107080292_2

download 107080292_2

of 161

Transcript of 107080292_2

  • 7/30/2019 107080292_2

    1/161

    January 2010

    Phase 2 Report on Environmental Building

    Regulations & Guidelines to achieve Energy

    Efficiency in Bangalore City

    Prepared for

    Renewable Energy & Energy Efficiency Partnership

    Vienna International Center, Austria

    w w w . t e r i i n . o r g

    www.teriuniversity.ac.in

  • 7/30/2019 107080292_2

    2/161

    The Energy and Resources Institute 2010

    Suggested format for citation

    T E R I. 2010

    Development of Building Regulations and Guidelines for Energy

    Efficiency, Bangalore City

    The Energy and Resources Institute. 154 pp.

    [Project Report No. 2009BS03]

    For more information

    T E R I University Tel. 25356590

    Centre for Research on Sustainable [email protected] Science Group(CRSBS) Fax25356589Southern Regional Centre Webwww.teri in.orgBangalore 560 071 India +91 Bangalore (0) 80

    India

  • 7/30/2019 107080292_2

    3/161

    TERI University Project Team

    Ms. Minni Mehrotra

    Ms. Mili Majumdar

    Mr. Pradeep Kumar

    Ms. Priyanka Kochhar

    Dr. Hina Zia

    Mr. T Senthil Kumar

    Mr. Nitish Poonia

    Mr. Kiriti Sahoo

    TERI University Project Advisor

    Dr. A Ravindra, Advisor to Chief Minister of Karnataka (Urban Affairs)

    Mr. P R Dasgupta, I A S (Retd), Senior Advisor & Coordinator for TERI South Regional Centre

    Secretarial Assistance

    Ms. Jyothi

    Acknowledgements

    We are thankful to the Government of Karnataka officials for their full co-operation and support to carry

    this project in Bangalore city. We would like to thank:

    1. Sri Bharat Lal Meena, I.A.S, Commissioner, Bruhat Bengaluru Mahanagara Palike, Narasimha Raja

    Square, Bangalore 560 002

    2. Sri Thirukangowdru, Joint Director Town, Bruhat Bengaluru Mahanagara Palike, Narasimha Raja

    Square, Bangalore 560 002

    3. Sri Siddaiah, I.A.S, Commissioner, Bangalore Development Authority, T. Chowdaiah Road, Kumara

    Park West, Bangalore 560 0204. Sri R. Rangaswamy, Executive Engineer (Electrical) Bangalore Development Authority, T. Chowdaiah

    Road, Kumara Park West, Bangalore 560 020

    5. Sri T. D. Nanjundappa, Engineer Officer-III, Bangalore Development Authority, T. Chowdaiah Road,

    Kumara Park West, Bangalore 560 020

    6. Sri Tushar Girinath, MD, Bangalore Electricity Supply Company Limited, K R Circle Bangalore - 560

    001

    7. Sri B. N. Sathyaprema Kumar, General Manager (HRD), Bangalore Electricity Supply Company

    Limited, K R Circle Bangalore - 560 001

    8. Sri Shivananda Murthy H G, MD, Karnataka Renewable Energy Development Ltd., No.19, Maj. Gen.

    A D Loghanathan, INA Cross, Queen's road., Bangalore - 560052.

    9. Dr H. Naganagouda, Assistant General Manager, Karnataka Renewable Energy Development Ltd.,

    No.19, Maj. Gen. A D Loghanathan, INA Cross, Queen's road., Bangalore - 560052.

  • 7/30/2019 107080292_2

    4/161

    List of Contents

    IN T RODUC T I ON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . . . 1

    EXI S T I N G BY E LAW S & RE V I S I O N S PR O P O S E D . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

    FR A ME W O R K O F EN V I R O N ME N T A L B U I LD I N G RE G U LA T I O N S A N D GU I D E LI N E S

    F O R BA N GA L OR E C I T Y. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

    GUI DELI N E 1: SOLAR PASS I V E DESIGN FOR NEW BUI LDI N G S . . . . . . . . . . . . . . . . . . . .4

    1.1 .1 MA NDA T OR Y CLA US E T O B E IN CL UD E D IN TH E RE V I S E D BY E LA W S . . 41.2 TE C H N I C A L N O T E S F O R SO LA R PA SS IV E DE SI GN F O R N EW B U I LD I N G S . . . . 4

    1.2.1 S O LA R PA S S IV E DE S I G N . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4

    1.2.2 LA N DS CA PI N G . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

    1.2.3 WA T ER B O D I E S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

    1.2.4 O R I E N T A T I O N . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6

    1.2.5 BU I LD I N G F O R M / S U R F A C E T O V O LU ME R A T I O . . . . . . . . . . . . . . . . . . . . . . . .8

    1.2.6 O P T I MI Z A T I O N O F B U I LD I N G E N V E LO P E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8

    1.2.7 WALL S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9

    1.2.8 TH E R MA L S T O R A G E / T H E R MA L C A P A C I T Y . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9

    1.2.9 C O N D U C T A N C E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .91.2.10 TH E R MA L I N S U LA T I O N . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

    1.2.11 OP T I MI Z A T I O N O F R O O F . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

    1.2.12 HE A T G A I N S T H R O U G H R O O F S C A N B E R E D U C E D B Y A D O P T I N G T H E

    F O LLO W I N G T E C H N I Q U E S. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11

    1.2.13 FE N E S T R A T I O N A N D SH A D I N G . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15

    1.2.14 FI N I S H E S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15

    1.2.15 .......BE N E F I T S O F ECBC R E C O MME N D E D E N V E LO P E I N C O MP A R I S O N

    WI T H C ON V EN T IO N AL B UI LDIN G E NV E LO P E F O R A IR C ON DI TI ON E D

    B U I LD I N G S I N BAN G AL O R E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

    1.2.16 EXT E R N A L S H A D I N G O F T H E E N V E LO P E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .171.3 L IF E CY CL E C O ST AN A LY S I S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17

    1.4 DA YL I GHT IN T E G R A T I O N . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

    1.5 BU I LD I N G E N V E LO P E O P T I MI Z A T I O N F O R N A T U R A LLY V E N T I LA T E D

    B U I LD I N G S T O A C H I E V E T H E R MA L C O MF O R T . . . . . .. . . . . .. . . . .. . . . . .. . . . .. . . . 18

    1.6 LO W E N E R G Y PAS SI V E C O O LI N G S T R A T E G I E S F O R BAN GAL OR E . . . . . . . . . . . .21

    1.6.1 VE N T I LA T I O N . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21

    1.6.2 RA DI A TI V E CO OLI N G . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

    1.6.3 SO ME LO W E N E R G Y C O O LI N G & D E S I G N S T R A T E G I E S T H A T C O U LD B E

    A DO P T E D IN R ES I DE NT IA L B UIL DI N GS IN BA N GA L O R E A R E DESC RI BE D

    B E LO W . T H E S E S T R A T E G I E S W E R E A N A LY S E D I N TRNSYS S O F T W A R E . . . . 25

    1.7 EX A M P L E O F A NA T U R AL LYVE N T I LA T E D O F F I C E BU I LD I N G I N BAN GA L OR E

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

    1.8 S U MMA R Y : . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

    1.8.1 NA TUR AL LY V EN T I LA T E D BU IL DI N GS R E COM ME N DA T I ON S . . . . .. . . . . 26

    1.9 GLO S S A R Y : . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . 26

    1.10 RE F E R E N C E: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

  • 7/30/2019 107080292_2

    5/161

    L I G H T I N G MA N UF A C T UR ER CO N TA CT DE T A IL S . . . . .. . . . . .. . . . .. . . . . .. . . . . .. . . . . . . 27

    GUI DELI N ES 2: P ROVI DE ROOF T REAT M EN T T O C UT H EAT G AI N S . . . . . .. . . . .. . . . 28

    2. 1 MAN D A T OR Y CL A U SE T O B E I NC LU DE D IN T HE RE V I S E D BY E LA W S . . .. . .. . 2 8

    2. 2 T E C H N I C A L G U I D A N C E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

    2.2.1 BR I E F IN T R O D U C T I O N . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

    2.2.2 H E A T G A I N S T H R O U G H R O O F S C A N B E R E D U C E D B Y A D O P T I N G T H E

    F O LLO W I N G T E C H N I Q U E S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

    2.2.3 WH Y I S T H I S R E Q U I R E D? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

    2.2.4 HO W I S I T B E N E F I C I A L? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

    2. 3 GLO S S A R Y : . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

    2. 4 RE F E R E N C E S: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

    GUI DELI N E 3: WI N DOWDESIGN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

    3. 1 FO R A I R - C O N D I T I O N E D B U I LD I N G S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

    3. 2 FO R NO N-C O N D I T I O N E D B U I LD I N G S. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

    3.3.1 WI N D O W S I N AI R-CO N D I T I O N E D B U I LD I N G S . . . . .. . . . . .. . . . . .. . . . . .. 41

    3.3.2 WI N D O W S I N N ON -C O N D I T I O N E D B U I LD I N G . . . . .. . . . . .. . . . . .. . . . . .. 46

    3.3.3 WI N D O W D E S I G N F O R NA T UR A L V E N TI L A TI ON . . . . .. . . . . .. . . . .. . . . . . 50

    3. 4 GLO S S A R Y . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . 54

    3. 5 RE F E R E N C E S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54

    GUI DELI N E 4: EN ERG Y EFFI C I EN C Y I N ART I FI C I AL LIGHTING . . . . . .. . . . .. . . . . . 56

    4.1.1 FOR B U I LD I N G S W I T H C O N N E C T E D E LE C T R I C A L LO A D MO R E T H A N

    100 K W. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . . 56

    4.1.2 FO R RE S I D E N T I A L B U I LD I N G S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56

    4.2.1 C O MME R C I A L & RE S I D E N T I A L B U I LD I N G S . . . . . .. . . . .. . . . . .. . . . .. . . . . 57

    4.3.1 EF F I C I E N C Y I N AR T I F I C I A L L I G H T I N G SC H E ME . . . . .. . . . . .. . . . .. . . . . . 58

    4.3.2 EXT E R N A L L I G H T I N G . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58

    4.3.3 IN T E R N A L L I G H T I N G F O R N EW C O MME R C I A L B U I LD I N G S . . .. . .. . .. 61

    4.3.4 RE T R O F I T T I N G O P T I O N S I N EXI S T I N G C O MME R C I A L B U I LD I N G S . . . .774.3.5 IN T E R N A L L I G H T I N G F O R N EW RE S I D E N T I A L B U I LD I N G S . . . . . . . . . . .77

