102 – Operational Manual USER’S MANUAL SLM102 · SLM102 – Operational Manual TRINITY [1]...

67
SLM102 – Operational Manual TRINITY [1] USER’S MANUAL SLM102 0.2 Class Multifunction Power and Energy meter This document contains the latest technical information about SLM102 which is a micro-controller based 0.2 Class Multifunction Power and Energy meter. The unit is tested against latest "MTE" Standard Model PRS400.3 having basic accuracy of 0.02%, traceable upto International Standards derived using appropriate ratio techniques. The product, SLM102 is sophisticated electronic equipment, and the user is advised to read this User’s Manual carefully before attempting to install or operate the equipment. Published on:------ Document Version: 1.0

Transcript of 102 – Operational Manual USER’S MANUAL SLM102 · SLM102 – Operational Manual TRINITY [1]...

SLM102 – Operational Manual

TRINITY [1]

USER’S MANUAL

SLM102

0.2 Class Multifunction Power and Energy meter

This document contains the latest technical information about SLM102 which is a micro-controller based 0.2 Class Multifunction Power and Energy meter. The unit is tested against latest "MTE" Standard Model PRS400.3 having basic accuracy of 0.02%, traceable upto International Standards derived using appropriate ratio techniques. The product, SLM102 is sophisticated electronic equipment, and the user is advised to read this User’s Manual carefully before attempting to install or operate the equipment. Published on:------ Document Version: 1.0

SLM102 – Operational Manual

TRINITY [2]

Warranty statement

Trinity warrants to the original retail purchaser of the Trinity product enclosed with this limited warranty statement that the product, if purchased new and used in the India conforms to the manufacturer’s specifications and will be free from defects in workmanship and materials for a period of one year from the date of original purchase, unless expressly stated otherwise by Trinity, in a written format. Should your Trinity product prove defective during the warranty period, please bring the product securely packaged in its original container or an equivalent, along with proof of the date of original purchase, to our Trinity Dealer or Factory. You are responsible for all costs (shipping, insurance, travel time) in getting the product to the service location. Trinity will, at its option, repair or replace on an exchange basis the defective unit, without charge for parts or labor. When warranty service involves the exchange of the product or of a part, the item replaced becomes Trinity property. The replacement unit may be new or refurbished to the Trinity standard of quality, and at Trinity’s option, the replacement may be another model of like kind and quality. Trinity’s liability for replacement of the covered product will not exceed the original retail selling price of the covered product. Exchange or replacement products or parts assume the remaining warranty period of the product covered by this limited warranty. What This Warranty Does Not Cover: This warranty does not apply to refurbished or reconditioned products. This warranty covers only normal use in India. This warranty does not cover damage to the Trinity product caused by parts or supplies not manufactured, distributed or certified by Trinity. This warranty is not transferable. This warranty does not cover third party parts, components or peripheral devices added to the Trinity product after its shipment from Trinity. Trinity is not responsible for warranty service should the Trinity label or logo or the rating label or serial number be removed or should the product fail to be properly maintained or fail to function properly as a result of misuse, abuse, improper installation, neglect, improper shipping, damage caused by disasters such as fire, flood, and lightning, improper electrical current, interaction with non-Trinity products, or service other than by an Trinity Authorized Service. The warranty and remedy provided above are exclusive and in lieu of all other express or implied warranties including, but not limited to, the implied warranties of merchantability or fitness for a particular purpose. In the event, the remedies above fail, Trinity’s entire liability shall be limited to a refund of the price paid for the Trinity product covered by this limited warranty. Except as provided in this written warranty, neither Trinity Energy Systems Pvt. Ltd. nor its affiliates shall be liable for any loss, inconvenience, or damage, including direct, special, incidental, or consequential damages, resulting from the use or inability to use the Trinity product, whether resulting from breach of warranty or any other legal theory.

SLM102 – Operational Manual

TRINITY [3]

Contents

Introduction ................................................................................................................ 4 Main Features Available in the Unit ...................................................................... 4 Technical Specifications ....................................................................................... 7 

Installation and Commissioning ............................................................................. 11 3P4W Installation Mode ...................................................................................... 11 3P3W Installation Mode ...................................................................................... 13 Connection Scheme ............................................................................................ 14 RS485 Connection .............................................................................................. 15 

Operational Details ................................................................................................... 16 Programming Mode ................................................................................................ 17 

Setting CT-Primary and date according to RTC ................................................. 17 Setting PT Ratio and Time according to RTC .................................................... 18 Setting Log Duration, Demand Window and Unit Address ................................. 19 Selecting Demand On, Installation type and CT-Secondary .............................. 20 Setting Four Alarm Relays, Alarm On, Alarm Value and Alarm Hysteresis ....... 21 Setting Four Events, Event On, Event Value and Event Hysteresis .................. 23 Selecting Baud Rate for RS485 Port and Changing Password .......................... 24 Setting IP Address .............................................................................................. 24 Setting MAC Address .......................................................................................... 25 Resetting Demand Manually / Daily/Monthly ...................................................... 27 Resetting Energy ................................................................................................. 28 Resetting Minimum and Maximum Parameters .................................................. 28 Resetting KW Demand and KVA Demand ......................................................... 29 Resetting Log ...................................................................................................... 30 Resetting Events Logging ................................................................................... 30 Resetting All Parameters .................................................................................... 31 

Run Mode ............................................................................................................... 32 Run Mode Displays ............................................................................................. 32 

Communications ...................................................................................................... 47 MODBUS RTU on RS485 Port ........................................................................... 47 Ethernet TCP/IP Communication ........................................................................ 48 SLM102 connected as Mini Web Server to a web browser. ....................... 48 Data Logging and USB Port ................................................................................ 49 Installing the USB Software ................................................................................ 49 Installation of USB driver .................................................................................... 50 Handling the Logger Window .............................................................................. 53 Downloading the Logged data ............................................................................ 53 Exporting the Logged Data including Min/Max Events and Harmonics Data ..... 54 Graph Representation ......................................................................................... 55 Plotting a Graph for Logged data. ....................................................................... 55 Programming Mode Using USB Utility ................................................................ 57 

Control Outputs ........................................................................................................ 59 Alarm Action ........................................................................................................ 59 SLM102 as a Demand Management .................................................................. 60 

Appendix ................................................................................................................... 61 Address map of RS485 Port for various parameters of both 3P4W and 3P3W. 61 

SLM102 – Operational Manual

TRINITY [4]

Introduction SLM102 is a micro-controller based 0.2 Class Multifunction Power and Energy meter which not only measures a host of electrical parameters to display three rows of eight digits, of Red Seven Segment LEDs display along with eighteen LED indicators. The unit acts as a comprehensive load managing device due to its four numbers of outputs relay contacts. These outputs are individually field programmable for both the parameter on which to generate an alarm as well as the values on which to activate an alarm and deactivate it. The unit is meant for use in three phase four wire and three phase three wire systems. The installation type, CT Ratios and PT Ratios are site selectable. The unit can also be used as Load Manager with its four relay contacts as well as Demand Controller. The method of Demand calculation i.e. Sliding window, Fixed window can also be selected at site. SLM102 has three ports for communication i.e. RS-485 for connection to SCADA/EMS, USB 2.0 for downloading of logged data and programming of field parameters, and Ethernet Port with TCP/IP protocol support for connection with LAN/Internet. It has 2 MB of memory for data logging of all measured parameters, min-max values and events. SLM102 is a versatile meter, with all the features needed to implement a robust electrical load management system. It can be configured to suit most control and communication needs.

Main Features Available in the Unit Exceeds class 0.2 revenue accuracy in Power & Energy Metering. On board Ethernet port supporting TCT/IP protocol. Acts as a small web-

server. Also supports MODBUS TCP/IP. RS485 port with MODBUS-RTU protocol. Demand Measurement: Fixed or Sliding for KW or KVA. Predictive Demand for Fix 30 minutes Window Harmonics measurement: All six waveforms upto 29th including THD. Bright Red LED display. Three rows of 8-digits each ensure unbroken display

even large energy register values. Four relay outputs for Alarm & Trip. Limits are field programmable. Event definition and logging. Data logging of all parameters for load pattern analysis. 2 MB memory on-

board. USB 2.0 port to download logged data. USB 2.0 port based programming of field selectable parameters.

SLM102 – Operational Manual

TRINITY [5]

Comprehensive and Accurate Measurement: 3Φ Voltage (L-N), 3Φ Voltage (L-L), 3Φ Current

KW (3Φ and Total), KVAR (3Φ and Total), KVA (3Φ and Total), PF (3Φ and

Total)

Bidirectional KWh, KVAh, KVARh, Frequency, THD and Demand & MD

Advance Measurement Features: SLM102 also measures the minimum & maximum values and also allows definition of events, so that the user can define the parameter of interest, event definition value and related time.

Voltage min/max. -

3Φ L-N

Voltage min/max. - 3Φ L-L (applicable only for 3P3W)

Current min/max. - 3Φ.

Hz min/max.

