HUBBELL / CHANCE – CENTRALIA, MISSOURI MAY 2005 ® ® Printed in USA Section 10A CUTOUTS (Standard, Linkbreak & Loadbreak) and CUTOUT-ARRESTER COMBINATIONS CAUTION: The equipment covered in this catalog section should be installed, used, and serviced only by competent personnel familiar with and following good work and safety practices. This equipment is for use by such personnel and is not intended as a substitute for adequate training and experience in safe procedures for this type of equipment. This catalog information and any related instruction sheets do not cover all details or situations in equipment use nor do they provide for every possible contingency to be encountered in relation to installation, operation or maintenance. Should additional information and details be desired, or if specific situations arise that are not covered adequately for the user's purpose the specifics should be referred to Hubbell Power System, Inc. Warranty - Material Hubbell Power Systems, Inc. warrants all products sold by it to be merchantable (as such term is defined in the Uniform Commercial Code) and to be free from defects in material and workmanship. Buyer must notify the Company promptly of any claim under this warranty. The Buyer's exclusive remedy for breach of this warranty shall be the repair or replacement, F.O.B. factory, at the Company's option, of any product defective under the warranty which is returned to the Company within one year from the date of shipment. NO OTHER WARRANTY, WHETHER EXPRESS OR ARISING BY OPERATION OF LAW, COURSE OF DEALING, USAGE OF TRADE OR OTHERWISE IMPLIED, SHALL EXIST IN CONNECTION WITH THE COMPANY'S PRODUCTS OR ANY SALE OR USE THEREOF. The Company shall in no event be liable for any loss of profits or any consequential or special damages incurred by Buyer. The Company's warranty shall run only to the first Buyer of a product from the Company, from the Company's distributor, or from an original equipment manufacturer reselling the Company's product, and is non-assignable and non-transferable and shall be of no force and effect if asserted by any person other than such first Buyer. This warranty applies only to the use of the product as intended by Seller and does not cover any misapplication or misuse of said product. Warranty - Application Hubbell Power Systems, Inc. does not warrant the accuracy of and results from product or system performance recommendations resulting from any engineering analysis or study. This applies regardless of whether a charge is made for the recommendation, or if it is provided free of charge. Responsibility for selection of the proper product or application rests solely with the purchaser. In the event of errors or inaccuracies determined to be caused by Hubbell Power Systems, Inc., its liability will be limited to the re-performance of any such analysis or study. © Copyright 2004 Hubbell 210 North Allen Street Centralia, MO 65240 NOTE: Because Hubbell has a policy of continuous product improvement, we reserve the right to change design and specifications without notice.

Transcript of 10A-1 10A CUTOUTS (Standard, Linkbreak & Loadbreak) and ... · 10A-1 HUBBELL / CHANCE –...

Page 1: 10A-1 10A CUTOUTS (Standard, Linkbreak & Loadbreak) and ... · 10A-1 HUBBELL / CHANCE – CENTRALIA, MISSOURI MAY 2005 ® ® Printed in USA Section 10A CUTOUTS (Standard, Linkbreak

10A-1

HUBBELL / CHANCE – CENTRALIA, MISSOURI MAY 2005

®®

Printed in USA

Section

10A

CUTOUTS (Standard, Linkbreak & Loadbreak)

andCUTOUT-ARRESTER COMBINATIONS

CAUTION: The equipment covered in this catalog section should be installed, used, and serviced only by competentpersonnel familiar with and following good work and safety practices. This equipment is for use by such personnel and is notintended as a substitute for adequate training and experience in safe procedures for this type of equipment.

This catalog information and any related instruction sheets do not cover all details or situations in equipment use nor do theyprovide for every possible contingency to be encountered in relation to installation, operation or maintenance. Shouldadditional information and details be desired, or if specific situations arise that are not covered adequately for the user'spurpose the specifics should be referred to Hubbell Power System, Inc.

Warranty - MaterialHubbell Power Systems, Inc. warrants all products sold by it to be merchantable (as such term is defined in the Uniform Commercial Code) and to be free from defects in material and workmanship.Buyer must notify the Company promptly of any claim under this warranty. The Buyer's exclusive remedy for breach of this warranty shall be the repair or replacement, F.O.B. factory, at the Company'soption, of any product defective under the warranty which is returned to the Company within one year from the date of shipment. NO OTHER WARRANTY, WHETHER EXPRESS OR ARISING BYOPERATION OF LAW, COURSE OF DEALING, USAGE OF TRADE OR OTHERWISE IMPLIED, SHALL EXIST IN CONNECTION WITH THE COMPANY'S PRODUCTS OR ANY SALE OR USETHEREOF. The Company shall in no event be liable for any loss of profits or any consequential or special damages incurred by Buyer. The Company's warranty shall run only to the first Buyer of aproduct from the Company, from the Company's distributor, or from an original equipment manufacturer reselling the Company's product, and is non-assignable and non-transferable and shall be ofno force and effect if asserted by any person other than such first Buyer. This warranty applies only to the use of the product as intended by Seller and does not cover any misapplication or misuse ofsaid product.

Warranty - ApplicationHubbell Power Systems, Inc. does not warrant the accuracy of and results from product or system performance recommendations resulting from any engineering analysis or study. This appliesregardless of whether a charge is made for the recommendation, or if it is provided free of charge.

Responsibility for selection of the proper product or application rests solely with the purchaser. In the event of errors or inaccuracies determined to be caused by Hubbell Power Systems, Inc., itsliability will be limited to the re-performance of any such analysis or study.

©Copyright 2004 Hubbell • 210 North Allen Street • Centralia, MO 65240

NOTE: Because Hubbell has a policy of continuous product improvement, we reserve the right to change design and specifications without notice.

Page 2: 10A-1 10A CUTOUTS (Standard, Linkbreak & Loadbreak) and ... · 10A-1 HUBBELL / CHANCE – CENTRALIA, MISSOURI MAY 2005 ® ® Printed in USA Section 10A CUTOUTS (Standard, Linkbreak

10A-2

MAY 2005 HUBBELL / CHANCE – CENTRALIA, MISSOURI

®®

U.S. Patent 4,546,341; 6,392,526 and other PatentsPending

Type C Cutouts

LOADBREAK cutoutwith Arc-Chute interrupter,pages 11-13

STANDARD cutout, pages 3-7

LINKBREAK cutout,pages 8-10

CUTOUT-ARRESTERCombinations,page 14

Application

The primary purpose of any cutout is to provide protection to thelines of your system and the various apparatus on those linessuch as transformers and capacitor banks. Chance Type Ccutouts provide reliable protection from low-level overloadsthat just melt the fuse link, intermediate faults, and very highfaults, through maximum interrupt capacity.