    4.3.6 RE T R O F I T T I N G O P T I O N S I N EXI S T I N G R E S I D E N T I A L B U I LD I N G S . . . 8 0

    GUI DELI N E 5: EN ERG Y EFFI C I EN T AIR CON DI T I ON I N G SY ST EM DESI G N FOR

    BUI LDI N G S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83

    5. 1 GU I D E LI N E: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83

    5.1.1 MAN DA T OR Y CL A U SE T O B E I N CL U DE D IN T H E RE V I S E D BY E LA W S 83

    5. 2 TE C H N I C A L N O T E S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83

    5.2.1 AI R C O N D I T I O N I N G . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83

    5.2.2 GU I D E LI N E S O N O P T I MI Z A T I O N O F C O O LI N G LO A D E S T I MA T I O N . .. 8 4

    5.2.3 GU I D E LI N E S O N AHU S P E C I F I C A T I O N S T O A C H I E V E E N E R G Y E F F I C I E N C Y . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87

    5.2.4 GU I D E LI N E S F O R E N E R G Y E F F I C I E N T C H I LLE R S . . . . .. . . . . .. . . . .. . . . . 90

    5.2.5 GU I D E LI N E S F O R E N E R G Y E F F I C I E N T C O O LI N G T O W E R . . . . . .. . . . . .. 93

  • 7/30/2019 107080292_2

    6/161

    GUI DELI N E 6: REPLACE EXISTING EQUIPMENT BY MINIMUM 3 ST AR RAT ED

    BEE LABELED AP P LI AN C ES EQUI P M EN T AN D USE M I N I M UM 3 ST AR

    RATED BEE LABELED AP P LI AN C ES/ EQUI P M EN T I N ALL N EW

    BUI LDI N G S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94

    MA N DA T O R Y R EQ UI R EM EN T I N ALL P RO C UR EM EN T N O RM S FO R G O V ERNM E N T

    A ND P UB LIC BU IL DIN G S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94

    6.1.1 S T A R R A T I N G F O R F R O S T F R E E R E F R I G E R A T O R . . . . .. . . . . .. . . . .. . . . . . 96

    6.1.2 ST A R RA TI N G - RO OM AIR C O N D I T I O N E R S . . . . . .. . . . .. . . . . .. . . . .. . . . . 97

    6.1.3 ST AR RA T IN G - D I R E C T C O OL RE F R I G E R A T O R . . . . .. . . . . .. . . . . .. . . . . . 97

    6.1.4 ST A R RA TI N G PL A N: C E I LI N G FA N S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98

    6.1.5 STAR RAT IN G P L AN : ELE C T R I C GE Y S E R S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99

    6.1.6 ST A R RA TI N G PL A N CO L O U R T E LE V I S I O N S. . . . . . . . . . . . . . . . . . . . . . . . . .100

    6.1.7 WH Y I S T H I S R E Q U I R E D? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .103

    6.1.8 H O W I S I T B E N E F I C I A L? . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .103

    GUI DELI N E 7: SOLARWA TE R HEATING SY ST EM S F OR DOM EST I C AN D

    C OM M ERC I AL BUI LDI N G S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .105

    7.1 MAN D AT OR Y R E QUIR EM EN T IN BY EL AW. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .105

    7.2.1 G U I D E LI N E S F O R D E S I G N , I N S T A LLA T I O N , A N D U S E O F S O LA R W A T E R

    H E A T I N G S Y S T E MS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .109

    7.2.2 GU I D E LI N E S F O R S Y S T E M S E LE C T I O N A N D U S E . . . . . . . . . . . . . . . . . . . . . 110

    7.2.3 GU I D E LI N E S F O R I N S U LA T E D H O T W A T E R P I P I N G . . . . . .. . . . . .. . . . . . 110

    7.2.4 H O W I S I T B E N E F I C I A L? /WH Y I S T H I S R E Q U I R E D? . . . . . .. . . . .. . . . . . 111

    GUI DELI N ES 8: EN ERG Y EFFI C I EN T ELEC T RI C AL SY S T EM S FOR BUI LDI N G S 116

    8. 1 GU I D E LI N E F O R EN E R G Y EF F I C I E N T ELE C T R I C A L S Y S T E MS F O R B U I LD I N G

    . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116

    8.1.1 MAN D A T OR Y CL A U SE T O BE INC LU DED I N T HE RE V I S E D BY E LAW S 116

    8. 2 TE C H N I C A L N O T E S F O R ELE C T R I C A L S Y S T E MS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116

    8.2.1 G U I D E LI N E S I N ELE C T R I C A L S Y S T E M D E S I G N . . . . .. . . . . .. . . . . .. . . . . . 1168.2.2 GU I D E LI N E S O N O P T I MI Z A T I O N O F E LE C T R I C A L L O A D . . . . . .. . . . .. . 117

    8.2.3 GU I D E LI N E S O N T R A N S F O R ME R RA T IN G AN D SE LE C T I O N . . . . .. . . . 119

    8.2.4 GU I D E LI N E S O N S E LE C T I O N O F ELE C T R I C A L MO T O R S . . . . . . . . . . . . .120

    8.2.5 G U I D E LI N E S O N I MP R O V E ME N T O F P O W E R F A C T O R . . . . . . . . . . . . . . . . 122

    8.2.6. GU I D E LI N E S O N C H E C K ME T E R I N G A N D MO N I T O R I N G . . . . . .. . . . . . 125

    8.2.7 GU I D E LI N E S O N D I S T R I B U T I O N S Y S T E M LO S S E S . . . . . . . . . . . . . . . . . . . . 126

    8.2.8 GUIDELINES ON P O W E R B A C K U P S Y S T E MS . . . . . . . . . . . . . . . . . . . . . . . . . 129

    8.2.9 GUIDELINES ON P OWER Q U A LI T Y . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131

    GUI DELI N E 9: PERFORM M AN DAT ORY EN ERG Y AUDI T FOR EX I ST I N G

    C OM M ERC I AL BUI LDI N G S WI T H C ON N EC T ED LOAD OF C ASES OF 50 0 KW OR 600 KVA AN D AP P LY EN ERG Y C ON SERVAT I ON M EASURES T O

    REDUC E EN ERG Y C ON SUM P T I ON I N EX I ST I N G

    C OM M ERC I AL/I N ST I T UT I ON AL BUI LDI N G S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133

    9. 1 GU I D E LI N E: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133

    9.1.1 MAN D AT OR Y R E QUIR EM EN T . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133

  • 7/30/2019 107080292_2

    7/161

    9. 2 GU I D A N C E NO T E S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133

    9. 3 EN E R G Y D E MA N D A N D C O N S U MP T I O N . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134

    9. 4 AU D I T O F I N D I V I D U A L S Y S T E MS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137

    9.4.1 ELE C T R I C A L S Y S T E M . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137

    9.4.2 L I G H T I N G SY ST EM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .139

    9.4.3 HVAC S Y S T E M . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .144

    9. 5 C O N T R O LS I N T H E HVAC S Y S T E M R E C O MME N D E D B Y EN E R G Y

    CO N S E R V A T I O N B U I LD I N G C O DE (ECBC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 152

    9. 6 BE N E F I T S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . 153

    9. 7 GLO S S A R Y . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .. . . . . . 153

  • 7/30/2019 107080292_2

    8/161

    INTRODUCTION

    In phase II of the project framing of environmental building regulations and guidelines to

    achieve energy efficiency and integrate renewable energy in Bangalore city is completed.

    It is proposed that the recommended regulations shall become a part of the existing

    building bye laws of Bangalore city and a separate document on guidelines will be

    published. This separate guidelines document will be available along with the building byelaws of Bangalore for the citizens of Bangalore city.

    The study in the phase II was divided into two parts.

    1. Study of existing building bye laws of Bangalore and identify sections which could

    be improved or detailed out for achieving energy efficiency in Buildings in

    Bangalore city.

    2. A set of guidelines and regulations are proposed to achieve energy efficiency and

    integrate renewable energy in the city.

    Existing Bye Laws & Revisions Proposed

    Under General Building Requirements following sections have been identified which need

    revision or detailing.

    Section 3.1.6 & 3.1.7, Width of road & Means of access

    According to the regulation, F.A.R and height of the building shall be regulated according to

    the width of public street or road. This is important to integrate daylight and natural

    ventilation inside the buildings.

    Revisions Proposed

    This section has been detailed out. Relation between Height of building & separation

    between two buildings has been established with respect to WWR (Window Wall Ratio) andLight transmittance of glass required for various Height / Separation ratio. This is included

    in optimization of window design guideline.

    Section 3.2 3 Basements

    According to the existing bye law, when basement is used for car parking, the convenient

    entry and exit shall be provided. Adequate drainage, ventilation, lighting arrangements and

    protection against fire shall be made to the satisfaction of the authority.

    Revisions proposed

    The daylight and natural ventilation requirement for basements will be specified in detail in

    the existing bye laws.

