NOT FOR RESIDENTIAL USE This Installation Manual provides the information required to install, install, troubleshoot and maintain FIRE SENTINEL ® RELEASE SYSTEM F S B X-120VAC/24V F S C X-120VAC/24V 12/13 P/N 111995.502195 an FSBX and FSCX

Transcript of 12/13 P/N 111995.502195 FSBX-120VAC/24V FSCX-120VAC/24V · This Installation Manual provides ......

Page 1: 12/13 P/N 111995.502195 FSBX-120VAC/24V FSCX-120VAC/24V · This Installation Manual provides ... FIRE SENTINEL® RELEASE SYSTEM FSBX-120VAC/24V FSCX-120VAC/24V 12/13 P/N 111995.502195

NOT FOR RESIDENTIAL USEThis Installation Manual provides the information required to install, install, troubleshoot and maintain

FIRE SENTINEL® RELEASE SYSTEM

FSBX-120VAC/24VFSCX-120VAC/24V

12/13 P/N 111995.502195

an FSBX and FSCX

Page 2: 12/13 P/N 111995.502195 FSBX-120VAC/24V FSCX-120VAC/24V · This Installation Manual provides ... FIRE SENTINEL® RELEASE SYSTEM FSBX-120VAC/24V FSCX-120VAC/24V 12/13 P/N 111995.502195

www.overheaddoor.com 02/13

THIS PAGE LEFT BLANK

Fire Sentinel® Release System

Page 3: 12/13 P/N 111995.502195 FSBX-120VAC/24V FSCX-120VAC/24V · This Installation Manual provides ... FIRE SENTINEL® RELEASE SYSTEM FSBX-120VAC/24V FSCX-120VAC/24V 12/13 P/N 111995.502195

Table of ContentsHow to use this manual ....................................................................... 2

Safety Information and Instructions................................................... 3

General Information ............................................................................ 4

Mechanical Installation (Mounting)................................................. 5-6

Electrical Connections .....................................................................7-19 High/Low Voltages .................................................................. 7 Smoke Detectors................................................................... 8-9 Supervised Annunciators ...................................................... 10 Remote Test and Trouble Silence ......................................... 10 Relay Outputs/Auxiliary Closed Limit .................................. 11 Control Circuit Sensing/Aux Open Limit ............................. 12 Safety Edge Connections/Wall Button Connections........... 13 Battery/Clock Backup Battery .............................................. 14 System Wiring ...................................................................15-17 Dip Switches/LEDs ................................................................. 18 Trouble Codes ........................................................................ 19

Maintenance ..................................................................................20-21 Specifications ......................................................................... 21

Testing ............................................................................................22-25

Release Device Compatibility Identifier/Replacement Parts ......... 25

Installation Notes ............................................................................... 26

Test Records ........................................................................................ 27

Warranty ............................................................................................. 28

How to use this manualThis Installation Manual provides the information required to install, troubleshoot and maintain an FSBX and FSCX Fire Sentinel® Release System.

This information includes:

• Important defining information related to safety terminology used throughout this manual, as well as safety related instructions which must be followed at all times while doing any steps/tasks/instructions detailed in this manual.

• Step by step installation, set-up and testing instructions for the FSBX and FSCX units.

• Important features and troubleshooting information for typical installation and normal operations that may occur.

• Important warranty and returned goods policy information.

DO NOT ATTEMPT TO INSTALL, REPAIR OR SERVICE THIS RELEASE DEVICE UNLESS YOU ARE A TRAINED SERVICE TECHNICIAN USING PROPER TOOLS AND INSTRUCTIONS.

www.overheaddoor.com 12/13 2Fire Sentinel® Release System

Page 4: 12/13 P/N 111995.502195 FSBX-120VAC/24V FSCX-120VAC/24V · This Installation Manual provides ... FIRE SENTINEL® RELEASE SYSTEM FSBX-120VAC/24V FSCX-120VAC/24V 12/13 P/N 111995.502195

www.overheaddoor.com 12/13 3Fire Sentinel® Release System

Safety Information and Instructions

WARNINGOverhead Doors are large, heavy objects that move with the help of springs under high tension and electricmotors. Since moving objects, springs under tension, and electric motors can cause injuries, your safety and thesafety of others depend on you reading the information in this manual. If you have any questions or do not under-stand the information presented, call your nearest service representative. For the number of your local OverheadDoor distributor, call 800-929-3667, and for Overhead Door Factory Technical Advice, call 800-275-6187.

IMPORTANT

POTENTIAL HAZARD EFFECT PREVENTION

HIGH SPRING TENSION

WARNING

ELECTRICAL SHOCK

READ PRIOR TO ANY DOOR OPERATION

1. Read manual and warnings carefully.

2. Keep the door in good working condition. Periodically lubricate all moving parts of door.

3. If door has a sensing edge, check operations monthly. Make any necessary repairs to keep it functional.

door by disconnecting it from the operator. The Door should open and close freely. If it does not, the door must be taken out of service and a trained service representative must correct the condition causing the malfunction.

5. Keep instructions in a prominent location.

MOVING DOOR

Could result inSerious Injury

or Death

WARNING

WARNING

Could result inSerious Injury

or Death

Could result inSerious Injury

or Death

DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. WARNING CAUTION

The word NOTE is used to indicate important steps to be followed or important considerations.

In this Manual, the words Danger, Warning, and Caution are used to stress important safety information. The word:

indicates an potentially hazardous situation which, if not avoided, could result in death or serious injury.indicates a potentially hazardous situation which, if not avoided, may result in injury or property damage.

Do Not operate unless the doorway is in sight and free of obstructions. Keep people clear of opening while door is moving.Do Not allow children to play with the door operator.Do Not change operator control to momentary contact unless an external reversing means is installed.Do Not operate a door that jams or one that has a broken spring.

Turn off electrical power before opening front cover. When replacing the cover, make sure wires are not pinched or near moving parts.Fire Sentinel® must be electrically grounded.

Do Not try to remove, repair or adjust springs or anything to which door spring parts are fastened, such as, wood block, steel bracket, cable or any other structure or like item.Repairs and adjustments must be made by a trained service representative using proper tools and instructions.

4. Each month, manually operate

Page 5: 12/13 P/N 111995.502195 FSBX-120VAC/24V FSCX-120VAC/24V · This Installation Manual provides ... FIRE SENTINEL® RELEASE SYSTEM FSBX-120VAC/24V FSCX-120VAC/24V 12/13 P/N 111995.502195

General InformationThe Overhead Door Fire Sentinel® Release Systems (FSBX and FSCX) are intended for use on rolling, single-slide and center parting level and inclined track doors. All models are normally energized Fail-Safe Sentinels incorporating an internal battery pack and proprietary control circuitry. All comply with UL864 9th Edition, December 31, 2008 requirements and ULC S527-99. The Devices respond to emergency conditions generated by manual or automatic initiating devices and shall be installed in accordance with NFPA and UL 864 9th Edition Standards effective 12.31.08 and ULC S527-99.

The available FSBX and FSCX features* include exclusive, annual test standard compliance technology, coded test plate diagnostics, selectable ,stuptuo yaler C-mrof ,scitsongaid metsys lortnoc lanretxe ,srotceted ekoms dna esaeler rof troppus yrettab ruoh 42 muminim ,syaled emit

supervised annunciator and limit switch outputs and troubleshooting capabilities. The system incorporates an Annual Internal Clock/Calendar which generates a Test Trouble Signal if the system has not been tested within 365 days per National Fire Code requirements. Motorized and

.)noitcidsiruJ gnivaH ytirohtuA( DJHA/JHA yb deriuqer snoitacificeps etadommocca ot ledom yb desserdda era snoitallatsni launam * Check model label on unit to be installed to verify applicable features and options.

CAUTION: REVIEW ALL INSTALLATION INSTRUCTIONS, PROCEDURES, CAUTIONS AND WARNINGS CONTAINED WITHIN THIS MANUAL PRIOR TO INSTALLING AND/OR SERVICING THIS PRODUCT. AS WITH ALL RELEASING DEVICE SYSTEMS, MAXIMUM FIRE PROTECTION IS PROVIDED WHEN INSTALLED IN ACCORDANCE WITH FACTORY SPECIFICATIONS AND USED WITH FUSE LINK SYSTEMS.

