8
10 and 12 Lead High-Wye Available Voltages 10 lead generators are identical to 12 lead generators with the exception that T10, T11, and T12 are permanently bonded together as T10 or T0 480V Connections shown in Blue 416V Connections shown in Red L1 T0 L2 T4 139V 120V 277V 240V L3 T10 T1 T2 T5 T8 T11 T3 T6 T12 T9 480V 416V T7 240V 208V

Transcript of 10 and 12 Lead High-Wye Available Voltages · U1 U2 U5 U6 V1 V V 240V 12 Lead Double-Delta...

Page 1: 10 and 12 Lead High-Wye Available Voltages · U1 U2 U5 U6 V1 V V 240V 12 Lead Double-Delta Available Voltages 10 lead generators are not reconnectable as Double-Delta Generators connected

10 and 12 Lead High-Wye Available Voltages

10 lead generators are identical to 12 lead generators with the exception that T10,

T11, and T12 are permanently bonded together as T10 or T0

480V Connections shown in Blue 416V Connections shown in Red

L1

T0

L2

T4 139V 120V

277V

240V

L3

T10

T1

T2

T5

T8

T11

T3

T6

T12

T9

480V 416V

T7

240V

208V

Page 2: 10 and 12 Lead High-Wye Available Voltages · U1 U2 U5 U6 V1 V V 240V 12 Lead Double-Delta Available Voltages 10 lead generators are not reconnectable as Double-Delta Generators connected

10 and 12 Lead High-Wye Available Voltages (ISO Standard)

10 lead generators are identical to 12 lead generators with the exception that U6, V6,

and W6 are permanently bonded together as N

480V Connections shown in Blue 416V Connections shown in Red

U

N

V

U2 139V 120V

277V

240V

W

U6

U1

V1

V2

V5

V6

W1

W2

W6

W5

480V 416V

U5

240V

208V

Page 3: 10 and 12 Lead High-Wye Available Voltages · U1 U2 U5 U6 V1 V V 240V 12 Lead Double-Delta Available Voltages 10 lead generators are not reconnectable as Double-Delta Generators connected

10 and 12 Lead Low-Wye Available Voltages

10 lead generators are identical to 12 lead generators with the exception that T10,

T11, and T12 are permanently bonded together as T10 or T0

240V Connections shown in Blue 208V Connections shown in Red

L1

T0

L2

T7

T4

139V

120V

L3

T10

T1

T2

T5

T8

T11

T3

T6

T12

T9 240V 208V

Page 4: 10 and 12 Lead High-Wye Available Voltages · U1 U2 U5 U6 V1 V V 240V 12 Lead Double-Delta Available Voltages 10 lead generators are not reconnectable as Double-Delta Generators connected

10 and 12 Lead Low-Wye Available Voltages (ISO Standard)

10 lead generators are identical to 12 lead generators with the exception that U6, V6,

and W6 are permanently bonded together as N

240V Connections shown in Blue 208V Connections shown in Red

U

N

V

U5

U2

139V

120V

W

U6

U1

V1

V2

V5

V6

W1

W2

W6

W5 240V 208V

Page 5: 10 and 12 Lead High-Wye Available Voltages · U1 U2 U5 U6 V1 V V 240V 12 Lead Double-Delta Available Voltages 10 lead generators are not reconnectable as Double-Delta Generators connected

12 Lead Series Delta Available Voltages

10 lead generators are not reconnectable as a Delta

240V Connections shown in Blue 208V Connections shown in Red

L1 T0

L2 T7 T4

120V 104V

120V 104V

240V 208V

L3

T10 T1

T2

T5

T8

T11 T3

T6

T12

T9 208V 180V

“Hig

h-Le

g”

Page 6: 10 and 12 Lead High-Wye Available Voltages · U1 U2 U5 U6 V1 V V 240V 12 Lead Double-Delta Available Voltages 10 lead generators are not reconnectable as Double-Delta Generators connected

12 Lead Series Delta Available Voltages (ISO Standard)

10 lead generators are not reconnectable as a Delta

240V Connections shown in Blue 208V Connections shown in Red

U N

W W2 W5

120V 104V

120V 104V

240V 208V

V

W1 W6

V6

V5

V2

V1 U6

U5

U1

U2 208V 180V

“Hig

h-Le

g”

Page 7: 10 and 12 Lead High-Wye Available Voltages · U1 U2 U5 U6 V1 V V 240V 12 Lead Double-Delta Available Voltages 10 lead generators are not reconnectable as Double-Delta Generators connected

L1

T0

L2

T11 T5

T12 T2 T6 T8

T10 T7 T4 T1

T9

120V 120V

240V

12 Lead Double-Delta Available Voltages

10 lead generators are not reconnectable as Double-Delta

Generators connected as Zig-Zag should be reconnected as Double-Delta Generators should be DERATED by 1/3 of their original capacity!

240V Connections shown in Blue 120V Connections shown in Red

Double-Delta connections always provide 240/120V Single-Phase

T3

Page 8: 10 and 12 Lead High-Wye Available Voltages · U1 U2 U5 U6 V1 V V 240V 12 Lead Double-Delta Available Voltages 10 lead generators are not reconnectable as Double-Delta Generators connected

U

N

W

W6 W2

V2 W1 V6 W5

U6 U5 U2 U1

V1

120V 120V

240V

12 Lead Double-Delta Available Voltages

10 lead generators are not reconnectable as Double-Delta

Generators connected as Zig-Zag should be reconnected as Double-Delta Generators should be DERATED by 1/3 of their original capacity!

240V Connections shown in Blue 120V Connections shown in Red

Double-Delta connections always provide 240/120V Single-Phase

V5