  • 7/30/2019 107080292_2

    9/161

    2 Phase 2 Report on Environmental Building Regulations and Guidelines

    framed fro Bangalore City

    Section 3.3 Requirements of Building Services

    3.3.1 Lighting and ventilation requirements

    Natural ventilation and area of opening

    According to the existing bye laws, rooms shall have, for admission of light and air, one or

    more openings. Minimum aggregate area of openings excluding doors, shall not be less

    than 1/6th

    of the floor area in case of residential buildings. In case of other public buildingslike institutes, offices, hospitals etc minimum aggregate area of opening shall be not less

    than 1/5th of the floor area.

    Proposed guideline

    There is a separate guideline framed on optimization of window design for air conditioned

    and non air conditioned buildings.

    Section 3.3.3 Transformer

    According to the existing bye laws, where the specified load is 25kW or more a space for

    locating the distribution transformers and associated equipment as per KERC code leaving

    3.0m from the building and without obstructing the fire driveway within the premises has

    to be provided.Revisions proposed

    A separate guideline along with some mandatory clause has been framed for installation

    and design of energy efficient electrical system in buildings. This includes a mandatory

    requirement of Transformers to comply with Energy Conservation Building Code (ECBC) of

    India requirements.

    Section 3.3.5 Electrical installations, Air conditioning and heating

    According to the existing bye laws, the planning, design and installation of air conditioning

    and heating installations of the building shall be in accordance with Part VIII of the

    National Building Code of India.

    Revisions proposedA separate guideline along with some mandatory clause has been framed for design of

    energy efficient air conditioning system for buildings in Bangalore.

    Section 3.4.10 Solar energy

    According to the existing bye laws,

    Solar lighting and solar water heating is mandatory for all new

    development/construction for different categories of buildings. If solar lighting and

    solar water heating is adopted, then refundable security deposit on fulfilling the

    conditions shall be returned with 2% interest.

    Solar photovoltaic lighting systems shall be installed in multi unit residential

    buildings (with more than five units) for lighting the set back areas and drive ways.

  • 7/30/2019 107080292_2

    10/161

    3 Phase 2 Report on Environmental Building Regulations and Guidelines

    framed fro Bangalore City

    Revisions proposed

    In the existing bye law, the requirements for different building types are not clear;

    this has been proposed in a separate guideline. Further incentives will be framed for

    all mandatory regulations in phase 3 of this project.

    For external solar lighting integration, separate guideline and mandatory clause has

    been framed.

    Frame work of Environmental Building Regulations and Guidelines forBangalore CityPart II of this report below comprises of the environmental building guidelines and

    mandatory regulations framed for Bangalore city to achieve energy efficiency and integrate

    renewable energy. Briefly 9 sections of guidelines & regulations have been framed, which

    are described below and further detailed out later.

    1. Solar passive design integration in new buildings.

    2. Provide roof treatment to cut heat gains.

    3. Window design for day lighting, ventilation and to reduce solar heat gains.

    4. Artificial lightinga. Energy efficient external lightingb. Renewable energy based external lightingc. Efficient indoor lighting for new commercial buildings, follow ECBC

    prescriptive / mandatory criteria for lighting design

    d. Efficient indoor lighting for new residential buildingse. Retrofit options for existing commercial buildings

    f. Retrofit options for existing residential buildings

    5. Energy efficient air conditioning design for buildings.

    6. Use of BEE labeled equipments and appliances to achieve energy efficiency innew and existing buildings.

    7. Solar water heating systems for residential and commercial buildings.

    8. Energy efficient electrical systems for building

    9. Perform mandatory energy audit for existing commercial buildings with

    connected load in cases of 500kW or 600KVA and reduce energy consumptionby 20% over previous year.

  • 7/30/2019 107080292_2

    11/161

    GUIDELINE 1: Solar Passive Design for New Buildings

    1.1 Guideline for Solar Passive design for New Buildings

    Achieve thermal and visual comfort inside the building by

    using natural energy sources and sinks, such that there is

    significant reduction in energy consumption by

    conventional air conditioning and artificial lighting in a

    building.

    1.1.1 Mandatory clause to be included in the Revised Bye Laws

    Design external shading for windows to protect heat gains from direct solar radiation and

    for protection against rain. In air conditioned buildings windows should comply with ECBC

    requirement. Roof should either comply with ECBC requirements or should be shaded.

    Table 1.1: Roof assembly U-factor requirements as per ECBC 2007

    Climate zone 24-Hour use buildings

    Hospitals, Hotels, Call centers etc.

    Daytime use buildings

    Other building Types

    Maximum U-factor of the overall assembly (W/m2K) Maximum U-factor of the overall assembly

    (W/m2K)

    Moderate U-0.409 U-409

    Vertical Fenestration U-factor and SHGC Requirements (U-factor in W/m2K)

    ClimateMaximum U-factor (W/m2-

    K)Maximum SHGC for

    WWR 40%Maximum SHGC for

    40%

  • 7/30/2019 107080292_2

    12/161

    5 Phase 2 Report on Environmental Building Regulations and Guidelines

    framed fro Bangalore City

    Figure 1.1: Water and trees as landscape

    elements at Sangath, Ahmedabad

    architecture design features and taking advantage of existing natural resources on the site.

    Designers can achieve energy efficiency in the buildings they design by studying the macro

    and micro climate of the site, applying solar passive and bio climatic design features and

    take advantage of natural resources on site.

    Designers can achieve solar passive building design by following the below mentioned

    steps.

    1. Modulating the microclimate of the site through landscaping

    2. Optimization of orientation and building form

    3. Optimization of building envelope and window design to reduce cooling demand

    4. Daylight integration to reduce artificial lighting demand.

    5. Low energy passive cooling strategies

    1.2.2 LandscapingLandscaping by vegetation is one of the most effective ways

    of altering micro climate for better conditions. Trees

    provide buffer to sun, heat, noise, air pollution.

    Landscaping can be used to direct or divert the air flow

    advantageously. Trees help to shade the building from

    intense direct solar radiation. Tree species could be

    selected depending upon climate zone and building design.

    Deciduous trees for example, provide shade in the summer

    and sunlight in the winter when their leaves fall. Planting

    them on West and South West orientation of a building

    provides natural shade. Evergreen trees provide shade and

    wind control round the year. Natural cooling without air conditioning can be achieved by

    locating trees to channel cool breeze inside the buildings. Additionally, the shade created by

    trees, reduces air temperature of the micro climate around the building through evapotranspiration. Properly designed roof gardens help to reduce heat loads in a building.

    1.2.3 Water BodiesWater has a moderating effect on the air temperature of the micro climate. It possess very

    high thermal storage capacity much higher than the building materials like Brick, concrete,

    stone. A large body of water in the form of lake, river, fountain has the ability to moderate

    the air temperatures in the micro climate. Water evaporation has a cooling effect in the

    surroundings. It takes up heat from the air through evaporation and causes significant

    cooling.

  • 7/30/2019 107080292_2

    13/161

    6 Phase 2 Report on Environmental Building Regulations and Guidelines

    framed fro Bangalore City

    Figure 1.2: Average daily solar radiation received on North orientation facade

    1.2.4 OrientationIn solar passive buildings, orientation is a major design consideration, mainly with regard

    to solar radiation, daylight and wind. The orientation of the building should be based on

    whether cooling or heating is predominant requirement in the building. The amount of

    solar radiation falling on a surface varies with orientation. In tropical climate zones for

    example, North Orientation receives solar radiation with minimum intensity as seen infigure 2. Thus in tropical climate like India long facades of buildings oriented towards

    North South are preferred. South orientation receives maximum solar radiation during

    winters which is preferable. East and West receive maximum solar radiation during

    summer. West is a crucial orientation because high intensity of solar radiation is received

    during evening hours, when the internal gains are also at its peak. Thus, designers need to

    be very careful while designing West faade and spaces behind west faade. Orientation also

    plays an important role with respect to wind direction. At building level, orientation affects

    the heat gain through building envelope and thus the cooling demand, orientation may

    affect the daylight factor depending upon the surrounding built forms, and finally the

    depending upon the windward and leeward orientation fenestration could be designed to

    integrate natural ventilation

  • 7/30/2019 107080292_2

    14/161

    7 Phase 2 Report on Environmental Building Regulations and Guidelines

    framed fro Bangalore City

    Figure 1.3: Average daily solar radiation received on South orientation facade

    Figure 1.4: Average daily solar radiation received on East orientation facade

  • 7/30/2019 107080292_2

    15/161

    8 Phase 2 Report on Environmental Building Regulations and Guidelines

    framed fro Bangalore City

    Figure 1.5: Average daily radiation received on West orientation facade

    1.2.5 Building form / surface to volume ratio

    Thermal performance of volume of a space inside the building has direct relationship withthe area of the envelope enclosing that volume. This parameter known as the S/V (Surface /

    volume) ratio, is determined by the building form. Building form affects solar access and

    wind exposure as well as the rate of heat gain and heat loss through the external envelope. A

    compact building gains less heat during the daytime and losses less heat at night. In

    Bangalore, buildings that are compact and have low S/V ratio to reduce heat gains are

    preferred. Four building geometries were studied for Bangalore climate zone to analyse the

    most efficient form which gains minimum heat gain from the external surfaces. These were

    square, rectangular, courtyard and circular.

    In Moderate climate zone of Bangalore, the Energy Performance Index (EPI) of circular

    building is lowest, in comparison to other building forms. This is because circular buildinghas the lowest Surface to Volume ratio. It is observed in VisualDOE software results that

    due to circular geometry, the conduction gains from the building envelope as well as solar

    gains from windows are least, in circular geometry in comparison to other building

    geometries.

    The building form also determines the air flow around the building and hence the

    ventilation rates inside. Circular form of building is an aerodynamic form which would also

    help enhance natural ventilation inside the building. The depth of the building determines

    the amount of daylight which can penetrate inside the building. Deeper the building, more

    artificial lights required which is not preferred in an energy efficient building.