Active Power min/max. - 3Φ & Σ system

Apparent Power min/max. - 3Φ & Σ system

Harmonic Measurement SLM102 measures the odd harmonics for 3Φ voltages and 3Φ currents upto 29th, including THDs for each waveform. Relay Outputs Options • Programmable relays for alarm or trip. • Alarm relays are individually configurable for different parameters. • Maximum Demand measurement in Sliding Window, or fixed window modes for

effective management of demand Data Logging • ON board 2 MB of Memory. • Logs all Min. /Max. Values. (Voltage, Current, Watt, VA, System Watt, System VA,

PF and Frequency). • Logs all electrical parameters, real-time and integrated (energies and demands)

and harmonics to get complete Energy system snap-shot. • Events Logging: 4 Events can be programmed by the user for: Each event log

consists of parameter of interest, date and time of event occurred.

SLM102 – Operational Manual

TRINITY [6]

Communications • USB port for downloading of logged Data and Programming of field parameters. • Supports MODBUS-RTU protocol on RS485 • Ethernet (TCP/IP). Also supports MODBUS-TCP/IP protocol • Acts as a mini web-server

Display

• Easy user interface through four push buttons switches. • Bright Red LED Display. Three rows of 8-digits each ensure unbroken display of

even large energy register values • Two LEDs for Active and Reactive Energy (1000 impulse / KWh or KVARh)

SLM102

SLM102 – Operational Manual

TRINITY [7]

Technical Specifications True RMS Basic Parameters

Parameter Mode

Type Statistics Symbol 3P4W 3P3W

Voltage (Volts L-N)

Direct Voltage Input PT Ratio Range of Reading Accuracy

: 0 to 300V AC : Programmable up to 66KV : 0.0 to 66KV : 0.2% of Reading :(50 < V < 300)

Vr √ -

Vy √ -

Vb √ -

Voltage (Volts L-L)

Direct Voltage Input PT Ratio Range of Reading Accuracy

: 0 to 450V AC : Programmable up to 66KV : 0.0 to 66KV : 0.5% of Reading :(85 < V < 545)

Vry √ √

Vbr √ -

Vby √ √

Current (Amps Ir, Iy, Ib)

Secondary Current Input CT Ratio Range of Reading Accuracy

: 1A or 5A : Programmable 5A to 5000A : 0.00 to 5000A : 0.2% of Reading (0.02 Ib< I < 1.2 Ib)

Ir √ √

Iy √ -

Ib √ √

Line Frequency 45 to 55 Hz, Accuracy

: 0.5% of Reading Hz √ √

Power

Parameter Mode

Type Statistics Symbol 3P4W 3P3W

Active Power (P)

Accuracy

: See Table-1 ( 0.5 < COSǾ < 0.8 )

(P) R-Phase √ √ (P) Y-Phase √ - (P) B-Phase √ √

Reactive Power (Q)

Accuracy

: See Table-1 ( 0.5 < SINǾ < 0.8 )

(Q) R-Phase √ √ (Q) Y-Phase √ - (Q) B-Phase √ √

Apparent Power (S) Accuracy

: 0.3% of Reading (0.01 Ib ≤ I < Imax)

(S) R-Phase √ - (S) Y-Phase √ - (S) B-Phase √ -

System Active

Power (P)

Accuracy

: See Table-1 ( 0.5 < COSǾ < 0.8 )

∑-P √ √

System Reactive

Power (Q)

Accuracy

: See Table-1 ( 0.5 < SINǾ < 0.8 )

∑-Q √ √

Apparent Power (S) Accuracy

: 0.3% of Reading (0.01 Ib ≤ I < Imax) ∑-S √ √

Power Factor

0.5 % for 0.5 < |PF| < 0.8, (0.05 Ib < I < 1.2 Ib)

PF R-Phase √ - PF Y-Phase √ - PF B-Phase √ - System PF √ √

SLM102 – Operational Manual

TRINITY [8]

Table 1- Percentage Error Limits for Power

Value of Current Power Factor Percentage Error Limits

0.01 Ib ≤ I < 0.05 Ib 1.0 ±0.4 0.05 Ib ≤ I ≤ Imax 1.0 ±0.2 0.02 Ib ≤ I < 0.1 Ib 0.5 Lagging ±0.5

0.8 Leading ±0.5 0.1 Ib ≤ I ≤ Imax 0.5 Lagging ±0.3

0.8 Leading ±0.3

Energy Parameter Mode

Type Statistics 3P4W 3P3W

Total Active Energy (KWh)

Range of reading Accuracy

: 0 to 9999999.9 MWh : 0.2S as per IS14697:1999. √ √

Total Reactive Energy (KVARh)

Range of Reading Accuracy

: 0 to 9999999.9 MVARh : 0.2S as per IS 14697:1999.

√ √

Total Apparent Energy (KVAh)

Range of Reading

: 0 to 9999999.9 MVAh

√ √

Demand

Parameter Mode

Statistics Symbol 3P4W 3P3W Active Power (KW) Demand : Sliding & Fixed Selectable

KWDMND √ √

Apparent Power (KVA) Demand : Sliding & Fixed Selectable

KVADMND √ √

Power Quality

Parameter Mode 3P4W 3P3W

Harmonics for Voltages(3rd to 29th ) √ √

Harmonics for Currents(3rd to 29th ) √ √

THD for each voltage √ √

THD for each current √ √

SLM102 – Operational Manual

TRINITY [9]

Minimum-Maximum

Parameter Mode

Type Statistics Symbol 3P4W 3P3W

VO

LTS

Min-Max Volts

(Volts L-N) (Volts L-L)

Minimum Value of Volt

Vr √ - Vy √ - Vb √ - Vry - √ Vbr - - Vby - √

CU

RREN

T

Min-Max Current (Amps

Ir, Iy, Ib)

Minimum Current Value

Ir √ √

Iy √ -

Ib √ √

HZ Min.–Max.

Line Frequency Minimum Line Frequency Hz √ √

W

ATT Min.-Max.

Active Power (P)

Minimum Active Power

(P) R-Phase √ √

(P) Y-Phase √ -

(P) B-Phase

√ √

VA Min.-Max.

Apparent Power (S) Minimum Apparent Power

(S) R-Phase

√ -

(S) Y-Phase

√ -

(S) B-Phase

√ -

SYSTEM

W

ATT Min.-Max.

System Active Power

(P)

Minimum System Active Power ∑-P √ √

SYSTE

M

VA

Min.-Max. System Apparent Power

(S)

Minimum System Apparent Power ∑-Q √ √

D

EM

AN

D Max. Demand Maximum Demand Value.

KW or

KVA √ √

Predictive Demand Fix-30 minutes Window KW or

KVA √ √

SLM102 – Operational Manual

TRINITY [10]

Input Specifications Supply : Three Phases and Neutral of a 3P4W

system / three phases of a 3P3W system

Voltage

Direct Voltage Input : Up to 480V L-L and 300V L-N

PT Ratio : Programmable up to 66KV

Site selectable.

Range of Reading : 1-66KV

Burden : 0.5VA

Current

Secondary Current

Input : 5A or 1A

Range of Reading : 5A – 5000A

Burden : < 1.0VA

Overload : 5A CT = 6A RMS Continuous

1A CT = 5A RMS Continuous

Power Supply:

Self Power. Unit has in-built 3 phase supply with an operating range of 50VAC -

480 VAC, 50-60 Hz.

Output Specifications Programmable Relay Output

Relay outputs : 4.

Relay rating : 3A @ 230 VAC, Resistive load.

SLM102 – Operational Manual

TRINITY [11]

Installation and Commissioning The SLM102 supports two installation modes – 3P4W and 3P3W. The installation processes of these modes are described below:

3P4W Installation Mode Follow these steps to install / commission the unit.

1. Push the unit into the panel and mount using the clamps provided. The unit is not required auxiliary supply as unit has in-built 3 phases supply with an operating range of 50VAC - 480VAC, 50-60 Hz.

2. Connect the three phases with the phase sequence being R-Y-B to the terminals marked U1, U2 and U3 respectively. Make sure that the three phases coming to the unit come through control fuses of 1.0 Amp rating. This will protect the electronics inside from damage due to severe over voltages or phase faults in the system.

3. Connect the neutral to the terminal marked U4.

4. Connect the two wires from the R-phase CT to terminals marked M1 & L1

such that S1 from CT goes to M1 on the unit. Connect the two wires from the Y-phase CT to terminals marked M2 & L2 such that S1 from CT goes to M2 on the unit. Connect the two wires from the B-phase CT to terminals marked M3 & L3 such that S1 from CT goes to M3 on the unit.

5. Switch on the three phase supply as well as Auxiliary supply. The unit will

come alive and display power information such as factory location for about three seconds and then, it will display the first page of Run Mode.

6. If there is very little current or no current in the CT circuits, the unit may show

PFs as 0.999 or 1.000. This will go away as soon as the current builds up in the CTs, above 0.4 % of rated CT.

SLM102 – Operational Manual

TRINITY [12]

7. Now, the unit needs to be programmed for the various parameters which are

field programmable. For this refer to next section “OPERATIONAL DETAILS”

8. The unit is ready for operation.

SLM102 – Operational Manual

TRINITY [13]

3P3W Installation Mode Follow these steps to install / commission the unit.