CAUTION: PROPER OPERATION CAN ONLY BE PROVIDED ONCE PROPERLY INSTALLED AND INPUT POWER HAS BEEN APPLIED.

CAUTION: TEST SYSTEM REGULARLY TO ENSURE PROPER OPERATION! (TESTING SHOULD BE DONE AT LEAST MONTHLY.)

For Technical Support, please call 1-800-275-6187

www.overheaddoor.com 02/13 4 Fire Sentinel® Release System

Page 6: 12/13 P/N 111995.502195 FSBX-120VAC/24V FSCX-120VAC/24V · This Installation Manual provides ... FIRE SENTINEL® RELEASE SYSTEM FSBX-120VAC/24V FSCX-120VAC/24V 12/13 P/N 111995.502195

Mechanical InstallationMounting Procedure:

WARNING: TO PREVENT SERIOUS INJURY OR DEATH - DO NOT INSTALL THIS UNIT ON A MOTORIZED DOOR WITHOUT A REVERSING ELECTRIC SAFETY EDGE.

Typical installation configuration may not accurately depict door manufacturer’s recommendations. See door manufacturer’s recommendations for use of this product with the door being installed. All hardware must be supplied by the door manufacturer or installer. Use only hardware approved and recognized by the appropriate testing or listing agencies in conjunction with the installation of this product. Only properly trained technicians, using proper tools and instructions, are to perform installation and testing as described herein. 1) The Release Device may be mounted on a vertical surface or optionally on a horizontal surface as illustrated in Figure 1.

WARNING: TO REDUCE THE RISK OF SERIOUS INJURY OR DEATH AND PREVENT DAMAGE TO THE UNIT, ALL INPUT CONNECTIONS MUST BE MADE WITH POWER SOURCES DISCONNECTED. DO NOT INSTALL THIS UNIT WITHOUT REVIEWING AND UNDERSTANDING ALL WARNINGS AND INSTRUCTIONS CONTAINED HEREIN, AND IN THE DOOR MANUFACTURERS INSTRUCTIONS AND MANUALS.

CAUTION: THESE INSTALLATION PROCEDURES MUST BE FOLLOWED TO ENSURE PERFORMANCE OF THE FSBX OR FSCX TO APPROPRIATE STANDARDS AND CODES.

www.overheaddoor.com 12/13 5

FIGURE 1

continued on next page

Fire Sentinel® Release System

NO LESSTHAN 12”

NO LESSTHAN 12”

Page 7: 12/13 P/N 111995.502195 FSBX-120VAC/24V FSCX-120VAC/24V · This Installation Manual provides ... FIRE SENTINEL® RELEASE SYSTEM FSBX-120VAC/24V FSCX-120VAC/24V 12/13 P/N 111995.502195

Mounting Procedure (continued):

3) Complete hardware installation by connecting fuse links, sash chain, S-hooks and turnbuckles per door manufacturer specifications. Place Armature in Supervisory Retaining Bracket (Figure 2) and attach cable or sash chain to the armature. Remove sash chain slack by adjusting turnbuckle. Do Not exceed 40 lbs maximum pull rating on device. The retaining bracket is meant to hold the armature and cable/sash until input power is supplied. The armature will be removed from the retainer and aligned with the supervised electromagnet when input power is supplied.

www.overheaddoor.com 02/13 6

Supervised Electromagnet

SupervisedRetaining Bracket

Armature inserted into retainer*.

S-hook & sash chain/cableto door

*Supports sash chain/cable until power is supplied

Supervised Electromagnet

Armature removed from retainer and affixed to electromagnet when input power is supplied.

2) The Release Device Enclosure must be mounted with minimum #10 size fastening screws or bolts for securing to structures other than masonry. • Masonry applications shall use 1/4" or greater anchors or studs as required to ensure proper mounting strength. Release device and associated hardware (sash chain [provided and preferred] or 1/16" cable, eyebolts, fuse links and turnbuckles) shall be installed as per door manufacturer recommendations.

FIGURE 2

Fire Sentinel® Release System

Page 8: 12/13 P/N 111995.502195 FSBX-120VAC/24V FSCX-120VAC/24V · This Installation Manual provides ... FIRE SENTINEL® RELEASE SYSTEM FSBX-120VAC/24V FSCX-120VAC/24V 12/13 P/N 111995.502195

Electrical Connections

High Voltage/Low Voltage:Installation of all wiring and connections, including Class 1 and Class 2 circuits, must be performed in accordance with, but not limited to, the latest NFPA, UL and N.E.C. standards and codes. In addition, all installations subject to Canadian standards shall be performed in accordance with the Canadian Electrical Code, Part1, with respect to wiring material type, wiring gauge related to power capacity requirements, circuit length and wiring methods. This unit is designed so that it may be used on automated motorized doors which incorporate appropriate safety features (see options below).

Current UL Recognized Monitored Reversing Devices 1) MillerEdge ME/MT series edge sensors 2) Overhead Door Photocells Kit P/N OPAKPE.S

3) Safe-T-Beams®:

Model OSTB-BX P/N 37221R (OHD)

Figure 3 1) BEFORE BEGINNING, turn off and disconnect power supply sources for the

Control Panel as well as motor where applicable. 2) Verify voltage rating of Control Panel to power source being used. Model voltage is indicated on the side of the unit. 3) C

4) For 120 VAC, connect L1/HOT to terminal 1. Connect L2/NEUT to terminal 3.Connect GROUND to terminal 2.

5) For 24 VDC, connect +24V to terminal 1, COMMON to termminal 3 and GROUND to terminal 2.

onnect power source inputs to TBX (chassis mount) screws 1 and 3. • Screw 2 of any model shall be utilized for earth ground where applicable.

• DO NOT connect battery at this time!

112087.0001

1-(L1) or (AC) or (DC-)2-(Earth GND)3-(L2) or (AC) or (DC+)

www.overheaddoor.com 12/13 7

PowerVoltage

LowVoltage

Fire Sentinel® Release System

WARNING: FAILURE TO DISCONNECT POWER SOURCES COULD RESULT IN ELECTRICAL SHOCK, SEVERE INJURY OR DEATH.

FIGURE 3

TBX

Page 9: 12/13 P/N 111995.502195 FSBX-120VAC/24V FSCX-120VAC/24V · This Installation Manual provides ... FIRE SENTINEL® RELEASE SYSTEM FSBX-120VAC/24V FSCX-120VAC/24V 12/13 P/N 111995.502195

Smoke Detectors:

1) When installing smoke detectors with this unit, refer to NFPA 72 and NFPA 80 and any other applicable codes or regulations for instructions concerning proper placement and detection coverage. See Electrical Connections pages 8, 9, 11 and 12 for information. • End of line devices and supervisory resistors shall be installed for electrical supervision of smoke detectors and annunciators.NOTE: 1. DO NOT interface this unit to 4-wire smoke detectors that do not incorporate electrical supervision! 2. Field and System Wiring shall consist of 22-18 AWG wiring. Use only 350 VAC, 125VDC, 2 Amp, 2 AG Fast Acting fuses. All circuits are not power limited. All End -of-Line devices must be installed adjacent to the last initiating device.Typical wiring: See compatibility list on page 25 and instructions provided with detector for additional information. Field wiring shall consist of 22-18 AWG wire. Do not mix and match 2-wire smoke detectors from different manufacturers.

Normally Open 2-wire Initiating Devices: 1) 2)

Connect wiring from N/O smoke loop to TB-1, screws 1 and 2.

End-of-line supervisory resistor shall be connected at the end-of-line

detector as shown in Figure 4A or 4B base wiring. Two Class B Style A

detectors maximum @ 0.060 Amp/14VDC-28.6VDC maximum.

(continued next page)

WARNING: TO REDUCE THE RISK OF SERIOUS INJURY OR DEATH AND PREVENT DAMAGE TO THE UNIT, ALL FIELD CONNECTIONS MUST BE MADE WITH POWER DISCONNECTED TO ALL COMPONENTS.