In addition, Type C cutouts can also be used as a sectionalizingdevice. With the use of a portable loadbreak tool, Type C cutoutscan function much like an overhead disconnect switch. Thereare 300 amp disconnect blade Type C cutouts available.

Ratings/Specifications

STANDARD Type C cutouts have maximum design voltageratings to simplify the confusing ratings of cutouts. There areno restrictions on application to grounded wye, ungroundedwye, or delta systems having maximum operating voltages(line-to-line) equal to or less than the cutout maximum designvoltage rating. (See the LINKBREAK and LOADBREAK cut-outs for their specifications.) Interruption tests have beenperformed at full system line-to-line voltage. In each voltageclass, there are continuous current ratings of 100 amps, 200amps and 300 amps. See the table on page 6 for other specifica-tions.

Page 3: 10A-1 10A CUTOUTS (Standard, Linkbreak & Loadbreak) and ... · 10A-1 HUBBELL / CHANCE – CENTRALIA, MISSOURI MAY 2005 ® ® Printed in USA Section 10A CUTOUTS (Standard, Linkbreak

10A-3

HUBBELL / CHANCE – CENTRALIA, MISSOURI MAY 2005

®®

Insulators

The insulators used on Type C cutouts are a sky-glaze gray.The metal to metal leakage distance on the 15 kV cutoutinsulator is 8.7 inches (220 mm), 12.6 inches (320 mm) on the27 kV (125 kV BIL), 17.3 inches (440 mm) on the 27 kV (150kV BIL), 26 inches (660 mm) on the 36 kV (170 kV BIL), and28.4 inches (720 mm) on the 36 kV (170 kV BIL) .

Fuseholders

The solid cap on the single vent fuseholder is a copper alloy,silver-plated to provide efficient current transfer. An integralring is provided in the top tube casting for opening andclosing the fuseholder with conventional disconnect toolsfrom the ground, from a bucket truck or from the pole.

The toggle type trunnion casting is a selective silver-plated bronze for efficient current transfer to the lowerhinge contacts. A cam shaped projection on each side of thetrunnion casting provides high pressure parallel currentpaths to the lower contacts. These projections, or pivot pins,are cast full round for smooth rotational operation in thehinge. The link ejector assists in arc interruption during lowfault current or excessive overload conditions. A groove in thecenter of the link ejector allows the fuse link’s pigtail to godirectly from the fuse tube to the attachment nut. A curvedejector minimizes bending stresses in the pigtail to preventbroken strands. A stainless steel torsion spring on the linkejector helps to rapidly eject the link from the bore of thefuseholder during interruption. The 200 amp link ejector hasa wider groove area and increased spring force to accommo-date the larger links.

The link ejector is pinned to the trunnion casting with astainless steel pin to provide resistance to corrosive elementsand provide smooth pivotal action. An interlocking featurebetween the link ejector and tube casting prevents excessivetension on the fuse link during closure, thereby preventinglink breakage.

The link ejector employs a hammer effect to enhance toggleaction of the trunnion during low fault and overload interrup-tions, hence dropout action is enhanced. The link ejectorprovides sufficient surface area to facilitate re-fusing bylinemen wearing gloves.

Quality Construction

Efficient Current Transfer

The Chance Type C cutout has an all copper current path. Allcontacts are silver-plated. Terminals are tin-plated bronzefor use with copper or aluminum conductors.

Loadbreak Hooks

Galvanized steel hooks are standard on all Type C cutouts,except the arc chute version, for use with a portable loadbreaktool. These sturdy hooks are mounted on the top support andserve to guide the fuseholder into the latch socket whenclosing at an off-center angle.

Top Contact

The top contact is attached to the galvanized-steel hood by astainless rivet to provide a smooth self-aligning action duringclosing even in severely corrosive environments. The topcontact provides a socket-type cavity for latching the fuse-holder and prevents any possible “over-travel” of the fuse-holder. The top contact is made of a highly conductive copperstrip with silver-plated embossments to resist corrosion. Thecontacts are held under constant pressure designed to main-tain firm contact with the fuseholder contact surface untilfault interruption is accomplished.

Hinge

The hinge on the Type C cutout employs large pivot areas forthe fuseholder’s trunnion and is cast of a copper alloy chosenfor its strength and corrosion resistance. The hinge contactsare highly conductive copper alloy stampings and are platedto assure low resistance current transfer from the trunnioncasting. The parallel current paths are backed up by highstrength cantilever springs and are riveted to the hingecastings. Fuseholder can be dropped into place and easilylifted up and out. No tricky maneuvering.

Type C STANDARD Cutout

Chance Type C fuseholders are also mutually interchangeable with the S & C Electric Company’s Type XS cutout.

100 AmpSingle Vent

200 AmpSingle Vent

300 AmpDisconnect

Page 4: 10A-1 10A CUTOUTS (Standard, Linkbreak & Loadbreak) and ... · 10A-1 HUBBELL / CHANCE – CENTRALIA, MISSOURI MAY 2005 ® ® Printed in USA Section 10A CUTOUTS (Standard, Linkbreak

10A-4

MAY 2005 HUBBELL / CHANCE – CENTRALIA, MISSOURI

®®

Type C STANDARD Cutout

kVBIL

110

125

150

170

STANDARD Type C Cutout withNEMA Type B Bracket Dimensions

A16"

406 mm163⁄8"

416 mm163⁄8"

416 mm171⁄4"

438 mm

B51⁄2"

137 mm71⁄8"

181 mm71⁄8"

181 mm81⁄2"

216 mm

C103⁄4"

273 mm121⁄2"

318 mm121⁄2"

318 mm15"

381 mm

D31⁄2"

89 mm31⁄8"

79 mm31⁄8"

79 mm13⁄4"

44 mm

E211⁄2"

559 mm263⁄4"

679 mm263⁄4"

679 mm321⁄2"

826 mm

PRODUCT FEATURES

InterchangeabilityChance was the first to design a cutout that could inter-change fuseholders and mounting assemblies with those ofanother manufacture. Standard Type C fuseholders andmounting assemblies are mutually interchangeable with theS&C Electric Company’s Type XS cutout (within the samevoltage class).

FusetubeThe 1⁄2-inch inside diameter of the Type C cutout’s 100ampere fusetube increases internal pressure giving superiorand reliable expulsion action. During frequently encoun-tered intermediate fault ranges this diameter also permitshigher TRV (transient recovery voltage) values to be toler-ated. This small bore design eliminates any concern relatedto high impedance phase-to-phase faults on ungrounded wyeand delta systems.

The inside liner is constructed of a synthetic arc-quenchingmaterial. The tube is made of fiberglass which permits thesmaller bore and provides a higher burst strength. It isprotected from the weather and environment by a specialultra-violet resistant coating.