1. Push the unit into the panel and mount using the clamps provided. The unit is not required auxiliary supply as it has in-built 3 phase supply with an operating range of 50VAC - 480 VAC, 50-60 Hz.

2. Connect the three phases with the R phase to terminal U1, B phase to terminal U3 and Y phase to terminal U4. Make sure that the three phases coming to the unit come through control fuses of 1.0 amp rating. This will protect the electronics inside from damage due to severe overvoltages or phase faults in the system.

3. Connect the two wires from the R-phase CT to terminals marked M1 & L1

such that S1 from CT goes to M1 on the unit. Connect the two wires from the B-phase CT to terminals marked M3 & L3 such that S1 from CT goes to M3 on the unit.

4. Switch on the three phase supply. The unit will come alive and display power

receiving information such as factory location for about three seconds and then, it will display the first page of Run Mode.

5. If there is very little current or no current in the CT circuits, the unit may show

PFs as 0.999 or 1.000. This will go away as soon as the current builds up in the CTs, above 0.4 % of rated CT.

6. Now, the unit needs to be programmed for the various parameters which are field programmable. For this refer to next section “OPERATIONAL DETAILS”.

7. The unit is ready for operation.

SLM102 – Operational Manual

TRINITY [14]

Connection Scheme

SLM102 – Operational Manual

TRINITY [15]

RS485 Connection

SLM102 – Operational Manual

TRINITY [16]

Operational Details The load manager SLM102 is a versatile meter, with all the features needed to implement with a robust electrical load management system. It can be configured to suit most control and communication needs. The unit is achieved by making as many parameters field programmable, as much as possible. There are basically three Modes of operation:

1. Programming Mode 2. Programming Mode using USB Utility 3. Run Mode

For Programming Mode using USB Utility, refer to last section, ”Data Logging and USB Port”. After supplying power (50 VAC - 480 VAC) to the three phases, the unit displays immediately power receiving information such as Factory name, RTC and then, enters into first page of Run Mode with the following display.

Now, user will enter into Programming Mode to define for all the desire parameters and can also operate the Run Mode by pressing keys provided with the following:

SLM102 – Operational Manual

TRINITY [17]

Programming Mode The unit is designed with a default password protection,”1947”. The password is also changeable from 0 to 9 according to user’s desire (see in the next section, programmable parameter, “Change Password”). The user will therefore enter a password before entering into Programming Mode. Now, press key for about 4 seconds and then, the password display will prompt with a four digits of zeroes of which first zero will be blinking.

To enter the password, press key one time to set for 1; press key to shift into second digit; Press again nine times to set for 9, press key again to shift into 3rd digit and press key four times to set for 4 and then, press key to shift into 4th digits and press key seven times to set for 7. If any digit entered is wrong and needs to enter again, press key several times till the digit becomes bilking and set as above steps. After entering the default password, press key to enter into Programming Mode (the display is shown in the next section). Hence, if the unit is in Programming Mode and keys are not operated for about 4 minutes, unit will return into Run Mode.

Setting CT-Primary and date according to RTC CT-Primary The CT Primary should be set to give actual current values for CT operated meter and is also freely programmable from 5A to 5000A. Date The date is RTC and can also be set with the format of date, month and year. i.e., DD/MM/YYYY format. To set CT Primary and Date, proceed the following instructions.

SLM102 – Operational Manual

TRINITY [18]

1. After entering the password as before, the unit will prompt with the following

display.

2. In the above first row, CT-Primary displays along with character ‘C’ blinking

that shows the parameter is selected for setting. Press key that will start blinking with the first digit of a value. Set CT-Primary by pressing and keys and press key to confirm the setting so that the blinking character will also return.

3. Press key that starts blinking DATE(dd) in second row which shows

DATE is selectable. Press key that blinks digit (i.e., 10) in third row. Set

DATE by pressing and keys as per current date. Press key to confirm the setting so that the blinking character will also return.

4. Press key to set MONTH that will start blinking with character (MM) in second row. press key that will start blinking with digit in third row. Set MONTH by pressing and keys. Press key to confirm the setting so that the blinking character will also return.

5. If the setting is completed press key for about four seconds to return into Run Mode. Otherwise, press key to enter into next programmable parameter.

Setting PT Ratio and Time according to RTC PT Ratio The PT-Ratio should be set so as to give actual voltage for PT-operated meter. The PT Ratio is selectable from any one of the following: 1, 30, 60, 100, 200, 300 and 600. Time The Time is RTC and can also be set with the format of hh.mm.ss.

SLM102 – Operational Manual

TRINITY [19]

To set PT Ratio and Time, proceed the following instructions.

1. In previous programmable parameters, press key till the next display enters such as shown below.

2. Set PT Ratio and TIME such as previous steps of CT Primary and DATE setting.

Setting Log Duration, Demand Window and Unit Address Log Duration For data logging, the Log Duration can be specified from 1 to 60 minutes. SLM102 has the capability to log data on its own Non-volatile RAM. This data is logged in an FIFO buffer. Once the buffer (23271 records) is full, the oldest data is discarded and the newest data is filled into the buffer. This data can then be downloaded by using a software utility provided by Trinity, into a PC, record by record. Demand Window The unit supports two types of demand window for the calculation of demand such as Fixed window or Sliding window. In case of Sliding Window, the method is selectable to either 30 minutes interval or 15 minutes interval. In case of Fixed Window, the method is 30 minutes interval only and hence, Predictive Demand will also display in Run Mode. Unit Address The unit address is for RS485 communication port only. For communicating in between the unit and host, the same unit address should be set from 1 to 255 accordingly. To set the Log Duration, Demand Window and Address, proceed the following instructions.

1. In the previous programmable parameter, press key till the next display enters such as shown below

SLM102 – Operational Manual

TRINITY [20]

2. In the above first row, Log Duration displays along with character ‘L’ blinking that shows the parameter is selected for setting. Press key that will start blinking with first digit. Set Log Duration by pressing and keys and press key to confirm the setting so that the blinking character will also return.

3. Press key to set for seond row, Dimand Window that Window will start blinking with its first character, ‘w’ and now set as above steps of Log duration. Similalry set Unit Address also.

4. If the setting is completed press key for about four seconds to return into Run Mode. Otherwise, press key to enter into next programmable parameter.

Selecting Demand On, Installation type and CT-Secondary Demand On Both the two KW Demand and KVA Demand can be set according to user’s desire for the calculation of Demand to either KVA or KW with an integration period of 30 or 15 minutes. Installation Types Unit supports two types of Electrical Installation such as 3P4W and 3P3W. User should select the installation type accordingly. CT-Secondary The CT Secondary can be selected to either 1 or 5 and the user should select the CT Secondary to give actual current value for CT operated meter. To set the above parameters, proceed the following instructions

SLM102 – Operational Manual

TRINITY [21]

1. In the previous programmable parameter display, press key till the next display enters such as shown below

2. In the above first row, DEMAND (DMD) displays along with character ‘D’

blinking that shows the parameter is selected for setting. Press key that will start blinking to either KW (W) or KVA(VA) . Set DEMAND by pressing

and keys and press key to confirm the setting so that the blinking character will also return. While selecting the Demand to KVA or KW, LED indicator will glow such as above solid circled parameters respectively.

3. Press key to set for second row, INSTALLATION (INS) that the character (i) will start blinking and set as steps above. Similalry set Unit Address also.

4. If the setting is completed press key for about four seconds to return into Run Mode. Otherwise, press key to enter into next programmable parameter.

Setting Four Alarm Relays, Alarm On, Alarm Value and Alarm Hysteresis Alarm Relay The unit has four relay contacts, which are individually field programmable from 1 to 4. However, the Delay for each Alarm relay can be programmed from 5 to 120 seconds using USB Logger utility only. In case of Demand, the Delay is fixed with 2 seconds. This Delay programming is applicable only for USB utility. Refer last section, “Programming Mode Using USB Logger Utility”. If user is not desired USB programming utility, Alarm Delay will be 5 seconds by default only.

SLM102 – Operational Manual

TRINITY [22]

Alarm On There are seven alarm parameters: Avg. Volts(VOLT), Avg. Amps(AMPS), KVA(VA), KW(VATT), KVAR(VAR), Demand(DMD), PF(PF) and None(NONE). These parameters are programmable for each alarm relay according to user’s requirement. In case, any Alarm parameter is not desired, NONE should be selected. Alarm Value Alarm values are freely programmable from 1 to 9999. In case of VOLT, the value is freely programmable from 1 to 99999. The value indicates the level at which the relay will close. E.g. If the Alarm On has been selected to KW, and the value is set to 450, the relay will close when the KW exceeds 450 and remains so for 1 minute. Also, the switching ON logic for PF is reversed. For all parameters, the relay closed when the parameter value exceeds that defined by Value for more than one minute. In case of PF however, the relay will close when the PF falls below the Value and remains so for more than one minute. Also, the PF Value is entered with a multiplication factor of 1000. e.g. If Second Relay is programmed for which ALARM ON is set to PF and ALARM VALUE is 955, then the second relay should close when the PF value falls below 0.955. Alarm Hysteresis The last parameter called Hysteresis defines the opening point for the relay which has closed in response to an alarm condition. This is specified as % of the Value. Thus, setting Hysteresis of 2 implies that the relay which closes when the parameter reaches Value, will open when the parameter falls below 0.98 x Value. This is done to prevent frequent operation / nuisance operation of the relay near the Value. To set the Alarm Parameters, proceed the following instructions.