    1.2.6 Optimization of building envelope

  • 7/30/2019 107080292_2

    16/161

    9 Phase 2 Report on Environmental Building Regulations and Guidelines

    framed fro Bangalore City

    Choice of building material for the envelope is important to reduce the energy consumption

    of the building, through reduced solar heat gain or loss thus reducing air conditioning

    loads. Optimized selection of building material for external envelope also plays an

    important role in achieving thermal comfort in buildings where thermal comfort is achieved

    through passive cooling strategies such as natural ventilation.

    Building envelopeBuilding envelope components are the key determinants of the amount of heat gain or loss

    and wind that enters inside the building. The important components of building envelope

    which affect the performance of the building are:

    Walls

    Roof

    Windows

    Surface finishes

    1.2.7 Walls

    Walls are a major part of the building envelope, which are exposed to external environmentconditions (solar radiation, outside air temperature, wind, precipitation). The composition

    of wall and thereby its heat storing capacity and heat conduction property has a major

    impact on indoor thermal comfort in naturally ventilated buildings and on cooling loads in

    air conditioned buildings. The wall material, thickness, finishes should be selected

    according to climate zone and buildings comfort requirement.

    1.2.8 Thermal storage / thermal capacityThermal capacity is the measure of the amount of energy required to raise the temperature

    of a layer of material, it is a product of density multiplied by specific heat and volume of the

    construction layer. The main effect of heat storage within the building structure is to

    moderate fluctuation in the indoor temperature.

    In a building system, we can understand thermal mass as the ability of a building material

    to store heat energy to balance the fluctuations in the heat energy requirements or room

    temperature in the building due to varying outside air temperature. The capacity to store

    heat depends upon the mass and therefore on the density of the material as well as on its

    specific heat capacity. Thus, high density materials such as concrete, bricks, stone are said

    to have high thermal mass owing to their high capacity to store heat while lightweight

    materials such as wood, or plastics have low thermal mass. The heat storing capacity of

    building materials help achieve thermal comfort conditions by providing a time delay. This

    thermal storage effect increases with increasing compactness, density and specific heat

    capacity of materials.

    1.2.9 ConductanceConductivity (K) is defined as the rate of heat flow through a unit area of unit thickness of

    the material, by a unit temperature difference between the two sides. The unit is W/mK

    (Watt per metre - degree Kelvin). The conductivity value varies from 0.03 W/mK for

  • 7/30/2019 107080292_2

    17/161

    10 Phase 2 Report on Environmental Building Regulations and Guidelines

    framed fro Bangalore City

    insulators to 400W/mK for metals. Materials with lower conductivity are preferred, as they

    are better insulators and would reduce the external heat gains from the envelope.

    1.2.10 Thermal insulationThermal insulation plays an important role in reducing the conductance or U value

    (W/m2K) of walls and roof. Insulation should always be placed on the hotter side of the

    surface.Thermal mass is not a substitute of insulation; in fact a high thermal mass material is

    usually not a good thermal insulator. Buildings should use insulation in combination with

    heat storing material. This storing mass should be placed towards the inside in passively

    cooled buildings.

    Energy Conservation Building Code (ECBC) requirement for external walls

    For air conditioned buildings, ECBC recommends thermal performance for external opaque

    walls. These are mentioned below:

    Climate zone 24-Hour use buildings

    Hospitals, Hotels, Call centres etc.

    Daytime use buildings

    Other building Types

    Maximum U-factor of the overall assembly (W/m2K) Maximum U-factor of the overall assembly (W/m2K)

    Moderate U-0.440 U-440

    1.2.11 Optimization of roofFig 1.6, shows the intensity of solar irradiation is maximum on the horizontal plane which is

    the roof. Conductance of heat from the roof can be very high if not insulated well. This can

    result in increased cooling load if the space below is air conditioned or high discomfort

    hours if the space below is naturally ventilated.

    Figure 1.6: Average daily Intensity of solar radiation incident on horizontal roof surface in Bangalore

  • 7/30/2019 107080292_2

    18/161

    11 Phase 2 Report on Environmental Building Regulations and Guidelines

    framed fro Bangalore City

    1.2.12 Heat gains through roofs can be reduced by adopting the followingtechniques.

    Green roof concept

    Green roofs have the potential to improve the thermal

    performance of a roofing system through shading, insulation,

    evapo transpiration and thermal mass, thus reducing a buildings

    energy demands for space conditioning. The green roof

    moderates the heat flow through the roofing system and helps in

    reducing the temperature fluctuations due to changing outside

    environment. Figure 1.7: Roof of buildings with roof garden

  • 7/30/2019 107080292_2

    19/161

    12 Phase 2 Report on Environmental Building Regulations and Guidelines

    framed fro Bangalore City

    Green roof is a roof of a building that is partially or

    completely covered with vegetation and soil that is planted

    over waterproofing membrane. If widely used green roofs can

    also reduce the problem of urban heat island which would

    further reduce the energy consumption in urban areas.

    Use of high reflective material on roof top

    Use light coloured roofs having an SRI (solar reflectance

    index) of 50% or more. The dark coloured, traditional

    roofing finishes have SRI varying from 5 - 20%. A good

    example of high SRI is the use of broken china mosaic and light coloured tiles as roof finish,

    which reflects heat off the surface because of high solar reflectivity and infrared emittance,

    which prevents heat gain and thus help in reducing the cooling load from the building

    envelope.

    Thermal insulation for roof

    Well insulated roof with the insulation placed on the external side is an effective measure toreduce solar heat gains from the roof top. The insulated materials should be well protected

    by water proofing.

    For air conditioned spaces, Energy Conservation Building Code (ECBC) recommends the

    thermal performance for external roof for all the five climate zones in India. Bangalore falls

    under Moderate climate zone, the maximum U-value recommended by ECBC for moderate

    climate zone is mentioned below:

    Table 1.2: Roof assembly U-factor requirements as per ECBC 2007

    Climate zone 24-Hour use buildings

    Hospitals, Hotels, Call centers etc.

    Daytime use buildings

    Other building TypesMaximum U-factor of the overall assembly (W/m2K) Maximum U-factor of the overall assembly (W/m2K)

    Moderate U-0.409 U-409

    Examples of ECBC compliant roof assembly

    Roof Ufactor (SI) Ufactor Btu/h (sf-oF) Rs/sf

    Foam concrete or perlite instead of mud Phuska 0.069 0.012 130

    RCC slab with Extruded polystyrene 2.4 36 kg/m3 0.380 0.067 252

    RCC slab with Extruded polystyrene 3 36 kg/m3 0.312 0.055 278

    RCC slab with Expanded polystyrene (thermocole) 3 24 kg/m3 0.409 0.072 205

    RCC slab with Phenolic foam 2.4 32 kg/m3 0.363 0.064 270

    RCC slab with Phenolic foam 3 32 kg/m3 0.301 0.053 302

    RCC slab withPolyurethane spray 2.4 42 2 kg/m3 0.319 0.056 229

    RCC slab withPolyurethane spray 3 42 2 kg/m3 0.259 0.046 246

    RCC slab withPolyisocyanurate spray 2.4 42 kg/m3 0.329 0.058 233

    RCC slab withPolyisocyanurate spray 3 42 kg/m3 0.267 0.047 251

    Figure 1.8: Broken china mosaic can be used as an

    external roof finish to reflect the incident solar radiation

  • 7/30/2019 107080292_2

    20/161

    13 Phase 2 Report on Environmental Building Regulations and Guidelines

    framed fro Bangalore City

    Insulation + cool roof

    Along with lower U-value for roof, ECBC also recommends cool roof. Cool roofs are roofs

    covered with a reflective coating that has high emissivity property which is very effective in

    reflecting the suns energy away from the roof surface. These cool roofs are known to stay

    10deg to 16dg C cooler than normal roof under a hot summer day. This quality greatly helps

    in reducing the cooling load that needs to be met by the HVAC system. Combination of

    insulated roof along with cool roof has higher saving energy potential.

    External shading of roof

    Shading of roof through design features

    like pergola or solar photovoltaic panels

    help reduce the incident direct solar

    radiation on the roof surface. This in

    turn helps to reduce the sol air

    temperature of the roof and conduction

    gains in the space below. It is observed

    using software simulations that shadingof roof has equal potential in reducing

    the energy consumption by air

    conditioning as that of an insulated roof.

    Thermal properties of few building and insulating materials for reference are given below in

    table 1.3.

    Table 1.3: Thermal Properties of Building and Insulating Materials at Mean Temperature of 50deg.C

    SL.

    NO.

    TYPE OF MATERIAL DENSITY THERMAL

    CONDUCTIVITY*

    SPECIFIC HEAT

    CAPACITY

    (1) (2) (3) (4) (5)

    Kg / m3 W / (m.K) KJ / (kg.K)

    Building Materials

    1. Burnt brick 1 820 0.811 0.88

    2. Mud brick 1 731 0.750 0.88

    3. Dense concrete 2 410 1.74 0.88

    4. R.C.C. 2 288 1.58 0.88

    5. Limestone 2 420 1.80 0.84

    6. State 2 750 1.72 0.84

    7. Reinforced brick 1 920 1.10 0.84

    8. Brick tile 1 892 0.798 0.88

    9. Line concrete 1 646 0.730 0.88

    10. Mud Phuska 1 622 0.519 0.88

    11. Cement mortar 1 648 0.719 0.92

  • 7/30/2019 107080292_2

    21/161

    14 Phase 2 Report on Environmental Building Regulations and Guidelines

    framed fro Bangalore City

    12. Cement concrete 1 762 0.721 0.84

    13. Cinder concrete 1 406 0.686 0.84

    14. Foam slag concrete 1 320 0.285 0.88

    15. Gypsum plaster 1 120 0.512 0.96

    16. Cellular concrete 740 0.188 1.05

    17. AC sheet 1 520 0.245 0.84

    18. GI sheet 7 520 61.06 0.50

    19. Timber 480 0.072 1.68

    20. Timber 720 0.144 1.68

    21. Plywood 640 0.174 1.76

    22. Glass 2 350 0.814 0.88

    23. Alluvial clay (40 percent sans) 1 958 1.211 0.84

    24. Sand 2 240 1.74 0.84

    25. Black cotton clay (Madras) 1 899 0.735 0.8826. Black cotton clay (Indore) 1 683 0.606 0.88

    27. Tar felt (2.3 kg/m3) - 0.479 0.88

    (Source, Handbook on Functional Requirements of buildings, SP:411987, BIS)

    SL.