Also, the Chance fusetube operates with fuselinks from allmajor suppliers.

BracketsC cutouts come packed one per carton including a NEMAHeavy Duty “B” bracket with captive 11⁄2" bolt for crossarmmounting.

Type X brackets, also for crossarm mounting, provides 25⁄8"additional clearance between the crossarm and the cutout.

“D” brackets are used to mount cutouts and/or arrestersdirectly to the pole. Three brackets may be used for three-phase application. Type D brackets provide a clean, quickmounting without crossarm or special pole bands.

All the above brackets are galvanized steel for long lastingservice. Cutouts can be ordered without any brackets.

Higher Interrupt CapacitiesBy using a copper arc shortening rod inside the top of thefusetube, higher interrupt ratings are obtainable. An arcshortening rod is attached to the cap of some fusetubes andlowers the fuse link within the fusetube. This permits a muchshorter arc, resulting in less arc energy, and higher inter-rupting capacities.

For 200 A tubes, it allows for full voltage rating.

It is necessary to use fuse links with removable buttonheadswhen arc shortening rods are employed.

170 kV BILA 170 kV BIL Type C cutout is available for use in areaswhere the 28.4-inch minimum leakage distance to ground isrequired. See ordering data, page 6.

Extra Corrosion Protection (150 and 170 kV BIL only)Type C cutouts are available with components of stainlesssteel inserts, hood and bolts, and copper alloy loadbreakhooks to offer greater corrosion resistance for environmentalareas where corrosion can become a major factor. To order astainless steel/copper alloy cutout add the suffix “S” to theend of the catalog number with the rating specificationsdesired. In additon, an optional spring assist may be providedto further enhance the toggle and drop out action in highlycorrosive applications.

TerminalsTin-plated bronze parallel groove type terminals are stan-dard on Type C cutouts. They can accommodate aluminum orcopper conductor sizes ranging from No. 6 (13.3 mm2) solidcopper through 4/0 (160.6 mm2) ACSR or 250 (167.5 mm2)kcmil stranded copper. The parallel groove design is perfectfor handling two different sizes of conductor as is the casewhen arresters are being used. Eyebolts are also available.See ordering data, page 10A-7.

Page 5: 10A-1 10A CUTOUTS (Standard, Linkbreak & Loadbreak) and ... · 10A-1 HUBBELL / CHANCE – CENTRALIA, MISSOURI MAY 2005 ® ® Printed in USA Section 10A CUTOUTS (Standard, Linkbreak

10A-5

HUBBELL / CHANCE – CENTRALIA, MISSOURI MAY 2005

®®

STAINLESS-STEELSPRING ENSURESPROPER TOGGLE ACTIONOF FUSELINK EJECTOR(CAST-BRONZE ON ALL 200AND LINKBREAK FUSEHOLDERS;STAINLESS-STEEL ON ALL 100A)

Compare Chance® quality and technical expertise

SILVER-TO-SILVERCONTACTS

CAST BRONZE HINGEFOR CORROSION RESISTANCE

COPPERCURRENT PATH

FUSEHOLDER TOGGLE LATCHLIMITS TENSION OF FUSELINK

SILVER-TO-SILVERCONTACTSWITH STAINLESS STEELBACKUP SPRINGS

CAST BRONZELOWER TUBECASTING

CAST BRONZE TOP TUBE CASTINGAND PULL RING

HIGH-STRENGTH FIBERGLASS FUSETUBECOATED WITH ULTRA-VIOLET INHIBITOR

GALVANIZED STEEL HOOKSFOR LOADBREAK TOOL

STAINLESS STEELBACKUP SPRINGTO MAINTAINCONTACT PRESSURE

BIRD-PROOFEDONE-PIECESOLID-PORCELAININSULATOR

TIN-PLATED BRONZE TERMINALSFOR USE WITH COPPEROR ALUMINUM CONDUCTOR

GALVANIZED-STEEL CHANNEL

COPPERARC-SHORTENING ROD(ON SOME RATINGS)

TWO-PLACE LOCKINGTO PREVENT SIDEMOVEMENT OF HOOD,CONTACTS OR HOOKS

HOT STICK HOLE IN TRUNNION CASTING

COPPER CURRENT PATH

Type C STANDARD CutoutAll Type C Cutouts meet or exceed ANSI/NEMA specifications.Manufacturing and/or use under U. S. Patent No. 4,546,341 and 6,392,526.

LARGE NUT TO FASTEN FUSELINKWITHOUT BREAK-ING STRANDS

MECHANICAL ASSIST:

FUSEHOLDER IS AVAIL-ABLE WITH A TORSIONALSPRING ON TRUNNION TOAID DROP OUT OPERATIONIN CORROSIVE ENVIRON-MENTS.

SYNTHETICFUSE TUBELINER

Page 6: 10A-1 10A CUTOUTS (Standard, Linkbreak & Loadbreak) and ... · 10A-1 HUBBELL / CHANCE – CENTRALIA, MISSOURI MAY 2005 ® ® Printed in USA Section 10A CUTOUTS (Standard, Linkbreak

10A-6

MAY 2005 HUBBELL / CHANCE – CENTRALIA, MISSOURI

®®

P700-1535P

E700-1768P

E700-2479P

P700-1535P

320 mm320 mm320 mm320 mm

P700-1535PE700-1768PE700-2479PP700-1535P

*Suffix: P = Parallel-groove clamps [No. 6 solid through 4/0 ACSR (13.3mm2 - 160.6mm2) or 250 kcmil stranded (167.5mm2)]B = NEMA Heavy Duty “B” bracket with 11⁄2" captive bolt

Terminal variations:P = Parallel-groove clamps [No. 6 solid through 4/0 ACSR (13.3mm2 - 160.6mm2) or 250 kcmil stranded (167.5mm2)]E = Small eyebolt [No. 8 solid through 2/0 stranded (7.7 - 90mm2)]

Change “P” to “E;” e.g., C710-112EBL = Large eyebolt [No. 6 solid through 4/0 stranded (13.3 - 160.6mm2) or 250 kcmil stranded (167.5mm2)]

Change “P” to “L;” e.g., C710-112LBBracket variations:

B = NEMA Heavy Duty “B” bracket with 11⁄2" captive boltX = Extended bracket (horizontal section 25⁄8" longer than NEMA Type B bracket)

Change “B” to “X;” e.g., C710-112PXD = Pole mounting bracket Change “B” to “D;” e.g., C710-112PD

(Blank) = Without crossarm bracket Drop “B” from Catalog No.; e.g., C710-112P

**Momentary rating — Solid blade†For application on single-phase to neutral or three-phase solidly-grounded wye-connected circuits where recovery voltagedoes not exceed the maximum-design voltage of the device.