1. In the previous programmable parameter display, press key till the next display enters such as shown below.

SLM102 – Operational Manual

TRINITY [23]

2. In the above first row, Relay (RL) displays along with character ‘R’ blinking that

shows the Relay is selected for setting. Press key that will start blinking digit (i.e., 2). Set Relay by pressing and keys and press key to confirm the setting so that the blinking character will also return.

3. Press key to set for Alarm Parameter that the character ‘d’ will start

blinking and press key and set as steps above. While selecting the Alarm parameters, LED indicator will glow such as above solid circled parameters respectively.

4. Press key to set for second row that blinks ‘V'. Press key that the digit start blinking. Set the Alarm Value such as steps above. Similalry set Hysteresis also.

Setting Four Events, Event On, Event Value and Event Hysteresis As previous Relays, unit has also four events which are individually field programmable from 1 to 4. There are 16 Logs that can be stored for each event. So that there are 64 logs for all four events. Each log stores event type and date-time of event occurrence. Event On Same as “Alarm On”. Event Value Same as “Alarm Value”. Event Hysteresis Same as “Alarm Hysteresis”.

1. In the previous programmable parameter display, press key till the next display enters such as shown below.

SLM102 – Operational Manual

TRINITY [24]

2. Set all the Event parameters such as same steps of Relays before .

Selecting Baud Rate for RS485 Port and Changing Password Baud Rate In case of RS485 connection, the baud rate is settable to either 9600 or 19200 for the speed of downloading. User can download live data to a host using software utility. Password The numerical password used can be changed according to user’s desire from 0 to 9. In case, the PASSWORD is not desired, set zero only for all four digits. In the PASSWORD prompt, just press key only to enter into Programming Mode! To set Baud Rate and password change, proceed the following instruction

1. In the previous programmable parameter display, press key till the next display enters such as shown below.

2. In the above first row, Baud Rate displays along with character ‘B’ blinking

that shows the parameter is selected. Press key that will start blinking digit (i.e., 9). Set Baud Rate by pressing and keys and press key to confirm the setting so that the blinking character will also return.

3. Press key to enter into next row, PASSWORD that character ‘P’ will also blink. Now, press key that will start blinking first digit ‘0’ and set by pressing key only and then, press key to shift to next digit and set by pressing key only. Similay, Set for rest digits also. If any set digit is supposed to change again, press key several times to return onto the desired digit.

Setting IP Address

SLM102 – Operational Manual

TRINITY [25]

The IP Address consists of four bytes. This IP address is necessary when PC is connected to the LAN or Internet. IP Address is a location of a given computer for network devices. Each byte can be set from 000 to 255.

1. In the previous programmable parameter display, press key till the next display enters such as shown below.

2. In the above first row, IP displays along with character ‘ip’ blinking that

shows the parameter is selected. Press key that first byte starts blinking. Set first byte by pressing key only and press key to shift to next IP address. Set such as same steps for third IP address and fourth IP address also.

3. If the setting is completed press key for about four seconds to return into Run Mode. Otherwise, press key to enter into next programmable parameter.

Setting MAC Address User can enter 6 bytes of MAC address. In a local area network (LAN) or other network, the MAC (Media Access Control) address is computer's unique hardware number (on an Ethernet LAN, it's the same as Ethernet address). The MAC address is used by the Media Access Control sub layer of the Data-Link Layer of telecommunication protocols. Each byte can be set from 000 to 255.

1. In the previous programmable parameter display, press key till the next display enters such as shown below.

SLM102 – Operational Manual

TRINITY [26]

2. In the above first row, MAC Address displays along with character ‘m’ blinking

that shows the parameter is selected. Press key. The characters, MAC ADDRESS shown above will be replaced by first byte and second byte such as diplay below.

3. In the first row, first digit of the fist byte will start blinking. Now set by pressing key only and press key to shift to second byte. Set second byte by

pressing key only and press key to shift onto third byte in second row and set it also such as same steps. Similarly, set fourth, fifth and sixth byte also. After setting all six bytes, press key to confirm that will return such as first display.

4. If the setting is completed press key for about four seconds to return into Run Mode. Otherwise, press key to enter into next programmable parameter.

SLM102 – Operational Manual

TRINITY [27]

Resetting Demand Manually / Daily/Monthly Reset Demand can be specified such as whether the demand will be reset automatically or manually. In case of automatic reset, there are two options: auto day (auto dd) or auto month (auto mm). If user selects auto day then MD will reset for every 24 hrs at 12:00 a.m. and if user selects auto month then MD will reset on 1st of every month at 7:00 a.m. To Reset Demand, proceed the following instructions.

1. In the previous programmable parameter display, press key till the next display enters such as shown below.

2. In the above first row, Demand Reset displays along with character ‘d’

blinking that shows the parameter is selected. Press key that reset type, e.g Auto Daily ‘A’ starts blinking. Select the reset types by pressing and

key and then, press key to confirm the setting. 3. If the setting is completed, press key for about four seconds to return into

Run Mode. Otherwise, press key to enter into next programmable parameter.

SLM102 – Operational Manual

TRINITY [28]

Resetting Energy The three energies-KWh, KVAh and KVARh can be reset to zeroes according to user’s requirement. To reset Energies, proceed the following instructions

1. In the previous programmable parameter display, press key till the next display enters such as shown below.

2. In the above first row, Reset Energy displays along with character ‘R’ blinking

that shows the parameter is selected. Press key that will blink to a parameter in second row. Select the Energy by pressing and key where LED indicator will glow onto KWh, KVAh and KVARh respectively. Now, press key to confirm the setting. Simultaneously, the unit will also reset and return into Run Mode.

Resetting Minimum and Maximum Parameters All the minimum and maximum parameter values can be reset. To Reset Minimum and Maximum, proceed the following instructions.

1. In the previous programmable parameter, Reset Energy display, Select the Minimum(min) by pressing and key such as same steps of Reset Energy where LED indicator will glow onto KW(WATT), HZ, KVA(VA), KVAR(VAR), VOLT, current(AMPS), Minimum(MIN) and Maximum(Max) such as shown below.

SLM102 – Operational Manual

TRINITY [29]

2. Now, press key to confirm the setting. Simultaneously, the unit will also restart and return into Run Mode.

Resetting KW Demand and KVA Demand Both KW Demand and KVA Demand can be reset. To reset both demand, proceed the following instructions.

1. In the previous programmable parameter, Reset Energy display, Select the Demand(DEMAND) by pressing and key such as same steps of Reset Energy where LED indicator will glow onto Demand (DMND) such as shown below.

2. Now, press key to confirm the setting. Simultaneously, the unit will also restart and return into Run Mode.

SLM102 – Operational Manual

TRINITY [30]

Resetting Log The logged data can be reset. To reset Log, proceed the following instructions.

1. In the previous programmable parameter, Reset Energy display, Select the Log(LOG) by pressing and key such as same steps of Reset Energy such as shown below.

2. Now, press key to confirm the setting. Simultaneously, the unit will also restart and return into Run Mode.

Resetting Events Logging All the four Events under which the desired parameters have been logged can be reset. To reset Events Logging, proceed the following instructions.

1. In the previous programmable parameter, Reset Energy display, Select the Demand(DEMAND) by pressing and key such as same steps of Reset Energy where LED indicator will glow onto Demand (DMND) such as shown below.

SLM102 – Operational Manual

TRINITY [31]

2. Now, press key to confirm the setting. Simultaneously, the unit will also restart and return into Run Mode.

Resetting All Parameters All the parameters can be reset. To reset all parameter, proceed the following instructions.

1. In the previous programmable parameter, Reset Energy display, Select the All (ALL) by pressing and key such as same steps of Reset Energy with the following display.

2. Now, press key to confirm the setting. Simultaneously, the unit will also restart and return into Run Mode.

SLM102 – Operational Manual

TRINITY [32]

Run Mode In the Run Mode, the various parameters measured and calculated by the meter are displayed on different pages; on a “seven segment LED” display. The pages will automatically scroll one by one at every 4 to 5 seconds. Press enter key to freeze the page. Freeze LED indicator will glow. In freeze condition, user can change the page using up or down key. The measured or calculated values displayed will auto scale to Mega from Kilo and to Kilo from value, once the value crosses 10,000. e.g., Once Wh ≥ 10000.0, it will show as 10.000 KWh and if value crosses 10000000 then it shows 1.000000 MWh. If the user has selected a PT-Ratio (PT-Primary/PT-Secondary)>1.0, voltages will auto scale to KV. SLM102 shows measured and calculated values on following different pages:

Run Mode Displays

The first page shows phase to neutral voltage in three phases. The LED indicator glows onto VOLT and PHASE which indicates that R-Phase, Y-Phase and B-Phase display in first row, second row and third row respectively. In case of 3P3W, the page will show phase to phase Voltage with R-phase in first row and B-phase in third row.