    NO.

    TYPE OF MATERIAL DENSITY THERMAL

    CONDUCTIVITY*

    SPECIFIC HEAT CAPACITY

    (1) (2) (3) (4) (5)

    Kg / m3 W / (m.K) KJ / (kg.K)

    Insulating Materials

    1. Expanded polystyrene 16.0 0.038 1.34

    2. Expanded polystyrene 24.0 0.035 1.34

    3. Expanded polystyrene 34.0 0.035 1.34

    4. Foam glass 127.0 0.056 0.75

    5. Foam glass 160.0 0.055 0.75

    6. Foam concrete 320.0 0.070 0.92

    7. Foam concrete 400.0 0.084 0.92

    8. Foam concrete 704.0 0.149 0.92

    9. Cork slab 164.0 0.043 0.96

    10. Cork slab 192.0 0.044 0.96

    11. Cork slab 304.0 0.055 0.96

    12. Rock wool (unbonded) 92.0 0.047 0.84

    13. Rock wool (unbonded) 150.0 0.043 0.84

    14. Mineral wool (unbonded) 73.5 0.030 0.92

    15. Glass wool (unbonded) 69.0 0.043 0.92

    16. Glass wool (unbonded) 189.0 0.040 0.92

  • 7/30/2019 107080292_2

    22/161

    15 Phase 2 Report on Environmental Building Regulations and Guidelines

    framed fro Bangalore City

    17. Resin bonded mineral wool 48.0 0.042 1.00

    18. Resin bonded mineral wool 64.0 0.038 1.00

    19. Resin bonded mineral wool 99.0 0.036 1.00

    20. Resin bonded glass wool 16.0 0.040 1.00

    21. Resin bonded glass wool 24.0 0.036 1.00

    22. Exfoliated vermiculite (loose) 264.0 0.069 1.00

    23. Asbestos mill board 1 397.0 0.249 0.88

    24. Hard board 979.0 0.279 0.84

    25. Straw board 310.0 0.057 1.42

    26. Soft board 320.0 0.066 1.30

    27. Soft board 249.0 0.047 1.30

    28. Wall board 262.0 0.047 1.30

    29. Chip board 432.0 0.067 1.26

    30. Chip board (perforated) 352.0 0.066 1.26

    31. Particle board 750.0 0.098 1.30

    32. Coconut pith insulation board 520.0 0.060 1.09

    33. Jute fibre 329.0 0.067 1.09

    34. Wood wool board

    (bonded with cement)

    398.0 0.081 1.13

    35. Wood wool board

    (bonded with cement)

    674.0 0.108 1.13

    36. Coil board 97.0 0.038 1.00

    37. Saw dust 188.0 0.051 1.00

    38. Rice husk 120.0 0.051 1.00

    39. Jute felt 291.0 0.042 0.88

    40. Asbestos fibre (loose) 640.0 0.060 0.84

    1.2.13 Fenestration and ShadingOf all the elements of building envelope, windows and glazed areas are most vulnerable to

    heat gains. Windows are required to bring inside natural daylight and wind, however, with

    light it also brings in heat. Proper location, sizing and detailing of windows and shading

    form is therefore a very important aspect in a solar passive building design. Hence window

    design has been detailed out as separate guidelines, which should be referred separately.

    1.2.14 FinishesThe external finish of a surface determines the amount of heat absorbed or rejected by it.

    For example, a smooth and light coloured surface reflects more light and heat in

    comparison to a dark surface. Light colours have higher emissivity and hence should be

    preferred in Moderate climate zones like Bangalore where the intensity of solar radiation is

    very high.

    Emissivity is the measure of the capacity of a surface to emit radiation.

  • 7/30/2019 107080292_2

    23/161

    16 Phase 2 Report on Environmental Building Regulations and Guidelines

    framed fro Bangalore City

    LCC of conventional and ecbc envelope for air conditioned commercial buildings

    0

    10000000

    20000000

    30000000

    40000000

    50000000

    60000000

    70000000

    80000000

    90000000

    0 1 2 3 4 5 6 7 8 9 10 1 1 1 2 1 3 1 4 1 5

    Year

    Rs Conventional envelope

    ECBC envelope

    The internal surfaces should also be finished in light colours, as that helps in obtaining

    higher reflectance of light inside the space

    1.2.15 Benefits of ECBC recommended envelope in comparison with conventionalbuilding envelope for air conditioned buildings in Bangalore

    It is observed in air conditioned buildings, adopting ECBC envelope in building has highenergy saving potential. Energy simulation engine was used to quantify energy saving

    potential in a daytime office building. It is observed that use of ECBC envelope results in

    annual electricity saving up to 12% in comparison with conventional envelope. In this

    analysis following was the ECBC and conventional envelope.

    Walls Composition (External to internal) U value (W/m2K)

    ECBC case Stone cladding+75mm Expanded Polystyrene+230mm Brick wall + internal

    plaster

    0.39

    Conventional case External plaster +230mm brick wall + internal plaster 1.87

    Roof Composition (External to internal) U value (W/m2K)

    ECBC case Roof finish+75mm Expanded Polystyrene+150mm Concrete slab + internal

    plaster

    0.39

    Conventional case Roof finish +150mm concrete slab + internal plaster 1.81

    Glass

    ECBC case (Double glazed unit) U value: 1.31 W/m2K

    SHGC = 0.27

    VLT = 40%

    Conventional case (Single glazed unit) U-value =6.16

    W/m2K

    SHGC = 0.81VLT = 0.88

  • 7/30/2019 107080292_2

    24/161

    17 Phase 2 Report on Environmental Building Regulations and Guidelines

    framed fro Bangalore City

    1.2.16 External shading of the envelopeIt is observed that latitude , longitude of Bangalore recieves high intensity of solar

    radiation. Though the air temperature is cool, making Bangalore fall under Moderate

    climate zone, the solar radition intensity is very high. Thus one of the effective solar passive

    design measure for Bangalore city is external shading of walls, roof, windows to reduce the

    external heat gains. Simulation engine was used to quantify the saving potential in an air

    conditioned building in Bangalore due to external shading. It is noted that energy saving

    upto 15% is possible through shading of roof by using elements like pergola, shading of East

    and west wall and through shading of windows.

    1.3 Life Cycle Cost AnalysisThere can be three cases considered for optimized building envelope to provide maximum

    energy saving potential due to optimum selection of building envelope.

    These are:

    1. Compliance of building envelope with ECBC (Energy Conservation Building Code)

    recommendations.

    2. Shading of envelope to reduce to reduce solar heat gains. This includes shading of East

    and West orientation facades, shading of roof and shading of windows.

    3. Shading of East & West walls, shading of roof and ECBC compliant window.

    Case % Energy saving

    potential

    % Increment in initial

    cost

    % Saving in Life

    Cycle Cost (LCC)

    Pay back period

    Base case - - -

    ECBC envelope 13%% 1.3% 1% 8 years

    Shaded envelope 16% 1.2% 1.9% 5 years

    Shaded walls, roof andECBC window

    16% 1.3% 1.9% 5 years

    Thus it is recommended from the above analysis that :

    Windows in air conditioned spaces should comply with ECBC recommendation.

    Windows in naturaly ventilated spaces should be fully shaded.

    Roof should be either compliant with ECBC recommendations or should be shaded.

    East and West walls should be shaded.

  • 7/30/2019 107080292_2

    25/161

    18 Phase 2 Report on Environmental Building Regulations and Guidelines

    framed fro Bangalore City

    Life Cycle Cost Analysis for building envelope options

    0

    10

    20

    30

    40

    50

    60

    70

    80

    90

    100

    110

    120

    1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

    Years

    Rupees(Million)

    Bas e cas e ECBC env elope c as e Propos ed Shading env elope c as e Propos ed s hadingw all,roof+ec bc glas s

    1.4 Daylight IntegrationDaylight is a natural source of light, which meets all the requirements of good lighting.

    Daylight provides a dynamic environment inside the building in consonance with the

    nature outdoors. Windows in buildings establish contact with nature through direct view

    and admit daylight inside. Adequate provision of daylight in buildings through proper

    planning of windows, in respect of position, area and shape is therefore an important aspect

    of a good building design. Daylight integration helps reduce dependence on artificial

    lighting and thus reduction in electricity consumption of the building. Details on daylight

    integartion is part of the window guideline.

    1.5 Building envelope optimization for naturally ventilated buildings toachieve thermal comfort

    Optimizing envelop requirement is one of the most important strategies to lower down heat

    built up in the interior space , hence plays a vital role in achieving thermal comfort as

    prescribed in the National Building Code 2005 for Naturally ventilated buildings.

    Optimize building envelope to reduce heat gains and maximize thermal comfort in naturally

    ventilated building.

    Buildings occupied for 24 hoursResidences

    For the achievement of thermal comfort in the naturally ventilated spaces of residences,

    following guidelines should be followed:

    1. For the effectiveness of natural ventilation, window should be designed as per the

    guideline outlines in window design for Natural ventilation.