‡Must use removable buttonhead fuse links.

Type C STANDARD Cutout

MaximumDesignVoltage15 kV15 kV15 kV15 kV

*CatalogNumber

C710-112PBC710-114PBC710-143PBC710-133PB

NominalSystem Voltage

Thru 14.4 kVThru 14.4 kVThru 14.4 kVThru 14.4 kV

220 mm220 mm220 mm220 mm

ArcShortening

RodNo

Yes‡

Yes‡

N/A

ContinuousCurrent(Amps)

100100200300

8.7"8.7"8.7"8.7"

Leakage to GroundMetal to Metal

InterruptCapacity

(Asym Amps)10,00016,00012,00012,000**

27 kV (125 kV BIL) — RUS Listed27 kV27 kV27 kV27 kV

NoYes‡

Yes‡

N/A

100100200300

8,00012,00010,00012,000**

Thru 24.9 kVThru 24.9 kVThru 24.9 kVThru 24.9 kV

C710-211PBC710-213PBC710-242PBC710-233PB

12.6"12.6"12.6"12.6"

27 kV (150 kV BIL) — RUS ListedNo Restrictionsthru 24.9 kV;

†26.4 thru 34.5 kVNo Restrictionsthru 24.9 kV;

†26.4 thru 34.5 kVNo Restrictionsthru 24.9 kV;

†26.4 thru 34.5 kVNo Restrictionsthru 24.9 kV;

†26.4 thru 34.5 kV

440 mm

440 mm

440 mm

440 mm

660 mm

660 mm

660 mm

26"

26"

26"

36 kV

27 kV

36 kV

Yes‡

Yes‡

N/A

100

200

300

11,200

12,000

12,000**

36 kV (170 kV BIL) — RUS ListedC710-613PB

C710-643PB

C710-633PB

720 mm

720 mm

720 mm

28.4"

28.4"

28.4"

36 kV

27 kV

36 kV

Yes‡

Yes‡

N/A

100

200

300

11,200

12,000

12,000**

36 kV (170 kV BIL) — RUS ListedC710-713PB

C710-743PB

C710-733PB

Thru 34.5 kVNo Restrictionsthru 24.9 kV;

†26.4 thru 34.5 kVThru 34.5 kV

Specifications and Ordering InformationAll Type C Cutouts meet or exceed ANSI/NEMA specifications.

15 kV (110 kV BIL) — RUS Listed

See page 10A-17 forCatalog Number System.

Thru 34.5 kVNo Restrictionsthru 24.9 kV;

†26.4 thru 34.5 kVThru 34.5 kV

No

Yes‡

Yes‡

N/A

C710-311PB

C710-313PB

C710-342PB

C710-333PB

27 kV

27 kV

27 kV

27 kV

100

100

200

300

8,000

12,000

10,000

12,000**

17.3"

17.3"

17.3"

17.3"

25.8 / 11.70

26.0 / 11.79

26.6 / 12.07

26.2 / 11.88

Weight(lb./kg.)

17.4 / 7.9817.6 / 7.9818.2 / 8.2617.7 / 8.03

ReplacementFusetube

CapP700-1535PE700-1767PE700-2146PP700-1535P

20.9 / 9.0720.2 / 9.1620.9 / 9.4820.4 / 9.25

E700-1743P

E700-2117P

P700-1535P

E700-1743P

E700-2117P

P700-1535P

28.6 / 12.97

29 / 13.15

28.6 / 12.97

33.9 / 12.97

34.3 / 15.55

33.9 / 15.37NOTE: 26" fuse links are recommended.

NOTE: 26" fuse links are recommended.

Page 7: 10A-1 10A CUTOUTS (Standard, Linkbreak & Loadbreak) and ... · 10A-1 HUBBELL / CHANCE – CENTRALIA, MISSOURI MAY 2005 ® ® Printed in USA Section 10A CUTOUTS (Standard, Linkbreak

10A-7

HUBBELL / CHANCE – CENTRALIA, MISSOURI MAY 2005

®®

Type C STANDARD Cutout

1.8 lb.2.0 lb.2.6 lb.2.1 lb.

*CutoutCatalogNumber

C710-112PBC710-114PBC710-143PBC710-133PB

Fuseholders and Mounting AssembliesOrdering Information

0.82 kg.0.91 kg.1.18 kg.0.95 kg.

15 kV (110 kV BIL)Mounting

Assembly only*Catalog No.

T710-1MMPB

Fuseholder orBlade onlyCatalog No.T710-112TT710-114TT710-143TT710-133T

5.85 kg.12.9 lb.

Weight Weight

36 kV (170 kV BIL)C710-613PBC710-643PBC710-633PB

T710-613TT710-643TT710-633T

2.8lb.3.2 lb.2.8 lb.

1.27 kg.1.45 kg.1.27 kg.

10.61 kg.23.4 lb.T710-6MMPB

36 kV (170 kV BIL)C710-713PBC710-743PBC710-733PB

T710-713TT710-743TT710-733T

2.8lb.3.2 lb.2.8 lb.

1.27 kg.1.45 kg.1.27 kg.

13.02 kg.28.7 lb.T710-7MMPB

C710-211PBC710-213PBC710-242PBC710-233PB

27 kV (150 kV BIL)

T710-211TT710-213TT710-242TT710-233T

2.1 lb.2.3 lb.2.7 lb.2.5 lb.

0.95 kg.1.14 kg.1.22 kg.1.13 kg.

7.08 kg.15.6 lb.T710-2MMPB

C710-311PBC710-313PBC710-342PBC710-333PB

T710-311TT710-313TT710-342TT710-333T

2.1 lb.2.3 lb.2.7 lb.2.5 lb.

0.95 kg.1.14 kg.1.22 kg.1.13 kg.

9.66 kg.21.3 lb.T710-3MMPB

27 kV (125 kV BIL)

300ABlade

100A 200AFuseholders

36 kV - 26" leakageT710-6MMPB

36 kV - 28.4" leakageT710-7MMPB

300ABlade

100A 200AFuseholders

300ABlade

200AFuseholders

100A

27 kV - 17.3" leakageT710-3MMPB

27 kV - 12.6" leakageT710-2MMPB

15 kV8.7" leakage

Catalog No.T710-1MMPB

MountingAssemblyonly

NOTE: 26" fuse links are recommended.

NOTE: 26" fuse links are recommended.