SLM102 – Operational Manual

TRINITY [33]

The second page shows individual current in three phases. The LED indicator glows onto AMPS and PHASE which indicates that R-Phase, Y-Phase and B-Phase display in first row, second row and third row respectively.

The third page shows Active Power (KW) in three phases. The LED indicator glows onto WATT and PHASE which indicates that R-Phase, Y-Phase and B-Phase display in first row, second row and third row respectively.

SLM102 – Operational Manual

TRINITY [34]

The fourth page shows Apparent Power (KVA) in three phases. The LED indicator glows onto VA and PHASE which indicates that R-Phase, Y-Phase and B-Phase display in first row, second row and third row respectively. This page is not applicable for 3P3W.

The fifth page shows Reactive Power (KVAR) in three phases. The LED indicator glows onto VAR and PHASE which indicates that R-Phase, Y-Phase and B-Phase display in first row, second row and third row respectively.

SLM102 – Operational Manual

TRINITY [35]

The sixth page shows PF in three phases. The LED indicator glows onto PF and PHASE which indicates that R-Phase, Y-Phase and B-Phase display in first row, second row and third row respectively. This page is not applicable for 3P3W.

The seventh page shows system powers. The LED indicator glows onto WATT, VA and VAR which indicates that Active Power (KW), Apparent Power (KVA) and Reactive Power (KVAR) display in first row, second row and third row respectively.

SLM102 – Operational Manual

TRINITY [36]

The eight page shows system PF with lagging PF and Frequency (Hz). The LED indicator glows onto PF and HZ which indicates that PF and Frequency display in first row and second row respectively.

The ninth page shows three Energies. The LED indicator glows onto Wh, VAh and VARh which indicates that Active Energy (KWh), Apparent Energy (KVAh) and Reactive Energy (KVARh) display in first row, second row and third row respectively.

The tenth page shows individual Voltage in three phases. The LED indicator glows onto VOLT which indicates that R-Phase, Y-Phase and B-Phase display in first row, second row and third row respectively. This page is not applicable for 3P3W.

SLM102 – Operational Manual

TRINITY [37]

The eleventh page shows THD Voltage in three phases. The LED indicator glows onto VOLT, THD and PHASE which indicate that THD voltage in R-Phase, Y-Phase and B-Phase display in first row, second row and third row respectively.

The twelfth page shows THD current in three phases. The LED indicator glows onto THD, AMPS and PHASE which indicate that THD current in R-Phase, Y-Phase and B-Phase display in first row, second row and third row respectively.

The thirteenth page shows minimum voltage in three phases. The LED indicator

SLM102 – Operational Manual

TRINITY [38]

glows onto VOLT, MIN and PHASE which indicate that minimum voltage in R-Phase, Y-Phase and B-Phase display in first row, second row and third row respectively.

The fourteenth page shows minimum current in three phases. The LED indicator glows onto AMPS, MIN and PHASE which indicate that minimum current in R-Phase, Y-Phase and B-Phase display in first row, second row and third row respectively.

The fifteenth page shows minimum Active Power in three phases. The LED indicator glows onto WATT, PHASE and MIN which indicate that minimum WATT in R-Phase, Y-Phase and B-Phase display in first row, second row and third row respectively.

SLM102 – Operational Manual

TRINITY [39]

The sixteenth page shows minimum Apparent Power (KVA) in three phases. The LED indicator glows onto VA, PHASE and MIN which indicate that minimum Apparent Power in R-Phase, Y-Phase and B-Phase display in first row, second row and third row respectively.

The seventeenth page shows minimum system of Active Power, Frequency (Hz) and Apparent Power. The LED indicator glows onto Active Power (WATT), Frequency (HZ) and Apparent Power (VA) which indicate that Active Power, Frequency and Apparent Power display in first row, second row and third row respectively.

SLM102 – Operational Manual

TRINITY [40]

The eighteenth page shows Maximum Voltage in three phases. The LED indicator glows onto VOLT, MAX and PHASE which indicate that maximum voltage in R-Phase, Y-Phase and B-Phase display in first row, second row and third row respectively.

The nineteenth page shows minimum current in three phases. The LED indicator glows onto AMPS, MIN and PHASE which indicate that minimum Current in R-Phase, Y-Phase and B-Phase display in first row, second row and third row respectively.

SLM102 – Operational Manual

TRINITY [41]

The twentieth page shows maximum current in three phases. The LED indicator glows onto AMPS, MAX and PHASE which indicate that maximum current in R-Phase, Y-Phase and B-Phase display in first row, second row and third row respectively.

The twenty-first page shows maximum Active Power in three phases. The LED indicator glows onto WATT, PHASE and MAX which indicate that maximum Active Power in R-Phase, Y-Phase and B-Phase display in first row, second row and third row respectively.

SLM102 – Operational Manual

TRINITY [42]

The twenty-second page shows maximum Apparent Power in three phases. The LED indicator glows onto Apparent Power (VA), PHASE and MIN which indicate that maximum Apparent Power in R-Phase, Y-Phase and B-Phase display in first row, second row and third row respectively.

The twenty-third page shows maximum Active Power, Frequency, Apparent Power. The LED indicator glows onto Active Power (WATT), HZ, VA and MAX which indicate that maximum Active Power, Frequency and Apparent Power display in first row, second row and third row respectively.

SLM102 – Operational Manual

TRINITY [43]

The twenty-fourth page shows Sliding Active Power Demand for 15 minutes. In case user defined demand is Apparent Power, the display will show “DMD-VA" in second row. The LED indicator glows onto WAT and DMND which indicate that Demand window is Active Power.

The twenty-fifth page shows maximum Active Power Demand occurrence with date and time. The LED indicator glows onto WATT, DMND and MAX for Active Power Demand. However, LED indicator will glow onto VA, DMND and MAX if user defined demand is Apparent Power. In fact, the demand is registered with following:

In case of fixed window selection, the demand is integrated over 30 minutes. In case of sliding window, it is integrated over 15 or 30 minutes, as selected by the user.

If the demand is calculated by the meter, based on sliding window technique,

then unlike utility installed demand meters, this demand figure does not reset to zero at the end of the 30 minute integration window.

If the user has initially selected KVA as demand parameter, the figure in the

SLM102 – Operational Manual

TRINITY [44]

Maximum Demand register is that of KVA demand. If later, the user changes the parameter to KW, the Maximum Demand register does not change. It continues to show the highest Demand reached to date, which was in KVA. This is because there is only one Maximum Demand register.

The twenty-sixth page shows last maximum Demand occurrence and status of the logging buffer. The demand displayed is the last maximum demand. If present maximum demand is 400 KVA and reset it and then, maximum Demand will become zero and Last maximum Demand will hold as 400 KVA.

The twenty-seventh page shows Predictive Demand. The LED indicator glows onto VA and DMND which shows Predictive Demand is for VA. If user selectable parameter is Watt (W), the LED indicator will glow onto WATT and DMND.

SLM102 – Operational Manual

TRINITY [45]

The twenty-eighth page shows alarm relays programmed for desired parameters. It also display the relays switch on with the futures 1, 2 and 3 whereas relay 4 is switched off.

The twenty-ninth page shows four events logging under which event 1 stores 10 logs; event 2 stores 12 logs; event 3 stores 11 logs; and event 4 stores 16 logs. This event logging can be seen to the USB data downloading. The maximum Log is 16 for each event. Once the Log is overflow, the event will start logging from 1 and OVERFLOW will show YES.

SLM102 – Operational Manual

TRINITY [46]

The thirtieth page shows number of logs with RTC date and time. The maximum log for all the parameters is 23271 records.

SLM102 – Operational Manual

TRINITY [47]

Communications

In addition to the industry standard RS-485 communication port, several other communication options are also available in SLM102. These options make it possible for a user to select SLM102 to provide power and energy information into a variety of existing or new control systems and communication networks. Each communication option supports data transfer with external devices or applications. Metering measurement, logged data, configuration and status data may be accessed via communication. SLM102 supports USB 2.0 for downloading of logged data, MODBUS-RTU on RS-485 port and an Ethernet port supporting TCP/IP protocol, which can be used as a small web-server and also in MODBUS-TCP/IP mode to connect to a SCADA application.

MODBUS RTU on RS485 Port The SLM102 support an isolated RS485 port, for half duplex multi-drop communication using MODBUS-RTU protocol. This makes it easy to integrate SLM102 to any EMS/SCADA application. The station id for every meter is site selectable, and so is the baud rate. The data which can be read using MODBUS query # 3 (Read Holding Registers) is provided in an address map, with the applicable multiplication factors, vide Appendix in last section. Communication line parameters: 9600 or 19200/8/N/1.

