame

3.4141(86.7181)

0.8524(21.6509)

0.4179 (10.6146)

0.1680(4.2672)

1.9730(50.1142)

3.8120(96.8248)

1.0070(25.5778)

2.9725(75.5015)

BUL 140U/UE J FRAME2-POLE

Page 19: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

19

3.0076,2[ ]

5.50139,7[ ]

3.8196,9[ ]

.9724,6[ ]

3.4487,4[ ]

.8822,2[ ] .54

13,6[ ]

.4711,9[ ]

1.0025,4[ ]

.8822,4[ ]

1.0025,4[ ]

1.0025,4[ ]

2.9374,3[ ]

2.4762,7[ ]

BUL 140U/UE H FRAME3-POLE

Page 20: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

20

4.00

5.50

3.00

1.00

3.81 5.50

.97

3.81

.97

1.001.00

2.00

BUL 140U/UE H FRAME

3-POLE4-POLE

Dimensions, Continued

Page 21: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

21

Dimensions, Continued

J Frame

1.3834,9[ ]

4.13104,8[ ]

7.00177,8[ ]

5.50139,7[ ]

1.3834,9[ ]

1.3834,9[ ]

Ø.205[ ]

.194,8[ ]

.8120,6[ ]

3.4487,3[ ]

4.43112,4[ ]

2.8472,2[ ]

3.1981,1[ ]

140U/UE J FRAME

3-POLE

5.50

7.00

4.13

7.00

1.38

5.50

.78

BUL 140U/UE J FRAME

3-POLE4-POLE

Page 22: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

22

140U K FRAME

10.13257,2[ ]

5.49139,4[ ]

1.7243,7[ ]

8.44214,3[ ]

1.7243,7[ ]

1.7243,7[ ]

Ø.287,1[ ]

1.0627[ ]

4.86123,3[ ]

.8421,4[ ]

8.88225,4[ ]

.6315,9[ ]

4.06103,2[ ]

1.0125,7[ ]

1.4336,2[ ]

.9524,2[ ]

1.4837,7[ ]

1.1930,2[ ]

Dimensions, Continued

K Frame

Page 23: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

23

Dimensions, Continued

L Frame5.48

139,2[ ]

1.7243,6[ ]

10.13257,2[ ]

8.44214,4[ ]

1.7243,7[ ]

1.7243,7[ ]

Ø.225,5[ ]

.256,4[ ]

.9724,6[ ]

5.43137,9[ ]

1.3434,1[ ]

3.3685,3[ ]

140U/UE L FRAME3-POLE

Page 24: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

24

7.22

1.721.72

10.13 8.44

.84

5.48

1.72

10.138.44

.84

BUL 140U/UE L FRAME4 POLE

Dimensions, Continued

Page 25: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

25

Dimensions, Continued

M Frame

8.25209,6[ ]2.75

69,9[ ]

16.00406,4[ ]

14.75374,7[ ]

Ø.389,5[ ]

.8421,4[ ]

1.0326,2[ ]1.87

47,6[ ]

.8421,4[ ]

1.0326,2[ ]

.7418,7[ ]

5.50139,6[ ]

.6315,9[ ]

BUL 140U/UE M FRAME

Page 26: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

26

11.00

2.752.75

16.00

8.25

2.75 .63

16.0014.75

14.75

.63

BUL 140U/UE N FRAME

4-POLE

Dimensions, Continued

N Frame

2.7569,9[ ]

Ø.348,7[ ]

14.75374,7[ ]

16.00406,4[ ]

.9724,6[ ]

1.0927,8[ ]2.00

50,8[ ]

7.18182,5[ ]

5.19131,8[ ]

.6315,9[ ]

5.50139,7[ ]

3.8497,6[ ]

5.50139,7[ ]

8.25209,6[ ]

2.7569,9[ ]

140U/UE N FRAME

Page 27: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

27

Upstream (max. settings) "T" represents max. discrimination to kA rating level of the downstream device.

Do

wns

trea

m

Bulletin 140UE H-Frame Bulletin 140UE J-Frame

Breaker Rating (A)

16 20 32 40 50 63 80 100 125 160 50 80 100 125 160 200 250

18, 25, 40, or 70 kA version 45 or 70 kA version

Bulletin140UE

H-FrameMCCB

18 kA & 25kA versions

16 — — 0.32kA

0.4kA

0.5kA

0.63kA

0.8kA 1 kA 1.3

kA 1.6kA — — T T T T T

20 — — 0.2kA

0.4kA

0.5kA

0.63kA

0.8kA 1 kA 1.3

kA 1.6kA — — T T T T T

32 — — — 0.1kA

0.5kA

0.63kA

0.8kA 1 kA 1.3

kA 1.6kA — — T T T T T

40 — — — — 0.8kA

0.63kA

0.8kA 1 kA 1.3

kA 1.6kA — — 10 kA 10 kA 10 kA 10 kA T

50 — — — — — 0.63kA

0.8kA 1 kA 1.3

kA 1.6kA — — 10 kA 10 kA 10 kA 10 kA 10 kA

63 — — — — — — 0.8kA 1 kA 1.3

kA 1.6kA — — 10 kA 10 kA 10 kA 10 kA 10 kA

80 — — — — — — — 1 kA 1.3kA

1.6kA — — 10 kA 10 kA 10 kA 10 kA 10 kA

100 — — — — — — — — 1 kA 1.6kA — — — — 10 kA 10 kA 10 kA

125 — — — — — — — — — — — — — — — 3 kA 3 kA

160 — — — — — — — — — — — — — — — — 3 kA

Bulletin140UE

H-FrameMCCB

45 kA & 70kA versions

16 — — 0.32kA

0.4kA

0.5kA

0.63kA

0.8kA 1 kA 1.3

kA1.6kA — — 40 kA 40 kA 40 kA 40 kA 40 kA

20 — — 0.2kA

0.4kA

0.5kA

0.63kA

0.8kA 1 kA 1.3

kA1.6kA — — 40 kA 40 kA 40 kA 40 kA 40 kA

32 — — — 0.1kA

0.5kA

0.63kA

0.8kA 1 kA 1.3

kA1.6kA — — 40 kA 40 kA 40 kA 40 kA 40 kA

40 — — — — 0.8kA

0.63kA

0.8kA 1 kA 1.3

kA1.6kA — — 10 kA 10 kA 10 kA 10 kA 10 kA

50 — — — — — 0.63kA

0.8kA 1 kA 1.3

kA1.6kA — — 10 kA 10 kA 10 kA 10 kA 10 kA

63 — — — — — — 0.8kA 1 kA 1.3

kA1.6kA — — 10 kA 10 kA 10 kA 10 kA 10 kA

80 — — — — — — — 1 kA 1.3kA

1.6kA — — — — 10 kA 10 kA 10 kA

100 — — — — — — — — 1 kA 1.6kA — — — — — 3 kA 3 kA

125 — — — — — — — — — — — — — — — — 3 kA

Bulletin140UE

J-FrameMCCB

45 kA & 70kA versions

50 — — — — — — — — — — — — 1 kA 1.25kA

1.6kA 2 kA 2.5

kA

63 — — — — — — — — — — — — — 1.25kA

1.6kA 2 kA 2.5

kA

80 — — — — — — — — — — — — — 1.25kA

1.6kA 2 kA 2.5

kA

100 — — — — — — — — — — — — — — 1.6kA 2 kA 2.5

kA

125 — — — — — — — — — — — — — — 1.6kA 2 kA 2.5

kA

160 — — — — — — — — — — — — — — — — 2.5kA

200 — — — — — — — — — — — — — — — — —

250 — — — — — — — — — — — — — — — — —

Bulletin140UE

L-FrameMCCB

50 kA & 70kA versions

250 — — — — — — — — — — — — — — — — —

320 — — — — — — — — — — — — — — — — —

400 — — — — — — — — — — — — — — — — —

500 — — — — — — — — — — — — — — — — —

630 — — — — — — — — — — — — — — — — —

Bulletin140UE

N-FrameMCCB

50 kA & 70kA versions

800 — — — — — — — — — — — — — — — — —

1250 — — — — — — — — — — — — — — — — —

1600 — — — — — — — — — — — — — — — — —

Discrimination — Short-circuit level to which discrimination is achieved.

Page 28: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

28

Upstream (max. settings) "T" represents max. discrimination to kA rating level of the downstream device.

Do

wns

trea

m

Bulletin 140UE L-Frame Bulletin 140UE N-Frame

Breaker Rating (A)

250 320 400 500 630 800 1250 1600

50 or 70 kA versions 50, 70, or 100 kA versions

Bulletin140UE

H-FrameMCCB

18 kA & 25kA versions

16 T T T T T T T T

20 T T T T T T T T

32 T T T T T T T T

40 T T T T T T T T

50 T T T T T T T T

63 T T T T T T T T

80 T T T T T T T T

100 T T T T T T T T

125 T T T T T T T T

160 T T T T T T T T

Bulletin140UE

H-FrameMCCB

45 kA & 70kA versions

16 40 kA 40 kA 40 kA 40 kA 40 kA 65 kA 65 kA 65 kA

20 40 kA 40 kA 40 kA 40 kA 40 kA 65 kA 65 kA 65 kA

32 40 kA 40 kA 40 kA 40 kA 40 kA 65 kA 65 kA 65 kA

40 40 kA 40 kA 40 kA 40 kA 40 kA 65 kA 65 kA 65 kA

50 40 kA 40 kA 40 kA 40 kA 40 kA 65 kA 65 kA 65 kA

63 40 kA 40 kA 40 kA 40 kA 40 kA 65 kA 65 kA 65 kA

80 40 kA 40 kA 40 kA 40 kA 40 kA 65 kA 65 kA 65 kA

100 40 kA 40 kA 40 kA 40 kA 40 kA 65 kA 65 kA 65 kA

125 26 kA 26 kA 26 kA 26 kA 26 kA 65 kA 65 kA 65 kA

Bulletin140UE

J-FrameMCCB

45 kA & 70kA versions

50 — — 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA

63 — — 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA

80 — — 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA

100 — — 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA

125 — — 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA

160 — — 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA

200 — — 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA

250 — — 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA

Bulletin140UE

L-FrameMCCB

50 kA & 70kA versions

250 — — — — — 40 kA 40 kA 40 kA

320 — — — — — 40 kA 40 kA 40 kA

400 — — — — — 40 kA 40 kA 40 kA

500 — — — — — 22 kA 22 kA 22 kA

630 — — — — — — — —

Bulletin140UE

N-FrameMCCB

50 kA & 70kA versions

800 — — — — — — — —

1250 — — — — — — — —

1600 — — — — — — — —

Discrimination, Continued

Page 29: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

29

Time-Current Curves

Bul.140U

Time-Current Curves for Bulletin 140U-G Thermal-Magnetic Molded Case Circuit Breakers

40752-600 (1)SC-6030-95Effective October 1997

Maximum

Interrupting Rating (See Tabulation Above)

Instantaneous Trip (See Tabulation Above)

Maximum Interrupting Time

Minimum

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

SDN O

CES

N I E

MIT

1,000

500

200

5,000

3,000

2,000

RUOH

1ET

UNI

M 1

SRUO

H 2

SDN OCES

NI EMIT

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

RUO H 1E TU

NIM 1

SRU OH 2

001080 6 0 90705

0 001

008

0 06

009

007

005

004

003

002

0 00,01

0008

0 006

0 009

0007

000 5

0004

0 003

0002

000,001

00 0, 08

00 0, 06

000,09

000,07

000,0 5

00 0, 04

000,03

000,02

00 0, 01

0008

0006

0009

0007

00 05

0004

0003

00 02

0001

008

00 6

009

007

005

004

003

002

00 1

080 6 090705 000 ,0 01

000 ,0 8

000,0 6

000 ,0 9

0 00 ,07

0 00,05

000,04

000,03

0 00,02

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING

10,000

300

Circuit Breaker Time/Current Curves

For application and coordination purposes only. Based on 40 °Cambient, cold start. Connected with four (4) feet of rated wire(60/75°C) per terminal. Tested in open air with current in all polesexcept for instantaneous trip, see below.