Page 8: 10A-1 10A CUTOUTS (Standard, Linkbreak & Loadbreak) and ... · 10A-1 HUBBELL / CHANCE – CENTRALIA, MISSOURI MAY 2005 ® ® Printed in USA Section 10A CUTOUTS (Standard, Linkbreak

10A-8

MAY 2005 HUBBELL / CHANCE – CENTRALIA, MISSOURI

®®

Type C 100-AmpLINKBREAK Cutout

22/36.4 kV - 150 kV BIL22/36.4 kV - 170 kV BIL

15 kv - 110 kV BIL15/27 kV - 125 kV BIL

changeable with any other manufacturer’s cutout.

All standard non-loadbreak fuseholders and the linkbreakfuseholders are interchangeable and fit into both the non-loadbreak and Type C LINKBREAK cutout mounting assem-blies produced after January 1985. Mounting assemblies aresame as Type C STANDARD cutouts, shown on page 10A-7.

Ratings / SpecificationsThe 15 kV Type C LINKBREAK cutout has a maximumdesign voltage rating of 15 kV. There are no voltage restric-tions on application to grounded wye, ungrounded wye, ordelta systems having maximum operating voltages (line toline) equal to or less than the cutout maximum design voltagerating.

The 15/27 and 22/36.4 kV Type C LINKBREAK cutouts havemaximum design slant voltage ratings. These cutouts are tobe used on systems which have phase-to-ground voltages nogreater than the value listed to the left of the slant (/) andwhich have phase-to-phase voltages no greater than thevalue listed to the right of the slant.

The Type C LINKBREAK cutout is to be used with onlyChance, McGraw-Edison and Kearney fuselinks. S&C Elec-tric fuselinks and other fuselinks which require more than 1inch elongation before breaking must not be used with theType C LINKBREAK cutout.

A sharp downward pull on the lever with a hookstickbreaks the fuselink.

15 kV - 110 kV BIL unit

ApplicationThe Chance Type C 100 amp LINKBREAK cutout providesshort circuit protection to utility lines with the added featureof mechanical linkbreak capability in a loadbreaking func-tion. Linkbreak cutouts provide reliable protection fromoverloads that just melt the fuselink through the maximuminterrupt capacity of the fuseholder and also provide induc-tive and capacitive loadbreak capability. For loadbreak rat-ings see chart, next page.

The unit will also accept the Type C 200 amp non-loadbreakfuseholder or a 300 amp disconnect blade. Each LINKBREAKcutout includes standard loadbreak hooks to use with por-table loadbreak tools. This method is particularly useful forswitching of the 200 amp fuseholder and 300 amp disconnectblade.

Design / Product FeaturesConstruction and product details shown on page 10A-3 applyto the LINKBREAK cutout except that the link-ejector on thelinkbreak fuseholder is a copper-alloy casting instead of astainless-steel stamping.

The unit utilizes a stainless-steel linkbreak lever to mechani-cally break fuselink elements thereby obtaining load inter-ruption within the fuseholder. The long lever is positioneddirectly in-line with the cutout, rather than on one side or inback of the cutout for convenient pull-down operation. TheType C LINKBREAK fuseholder is not designed to be inter- 15/27 kV - 125 kV BIL unit

Page 9: 10A-1 10A CUTOUTS (Standard, Linkbreak & Loadbreak) and ... · 10A-1 HUBBELL / CHANCE – CENTRALIA, MISSOURI MAY 2005 ® ® Printed in USA Section 10A CUTOUTS (Standard, Linkbreak

10A-9

HUBBELL / CHANCE – CENTRALIA, MISSOURI MAY 2005

®®

Type C 100-AmpLINKBREAK Cutout

LINKBREAK Cutout with NEMA Type B Bracket

F165⁄8"422mm16"406mm16"406mm

141⁄2"368mm

A16"406mm

163⁄8"416mm

163⁄8"416mm

171⁄4"438mm

B53⁄8"137mm71⁄8"181mm71⁄8"181mm81⁄2"216mm

C103⁄4"273mm

121⁄2"318mm

121⁄2"318mm15"381mm

D31⁄2"89

mm31⁄8"79

mm31⁄8"79

mm13⁄4"416mm

E22"559mm

263⁄4"679mm

263⁄4"679mm

321⁄2"826mm

BILkV

110

125

150

170

CapacitiveAmperes

100100100100505050

*Specifications and ordering information on next page.†Limited to grounded-wye systems with grounded-wyeloads.

InductiveAmperes

100100100100100100100

kV,Nominal

System Voltage14.414.424.924.934.534.534.5

*CutoutCatalogNumber

C720-112PBC720-114PBC720-211PB†

C720-213PB†

C720-311PB†

C720-313PB†

C720-613PB†

Loadbreak Ratings

Dimensions

22/36.4 kV - 150 kV BIL unit 22/36.4 kV - 170 kV BIL unit

Page 10: 10A-1 10A CUTOUTS (Standard, Linkbreak & Loadbreak) and ... · 10A-1 HUBBELL / CHANCE – CENTRALIA, MISSOURI MAY 2005 ® ® Printed in USA Section 10A CUTOUTS (Standard, Linkbreak

10A-10

MAY 2005 HUBBELL / CHANCE – CENTRALIA, MISSOURI

®®

29.3 / 13.29

*Suffix: P = Parallel-groove clamps [No. 6 solid through 4/0 ACSR (13.3mm2 - 160.6mm2) or 250 kcmil stranded (167.5mm2)]B = B = NEMA Heavy Duty “B” bracket with 11⁄2" captive bolt

Terminal variations:P = Parallel-groove clamps [No. 6 solid through 4/0 ACSR (13.3mm2 - 160.6mm2) or 250 kcmil stranded (167.5mm2)]E = Small eyebolt [No. 8 solid through 2/0 stranded (7.7 - 90mm2)]

Change “P” to “E;” e.g., C720-112EBL = Large eyebolt [No. 6 solid through 4/0 stranded (13.3 - 160.6mm2) or 250 kcmil stranded (167.5mm2)]

Change “P” to “L;” e.g., C720-112LBBracket variations:

B = B = NEMA Heavy Duty “B” bracket with 11⁄2" captive boltX = Extended bracket (horizontal section 25⁄8" longer than NEMA Type B bracket)

Change “B” to “X;” e.g., C720-112PXD = Pole mounting bracket Change “B” to “D;” e.g., C720-112PD

(Blank) = Without crossarm bracket Drop “B” from Catalog No.; e.g., C720-112P

Extra corrosion resistance:S = Available on only 150 kV and 170 kV BIL, e.g., C720-311PBS

†For application on single-phase to neutral circuits with phase-to-ground voltages not exceeding the value to the left of theslant; and for application on three-phase solidly-grounded-wye systems with solidly-grounded loads with line-to-line voltagesnot exceeding the value to the right of the slant.‡Must use removable buttonhead fuse links.