Electrical Connections

31/20 moc.rooddaehrevo.www 8

FIGURE 4A FIGURE 4B

Fire Sentinel® Release System

2W-B & 2WT-B

112228.0001 (5) + OUT(4) – OUT(3) – IN(2) + IN(1)

(5) + OUT(4) – OUT(3) – IN(2) + IN(1)

112228.0001

P/N 608964.0005(SLR835BH-2)

112228.0001

Page 10: 12/13 P/N 111995.502195 FSBX-120VAC/24V FSCX-120VAC/24V · This Installation Manual provides ... FIRE SENTINEL® RELEASE SYSTEM FSBX-120VAC/24V FSCX-120VAC/24V 12/13 P/N 111995.502195

Smoke Detectors (continued)

Electrical Connections

Normally Open 4-wire Initiating Devices: erus gnikam ,2 dna 1 swercs ,1-BT ot pool ekoms O/N morf gniriw tcennoC )1

end of line supervisory resistor (112228.0001) is installed as indicated. 2) Auxiliary power (+28.6VDC) for smoke detectors may be obtained from TB1 positions 3 and 4. Observe proper polarity — TB1-3 (+), TB1-4 (-). 3) (2) detector maximum @ 0.075 Amp/28.6VDC maximum. 4) Electrical power supervision in the form of an end-of-line device (EOLR-1) shall be provided on all smoke detectors. See information

6 dna 5 serugiF ,rerutcafunam rotceted morf snoitacificeps dna base wiring.

NOTE: TB1 initiating device loops are supervised and cannot be directly series or parallel connected between release devices or shared with other alarm equipment. Incorrect wiring from unit to unit may cause damage to FIRE SENTINEL®..

www.overheaddoor.com 12/13 9

FIGURE 5 FIGURE 6

112228.0001 112228.0001

(5) COM(4) N.O.(3) - IN/OUT(2) + OUT + IN(1)

(+)

(- )

(+)

(- )

(+)

(- )

(5) COM(4) N.O.(3) - IN/OUT(2) + OUT + IN(1)

EOLR-1

Fire Sentinel® Release System

4W-B & 4WT-B

1

2

SUPERVISORY RESISTOR *

COM

N/O

FIRE ALARM PANEL

(-)

(+)

Alarm Relay Module Installation

* A supervisory resistor must be installed at the Relay Module.

ALARM RELAY MODULE

112228.0001

Page 11: 12/13 P/N 111995.502195 FSBX-120VAC/24V FSCX-120VAC/24V · This Installation Manual provides ... FIRE SENTINEL® RELEASE SYSTEM FSBX-120VAC/24V FSCX-120VAC/24V 12/13 P/N 111995.502195

Supervised Annunciators:

Remote Test and Trouble Plate:

• (+24VDC output), connect annunciator (optional) observing polarity to TB1-10 (+) and TB1-11 (-).

• Install resistor as illustrated. Figure 7. • DO NOT connect a speaker to this output.

WARNING: TO REDUCE THE RISK OF SERIOUS INJURY OR DEATH AND PREVENT DAMAGE TO THE UNIT, ALL FIELD CONNECTIONS MUST BE MADE WITH POWER DISCONNECTED TO ALL COMPONENTS.

Electrical Connections

The Remote Test and Trouble Plate provides convenient test and trouble silencing capabilities. The Trouble Silence function allows a user to temporarily silence the Trouble Sounder with a keyed function. The plate includes an LED Trouble Indicator, which illuminates indicating that trouble still exists. If the trouble condition is not corrected after 24 hours the trouble sounder will commence again and a manual intervention for reset is required. • Connect wiring from remote test plate to TB1 positions 15, 16, 17 and 18. • Observe wiring sequence as indicated in Figure 8. • Trouble Code table located on page 19.

DC + DC -

112228.0001

www.overheaddoor.com 02/13 10

FIGURE 7

FIGURE 8

Fire Sentinel® Release System

ANNUNCIATOR

REMOTE TEST PLATE

Com

mon

Test

Rese

t

Rem

ote

Trou

ble

(BLK

)

(WH

T)

(GRN

)

(RED

)

Page 12: 12/13 P/N 111995.502195 FSBX-120VAC/24V FSCX-120VAC/24V · This Installation Manual provides ... FIRE SENTINEL® RELEASE SYSTEM FSBX-120VAC/24V FSCX-120VAC/24V 12/13 P/N 111995.502195

Relay Outputs: Two separate

NOTE: Relay contacts 2A @ 28 VDC resistive, common mode

SPDT dry contact relay outputs (resistive) are provided for switching or signaling of supplementary devices. A non-delayed output(relay toggles on alarm- beginning of time delay) is provided on TB1-12 (C), 13 (N/C), and 14 (N/O) and a Trouble Relay output for supplementary trouble annunciating devices is provided on TB1-19 (C), 20 (N/C), and 21 (N/O). The Trouble Relay toggles

indicating a fault in any of the supervised connections including initiating devices, signalling devices and supervised

option modules. See figure 9.

AOM Auxiliary Closed Limit:Required for FSCX – optional for FSBX Connect a normally open dry

to position TB-1, 8 and 9. See figure 10. FSBX is not intended for use with external automation. Wiring connections are to be made within 20 feet (6.1 m) and are to be enclosed in conduit.

Electrical Connections

www.overheaddoor.com 12/13 11

Alarm Relay TSystem rouble Relay

10 11 12 13 14 15 16 17 18 19 20 21FIGURE 9

FIGURE 10

112228.0001

112228.0001

112228.0001

112228.0001

112228.0001

112228.0001

Remote TestReset Station

Com

mon

Annunciator

AUX

Ope

n Li

mit

Switc

h

AUX

Clos

e Li

mit

Switc

h

AUX

Com

mon

Ann

unci

ator

+

Ann

unci

ator

AuxiliaryOpenLimit

AuxiliaryClosed

Limit

Test

Rese

t

Rem

ote

Trou

ble

EOLR-1

Smoke Power TB1-3 (+) and TB1-4 (–)

Alarm Relay System TroubleRelay

Fire Sentinel® Release System

(On circuit board.) (On circuit board.)

contact (Contacts close when door is at down limit)

AOMRefer to Operator manufacturer’s wiring instructions for proper

Page 13: 12/13 P/N 111995.502195 FSBX-120VAC/24V FSCX-120VAC/24V · This Installation Manual provides ... FIRE SENTINEL® RELEASE SYSTEM FSBX-120VAC/24V FSCX-120VAC/24V 12/13 P/N 111995.502195

Control Circuit Sensing: FSCX ONLY This option is used to detect the presence of control voltage on motor driven doors for automated fire alarm closure. When control circuit voltage is not present (24V-30V AC or DC) the FSCX will sound a trouble, indicating the loss of door operator control voltage. In alarm, if control voltage is not present FSCX will mechanically release the door after the factory set 10 second delay (or longer optional delay). Connect control

circuit voltage to position 30 (–) and 31(+).

Electrical Connections

www.overheaddoor.com 02/13 12

Auxiliary Open Limit: FSCX ONLY

• Connect a normally open dry contact (Contacts close when door is at up limit) .8 dna 7 ,1-BT snoitisop ot

WARNING: TO REDUCE THE RISK OF SERIOUS INJURY OR DEATH AND PREVENT DAMAGE TO THE UNIT, ALL FIELD CONNECTIONS MUST BE MADE WITH POWER DISCONNECTED TO ALL COMPONENTS.

Control Sense (+)

Control Sense Out (–)

Monitored Operator Safety Edge CommonMonitored Operator Safety Edge InCloseOpen

Stop

3-Button Common

Open

Close

Stop

3-Button Common Station

Monitored Safety Edge

Remote TestReset Station

Annunciator

AUX

Ope

n Li

mit

Switc

h

AUX

Clos

e Li

mit

Switc

h

AUX

Com

mon

Ann

unci

ator

+

Ann

unci

ator

EOLR-1

Smoke Power TB1-3 (+) and TB1-4 (–)

Alarm Relay System Trouble Relay

FIGURE 11

Fire Sentinel® Release System

(On circuit board.) (On circuit board.)

Com

mon

Test

Rese

t

Rem

ote

Trou

ble

ELECTRIC OPERATOR

AuxiliaryOpenLimit

AuxiliaryClosed

Limit

AOM

112228.0001

112228.0001

112228.0001

112228 0001

112228 000

112228 0001

BLUE

YELLOW

Page 14: 12/13 P/N 111995.502195 FSBX-120VAC/24V FSCX-120VAC/24V · This Installation Manual provides ... FIRE SENTINEL® RELEASE SYSTEM FSBX-120VAC/24V FSCX-120VAC/24V 12/13 P/N 111995.502195

Safety Edge Connection: FSCX ONLY— Figure 11 • Connect safety edge across the operator’s “safety edge” sense terminal

and the FSCX “Safety Edge” TB-1, 26 and 27.