Maximum VoltsBreakerType

140U-G

Breaker Rating

Continuous Amperes

15-6070-100

Interrupting Rating (UL Listed)BreakerType

140U-G

Ac Volts60 Hz

480

Instantaneous Trip, AmperesSingle Pole

500-13001300-1800

Symmetrical RMS Amperes240 Volts

65,000

2 Poles in Series

400-1100700-1300

480 Volts

22,000

Page 30: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

30

Time-Current Curves, Continued

Bul.140U/UE

Bulletin 140U/UE - H-, J-, L-Frames Current Limiting Characteristics (Ip) 210…415V AC, 50/60 Hz

40752-610 (1)Effective April 2004

0.3

5 7 10 20 30 50 kA 100

200kA

100

80

60

40

20

10

8

6

4

2

I TN

ER

RU

C FFO-T

UC

D

SHORT CIRCUIT CURRENT ISrms

0.2

H

J

Lcos =0.25

Page 31: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

31

Bul.140U/UE

Time-Current Curves for Bulletin 140U-H Thermal-Magnetic Molded Case Circuit Breakers

40752-601 (1)SC-XXXEffective March 2004

Notes:( a ) Fixed Inverse-Time

Overcurrent Release.( b ) Fixed Electromagnetic Release.

( c )TotalOperationTime.

( d ) Interrupting Rating determinesend of Curve.

1 minute1 minute

Thermal/Magnetic TripRated Operating Voltage : 600Y / 347V AC

480V AC415 V AC

Number of Poles: 3, 4Ambient 40oCInterrupting Ratings - 50/60 HzRMS Symmetrical Amperes (kA), Icu

Two Series Poles Inst. MagneticTrip Shown.Individual Pole Inst. Magnetic Trip +30%.DC Inst. Magnetic Trip +30% Higher Than AC.

Time-Current Curves, Continued

Page 32: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

32

Time-Current Curves, Continued

Bul.140U/UE

Bulletin 140U/UE - H-, J-, L-Frames Current Limiting Characteristics (Ip) 210…415V AC, 50/60 Hz

40752-610 (1)Effective April 2004

0.3

5 7 10 20 30 50 kA 100

200kA

100

80

60

40

20

10

8

6

4

2

I TN

ER

RU

C FFO-T

UC

D

SHORT CIRCUIT CURRENT ISrms

0.2

H

J

Lcos =0.25

Page 33: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

33

Time-Current Curves, Continued

Bul.140U/UE

Earth Leakage Curves for Bulletin 140U/UE-H IEC-Rated Thermal-Magnetic Molded Case Circuit Breakers

40752-602 (1)Curve No. TC01212003EEffective September 2005

.1

1S

500ms

300ms

150ms

60ms

Ig (Amperes)

1000.0

.001

.002

.003

.004

.005

.006

.007

.008

.009

.01

.02

.03

.04

.05

.06

.07

.08

.09

.1

.2

.3

.4

.5

.6

.7

.8

.91.0

2.0

3.0

4.0

5.0

6.07.08.09.0

10.0

100.090.080.070.060.0

50.0

40.0

30.0

20.0

200.0

300.0

400.0

500.0

600.0700.0800.0900.0

SD

NO

CESNI

EMI T S

DN

OCE

SNI

EMI

T

.001

.002

.003

.004

.005

.006

.007

.008

.009

.01

.02

.03

.04

.05

.06

.07

.08

.09

.1

.2

.3

.4

.5

.6

.7

.8

.91.0

2.0

3.0

4.0

5.0

6.07.08.09.0

10.0

100.090.080.070.060.0

50.0

40.0

30.0

20.0

200.0

300.0

400.0

500.0

600.0700.0800.0900.0

1000.0.01 .02 .03 .04 .1 .2 .3.07.05 .4 2.01.0.7.5 3.0 4.0 5.0 7.0 10.0 20.0 50.0 80.0

.01 .02 .03 .04 .1 .2 .3.07.05 .4 2.01.0.7.5 3.0 4.0 5.0 7.0 10.0 20.0 50.0 80.0

Inst.

Available I n Settings.03 .3 1 3 10

Circuit Breaker Time/Current Curves

1. 140U/UE-H Circuit Break.Earth Leakage Mod., 3 and 4 Poles,110 - 480V 60Hz.

2. For application and coordination purposes only. -20 C to55 C ambient.

3. Total clearing times include the response time of the EarthLeakage module, opening time of the circuit breaker, andinterruption of current.

4. For additional curve tolerances, contact Rockwell Automation.

°°

Page 34: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

34

Bul.140U/UE

Earth Leakage Curves for Bulletin 140U/UE-H UL-Rated Thermal-Magnetic Molded Case Circuit Breakers

40752-603 (1)Curve No. TC01212004EEffective September 2005

1000.0

.001

.002

.003

.004

.005

.006

.007

.008

.009

.01

.02

.03

.04

.05

.06

.07

.08

.09

.1

.2

.3

.4

.5

.6

.7

.8

.91.0

2.0

3.0

4.0

5.0

6.07.08.09.0

10.0

100.090.080.070.060.0

50.0

40.0

30.0

20.0

200.0

300.0

400.0

500.0

600.0700.0800.0900.0

SD

NO

CESNI

EMI T

1000.0

.001

.002

.003

.004

.005

.006

.007

.008

.009

.01

.02

.03

.04

.05

.06

.07

.08

.09

.1

.2

.3

.4

.5

.6

.7

.8

.91.0

2.0

3.0

4.0

5.0

6.07.08.09.0

10.0

100.090.080.070.060.0

50.0

40.0

30.0

20.0

200.0

300.0

400.0

500.0

600.0700.0800.0900.0

SD

NO

CES

NIE

MIT

Ig (A)

Available Ig (A)Settings

1S

500ms

300ms

150ms

60ms

.01 .02 .03 .04 .1 .2 .3.07.05 .4 2.01.0.7.5 3.0 4.0 5.0 7.0 10.0

.01 .02 .04 .05 .07.03 .1 .2 .3 .4 .5 .7 1.0 3.02.0 4.0 5.0 7.0 10.0 20.0 50.0 80.0

20.0 50.0 80.0

Inst.

.03 .1 .3 1 3 10

Circuit Breaker Time/Current Curves

1. 140U/UE-H Cir. Break. Earth Leakage Mod., 3 and 4 Poles,110 - 480V 60Hz.

2. For application and coordination purposes only. -20 C to55 C ambient.

3. Total clearing times include the response time of the EarthLeakage module, opening time of the circuit breaker, andinterruption of current.

4. For additional curve tolerances, contact Rockwell Automation

°°

Time-Current Curves, Continued

Page 35: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

35

Time-Current Curves, Continued

Bul.140U/UE

Time-Current Curves for Bulletin 140U-J Thermal-Magnetic Molded Case Circuit Breakers

40752-620 (1)SC-XXXEffective March 2004

Allen-Bradley 63…250 A

Page 36: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

36

Bul.140U/UE

Time-Current Curves for Bulletin 140U-J Electronic LS Molded Case Circuit Breakers

40752-621 (1)TC-01201002EEffective September 2003

.01

1

2

3

4

5

6789

10

20

30

40

50

60708090

100

1000900800700600

500

400

300

200

2000

3000

4000

5000

6000700080009000

10000

.02

.03

.04

.05

.06

.07

.08.09

.1

.2

.3

.4

.5

.6.7.8.91

3

4

5

6789

10

20

30

40

50

60708090

100

1000900800700600

500

400

300

200

2000

3000

4000

5000

6000700080009000

10000

ETU

NIM

1S

RU

OH

2S

DN

OCES

NIE

MI TR

UO

H1

.01

.02

.03

.04

.05

.06

.07

.08

.09

.1

.2

.3

.4

.5

.6

.7

.8

.91

Maximum TotalClearing Time

Available Long Delay Time:2,4,7,10,12,15,20,24 sec.

Shown @ 6x2,4,7,15,24

seconds +0/-30%

Ir

7

2

SD

NO

CESNI

EMI T

Available Short DelayPick Up Settings

2 - 8,10, x 5%14 Ir

(See Note 7)

Application DeterminesEnd of Curve

2

InstantaneousOverride (See Note 10)

Available Sensors ( ):In

Circuit Breaker Time/Current Curve

Long Delay (LD) & Short Delay (SD) with I2T Response (LS)

50A100A160A250A

Current in Multiples of ( )Ir

Current in Multiples of ( )Ir

1 2 3 4 5 7 10 20 30 40 50 70 100 2 3 4 5 7 10 20 30 40 50 70 100.5 .7

1 2 3 4 5 7 10 20 30.5 .7

8

Current in Multiples of ( I n )

Notes:

1. Curve accuracy applies from -20 C to +55 C ambient. Temperatures above +88 C cause an overtemperature protection trip. For possible continuous ampere derating for ambient above 40 C,consult Rockwell Automation.

2. Application frequency is 50/60 Hertz.

4. The right portion of the curve is determined by the interrupting rating of the circuit breaker.

5. The left portion of the curve is shown as a multiple of the Long Delay Setting(Long Delay Pick Up = 115% of ). Range is 110% - 120%.

6. Total clearing times shown include the response times of the trip unit, the breaker opening, and theinterruption of the current.

7. The Short Delay Pick Up has 9 settings/positions: 2 - 8 & 10, 14.

8. Short Delay T band has a tolerance of 15%.

9. Breakpoint back to FLAT response occurs @ 8x for upper line of the T curve.

10. For high fault current levels an additional fixed instantaneous hardware override is provided at14x ( ).

11. For LD Response & SD with Flat Response curve, see: 40752-622

12. For LD Response & SD with T Response (this curve):

13. For Ground Fault Delay Response curve, see: 40752-623

° ° °°

I

I ±

I I

I

I

3. There is a memory effect that can act to shorten the Long Delay. The memory effect comes into playif a current above the circuit breaker itself. A subsequent overload will cause the circuit breaker to tripin shorter time than normal. The amount of time delay reduction is inverse to the amount of time thathas elapsed since the previous overload. Approximately five minutes is required between overloads tocompletely reset memory.

r

r

n

2

2

240752-621

Long Delay Response & Short Delay with Response CurveI T2

I2T Trip Style

14

I2T Short Delay(See Note 8)

Minimum TotalClearing Time

10

7

5

4

.

.4

.

.15

.24

6

.

3

1.15

See Note 9 14x

67ms

In 50 A 100 A 160 250 A

A 20A 40A 63A 100AB 20A 45A 80A 125AC 25A 50A 90A 150AD 30A 63A 100A 160AE 32A 70A 110A 175AF 40A 80A 125A 200AG 45A 90A 150A 225AH 50A 100A 160A 250A

A 20A 40A 63A 100AB 20A 45A 80A 125AC 25A 50A 90A 150AD 30A 63A 100A 160AE 32A 70A 110A 175AF 40A 80A 125A 200AG 45A 90A 150A 225AH 50A 100A 160A 250A

Ir

Time-Current Curves, Continued

Page 37: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

37

Time-Current Curves, Continued

Bul.140U/UE

Time-Current Curves for Bulletin 140U-J Electronic LSI Molded Case Circuit Breakers

40752-622 (1)TC01201001EEffective September 2003

.01

1

2

3

4

5

6789

10

20

30

40

50

60708090

100

1000900800700600

500

400

300

200

2000

3000

4000

5000

6000700080009000

10000

.02

.03

.04

.05

.06

.07

.08.09

.1

.2

.3

.4

.5

.6.7.8.91

3

4

5

6789

10

20

30

40

50

60708090

100

1000900800700600

500

400

300

200

2000

3000

4000

5000

6000700080009000

10000

ETU

NIM

1S

RU

OH

2S

DN

OCES

NIE

MI TR

UO

H1

.01

.02

.03

.04

.05

.06

.07

.08

.09

.1

.2

.3

.4

.5

.6

.7

.8

.91

2

Maximum TotalClearing Time

Available Long Delay Time:2,4,7,10,12,15,20,24 sec.

Shown @ 6x2,4,7,15,24

seconds +0/-30%

Ir

7

2

SD

NO

CESNI

EMI T

Available Short DelayPick Up Settings

2 - 8,10, x 5%14 Ir

(See Note 7)

2

Available Sensors ( ):In

Circuit Breaker Time/Current CurvesLong Delay (LD) & Short Delay (SD) with Flat Response (LSI)

50A100A160A250A

Current in Multiples of ( )Ir

Current in Multiples of ( )Ir

1 2 3 4 5 7 10 20 30 40 50 70 100 2 3 4 5 7 10 20 30 40 50 70 100.5 .7

1 2 3 4 5 7 10 20 30.5 .7

8

Current in Multiples of ( )In

Long Delay Response & Short Delay with Flat Response Curve

14

Minimum TotalClearing Time

10

4

.4

.15

.24

63

1.15

Notes:

1. Curve accuracy applies from -20 C to +55 C ambient. Temperatures above +88 C cause an over-temperature protection trip. For possible continuous ampere derating for ambient above 40 C, consultRockwell Automation.