MaximumDesignVoltage15 kV15 kV

*CatalogNumber

C720-112PBC720-114PB

NominalSystem Voltage

Thru 14.4 kVThru 14.4 kV

220 mm220 mm

Weight(lb./kg.)

ArcShortening

RodNo

Yes‡

ContinuousCurrent(Amps)

100100

8.7"8.7"

Leakage to GroundMetal to Metal

InterruptCapacity

(Asym Amps)10,00016,000

17.7 / 8.0317.9 / 8.12

Specifications and Ordering InformationAll Type C Cutouts meet or exceed ANSI/NEMA specifications.

15 kV (110 kV BIL) — RUS Listed

See page 10A-17 forCatalog Number System.

22/36.4 kV

22/36.4 kV

22/36.4 kV (150 kV BIL) — RUS Listed

C720-311PB

C720-313PB

No Restrictionsthru 20.8 kV;

†22.8 thru 34.5 kV

660 mm26.0"22/36.4 kV Yes‡11,200

22/36.4 kV (170 kV BIL) — RUS Listed

C720-613PBNo Restrictionsthru 20.8 kV;

†22.8 thru 34.5 kV

15/27 kV

15/27 kV

No

Yes‡

8,000

12,000

100

100

15/27 kV (125 kV BIL) — RUS Listed

C720-211PB

C720-213PB

No Restrictionsthru 14.9 kV;

†20.8 thru 24.9 kV

12.6"

12.6"

320 mm

320 mm

lb.2.52.72.72.92.72.9

3.5

kg.1.131.221.221.321.221.32

1.59

WeightFuseholderCatalog No.T720-112TT720-114TT720-211TT720-213TT720-311TT720-313T

T720-613T

CutoutCatalog Number

C720-112PBC720-114PBC720-211PBC720-213PBC720-311PBC720-313PB

C720-613PB

kV& BIL15 kV

110 kV BIL15/27 kV

125 kV BIL22/36.4 kV150 kV BIL22/36.4 kV170 kV BIL

*Mounting assemblies are same as Type C STANDARD cutouts,shown on page 10A-7.

Type C 100-AmpLINKBREAK Cutout

110 kV BIL 170 kV BIL125 & 150 kV BIL

*Fuseholders (100 Amp only)

ReplacementFusetube

CapP700-1469PE700-1784P

P700-1469P

E700-1785P

20.4 / 9.25

20.6 / 9.34

No

Yes‡

8,000

12,000

100

100

17.3"

17.3"

440 mm

440 mm

P700-1469P

E700-1785P

26.2 / 11.79

26.4 / 11.88

100 PE700-1787P

NOTE: 26" fuse links are recommended.

Page 11: 10A-1 10A CUTOUTS (Standard, Linkbreak & Loadbreak) and ... · 10A-1 HUBBELL / CHANCE – CENTRALIA, MISSOURI MAY 2005 ® ® Printed in USA Section 10A CUTOUTS (Standard, Linkbreak

10A-11

HUBBELL / CHANCE – CENTRALIA, MISSOURI MAY 2005

®®

B

67⁄8"175 mm

85⁄8"219 mm

85⁄8"219 mm

C

103⁄4"273 mm

121⁄2"318 mm

121⁄2"318 mm

A

251⁄4"642 mm

281⁄4"719 mm

281⁄4"719 mm

D

31⁄2"89 mm

31⁄8"79 mm

31⁄8"79 mm

E

255⁄8"651 mm

307⁄8"784 mm

307⁄8"784 mm

kV BIL

110

125

150

Dimensions

Application

The Type C Loadbreak Cutout is available for application on15, 25 and 35 kV distribution systems. The addition of the arcchute expands the flexibility of the Chance protective devicesfamily by providing loadbreak capability for cutouts anddisconnect solid blade units. The loadbreak cutout providesshort circuit protection to utility lines with the added featureof a loadbreaking function.

The loadbreak cutout is applicable for transformer andcapacitor bank switching or line sectionalizing.Loadbreak cutouts provide protection from overloads thatjust melt the fuselink through the maximum interruptcapacity of the fuseholder. They also provide loadbreakcapability through 300 amperes.

Design

All design features and most components of the loadbreakunit are identical to those incorporated in the Type C stan-dard cutout. The loadbreak portion of the Type C Loadbreakcutout is a heavy duty, reliable load interrupter that providesa positive visible loadbreak. A common loadbreak mountingassembly will accept the Chance Type C 100 amp and 200amp loadbreak fuseholders or a 300 amp loadbreak discon-nect blade.

Ratings/Specifications

The 15kV Type C loadbreak cutout has a maximum designvoltage rating of 15kV. There are no voltage restrictions onapplicaton to grounded wye, ungrounded wye, or delta sys-tems having maximum operating voltages (line to line) equalto or less than the cutout maximum design voltage rating.

The 15/27 and 20/34.5 kV Type C loadbreak cutouts havemaximum design slant voltage ratings. These cutouts are tobe used on systems which have phase-to-ground voltages nogreater than the value listed to the left of the slant (/) andwhich have phase-to-phase voltages no greater than thevalue listed to the right of the slant.

Fuseholders and mounting assemblies from other manufac-turers' loadbreak cutouts are not interchangeable withChance loadbreak cutouts. Likewise, Chance fuseholdersand mountings are not interchangeable with other manufac-turers' loadbreak cutouts.

Operation

The self-contained loadbreak device enables the lineman tointerrupt load current by means of a simple hookstick opera-tion. To break the current, the lineman inserts a hookstickinto the operating ring and rapidly opens the device. Uponopening, a spring-loaded stainless steel blade mechanismsnaps out through a gray arc chute and elongates, cools andextinguishes the confined arc. The loadbreaking operation isindependent of the operating speed of the lineman. The fuseremains undamaged. No special or portable tools are re-quired to operate the unit. In the open position, the fuse-holder or blade hangs in an approximate vertical position forthe visible-break.

Type CLOADBREAK Cutoutwith Arc Chute type interrupter• 15 kv • 15/27 kV • 20/34.5 kV

Page 12: 10A-1 10A CUTOUTS (Standard, Linkbreak & Loadbreak) and ... · 10A-1 HUBBELL / CHANCE – CENTRALIA, MISSOURI MAY 2005 ® ® Printed in USA Section 10A CUTOUTS (Standard, Linkbreak

10A-12

MAY 2005 HUBBELL / CHANCE – CENTRALIA, MISSOURI

®®

Type CLOADBREAK Cutout

with Arc Chute Interrrupers

15 kV (110 kV BIL) — RUS Listed

See page 10A-17 forCatalog Number System.