    2. Windows should be fully shaded in order to maximize thermal comfort in the space.

  • 7/30/2019 107080292_2

    26/161

    19 Phase 2 Report on Environmental Building Regulations and Guidelines

    framed fro Bangalore City

    3. Building envelope should be as per the recommendations included in this guideline.

    This recommended envelope design is for naturally ventilated residential spaces with 6

    air change per hour.

    Buildings occupied for Day time hours (9 hours)

    Offices

    For the achievement of thermal comfort in the naturally ventilated office spaces, following

    guidelines should be followed:

    For the effectiveness of natural ventilation, window should be designed as per the guideline

    outlined in Window Design for Natural Ventilation. Windows should be fully shaded in

    order to maximize thermal comfort in the space. Building envelope should be as per the

    recommendations included in this guideline. Building envelope should be as per the

    recommendations included in this guideline. This recommended envelope design is for

    naturally ventilated office spaces with 6 air change per hour. Optimum Building Envelop

    Configuration for Naturally Ventilated Residences and Offices:

    The recommended envelop of the space shall be as per the following properties:

    Table 1.4: Envelop Specifications

    Envelope with brick wall Composition U-value

    Wall Plaster + brick + plaster 2.203

    Roof (Insulated) Plaster + concrete + expanded polystyrene + plaster + stone 0.349

    Floor Floor + stone + concrete 0.417

    Glass for opening Single glazing unit fully shaded -

    Envelope with concrete wall Composition U-value

    Wall Plaster + concrete + plaster 3.443

    Roof (Insulated) Plaster + concrete + expanded polystyrene + plaster + stone 0.349

    Floor Floor + stone + concrete 0.417

    Glass for opening Single glazing unit fully shaded -

    Envelope with mud-block

    wallComposition U-value

    Wall Plaster + mud block + plaster 3.443

    Roof (insulated) Plaster + concrete + expanded polystyrene + plaster + stone 0.349

    Floor Floor + stone + concrete 0.417

    Glass for opening Single glazing unit (fully shaded) -

    1. The U-Value prescribed in the table should be taken as recommendation while

    designing the roof, wall, and floor component.

    2. For the clarity of the user it should be noted that, the different combinations of envelopdiffers from each other with respect to only wall material; while the roof , floor and

    glazing type remains the same.

  • 7/30/2019 107080292_2

    27/161

    20 Phase 2 Report on Environmental Building Regulations and Guidelines

    framed fro Bangalore City

    Figure 1.9: Zone Temperature conditions of non air conditioned space in office and residences on hottest day (April

    11) of the year

  • 7/30/2019 107080292_2

    28/161

    21 Phase 2 Report on Environmental Building Regulations and Guidelines

    framed fro Bangalore City

    1.6 Low energy Passive Cooling Strategies for Bangalore

    Bangalore falls under moderate climate zone with favorable outdoor conditions to design

    hybrid low energy buildings. Weather analysis for Bangalore shows that design strategies

    such as shading from direct solar radiation and natural ventilation are very effective in

    achieving comfort in non air conditioned living spaces. High thermal mass and evaporative

    cooling are other effective design strategies shown in figure below reference: Climate

    calculator)

    1.6.1 VentilationVentilation fulfills a number of requirements associated with human comfort:

    Health: respiration, odour avoidance and pollutant removal.

    Cooling: removal of heat produced by internal and solar gains, both during daytime and

    at night time.

    Comfort: Provision of air movement to increase perceived cooling.

    Methods of ventilation

    Ventilation requirement could be met by the following ways:

    1. Natural ventilation

    2. Mechanical ventilation

    3. Mixed mode ventilation

  • 7/30/2019 107080292_2

    29/161

    22 Phase 2 Report on Environmental Building Regulations and Guidelines

    framed fro Bangalore City

    Figure 1.10: Cross ventilation achieved through

    openings

    Figure 11: Stack effect through openings at

    different level.

    Natural Ventilation

    Natural ventilation systems rely on pressure to move fresh air through buildings.

    Pressure difference can be caused by wind (cross ventilation) or the buoyancy effect

    created by temperature differences or differences in humidity (stack effect). In both the

    cases the amount of ventilation critically depends on design of openings, their size and

    placement. Natural ventilation unlike forced ventilation uses natural sources like wind

    and buoyancy to deliver fresh air into the building.

    Cross Ventilation

    A pressure is generated on a surface whenever moving

    air is obstructed or deflected. The distribution of

    pressure depends upon the wind direction and the

    geometry of the surfaces. Pressures will generally be

    positive on the windward sides of buildings and negative

    on leeward sides. The lateral pressure distribution gives

    rise to cross-ventilation; that is airflow from the windward

    to the leeward side of the building. This requires that the

    interior of the building is not sealed by dividing walls, or

    that where rooms are double banked, openings at high level are provided.

    Cross ventilation was assisted by having high level openings in the internal walls and

    over doors in traditional houses.

    Stack Effect

    Air moves through a structure in response to pressure

    differences generated by either the thermal buoyancy

    (stack effect) or wind. Buoyancy pressures are generated

    by air warmer than its surroundings as the warmer air is of

    lower density than the cooler air.

    The pressure generated is dependent upon the average

    temperature difference between inside and outside and the height

    of the 'stack' or column of warmer air. Where there are openings

    at the top and bottom of the stack, the cooler heavier air will enter

    the lower openings and displace the warmer lighter air at the top.

    This is known as 'displacement ventilation', and if there is a

    source of heat which maintains the stack, the flow will continue.

    It is important to note that in these conditions air temperatures

    low down will be close to outdoor temperatures and those

    higher up will be warmer.

  • 7/30/2019 107080292_2

    30/161

    23 Phase 2 Report on Environmental Building Regulations and Guidelines

    framed fro Bangalore City

    Direct evaporative cooling, source Passivecooling techniques, B.Mohanty

    Traditionally, this concept was used very commonly by having high ceilings in

    conjunction with ventilators and low level openings, courtyards and atria.

    Probable indoor wind speed

    The available wind speed in a room with single window on the windward side is about

    10 percent of outdoor velocity. The value however is increased upto 15 percent when

    two windows are provided instead of one and wind impinges obliquely on them.

    Effect of area of openings on the indoor wind velocity is depicted in the graph below.

    Building design guidelines for natural ventilation

    1. Maximize wind induced ventilation by orienting the longer facades of the building

    towards predominant wind direction. However, if this is not possible, it could be oriented at

    any convenient angle between 0o and 30o without loosing any beneficial aspect of the

    breeze.

    2. Inlet openings in the buildings should be well distributed and should be located on the

    windward side at a low level, and outlet openings should be located on the leeward side at a

    higher level, to maximize the stack effect.

    3. Buildings should be sited where obstructions for summer

    winds are minimum.

    4. Naturally ventilated buildings should have a narrow floor

    width, infact its difficult to naturally ventilate buildings with

    floor depth more than 45feet.

    5. For total area of openings (inlet and outlet) of 20 to 30% of

    floor area, the average indoor wind velocity that could be

    achieved is around 30% of outdoor wind velocity. Even onincreasing the size of window further, the maximum indoor

    wind velocity does not exceed 40% of outside wind velocity.

    6. Window openings should be operable by occupants.

    7. In addition to the primary consideration of airflow in and out of the building, airflow

    between the rooms of the building is important. Where possible, interior doors should be

    designed to be open to encourage whole-building ventilation.

    8. Use of clerestories or vented skylights, A clerestory or a vented skylight will provide an

    opening for stale air to escape in a buoyancy ventilation strategy. The light well of theskylight could also act as a solar chimney to augment the flow. Openings lower in the

    structure, such as basement windows, must be provided to complete the ventilation system.

    Evaporative Cooling

    Evaporative cooling lowers indoor air temperature by evaporative cooling. This cooling

    strategy is also effective in Moderate climate of Bangalore. In evaporative cooling the

    Nocturnal cooling

  • 7/30/2019 107080292_2

    31/161

    24 Phase 2 Report on Environmental Building Regulations and Guidelines

    framed fro Bangalore City

    sensible heat of air is used to evaporate the water, thereby releasing energy and air gets

    cooled, which in turn cools the indoor living spaces.

    Increase in contact between air and water increases the rate of evaporation. Water bodies

    like ponds, lake or fountains in the landscape help reduce micro climate air temperature

    around the buildings.

    Traditionally also evaporative cooling has been used to cool the hot breeze. Water was usedcommonly to reduce local temperatures by evaporative cooling, to humidify the air and also

    to clean the air by capturing dust particles. It has been calculated that the temperature of 1

    cubic metre of air will be reduced by 1 C by the evaporation of 0-5 g of water (Evans). In

    public buildings water in pools and fountains can be used as a cooling element combined

    with a cross-ventilating arrangement of openings.

    Figure 13: Ways of integrating evaporative cooling

    Figure 12: HUL solar passive building in Bangalore with ponds

    integrated in the circulation areas to integrate evaporative cooling.

    1.6.2 Radiative cooling

    Principle: If two elements at different temperatures are kept facing one another, a netradiation heat loss from the hotter element will occur until a state of equilibrium

    between the two elements is achieved.

    In order to have an appreciable net heat flux between the two bodies, the temperature

    difference should be significant

    Low energy passive design stretegies in residential building typology in Bangalore city

    Thermal comfort through out the year can be easily achieved in residential buildings in

    Bangalore by adopting the following passive design strategies:

    Long faade oriented towards North South

    East and West facades to be shaded

    Solar chimneys integration to enhance natural ventilation

    Insulated roof

    Roof pond in certain areas for radiant cooling

    Direct evaporative cooling

  • 7/30/2019 107080292_2

    32/161

    25 Phase 2 Report on Environmental Building Regulations and Guidelines

    framed fro Bangalore City

    1.6.3 Some low energy cooling & design strategies that could be adopted inresidential buildings in Bangalore are described below. These strategies wereanalysed in TRNSYS software.