2. Application frequency is 50/60 Hertz.

4. The right portion of the curve is determined by the interrupting rating of the circuit breaker.

5. The left portion of the curve is shown as a multiple of the Long Delay Setting.(Long Delay Pick Up = 115% of ). Range is 110% - 120%.

6. Total clearing times shown include the response times of the trip unit, the breaker opening, and theinterruption of the current.

7. The Short Delay Pick Up has 9 settings/positions, 2 - 8 & 10, 14.

8. For high fault current levels an additional fixed instantaneous hardware override is provided at14x ( ).

9. For LD Response & SD with Flat Response (this curve): 40752-622

10. For LD Response & SD with T Response curve, see:

11. For Ground Fault Delay Response curve, see: 40752-623

° ° °°

I

I

I

3. There is a memory effect that can act to shorten the Long Delay. The memory effect comes into playif a current above the circuit breaker itself. A subsequent overload will cause the circuit breaker to tripin shorter time than normal. The amount of time delay reduction is inverse to the amount of time thathas elapsed since the previous overload. Approximately five minutes is required between overloads tocompletely reset memory.

r

n

240752-621

Adjustable Flat Trip Style

14x

Application DeterminesEnd of Curve

InstantaneousOverride (See Note 8)

7

.

5

.

In 50A 100A 160A 250A

A 20A 40A 63A 100AB 20A 45A 80A 125AC 25A 50A 90A 150AD 30A 63A 100A 160AE 32A 70A 110A 175AF 40A 80A 125A 200AG 45A 90A 150A 225AH 50A 100A 160A 250A

A 20A 40A 63A 100AB 20A 45A 80A 125AC 25A 50A 90A 150AD 30A 63A 100A 160AE 32A 70A 110A 175AF 40A 80A 125A 200AG 45A 90A 150A 225AH 50A 100A 160A 250A

Ir

300ms(P,Q,R)

120ms(M,N,O)

Inst.(J,K,L)

Page 38: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

38

Bul.140U/UE

Time-Current Curves for Bulletin 140U-J Electronic LSG & LSIG Molded Case Circuit Breakers

40752-623 (1)TC01203004EEffective September 2003

.01

2

3

4

5

6

8

10

20

30

40

50

60708090

100

1000900800700600

500

400

300

200

.02

.03

.04

.05

.06

.07

.08

.09.1

.2

.3

.4

.5

.6

.7

.8

.91

7

9

2000

3000

4000

5000

6000700080009000

10000

ETU

NIM

1S

DN

OCES

NIE

MI T

Ground Current in Multiple of ( )In

.1 .2 .3 .4 .5 .7 1.0 2.0

.1 .2 .3 .4 .5 .7 1.0 2.0

Notes:

1. Curve accuracy applies from -20 C to +55 C ambient. Temperatures aboveFor possible continuous ampere derating for

ambient above 40 C, consult Rockwell Automation.

3. Trip units are suitable for functional field testing with test kit style # 70C1056G52.

° ° °

°

I

+88 Ccause an over-temperature protection trip.

2.Application frequency is 50/60 Hertz.

4. For LD Response & SD with Flat Response curve, see: 40752-6225. For LD Response & SD with T Response curve, see:

6. For Ground Fault Delay Response (this curve): 40752-623

240752-621

Ground Fault Pickup Settings(Tolerance 10%)

0.4X

120ms(K,N,Q)

300ms(L,O,R)

Inst.(J,M,P)

Circuit Breaker Time/Current Curves

0.2X 1X0.6X

0.8X

NOTE: Labels shown are for 250A style.

SwitchSetting

JKLMNOPQR

SwitchSetting

JKLMNOPQR

tSD

Inst.Inst.Inst.120120120300300300

t

Inst.Inst.Inst.120120120300300300

tGF

Inst.120300Inst.120300Inst.120300

Inst.120300Inst.120300Inst.120300

Ground Fault Delay Response (LSG, LSIG)

Cat. No. 140U-JTI3-D25

Cat. No. 140U-JTG3-D25

0.3X

Time-Current Curves, Continued

Page 39: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

39

Time-Current Curves, Continued

Bul.140U/UE

Earth Leakage Curves for Bulletin 140U/UE-J IEC-Rated Thermal-Magnetic Molded Case Circuit Breakers

40752-624 (1)Curve No. TC01205001EEffective September 2005

1000

.001

.002

.003

.004

.005

.006

.007

.008

.009

.01

.02

.03

.04

.05

.06

.07

.08

.09

.1

.2

.3

.4

.5

.6

.7

.8

.91.0

2.0

3.0

4.0

5.0

6.0

7.08.09.010.0

100.090.080.070.0

60.0

50.0

40.0

30.0

20.0

200.0

300.0

400.0

500.0

600.0

700.0

800.0900.0

TIM

E IN

SEC

ON

DS

1000

.001

.002

.003

.004

.005

.006

.007

.008

.009

.01

.02

.03

.04

.05

.06

.07

.08

.09

.1

.2

.3

.4

.5

.6

.7

.8

.91.0

2.0

3.0

4.0

5.0

6.0

7.08.09.010.0

100.090.080.070.0

60.0

50.0

40.0

30.0

20.0

200.0

300.0

400.0

500.0

600.0

700.0

800.0900.0

TIME IN

SECO

ND

S

1031.3.1

1S

500ms

300ms

150ms

60ms

Inst

.01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1.0 2 3 4 5 7 10

.01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1.0 2 3 4 5 7 10

Available I n settings

I n

.03

Circuit Breaker Time/Current Curves

1. 140U/UE-J Circuit Breaker Earth Leakage Module, 3 and 4 Poles, 110 - 480V 50/60Hz.

2. For application and coordination purposes only. -20C to 55C ambient.

3. Total clearing times include the response time of the Earth Leakage module, opening time of the circuit breaker, and interruption of current.

4. For additional curve tolerances, contact Rockwell Automation.

(Amperes)

Page 40: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

40

Bul.140U/UE

Earth Leakage Curves for Bulletin 140U/UE-J UL-Rated Thermal-Magnetic Molded Case Circuit Breakers

40752-625 (1)Curve No. TC01204004EEffective September 2005

F

1000

.001

.002

.003

.004

.005

.006

.007

.008

.009

.01

.02

.03

.04

.05

.06

.07

.08

.09

.1

.2

.3

.4

.5

.6

.7

.8

.91.0

2.0

3.0

4.0

5.0

6.0

7.08.09.010.0

100.090.080.070.0

60.0

50.0

40.0

30.0

20.0

200.0

300.0

400.0

500.0

600.0

700.0

800.0900.0

TIM

E IN

SEC

ON

DS

1000

.001

.002

.003

.004

.005

.006

.007

.008

.009

.01

.02

.03

.04

.05

.06

.07

.08

.09

.1

.2

.3

.4

.5

.6

.7

.8

.91.0

2.0

3.0

4.0

5.0

6.0

7.08.09.010.0

100.090.080.070.0

60.0

50.0

40.0

30.0

20.0

200.0

300.0

400.0

500.0

600.0

700.0

800.0900.0

TIME IN

SECO

ND

S

Ig(A)

1031.3.1 Available Ig(A) Settings.

1S

500ms

300ms

150ms

60ms

Inst

.03

Circuit Breaker Time/Current Curves

1. 140U/UE-J Circuit Breaker Earth Leakage Module, 3and 4 Poles, 110 - 480V 50/60Hz.

2. For application and coordination purposes only. -20C to 55C ambient.

3. Total clearing times include the response time of the Earth Leakage module, opening time of the circuit breaker, and interruption of current.

4. For additional curve tolerances, contact Rockwell Automation.

.01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1.0 2 3 4 5 7 10

.01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1.0 2 3 4 5 7 10

Time-Current Curves, Continued

Page 41: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

41

Time-Current Curves, Continued

Bul.140U

Time-Current Curves for Bulletin 140U-K3/K6 Thermal-Magnetic Molded Case Circuit Breakers

40752-630 (1)SC-4118-87BEffective October 1997

Maximum

Maximum Single PoleTrip Times at 25°C ➀

Adjustable Magnetic Trip

X5

±20% ±10%X01

(250-400A)

(125-225A)

(100A)

Circuit Breaker Time/Current Curves

For application and coordination purposes only.Based on 40 °C ambient, cold start. Connected with four (4) feet ofrated wire (60°C up to 125 A. 75° C above 125 A) per terminal.Tested in open air with current in all poles. Instantaneous calibrationbased on single-pole tests.

Maximum Voltage600V., AC (60 Hz)250 V., DC

Breaker RatingRated Amperes (In)

Interrupting Rating (UL/CSA)

Single pole data at 25°C based on NEMA Procedures(AB 4-1991) for verifying performance of molded case circuitbreakers.

RMS Sym AmperesBreakerType

Instantaneous Trip Amperes

65,000100,000

100, 125, 150,175, 200, 225,250, 300, 350,400

500 to 1000% of trip unit rating(See Figure Below)(Dc values are approximately 40% higher)

Amperes

TypicalTrip UnitNameplate

Individual PoleAdjustments

ThermalMagneticTrip Unit

C Push to Trip

MagneticMultiples Of In

10

7.5

10 5

7.5

10 5

Amps(In)

Cat.No.40°C

7.5

5

Minimum

@ 240 V., AC @ 480 V., AC @ 600 V., AC @ 250 V., DC

35,00065,000

25,00035,000

10,00022,000

140U-K3140U-K6

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

SDNO

CES

NI E

MIT

1,000

500

300

200

5,000

3,000

2,000

RUOH

1ET

UN I

M 1

SRU O

H 2

SDN OC ES

NI EM IT

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

R UOH 1ETU

NIM 1

SRUOH 2

0010806 090705

0001

00 8

00 6

009

0 07

005

0 04

00 3

00 2

0 00,01

000 8

0006

0 009

0007

00 05

000 4

00 03

0002

000 ,0 01

00 0,08

000,06

000 ,09

000,07

00 0,05

000,04

000 ,03

0 00,02

000 ,01

0 008

0 006

0009

0007

0 005

0004

0003

0002

000 1

00 8

006

009

007

0 05

00 4

0 03

00 2

001

0806 09070 5 000,0 01

000,08

000 ,06

000,09

000,07

000,05

000, 04

000 ,03

000, 02

Maximum Interrupting Time

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING (In)

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING (In)

10,000

Interrupting RatingDetermines Endof Curve

Page 42: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

42

Bul.140U

Time-Current Curves for Bulletin 140U-K0 Thermal-Magnetic Molded Case Circuit Breakers

40752-631 (1)SC-4119-87BEffective October 1997

Maximum

Maximum Single PoleTrip Times at 25°C ➀

Adjustable Magnetic Trip

±20% ±10%X01

(250-400A)

(125-225A)

(100A)

X5

Circuit Breaker Time/Current CurvesFor application and coordination purposes only.Based on 40 °C ambient, cold start. Connected with four (4) feet ofrated wire (60°C up to 125 A. 75° C above 125 amps) per terminal.Tested in open air with current in all poles. Instantaneous calibrationbased on single-pole tests.

Maximum Voltage600V., AC (60 Hz)250 V., DC

Breaker RatingRated Amperes (In)

Interrupting Rating (UL/CSA)

Single pole test data at 25°C based on NEMA Procedures(AB 4-1991) for verifying performance of molded case circuitbreakers.

