11 3ph Fault Curve
description
Transcript of 11 3ph Fault Curve
![Page 1: 11 3ph Fault Curve](https://reader036.fdocuments.in/reader036/viewer/2022081805/563dbabc550346aa9aa7a0a8/html5/thumbnails/1.jpg)
A05 SE44 OCR - P
OC1
Siemens
7SJ62
CT Ratio 600:1
IEC - Normal Inverse
Pickup = 0.8 (0.1 - 2 Sec - 1A)
Time Dial = 0.22
3x = 1.39 s, 5x = 0.942 s, 8x = 0.725 s
Inst = 17 (0.1 - 35 Sec - 1A)
Time Delay = 0.01 s
8.316 kA @ 11 kV
t1: 0.525 s
SWS IC 1 OCR - P
OC1
ABB
REF 610
CT Ratio 600:1
IEC - Normal Inverse
Pickup = 0.8 (0.3 - 5 xCT Sec)
Time Dial = 0.11
3x = 0.693 s, 5x = 0.471 s, 8x = 0.363 s
8.316 kA @ 11 kV
t1: 0.262 s
SWS B/C OCR - P
OC1
ABB
REF 610
CT Ratio 600:1
IEC - Normal Inverse
Pickup = 0.8 (0.3 - 5 xCT Sec)
Time Dial = 0.11
3x = 0.693 s, 5x = 0.471 s, 8x = 0.363 s
8.316 kA @ 11 kV
t1: 0.262 s
Normalized (shifted) TCC
3-Phase (Sym) fault: 8.316kA @ 11kV
Adj Bus: NMC hospital SWS bus B
Connector: CT10 - T3
SQOP File: 11 KV 3 PH FAULT SQOP
Data Rev: Base
Configuration: Normal
Date: 02-11-2015
TR OCR 2 - P
OC1
ABB
REF 610
CT Ratio 100:1
IEC - Normal Inverse
Pickup = 1 (0.3 - 5 xCT Sec)
Time Dial = 0.2
3x = 1.26 s, 5x = 0.856 s, 8x = 0.659 s
Inst = 16 (0.5 - 35 xCT Sec)
Time Delay = 0.04 s
8.316 kA @ 11 kV
t1: 0.04 s
100.005 .01 .1 1 10.03 .05 .3 .5 3 5 30 50
Per Unit
100.005 .01 .1 1 10.03 .05 .3 .5 3 5 30 50
Per Unit
1K
.01
.1
1
10
100
.03
.05
.3
.5
3
5
30
50
300
500
1K
.01
.1
1
10
100
.03
.05
.3
.5
3
5
30
50
300
500
ETAP Star 7.0.0
11 3PH FAULT CURVE
Project: NMC specialty
Location: abu dhabi
Contract:
Engineer:
Filename: C:\ETAP 700\NMC speciality hospital\NMC speciality hospital.OTI
Date: 02-11-2015
SN: 12345678
Rev: Base
Fault: Phase(Normalized)
I> A05 SE44 OCR
R SWS IC 1 OCR
A05 SE44 OCR
SWS IC 1 OCR
±
R TR OCR 2
T3
1.5 MVA
R SWS B/C OCR
T3
1.5 MVA
SWS B/C OCR
TR OCR 2