NominalSystemVoltage

Thru 14.4 kVThru 14.4 kVThru 14.4 kVThru 14.4 kV

InterruptCapacity(AsymAmps)10,00016,00012,000

12,000**

22.5 / 10.222.7 / 10.323.3 / 10.622.8 / 10.4

Continuous& Loadbreak

Current(Amps)

100100200300

Weight(lb./kg.)

ArcShorten-

ingRodNo

Yes‡

Yes‡

N/A

Numberof

Opera-tions20020020050

Leakageto Ground,

Metal to Metal8.7"8.7"8.7"8.7"

220 mm220 mm220 mm220 mm

MaximumDesignVoltage15 kV15 kV15 kV15 kV

*CatalogNumber

C730-112PBC730-114PBC730-143PBC730-133PB

15/27 kV (125 kV BIL) — RUS Listed

No Restrictionsthru 14.4 kV;

†20.8 thru 24.9 kV

8,00012,00010,00012,000**

100100200300

NoYes‡

Yes‡

N/A

20020020050

15/27 kV15/27 kV15/27 kV15/27 kV

C730-211PBC730-213PBC730-242PBC730-233PB

12.6"12.6"12.6"12.6"

320 mm320 mm320 mm320 mm

20/34.5 kV (150 kV BIL) — RUS ListedNo Restrictionsthru 14.4 kV;

†20.8 thru 34.5 kV

8,000

12,000

100

100

No

Yes‡

100

100

C730-311PB

C730-313PB

17.3"

17.3"

440 mm

440 mm

20/34.5 kV

20/34.5 kV

*Suffix: P = Parallel-groove clamps [No. 6 solid through 4/0 ACSR (13.3mm2 - 160.6mm2) or 250 kcmil stranded (167.5mm2)]B = NEMA Heavy Duty “B” bracket with 11⁄2" captive bolt

Terminal variations:P = Parallel-groove clamps [No. 6 solid through 4/0 ACSR (13.3mm2 - 160.6mm2) or 250 kcmil stranded (167.5mm2)]E = Small eyebolt [No. 8 solid through 2/0 stranded (7.7 - 90mm2)]

Change “P” to “E;” e.g., C730-112EBL = Large eyebolt [No. 6 solid through 4/0 stranded (13.3 - 160.6mm2) or 250 kcmil stranded (167.5mm2)]

Change “P” to “L;” e.g., C730-112LBBracket variations:

B = NEMA Heavy Duty “B” bracket with 11⁄2" captive boltX = Extended bracket (horizontal section 25⁄8" longer than NEMA Type B bracket)

Change “B” to “X;” e.g., C730-112PXD = Pole mounting bracket Change “B” to “D;” e.g., C730-112PD

(Blank) = Without crossarm bracket Drop “B” from Catalog No.; e.g., C730-112PExtra corrosion resistance:

Not Available**Momentary rating — Solid blade†For application on single-phase to neutral circuits with phase-to-ground voltages not exceeding the value to the left of theslant; and for application on three-phase solidly-grounded-wye systems with solidly-grounded loads with line-to-line voltagesnot exceeding the value to the right of the slant.‡Must use removable buttonhead fuse links.

20/34.5 kV,150 kV BIL

15 kV, 110 kV BIL▼

15/27 kV,125 kV BIL

Specifications and Ordering InformationAll Type C Cutouts meet or exceed ANSI/NEMA specifications.

ReplacementFusetube

CapP700-1535PE700-1767PE700-2146PP700-1535P

25.1 / 11.425.3 / 11.526.0 / 11.825.5 / 11.6

P700-1535PE700-1768PE700-2479PP700-1535P

30.9 / 14.0

31.1 / 14.1

P700-1535P

E700-1768P

Page 13: 10A-1 10A CUTOUTS (Standard, Linkbreak & Loadbreak) and ... · 10A-1 HUBBELL / CHANCE – CENTRALIA, MISSOURI MAY 2005 ® ® Printed in USA Section 10A CUTOUTS (Standard, Linkbreak

10A-13

HUBBELL / CHANCE – CENTRALIA, MISSOURI MAY 2005

®®

3.3 lb.3.5 lb.4.1 lb.3.6 lb.

CutoutCatalogNumber

C730-112PBC730-114PBC730-143PBC730-133PB

1.5 kg.1.6 kg.1.9 kg.1.6 kg.

15 kV (110 kV BIL)Mounting

Assembly only*Catalog No.

T730-1MMPB

Fuseholder orBlade onlyCatalog No.T730-112TT730-114TT730-143TT730-133T

8.4 kg.18.6 lb.

Weight Weight

20/34.5 kV (150 kV BIL)C730-311PBC730-313PB

T730-311TT730-313T

3.6 lb.3.8 lb.

1.6 kg.1.7 kg. 12.1 kg.26.6 lb.T730-3MMPB

3.6 lb.3.8 lb.4.4 lb.4.0 lb.

9.4 kg.20.8 lb.T730-2MMPB

1.6 kg.1.7 kg.2.0 kg.1.8 kg.

T730-211TT730-213TT730-242TT730-233T

15/27 kV (125 kV BIL)C730-211PBC730-213PBC730-242PBC730-233PB

20/34.5 kV — T730-3MMPB15/27 kV — T730-2MMPB

15 kV — T730-1MMPB

200A100A 300A

300ABladeFuseholders

100A 200A

Type CLOADBREAK CutoutFuseholders and Mounting Assemblies

Replacement Arc Chute Interrupter: Catalog No. T730-0080 (1.2 lb. / 0.54 kg.)

Page 14: 10A-1 10A CUTOUTS (Standard, Linkbreak & Loadbreak) and ... · 10A-1 HUBBELL / CHANCE – CENTRALIA, MISSOURI MAY 2005 ® ® Printed in USA Section 10A CUTOUTS (Standard, Linkbreak

10A-14

MAY 2005 HUBBELL / CHANCE – CENTRALIA, MISSOURI

®®

Direct

Direct

Direct

Small BlockNormal Duty

5 kA

Large BlockHeavy Duty

10 kA

RiserPole

Oh

io B

rass

9

DL

EL

FL

10

DM

EM

FM

18

DN

EN

FN

27

DP

EP

FP

125 &150 150110

Polymer

Metal Oxide Varister (MOV)OperatingDesign

Housing

kV BILfor Cutout

kV RatingMC

OV

Du

ty C

ycle

kV R

atin

g

Arr

este

r Man

ufa

ctu

rer

Selection considerations:

Refer to the matrix at right and insert the letters of thedesired combination in place of the “0” and “dash” in the TypeC Cutout Catalog Number.

Example: C710-112PB cutoutwith large-block 10 kV arrester would beC71EM112PB cutout-arrester combination.