RMS Sym AmperesBreakerType

Instantaneous Trip Amperes

200,000

100, 125, 150,175, 200, 225,250, 300, 350,400

500 to 1000% of trip unit rating(See Figure Below)(DC values are approximately 40% higher)

Amperes

TypicalTrip UnitNameplate

Individual PoleAdjustments

ThermalMagneticTrip Unit

C Push to Trip

MagneticMultiples Of In

10

7.5

10 5

7.5

10 5

Amps(In)

Cat.No.40°C

7.5

5

Minimum

@ 240 V., AC @ 480 V., AC @ 600 V., AC @ 250 V., DC

100,000 50,000 22,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

SDN O

CES

NI E

MIT

1,000

500

300

200

5,000

3,000

2,000

RUO H

1ET

UNI

M 1

S RUO

H 2

SDN OC ES

N I EMIT

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

RUO H 1ETU

NIM 1

SRUOH 2

0010806 090705

0001

008

006

009

007

005

00 4

003

002

000,01

0008

0006

0009

000 7

0 005

000 4

0003

0002

0 00,00 1

000,0 8

000,0 6

000,09

000,07

000,05

000,04

000,03

000,02

00 0,01

000 8

000 6

0009

0007

0005

0004

0003

0002

000 1

008

006

009

00 7

00 5

004

003

002

00 1

0806 0 9070 5 000 ,0 01

0 00,08

000,06

000,09

000, 07

00 0,05

000, 04

000,03

000,02

Maximum Interrupting Time

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING (In)

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING (In)

10,000

Interrupting RatingDetermines Endof Curve

600 V., Ac

480 V., Ac

240 V., Ac

140U-K0

Time-Current Curves, Continued

Page 43: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

43

Time-Current Curves, Continued

Bul.140UTime-Current Curves for Bulletin 140U-K Electronic LS, LSG Trip Units andBulletin 140U-K3, -K6 Molded Case Circuit Breakers

40752-632 (1)SC-5638-93Effective October 1997

X 6

X 8

X 4

X7

X2

Long Delay➀Minimum TotalClearing Time

Long Delay➀Maximum TotalClearing Time

Standard FixedRating Plug

Short DelayPick UpSettings(Tolerance± 10%)

X5

X3

CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)

.5

.5

SDNOCES

NI EM IT

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

RUOH 1ET U

NIM 1

SRUOH 2

20105432

1.8.6CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)

.7 .9 6 7 8 9

20105432 6 7 8 9.7 .9

Fixed InstantaneousOverride ➁

InterruptingRatingDeterminesEnd ofCurve ➂

000,01

.1

.01

0001

0005

0004

0003

0002

0 00, 02

.001

SDNOC ES

CURRENT IN AMPS

000,03

000,04

000,05

000,001

.02

.03

.04

.05

Short Delay

Engaged

Remove

Cat.

In

Rating Plug

Push to TripPickup • x Ir

Trip Unit40oC

5

73

2 8

4 6

TEST

Curve accuracy applies from –20° C to +55° C ambient. For possible continuousampere derating for ambient above 40°C, consult Rockwell Automation.

For high fault current levels a fixed instantaneous override is provided at 4000 A.(Tolerance ±15%).

The end of the curve is determined by the interrupting rating of the circuit breaker.See above tabulation.

For ground fault time/current curve see 40752-636.

NotesElectronic trip units are suitable for functional field testing with test kit.For field testing using primary injection methods, follow NEMA publication AB-4-1991.

There is a memory effect that can act to shorten the long delay. The memory effectcomes into play if a current above the long delay pick up value exists for a time and thenis cleared by the tripping of a down stream device or the circuit breaker itself. Asubsequent overload will cause the circuit breaker to trip in shorter time than normal.The amount of time delay reduction is inverse to the amount of time that has elapsedsince the previous overload. Approximately five minutes is required between overloadsto completely reset the memory.

Circuit Breaker Time/Current Curves (Phase Current) ➃

Technical Data Covers, Bul. No. 140U-KTH3, -KTG3 Electronic Trip Units for use withCircuit Breaker Types 140U-K3X3 and -K6X3, 400 A Max.

Available Rating Plugs

Interrupting Ratings – 50/60 HzRMS Sym. Amperes (kA)

BreakerType

UL/CSA

140U-K3140U-K6

65100

3565

2535

4065

65100

240V 480V 600V

240V 380V 415V

IEC 947-2

4065

400350300250225200

FixedFixedFixedFixedFixedFixed

140U-KRP3-D40140U-KRP3-D35140U-KRP3-D30140U-KRP3-D25140U-KRP3-D22140U-KRP3-D20

800-3200700-2800600-2400500-2000450-1800400-1600

BreakerType

Fixed Short Delay Time Typical Trip Unit Nameplate

AmpereRating (In)

Type Short DelayPickup RangeAmperes

CatalogNumber

140U-K3140U-K6

.186

Page 44: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

44

Time-Current Curves, Continued

Bul.140U

Time-Current Curves for Bulletin 140U-K Electronic LSI, LSIG Trip Units and Bulletin 140U-K3, -K6 Molded Case Circuit Breakers

40752-633 (1)SC-5639-93Effective October 1997

X6

X8

X4

X 7

X3

X2

Standard FixedRating Plug

200 ms

100 ms

I

300 ms

X5

SDN OC ES

NI EMI T

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

RUOH 1ETU

NIM 1

SRUOH 2

CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)

.5

.5 201054321.8.6

1.8.6CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)

.7 .9 6 7 8 9

20105432 6 7 8 9

Short DelayPick UpSettings(Tolerance±10%)

Long Delay➀Minimum TotalClearing Time

Long Delay➀Maximum TotalClearing Time

.7 .9

Fixed InstantaneousOverride ➁

InterruptingRatingDeterminesEnd ofCurve ➂

000,01

.1

.01

0001

0005

0 004

0003

0002

000,02

.001

S DN OC ES

CURRENT IN AMPS

000,03

000 ,04

000 ,05

0 00, 00 1

1

.02

.03

.04

.05

.2

.3

.4

.5

TEST

Short Delay

Engaged

Remove

Cat.

In

Rating Plug

Push to TripPickup • xIr Time • ms

Trip Unit40oC

5

73

2 8

4 6300

100

INST

200

Curve accuracy applies from –20°C to +55°C ambient. For possible continuous amperederating for ambient above 40°C, consult Rockwell Automation.

For high fault current levels a fixed instantaneous override is provided at 4000A.(Tolerance ±15%).

The end of the curve is determined by the interrupting rating of the circuit breaker.See above tabulation.

For ground fault time/current curve see 40752-636.

NotesElectronic trip units are suitable for functional field testing with test kit.For field testing using primary injection methods, follow NEMA publication AB-4-1991.

There is a memory effect that can act to shorten the long delay. The memory effectcomes into play if a current above the long delay pick up value exists for a time and thenis cleared by the tripping of a down stream device or the circuit breaker itself. Asubsequent overload will cause the circuit breaker to trip in shorter time than normal.The amount of time delay reduction is inverse to the amount of time that has elapsedsince the previous overload. Approximately five minutes is required between overloadsto completely reset the memory.

Circuit Breaker Time/Current Curves (Phase Current) ➃

Technical Data Covers, Cat. Nos. 140U-KTL3, -KTI3 Electronic Trip Units for use withCircuit Breaker Types 140U-K3, -K6, 400A. max.

Available Rating Plugs

Interrupting Ratings – 50/60 HzRMS Sym. Amperes (kA)

BreakerType

UL/CSA

140U-K3140U-K6

65100

3565

2535

4065

65100

240V 480V 600V

240V 380V 415V

IEC 947-2

4065

400350300250225200

FixedFixedFixedFixedFixedFixed

140U-KRP3-D40140U-KRP3-D35140U-KRP3-D30140U-KRP3-D25140U-KRP3-D22140U-KRP3-D20

800-3200700-2800600-2400500-2000450-1800400-1600

BreakerType

Adjustable Short Delay Time Typical Trip Unit Nameplate

AmpereRating (In)

Type Short DelayPickup RangeAmperes

CatalogNumber

140U-K3140U-K6

Page 45: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

45

Time-Current Curves, Continued

Bul.140U

Time-Current Curves for Bulletin 140U-K Electronic LS, LSG Trip Units and 140U-K0 Molded Case Circuit Breakers

40752-634 (1)SC-5644-93Effective October 1997

X6

X8

X4

X7

X2

Long Delay➀Minimum TotalClearing Time

Long Delay➀Maximum TotalClearing Time

Standard FixedRating Plug

Short DelayPick UpSettings(Tolerance± 10%)

X5

X3

CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)

.5

.5

SDNOCES

NI EMI T

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

RUOH 1ET U

NIM 1

SRUOH 2

201054321.8.6

1.8.6CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)

.7 .9 6 7 8 9

20105432 6 7 8 9.7 .9

InterruptingRatingDeterminesEnd ofCurve ➂

.02

.03

.04

.05

S DNOC ES

Fixed InstantaneousOverride ➁

MaximumInterruptingTime

600 VAC

480 VAC

240 VAC

000,01

.1

.01

0005

0004

0003

0 002

000,02

.001

CURRENT IN AMPS

000,0 3

000 ,04

000,05

0 00,001

0 00,002

Short Delay

Engaged

Remove

Cat.

In

Rating Plug

Push to TripPickup • x Ir

Trip Unit40oC

5

73

2 8

4 6

TEST

Curve accuracy applies from –20 °C to +55 °C ambient. For possible continuous ampderating for ambient above 40 °C, consult Rockwell Automation

For high fault current levels a fixed instantaneous override is provided at 4000A.(Tolerance ±15%).

The end of the curve is determined by the interrupting rating of the circuit breaker.See above tabulation.

For ground fault time/current curve see 40752-636.

NotesElectronic trip units are suitable for functional field testing with test kit.For field testing using primary injection methods, follow NEMA publication AB-4-1991.

There is a memory effect that can act to shorten the long delay. The memory effectcomes into play if a current above the long delay pick up value exists for a time and thenis cleared by the tripping of a down stream device or the circuit breaker itself. Asubsequent overload will cause the circuit breaker to trip in shorter time than normal.The amount of time delay reduction is inverse to the amount of time that has elapsedsince the previous overload. Approximately five minutes is required between overloadsto completely reset the memory.

Circuit Breaker Time/Current Curves (Phase Current) ➃

Technical Data Covers, Cat. No. 140U-KTH3, -KTG3 Electronic Trip Units for use withCircuit Breaker Type 140U-K0, 400A. max.

Available Rating Plugs

Interrupting Ratings – 50/60 HzRMS Sym. Amperes (kA)

BreakerType

UL/CSA

200

100 50

100

200

240V 480V 600V

240V 380V 415V

IEC 947-2

100

400350300250225200

FixedFixedFixedFixedFixedFixed

140U-KRP3-D40140U-KRP3-D35140U-KRP3-D30140U-KRP3-D25140U-KRP3-D22140U-KRP3-D20

800-3200700-2800600-2400500-2000450-1800400-1600

BreakerType

Fixed Short Delay Time Typical Trip Unit Nameplate

AmpereRating (In)

Type Short DelayPickup RangeAmperes

CatalogNumber

140U-K0

140U-K0

Page 46: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

46

Bul.140U

Time-Current Curves for Bulletin 140U-K Electronic LSI, LSIG Trip Units and 140U-K0 Molded Case Circuit Breakers

40752-635 (1)SC-5645-93Effective October 1997

X6

X8

X4

X 7

X3

X2

Standard FixedRating Plug

200 ms

100 ms

I

300 ms

X5

.02

.03

.04

.05Fixed InstantaneousOverride ➁

InterruptingRatingDeterminesEnd ofCurve ➂

000,01

.1

.01

0005

0004

0003

000 2

0 00, 02

.001

S DNOC ES

CURRENT IN AMPS

0 00, 03

0 00, 04

00 0,0 5

00 0,0 01

1

000,002

600 VAC

480 VAC

240 VAC

MaximumInterruptingTime

TEST

Short Delay

Engaged

Remove

Cat.

In

Rating Plug

Push to TripPickup • xIr Time • ms

Trip Unit40oC

5

73

2 8

4 6300

100

INST

200

Curve accuracy applies from –20°C to +55°C ambient. For possible continuousampere derating for ambient above 40°C, consult Rockwell Automation.

For high fault current levels a fixed instantaneous override is provided at 4000A.(Tolerance ±15%).

The end of the curve is determined by the interrupting rating of the circuit breaker.See above tabulation.

For ground fault time/current curve see 40752-636.

Noteselectronic trip units are suitable for functional field testing with test kit.For field testing using primary injection methods, follow NEMA publication AB-4-1991.