    1. Long faade oriented towards North South, this is based on the solar radiation

    analysis for Bangalore city. East and West faade receive higher intensity of solarradiation throughout the year and hence short facades of the building should be

    oriented towards East and West. This ensures minimum solar heat gain inside the

    building.

    2. Insulated roof: Solar analysis of Bangalore predicts high intensity of solar radiation

    being received on horizontal surfaces. To reduce conduction gains from the roof, it

    is very esstial to insulate the roof from outside.

    3. Solar chimneys to enhance natural ventilation, through stack effect. Inlet openings

    provided at lower level and outlet opening through solar chimney increase the

    temperature difference between the hot air and cool air, this enhances the air

    movement and therefore natural ventilation. Natural ventilation is very effective in

    Moderate climate of Bangalore as the outside air temperature falls under comfortzone.

    4. Radiant cooling is also effectice in Bangalore and therefore roof pond could be

    provided wherever possible.

    5. Evaporative cooling: In summer months in Bangalore which are April, May and

    June evaporative cooling is effective, as the outside temperature is high and

    Relative Humidity (RH) is lower. This can be integrated in buildings through

    evaporative coolers, or wet Khas Khas integrated around windows and through

    designing water bodies in the landscape.

    1.7 Example of a Naturally Ventilated office Building in Bangalore

    TERIs South Regional office is located in Bangalore which

    forms an example of passive building in the Moderate climate

    zone of India.

    Following are some of key features of the building:

    The building is oriented with long facades oriented North

    South.

    The building has maximum

    openings in the North faade which

    helps bring inside the building glarefree daylight and cool breeze.

    The skylights are oriented towards

    North, which provides uniform glare

    free daylight through out the

    building.

  • 7/30/2019 107080292_2

    33/161

    26 Phase 2 Report on Environmental Building Regulations and Guidelines

    framed fro Bangalore City

    Walls on the South faade are externally finished with

    black kadappa stone with a cavity wall. This behaves

    as a solar chimney. There are no openings at lower

    level in this wall, only ventilators at the top of the wall

    are provided for hot air to rise and escape. This

    creates a negative pressure and starts pulling freshcool air from North side of the building. The building

    works in natural ventilation mode through out the

    year, and this is achieved as there are no floor to

    ceiling partitions in the whole building.

    There are roof gardens designed, which provide good insulation and moderates

    fluctuation in temperature.

    The month bill for energy consumption is about Rs 30,000 for the entire complex, with

    daily average demand of 12 kW (peak at 18 kW). With floor area being 26,663 square

    feet, the specific energy bill works out to be Rs 1.12 per square foot, which is almost one-

    tenth of a conventional building with air conditioning.

    1.8 Summary:Recommendations for air conditioned buildings

    Long faade preferably towards North-South

    East West faade to be shaded

    Windows to comply with ECBC requirement.

    Roof to either comply with ECBC or to be fully shaded.

    Circular building form is preferable.

    Light colour external finish.

    1.8.1 Naturally ventilated buildings recommendations Long faade preferably towards North-South

    East West faade to be shaded

    Windows to be fully shaded.

    Roof to be insulated or to be shaded.

    Light colour external finish.

    1.9 Glossary:Orientation: It is the direction an envelope element faces, i.e., the direction of a vector

    perpendicular to and pointing away from the surface outside of the element.

    Reflectance: The fraction of radiant energy that is reflected from a surface.

    Solar heat gain coefficient: Solar heat gain coefficient (SHGC) is the fraction of

    external solar radiation that is admitted through a window or skylight, both directly

    transmitted, and absorbed and subsequently released inward.

    Transmittance: The fraction of radiant energy that passes through a surface.

  • 7/30/2019 107080292_2

    34/161

    27 Phase 2 Report on Environmental Building Regulations and Guidelines

    framed fro Bangalore City

    U-factor: It measures the rate of heat transfer through a building element over a given

    area, under standardised conditions. The usual standard is at a temperature gradient of 24

    C, at 50% humidity with no wind.

    1.10 Reference: Bureau of Indian Standards, 2005, National Building Code of India

    A Knowledge Bank for Sustainable Building Design CD, MNRE & TERI, New

    Delhi

    Energy Conservation Building Code 2007, Bureau of Energy Efficiency, Ministry of

    Power, Government of India

    VisualDOE version 4.1 Software

    Ecotect Version 5.0.

    Lighting Manufacturer contact details

    SN Name Address Contact details

    Paint

    1 THERMATEK (Ishaan

    Industries)

    ALA INC, No. 303,6th Main, Yellama

    Temple Road, Indira Nagar, Bangalore-

    560038.

    Ph: 080 25352493Mobile: 9980560857

    2 Kansai Nerolac Paints

    Limited

    Nerolac House, SY No 39/1, P C S

    Industrial Estate, Banner gata Road

    AREKER Village, Bangalore -560076

    Ph: 080-26597145

    Insulation

    3 U. P. Twiga Fiberglass

    Limited

    No. 28/3 1st Floor, 23rd Cross,

    Banashankari 2nd Stage Main Road,

    Near State Bank of India, Bangalore -

    560070

    Ph: 080-26712510Mobile-9686406229

    4 Lloyd Insulations (India)

    Ltd

    101-102, Oxford Chamber, No. 16,

    Rustam Bagh Main Road, Bangalore:

    560017

    Ph: 080-25202084

    Glass Products

    5 3M Construction MarketCenter

    Concorde block, UB City, 24, Vittal MalyaRoad, Bangalore-560001

    Ph: 080-66595759Fax: 080-22231450

    6 Saint-Gobain GlassIndia Ltd.

    Sai Comples, 4th Floor, 114, M G Road,Bangalore 560 001

    Ph: 080-25091123Fax: 080-25583795

  • 7/30/2019 107080292_2

    35/161

    GUIDELINES 2:Provide roof treatment to cut heat gains

    Provide roof treatment to cut down heat gain in the air-conditioned and naturally ventilated

    space to maximize thermal comfort.

    2.1 Mandatory clause to be included in the Revised Bye LawsAll exposed roof in air conditioned spaces and naturally ventilated shall comply with the ECBC

    2007 requirement as outlined below or shall be shaded

    Table 2.1: Roof assembly U-factor requirements as per ECBC 2007

    Climate

    zone

    24-Hour use buildings

    Hospitals, Hotels, Call centres etc.

    Daytime use buildings

    Other building Types

    Maximum U-factor of the overall assembly (W/m2K) Maximum U-factor of the overall assembly(W/m2K)

    Moderate U-0.409 U-409

    The roof insulation shall not be located on a suspended ceiling with removable

    Ceiling panels. (Mandatory)

    2.2 Technical Guidance

    2.2.1 Brief IntroductionOptimizing roof material can play vital role in lowering down heat built up in both air-

    conditioned space and naturally ventilated space. Roof treatment is one of the effective

    strategies to cut down heat gain helps in reducing cooling load from air conditioned space.

    In the same way, it helps in maximizing thermal comfort in naturally ventilated space.

    Roof optimization in Air Conditioned Space:

    It is observed in air conditioned buildings, adopting ECBC envelope in building has highenergy saving potential. Energy simulation engine was used to quantify energy saving

    potential in a daytime office building. . It is observed that in single storey buildings and in

    double storey buildings, insulated + cool roof as recommended by ECBC has energy saving

    potential up to 60% in comparison to conventional buildings. This saving potential

    however, reduces with increase in number of floors and in case of high rise buildings, where

    roof contribution towards external heat gains is minimized

    Shading of roof also has similar energy saving potential. This could be achieved by

    designing pergolas, trellis on roof or by installation of solar panels. Energy saving potential

    in a building with two floors and built up area 3200m2, after complying to ECBC

    recommendations and shading the roof are given below in the graph.

    Roof Composition (External to internal) U value (W/m2K)

    ECBC compliant

    insulated + cool roo

    Roof finish+75mm Expanded Polystyrene+150mm Concrete slab + internal plaster 0.39

    Conventional case Roof finish +150mm concrete slab + internal plaster 1.81

  • 7/30/2019 107080292_2

    36/161

    29 Phase 2 Report on Environmental Building Regulations and Guidelines

    framed fro Bangalore City

    Recommended roof treatment for Naturally Ventilated spacesThermal comfort in a naturally ventilated space can be maximized by using appropriate

    treatment for the roof. Computer simulation analysis was performed in order to investigate

    the role of roof treatment to maximize thermal comfort in a naturally ventilated space.

    Following are envelope configuration used for simulation analysis

    Walls Composition (External to internal) U value (W/m2K)

    ECBC case Stone cladding+75mm Expanded Polystyrene+230mm Brick wall + internal

    plaster

    0.39

    Conventional case External plaster +230mm brick wall + internal plaster 1.87

    The thermal comfort hours are further maximized when the surface reflectivity increased to

    0.7 y using white paint on external roof surface and insulation thickness.

    Roof Composition (External to internal) U value (W/m2K)

    ECBC case Roof finish+75mm Expanded Polystyrene+150mm Concrete slab + internal plaster 0.39

    Conventional case Roof finish +150mm concrete slab + internal plaster 1.81

    Glass Type Properties

    ECBC case (Single glazed

    unit)U-value =6.16 W/m2K , SHGC = 0.81 , VLT = 0.88

    Conventional case (Single

    glazed unit)U-value =6.16 W/m2K , SHGC = 0.81 , VLT = 0.88

    Energy use in conventional building, building

    with ECBC compliant roof, building with shaded

    roof

    0

    200,000

    400,000

    600,000

    800,0001,000,000

    1,200,000

    base 0.30wwr ECBC + cool roof

    0.30wwr

    Shaded roof

    0.30wwr

    Energyuse(kWh)

    Energy consumption kWh (Cooling+Lighting)

    61% saving 62% saving

  • 7/30/2019 107080292_2

    37/161

    30 Phase 2 Report on Environmental Building Regulations and Guidelines

    framed fro Bangalore City

    2.2.2 Heat gains through roofs can be reduced by adopting the followingtechniques

    Green roof concept

    Green roofs have the potential to improve the thermal

    performance of a roofing system through shading, insulation,

    evapo-transpiration and thermal mass, thus reducing a

    buildings energy demands for space conditioning. The green

    roof moderates the heat flow through the roofing system and

    helps in reducing the temperature fluctuations due to changing

    outside environment.Figure 2.1: Roof of buildings with roof garden.