SLM102 – Operational Manual

TRINITY [48]

The register map is described in Appendix. All addresses are in decimal whose parameters are unsigned long. If illegal address is sent in query or the host, tries to read more than 64 bytes of data in one query exception message is generated. Reserved values are for future use, which are transmitted as zeroes.

Ethernet TCP/IP Communication Ethernet-TCP/IP connection, Multiple sockets Ethernet connectivity enables the unit to respond to as many as 12 different requests. The SLM102 can act as a small web-server. This on-board web-sever, offers quick and easy access to basic measurement, without special software. Built-in web pages display a range of power, energy and basic power quality information through any web enabled device. It also supports MODBUS-TCP/IP protocol. To access the Ethernet TCP/ IP communication, connect the RJ45 Ethernet cable into the port provided at the bottom of the unit and enter your protocol in the address bar and then, the web page will open such as shown below.

SLM102 connected as Mini Web Server to a web browser.

User can browse four pages such as Home, Individual parameters, Minimum and Maximum parameters and system values.

SLM102 – Operational Manual

TRINITY [49]

Data Logging and USB Port SLM102 has a 2 MB non-volatile memory. This memory is used to store the minimum and maximum values of important parameters, events as defined by the user and the snapshot of the entire electrical system where all instantaneous and integrated parameters along with Harmonic data are saved. Maximum numbers of such electrical snapshots are 23271. While the electrical snapshots as saved in the logs can give a good idea of the overall behavior of the system, the Event Log feature captures time-stamped records of important power system occurrences that can be aligned with corresponding production effects to better understand and optimize energy use and cost. The log maintains a time-stamped record of 26 parameters. One can monitor values over a day, a week, a month or any period to record the highest and lowest values of voltage, current, power factor including Event parameters. SLM102 supports USB 2.0 for downloading logged data. Users are provided a CD for USB software installation along with the purchase of SLM102. Before installing the software, users are advised to read carefully Read Me document in the Logger disc for a list of minimum system requirements to be installed, if uninstalled before. If your system does not meet the minimum system requirements, installation of SLM102 software will not be possible.

Installing the USB Software

1. Insert the Logger setup CD into the CD-ROM drive of your computer after windows is started.

2. Double click on the Logger and select Logger Setup or Setup and then,

double click on any of the setup to install. A wizard will welcome for Logger Setup. To proceed the installation, click Next and then, the wizard will show the following dialog box for the location.

SLM102 – Operational Manual

TRINITY [50]

3. Before selecting the location, user can also check the disk space for each drive clicking Disk Cost. The Logger Setup has also two options such as Everyone and Just me of which Everyone is selected by default. User can select Just me accordingly.

4. To confirm the installation, click Next in the next wizard and wait for some time

while proceeding the installation. After completing the installation, the wizard will ask the Logger Setup has been installed successfully. Now click Close to exit the wizard.

Installation of USB driver Make sure that the USB cable is connected in between the PC and unit. If the USB connection is not all right, remove the USB cable and connect again. If the USB is connected for the first time, the wizard will show with following option.

SLM102 – Operational Manual

TRINITY [51]

Select the option, Yes, This time only and click Next to proceed for the next wizard such as shown below.

The wizard will ask if your hardware comes with an installation CD or floppy disk, insert it now. Select the wizard option, Installation from a list or

SLM102 – Operational Manual

TRINITY [52]

specific location and click Next to give the following dialog box where the file is located.

In the above dialog box, select option Search for the best drive in these location and click check box of Include this location in the search to specify path of usb drivers and then, click Next to get the path where the file is located.

SLM102 – Operational Manual

TRINITY [53]

5. Now click OK, to complete the wizard.

6. Wait for sometime while completing the wizard and then the wizard will

prompt the new hardware gets completed. Now click Finish to complete the installation.

Handling the Logger Window The Logger window consists of the following: Downing logged data, harmonic data, Graph representation onto Logger window and Exporting the Logged data in to a excel sheet.

Downloading the Logged data 1. By default the utility will show Logger 1.0 on desktop. Double-click on the

Logger icon. Now the Logger will open with the following window.

SLM102 – Operational Manual

TRINITY [54]

2. In the unit type list box, select the SLM102 and click OK and DOWNLOAD to start downloading the logged data with the following window.

3. In this LOG DATA window, click HARMONICS DATA at the bottom of the window to open the harmonics data window for all current and voltage.

Exporting the Logged Data including Min/Max Events and Harmonics Data The logged data can also be exported into excel sheet so that the Min-Max &event logs including the Harmonics can also be obtained in it such as shown below.

SLM102 – Operational Manual

TRINITY [55]

Graph Representation The graph plots for various selected parameters of Logged data as well as system data including harmonics distortion including date and time. Hence, the back ground color, Axis colors and Label colors can also be selectable.

Plotting a Graph for Logged data. The logged data can be plotted to a graph with the selected parameters, date and time. To plot a graph, proceed the following instructions,

1. At the top of the Logger Windows, click Graph to show a graph window.

2. At the bottom of the of the graph window, enter starting date and time in the Start box, enter ending date and time in End box under Date and Time. There are also two type of Scale such as Auto scale and Manual scale. In case of Auto scale, it is already selected by default. In case of Manual scale, select Manual scale.

3. To select for the parameters to be plotted, double-click in check box which will display the parameter selected at right list such as shown below.

SLM102 – Operational Manual

TRINITY [56]

4. If the parameters selected are not desired, double-click again in the check box

to remove for a selected parameter from the list. 5. To change the color of the selected parameters displayed at right side (e.g. Ir,

Iy, Ib and KW) double-click on it, and then the color palette will show such as below.

6. Select the desired color and click Ok. Now, the selected parameter will plot with the selected color. Similarly, each selected parameter can also be plotted. Before plotting the parameters, the background color, axis color and label color

should be specified by clicking , and so as to represent along with the selected colors.

7. Now, click to plot a graph for the selected parameters such as shown below.

SLM102 – Operational Manual

TRINITY [57]

8. The plotted graphs can be saved and printed by clicking and respectively. Hence, to return into previous Logger Windows, click .

Programming Mode Using USB Utility All the users’ programmable parameters in Programming Mode of unit can also be programmed remotely using Logger Utility. Using utility, user can easily specify for all the programmable parameters which is also more convenient than the programming in unit. Make sure USB cable coming from the PC is connected to SLM102 where the USB port is provided at the top of the unit. To configure the Programming Mode using Logger utility, proceed the following instructions By default the utility will show Logger icon on desktop. Double-click on the Logger icon. Now the Logger will open with the following window.

SLM102 – Operational Manual

TRINITY [58]

Click down arrow and select SLM102(Prog) in list box that will open the page such as shown below.

By default the cursor will blink in password box which shows user will enter password and click to enter into above Programming Mode. After configuring each programmable parameter, click respectively to confirm the settings. If user selelcts Installation type and CT Ratio, the unit may restart. User will wait till the unit enters into Run Mode and then user will again enter password. In case, a message displays “Error In USB Communication” click OK and try again so that all the programmable parameter can be configured.

SLM102 – Operational Manual

TRINITY [59]

Control Outputs The relay contacts provided in SLM102 are rated for 3A @ 230VAC. They are also protected by snubbers against fast voltage transients which occur when inductive loads are switched off. Thus, the following points are to be taken care of when using these relay contacts:

1. Use 230VAC coils only in the contactors. DO NOT use 440V AC coils. 2. DO NOT switch small loads like electronic Hooters, small relays with 230VAC

coils etc. directly from the relay contact of SLM102. If done so, the small leakage current from the snubbers will not allow these loads to be switched off fully. Thus, the electronic hooters will give a low hum continuously, and the small relays will switch on but not switch off. Use these relay contacts to switch an Auxiliary contactor and put the load on the contactor contacts.

Alarm Action Considering two alarm relays with previous section, ”Setting Four Alarm Relays, Alarm On, Alarm Value and Alarm Hysteresis” in Programming Mode, user can configure for a desired parameter for alarm control action such as shown below. Relay 1

Relay 2

SLM102 – Operational Manual

TRINITY [60]

All relays, from 1 to 4 are programmable with the following parameters, Avg. Volts, Avg. Amps, KVA, KW, KVAR, Demand and PF. The value indicates the level at which the relay will close. E.g. If the Alarm On has been selected to KW, and the value is set to 450, the relay will close when KW exceeds 450 and remains so for 1 minute. All parameters have this response time of 1 minute, except Demand which has a response time of 2 seconds. This is because Demand is already an integrated parameter. Also, the switching ON logic in case of PF is reversed. For all parameters, the relay closed when the parameter value exceeds that defined by Value for more than one minute. In case of PF however, the relay will close when the PF falls below the Value and remains so for more than one minute. Also, the PF Value is entered with a multiplication factor of 1000. e.g. when the second alarm is set for PF and alarm Value is set to 955, the relay should close when the PF value falls below 0.955 The last parameter called Hysteresis defines the opening point for the relay which has closed in response to an alarm condition. This is specified as % of the Value. Thus, setting Hysteresis of 2 implies that the relay which closes when the parameter reaches Value, will open when the parameter falls below 0.98 x Value. This is done to prevent frequent operation / nuisance operation of the relay near the Value. E.g. If the Value has been set to 400, and Hysteresis to 5%, the relay will close when the parameter reaches 400 and then, the relay opens when it falls below 380. The response times as outlined above for closing of relays also applies to opening of relays. Thus, the relay will open at 380 only if the parameter falls below 380 and remains so for 1 minute (2 seconds in case of Demand). If all four relays are programmed to close on Demand and different values for closing and opening are set by the user, SLM102 can be used effectively as a Maximum Demand Controller with four relay contacts!