There is a memory effect that can act to shorten the long delay. The memory effectcomes into play if a current above the long delay pick up value exists for a time and thenis cleared by the tripping of a down stream device or the circuit breaker itself. Asubsequent overload will cause the circuit breaker to trip in shorter time than normal.The amount of time delay reduction is inverse to the amount of time that has elapsedsince the previous overload. Approximately five minutes is required between overloadsto completely reset the memory.

SDN OC ES

NI EMI T

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

RUOH 1ETU

NIM 1

SRUOH 2

CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)

.5

.5 2010

1.8.6CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)

.7 .9 6 7 8 9

20102 6 7 8 9

Short DelayPick UpSettings(Tolerance±10%)

Long Delay➀Minimum TotalClearing Time

Long Delay➀Maximum TotalClearing Time

.7 .9

Circuit Breaker Time/Current Curves (Phase Current) ➃

Technical Data Covers, Cat. Nos. 140U-KTL3, -KTI3 Electronic Trip Units for use withCircuit Breaker Cat. No 140U-K0, 400A. max.

Available Rating Plugs

Interrupting Ratings – 50/60 HzRMS Sym. Amperes (kA)

BreakerType

UL/CSA

140U-K0

100 50

100

200

240V 480V 600V

240V 380V 415V

IEC 947-2

100

BreakerType

Adjustable Short Delay Time Typical Trip Unit Nameplate

AmpereRating (In)

Type Short DelayPickup RangeAmperes

CatalogNumber

140U-K0

400350300250225200

FixedFixedFixedFixedFixedFixed

140U-KRP3-D40140U-KRP3-D35140U-KRP3-D30140U-KRP3-D25140U-KRP3-D22140U-KRP3-D20

800-3200700-2800600-2400500-2000450-1800400-1600

200

1 5

5

Time-Current Curves, Continued

Page 47: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

47

Time-Current Curves, Continued

Bul.140U

Time-Current Curves for Bulletin 140U-K Electronic Trip Units with Ground Fault Protection

40752-636 (1)SC-5650-93Effective October 1997

Ground Fault PickupSettings(Tolerance ± 10%Except ± 20% on1xIG Setting)

Ix3G

1

Ix4G

Ix2G

I x1G

2 3 4 5 6 7 8 9 10 100

TESTEngaged

Remove

Cat.

In

Rating Plug

Push to Trip

Trip Unit40oC

Ground Fault

Pickup • xIg Time • ms

Short Delay

Pickup • xIr

5

73

2 8

4 6500

150

INST

3004

2

1

3 5

Ig = 80A

TESTEngaged

Remove

Cat.

In

Rating Plug

Push to Trip

Trip Unit40oC

5

73

2 8

4 6

Short Delay

Pickup • x Ir Time • ms

Ground Fault

Pickup • xIg Time • ms

300

100

INST

200500

150

INST

3004

2

1

3 5

Ig = 80A

For phase time/current curves see 40752-632, -633, -634, or 40752-635.➀

NotesCurve accuracy applies from –20 °C to +55 °C ambient. For possible continuousampere derating for ambient above 40 °C, consult Rockwell Automation.

Electronic trip units are suitable for functional field testing with test kit.For field testing using primary injection methods, follow NEMApublication AB-4-1991.

GROUND CURRENT-AMPERES

SDNOCES

NI EMIT

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

RUOH 1ETU

NIM 1

SRUOH 2

000 8

GROUND CURRENT-IN MULTIPLES OF Ig = 80A

008

084

00 4

023

042

06108

06 504602 7

Ix5G

I

500 ms

300 ms

150 ms

Circuit Breaker Time/Current Curves (Ground Current) ➀

Electronic Trip Units for use with Bulletin 140U-K3, -K6, and K0Molded Case Circuit BreakersFor use with Trip Unit Catalog Numbers140U-KTG3-D40140U-KTI3-D40

Page 48: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

48

Time-Current Curves, Continued

Bul.140U

Time-Current Curves for Bulletin 140U-K0 Thermal-Magnetic Molded Case Circuit Breakers

40752-651 (1)SC-4119-87BEffective October 1997

Maximum

Maximum Single PoleTrip Times at 25°C ➀

Adjustable Magnetic Trip

±20% ±10%X01

(250-400A)

(125-225A)

(100A)

X5Circuit Breaker Time/Current CurvesFor application and coordination purposes only.Based on 40 °C ambient, cold start. Connected with four (4) feet ofrated wire (60°C up to 125 A. 75 °C above 125 amps) per terminal.Tested in open air with current in all poles. Instantaneous calibrationbased on single-pole tests.

Maximum Voltage600V., AC (60 Hz)250 V., DC

Breaker RatingRated Amperes (In)

Interrupting Rating (UL/CSA)

Single pole test data at 25 °C based on NEMA Procedures(AB 4-1991) for verifying performance of molded case circuitbreakers.

RMS Sym AmperesBreakerType

Instantaneous Trip Amperes

200,000

100, 125, 150,175, 200, 225,250, 300, 350,400

500 to 1000% of trip unit rating(See Figure Below)(Dc values are approximately 40% higher)

Amperes

TypicalTrip UnitNameplate

Individual PoleAdjustments

ThermalMagneticTrip Unit

C Push to Trip

MagneticMultiples Of In

10

7.5

10 5

7.5

10 5

Amps(In)

Cat.No.40°C

7.5

5

Minimum

@ 240 V., AC @ 480 V., AC @ 600 V., AC @ 250 V., DC

100,000 50,000 22,0000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

SDN O

CES

NI E

MIT

1,000

500

300

200

5,000

3,000

2,000

RUO H

1ET

UNI

M 1

S RUO

H 2

SDN OC ES

N I EMIT

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

RUO H 1ETU

NIM 1

SRUOH 2

0010806 090705

0001

008

006

009

007

005

00 4

003

002

000,01

0008

0006

0009

000 7

0 005

000 4

0003

0002

0 00,00 1

000,0 8

000,0 6

000,09

000,07

000,05

000,04

000,03

000,02

00 0,01

000 8

000 6

0009

0007

0005

0004

0003

0002

000 1

008

006

009

00 7

00 5

004

003

002

00 1

0806 0 9070 5 000 ,0 01

0 00,08

000,06

000,09

000, 07

00 0,05

000, 04

000,03

000,02

Maximum Interrupting Time

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING (In)

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING (In)

10,000

Interrupting RatingDetermines Endof Curve

600 V., Ac

480 V., Ac

240 V., Ac

140U-K0

Page 49: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

49

Time-Current Curves, Continued

Bul.140U/UE

Time-Current Curves for Bulletin 140U-L Thermal-Magnetic Molded Case Circuit Breakers

40752-650 (1)TC-XXXXXEffective June 2003

Maximum Interruption Time

Interruption Rating determines end of curve

Current in Multiples of Rating (In)

ETU

NIM

1

E TUNI

M 1

Hour 1

Hour

1

Circuit Breaker Time/Current Curves

For application and coordination purposes only. Thermal calibrationbased on 40 °C ambient, cold start. Connected with four (4) feet of rated wire (75C) per terminal. Tested in open air with current in allpoles. Instantaneous calibration based on single-pole tests.

Maximum Voltage600V., AC (50/60 Hz)250 V., DC

Poles3 and 4

Breaker RatingRated Amperes (I Instantaneous Trip Amperes (see below)

250, 300, 320, 350 500 to 1000% of trip unit rating(DC values are approximately 40% higher)

n)

Interrupting Rating (UL/CSA)

BreakerType

RMS Sym Amperes Amperes

@ 240 V., AC @ 480 V., AC @ 600 V., AC @ 250 V., DC

140U-L3

140U-L6

65

42352218

65

35

100

Interrupting Rating (IEC 60947-2)

BreakerType

RMS Sym kA, 50/60 Hz, AC kA, DC

@ 240 V. (Ue) @ 480 V (Ue)

140U-L3

140U-L6

65

42252212

70

35

100

@600V. (Ue) @ 250 V.(Ue)

Icu Icu Icu IcuIcs Ics Ics Ics

65

4213226

70

35

100

Page 50: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

50

Time-Current Curves, Continued

Bul.140U/UE

Earth Leakage Curves for Bulletin 140U/UE-L Thermal-Magnetic Molded Case Circuit Breakers

40752-651 (1)Curve No. TC01212009EEffective September 2005

1000.0

.001

.002

.003

.004

.005

.006

.007

.008

.009

.01

.02

.03

.04

.05

.06

.07

.08

.09

.1

.2

.3

.4

.5

.6

.7

.8

.91.0

2.0

3.0

4.0

5.0

6.07.08.09.0

10.0

100.090.080.070.060.0

50.0

40.0

30.0

20.0

200.0

300.0

400.0

500.0

600.0700.0800.0900.0

SD

NO

CESNI

EMI T

1000.0

.001

.002

.003

.004

.005

.006

.007

.008

.009

.01

.02

.03

.04

.05

.06

.07

.08

.09

.1

.2

.3

.4

.5

.6

.7

.8

.91.0

2.0

3.0

4.0

5.0

6.07.08.09.0

10.0

100.090.080.070.060.0

50.0

40.0

30.0

20.0

200.0

300.0

400.0

500.0

600.0700.0800.0900.0

SD

NO

CES

NIE

MIT

Ig (A)

Available Ig (A)Settings

1S

Inst.

500ms

300ms

150ms

60ms

.01 .02 .03 .04 .1 .2 .3.07.05 .4 2.01.0.7.5 3.0 4.0 5.0 7.0 10.0

.01 .02 .04 .05 .07.03 .1 .2 .3 .4 .5 .7 1.0 3.02.0 4.0 5.0 7.0 10.0 20.0 50.0 80.0

20.0 50.0 80.0

.03 .1 .5 2 6 30

Circuit Breaker Time/Current Curves

1. 140U/UE-L Cir. Break. Earth Leakage Mod., 3 and 4 Poles,110 … 480V 60Hz.

2. For application and coordination purposes only. -20 C …55 C ambient.

3. Total clearing times include the response time of the EarthLeakage module, opening time of the circuit breaker, andinterruption of current.

4. For additional curve tolerances, contact Rockwell Automation.

°°

Page 51: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

51

Time-Current Curves, Continued

Bul.140U/UE

Earth Leakage Curves for Bulletin 140U/UE-L Thermal-Magnetic Molded Case Circuit Breakers

40752-652 (1)Curve No. TC01212008EEffective September 2005

1031.3.1

1S

500ms

300ms

150ms

60ms

.03

I n (Amperes)

1000.0

.001

.002

.003

.004

.005

.006

.007

.008

.009

.01

.02

.03

.04

.05

.06

.07

.08

.09

.1

.2

.3

.4

.5

.6

.7

.8

.91.0

2.0

3.0

4.0

5.0

6.07.08.09.0

10.0

100.090.080.070.060.0

50.0

40.0

30.0

20.0

200.0

300.0

400.0

500.0

600.0700.0800.0900.0

SD

NO

CESNI

EMI T S

DN

OCE

SNI

EMI

T

.001

.002

.003

.004

.005

.006

.007

.008

.009

.01

.02

.03

.04

.05

.06

.07

.08

.09

.1

.2

.3

.4

.5

.6

.7

.8

.91.0

2.0

3.0

4.0

5.0

6.07.08.09.0

10.0

100.090.080.070.060.0

50.0

40.0

30.0

20.0

200.0

300.0

400.0

500.0

600.0700.0800.0900.0

1000.0.01 .02 .03 .04 .1 .2 .3.07.05 .4 2.01.0.7.5 3.0 4.0 5.0 7.0 10.0 20.0 50.0 80.0

.01 .02 .03 .04 .1 .2 .3.07.05 .4 2.01.0.7.5 3.0 4.0 5.0 7.0 10.0 20.0 50.0 80.0

Inst.

Circuit Breaker Time/Current Curves

1. 140U/UE-L Cir. Break. Earth Leak. Mod., 3 and 4 Poles,110 … 480V 60Hz.

2. For application and coordination purposes only. -20 C …55 C ambient.

3. Total clearing times include the response time of the EarthLeakage module, opening time of the circuit breaker, andinterruption of current.

