120209 lighting circuiting & design
-
Upload
sdouglass11 -
Category
Business
-
view
131 -
download
4
Transcript of 120209 lighting circuiting & design
Sharing our Guidance
Lighting Circuiting and Design
By: Hilmi Tannous
X
Lighting Circuiting and Design
• Always have a complete Luminaire schedule on plans• Include the Fixture Lamps• Include the Total Fixture Wattage• Include a detailed Fixture description• Include a complete Catalog number• Include the Fixture Voltage
Lighting Circuiting
04/12/23 2
X
Lighting Circuiting and Design
• Always add the details from the previous slide to a client provided
Luminaire schedule, like the Casual Male, F21 or JCP projects
• Our Master Luminaire schedule is located in:
T:\Engineering\Details and Schedules - Autocad\Div 26 - Electrical\
260000 - ELECTRICAL DRAWING ELEMENTS
Lighting Circuiting (cont.)
04/12/23 3
X
Lighting Circuiting and Design
• When circuiting lighting plans
always print the lighting plans
and redline the design
DO NOT CIRCUIT ON SCREEN!
• Count all light fixtures and use
different color highlighters
• Keep all lights on the same
circuits, adjacent to each other
Lighting Circuiting (cont.)
04/12/23 4
X
Lighting Circuiting and Design
• For T8 & T5 Fluorescent Lamps use the total Lamp Wattage
• i.e. If you have (2) 32W T8 lamps use 64W
• Fluorescent Ballast factor can vary from .76 to 1.18
• BALLASTS SHALL BE INSTANT START, ELECTRONIC TYPE, CLASS P, "A"
SOUND RATING AND MAXIMUM HARMONIC CONTENT OF 10%
• DIMMING BALLASTS SHALL BE 3-WIRE TYPE, WITH DIMMING
CAPABILITY TO 10% OF RATED FULL OUTPUT
• ALL FIXTURE / BALLAST / LAMP COMBINATIONS SHALL BE ENERGY
SAVING TYPE
New Wattage Standards
04/12/23 5
X
Lighting Circuiting and Design
• GE 3 Lamp Ballast type 23673-GE-332 with 3 lamps the total fixture
wattage is 85W. 11W less
• Same Ballast with 2 lamps is 65W. 1W more
• GE 4 Lamp Ballast type 23675-GE-432 with 3 lamps the total fixture
wattage is 113W. 15W less
• Same Ballast with 3 lamps is 97W. 1W more
• Two level switching fixture with (2) ballasts [ 2-lamps and 1-lamp] total
wattage is 61+36= 97W
• To be safe use the total Lamp Wattage
New Wattage Standards (cont.)
04/12/23 6
X
Lighting Circuiting and Design
• For CFL use the fixture wattage +4W. I.e. fixture with (2) 16W use
18+18+4= 40W
• Except the 42W CFL add 5W
• GE CFL13W 1 lamp fixture with 87533-GE1CFL13PH total system
wattage is 16W
• GE CFL42W 1 lamp fixture with 87573-GE1CFL42PH total system
wattage is 47W
New Wattage Standards (cont.)
04/12/23 7
X
Lighting Circuiting and Design
• For HID & HPS lamps:
• 39W use 44W
• 70W use 78W
• 400W use 470W
• 575W use 635W
• 750W use 840W
• 1000W 1130W
New Wattage Standards (cont.)
04/12/23 8
X
Lighting Circuiting and Design
• For traditional incandescent Lamps like types A, use the Wattage of the
Lamp
• For low voltage MR16 lamps add 10% for ballast factors
New Wattage Standards (cont.)
04/12/23 9
X
Lighting Circuiting and Design
• For LED fixtures:
• If the driver is built-in, the total fixture wattage is what the
manufacturer advertised, per IEC and DOE standard
• For remote driver fixtures and fixtures where the EC has to provide a
step down 24V transformer, add the LED wattage and driver
efficiency
New Wattage Standards (cont.)
04/12/23 10
Lighting Circuiting and DesignCONCLUSION . . .