• Connect operator’s “open” terminal to FSCX “open” TB-1, no. 24.

• C

WALL BUTTON CONNECTION FSCX ONLY

onnect operator’s “close” terminal to FSCX “close” TB-1, no. 25.

• Connect operator’s “common” terminal to FSCX “operator common” TB-1, no. 22.

• Connect operator’s “stop” terminal to the “stop” terminal on the 3-button control.

• Connect operator’s “open” terminal to the “open” terminal on the 3-button control.

• C• Connect 3 button common to TB-1, no. 23.

onnect operator’s “close” terminal to the “close” terminal on the 3-button control.

Electrical Connections

www.overheaddoor.com 02/13 13Fire Sentinel® Release System

Control Sense (+)

Control Sense (–)

Monitored Operator Safety Edge CommonMonitored Operator Safety Edge InCloseOpen

3-button Common

Operator Common

Open

Close

Stop

3-Button Common Station

MONITOREDSAFETY EDGE

MONITORED EDGEINTERFACE MODULE

Remote TestReset Station

Annunciator

AUX

Ope

n Li

mit

Switc

h

AUX

Clos

e Li

mit

Switc

h

AUX

Com

mon

Ann

unci

ator

+

Ann

unci

ator

EOLR-1

Smoke Power TB1-3 (+) and TB1-4 (–)

Alarm Relay System Trouble Relay

FIGURE 11 (repeated)

ELECTRICOPERATOR

(On circuit board.) (On circuit board.)

Com

mon

Test

Rese

t

Rem

ote

Trou

ble

AuxiliaryOpenLimit

AuxiliaryClosed

Limit

AOM

no.

112228.0001

112228.0001

112228.0001

112228 000

112228 0001

112228 0001

BLUE

YELLOW

Page 15: 12/13 P/N 111995.502195 FSBX-120VAC/24V FSCX-120VAC/24V · This Installation Manual provides ... FIRE SENTINEL® RELEASE SYSTEM FSBX-120VAC/24V FSCX-120VAC/24V 12/13 P/N 111995.502195

Electrical ConnectionsBattery: Must be connected at this time,

s*eirettab elbaegrahcer-non eht tcennoC )2(112087.0001) to the

FSBX or FSCX observing Figure 12 for proper mounting

and connection.

NOTE: The transformer is used only in 120VAC models

* Batteries must be replaced with P/N 112087.0001. Standard AA batteries will not work and may cause damage to the unit and will void the factory warranty.

and

.sledom CDV42 no dedivorp ton si

www.overheaddoor.com 02/13 14

Replaceable fuses 2A @ 350VAC,125VDC, 2AG Fast Acting

Power

LowVoltage

Voltage112087.0001

1-(L1) or (AC) or (DC-)2-(Earth GND)3-(L2) or (AC) or (DC+)

FIGURE 12

Fire Sentinel® Release System

Red wire

SYSTEMBACKUP

BATTERIES

to Red terminal

Black wire to Black terminal

TBX

1) Install System Backup Batteries.• Connect + lead of left battery to – lead of right battery using jumper wire provided.• Connect black wire to black terminal on left battery.• Connect red wire to red terminal on right battery.

Page 16: 12/13 P/N 111995.502195 FSBX-120VAC/24V FSCX-120VAC/24V · This Installation Manual provides ... FIRE SENTINEL® RELEASE SYSTEM FSBX-120VAC/24V FSCX-120VAC/24V 12/13 P/N 111995.502195

Electrical ConnectionsReplaceable fuses 2A @ 350VAC,125VDC, 2AG Fast Acting

REMOTE TEST PLATE

2JQ2-RFUSE

PARTS KIT

BA

T+

BA

T-

AC

-2A

C-1

www.overheaddoor.com 12/13 15

FIGURE 13

Fire Sentinel® Release System

RESISTOR

112228.0001

TROUBLE

NORMAL

TEST RESET

Page 17: 12/13 P/N 111995.502195 FSBX-120VAC/24V FSCX-120VAC/24V · This Installation Manual provides ... FIRE SENTINEL® RELEASE SYSTEM FSBX-120VAC/24V FSCX-120VAC/24V 12/13 P/N 111995.502195

(-) (+)

)+( )-( (-)(+)

(-) (+)

(-)

(+)

TERM-2

DOWN LIMIT PROXIMITY SWITCH

OPTIONAL EQUIPMENT NOT INCLUDED WITH THE RELEASE DEVICE.

TERM

-7TE

RM-8

TERM

-9

TERM

-21

TERM

-20

TERM

-19

TERM

-14

TERM

-13

TERM

-12

120V

AC

112228.0001

112228.0001

112228.0001

AD

WH

T

BLK

GRN

RED

WH

TG

RN

WHITE

BLK

TERM

-11

TERM

-10

TERM

-18

TERM

-17

TERM

-16

TERM

-15

TERM-4TERM-3TERM-2TERM-1

TWO-WIREINITIATING DEVICE

FOUR-WIREINITIATING DEVICE

TERM-1SYSTEMTROUBLERELAY

ALARMRELAY

FIRE SENTINEL®MODEL FSBX120VAC

ON

F I R E

Remote Test Reset Station

1 2

3 4

5 6

7 8

—OR—

Field and System Wiring shall consist of 22-18 AWG wiring. Use only 350 VAC, 125VDC, 2 Amp, 2 AG Fast Acting fuses. All circuits are not power limited. SYSTEM WIRING NOTES: 1. Supervised, 35 Ohm maximum line impedance. 11228.0001 end of line resistor required for supervision. 2. Not supervised, 75 Ohm maximum line impedance. 3. 4 Class B Style A detectors maximum 112228.0001 end of line resistor required for supervision. 4. 2 Class B Style W notification appliances maximum @ 0.16 Amp/28.6VDC maximum Supervised 20 Ohm maximum line impedance. Place 112228.0001 at positions 10 and 11 if appliances are not used. 5. Form C dry contacts, relay contacts 2A @ 28.6VDC resistive, common mode. 6. End of line relay (EOLR-1) shall be installed with 4-wire detectors. Do Not loop wire under terminals for connections. 7. Smoke power TB1-3 (+) and TB1-4 (–). Supervised, see items 2, 6 above. 8. (2) Class B Style A detectors maximum @ 0.075 Amp/28.6VDC maximum Supervised, see item 1 above. 9. All wiring connections are

10. Replace batteries every 2 years.

to be made within 20 feet (6.1 m), enclosed in conduit and in the same room. GROUND FAULT: 20 kOhms maximum from one conductor to earth ground.

WARNING: TO REDUCE THE RISK OF SERIOUS INJURY OR DEATH AND PREVENT DAMAGE TO THE UNIT, ALL INPUT CONNECTIONS MUST BE MADE WITH THE UNIT POWERED DOWN. ALL AUXILIARY LIMIT SWITCHES MUST BE DRY CONTACTS.

Electrical Connections

FIGURE 13A

All information on this page applies to both Figure 13A and 14.

www.overheaddoor.com 12/13 16Fire Sentinel® Release System

A SOUNDER/STROBE **

**

*

*

ORANGE

3 1

Page 18: 12/13 P/N 111995.502195 FSBX-120VAC/24V FSCX-120VAC/24V · This Installation Manual provides ... FIRE SENTINEL® RELEASE SYSTEM FSBX-120VAC/24V FSCX-120VAC/24V 12/13 P/N 111995.502195

(–) (+)

(–)(+) )+( )–(

(–) (+)

(–)

(–)(+)

(+)

(+)TERM

-2

TERM-7TERM-8TERM-9TERM-21

TERM-20TERM-19

TERM-14TERM-13TERM-12

120VAC

112228.0001

ADASOUNDER/STROBE

BLUE

YELLOW

BLUE

YELLOW

PURPLE

208V230V

SINGLE PHASE

THREE PHASE

GND GND

GND GND

NEUTRAL

LINE 3LINE 2LINE 1

LINE(HOT)