4. For additional curve tolerances, contact Rockwell Automation.

°°

Available I n Settings

Page 52: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

52

Time-Current Curves, Continued

Bul.140U/UE

Long Delay Response & Short Delay with Flat Response Curve, Bulletin 140U/UE-L

40752-653 (1)TC01207004EEffective March 2006

.01

1

2

3

4

5

6789

10

20

30

40

50

60708090

100

1000900800700600

500

400

300

200

2000

3000

4000

5000

6000700080009000

10000

.02

.03

.04

.05

.06

.07

.08.09

.1

.2

.3

.4

.5

.6.7.8.91

3

4

5

6789

10

20

30

40

50

60708090

100

1000900800700600

500

400

300

200

2000

3000

4000

5000

6000700080009000

10000

ETU

NIM

1S

RU

OH

2S

DN

OCES

NIE

MI TR

UO

H1

.01

.02

.03

.04

.05

.06

.07

.08

.09

.1

.2

.3

.4

.5

.6

.7

.8

.91

2

Maximum TotalClearing Time

Available Long Delay Time:2,4,7,10,12,15,20,24 sec.

Shown @ 6x2,4,7,15,24

seconds +0/-30%

Ir

7

2

SD

NO

CESNI

EMI T

2

Available Sensors ( ):In

Circuit Breaker Time/Current Curves (Phase Current)

Long Delay (LD) & Short Delay (SD) with Flat Response

250A400A600A630A

Current in Multiples of ( )Ir

Current in Multiples of ( )Ir

1 2 3 4 5 7 10 20 30 40 50 70 100 2 3 4 5 7 10 20 30 40 50 70 100.5 .7

1 2 3 4 5 7 10 20 30.5 .7

8

Current in Multiples of ( )In

Minimum TotalClearing Time

10

4

4

.15

.24

63

1.15

Notes:

1. Curve accuracy applies from -20 C to +55 C ambient. Temperatures above +85 C cause an over-temperature protection trip. For possible continuous ampere derating for ambient above 40 C, refer toRockwell Automation.

2. Application frequency is 50/60 Hertz.

4. The right portion of the curve is determined by the interrupting rating of the circuit breaker.

5. The left portion of the curve is shown as a multiple of the Long Delay Setting.(Long Delay Pick Up = 115% of ). Range is 110% - 120%.

6. Total clearing times shown include the response times of the trip unit, the breaker opening, and theinterruption of the current.

7. The Short Delay Pick Up has 8 settings/positions, 2 - 8 & 10.

8. For high fault current levels an additional fixed instantaneous hardware override is provided(corresponding to SDPU position 9) at 14x ( ) and designated as 14 . Instantaneous tolerance is 20%.

9. For LD Response & SD with Flat Response (this curve): TC01207004E

10. For LD Response & SD with T Response curve, see: TC01207005E

11. For Ground Fault Delay Response curve, see: TC01207006E

° ° °°

I

3. There is a memory effect that can act to shorten the Long Delay. The memory effect comes into play if acurrent above the circuit breaker itself. A subsequent overload will cause the circuit breaker to trip inshorter time than normal. The amount of time delay reduction is inverse to the amount of time that haselapsed since the previous overload. Approximately five minutes is required between overloads tocompletely reset memory.

I

I I

r

n i

2

Adjustable Flat Trip Style

14 Ii

Application DeterminesEnd of Curve

InstantaneousOverride (See Note 8)

7

.

5

.

300ms(P,Q,R)

120ms(M,N,O)

Inst.(J,K,L)

Bulletin 140U/UE L-Frame 3- and 4-Pole Molded Case Circuit Breakers

In 250A 400A 600A 630AIr

250A300A315A350A400A450A500A600A

250A300A315A350A400A450A500A600A

250A300A315A350A400A500A600A630A

250A300A315A350A400A500A600A630A

160A200A225A250A300A315A350A400A

160A200A225A250A300A315A350A400A

100A125A150A160A175A200A225A250A

100A125A150A160A175A200A225A250A

ABCDEFGH

ABCDEFGH

Available Short DelayPick Up Settings2 - 8,10 x 5%Ir

(See Note 7)

.

Page 53: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

53

Time-Current Curves, Continued

Bul.140U/UE

Long-Delay Response & Short-Delay with I2T Response Curve, Bulletin 140U/UE-L

40752-654 (1)TC01207005EEffective March 2006

.01

1

2

3

4

5

6789

10

20

30

40

50

60708090

100

1000900800700600

500

400

300

200

2000

3000

4000

5000

6000700080009000

10000

.02

.03

.04

.05

.06

.07

.08.09

.1

.2

.3

.4

.5

.6.7.8.91

3

4

5

6789

10

20

30

40

50

60708090

100

1000900800700600

500

400

300

200

2000

3000

4000

5000

6000700080009000

10000

ETU

NIM

1S

RU

OH

2S

DN

OCES

NIE

MI TR

UO

H1

.01

.02

.03

.04

.05

.06

.07

.08

.09

.1

.2

.3

.4

.5

.6

.7

.8

.91

Maximum TotalClearing Time

Available Long Delay Time:2,4,7,10,12,15,20,24 sec.

Shown @ 6x2,4,7,15,24

seconds +0/-30%

Ir

7

2

SD

NO

CESNI

EMI T

Available Short DelayPick Up Settings

2 - 8 & x 5%10 Ir

(See Notes 7 and 10)

Application DeterminesEnd of Curve

2

InstantaneousOverride (See Note 10)

Available Sensors ( ):In

Circuit Breaker Time/Current Curves (Phase Current)

Long Delay (LD) & Short Delay (SD) with I2T Response

250A400A600A630A

Current in Multiples of ( )Ir

Current in Multiples of ( )Ir

1 2 3 4 5 7 10 20 30 40 50 70 100 2 3 4 5 7 10 20 30 40 50 70 100.5 .7

1 2 3 4 5 7 10 20 30.5 .7

8

Current in Multiples of ( )In

Notes:

1. Curve accuracy applies from -20 C to +55 C ambient. Temperatures above +85 C cause an overtemperature protection trip. For possible continuous ampere derating for ambient above 40 C, refer toRockwell Automation.

2. Application frequency is 50/60 Hertz.

4. The right portion of the curve is determined by the interrupting rating of the circuit breaker.

5. The left portion of the curve is shown as a multiple of the Long Delay Setting(Long Delay Pick Up = 115% of ). Range is 110% - 120%.

6. Total clearing times shown include the response times of the trip unit, the breaker opening, and theinterruption of the current.

7. The Short Delay Pick Up has eight settings/positions: 2 - 8 & 10.

8. Short Delay T band has a tolerance of 15%.

9. Breakpoint back to FLAT response occurs @ 8x for upper line of the T curve.

10. For high fault current levels an additional fixed instantaneous hardware override is provided(corresponding to SDPU position 9) at 14x ( ) and designated as 14 Instantaneous tolerance is

20%

11. For LD Response & SD with Flat Response curve, see: 40752-653

12. For LD Response & SD with T Response (this curve): 40752-654

13. For Ground Fault Delay Response curve, see: 40752-655

° ° °°

I ±

I

±

I

3. There is a memory effect that can act to shorten the Long Delay. The memory effect comes into playif a current above the circuit breaker itself. A subsequent overload will cause the circuit breaker to tripin shorter time than normal. The amount of time delay reduction is inverse to the amount of time thathas elapsed since the previous overload. Approximately five minutes is required between overloads tocompletely reset memory.

I

I

I I

r

r

n i

2

2

2

.

Long Delay Response & Short Delay with Response CurveI T2

I2T Trip Style

I2T Short Delay(See Note 8)

Minimum TotalClearing Time

10

7

5

4

.

.4

.

.15

.24

6

.

3

1.15

See Note 9

14 Ii

67ms

Bulletin 140U/UE L-Frame 3- and 4-Pole Molded Case Circuit Breakers

In 250A 400A 600A 630AIr

250A300A315A350A400A450A500A600A

250A300A315A350A400A450A500A600A

250A300A315A350A400A500A600A630A

250A300A315A350A400A500A600A630A

160A200A225A250A300A315A350A400A

160A200A225A250A300A315A350A400A

100A125A150A160A175A200A225A250A

100A125A150A160A175A200A225A250A

ABCDEFGH

ABCDEFGH

Page 54: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

54

Time-Current Curves, Continued

Bul.140U/UE

Ground Fault Delay Response Curve, Bulletin 140U/UE-L

40752-655 (1)TC01207006EEffective March 2006

.01

2

3

4

5

6

8

10

20

30

40

50

60708090

100

1000900800700600

500

400

300

200

.02

.03

.04

.05

.06

.07

.08

.09.1

.2

.3

.4

.5

.6

.7

.8

.91

7

9

2000

3000

4000

5000

6000700080009000

10000

ETU

NIM

1S

DN

OCES

NIE

MI T

Ground Current in Multiple of ( )In

.1 .2 .3 .4 .5 .7 1.0 2.0

.1 .2 .3 .4 .5 .7 1.0 2.0

bulletin 140U/UE L-Frame 3- and 4-Pole Molded Case Circuit Breakers

Ground Fault Pickup Settings(Tolerance 10%)

.4X

Circuit Breaker Time/Current Curves (Ground Current)

.3X

.2X 1X.6X

.8X

NOTE: Refer to table below for variations.

Ground Fault Delay Response Notes:

1. Curve accuracy applies from -20 C to +55 C ambient. Temperatures above +85 C cause anover-temperature protection trip. For possible continuous ampere derating for ambient above40 C, refer to Rockwell Automation.

2.Application frequency is 50/60 Hertz.

3. Trip units are suitable for functional field testing with test kit style # 70C1056G52.

4. For LD Response & SD with Flat Response curve, see: 40752-6535. For LD Response & SD with T Response curve, see: 40752-654

6. For Ground Fault Delay Response (this curve): 40752-655

° ° °

°

I2

Inst.(J,M,P)

120ms(K,N,Q)

300ms(L,O,R)

Available Sensors ( ):In

250A400A600A630A

In 250A 400A 600A 630AIr

250A300A315A350A400A450A500A600A

250A300A315A350A400A450A500A600A

250A300A315A350A400A500A600A630A

250A300A315A350A400A500A600A630A

160A200A225A250A300A315A350A400A

160A200A225A250A300A315A350A400A

100A125A150A160A175A200A225A250A

100A125A150A160A175A200A225A250A

ABCDEFGH

ABCDEFGH

Page 55: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

55

Time-Current Curves, Continued

Bul.140U

Time-Current Curves for Bulletin 140U-Q3/Q6 Thermal-Magnetic Molded Case Circuit Breakers

40752-670 (1)SC-4547-89BEffective October 1997

MaximumMinimum

Maximum SinglePole Trip Timesat 25°C 1

Adjustable Magnetic Trip

X5

X01

±20% ±10%

TypicalTrip UnitNameplate

Individual PoleAdjustments

ThermalMagneticTrip Unit

C Push to Trip

MagneticMultiples Of In

10

7.5

10 5

7.5

10 5

Amps(In)

Cat.No.40°C

7.5

5

Circuit Breaker Time/Current Curves

For application and coordination purposes only. Thermal calibrationbased on 40 °C ambient, cold start. Connected with four (4) feet ofrated wire (75°C) per terminal. Tested in open air with current in allpoles. Instantaneous calibration based on single-pole tests.

Maximum Voltage600 V., AC (50/60 Hz.)250 V., DC

Breaker RatingRated Amperes (In)

Interrupting Rating

UL/CSA

RMS Sym. kA, 50/60 Hz.

Single pole data at 25 °C based on NEMA Procedures(AB 4-1991) for verifying performance of molded case circuitbreakers.

240 V.

BreakerType

140U-Q3140U-Q6

Utilization Category AUIMP = 8 kV

Instantaneous Trip Amperes(See Figure Below)

480 V. 600 V. 250 V.

1020

IEC 947-2

RMS Sym. kA, 50/60 Hz.

240 V., (Ue) 380 V., (Ue) 415 V., (Ue) 250 V., (Ue)

kA, Dc

kA, Dc

Icu Ics Icu Ics Icu Ics Icu Ics

65 17 40 10 40 10 10 3100 25 65 17 65 17 20 5

Note: For additional information on the trip unit, see IL 29C606.