  • 7/30/2019 107080292_2

    38/161

    31 Phase 2 Report on Environmental Building Regulations and Guidelines

    framed fro Bangalore City

    Green roof is a roof of a building that is partially or completely covered with vegetation and

    soil that is planted over waterproofing membrane. If widely

    used green roofs can also reduce the problem of urban heat

    island which would further reduce the energy consumption in

    urban areas.

    Use of high reflective material on roof topUse light coloured roofs having an SRI (solar reflectance index)

    of 50% or more. The dark coloured, traditional roofing finishes

    have SRI varying from 5 - 20%. A good example of high SRI is

    the use of broken china mosaic and light coloured tiles as roof

    finish, which reflects heat off the surface because of high solar reflectivity and infrared

    emittance, which prevents heat gain and thus help in reducing the cooling load from the

    building envelope.

    Thermal insulation for roof

    Well insulated roof with the insulation placed on the external side is an effective measure to

    reduce solar heat gains from the roof top. The insulated materials should be well protected

    by water proofing.

    For air conditioned spaces, Energy Conservation Building Code (ECBC) recommends the

    thermal performance for external roof for all the five climate zones in India. Bangalore falls

    under Moderate climate zone, the maximum U-value recommended by ECBC for moderate

    climate zone is mentioned below:

    Table 2.2: Roof assembly U-factor requirements as per ECBC 2007

    Climate zone 24-Hour use buildings

    Hospitals, Hotels, Call centres etc.

    Daytime use buildings

    Other building Types

    Maximum U-factor of the overall assembly (W/m2K) Maximum U-factor of the overall assembly (W/m2K)

    Moderate U-0.409 U-409

    Insulation + cool roof

    Along with lower U-value for roof, ECBC also recommends cool roof. Cool roofs are roofs

    covered with a reflective coating that has high emissivity property which is very effective in

    reflecting the suns energy away from the roof surface. These cool roofs are known to stay 10

    C to 16 C cooler than normal roof under a hot summer day. This quality greatly helps in

    reducing the cooling load that needs to be met by the HVAC system. Combination of

    insulated roof along with cool roof has higher saving energy potential.

    Figure 2.2: Broken china mosaic can be used asan external roof finish to reflect the incident solarradiation.

  • 7/30/2019 107080292_2

    39/161

    32 Phase 2 Report on Environmental Building Regulations and Guidelines

    framed fro Bangalore City

    External shading of roof

    Shading of roof through design features like

    pergola or solar photovoltaic panels help

    reduce the incident direct solar radiation on

    the roof surface. This in turn helps to reduce

    the sol air temperature of the roof and

    conduction gains in the space below. It is

    observed using software simulations that

    shading of roof has equal potential in

    reducing the energy consumption by air

    conditioning as that of an insulated roof.

    Thermal properties of few building and insulating materials for reference are given below in

    table 2.3.

    Table 2.3: Thermal Properties of Building and Insulating Materials at Mean Temperature of 50deg.C

    SL. NO. TYPE OF MATERIAL DENSITY THERMAL CONDUCTIVITY* SPECIFIC HEAT CAPACITY

    (1) (2) (3) (4) (5)

    Kg / m3 W / (m.K) KJ / (kg.K)

    Building Materials

    1. Burnt brick 1 820 0.811 0.88

    2. Mud brick 1 731 0.750 0.88

    3. Dense concrete 2 410 1.74 0.88

    4. R.C.C. 2 288 1.58 0.88

    5. Limestone 2 420 1.80 0.84

    6. State 2 750 1.72 0.84

    7. Reinforced brick 1 920 1.10 0.84

    8. Brick tile 1 892 0.798 0.889. Line concrete 1 646 0.730 0.88

    10. Mud Phuska 1 622 0.519 0.88

    11. Cement mortar 1 648 0.719 0.92

    12. Cement concrete 1 762 0.721 0.84

    13. Cinder concrete 1 406 0.686 0.84

    14. Foam slag concrete 1 320 0.285 0.88

    15. Gypsum plaster 1 120 0.512 0.96

    16. Cellular concrete 740 0.188 1.05

    17. AC sheet 1 520 0.245 0.84

    18. GI sheet 7 520 61.06 0.50

    19. Timber 480 0.072 1.68

    20. Timber 720 0.144 1.68

    21. Plywood 640 0.174 1.76

    22. Glass 2 350 0.814 0.88

    23. Alluvial clay (40 percent sans) 1 958 1.211 0.84

    24. Sand 2 240 1.74 0.84

  • 7/30/2019 107080292_2

    40/161

    33 Phase 2 Report on Environmental Building Regulations and Guidelines

    framed fro Bangalore City

    25. Black cotton clay (Madras) 1 899 0.735 0.88

    26. Black cotton clay (Indore) 1 683 0.606 0.88

    27. Tar felt (2.3 kg/m3) - 0.479 0.88

    (Source, Handbook on Functional Requirements of buildings, SP:411987, BIS)

    SL. NO. TYPE OF MATERIAL DENSITY THERMAL CONDUCTIVITY* SPECIFIC HEAT CAPACITY

    (1) (2) (3) (4) (5)

    Kg / m3 W / (m.K) KJ / (kg.K)

    Insulating Materials

    1. Expanded polystyrene 16.0 0.038 1.34

    2. Expanded polystyrene 24.0 0.035 1.34

    3. Expanded polystyrene 34.0 0.035 1.34

    4. Foam glass 127.0 0.056 0.75

    5. Foam glass 160.0 0.055 0.75

    6. Foam concrete 320.0 0.070 0.92

    7. Foam concrete 400.0 0.084 0.92

    8. Foam concrete 704.0 0.149 0.92

    9. Cork slab 164.0 0.043 0.96

    10. Cork slab 192.0 0.044 0.96

    11. Cork slab 304.0 0.055 0.96

    12. Rock wool (unbonded) 92.0 0.047 0.84

    13. Rock wool (unbonded) 150.0 0.043 0.84

    14. Mineral wool (unbonded) 73.5 0.030 0.92

    15. Glass wool (unbonded) 69.0 0.043 0.92

    16. Glass wool (unbonded) 189.0 0.040 0.92

    17. Resin bonded mineral wool 48.0 0.042 1.0018. Resin bonded mineral wool 64.0 0.038 1.00

    19. Resin bonded mineral wool 99.0 0.036 1.00

    20. Resin bonded glass wool 16.0 0.040 1.00

    21. Resin bonded glass wool 24.0 0.036 1.00

    22. Exfoliated vermiculite

    (loose)

    264.0 0.069 1.00

    23. Asbestos mill board 1 397.0 0.249 0.88

    24. Hard board 979.0 0.279 0.84

    25. Straw board 310.0 0.057 1.42

    26. Soft board 320.0 0.066 1.3027. Soft board 249.0 0.047 1.30

    28. Wall board 262.0 0.047 1.30

    29. Chip board 432.0 0.067 1.26

    30. Chip board (perforated) 352.0 0.066 1.26

    31. Particle board 750.0 0.098 1.30

  • 7/30/2019 107080292_2

    41/161

    34 Phase 2 Report on Environmental Building Regulations and Guidelines

    framed fro Bangalore City

    32. Coconut pith insulation

    board

    520.0 0.060 1.09

    33. Jute fibre 329.0 0.067 1.09

    34. Wood wool board

    (bonded with cement)

    398.0 0.081 1.13

    35. Wood wool board

    (bonded with cement)

    674.0 0.108 1.13

    36. Coil board 97.0 0.038 1.00

    37. Saw dust 188.0 0.051 1.00

    38. Rice husk 120.0 0.051 1.00

    39. Jute felt 291.0 0.042 0.88

    40. Asbestos fibre (loose) 640.0 0.060 0.84

    2.2.3 Why is this required?Roof receives a significant amount of solar radiation round the year. As illustrated in Fig 1,

    shows the intensity of solar irradiation is maximum on the horizontal plane which is the

    roof. Conductance of heat from the roof can be very high if not insulated well.

    This can result in increased cooling load if the space below is air conditioned or high

    discomfort hours if the space below is naturally ventilated.

    2.2.4 How is it beneficial?Treatment of roof in the form of roof insulation reduces cooling demand from air

    conditioning and related energy consumption in air-condition and helps in maximizing

    thermal comfort in non-air-conditioned spaces. Application of insulation on roof can bring

    down energy consumption in air-conditioned spaces below roof.

    Figure 2.3: Average daily Intensity of solar radiation incident on horizontal roof surface in Bangalore

  • 7/30/2019 107080292_2

    42/161

    35 Phase 2 Report on Environmental Building Regulations and Guidelines

    framed fro Bangalore City

    LCCA of conventional buildings and ECBC compliant roof

    building

    0

    50

    100

    150

    200

    1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

    Millions

    Years

    Cost(Rs)

    Base case ECBC + cool roof case

    Energy modeling has been carried out to quantify energy saving potential of roof insulation

    and life cycle analysis has been carried out to calculate payback period for applying roof

    insulation in a day use office air conditioned building. It has been observed that due to high

    energy saving in single or double storey building after complying with ECBC thermal

    performance of the roof, pay back period in Bangalore will be less than one year.

    In naturally ventilated buildings, roof insulation brings positive impacts on t