L NE 2

L NE 1

SPLICE

SPLICE

SPLICE

YELLOWORANGERED

OPEN

CLOSE

STOP

MONITOREDEDGE

INTERFACEMODULE

SENSINGEDGE

RED

WHITEGREEN

BLACK

TERM-11

TERM-10

1

3

TERM-18TERM-17TERM-16TERM-15

TERM-22

AUX OUTPUTBOARD

TERM-23TERM-24

115V

TERM-25

TERM-4

TERM-3

TERM-2

TERM-1

TWO-WIREINITIATING DEVICEFOUR-WIRE

INITIATING DEVICE

TERM-1

UP1

DN1**

OPENCLOSE

SystemTroubleRelay

RMX® / RSX® / RHX® / CDX™OPERATOR

ON

FIRE

Remote TestReset Station

1 2 3 4 5 6 7 8

L2L1

L3L2L1

NL1

STOP

GND1-BTNODC STBODC STB

NO SAFETYNO SAFETYEXT INTLKEXT INTLK

AlarmRelay

ExternalRadio

—OR—

GREENPURPLEPINKBLACK

GREYWHITEORANGE

TERM-30TERM-31

BLA

WHITE(N)

L1 CKGREEN

FIRE SENTINEL®MODEL

FSCX120V

TERM-27TERM-26

**

*

*

**

*

TERMINAL LEGEND AND HOOKUPS: 1. Smoke Alarm Return 2. Smoke Alarm Power 3. Smoke Alarm Power 4. Power Return (System Ground)

5. N/A 6. N/A 7. Auxiliary Open Limit Switch (must be dry switch contact) 8. Limit Switch Common 9. Auxiliary Close Limit Switch (must be dry switch contact)

10. Annunciator Output (+) 11. Annunciator Return (–) 12. Alarm Relay Common (dry contact) 13. Alarm Relay Normally Closed (dry contact) 14. Alarm Relay Normally Open (dry contact)

15. Remote Common (System Ground) 16. Remote Test (must be dry switch contact) 17. Remote Reset (must be dry switch contact) 18. Remote Trouble Indicator (red LED anode) 19. Trouble Relay Common (dry contact) 20. Trouble Relay Normally Closed (dry contact) 21. Trouble Relay Normally Open (dry contact)

RELAY BOARD TERMINALS FROM LEFT: 22. 3-button Common 23. Stop 24. Open 25. Close 26. Analog Operator Safety Edge 27. Analog Operator Safety Edge Common 28. Digital Operator Safety Edge 29. Digital Operator Safety Edge 30. Control Sense Out 31. Control Sense In

Electrical ConnectionsFIGURE 14All information on this page applies to Figures 13A and 14.

www.overheaddoor.com 12/13 17Fire Sentinel® Release System

* ** OPTIONAL EQUIPMENT N DOWN LIMIT—USE PROXIMITY SWITCHOT INC LUDED WITH THE RELEASE DEV IC E. FSBX.

*

112228.0001

112228.0001

(–)BROWNTAN

Page 19: 12/13 P/N 111995.502195 FSBX-120VAC/24V FSCX-120VAC/24V · This Installation Manual provides ... FIRE SENTINEL® RELEASE SYSTEM FSBX-120VAC/24V FSCX-120VAC/24V 12/13 P/N 111995.502195

Electrical ConnectionsDip Switches:

LED Indications when lit:

.51 erugiF ot refeR

ON1 2 3 4 5 6 7 8

FIGURE 15

www.overheaddoor.com 02/13 18

1. Delay Alarm Time (OFF: 10s, ON: 20s.) 2. Delay Alarm Time Extended (OFF: as set by 1, ON: 60s.)

3. Safety Timer (OFF: 2 minutes, ON: 4 minutes.)

4. Annunciator Down Limit (if set ON: notification appliances

will shut off when automated door reaches down limit in

tests only.)

5. Auto Open on Reset (if set ON: automated doors will open

when the alarm is reset in tests only.)

6. Relay Board Present (OFF: Board not present ON: Board

present [use to enable/disable relay board functions.])

7. Stop on Obstruction (ON: in alarm, automated doors will

stop at the obstruction on the third closing cycle.)

(See

Test Procedures, page 24) 8. Alarm on Power Loss (ON: loss of external power will trigger

an alarm sequence.)

Three LEDs in the upper left corner of the board are:

Green: AC Present - LED 9

Yellow: Battery OK - LED 10

Yellow: Trouble - LED 11

Next to the JP16 header connector:

Yellow: Magnet open/not present - LED 2

Green: Magnet on- LED19

Upper Right:

Green: 5V Power on - LED 23

LEDs along the Terminal Block—left to right:

Yellow: Smoke detector loop open - LED 22

Red: Smoke detector alarm or short - LED 21

Green: Open Limit - LED 6

Green: Down Limit - LED 4

Yellow: Alarm annunciator loop open - LED 7

Red: Alarm annunciator loop short - LED 8

LED11

LED10

LED9

RESET

TESTJP9 JP8 JP4 JP6 JP10 JP2

JP26

JP3

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21

LED8

LED7

LED20

LED4

LED6

LED21

LED22

LED19

LED23

LED2

JP16

JP21

JP23

16

JP19

JP25

S6

S5

S4ON

1

Fire Sentinel® Release System

NOTE: Relay Board LEDs are not shown.1 2 3 4 5 6 7 8

Page 20: 12/13 P/N 111995.502195 FSBX-120VAC/24V FSCX-120VAC/24V · This Installation Manual provides ... FIRE SENTINEL® RELEASE SYSTEM FSBX-120VAC/24V FSCX-120VAC/24V 12/13 P/N 111995.502195

www.overheaddoor.com 12/13 19Fire Sentinel® Release System

Electrical Connections (Trouble Code Chart)The Trouble LED on the Main Board will flash out these codes in sequence. Each trouble present is counted out in sequence separated by a distinct pause.After all uncleared troubles have been counted out, the sequence repeats.

(1) FLASH

TROUBLE LED (YELLOW)

TROUBLE CODE

REQUIRED ACTION

MAGNET FAULT

(3) FLASHES

(5) FLASHES

(6) FLASHES

(7) FLASHES

(8) FLASHES

(9) FLASHES

(10) FLASHES

(11) FLASHES

(12) FLASHES

(15) FLASHES

(16) FLASHES

(17) FLASHES

(18) FLASHES

(22) FLASHES

(29) FLASHES

GROUND FAULT

BATTERY NOT CHARGING

CHARGER VOLTAGE FAIL

BATTERY LOW

EXTERNAL POWER LOSS

RETAINER SWITCH

ANNUNCIATOR CIRCUIT OPEN

ANNUNCIATOR CIRCUIT SHORT

ALARM LOOP OPEN

TEST REQUIRED

REAL-TIME CLOCK ERROR

STUCK RESET

CONTROL SENSING VOLTAGE NOT PRESENT

NON-RECHARGEABLE BATTERY RUN TIME EXCEEDED

SAFETY EDGE FAULT

Check electromagnet cable and terminal JP3

Check all low voltage �eld wiring especially insulation

Check SLA battery cables

Check AC voltage and wiring

Check AC voltage and wiring; Check fuse F3; replace with known good battery

Check AC voltage and wiring; Check fuse F2

Remove armature from bracket and place on magnet

Check annunciator (Horn/Strobe) wiring; Verify EOL resistor is installed

Check annunciator (Horn/Strobe) wiring

Check smoke alarm wiring and smoke alarm EOL (resistor/relay termination)

Perform drop or close test

Replace non-rechargeable battery and perform drop or close test

Check reset button and keyswitch; Check keyswitch wiring

Check terminals 30, 31 and pigtail - Check operator has power

Replace non-rechargeable battery

Check safety edge and safety edge wiring

Page 21: 12/13 P/N 111995.502195 FSBX-120VAC/24V FSCX-120VAC/24V · This Installation Manual provides ... FIRE SENTINEL® RELEASE SYSTEM FSBX-120VAC/24V FSCX-120VAC/24V 12/13 P/N 111995.502195

WARNING: TO PREVENT POSSIBLE SERIOUS INJURY OR DEATH DURING MAINTENANCE: • PLACE DOOR IN FULLY CLOSED POSITION • DISCONNECT ANY AND ALL POWER FROM SYSTEM AND SYSTEM COMPONENTS INCLUDING MOTORS WHERE APPLICABLE

Maintenance

System batteries must be changed a minimum of every two years or upon generation of system battery trouble. Included is a pair of sealed lead acid

fo riap a sa llew sa ,pukcab yrettab metsys rof dezilitu seirettab elbaegrahceron-board lithium battery used for the System Annual Test Clock. All batteriesshould

be replaced simultaneously by a properly trained technician using proper

tools and instructions. For proper replacement parts, see list on page 25.