300, 350, 400,500, 600

500 to 1000% of trip unit rating (DC valuesare approximately 40% higher)

65 35 25100 65 35

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

S DN O

CES

N I E

MIT

1,000

500

300

200

5,000

3,000

2,000

RUOH

1ET

UNI

M 1

SRU O

H 2

SDN OCES

NI EMIT

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

RU OH 1ET U

NIM 1

SRUO H 2

0010806 090705

0001

008

006

00 9

007

005

004

003

002

000,01

000 8

0006

0009

0007

0005

0004

0003

0002

000, 001

000,08

000,06

000 ,09

000, 07

00 0,05

00 0,04

000,03

000,02

000, 01

00 08

00 06

0009

0007

0005

00 04

0003

00 02

0001

008

006

009

00 7

005

004

003

0 02

001

0806 090705 00 0,001

000 ,08

000,06

00 0,09

000,0 7

000,05

000,04

000,03

000,02

Maximum Interrupting Time

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING (In)

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING (In)

Interrupting RatingDetermines End ofCurve

10,000

140U-Q3140U-Q6

Time-Current Curves, Continued

Page 56: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

56

Bul.140U/UE

Time-Current Curves for Bulletin 140U-M5, -M6 Thermal-Magnetic (300…600 A) Molded Case Circuit Breakers

40752-674 (1)SC-6911-98Effective February 1999

MaximumMinimum

Maximum SinglePole Trip Timesat 25?C 1

Adjustable Magnetic Trip

X5

X01

?20% ?10%

TypicalTrip UnitNameplate

BreakerType

140U-M5140U-M6

Circuit Breaker Time/Current Curves

For application and coordination purposes only. Thermal calibration based on 40 °C ambient, cold start. Connectedwith four (4) feet of rated wire (75 °C) per terminal.Tested in open air with current in all poles.Instantaneous calibration based on single-pole tests.

Maximum Voltage600 V AC (50/60 Hz.)250 V DC

Breaker RatingRated Amperes (In

Interrupting Rating

UL/CSA

RMS Sym. kA, 50/60 Hz.

Single pole data at 25 ° C based on NEMA Procedures(AB 4-1991) for verifying performance of molded case circuitbreakers.

Utilization Category AUIMP = 8 kV

Instantaneous Trip Amperes(See Figure Below)

250V

2225

240V (Ue) 380/415V (Ue) 690V (Ue) 250V (Ue)

kA, DC

kA, DC

Icu Ics

65100

Note: For additional information on the trip unit, see IL 29C607.

300, 350, 400,500, 600

500 to 1000% of trip unit rating (DC valuesare approximately 40% higher)

BreakerType

140U-M5140U-M6

65100

Icu Ics

5070

5050

Icu Ics

2025

1013

Icu Ics

2020

1010

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

S DNO CE S

NI EM IT

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

RUOH 1E TU

NIM 1

SRU OH 2

00 10806 090705

000 1

00 8

006

00 9

007

005

0 04

0 03

002

000,01

0008

00 06

0009

0007

0005

00 04

0003

0002

0 00 ,001

000, 08

00 0,0 6

000 ,09

00 0,07

0 00, 05

00 0,04

0 00,03

000 ,02

00 0,01

0008

0006

0009

000 7

0005

0004

0003

0002

0001

0 08

0 06

009

007

005

0 04

0 03

002

0 01

080 6 0 90705 000 ,00 1

0 00, 08

000,0 6

000, 09

000 ,07

0 00,05

000,04

00 0,0 3

0 00, 02

Maximum Interrupting Time

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING (In)

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING (In)

Interrupting RatingDetermines End ofCurve

10,000

600V

2535

480V

5065

240V

65100

IEC 947-2

RMS Sym. kA, 50/60 Hz.

Individual PoleAdjustments

Push to Trip

MagneticMultiples Of In

10

7.5

10 5

7.5

10 5

Amps(In)

Cat.No.40 °C

7.5

5

)

Time-Current Curves, Continued

Page 57: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

57

Bul.140U/UE

Time-Current Curves for Bulletin 140U-M5, -M6 Thermal-Magnetic (700 & 800 A) Molded Case Circuit Breakers

40752-675 (1)SC-6912-98Effective February 1999

MaximumMinimum

Maximum SinglePole Trip Timesat 25?C 1

Adjustable Magnetic Trip

TypicalTrip UnitNameplate

Individual PoleAdjustments

ThermalMagneticTrip Unit

Push to Trip

MagneticMultiples Of In

Amps(In)

Cat.No.

Circuit Breaker Time/Current CurvesFor application and coordination purposes only. Thermal calibration based on 40 °C ambient, cold start. Connected with four (4) feet of rated wire (75 °C) per terminal.Tested in open air with current in all poles.Instantaneous calibration based on single-pole tests.

Maximum Voltage600 V AC (50/60 Hz.)250 V DC

Breaker RatingRated Amperes (I n) Instantaneous Trip Amperes

(See Figure Below)700, 800 400 to 800% of Trip Unit rating (DC values

are approximately 40% higher)

BreakerType

140U-M5140U-M6

Interrupting Rating

UL/CSA

RMS Sym. kA, 50/60 Hz.

Single pole data at 25°C based on NEMA Procedures(AB 4-1991) for verifying performance of molded case circuitbreakers.

Utilization Category AUIMP = 8 kV

250V

2225

240V (Ue) 380/415V (Ue) 690V (Ue) 250V (Ue)

kA, DC

kA, DC

Icu Ics

65100

BreakerType

140U-M5140U-M6

65100

Icu Ics

5070

5050

Icu Ics

2025

1013

Icu Ics

2020

1010

600V

2535

480V

5065

240V

65100

IEC 947-2

RMS Sym. kA, 50/60 Hz.

°C

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

SDN O

C ES

N I E

M IT

1,000

500

300

200

5,000

3,000

2,000

R UOH

1E T

UN I

M 1

SRU O

H 2

SDNOCES

NI EM IT

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

RUOH 1ETU

NIM 1

SRUOH 2

0010806 090 70 5

00 01

008

006

009

007

00 5

004

0 03

002

000, 01

0008

0006

0009

0007

0005

0004

0003

0002

0 00,0 01

0 00, 0 8

00 0,0 6

00 0,09

0 00, 07

0 00,05

00 0,04

000,03

000,02

000,01

0008

0006

00 09

0 007

0005

0004

00 03

0002

0001

008

006

009

00 7

005

004

003

00 2

00 1

0806 090705 0 00,00 1

0 00,0 8

0 00,06

000 ,09

000 ,07

0 00 ,05

0 00,0 4

000 ,0 3

000,02

Maximum Interrupting Time

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING (In)

CURRENT IN PERCENT OF BREAKER TRIP UNIT RATING (In)

Interrupting RatingDetermines End ofCurve

10,000

8

6

4 8

6

4 8

6

4

X4

?20% X8

?10%

Time-Current Curves, Continued

Page 58: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

58

Bul.140U/UE

Time-Current Curves for Bulletin 140U-M Electronic LS, LSG Trip Units and 140U-M5, -M6 Molded Case Circuit Breakers

40752-676 (1)SC-7204-99Effective February 1999

X6

X 8

X4

X7

X2

Long Delay➀Minimum TotalClearing Time

Long Delay➀Maximum TotalClearing Time

Standard FixedRating Plug

Short DelayPick UpSettings(Tolerance ±10%)

X5

X3

CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)

.5

.5

SDNOCES NI EMIT

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

RU

OH 1

ET

UNI

M 1S

RU

OH 2

201054321.8.6

1.8.6CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)

.7 .9 6 7 8 9

20105432 6 7 8 9.7 .9

Fixed InstantaneousOverride ➁

000 ,01

.1

.01

0001

0005

0 004

0003

00 02

0 00 ,02

.001

SDNOC ES

CURRENT IN AMPS

000,0 3

000,0 4

000,0 5

0 00,001

.02

.03

.04

.05

Circuit Breaker Time/Current Curves (Phase Current) ➃

Technical Data Covers, Cat. Nos. 140U-MTL3, -MTG3 Electronic Trip Unitfor use with Circuit Breaker Types 140U-M5, -M6, 800 A max.

Available Rating Plugs

Interrupting Rating

UL/CSA

RMS Sym. kA, 50/60 Hz

5065

2535

65100

240V 480V 600V

IEC 947-2

RMS Sym. kA, 50/60 Hz

800700600500450400

FixedFixedFixedFixedFixedFixed

140U-MRP3-D80140U-MRP3-D70140U-MRP3-D60140U-MRP3-D50140U-MRP3-D45140U-MRP3-D40

1600-64001400-56001200-48001000-4000900-3600800-3200

BreakerType

Fixed Short Delay Time Typical Trip Unit Nameplate

AmpereRating (I n)

Type Short DelayPickup RangeAmperes

Rating PlugCatalogNumber

240V (Ue) 380/415V (U e) 690V (U e)Icu Ics Icu Ics Icu Ics

Utilization Category AUimp = 8kV

65100

65100

5070

5050

2025

1013

Engaged

Remove

Cat.

In

Rating Plug

Push to Trip

Short DelayPickup x In

5

73

2 8

4 6Trip Unit40oC Ambient

Test

Curve accuracy applies from –20 °C to +55°C ambient. For possible continuous amperederating for ambient above 40 °C, consult Rockwell Automation.

For high fault current levels a fixed instantaneous override is provided at 5500A.(Tolerance ±15%).

The end of the curve is determined by the interrupting rating of the circuit breaker.See above tabulation.

For ground fault time/current curves see 40752-678.

NotesElectronic trip units are suitable for functional field testing with test kit.For field testing using primary injection methods, follow NEMA AB4-1991 publications.

Calibration response in short delay pick-up range is same for 1, 2 or 3 poles in series.

There is a memory effect that can act to shorten the long delay. The memory effect comesinto play if a current above the long delay pick-up value exists for a time and then is clearedby the tripping of a downstream device or the circuit breaker itself. A subsequent overloadwill cause the circuit breaker to trip in shorter time than normal. The amount of time delayreduction is inverse to the amount of time that has elapsed since the previous overload.Approximately five minutes is required between overloads to completely reset the memory.

BreakerType

InterruptingRatingDeterminesEnd ofCurve ➂

140U-M5140U-M6

140U-M5140U-M6

Time-Current Curves, Continued

Page 59: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

59

Bul.140U/UE

Time-Current Curves for Bulletin 140U-M Electronic LSI, LSIG Trip Units and 140U-M5, -M6 Molded Case Circuit Breakers

40752-677 (1)SC-6913-98Effective February 1999

X6

X8

X4

X7

X3

X2

Standard FixedRating Plug

200 ms

100 ms

I

300 ms

X5

SD NOCES N I EM IT

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

RU

OH 1

ET

UNI

M 1S

RU

OH 2

CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)

.5

.5 201054321.8.6

1.8.6CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)

.7 .9 6 7 8 9

20105432 6 7 8 9

Short DelayPickupSettings(Tolerance?10%)

Long Delay➀Minimum TotalClearing Time

Long Delay➀Maximum TotalClearing Time

.7 .9

Fixed InstantaneousOverride ➁

InterruptingRatingDeterminesEnd ofCurve ➂

000,01

.1

.01

0001

0005

00 04

00 03

000 2

000 ,0 2

.001

SDN OCES

CURRENT IN AMPS

000 ,0 3

0 00,04

0 00,05

000,0 0 1

.02

.03

.04

.05

Circuit Breaker Time/Current Curves (Phase Current) ➃

Technical Data Covers, Cat. nos. 140U-MTH3, -MTI3 Electronic Trip Units for use withCircuit Breaker Types 140U-M5, -M6, 800 A max.

Available Rating Plugs

Interrupting Rating

800700600500450400

FixedFixedFixedFixedFixedFixed

140U-MRP3-D80140U-MRP3-D70140U-MRP3-D60140U-MRP3-D50140U-MRP3-D45140U-MRP3-D40

1600-64001400-56001200-48001000-4000900-3600800-3200

BreakerType

Adjustable Short Delay Time Typical Trip Unit Nameplate

AmpereRating (In)

Type Short DelayPickup RangeAmperes

Rating PlugCatalogNumber

140U-M5140U-M6

65100

Utilization Category AU imp = 8kV

140U-M5140U-M6

BreakerType

240V (Ue)

Icu Ics65

100

240V 480V 600V

5070

380/415V (U e )

Icu Ics5050

2025

690V (U e)

Icu Ics1013

65100

5065

2535

UL/CSA

RMS Sym. kA, 50/60 Hz

IEC 947-2

RMS Sym. kA, 50/60 Hz

Engaged

Remove

Cat.