G233⁄4" (603 mm)251⁄2" (648 mm)251⁄2" (648 mm)28" (711 mm)

E22" (559 mm)

263⁄4" (679 mm)263⁄4" (679 mm)321⁄2" (826 mm)

kV BIL110125150170

Arrester Selection Guide for Cutout-Arrester Combinations

Type CCUTOUT-ARRESTER COMBINATIONS

15 kV cutout with direct-connected Ohio Brass large-block, MOV, polymer 9 kV lightning arrester

Advantages of combinationChance cutout-arrester combinations cost less than the totalcost of separately purchased components. The combinationunits install faster, more economically and take up less spacein storage, transit and service. Each combined unit takes upa minimum of space on the crossarm and has a favorableweight distribution for minimal off-center loading. The field-

Over-the-Arm Type only

Cutout-ArresterDimensions

How to determine entries for positions 4 and5 in Catalog Number, on page 10A-17 —

Arr

este

rC

on

nec

tio

nM

eth

od

13"(330 mm)

proven quality of both cutout and arrester assure consistenthigh performance for the combinations.

These units include Chance cutouts fitted with only OhioBrass® MOV arresters, superseding previous silicon-carbideunits. For easy conversion to the new arrester designationsystem, refer to the Cutout Cross-Reference Guide, Bulletin10-0203.

Note:Arresters can be combined with any Type C Cutout:Standard, Linkbreak, Loadbreak, ElectronicSectionalizer or Loadbreak Sectionalizer (see Cata-log Section 10 D for Sectionalizers).

Page 15: 10A-1 10A CUTOUTS (Standard, Linkbreak & Loadbreak) and ... · 10A-1 HUBBELL / CHANCE – CENTRALIA, MISSOURI MAY 2005 ® ® Printed in USA Section 10A CUTOUTS (Standard, Linkbreak

10A-15

HUBBELL / CHANCE – CENTRALIA, MISSOURI MAY 2005

®®

Interrupting or MomentaryCurrent (Amps)

1 = 8,0002 = 10,000 (27kV must useremovable buttonhead links)

3 = 12,000 (All must useremovable buttonhead links)

4 = 16,000 (All must useremovable buttonhead links)

M = Mounting ass’y. only

Type C Cutouts

For cutout-arrester combinations,see table below for two-letter arrester codes.

7C

Position 10:Bracket Variations

B = NEMA Heavy Duty “B” bracket for crossarm (11⁄2" bolt)X = Extended type bracket for crossarm (Horizontal section

is 25⁄8" longer than Type B bracket)D = D-shape bracket (pole)Z = No bracket (must be used with M or S in position 11)Blank = No bracket (cannot use with M or S in position 11)

Position 11:Blank = No option (may not be used with Z in

position 10)

M = ‡Mechanical Assist Fuseholder

S = ‡Extra Corrosion Resistance for 150 and 170BIL only; 3 or 6 must be in position 6.Not available on Loadbreak cutouts.

‡May not be used with Blank in position 10.

Position 9:Terminal Variations

(tin plated)P = Parallel-groove

clampsE = Small eyeboltsL = Large eyebolts

T = Fuseholder only(enter T in position 1and leave Blankpositions 10 & 11)

Positions 4 & 5:

O No arrester

*Position 6:Type C Cutout — kV Rating

STANDARD100 amp

1527273636

200 amp

1527272727

300 amp

1527273636

LINKBREAK100 amp

1515/27

22/36.422/36.4

LOADBREAKBIL,kV110125150170170

No.

12367

100 amp

1515/27

20/34.5

200 amp

1515

300 amp

1515/27

Position 3:Kind

1 = Standard2 = Linkbreak3 = Loadbreak4 = †Electronic Sectionalizer5 = †Loadbreak Sectionalizer

†See Section 10D for positions 7 & 8.

*Position 7:Continuous

Current1 = 100 Amps(Accepts 1–100 Amp links)

3 = 300 Amps solid blade

4 = 200 Amps(Accepts 140–200 Amp links)

M = Mounting ass’y. only

*Position 8:

*Not all combinations of kV Rating, Continuous CurrentRating and Interrupting Rating (Positions 6, 7 & 8) areavailable. See preceding pages for combinations offered ineach kind of cutout (Standard, Linkbreak, Loadbreak).

Accessories

Catalog No.T700-1325T700-1326T700-1327

Terminal ConnectorsMinimum Order Quantity

101010

DescriptionParallel-Groove Clamp, tin-plated bronze forNo. 6 solid thru 4/0 ACSR or 250 kcmil strandedSmall Eyebolt for No. 8 solid thru 2/0 strandedLarge Eyebolt for No. 6 solid thru 4/0 ACSR or 250 kcmil stranded

C206-0283C206-0280C206-0299C206-0632

Mounting Brackets————

NEMA Heavy Duty “B” Bracket with 2" captive bolt for crossarm mountingExtended Crossarm Bracket (Horizontal section is 25⁄8" longer than NEMA “B” bracket)“D” Pole Mounting BracketCutout/Arrester Bracket complete with carriage bolts and backstrap

Direct

Direct

Direct

Small BlockNormal Duty

5 kA

Large BlockHeavy Duty

10 kA

RiserPoleO

hio

Bra

ss

9

DL

EL

FL

10

DM

EM

FM

18

DN

EN

FN

27

DP

EP

FP

125 &150

150110

Polymer

Metal Oxide Varister(MOV)

OperatingDesign

Housing

kV BILfor Cutout

kV RatingMC

OV

Du

ty C

ycle

kV R

atin

g

Arr

es

ter

Ma

nu

fac

ture

r

Arr

este

rC

on

nec

tio

nM

eth

od

Basic format: C 7 X X X X X X X X XPositions: 1 2 3 4 5 6 7 8 9 10 11CATALOG NUMBER SYSTEM

Page 16: 10A-1 10A CUTOUTS (Standard, Linkbreak & Loadbreak) and ... · 10A-1 HUBBELL / CHANCE – CENTRALIA, MISSOURI MAY 2005 ® ® Printed in USA Section 10A CUTOUTS (Standard, Linkbreak

Web: http://www.hubbellpowersystems.comE-mail: [email protected]

®®® ®™

MEXICO

HUBBELL DE MEXICO, S.A. DE. CVAv. Coyoacan No. 1051Col. Del Valle03100 Mexico, D.F.Phone: 52-55-9151-9999Fax: 52-55-9151-9988e-mail: [email protected]

CANADA

HUBBELL CANADA LP870 Brock Road SouthPickering, Ontario L1W 1Z8Phone: 905-839-1138Fax: 905-831-6353e-mail: [email protected]

UNITED STATES

HUBBELL POWER SYSTEMS, INC.210 N. AllenCentralia, Mo 65240-1395Phone: 573-682-5521Fax: 573-682-8714e-mail: [email protected]