Batteries should be disposed of in accordance with Federal, State and Local Regulations.

System fuses are all 2A @ 350V, 125VDC, 2AG Fast Acting. Reference pages 14, 15 (Figures 12 and 13).

www.overheaddoor.com 02/13 20Fire Sentinel® Release System

Page 22: 12/13 P/N 111995.502195 FSBX-120VAC/24V FSCX-120VAC/24V · This Installation Manual provides ... FIRE SENTINEL® RELEASE SYSTEM FSBX-120VAC/24V FSCX-120VAC/24V 12/13 P/N 111995.502195

ELECTRICALOPERATING VOLTAGES: CURRENT REQUIREMENTS: 24 VDC .....................................................SUPERVISORY (non-alarm) .385 A/Alarm .610 A maximum. 120 VAC................................................. 0.430 A maximum.INPUT POWER SUPERVISED: NOTE: 1. Initial power up inrush current shall not exceed 3 times rated current on any model.

DOOR POSITION INPUTS: MAXIMUM LOOP RESISTANCE: 35 Ohms.

MAXIMUM CURRENT: Not to exceed .002 A maximum.

MAXIMUM VOLTAGE: 5VDC.FORM C OUTPUT (MAXIMUM CONTACT RATING):

2 A @ 28VDC resistive, common mode.SMOKE DETECTOR POWER:

18.6–28.8VDC @ .021 A STANDBY, .075 A ALARM. (See pages 8 & 9.) FUSES: ALL FUSES: 2A @ 350V, 125VDC, 2AG, Fast Acting Type (See figure 12 & 13).

NOTIFICATION APPLIANCES: 28.8VDC @ .160 A ALARM (See figures 7). BATTERY BACKUP: 12VDC, 5AH, QTY=2, 24hr. supervised circuit. GROUND FAULT: 20 kOhms maximum from one conductor to earth ground.

MECHANICALLOAD RATING: SUPPORT AND RELEASE–40lb. maximum.PHYSICAL DIMENSIONS: 10.250" x 9.750" x 4.750" (H x W x D) I.D.WEIGHT: 19 lbs. w/batteries.

Electrical and Mechanical SpecificationsMODEL FSBX MODEL FSCX

ELECTRICALOPERATING VOLTAGES: CURRENT REQUIREMENTS: 24 VDC .....................................................SUPERVISORY (non-alarm) .385 A/Alarm .610 A maximum. 120 VAC ............................................... 0.430 A maximum.INPUT POWER SUPERVISED: NOTE: 1. Initial power up inrush current shall not exceed 3 times rated current on any model.

CONTROL SENSE-ALL MODELS: Input voltage: 24VAC / DC typical Input Current—Not to exceed .005 A.DOOR POSITION INPUTS: MAXIMUM LOOP RESISTANCE: 35 Ohms. MAXIMUM CURRENT: Not to exceed .002 A maximum. MAXIMUM VOLTAGE: 5VDC.FORM C OUTPUT (MAXIMUM CONTACT RATING): 2 A @ 28VDC resistive, common mode.SMOKE DETECTOR POWER: 18.6–28.8VDC @ .021 A STANDBY, .075 A ALARM. (See pages 8 & 9.) FUSES: ALL FUSES: 2A @ 350V, 125VDC, 2AG, Fast Acting Type (See figure 12 & 13).NOTIFICATION APPLIANCES: 28.8VDC @ .160 A ALARM (See figures 7).BATTERY BACKUP: 12VDC, 5AH, QTY=2, 24hr. supervised circuit. GROUND FAULT: 20 kOhms maximum from one conductor to earth ground.REMOTE TEST/RESET STATION: SPDT, 1A @ 125VAC. Position 1-test, Position 2-normal, Position 3-trouble/alarm reset. Indicators—Red LED - trouble indication (see Trouble Codes pg. 19) On the reset of a trouble, the sounder will turn off, but the LED will remain lighted until the troubles are fixed and a reset is performed. The sounder will reactivate within 24 hours if the trouble is not cleared.

REMOTE TEST/RESET STATION: SPDT, 1A @ 125VAC. Position 1-test, Position 2-normal, Position 3-trouble/alarm reset. Indicators—Red LED - trouble indication (see Trouble Codes pg. 19) On the reset of a trouble, the sounder will turn off, but the LED will remain lighted until the troubles are fixed and a reset is performed. The sounder will reactivate within 24 hours if the trouble is not cleared.

MECHANICALLOAD RATING: SUPPORT AND RELEASE: 40lbs. maximum.PHYSICAL DIMENSIONS: 10.250" x 9.750" x 4.750" (H x W x D) I.D. WEIGHT: 20 lbs. with batteries.

www.overheaddoor.com 12/13 21Fire Sentinel® Release System

Page 23: 12/13 P/N 111995.502195 FSBX-120VAC/24V FSCX-120VAC/24V · This Installation Manual provides ... FIRE SENTINEL® RELEASE SYSTEM FSBX-120VAC/24V FSCX-120VAC/24V 12/13 P/N 111995.502195

NOTE: TESTING MUST BE PERFORMED AND WITNESSED FOR NORMAL OPERATION AFTER INSTALLATION. A “Test Required” trouble will occur until a complete test cycle is performed. This is a normal condition and part of the Internal Annual Test Clock/Calendar. The annual test is a National Fire Code requirement. More frequent tests may be required by the local Authority Having Jurisdiction (AHJ). Refer to test procedures contained herein, as well as other testing programs recommended by door manufacturer.

Test Procedures

The following tests as described using the Remote Test Plate (RTP) may alternatively be performed by the chassis mounted push button test and reset switches. It is recommended that test and reset functions be performed utilizing the RTP provided with the unit.Test steps 1-5 verify a mechanical release to a non-motorized door or a motorized door with external power normal. Test steps 6-10 verify a mechanical release under battery power with external power loss. 1) Turn ON power to the FSBX or FSCX and turn OFF power to the motor operator (if applicable). • A "Test Required" trouble and "Retainer Switch" trouble will be generated at power up. This is normal.

Mechanical Door Drop Test for Models BX and CX:

WARNING: TO PREVENT POSSIBLE SERIOUS INJURY OR DEATH: • WHILE PERFORMING THE MECHANICAL OR ELECTRICAL DOOR DROP TEST, KEEP YOURSELF AND ANY OTHERS CLEAR OF THE DOOR AND ANY MOVING PARTS.

• CLEAR ANY OBJECTS OR PEOPLE FROM DOOR PATH.

• PROHIBIT TRAFFIC THROUGH THE DOOR OPENING WHILE TESTING.

• Turn RTP to RESET, then NORMAL, to silence the troubles. • Remove the Armature from the Retaining Bracket (Figure 2, page 6) and align it with the Supervised Electromagnet. WARNING: CLEAR THE DOOR OPENING BEFORE BEGINNING STEP 2. 2) Turn RTP to the TEST position. The annunciator will sound indicating a door closure is about to occur and after a 10 second factory set alarm verification delay (or longer optional delay) the device will mechanically release the door. 3) Turn RTP to RESET position and then back to the NORMAL position. This test verifies a mechanical release for a non-motorized door or in absence of power to the motor for externally automated doors. 4) Mechanically reset the door and reattach Armature to the Supervised Magnet. • Make sure the door is fully raised. 5) DO NOT restore power to the motor. WARNING: CLEAR THE DOOR OPENING BEFORE BEGINNING STEP 6. 6) Turn OFF power to the FSBX or FSCX. 7) The power LED (red) will turn off and "External Power Loss" and "Battery Not Charging" troubles will be generated in approximately 10 seconds. This is a normal condition. • Turn the RTP to the TEST position. The annunciator will sound indicating a door closure is about to occur and after a 10 second factory set alarm verification delay (or longer optional delay) the device will mechanically release the door. 8) Turn the RTP to the RESET position and then back to NORMAL. This test verifies a mechanical release in absence of power to the FSBX or FSCX and motor (if applicable). 9) Mechanically reset the door and reattach the armature to the release magnet. 10) Restore power to the Release System and Motor operator and raise the door

to the fully open position.