SLM102 as a Demand Management Each relay can be programmed separately to generate alarm on a specific parameter with its specific value. The value at which it should open is also programmable. Thus, user could have the first relay programmed to close when the avg. Voltage exceeds certain value, second when the Avg. Amps exceeds some level, third for KW, or KVAR or PF or Demand and so on. Before programming the relays, having a look into Run Mode for Predictive Demand value is true for Demand Management. This allows the user to deploy SLM102 as a true Demand manager, to generate alarm signals for four different conditions!

SLM102 – Operational Manual

TRINITY [61]

Appendix

Address map of RS485 Port for various parameters of both 3P4W and 3P3W.

RS‐485 MAP FOR SLM102          

If PF is Lead Side then PF and Var Value are Negative. 

  

                      

1000  VOLT‐R  4  FLOAT          

1002  AMPS‐R  4  FLOAT    

1004  WATT‐R  4  FLOAT    

1006  VA‐R  4  FLOAT    

1008  VAR‐R  4  FLOAT    

1010  PF‐R  4  FLOAT    

1012  3rd Har. Volt‐R  4  FLOAT    

1014  5th Har. Volt‐R  4  FLOAT    

1016  7th Har. Volt‐R  4  FLOAT    

1018  9th Har. Volt‐R  4  FLOAT    

1020  11th Har. Volt‐R  4  FLOAT    

1022  13th Har. Volt‐R  4  FLOAT    

1024  15th Har. Volt‐R  4  FLOAT    

1026  17rd Har. Volt‐R  4  FLOAT    

1028  19th Har. Volt‐R  4  FLOAT    

1030  21th Har. Volt‐R  4  FLOAT    

1032  23rd Har. Volt‐R  4  FLOAT    

1034  25th Har. Volt‐R  4  FLOAT    

1036  27th Har. Volt‐R  4  FLOAT    

1038  29th Har. Volt‐R  4  FLOAT    

1040  VOLT ‐ THD‐R  4  FLOAT    

1042  3rd Har. Amps‐R  4  FLOAT    

1044  5th Har. Amps‐R  4  FLOAT    

1046  7th Har. Amps‐R  4  FLOAT    

1048  9th Har. Amps‐R  4  FLOAT    

1050  11th Har. Amps‐R  4  FLOAT    

1052  13th Har. Amps‐R  4  FLOAT    

1054  15th Har. Amps‐R  4  FLOAT    

1056  17th Har. Amps‐R  4  FLOAT    

1058  19th Har. Amps‐R  4  FLOAT    

1060  21th Har. Amps‐R  4  FLOAT    

1062  23rd Har. Amps‐R  4  FLOAT    

1064  25th Har. Amps‐R  4  FLOAT    

1066  27th Har. Amps‐R  4  FLOAT    

1068  29th Har. Amps‐R  4  FLOAT    

1070  AMPS ‐THD‐R  4  FLOAT    

1072  VRY  4  FLOAT  148       148    

1200  VOLT‐Y  4  FLOAT          

1202  AMPS‐Y  4  FLOAT    

1204  WATT‐Y  4  FLOAT    

1206  VA‐Y  4  FLOAT    

1208  VAR‐Y  4  FLOAT    

1210  PF‐Y  4  FLOAT    

1212  3rd Har. Volt‐Y  4  FLOAT    

1214  5th Har. Volt‐Y  4  FLOAT    

SLM102 – Operational Manual

TRINITY [62]

1216  7th Har. Volt‐Y  4  FLOAT    

1218  9th Har. Volt‐Y  4  FLOAT    

1220  11th Har. Volt‐Y  4  FLOAT    

1222  13th Har. Volt‐Y  4  FLOAT    

1224  15th Har. Volt‐Y  4  FLOAT    

1226  17rd Har. Volt‐Y  4  FLOAT    

1228  19th Har. Volt‐Y  4  FLOAT    

1230  21th Har. Volt‐Y  4  FLOAT    

1232  23rd Har. Volt‐Y  4  FLOAT    

1234  25th Har. Volt‐Y  4  FLOAT    

1236  27th Har. Volt‐Y  4  FLOAT    

1238  29th Har. Volt‐Y  4  FLOAT    

1240  VOLT ‐ THD‐Y  4  FLOAT    

1242  3rd Har. Amps‐Y  4  FLOAT    

1244  5th Har. Amps‐Y  4  FLOAT    

1246  7th Har. Amps‐Y  4  FLOAT    

1248  9th Har. Amps‐Y  4  FLOAT    

1250  11th Har. Amps‐Y  4  FLOAT    

1252  13th Har. Amps‐Y  4  FLOAT    

1254  15th Har. Amps‐Y  4  FLOAT    

1256  17th Har. Amps‐Y  4  FLOAT    

1258  19th Har. Amps‐Y  4  FLOAT    

1260  21th Har. Amps‐Y  4  FLOAT    

1262  23rd Har. Amps‐Y  4  FLOAT    

1264  25th Har. Amps‐Y  4  FLOAT    

1266  27th Har. Amps‐Y  4  FLOAT    

1268  29th Har. Amps‐Y  4  FLOAT    

1270  AMPS ‐THD‐Y  4  FLOAT    

1272  VYB  4  FLOAT  148       148    

1400  VOLT‐B  4  FLOAT          

1402  AMPS‐B  4  FLOAT    

1404  WATT‐B  4  FLOAT    

1406  VA‐B  4  FLOAT    

1408  VAR‐B  4  FLOAT    

1410  PF‐B  4  FLOAT    

1412  3rd Har. Volt‐B  4  FLOAT    

1414  5th Har. Volt‐B  4  FLOAT    

1416  7th Har. Volt‐B  4  FLOAT    

1418  9th Har. Volt‐B  4  FLOAT    

1420  11th Har. Volt‐B  4  FLOAT    

1422  13th Har. Volt‐B  4  FLOAT    

1424  15th Har. Volt‐B  4  FLOAT    

1426  17rd Har. Volt‐B  4  FLOAT    

1428  19th Har. Volt‐B  4  FLOAT    

1430  21th Har. Volt‐B  4  FLOAT    

1432  23rd Har. Volt‐B  4  FLOAT    

1434  25th Har. Volt‐B  4  FLOAT    

1436  27th Har. Volt‐B  4  FLOAT    

1438  29th Har. Volt‐B  4  FLOAT    

1440  VOLT ‐ THD‐B  4  FLOAT    

1442  3rd Har. Amps‐B  4  FLOAT    

1444  5th Har. Amps‐B  4  FLOAT    

1446  7th Har. Amps‐B  4  FLOAT    

1448  9th Har. Amps‐B  4  FLOAT    

1450  11th Har. Amps‐B  4  FLOAT    

1452  13th Har. Amps‐B  4  FLOAT    

1454  15th Har. Amps‐B  4  FLOAT    

SLM102 – Operational Manual

TRINITY [63]

1456  17th Har. Amps‐B  4  FLOAT    

1458  19th Har. Amps‐B  4  FLOAT    

1460  21th Har. Amps‐B  4  FLOAT    

1462  23rd Har. Amps‐B  4  FLOAT    

1464  25th Har. Amps‐B  4  FLOAT    

1466  27th Har. Amps‐B  4  FLOAT    

1468  29th Har. Amps‐B  4  FLOAT    

1470  AMPS ‐THD‐B  4  FLOAT    

1472  VBR  4  FLOAT  148       

148   2000  SYS W  4  FLOAT  For Address 2010 and 

2011 Alarm status, there are four bytes. First Three Bytes are zero. Fourth Byte shows Relay position. First Bit of this byte shows First relay status. If it is 1 then it shows First relay is on. Same as second, third and fourth bit is used for second, third and fourth relay.                                   For Address 2014 and 2015. Unit is single Byte Parameter. First byte shows Unit value and other  three  are Dummy Bytes. Unit shows the unit of wh, Varh and Vah.  If Unit =2 means value of wh, Vah and Varh are in Kilo. If Unit = 3 means value of wh, vah and varh are in Mega. If Unit = 1  means wh, vah and varh are not in  kilo or mega range. 