In

Rating Plug

Push to Trip

Trip Unit40oC Ambient

Test

5

73

2 8

4 6

Short DelayPickup x In

300

100I

200

TimeMIsec

Curve accuracy applies from –20 °C to +55 °C ambient. For possible continuous amperederating for ambient above 40 °C, consult Rockwell Automation.

For high fault current levels a fixed instantaneous override is provided at 5500A.(Tolerance ±15%).

The end of the curve is determined by the interrupting rating of the circuit breaker.See above tabulation.

For ground fault time/current curves see 40752-678.

NotesElectronic trip units are suitable for functional field testing with test kit.For field testing using primary injection methods, follow NEMA AB4-1991 publications.

Calibration response in short delay pickup range is same for 1, 2 or 3 poles in series.

There is a memory effect that can act to shorten the long delay. The memory effect comesinto play if a current above the long delay pickup value exists for a time and then is clearedby the tripping of a downstream device or the circuit breaker itself. A subsequent overloadwill cause the circuit breaker to trip in shorter time than normal. The amount of time delayreduction is inverse to the amount of time that has elapsed since the previous overload.Approximately five minutes is required between overloads to completely reset the memory.

Time-Current Curves, Continued

Page 60: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

60

Bul.140U/UE

Time-Current Curves for Bulletin 140U-M Electronic Trip Units with Ground Fault Protection

40752-678 (1)SC-6914-98Effective February 1999

Ground Fault PickupSettings(Tolerance ± 10%Except ± 20% on1xIG Setting)

Ix3G

1

Ix4G

Ix2G

Ix1G

2 3 4 5 6 7 8 910 100

GROUND CURRENT-AMPERES

SDNOCES

NI EMIT

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

RUOH 1ETU

NIM 1

SRUOH 2

00061

GROUND CURRENT-IN MULTIPLES OF Ig = 160A

0061

069

0 08

046

084

023

0 61

021108210441

Ix5G

I

500 ms

300 ms

150 ms

Engaged

Remove

Cat.

In

Rating Plug

Push to Trip

Trip Unit40 oC Ambient

Test

500

150300

4

2

1

3 5

Ig = 160A

5

73

2 8

4 6

Short DelayPickup x In

I

Ground FaultPickup x Ig

TimeMIsec

300

100I

200

TimeMIsec

Fixed Short Delay Time

Adjustable Short Delay Time

Circuit Breaker Time/Current Curves (Ground Current) ➀

Technical Data Covers, Electronic Trip Units for use withCircuit Breaker Types 140U-M5, -M6, 800 A max.

For phase time/current curves see:40752-67440752-67540752-67640752-677

Typical Trip Unit Nameplate

Typical Trip Unit Nameplate

NotesCurve accuracy applies from –20 °C to +55 °C ambient. For possible continuous amperederating for ambient above 40 °C, consult Rockwell Automation.

Electronic trip units are suitable for functional field testing with test kit.For field testing using primary injection methods, follow NEMA publication (AB4-1991).

Engaged

Remove

Cat.

In

Rating Plug

Push to Trip

Trip Unit40 o C Ambient

Test

500

150300

4

2

1

3 5

Ig = 160A

5

73

2 8

4 6

Short DelayPickup x In

I

Ground FaultPickup x Ig

TimeMIsec

Ground Fault Protection

Time-Current Curves, Continued

Page 61: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

61

Bul.140U/UE

Time-Current Curves for Bulletin 140U-N Electronic LS Trip Units

40752-690 (1)SC-5375-92AEffective October 1997

X6

X8

X4

X 7

X2

Long Delay➀Minimum TotalClearing Time

Long Delay➀Maximum TotalClearing Time

Standard FixedRating Plug

Short DelayPick UpSettings(Tolerance± 10%)

X5

X3

CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)

.5

.5

SDNOCES NI EMIT

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

RU

OH 1

ET

UN I

M 1S

RU

OH 2

201054321.8.6

1.8.6 000,001

.1

.01

000,01

000,05

000,04

000,03

0 00,0 2

000,002

.001

SDNOCES

CURRENT IN AMPS

CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)

000,06000, 07000,08000,09

.7 .9 6 7 8 9

20105432 6 7 8 9

.05

.03

.02

.005

.003

.002

Fixed InstantaneousOveride➁

InterruptingRatingDeterminesEnd of Curve➂

Typical Trip Unit Nameplate

.7 .9

FrameRatingAmperes(Max.)

A vailable Rating PlugsAmpereRating (I n)

12001000 800 700 600 600, 800, 1000, 1200

FixedFixedFixedFixedFixedAdj.

140U-NRP3-E12140U-NRP3-E10140U-NRP3-D80140U-NRP3-D70140U-NRP3-D60140U-NRPA-E12

2400-96002000-80001600-64001400-56001200-48001200-9600

Type CatalogNumber

Short DelayPickup RangeAmperes

1200

Interrupting Ratings – 50/60 HzRMS Sym. Amperes (kA)

BreakerType

ND, CNDHND, CHNDNDC, CNDC

65100200

65100200

5065

100

253550

5065

100

UL/CSA240V 480V 600V

IEC 947-2220-240V 380-415V

ICS = .25 ICUICW = 15 kA @ .5SUimp = 8kV

I2t Ramp Short Time Delay

Circuit Breaker Time/Current Curves (Phase Current)

Electronic Trip Units are AC only devices that employ microprocessorbased technology that provides true RMS current sensing means for proper correlationwith thermal characteristics of conductors and equipment. They are used with CircuitBreaker Types 140U-N5, -N6, and -N0.

Trip Unit40° C Ambient

Short DelayPickup

5

73

2 8

4 6 TEST

RemoveEngaged

Pushto

Trip

Rating Plug

Cat.–/n–

“Y”x In

NotesCurve accuracy applies from -20 °C to +55°ambient above 40 °C, consult Rockwell Automation

Electronic trip units are suitable for functional field testing with test kit. Forfield testing using primary injection methods, follow NEMA publication AB-4-1991.

For ground fault time-current curves see 40752-692.

There is a memory effect that can act to shorten the long delay. The memory effect comes intoplay if a current above the long delay pickup value exists for a time and then is cleared by thetripping of a downstream device or the circuit breaker itself. A subsequent overloads will causethe circuit breaker to trip in shorter time than normal. The amount of time delay reduction isinverse to the amount of time that has elapsed since the previous overload. Approximately fiveminutes is required between overloads to completely reset the memory

For high fault current levels a fixed instantaneous override is provided at14000A (Tolerance±15%).

The end of the curve is determined by the interrupting rating of the circuit breaker. See abovetabulation.

Not UL/CSA Listed.

Time-Current Curves, Continued

Page 62: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

62

Bul.140U/UE

Time-Current Curves for Bulletin 140U-N LSI Electronic Trip Unit

40752-691 (1)SC-5376-92AEffective October 1997

.1

.01

.001

.05

.03

.02

.005

.003

.002

X6

X 8

X4

X7

X3

X2

Standard FixedRating Plug

200 MS

100MS

I

300 MS

X5

SDNOCES NI EM IT

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

RU

OH 1

ET

UN I

M 1S

RU

OH 2

SDNOCES

CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)

.5

.5 201054321.8.6

1.8.6 000,001

000,01

0 00 ,0 5

000 ,04

000,03

0 00,02

000,002CURRENT IN AMPS

CURRENT IN MULTIPLES OF RATING PLUG AMPERES (In)

0 00 ,06000,07000,08000,09

.7 .9 6 7 8 9

20105432 6 7 8 9

Short DelayPick UpSettings(Tolerance±10%)

Long Delay➀Minimum TotalClearing Time

Long Delay➀Maximum TotalClearing Time

Fixed InstantaneousOveride➁

InterruptingRatingDeterminesEnd of Curve➂

.7 .9

NotesCurve accuracy applies from -20 °C to +55° C ambient. For possible ampere derating forambient above 40 °C, consult Rockwell Automation

Electronic trip units are suitable for functional field testing with test kit. Forfield testing using primary injection methods, follow NEMA publication AB-4-1991.

For ground fault time-current curves see 40752-692.

FrameRatingAmperes(Max.)

A vailable Rating PlugsAmpereRating (I n)

12001000 800 700 600 600, 800, 1000, 1200

FixedFixedFixedFixedFixedAdj.

140U-NRP3-E12140U-NRP3-E10140U-NRP3-D80140U-NRP3-D70140U-NRP3-D60140U-NRPA-E12

2400-96002000-80001600-64001400-56001200-48001200-9600

Type CatalogNumber

Short DelayPickup RangeAmperes

1200

Interrupting Ratings – 50/60 HzRMS Sym. Amperes (kA)

BreakerType

140U-N5140U-N6140U-N0

65100200

65100200

5065

100

253550

5065

100

UL/CSA240V 480V 600V

IEC 947-2220-240V 380-415V

ICS = .25 ICUICW = 15 kA @ .5SUimp = 8kV

Trip Unit40°C Ambient

Short DelayPickup

5

73

2 8

4 6 TEST

RemoveEngaged

Pushto

Trip

Rating Plug

Cat.–/n–

“Y”x In

Typical Trip Unit NameplateAdjustable Short Time Delay

Circuit Breaker Time/Current Curves (Phase Current)

Electronic Trip Units are AC only devices that employ microprocessor-based technology that provides true RMS current sensing means for proper correlationwith thermal characteristics of conductors and equipment. For use with CircuitBreaker Types 140U-N5, -N6, and -N0.

There is a memory effect that can act to shorten the long delay. The memory effect comes intoplay if a current above the long delay pickup value exists for a time and then is cleared by thetripping of a downstream device or the circuit breaker itself. A subsequent overloads will causethe circuit breaker to trip in shorter time than normal. The amount of time delay reduction isinverse to the amount of time that has elapsed since the previous overload. Approximately fiveminutes is required between overloads to completely reset the memory

For high fault current levels a fixed instantaneous override is provided at14000A (Tolerance±15%).

The end of the curve is determined by the interrupting rating of the circuit breaker. See abovetabulation.

Not UL/CSA Listed.

Time-Current Curves, Continued

Page 63: 140u-td001_-en-p

Visit our website: www.ab.com/catalogs

Bulletin 140U/UE

Molded Case Circuit Breakers

63

Bul.140U/UE

Time-Current Curves for Bulletin 140U-N Electronic LSG, LSIG Trip Units with Ground Fault Protection

40752-692 (1)SC-5377-92AEffective October 1997

0005

0004

0003

0002

Trip Unit40°C Ambient

TEST

RemoveEngaged

Pushto

Trip

Cat.–/n–

Ground FaultPickup Time

4

62

1

3 5500

150

1

300

IG=200A Millisec

“Y”

Circuit Breaker Time/Current Curves (Ground Current)

Electronic Trip Units are AC only devices that employ microprocessor-basedtechnology that provides true RMS current sensing means for proper correlation

with thermal characteristics of conductors and equipment. They are used with CircuitBreaker Types 140U-N5, -N6, and N0.

Rating PlugShort DelayPickup

5

73

2 8

4 6

x In x IG

SDNOCES NI EMIT

10,000

100

50

30

20

10

5

3

2

1

.5

.3

.2

.1

.05

.03

.02

.01

.005

.003

.002

.001

1,000

500

300

200

5,000

3,000

2,000

RU

OH 1

ET

UNI

M 1S

RU

OH 2

001

05.

0001

0 08

006

009

007

005

004

003

002

0005

0004

0003

00 02

0001

008

006

009

007

005

004

003

002

CURRENT IN AMPERES

06.07.08.09.

001

05 .06 .07 .08.09 .

CURRENT IN AMPERES

.A 004

.A 002

.A 008

.A 0021

.A 006

.A 0001

Typical Trip Unit Nameplate

Curve accuracy applies from –20 °C to + 55°C ambient.Electronic trip units are suitable for functional field testing with test kit.

For field testing using primary injection methods, follow NEMA publication AB-4-1991.For phase time-current curves see 40752-690, and -691.

Notes

Ground Fault Pick Up Settings(Tolerance ±10% Except±20% on 200 A. Setting)

.15 SEC

.3 SEC

.5 SEC

I

Page 64: 140u-td001_-en-p

Publication 140U-TD001B-EN-P – November 2006 Copyright ©2006 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.