• Turn the RTP to RESET and back to NORMAL to clear trouble indicator on the RTP.

www.overheaddoor.com 02/13 22Fire Sentinel® Release System

Page 24: 12/13 P/N 111995.502195 FSBX-120VAC/24V FSCX-120VAC/24V · This Installation Manual provides ... FIRE SENTINEL® RELEASE SYSTEM FSBX-120VAC/24V FSCX-120VAC/24V 12/13 P/N 111995.502195

WARNING: TO PREVENT POSSIBLE SERIOUS INJURY OR DEATH: • WHILE PERFORMING THE MECHANICAL OR ELECTRICAL DOOR DROP TEST, KEEP YOURSELF AND ANY OTHERS CLEAR OF THE DOOR AND ANY MOVING PARTS. • CLEAR ANY OBJECTS OR PEOPLE FROM DOOR PATH.• PROHIBIT TRAFFIC THROUGH THE DOOR OPENING WHILE TESTING.

Test ProceduresAutomatic Door Closure Tests (Motorized Doors/FSCX only):

THREE CYCLE OBSTRUCTION TEST with release on obstruction

1) Make sure the DIP switch at position 6 (relay board PRESENT)

is set in the ON position on the Main Circuit Board. • Make sure the door is open and there are no obstructions in its path.

1) Make sure the DIP switch at position 6 (relay board PRESENT) is set in the ON position on the Main Circuit Board. • Place a chair or other suitable obstruction in the normal path of the door.

WARNING: KEEP THE DOOR OPENING CLEAR OF ALL PERSONNEL.THIS TEST SHOULD BE PERFORMED USING THE TEST AND RESET FUNCTIONS OF THE REMOTE TEST STATION. (It may be performed using the test and reset switches of the device enclosure.)

WARNING: THIS EQUIPMENT IS DESIGNED TO BE USED IN CONJUNCTION WITH AN OPERATOR INCORPORATING A MONITORED REVERSING FEATURE SAFETY EDGE. DO NOT

EXECUTE THIS TEST WITHOUT A SAFETY EDGE INSTALLED!

2) Turn the key switch to TEST and leave it there. The annunciator will turn on indicating that a door closure is about to occur. After the factory set 10 second delay (or longer optional delay), the device will turn on the motor initiating a closure.

2) hctiws yek nruT

3) Allow the door to fully close.4) Reset the FSCX by turning the key switch to the RESET position, then back to NORMAL.

5) Open the door.back to NORMAL.

no nrut lliw rotaicnunna ehT ereht ti evael dna TSET ot

indicating that a door closure is about to occur. After the factory set 10 second delay (or

.erusolc a gnitaitini rotom eht no nrut lliw ecived eht ,)yaled lanoitpo regnol

Upon contact with the obstruction, the safety edge will reverse the motor and raise the door to the fully open position. The FSCX will make three attempts to close the door with the motor, after which the FSCX will release the door through the drop release mechanism. STAND CLEAR OF ANY PATH THE OBSTRUCTION MIGHT TAKE AFTER BEING STRUCK BY THE DROPPED DOOR. The door will drop onto the obstruction and will fully close once the obstruction is removed. The annunciator will continue to sound until the alarm condition is cleared. 3) Reset

4) Reset the door sash chain and armature. *N-O REV INPUT will not allow “STOP ON OBSTRUCTION.”

the FSCX by turning the key switch to the RESET position and then back to NORMAL.

THREE CYCLE OBSTRUCTION TEST WITH STOP ON OBSTRUCTION 1) Make sure the DIP switches at position 6 (relay board PRESENT) and

eht no noitisop NO eht ni tes era )noitcurtsbo no pots( 7 noitisop .draoB tiucriC niaM

• Place a chair or other suitable obstruction in the normal path of the door.

no nrut lliw rotaicnunna ehT ereht ti evael dna TSET ot hctiws yek eht nruT )2 dnoces 01 tes yrotcaf eht retfA .rucco ot tuoba si erusolc rood a taht gnitacidni delay (or longer optional delay), the device will turn on the motor initiating .erusolc a CONTINUED NEXT PAGE

www.overheaddoor.com 02/13 23Fire Sentinel® Release System

WARNING: KEEP THE DOOR OPENING CLEAR OF ALL PERSONNEL.THIS TEST SHOULD BE PERFORMED USING THE TEST AND RESET FUNCTIONS OF THE REMOTE TEST STATION. (It may be performed using the test and reset switches of the device enclosure.)

WARNING: KEEP THE DOOR OPENING CLEAR OF ALL PERSONNEL.THIS TEST SHOULD BE PERFORMED USING THE TEST AND RESET FUNCTIONS OF THE REMOTE TEST STATION. (It may be performed using the test and reset switches of the device enclosure.)

Page 25: 12/13 P/N 111995.502195 FSBX-120VAC/24V FSCX-120VAC/24V · This Installation Manual provides ... FIRE SENTINEL® RELEASE SYSTEM FSBX-120VAC/24V FSCX-120VAC/24V 12/13 P/N 111995.502195

Test ProceduresAutomatic Door Closure Tests (Motorized Doors/FSCX only) (continued):

THREE CYCLE OBSTRUCTION TEST WITH STOP ON OBSTRUCTION CONTINUEDIf the obstruction is removed, the FSCX will wait 10 seconds and then close the door. Should the door contact a second obstruction, the FSCX will fully open the door, then attempt to close the door again. If the obstruction is still there, the FSCX will open the door to the up limit and mechanically release the door. STAND CLEAR OF ANY PATH THE OBSTRUCTION MIGHT TAKE AFTER BEING CONTACTED BY THE DROPPED DOOR. The annunciator will continue to sound until the alarm condition is cleared. 3) Reset

4) Reset door sash chain and armature.5) Open the door.

the FSCX by turning the key switch to the RESET position and then back to NORMAL.

AUTO OPEN

ON RESET

TEST

1) Make sure the DIP switches at position 5 (auto open on reset, test only) and position 6 (relay board PRESENT) are set in the ON position on the .draoB tiucriC niaM

THIS TEST SHOULD BE PERFORMED USING THE TEST AND RESET FUNCTIONS OF THE REMOTE TEST STATION. (It may be performed using the test and reset switches of the device enclosure.)

2) Turn the key switch to TEST and leave it there. • Make sure there are no obstructions in the path of the door. 3) Allow the door to fully close. 4) Reset the FSCX by turning the key switch to the RESET position and back to NORMAL. • After the reset is complete the door will automatically start to open to

.timil pu eht

NOTIFICATION

NOTE: If Dip Switch 5 is not set to ON—the door will automatically re-open.

OFF ON CLOSE LIMIT TEST ,timil nwod no ffo noitacifiton( 4 noitisop ta sehctiws PID eht erus ekaM )1 noitisop NO eht ot tes era )TNESERP draob yaler( 6 noitisop dna )ylno tset

on the Main Circuit Board.

THIS TEST SHOULD BE PERFORMED USING THE TEST AND RESET FUNCTIONS OF THE REMOTE TEST STATION. (It may be performed using the test and reset switches of the Device Enclosure.)

timil nwod eht ni ton si rotarepo eht erus ekaM )2 • If in the down limit, press the open button on the 3-button station to open the door. 3) Turn the key switch to TEST and leave it there. • Make sure there are no obstructions in the path of the door. 4) Allow the door to fully close. • When the door reaches the down limit, the notification appliances will shut off. If the open button on the 3-button station is pressed and the door leaves the down limit, the notification appliances will turn back on. 5) Reset the FSCX by turning the key switch to RESET and then back to NORMAL.

www.overheaddoor.com 02/13 24Fire Sentinel® Release System

WARNING

WARNING: KEEP THE DOOR OPENING CLEAR OF ALL PERSONNEL.

: TO PREVENT POSSIBLE SERIOUS INJURY OR DEATH: • WHILE PERFORMING THE MECHANICAL OR ELECTRICAL DOOR DROP TEST, KEEP YOURSELF AND ANY OTHERS CLEAR OF THE DOOR AND ANY MOVING PARTS.• CLEAR ANY OBJECTS OR PEOPLE FROM DOOR PATH.• PROHIBIT TRAFFIC THROUGH THE DOOR OPENING WHILE TESTING.