2002  SYS VA  4  FLOAT 2004  SYS VAR  4  FLOAT 2006  FREQUENCY  4  FLOAT 2008  SYS PF  4  FLOAT 2010  ALARM STATUS  4  CHAR * 4 2012  DEMAND  4  FLOAT 2014  Unit & DUMMY  4  CHAR*4 2016  SYS WH  4  FLOAT 2018  SYS VAH  4  FLOAT 2020  SYS VARH  4  FLOAT 2022  MIN SYS W  4  FLOAT 2024  SECOND & MINUTE 2  CHAR*2 2025  HOUR & DUMMY 2  CHAR*2 2026  DATE & MONTH 2  CHAR*2 2027  YEAR & DUMMY 2  0 2028  MIN SYS VA  4  FLOAT 2030  SECOND & MINUTE 2  CHAR*2 2031  HOUR & DUMMY 2  CHAR*2 2032  DATE & MONTH 2  CHAR*2 2033  YEAR & DUMMY 2  0 2034  MIN FREQUENCY  4  FLOAT 2036  SECOND & MINUTE 2  CHAR*2 2037  HOUR & DUMMY 2  CHAR*2 2038  DATE & MONTH 2  CHAR*2 2039  YEAR & DUMMY 2  0 2040  MAX SYS W  4  FLOAT 2042  SECOND & MINUTE 2  CHAR*2 2043  HOUR & DUMMY 2  CHAR*2 2044  DATE & MONTH 2  CHAR*2 2045  YEAR & DUMMY 2  0 2046  MAX SYS VA  4  FLOAT    2048  SECOND & MINUTE 2  CHAR*2    2049  HOUR & DUMMY 2  CHAR*2    2050  DATE & MONTH 2  CHAR*2    2051  YEAR & DUMMY 2  0    2052  MAX FREQ  4  FLOAT    2054  SECOND & MINUTE 2  CHAR*2    2055  HOUR & DUMMY 2  CHAR*2    2056  DATE & MONTH 2  CHAR*2    2057  YEAR & DUMMY 2  0    2058  MAX DEMAND  4  FLOAT    2060  SECOND & MINUTE 2  CHAR*2    

SLM102 – Operational Manual

TRINITY [64]

2061  HOUR & DUMMY 2  CHAR*2    2062  DATE & MONTH 2  CHAR*2    

2063  YEAR & DUMMY 2 0 132 

  

2064  PRD DEMAND  4  FLOAT       

132   

3000  MIN VOLT‐R  4  FLOAT          3002  SECOND & MINUTE 2  CHAR*2    3003  HOUR & DUMMY 2  CHAR*2    3004  DATE & MONTH 2  CHAR*2    3005  YEAR & DUMMY 2  0    3006  MIN AMPS‐R  4  FLOAT    3008  SECOND & MINUTE 2 CHAR*2    3009  HOUR & DUMMY 2 CHAR*2    3010  DATE & MONTH 2 CHAR*2    3011  YEAR & DUMMY 2 0    3012  MIN WATT‐R  4  FLOAT    3014  SECOND & MINUTE 2 CHAR*2    3015  HOUR & DUMMY 2 CHAR*2    3016  DATE & MONTH 2 CHAR*2    3017  YEAR & DUMMY 2 0    3018  MIN VA‐R  4  FLOAT    3020  SECOND & MINUTE 2 CHAR*2    3021  HOUR & DUMMY 2 CHAR*2    3022  DATE & MONTH 2 CHAR*2    3023  YEAR & DUMMY 2 0    3024  MAX VOLT‐R  4  FLOAT    3026  SECOND & MINUTE 2 CHAR*2    3027  HOUR & DUMMY 2 CHAR*2    3028  DATE & MONTH 2 CHAR*2    3029  YEAR & DUMMY 2 0    3030  MAX AMPS‐R  4  FLOAT    3032  SECOND & MINUTE 2 CHAR*2    3033  HOUR & DUMMY 2 CHAR*2    3034  DATE & MONTH 2 CHAR*2    3035  YEAR & DUMMY 2 0    3036  MAX WATT‐R  4  FLOAT    3038  SECOND & MINUTE 2 CHAR*2    3039  HOUR & DUMMY 2 CHAR*2    3040  DATE & MONTH 2 CHAR*2    3041  YEAR & DUMMY 2 0    3042  MAX VA‐R  4  FLOAT    3044  SECOND & MINUTE 2 CHAR*2    3045  HOUR & DUMMY 2 CHAR*2    

3046  DATE & MONTH 2 CHAR*2    

3047  YEAR & DUMMY 2 0  96       

SLM102 – Operational Manual

TRINITY [65]

96   

3300  MIN VOLT‐Y  4  FLOAT          3302  SECOND & MINUTE 2  CHAR*2    3303  HOUR & DUMMY 2  CHAR*2    3304  DATE & MONTH 2  CHAR*2    3305  YEAR & DUMMY 2  0    3306  MIN AMPS‐Y  4  FLOAT    3308  SECOND & MINUTE 2 CHAR*2    3309  HOUR & DUMMY 2 CHAR*2    3310  DATE & MONTH 2 CHAR*2    3311  YEAR & DUMMY 2 0    3312  MIN WATT‐Y  4  FLOAT    3314  SECOND & MINUTE 2 CHAR*2    3315  HOUR & DUMMY 2 CHAR*2    3316  DATE & MONTH 2 CHAR*2    3317  YEAR & DUMMY 2 0    3318  MIN VA‐Y  4  FLOAT    3320  SECOND & MINUTE 2 CHAR*2    3321  HOUR & DUMMY 2 CHAR*2    3322  DATE & MONTH 2 CHAR*2    3323  YEAR & DUMMY 2 0    3324  MAX VOLT‐Y  4  FLOAT    3326  SECOND & MINUTE 2 CHAR*2    3327  HOUR & DUMMY 2 CHAR*2    3328  DATE & MONTH 2 CHAR*2    3329  YEAR & DUMMY 2 0    3330  MAX AMPS‐Y  4  FLOAT    3332  SECOND & MINUTE 2 CHAR*2    3333  HOUR & DUMMY 2 CHAR*2    3334  DATE & MONTH 2 CHAR*2    3335  YEAR & DUMMY 2 0    3336  MAX WATT‐Y  4  FLOAT    3338  SECOND & MINUTE 2 CHAR*2    3339  HOUR & DUMMY 2 CHAR*2    3340  DATE & MONTH 2 CHAR*2    3341  YEAR & DUMMY 2 0    3342  MAX VA‐Y  4  FLOAT    3344  SECOND & MINUTE 2 CHAR*2    3345  HOUR & DUMMY 2 CHAR*2    

3346  DATE & MONTH 2 CHAR*2    

3347  YEAR & DUMMY 2 0  96       

96   

3600  MIN VOLT‐B  4  FLOAT          3602  SECOND & MINUTE 2  CHAR*2    

SLM102 – Operational Manual

TRINITY [66]

3603  HOUR & DUMMY 2  CHAR*2    3604  DATE & MONTH 2  CHAR*2    3605  YEAR & DUMMY 2  0    3606  MIN AMPS‐B  4  FLOAT    3608  SECOND & MINUTE 2 CHAR*2    3609  HOUR & DUMMY 2 CHAR*2    3610  DATE & MONTH 2 CHAR*2    3611  YEAR & DUMMY 2 0    3612  MIN WATT‐B  4  FLOAT    3614  SECOND & MINUTE 2 CHAR*2    3615  HOUR & DUMMY 2 CHAR*2    3616  DATE & MONTH 2 CHAR*2    3617  YEAR & DUMMY 2 0    3618  MIN VA‐B  4  FLOAT    3620  SECOND & MINUTE 2 CHAR*2    3621  HOUR & DUMMY 2 CHAR*2    3622  DATE & MONTH 2 CHAR*2    3623  YEAR & DUMMY 2 0    3624  MAX VOLT‐B  4  FLOAT    3626  SECOND & MINUTE 2 CHAR*2    3627  HOUR & DUMMY 2 CHAR*2    3628  DATE & MONTH 2 CHAR*2    3629  YEAR & DUMMY 2 0    3630  MAX AMPS‐B  4  FLOAT    3632  SECOND & MINUTE 2 CHAR*2    3633  HOUR & DUMMY 2 CHAR*2    3634  DATE & MONTH 2 CHAR*2    3635  YEAR & DUMMY 2 0    3636  MAX WATT‐B  4  FLOAT    3638  SECOND & MINUTE 2 CHAR*2    3639  HOUR & DUMMY 2 CHAR*2    3640  DATE & MONTH 2 CHAR*2    3641  YEAR & DUMMY 2 0    3642  MAX VA‐B  4  FLOAT    3644  SECOND & MINUTE 2 CHAR*2    3645  HOUR & DUMMY 2 CHAR*2    

3646  DATE & MONTH 2 CHAR*2    

3647  YEAR & DUMMY 2 0  96       

SLM102 – Operational Manual

TRINITY [67]

P.O No. : ………………………………………………………………… Customer : ………………………………………………………………… Sr. No. : ………………………………………………………………… Routine and function tests conducted to relevant standards and our Specifications/Literature/O & M Manual. Traceability: tested against "MTE" Standard Model PRS400.3 having basic accuracy of 0.02% traceable upto International Standards derived using appropriate ratio techniques. Result of Test : ………………………………………………………………… Remarks : ………………………………………………………………… Test engineer : ………………………………………………………………… Date : …………………………………………………………………