WARNING: KEEP THE DOOR OPENING CLEAR OF ALL PERSONNEL.

Upon contact with the obstruction, the safety edge will reverse the motor and raise the door to the fully open position. The FSCX will make three attempts to close through the motor. On the third up limit the FSCX will close the door and stop at the obstruction.

Page 26: 12/13 P/N 111995.502195 FSBX-120VAC/24V FSCX-120VAC/24V · This Installation Manual provides ... FIRE SENTINEL® RELEASE SYSTEM FSBX-120VAC/24V FSCX-120VAC/24V 12/13 P/N 111995.502195

Test ProceduresAutomatic Door Closure Tests (Motorized Doors/FSCX only) (continued):

www.overheaddoor.com 12/13 25

ALARM ON POWER LOSS TEST 1) Make sure the DIP switch at position 8 (alarm on power loss) is set in the ON position on the Main Circuit Board. 2) UNPLUG the unit from the AC power source OR DISCONNECT the DC power input to the unit. • After the factory set 10 second time delay (or longer optional delay) the device will close the door. 3) Re-apply AC or DC power to the unit. 4) Reset the FSCX by turning the key switch to RESET and back to NORMAL.

After completing all tests, verify the door is in normal operating condition (open or closed) and that all power required for normal operation has been restored to the unit and operator. This equipment is designed to operate with its power source applied.

SET DIP SWITCHES AS DESIRED.

Release Device Compatibility IdentifierPhotoelectric Smoke DetectorsSystem Sensor Model No ............Description 2W-B ..............................................2-wire smoke detector, compatibility identifier A 2WT-B ............................................2-wire smoke detector w/135°F thermal sensor, compatibility identifier A 4W-B ..............................................4-wire smoke detector 4WT-B ............................................4-wire smoke detector w/135°F thermal sensorHochiki Model No ...........................Description SLR835BH-2 ................................2-wire smoke detector w/135°F thermal sensor, compatibility identifier HD-6

Heat DetectorsSystem Sensor Model No ............Description 5603 ...............................................135°F fixed temperature 5604 ...............................................194°F fixed temperature

Notification DevicesSystem Sensor Model No ............Description SR ...............................................Strobe. Set for 15 cd per System Sensor Instructions HR ...............................................Horn. Set for non-temporal horn per System Sensor Instructions P2R ...............................................Horn/Strobe. Set for 15 cd and non-temporal horn per System Sensor instructions

End of Line Devices System Sensor Model No ..........Description EOLR-1 ..........................................End of line relay

Replacement PartsOverhead Door Part No ... ........... ..Qty ..................................... ..Description 111658.0001.S ...........................1 .......................................... Sytem backup battery (12 Volt) 112087.0001.S ...........................1 ...........................................System non-rechargeable battery (NRB2.4-7.2)

as req'd ..............................End of line relay etalP/w.........................as req'd ..............................End of line resistor etalP/w 112249.0001.S

111995.XXXXXX .....................as req'd ..............................Installation Manual 112012.0001.S ...........................1 ..........................................Armature Assembly 112007.0001.S ...........................1 ...........................................Remote Test Plate

112228.0001.S ...........................10 pack..............................Supervisory Resistor

112226.000 S.1 ...........................10 .kcap ............................. Fuse 2A

WARNING: TO PREVENT POSSIBLE SERIOUS INJURY OR DEATH: • WHILE PERFORMING A MECHANICAL OR ELECTRICAL DOOR DROP TEST, STAY CLEAR OF THE DOOR AND ANY MOVING PARTS.

• CLEAR ANY OBJECTS OR PEOPLE FROM DOOR PATH.

• PROHIBIT TRAFFIC THROUGH THE DOOR OPENING WHILE TESTING.

Fire Sentinel® Release System

112325.0001.S ......................

Hochiki Model No ...........................Description DFE-135 ..................................... 135˚F fixed temperature

Page 27: 12/13 P/N 111995.502195 FSBX-120VAC/24V FSCX-120VAC/24V · This Installation Manual provides ... FIRE SENTINEL® RELEASE SYSTEM FSBX-120VAC/24V FSCX-120VAC/24V 12/13 P/N 111995.502195

Installation Notes

www.overheaddoor.com 02/13 26Fire Sentinel® Release System

Page 28: 12/13 P/N 111995.502195 FSBX-120VAC/24V FSCX-120VAC/24V · This Installation Manual provides ... FIRE SENTINEL® RELEASE SYSTEM FSBX-120VAC/24V FSCX-120VAC/24V 12/13 P/N 111995.502195

Test RecordsDATE SERIAL # INSTALLER/TESTER NAME WITNESS NAME PASS FAIL

www.overheaddoor.com 02/13 27

Make copies of this page as needed for additional testing. Keep records of all tests in a permanent file.

Fire Sentinel® Release System

Page 29: 12/13 P/N 111995.502195 FSBX-120VAC/24V FSCX-120VAC/24V · This Installation Manual provides ... FIRE SENTINEL® RELEASE SYSTEM FSBX-120VAC/24V FSCX-120VAC/24V 12/13 P/N 111995.502195

Overhead Door Corporation Fire Sentinel® Release System

Limited Warranty The Distributor of Overhead Door Corporation products whose name appears below (”Seller”) warrants to the original purchaser of the Fire Sentinel® Release System specified below(”Product”), subject to all terms and conditions hereof, that the Product and all components thereof will be free from defects in material and workmanship under normal use and service for the following period, measured from the date of the installation:

• One (1) year

its option,the Product or any part thereof which is determined by Seller to be defective during the applicable warranty period. Any labor charges are excluded and will be the responsibility of the purchaser. This warranty is made to the original purchaser of the Product only, and is not transferable or assignable.

This warranty applies only to the Product which is installed in commercial or industrial building applications. This warranty does not apply to any unauthorized alteration or repair of the Product, or to any Product or component which has been damaged or deteriorated due to misuse, neglect, accident or failure to provide necessary maintenance, normal wear and tear, or acts of God or other causes beyond the resonable control of Seller and does not cover batteries, or repairs and maintenance to the operator or door components.

THIS WARRANTY IS EXCLUSIVE AND IN LIEU OF ANY OTHER WARRANTIES, EITHER EXPRESSED OR IMPLIED, INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE.

IN NO EVENT SHALL SELLER BE RESPONSIBLE FOR, OR LIABLE TO ANYONE FOR, SPECIAL, INDIRECT, COLLATERAL, PUNITIVE, INCIDENTAL OR CONSEQUENTIAL DAMAGES, even if Seller has been advised of the possibility of such damages. Such excluded damages include,

MODEL #:

SERIAL #:

ORIGINAL PURCHASER:

INSTALLATION ADDRESS:

DOOR NUMBER (MULTIPLE DOOR INSTALLATIONS):

DOOR TYPE:

SELLER:

SELLER’S ADDRESS:

DATE OF INSTALLATION:

SIGNATURE OF SELLER:

28

Claims under this warranty must be made promptly after discovery, within the applicable warranty period, and in writing to the authorized distributor or installer whose name and address appeared below. (Proof of purchase and identification as the original purchaser maybe required.) The purchaser must allow Seller reasonable opportunity to inspect any Productclaimed to be defective prior to removal or any alteration of its condition.

Page 30: 12/13 P/N 111995.502195 FSBX-120VAC/24V FSCX-120VAC/24V · This Installation Manual provides ... FIRE SENTINEL® RELEASE SYSTEM FSBX-120VAC/24V FSCX-120VAC/24V 12/13 P/N 111995.502195

www.overheaddoor.com

THIS PAGE LEFT BLANK

Fire Sentinel® Release System

Page 31: 12/13 P/N 111995.502195 FSBX-120VAC/24V FSCX-120VAC/24V · This Installation Manual provides ... FIRE SENTINEL® RELEASE SYSTEM FSBX-120VAC/24V FSCX-120VAC/24V 12/13 P/N 111995.502195

www.overheaddoor.com

THIS PAGE LEFT BLANK

Fire Sentinel® Release System

Page 32: 12/13 P/N 111995.502195 FSBX-120VAC/24V FSCX-120VAC/24V · This Installation Manual provides ... FIRE SENTINEL® RELEASE SYSTEM FSBX-120VAC/24V FSCX-120VAC/24V 12/13 P/N 111995.502195

1 Door DriveMt. Hope, Ohio 44660